Quick Start Guide00825-0100-4140, Rev AB

May 2017

Rosemount™ 2140 Level DetectorVibrating Fork

Quick Start Guide for Installation

May 2017Quick Start Guide

1.0 About this guideThis Quick Start Guide provides basic guidelines for Rosemount 2140 and 2140:SIS Vibrating Fork Liquid Level Detectors (“level detectors”).

Refer to the Rosemount 2140 Reference Manual for more instructions, and the Rosemount 2140 Product Certifications Manual for approvals information and safety matters. Manuals are available electronically at Emerson.com/Rosemount.

1.1 Symbols used in this guide

1.2 Required equipmentStandard tools e.g. screwdrivers and wire strippers/cutters.

1.3 Contents

Failure to follow safe installation guidelines could result in death or serious injury.

Use the level detector only as specified in this guide and the product reference manual.

The level detector must be installed, connected, commissioned, operated, and maintained by suitably qualified personnel only, observing national and local requirements that may apply.

The weight of a level detector with a heavy flange and extended fork length may exceed 37 lb. (18 kg).A risk assessment is required before carrying, lifting, and installing the level detector.

Explosions could result in death or serious injury.

Refer to the Rosemount 2140 Product Certifications Manual for restrictions associated with the intrinsically safe, explosion-proof/flameproof and dust approvals for this product.

Electrical shock could cause death or serious injury

Make sure that the level detector is not powered when removing the terminal cover and making terminal connections.

If the level detector is installed in a high voltage environment and a fault condition or installation error occurs, high voltage may be present on leads and terminals.

External surfaces may be hot.

Care must be taken to avoid possible burns. The flange and process seal may be hot at high process temperatures. Allow to cool before servicing.

Refer to the Rosemount 2140 Reference Manual for further information.

Adobe® Acrobat® Reader software is needed to view the document contents.

Switch off power (0) to the level detector.

Switch on power (1) to the level detector.

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Adjust display orientation (optional) . . . . . . . . 8Prepare the electrical connections . . . . . . . . . . 9

Connect wiring and power up . . . . . . . . . . . . . 10Confirm system readiness . . . . . . . . . . . . . . . . 15Configure level detector using Guided Setup 15

www

2

Quick Start GuideMay 2017

2.0 Installation

2.1 Installation considerations

Correct fork alignments

Figure 1. Pipe Installation

Figure 2. Tank Installation

OK

OK

Threaded

Tri Clamp

Threaded

Tri Clamp

OKOKOK

Threaded

Tri Clamp

Flanged

3

May 2017Quick Start Guide

2.2 Mounting the threaded version

Step 1: Seal and protect the threadsUse anti-seize paste or PTFE tape according to your site procedures.

Step 2: Mount the level detector on tank or pipework

Threaded tank or pipework connection (vertical installation)

Threaded tank or pipework connection (horizontal installation)

Gasket may be used as a sealantfor BSPP (G) threaded connections.

Gasket (for BSPP (G) threaded connection)

Tighten using the hexagon only

Gasket (for BSPP (G) threaded connection)

Tighten using the hexagon only

4

Quick Start GuideMay 2017

Threaded flange connection1. Place the customer supplied flange on the tank nozzle.

2. Tighten the bolts and nuts with sufficient torque for the flange and gasket.

3. Screw the level detector into the flange thread.

Gasket (customer supplied)

Gasket for BSPP (G) threads only

5

May 2017Quick Start Guide

2.3 Mounting the flanged version

Step 1: Lower the level detector into the nozzle

Step 2: Tighten the bolts and nuts

Gasket (customer supplied)

6

Quick Start GuideMay 2017

2.4 Mounting the Tri Clamp version

Step 1: Lower the level detector onto the flange face

Step 2: Fit the Tri Clamp

Seal (supplied with Tri Clamp)

7

May 2017Quick Start Guide

3.0 Adjust display orientation (optional)To improve field access to wiring or get a better view of the optional LCD display:1. Loosen the set screw until the level detector housing can rotate smoothly.

a. Do not unscrew all the way. Rotating the housing, without this screw in place, can damage the internal wiring.

