Relion® 670/650 series
670/650 seriesVersion 2.2 IECQuick start guide
Document ID: 1MRK 500 129-UEN Issued: November 2018
Revision: BProduct version: 2.2
© Copyright 2018 ABB. All rights reserved
Table of contents
Section 1 Introduction.........................................................................................................3
Section 2 Safety information............................................................................................. 52.1 Symbols on the product................................................................................................................... 52.2 Warnings.............................................................................................................................................. 52.3 Caution signs...................................................................................................................................... 6
Section 3 Unpacking and inspecting.................................................................................93.1 Removing transport packaging...................................................................................................... 93.2 Inspecting the product..................................................................................................................... 93.2.1 Identifying the product................................................................................................................ 93.2.2 Checking delivery items............................................................................................................... 93.2.3 Inspecting the IED......................................................................................................................... 93.2.4 Returning an IED damaged in transit........................................................................................ 9
Section 4 IED hardware......................................................................................................114.1 Overview............................................................................................................................................. 114.1.1 Variants of case size with local HMI display........................................................................... 114.1.2 Case from the front and rear sides.......................................................................................... 12
Section 5 Powering up the IED..........................................................................................175.1 How to know the voltage level.......................................................................................................175.2 How to connect to the power supply...........................................................................................185.3 Energizing the IED............................................................................................................................19
Section 6 LHMI overview................................................................................................... 216.1 Local HMI............................................................................................................................................216.1.1 Keypad............................................................................................................................................216.1.2 Display........................................................................................................................................... 246.1.3 LEDs................................................................................................................................................276.1.4 Local HMI functionality...............................................................................................................286.1.4.1 Protection and alarm indication........................................................................................... 28
Section 7 Connecting to the PCM600 software.............................................................317.1 PCM600 tool......................................................................................................................................317.1.1 Connectivity packages................................................................................................................317.2 Preparing for the connection.........................................................................................................327.3 Installing the PCM600 software....................................................................................................327.4 Connecting the cables.....................................................................................................................32
Section 8 Editing the network settings.......................................................................... 338.1 Setting up communication between PCM600 and the IED..................................................... 33
Section 9 Working with the PCM software.....................................................................39
Table of contents
670/650 series 1Quick start guide
2
Section 1 IntroductionGUID-DCFD62E5-F592-4513-84B0-EC73C7C61838 v1
The Quick Start Guide contains instructions on how to setup the Relion 670/650 series IED toget started. The guide provides instructions to setup with a preconfigured IED, however, it isalso useful for the customized version of the IED.
The guide describes basic instructions only. For complete information, see the IED manuals.
GUID-CE76425E-C9C1-404F-8BB3-AD133E903EE7 V4 EN-US
Figure 1: Sample of an IED
1MRK 500 129-UEN B Section 1Introduction
670/650 series 3Quick start guide
4
Section 2 Safety information
2.1 Symbols on the productGUID-E48F2EC3-6AB8-4ECF-A77E-F16CE45CA5FD v4
All warnings must be observed.
Read the entire manual before doing installation or any maintenance work onthe product.
Class 1 Laser product. Take adequate measures to protect your eyes and do notview directly with optical instruments.
Do not touch the unit in operation. The installation shall take into account theworst case temperature.
2.2 WarningsIP1504-1 v2
Observe the warnings during all types of work related to the product.GUID-C9B6638A-57E7-4E05-9A33-A60E359C54AF v1
Only electrically skilled persons with the proper authorization and knowledge ofany safety hazards are allowed to carry out the electrical installation.
M2366-2 v2
National and local electrical safety regulations must always be followed.Working in a high voltage environment requires serious approach to avoidhuman injuries and damage to equipment.
M2362-2 v1
Do not touch circuitry during operation. Potentially lethal voltages and currentsare present.
M2364-2 v1
Always use suitable isolated test pins when measuring signals in open circuitry.Potentially lethal voltages and currents are present.
1MRK 500 129-UEN B Section 2Safety information
670/650 series 5Quick start guide
M2370-2 v1
Never connect or disconnect a wire and/or a connector to or from a IED duringnormal operation. Hazardous voltages and currents are present that may belethal. Operation may be disrupted and IED and measuring circuitry may bedamaged.
GUID-BEDD698E-356C-4CF9-9DAE-64DB3CEADEAD v1
Dangerous voltages can occur on the connectors, even though the auxiliaryvoltage has been disconnected.
