Quick guide to ASIMON configurationFor version 3.0 or greater
SAFETY AT WORK
Date: 3/18/2009
![Page 2: Quick guide to ASIMON configuration For version 3.0 or greater SAFETY AT WORK Date: 3/18/2009.](https://reader033.fdocuments.us/reader033/viewer/2022061612/5697c02b1a28abf838cd8c8f/html5/thumbnails/2.jpg)
Step 1: Launch and start new program
Open ASIMON 3.0 or higher and Launch a new configuration as shown below
Click “OK”
![Page 3: Quick guide to ASIMON configuration For version 3.0 or greater SAFETY AT WORK Date: 3/18/2009.](https://reader033.fdocuments.us/reader033/viewer/2022061612/5697c02b1a28abf838cd8c8f/html5/thumbnails/3.jpg)
Step 2: Information about monitor and bus
Information Monitor tab: Fill in a configuration title Choose an operation mode
One OSSD = 1 safety zone Two independent OSSD = 2 safety
zones Two dependent = If 1st zone trips,
2nd zone will trip as well.
Current safety monitor will use the enhance function. Only older safety monitoring units with firmware <2.0 will require basic.
![Page 4: Quick guide to ASIMON configuration For version 3.0 or greater SAFETY AT WORK Date: 3/18/2009.](https://reader033.fdocuments.us/reader033/viewer/2022061612/5697c02b1a28abf838cd8c8f/html5/thumbnails/4.jpg)
Step 2: Information about monitor and bus
Information Bus tab: Check any safety and
standard addresses on your network.
![Page 5: Quick guide to ASIMON configuration For version 3.0 or greater SAFETY AT WORK Date: 3/18/2009.](https://reader033.fdocuments.us/reader033/viewer/2022061612/5697c02b1a28abf838cd8c8f/html5/thumbnails/5.jpg)
Step 2: Information about monitor and bus
Diagnosis/Service tab: Optional: Here you can
provide an AS-I address to the safety monitor for diagnostic feedback.
Click “OK”
![Page 6: Quick guide to ASIMON configuration For version 3.0 or greater SAFETY AT WORK Date: 3/18/2009.](https://reader033.fdocuments.us/reader033/viewer/2022061612/5697c02b1a28abf838cd8c8f/html5/thumbnails/6.jpg)
Step 3: Configure safety zones
Drag and Drop configuration of safety zones
Three main items are needed for each safety zone
1. Monitoring devices
2. Output devices (Stop)
3. Start devices
![Page 7: Quick guide to ASIMON configuration For version 3.0 or greater SAFETY AT WORK Date: 3/18/2009.](https://reader033.fdocuments.us/reader033/viewer/2022061612/5697c02b1a28abf838cd8c8f/html5/thumbnails/7.jpg)
Step 3: Configure safety zones
Add monitoring devices: Simply drag the desire
monitoring icon over to the blank window and release.
Choose the type of contact monitoring
Select the address of the safety module to monitor
Click “OK” Repeat for additional devices
![Page 8: Quick guide to ASIMON configuration For version 3.0 or greater SAFETY AT WORK Date: 3/18/2009.](https://reader033.fdocuments.us/reader033/viewer/2022061612/5697c02b1a28abf838cd8c8f/html5/thumbnails/8.jpg)
Step 3: Configure safety zones
Add output (stop) device: Simply drag the desire
monitoring icon over to the blank window and release.
Two types to select from: Stop Cat 0 – Immediate stop Stop Cat 1 – User define delay
stop
Provide a name Select desired OSSD (Zone) Click “OK”
![Page 9: Quick guide to ASIMON configuration For version 3.0 or greater SAFETY AT WORK Date: 3/18/2009.](https://reader033.fdocuments.us/reader033/viewer/2022061612/5697c02b1a28abf838cd8c8f/html5/thumbnails/9.jpg)
Step 3: Configure safety zones
Add start device: Simply drag the desire
monitoring icon over to the blank window and release.
Main types to select from: Auto Start – Auto start when all
devices in closed state Monitor Start/Monitor input –
Push button wired to monitor will provide enable signal to start.
Provide name Click “OK”
![Page 10: Quick guide to ASIMON configuration For version 3.0 or greater SAFETY AT WORK Date: 3/18/2009.](https://reader033.fdocuments.us/reader033/viewer/2022061612/5697c02b1a28abf838cd8c8f/html5/thumbnails/10.jpg)
Step 3: Configure safety zones
Add 2nd OSSD zone: Click for a new window Repeat step 3 again
![Page 11: Quick guide to ASIMON configuration For version 3.0 or greater SAFETY AT WORK Date: 3/18/2009.](https://reader033.fdocuments.us/reader033/viewer/2022061612/5697c02b1a28abf838cd8c8f/html5/thumbnails/11.jpg)
Step 4: Download to safety monitor
Make sure safety monitor is powered up with AS-I and 24 VDC.
Connect the E7001S cable to your serial port or USB adapter to the safety monitor
Make sure you have the correct COM port assigned
If the menu under Monitor is grayed out, please check cable connection between PC and safety monitor
![Page 12: Quick guide to ASIMON configuration For version 3.0 or greater SAFETY AT WORK Date: 3/18/2009.](https://reader033.fdocuments.us/reader033/viewer/2022061612/5697c02b1a28abf838cd8c8f/html5/thumbnails/12.jpg)
Step 4: Download to safety monitor
New monitor will have password defaulted as “SIMON” --Case sensitive
You will need to change this before downloading
4-8 alphanumerical characters; case sensitive
![Page 13: Quick guide to ASIMON configuration For version 3.0 or greater SAFETY AT WORK Date: 3/18/2009.](https://reader033.fdocuments.us/reader033/viewer/2022061612/5697c02b1a28abf838cd8c8f/html5/thumbnails/13.jpg)
Step 4: Download to safety monitor
Before you download the configuration, please make sure all safety devices on the system is in the close position. If not, the download will not be completed.
Go to Monitor/PC to Monitor Enter the password you just
created in the last slide.
![Page 14: Quick guide to ASIMON configuration For version 3.0 or greater SAFETY AT WORK Date: 3/18/2009.](https://reader033.fdocuments.us/reader033/viewer/2022061612/5697c02b1a28abf838cd8c8f/html5/thumbnails/14.jpg)
Step 4: Download to safety monitor
Click “Yes” to teach the code sequences
This will teach the safety code from each safety I/O module into the monitor
![Page 15: Quick guide to ASIMON configuration For version 3.0 or greater SAFETY AT WORK Date: 3/18/2009.](https://reader033.fdocuments.us/reader033/viewer/2022061612/5697c02b1a28abf838cd8c8f/html5/thumbnails/15.jpg)
Step 4: Download to safety monitor
Once completed, a configuration log file is generated detailing the current configuration of the system.
This file can be request later and printed out as safety documentation
Click “OK”
![Page 16: Quick guide to ASIMON configuration For version 3.0 or greater SAFETY AT WORK Date: 3/18/2009.](https://reader033.fdocuments.us/reader033/viewer/2022061612/5697c02b1a28abf838cd8c8f/html5/thumbnails/16.jpg)
Step 4: Download to safety monitor
In order to run the safety system, you must now enter in the password again as a form of validating the system
![Page 17: Quick guide to ASIMON configuration For version 3.0 or greater SAFETY AT WORK Date: 3/18/2009.](https://reader033.fdocuments.us/reader033/viewer/2022061612/5697c02b1a28abf838cd8c8f/html5/thumbnails/17.jpg)
Step 4: Download to safety monitor
After validation, the configuration log will be changed to note the time and date.
Click “Yes” to put the monitor in run mode.