2. First, rotate the housing clockwise to the desired location.

If the desired location cannot be achieved due to the internal thread limit, rotate the housing counterclockwise.

3. Re-tighten the set screw.

H3/32 in.Torque 30 in-lb (3 Nm)

Do not attempt to rotate the display beyond the thread limits.

8

Quick Start GuideMay 2017

4.0 Prepare the electrical connections

4.1 Cable selectionUse 24-14 AWG wire. Twisted-pairs and shielded wiring is recommended for environments with high EMI (electromagnetic interference). Two wires can be safely connected to each terminal screw.

4.2 Cable gland/conduitFor intrinsically safe, explosion-proof/flameproof, and dust-proof installations, use the supplied blanking plug and a suitably certified cable gland/conduit entry device(s).

4.3 Power supplyThe level detector operates on 10.5 - 42.4 Vdc (10.5 - 30 Vdc in intrinsically safe installations) at the level detector terminals.

4.4 Power consumptionMaximum of 1 W, current maximum 23 mA.

4.5 Load limitationsFor HART® communication, a minimum load resistance of 250 Ù is required.

The maximum loop resistance is determined by the voltage level of the external power supply, as described in Figure 3.

Figure 3. Load Limitations

Maximum Loop Resistance = 43.5 * (External Power Supply Voltage - 10.5)

0

External Power Supply Voltage (Vdc)

200

Loop

Res

ista

nce

(Ohm

s)

400

600

800

1000

1200

1400

10 20 30 40 4024 42.4

10.5

250

1392

848

587

16.3

9

May 2017Quick Start Guide

5.0 Connect wiring and power up

Step 1: Remove the cover

Step 2: Remove the plastic plugs

Step 3: Pull the cable through the cable gland/conduit

Verify that the power supply is disconnected or switched off.

½-14 NPT M20 x 1.5

M20(No marking)

Identification of thread size and type

Use a suitably rated cable, and cable gland/conduit entry device.

10

Quick Start GuideMay 2017

Step 4: Connect the cable wires

Figure 4. 4-20 mA/HART® Communication

A. Field Communicator (IS approved for intrinsically safe installations)B. Approved IS barrier (for intrinsically safe installations only)C. HART modemD. Load resistance (250 )E. Current meterF. Power supply

Torque 7 in-lb (0.8Nm)

-+-

+

Fn1 2 34 5 6

7 8 90 -

.

A

BD

E

F

C

11

May 2017Quick Start Guide

Step 5: Ensure proper groundingMake sure grounding is done according to national and local electrical codes. Failure to do so may impair the protection provided by the equipment.

Transmitter case grounding

The most effective grounding method is direct connection to earth ground with minimal impedance (< 1 ). Use either internal or external grounding screw.

Figure 5. Ground Screws

A. External ground screwB. Internal ground screw

Signal cable shield grounding

Make sure the instrument cable shield is: Trimmed close and insulated from touching the level detector housing. Connected to the next shield if cable is routed through a junction box. Connected to a good earth ground at the power supply end.

Figure 6. Cable Shield

A. Trim shield and insulate C. Trim shieldB. Minimize distance D. Connect shield back to power supply ground

B

A

A

B

B

C CD

12

Quick Start GuideMay 2017

Step 6: Tighten the cable glandApply PTFE tape or other sealant to the threads.

NoteArrange the wiring with a drip loop.

Step 7: Seal any unused port with the enclosed metal plugApply PTFE tape or other sealant to the thread.

13

May 2017Quick Start Guide

Step 8: Attach and tighten the covers1. Verify the cover jam screws are completely threaded into the housing.

2. Attach and tighten the covers. Make sure the covers are fully engaged.

3. Required for explosion-proof/flameproof and dust-proof installations only:a. Turn the cover jam screw counterclockwise until it contacts the cover.b. Turn the jam screw an extra 1/2 turn counterclockwise to secure the cover.