M2369-2 v3
Always connect the IED to protective earth, regardless of the operatingconditions. This also applies to special occasions such as bench testing,demonstrations and off-site configuration. This is class 1 equipment that shallbe earthed.
M2367-2 v1
Never disconnect the secondary connection of current transformer circuitwithout short-circuiting the transformer’s secondary winding. Operating acurrent transformer with the secondary winding open will cause a massivepotential build-up that may damage the transformer and may cause injuries tohumans.
M2372-2 v1
Never remove any screw from a powered IED or from a IED connected topowered circuitry. Potentially lethal voltages and currents are present.
SEMOD168311-3 v1
Take adequate measures to protect the eyes. Never look into the laser beam.
GUID-11CCF92B-E9E7-409C-84D0-DFDEA1DCBE85 v2
The IED with accessories should be mounted in a cubicle in a restricted accessarea within a power station, substation or industrial or retail environment.
2.3 Caution signsIP1503-1 v1
GUID-5D1412B8-8F9D-4D39-B6D1-60FB35797FD0 v2
Whenever changes are made in the IED, measures should be taken to avoidinadvertent tripping.
GUID-F2A7BD77-80FB-48F0-AAE5-BE73DE520CC2 v1
The IED contains components which are sensitive to electrostatic discharge.ESD precautions shall always be observed prior to touching components.
Section 2 1MRK 500 129-UEN BSafety information
6 670/650 seriesQuick start guide
M2695-2 v2
Always transport PCBs (modules) using certified conductive bags.
M2696-2 v1
Do not connect live wires to the IED. Internal circuitry may be damaged
M2697-2 v2
Always use a conductive wrist strap connected to protective earth whenreplacing modules. Electrostatic discharge (ESD) may damage the module andIED circuitry.
M2698-2 v2
Take care to avoid electrical shock during installation and commissioning.
M2693-2 v1
Changing the active setting group will inevitably change the IEDs operation. Becareful and check regulations before making the change.
GUID-3BEE51C6-8793-4C89-B8A8-07D0FA6EE4CA v3
Avoid touching the enclosure of the coupling capacitor REX061 unit and theshunt resistor REX062 unit. The surface may be hot during normal operation.The temperature can rise 50°C in REX061 and 65°C in REX062 above theambient temperature.
1MRK 500 129-UEN B Section 2Safety information
670/650 series 7Quick start guide
8
Section 3 Unpacking and inspecting
3.1 Removing transport packagingAMU0600514 v5
IEDs require careful handling.
1. Examine the delivered products to ensure that they have not been damaged during thetransport.
2. Remove the transport packing carefully without force.
The cardboard packaging material is 100% recyclable.
3.2 Inspecting the product
3.2.1 Identifying the productAMU0600513 v5
1. Locate the IED's order number from the label attached to the IED's case.2. Compare the IED's order number with the ordering information to verify that the received
product is correct.
3.2.2 Checking delivery itemsGUID-2A6D8F5A-470F-40D1-9EAE-60DE4DD85EE6 v1
Check that all items are included in the delivery in accordance with the delivery documents.
3.2.3 Inspecting the IEDGUID-F6333353-F05D-4B41-BE44-5CE5274E788E v2
• Check the IED to see if any damage occurred during transportation.
3.2.4 Returning an IED damaged in transitGUID-966A05ED-CD30-4F66-957E-00FF38943A73 v4
If damage has occurred during transport, appropriate actions must be taken against the latestcarrier. Please inform the nearest ABB office or representative. Notify ABB immediately if thereare any discrepancies in relation to the delivery documents.
1MRK 500 129-UEN B Section 3Unpacking and inspecting
670/650 series 9Quick start guide
10
Section 4 IED hardware
4.1 OverviewIP14270-1 v1
4.1.1 Variants of case size with local HMI displayM15024-3 v6
IEC04000458-2-en.psdIEC04000458 V2 EN-US
Figure 2: 1/2 19” case with local HMI display.
IEC05000762-2-en.psdIEC05000762 V2 EN-US
Figure 3: 3/4 19” case with local HMI display.
1MRK 500 129-UEN B Section 4IED hardware
670/650 series 11Quick start guide
IEC04000460-2-en.psdIEC04000460 V2 EN-US
Figure 4: 1/1 19” case with local HMI display.
4.1.2 Case from the front and rear sidesIP16286-1 v2
M16105-3 v10
Table 1: Designations for 1/2 x 19” casing with 1 TRM slot
1MRK002801-AC-2-670-1.2-PG V.3 EN1MRK002801-AC-2-670-1.2-PG V4 EN-US
Rear position Module
X11 PSM
X31 and X32 etc. to X51 and X52 BIM, BOM, SOM, IOM or MIM
X301, X302, X303, X304 SFP
X305 LDCM
X306 LDCM or OEM
X3061, X3062 SFP if OEM is selected
X311: A, B, C, D SLM
X312 LDCM, IRIG-B, GTM
X313 LDCM, IRIG-B, GTM, RS485
X401 TRM
Table continues on next page
Section 4 1MRK 500 129-UEN BIED hardware
12 670/650 seriesQuick start guide
SEMOD111882-4 v8
Table 2: Designations for 3/4 x 19” casing with 1 TRM slot
1MRK002801-AC-3-670-1.2-PG V4 EN-US
Rear position Module
X11 PSM
X31 and X32 etc. to X101 and X102 BIM, BOM, SOM, IOM or MIM
X301, X302, X303, X304 SFP
X305 LDCM
X306 LDCM
X3061, X3062 SFP if OEM is selected
X311: A, B, C, D SLM
X312 LDCM, IRIG-B, GTM
X313 LDCM, IRIG-B, GTM, RS485
X401 TRM
1MRK 500 129-UEN B Section 4IED hardware
670/650 series 13Quick start guide
SEMOD111884-4 v7
Table 3: Designations for 3/4 x 19” casing with 2 TRM slot
1MRK002801-AC-4-670-1.2-PG V.3 EN1MRK002801-AC-4-670-1.2-PG V4 EN-US
Rear position Module
X11 PSM
X31 and X32 etc. to X71 and X72 BIM, BOM, SOM, IOM or MIM
X301. X302, X303, X304 SFP
X305 LDCM
X306 LDCM
X3061, X3062 SFP if OEM is selected
X311: A, B, C, D SLM
X312 LDCM, IRIG-B, GTM
X313, X322, X323 LDCM, IRIG-B, GTM, RS485
X401 TRM 1
X411 TRM 2
Section 4 1MRK 500 129-UEN BIED hardware
14 670/650 seriesQuick start guide
M16106-3 v10
Table 4: Designations for 1/1 x 19” casing with 1 TRM slot
1MRK002801-AC-5-670-1.2-PG V.3 EN1MRK002801-AC-5-670-1.2-PG V4 EN-US
Rear position Module
X11 PSM
X31 and X32 etc. to X161and X162
BIM, BOM, SOM, IOM orMIM
X301, X302, X303, X304 SFP
X305 LDCM
X306 LDCM
X3061, X3062 SFP if OEM is selected
X311: A, B, C, D SLM
X312 LDCM, IRIG-B, GTM
X313 LDCM, IRIG-B, GTM,RS485
X401 TRM
1MRK 500 129-UEN B Section 4IED hardware
670/650 series 15Quick start guide
M16108-3 v10
Table 5: Designations for 1/1 x 19” casing with 2 TRM slots
1MRK002801-AC-6-670-1.2-PG V.3 EN1MRK002801-AC-6-670-1.2-PG V4 EN-US
Rear position Module
X11 PSM
X31 and X32 etc. to X131and X132
BIM, BOM, SOM, IOM orMIM
X301, X302, X303, X304 SFP
X305 LDCM
X306 LDCM
X3061, X3062 SFP if OEM is selected
X311: A, B, C, D SLM
X312 LDCM, IRIG-B, GTM
X313, X322, X323 LDCM, IRIG-B, GTM,RS485
X401 TRM 1
X411 TRM 2
SLM and LDCM modules not used inRES670.
Section 4 1MRK 500 129-UEN BIED hardware
16 670/650 seriesQuick start guide
Section 5 Powering up the IEDGUID-1B10552A-270B-4FFC-A065-AB30ECCE5EE0 v1
All Relion 670/650 series IEDs have either low or high power supply ranges.
Low-range: 24-60 V DC
High-range: 90-250 V DC
5.1 How to know the voltage levelGUID-ADB6E158-6051-4DF1-83B8-BE9590FF132B v1
1. See the label on the right-hand side of the IED to know the voltage level for the IED.
The label also contains data such as, IED serial number and analog input ranges.
For example, see Figure 5.