M2.5

Cover jam screw(one per side)

M2.5

Verify that the covers cannot be removed.

14

Quick Start GuideMay 2017

Step 9: Connect the power supplyIt may take up to 15 seconds before the LCD display lights up.

6.0 Confirm system readiness

6.1 Confirm HART revision capabilityIf using HART-based control or asset management systems, confirm the HART 7 capability of such systems prior to commissioning and installation. Not all systems are capable of communicating with the HART Revision 7 protocol. This level detector can be configured for either HART Revision 5 or 7.

6.2 Confirm correct device driver Verify that the correct Device Driver (DD) or Device Type Manager (DTM) is

loaded on your systems to ensure proper communication. Download the DD/DTM from Emerson.com/Rosemount.

6.3 Change HART revision modeIf the HART configuration tool is not capable of communicating with HART Revision 7, the device will load a generic menu with limited capability.

To change the HART revision mode from the generic menu:1. Go to Manual Setup > Device Information > Identification > Message.

2. In the Message field, enter “HART5” or “HART7” and then 27 trailing spaces.

7.0 Configure level detector using Guided SetupThe Rosemount 2140 and Rosemount 214:SIS can be configured using a Field Communicator, a PC running the AMS Device Manager, or any other Device Descriptor (DD) compatible host system.

7.1 AMS Device Manager1. Start AMS Device Manager.

2. Select View > Device Connection View.

3. In the Device Connection View, double-click the HART modem icon.

4. Double-click the device icon.

5. From the Home screen, select Configure > Guided Setup.

6. Select Basic Setup and follow the on-screen instructions.

7.2 Field Communicator1. Turn on the Field Communicator.

2. From the Main Menu, tap the HART symbol. The Field Communicator now connects to the device.

3. From the Home screen, select Configure > Guided Setup.

4. Select Basic Setup and follow the on-screen instructions.

www

Rosemount 2140 Reference Manual

15

Global HeadquartersEmerson Automation Solutions 6021 Innovation Blvd.Shakopee, MN 55379, USA

+1 800 999 9307 or +1 952 906 8888

+1 952 949 7001

[email protected]

North America Regional OfficeEmerson Automation Solutions 8200 Market Blvd.Chanhassen, MN 55317, USA

+1 800 999 9307 or +1 952 906 8888

+1 952 949 7001

[email protected]

Latin America Regional OfficeEmerson Automation Solutions 1300 Concord Terrace, Suite 400Sunrise, FL 33323, USA

+1 954 846 5030

+1 954 846 5121

[email protected] Linkedin.com/company/Emerson-Automation-Solutions

Twitter.com/Rosemount_News

Facebook.com/Rosemount

Youtube.com/user/RosemountMeasurement

Google.com/+RosemountMeasurement

Standard Terms and Conditions of Sale can be found at www.Emerson.com/en-us/Terms-of-UseThe Emerson logo is a trademark and service mark of Emerson Electric Co.Rosemount and Rosemount logotype are trademarks of Emerson.HART is a registered trade mark of FieldComm Group.All other marks are the property of their respective owners.© 2017 Emerson . All rights reserved.

Europe Regional OfficeEmerson Automation Solutions Europe GmbHNeuhofstrasse 19a P.O. Box 1046CH 6340 BaarSwitzerland

+41 (0) 41 768 6111

+41 (0) 41 768 6300

[email protected]

Asia Pacific Regional OfficeEmerson Automation Solutions Asia Pacific Pte Ltd1 Pandan CrescentSingapore 128461

+65 6777 8211

+65 6777 0947 [email protected]

Middle East and Africa Regional OfficeEmerson Automation Solutions Emerson FZE P.O. Box 17033Jebel Ali Free Zone - South 2Dubai, United Arab Emirates

+971 4 8118100

+971 4 [email protected]

Quick Start Guide00825-0100-4140, Rev AB

May 2017