10
9
8
7
7
6
6
5
1
2
3
4
11
=IEC15000506=2=en=Original.vsdxIEC15000506 V2 EN-US
Figure 5: Example of Relion 670 IED label
1 QR-code containing the complete ordering code
2 Power supply module (PSM)
3 mA input module (MIM)
4 Ordering and serial number
5 Manufacturer
6 Transformer designations
7 Transformer input module, rated currents and voltages
8 Optional, customer specific information
1MRK 500 129-UEN B Section 5Powering up the IED
670/650 series 17Quick start guide
9 Order number, dc supply voltage and rated frequency
10 Product type, description and serial number
11 Product type
5.2 How to connect to the power supplyGUID-30AD9F73-5CA5-41A7-8283-C322AF1DA813 v2
The power supply module is on the leftmost side (rear view) of the IED. The connector X11 is a5-input phoenix type contact. See Figure 6 for example.
IEC08000471-BG V1 EN-US
Figure 6: Rear view of the 1/2 x 19" IED
1. Connect wires or cables to the IED terminals (see Figure 7 for PSM connection diagram) inaccordance with the established guidelines for this type of equipment.
Insert only the corresponding male connector to the female connector.Inserting anything else (such as a measurement probe) may violate the femaleconnector and prevent a proper electrical contact between the printed circuitboard and the external wiring connected to the screw terminal block.
X1113
X11
2 X11
4 5
Power supply module (PSM)
INTERNAL FAIL
p1
+ -
ReadyFail
+ Protective earth must be connected
EL1MRK002801-AC-7-670-1.2-PG V3 EN-US
Figure 7: Power supply module (PSM)
The auxiliary power wiring should have a minimum cross-sectional area of 1.0 mm2 and avoltage rating of 250 V. Branch circuit protection must be provided in the auxiliary powersupply wiring to the IED, and if necessary it must be possible to disconnect manually from thepower supply. Fuse or circuit breaker up to 6 A and 250 V should be close to the equipment.
Section 5 1MRK 500 129-UEN BPowering up the IED
18 670/650 seriesQuick start guide
Ensure that the IED is earthed before starting it.
5.3 Energizing the IEDGUID-E40DE80C-8DA4-4E17-876C-4CC3CE706347 v4
Before connecting the auxiliary power, check that the terminal strip is wired and placedcorrectly. Remove the protective film from the top side of the unit.
During IED start-up, you can observe the following sequence:
1. The Green Ready LED starts to flash.2. The LCD lights up and starting... is displayed.3. The main menu is displayed. A final steady green Ready LED indicates a successful start-
up of the device.
If the self supervision of the IED detects a diagnostic error during the start-up process, thegreen Ready LED flashes. Further information on the error may be visible on the local HMIunder Main menu/Diagnostics/IED status/General. Note down the displayed information asreference when contacting ABB technical support.
1MRK 500 129-UEN B Section 5Powering up the IED
670/650 series 19Quick start guide
20
Section 6 LHMI overview
6.1 Local HMIAMU0600442 v15
The LHMI of the IED contains the following elements
• Keypad• Display (LCD)• LED indicators• Communication port for PCM600
The LHMI is used for setting, monitoring and controlling.
6.1.1 KeypadAMU0600428 v19
The LHMI keypad contains push-buttons which are used to navigate in different views ormenus. The push-buttons are also used to acknowledge alarms, reset indications, provide helpand switch between local and remote control mode.
The keypad also contains programmable push-buttons that can be configured either as menushortcut or control buttons.
1MRK 500 129-UEN B Section 6LHMI overview
670/650 series 21Quick start guide
1
18
19
7
6
5
4
3
2
8
20
21
22
17161514131211109
23
24
IEC15000157-2-en.vsd
IEC15000157 V2 EN-US
Figure 8: LHMI keypad with object control, navigation and command push-buttons andRJ-45 communication port
1...5 Function button
6 Close
7 Open
8 Escape
9 Left
10 Down
11 Up
12 Right
13 Key
14 Enter
15 Remote/Local
16 Uplink LED
17 Not in use
18 Multipage
19 Menu
20 Clear
21 Help
Section 6 1MRK 500 129-UEN BLHMI overview
22 670/650 seriesQuick start guide
22 Communication port
23 Programmable indication LEDs
24 IED status LEDs
Object control
If the control position of the IED is set to local with the R/L button, the controlled objects canbe opened and closed using the object control buttons.
Object to be controlled is selected from the single line diagram.
Table 6: Object control push-buttons
Name Description
CloseClosing the object.The LED indicates the current object state.
OpenOpening the object.The LED indicates the current object state.
Navigation
The arrow buttons are used for navigation. To scroll information, press the arrow buttonseveral times or simply keep it pressed down.
Table 7: Navigation push-buttons
Name Description
ESC• Leaving setting mode without saving the values.• Cancelling certain actions.• Adjusting the display contrast in combination with or .• Running the display test in combination with .• Deleting a character in combination with when editing a string.• Inserting a space in combination with when editing a string.
Enter• Entering parameter setting mode.• Confirming a new value of a setting parameter.• Confirming selection in dialogs and alarm panel.
Up
Down
• Moving up and down in menus.• Selecting objects in the SLD.• Moving selection in dialogs and alarm panel.• Scrolling active digits of a parameter when entering a new setting value.
Left
Right
• Moving left and right in menus.• Selecting pages in the SLD.• Changing the active digit of a parameter when entering a new setting value.
Key• Activating the authorization procedure, when the user is not logged in.• Logging out, when the user is currently logged in.
1MRK 500 129-UEN B Section 6LHMI overview
670/650 series 23Quick start guide
Commands
Table 8: Command push-buttons
Name Description
Menu• Moving directly to Main menu, if currently
in any other menu or view.• Moving to the default view, if currently in
Main menu.
R/LChanging the control position (remote or local)of the device.
• When the R LED is lit, remote control isenabled and local control disabled.
• When the L LED is lit, local control isenabled and remote control disabled.
• When none of the LEDs are lit, both controlpositions are disabled.
Clear• Activating the Clear/Reset view.
HelpShowing the help menu.
MultipageOpening alarm panel and selecting alarm pagefrom the view.
Function buttons
Table 9: Function buttons
Name Description
Functionbutton
Executing the defined function: OFF, menu short cut or binary control.
6.1.2 DisplayGUID-55739D4F-1DA5-4112-B5C7-217AAF360EA5 v13
The LHMI includes a graphical monochrome liquid crystal display (LCD) with a resolution of 320x 240 pixels. The character size can vary. The amount of characters and rows fitting the viewdepends on the character size and the view that is shown.
The display view is divided into four basic areas.
Section 6 1MRK 500 129-UEN BLHMI overview
24 670/650 seriesQuick start guide
IEC15000270-1-en.vsdx
IEC15000270 V1 EN-US
Figure 9: Display layout
1 Path
2 Content
3 Status
4 Scroll bar (appears when needed)
• The path shows the current location in the menu structure. If the path is too long to beshown, it is truncated from the beginning, and the truncation is indicated with three dots.
• The content area shows the menu content.• The status area shows the current IED time, the user that is currently logged in and the
object identification string which is settable via the LHMI or with PCM600.• If text, pictures or other items do not fit in the display, a vertical scroll bar appears on the
right. The text in content area is truncated from the beginning if it does not fit in thedisplay horizontally. Truncation is indicated with three dots.
1MRK 500 129-UEN B Section 6LHMI overview
670/650 series 25Quick start guide
IEC15000138-1-en.vsdx
IEC15000138 V1 EN-US
Figure 10: Truncated path
The function key button panel shows on request what actions are possible with the functionbuttons. Each function button has a LED indication that can be used as a feedback signal forthe function button control action. The LED is connected to the required signal with PCM600.
IEC13000281-1-en.vsdGUID-C98D972D-D1D8-4734-B419-161DBC0DC97B V1 EN-US
Figure 11: Function button panel
The indication LED panel shows on request the alarm text labels for the indication LEDs. Threeindication LED pages are available.
Section 6 1MRK 500 129-UEN BLHMI overview
26 670/650 seriesQuick start guide
IEC13000240-1-en.vsdGUID-5157100F-E8C0-4FAB-B979-FD4A971475E3 V1 EN-US
Figure 12: Indication LED panel
The function button and indication LED panels are not visible at the same time. Each panel isshown by pressing one of the function buttons or the Multipage button. Pressing the ESCbutton clears the panel from the display. Both panels have a dynamic width that depends onthe label string length.
6.1.3 LEDsAMU0600427 v14
The LHMI includes three status LEDs above the display: Ready, Start and Trip.
There are 15 programmable indication LEDs on the front of the LHMI. Each LED can indicatethree states with the colors: green, yellow and red.
There are 3 separate panels of LEDs available. The 15 physical three-color LEDs in one LEDgroup can indicate 45 different signals. Altogether, 135 signals can be indicated since there arethree LED groups. The LEDs are lit according to priority, with red being the highest and greenthe lowest priority. For example, if on one panel there is an indication that requires the greenLED to be lit, and on another panel there is an indication that requires the red LED to be lit, thered LED takes priority and is lit. The LEDs can be configured with PCM600 and the operationmode can be selected with the LHMI or PCM600.
Information panels for the indication LEDs are shown by pressing the Multipage button.Pressing that button cycles through the three pages. A lit or un-acknowledged LED is indicatedwith a highlight. Such lines can be selected by using the Up/Down arrow buttons. Pressing theEnter key shows details about the selected LED. Pressing the ESC button exits frominformation pop-ups as well as from the LED panel as such.
The Multipage button has a LED. This LED is lit whenever any LED on any panel is lit. If there areun-acknowledged indication LEDs, then the Multipage LED blinks. To acknowledge LEDs, pressthe Clear button to enter the Reset menu (refer to description of this menu for details).
There are two additional LEDs which are next to the control buttons and . TheseLEDs can indicate the status of two arbitrary binary signals by configuring theOPENCLOSE_LED function block. For instance, OPENCLOSE_LED can be connected to a circuitbreaker to indicate the breaker open/close status on the LEDs.
1MRK 500 129-UEN B Section 6LHMI overview
670/650 series 27Quick start guide
IEC16000076-1-en.vsdIEC16000076 V1 EN-US
Figure 13: OPENCLOSE_LED connected to SXCBR
6.1.4 Local HMI functionality
6.1.4.1 Protection and alarm indicationGUID-09CCB9F1-9B27-4C12-B253-FBE95EA537F5 v17
Protection indicators
The protection indicator LEDs are Ready, Start and Trip.
The yellow and red status LEDs are configured in the disturbance recorderfunction, DRPRDRE, by connecting a start or trip signal from the actual functionto a BxRBDR binary input function block using the PCM600 and configure thesetting to Off, Start or Trip for that particular signal.
Table 10: Ready LED (green)
LED state Description
Off Auxiliary supply voltage is disconnected.
On Normal operation.
Flashing Internal fault has occurred.
Table 11: Start LED (yellow)
LED state Description
Off Normal operation.
On A protection function has started and an indication message is displayed.The start indication is latching and must be reset via communication, LHMI orbinary input on the LEDGEN component. To open the reset menu on the LHMI,
press .
Flashing The IED is in test mode and protection functions are blocked, or the IEC61850protocol is blocking one or more functions.The indication disappears when the IED is no longer in test mode and blockingis removed. The blocking of functions through the IEC61850 protocol can bereset in Main menu/Test/Reset IEC61850 Mod. The yellow LED changes toeither On or Off state depending on the state of operation.
Section 6 1MRK 500 129-UEN BLHMI overview
28 670/650 seriesQuick start guide
Table 12: Trip LED (red)
LED state Description
Off Normal operation.
On A protection function has tripped. An indication message is displayed if theauto-indication feature is enabled in the local HMI.The trip indication is latching and must be reset via communication, LHMI orbinary input on the LEDGEN component. To open the reset menu on the LHMI,
press .
Flasing Configuration mode.
Alarm indicators
The 15 programmable three-color LEDs are used for alarm indication. An individual alarm/status signal, connected to any of the LED function blocks, can be assigned to one of the threeLED colors when configuring the IED.
Table 13: Alarm indications
LED state Description
Off Normal operation. All activation signals are off.
On • Follow-S sequence: The activation signal is on.• LatchedColl-S sequence: The activation signal is on, or it is off but the indication has not
been acknowledged.• LatchedAck-F-S sequence: The indication has been acknowledged, but the activation
signal is still on.• LatchedAck-S-F sequence: The activation signal is on, or it is off but the indication has
not been acknowledged.• LatchedReset-S sequence: The activation signal is on, or it is off but the indication has
not been acknowledged.
Flashing • Follow-F sequence: The activation signal is on.• LatchedAck-F-S sequence: The activation signal is on, or it is off but the indication has
not been acknowledged.• LatchedAck-S-F sequence: The indication has been acknowledged, but the activation
signal is still on.
1MRK 500 129-UEN B Section 6LHMI overview
670/650 series 29Quick start guide
30
Section 7 Connecting to the PCM600 softwareGUID-DD4CDCDE-8909-48EC-96EA-93B43FA106D1 v1
The software suite used for communicating to the IED is the PCM600. This tool enables toread and modify the settings in the IED, and to view the events register, disturbance recorder(oscillography), and other monitoring tasks.
7.1 PCM600 toolAMU0600443 v13
Protection and Control IED Manager PCM600 offers all the necessary functionality to workthroughout all stages of the IED life cycle.
• Planning• Engineering• Commissioning• Operation and disturbance handling• Functional analysis
When using PCM600 for writing to the IED, ensure that the LHMI is not in amenu position where settings can be made. Only one active transaction, fromLHMI or PCM600, is allowed at a time.
With the individual tool components, you can perform different tasks and functions andcontrol the whole substation. PCM600 can operate with many different topologies, dependingon the customer needs.
For more information, see PCM600 documentation.
7.1.1 Connectivity packagesGUID-D480127C-3F19-44A3-9A6F-A8549C02CDCD v2
A connectivity package is a software component that consists of executable code and datawhich enables system tools to communicate with an IED. Connectivity packages are used tocreate configuration structures in PCM600. The latest PCM600 and connectivity packages arebackward compatible with older IED versions.
A connectivity package includes all of the data which is used to describe the IED, for example,it contains a list of the existing parameters, data format used, units, setting range, accessrights and visibility of the parameter. In addition, it contains code which allows softwarepackages that consume the connectivity package to properly communicate with the IED. Italso allows for localization of text even when its read from the IED in a standard format suchas COMTRADE.
Update Manager is a tool that helps in defining the right connectivity package versions fordifferent system products and tools. Update Manager is included with products that useconnectivity packages. Update Manager is a part of PCM600 and is delivered with it.
1MRK 500 129-UEN B Section 7Connecting to the PCM600 software
670/650 series 31Quick start guide
7.2 Preparing for the connectionGUID-D80F3808-4149-4737-A25A-7FF240E451C5 v1
1. Keep a crossover RJ45 cable ready to connect between the PC and IED.Most modern PCs can automatically ‘crossover’ the straight connection RJ45 cables. Forexample, if a Gigabit Ethernet is used in the system, a crossover cable is not required. If itis unsure whether the PC has this functionality, then use a crossover cable.
7.3 Installing the PCM600 softwareGUID-D0D14BE6-81C5-4D16-9D5F-2536143720CE v2
1. Download the latest version of PCM600 software from ABB Software Library.2. Follow the instructions in the installation wizard to install the software.
7.4 Connecting the cablesGUID-C03819DA-1243-4C59-A74F-30334C267602 v1
1. Connect the RJ45 Ethernet cable between the front port of the IED and the PC.
IEC18000031-1-en.vsdx
IEC18000031 V1 EN-US
Figure 14: RJ45 cable connection to the front port of the IED
The default IP address of the front port of the IED, 10.1.150.3, is used to establish a connection.
Section 7 1MRK 500 129-UEN BConnecting to the PCM600 software
32 670/650 seriesQuick start guide
Section 8 Editing the network settingsGUID-46742F3A-48A3-4C24-A354-AD721C69023C v1
Before starting the PCM600 program, edit the network settings of the computer system. Thecomputer system and the IED should be configured to communicate correctly because bothwill be available on the same network. This is possible when the IED and the computer systemhave the same Subnet Mask but different IP addresses.
Figure shows this concept and the addresses are used as an example; other addresses canalso be used.
Subnet Mask for both:255.255.255.0
IEC18000032-1-en.vsdx
670 IEDIP address (Front Port): 10.1.150.3
PCIP address: 10.1.150.4
IEC18000032 V1 EN-US
Figure 15: Network settings to connect PC with an IED
Based on the version of the Windows operating system, follow the instructions to edit networksettings.
The PCM600 software version 2.8 or later is used to connect to the IED thatsupports Windows XP, 7, 8, 8.1, and 10.
8.1 Setting up communication between PCM600 and theIED
SEMOD58570-5 v15
The communication between the IED and PCM600 is independent of the communicationprotocol used within the substation or to the NCC.
The communication media is always Ethernet and the used transport layer is TCP/IP.
1MRK 500 129-UEN B Section 8Editing the network settings
670/650 series 33Quick start guide
Each IED has an RJ-45 Ethernet interface connector on the front. The front Ethernet connectoris recommended to be used for communication with PCM600.
When an Ethernet-based station protocol is used, PCM600 communication can use the sameEthernet port and IP address.
To connect PCM600 to the IED, two basic variants must be considered.
• Direct point-to-point link between PCM600 and the IED front port.• A link via a station LAN or from remote via a network.
The physical connection and the IP address must be configured in both cases to enablecommunication.
The communication procedures are the same in both cases.
1. If needed, set the IP address for the IEDs.2. Set up the PC or workstation for a direct link (point-to-point), or3. Connect the PC or workstation to the LAN/WAN network.4. Configure the IED IP addresses in the PCM600 project for each IED to match the IP
addresses of the physical IEDs.
Setting up IP addresses
Communication between the IED and PCM600 is enabled from the LHMI. The IP address andthe corresponding communication subnetwork mask must be set via the Ethernetconfiguration tool (ECT) for each available Ethernet interface in the IED. Each Ethernetinterface has a default factory IP address when the IED is delivered. The IP adress and thesubnetwork mask might have to be reset when an additional Ethernet interface is installed oran interface is replaced.
DHCP is available for the front port, and a device connected to it can thereby obtain anautomatically assigned IP address via the local HMI path Main menu/Configuration/Communication/Ethernet configuration/Front port/DHCP.
Alternatively the default IP address for the IED front port is 10.1.150.3 and the correspondingsubnetwork mask is 255.255.255.0, which can be set via the local HMI path Main menu/Configuration/Communication/TCP-IP configuration/ETHFRNT:1Main menu/Configuration/Communication/Ethernet configuration/AP_FRONT.
Setting up the PC or workstation for point-to-point access to IEDs frontport
An ethernet cable (max 2 m length) with RJ-45 connectors is needed to connect two physicalEthernet interfaces together without a hub, router, bridge or switch in between.
If an IED is equipped with optical LC interface, a converter between RJ-45 andLC is needed.
1. Select Search programs and files in the Start menu in Windows.
Section 8 1MRK 500 129-UEN BEditing the network settings
34 670/650 seriesQuick start guide
IEC13000057-1-en.vsdIEC13000057 V1 EN-US
Figure 16: Select: Search programs and files
2. Type View network connections and click on the View network connections icon.
1MRK 500 129-UEN B Section 8Editing the network settings
670/650 series 35Quick start guide
IEC13000058-1-en.vsdIEC13000058 V1 EN-US
Figure 17: Click View network connections
3. Right-click and select Properties.
IEC13000059-1-en.vsd
IEC13000059 V1 EN-US
Figure 18: Right-click Local Area Connection and select Properties
4. Select the TCP/IPv4 protocol from the list of configured components using thisconnection and click Properties.
Section 8 1MRK 500 129-UEN BEditing the network settings
36 670/650 seriesQuick start guide
IEC13000060-1-en.vsdIEC13000060 V1 EN-US
Figure 19: Select the TCP/IPv4 protocol and open Properties
5. Select Use the following IP address and define IP address and Subnet mask if the frontport is used and if the IP address is not set to be obtained automatically by the IED,seeFigure 20. The IP address must be different from the IP address chosen for the IED.
IEC13000062-1-en.vsdIEC13000062 V1 EN-US
Figure 20: Select: Use the following IP address
6. Close all open windows and start PCM600.
The PC and IED must belong to the same subnetwork for this set-up to work.
1MRK 500 129-UEN B Section 8Editing the network settings
670/650 series 37Quick start guide
Setting up the PC to access the IED via a network
The same method is used as for connecting to the front port.
The PC and IED must belong to the same subnetwork for this set-up to work.
Section 8 1MRK 500 129-UEN BEditing the network settings
38 670/650 seriesQuick start guide
Section 9 Working with the PCM softwareGUID-F61C3F9B-7CD0-4F92-9ACA-D4852B3FA994 v2
The Protection and Control IED Manager, PCM600, tool provides versatile functionalities forthe complete life-cycle of all Relion IEDs at all voltage levels. It enables to read or write theconfiguration and settings from and to the IED.
After connecting the PCM software and modified network settings, the system is ready toconnect to the IED.
To operate with PCM600, there must be at least one IED Connectivity Package installed andselected to be used with the PCM600 version installed. See the PCM600 getting started guidefor detailed information about working with PCM600.
1MRK 500 129-UEN B Section 9Working with the PCM software
670/650 series 39Quick start guide
40
41