Technical Data TD008008ENEffective September 2020 Supersedes December 2014
Quick connect heavy-duty safety switches
IntroductionEaton’s individual cable connector receptacle switches provide a convenient and safe way to quickly connect and disconnect portable equipment. Depending on the configuration, either the load-side or line-side terminals are factory wired to individual receptacles located behind an interlocked door for added safety. The switch cannot be turned to the ON position without first closing the receptacle compartment door.
2
Technical Data TD008008ENEffective September 2020
Quick connect heavy-duty safety switches
EATON www.eaton.com
Features, functions, and benefitsDouble-throw switch
Provides a safe and quick means of connecting portable generators to facilities, transferring the building to backup power, or providing for temporary connection of portable loads.
Features
• Increased flexibility: 100–1200 A ratings• 240 V or 600 Vac• Source 1 and Source 2 available in the following configurations
• Fusible/fusible
• Fusible/non-fusible
• Non-fusible/fusible
• Non-fusible/non-fusible
• Available in NEMA Type 1 or 3R enclosures for indoor or outdoor applications
Code compliance
• Interlocked receptacle compartment (NECT 702.12)• Optional auxiliary contacts for remote indication of switch position
(for compliance with NEC 700.3)• ULT 98 listed
Load lugs
Lower switch
Generator receptacles
Upper switch
Utility lugs
ON
ON
OFF
Upperswitch
Lowerswitch
Figure 1. Double-throw switch configuration
Company switch
The Company switch allows for a portable load, such as theater lighting, to be quickly connected to utility power.
Features
• Receptacles that allow for the connection of lighting, sound, and other portable loads
• Factory wired to ensure connection reliability and simple plug-in setup
• May be locked in the OFF position to prevent access by unauthorized personnel
• Increased flexibility: 100–1200 A ratings• 240 V or 600 Vac • Available in NEMAT Type 1 or 3R enclosures for indoor
or outdoor applications
Code compliance
• Meets minimum requirements of NEC Section 520.5(B) for theaters and Section 525.21(A) for carnivals while including a safety interlock, as well as ULT and CSAT listings for the complete device
• Fusible configurations also meet the requirements of NEC Section 525.22 for termination boxes
Utility lugs
Receptacle outlets to portable load
Figure 2. Company switch configuration
3
Technical Data TD008008ENEffective September 2020
Quick connect heavy-duty safety switches
EATON www.eaton.com
Generator switch
The Generator switch offers a simple connection for portable generators in locations in which utility power is unavailable.
Features
• Contains one vertically oriented switch in an interlocked enclosure that contains receptacles for connecting the portable source
• Receptacles allow the user to attach to the switch using simple cable connections
• Increased flexibility: 100–1200 A ratings• 240 V or 600 Vac• Available in NEMA Type 1 or 3R enclosures for indoor or
outdoor applications• Lock-off provision that enables the handle to be padlocked
in the OFF position
Code compliance
• Meets the requirement of NEC 708.20(F)(6)• UL Listed—File No. E5239• To avoid backfed generator power onto the grid, ensure that the
necessary code requirements are followed (for example, key interlocking, double-throw switch, tie interlocking, and so on)
Load lugs
Receptacle inlets from portable source
Figure 3. Generator switch configuration
4
Technical Data TD008008ENEffective September 2020
Quick connect heavy-duty safety switches
EATON www.eaton.com
Dimensions in inches (mm)
18.57(471.7)
50.45(1281.4)Conduit
entryallowedalongthisside
61.24(1555.5)
18.15(461.0)
No conduit entry on this end
13.56 (344.4) 8.59 (218.2)
Conduitentry
allowedin thisarea
5.00(127.0)60.51
(1537.0)
95.75(2432.1)
68.25(1733.6)
62.89(1597.4)
33.50(850.9)
6.00(152.4)
Grade
14.00 (355.6) 2.24 (56.9)7.00 (177.8)
58.38(1482.9)
4.14(105.2)
38.90(988.1)
Figure 4. 100/200 A QCDT switch (drawing 95-1807)
23.65(600.7)
93.11(2365.0)
26.68(677.7)
50.18(1274.6)
10.63(270.0)
26.25(666.8)
15.61(396.5)
5.12(130.0)
2.65(67.31)
44.43(1128.5)
92.49(2349.2)
17.75(450.9)
16.00 (406.4)8.02
(203.7)
8.00 (203.2)4.42
(112.3)
1.37(34.8)
2.93(74.4)
20.95(532.1)
ø0.560Mounting
holes
87.25(2216.2)
15.40(391.2)
Figure 5. 400 A QCDT switch (drawing 95-1805)
15.61(396.5)
29.25(743.0)16.00 (406.4)
8.02(203.7)
8.00 (203.2)
“A”
23.65(600.7)
37.75(958.9)
38.18(969.8)
61.68(1566.7)
5.12(130.0)
4.42(112.3)
93.11(2365.0)
10.63(270.0)
2.65(67.3)
44.43(1128.5)
92.49(2349.2)
1.37(34.8)
2.93(74.4)
20.95(532.1)
ø0.560Mounting
holes
87.25(2216.2)
Figure 6. 600–800 A QCDT switch (drawing 95-1798)
5
Technical Data TD008008ENEffective September 2020
Quick connect heavy-duty safety switches
EATON www.eaton.com
ø0.56Mountingholes
43.82(1112.9)
66.70(1694.2)
90.60(2301.2)
Conduit entry allowed along left side
Conduit entryallowed inthis area
27.71 (703.8)20.47 (250.0)
42.32 (1075.0)
Conduit entryallowed in top end wall
22.61(574.2) 88.15
(2238.1)
84.56(2147.8)
58.28 (1480.3)
Grade
6.00 (152.4) Minimum
16.82 (427.2)
81.19(2062.3)
36.00(914.4)
3.37(85.6)
4.37(110.9)
Figure 7. 1200 A QCDT switch (drawing 95-6181)
27.43(696.7)
38.15(969.0)
18.57(471.7)
1.93 (49.0)
6.25 (158.8)
28.42(721.9)
13.68 (347.5)8.61 (218.7)
37.40(950.0)
39.12(993.6)
39.78(1010.4)
2.24 (56.9)7.00 (177.8)
14.00 (355.6)
35.27(895.9)
4.15(105.4)
6.00 (152.4) Minimum
5.00(127.0)
18.00(457.2)
R0.25
1.06(26.9)Conduit
entry allowed along left side
ø0.56Mounting Holes
GradeConduit entry allowed in top end wall
Conduit entry allowed in this area
Figure 8. 100 A QCST switch (drawing 95-1961)
18.00(457.2)
18.57(471.7)
40.89(1038.6)
30.17(766.3)
1.94(49.3)
Conduit entryallowed in top end wall
Conduit entryallowed along left side
ø0.56Mountingholes
Conduit entry allowed inthis area
Conduit entry allowed in this area
13.68(347.5)
6.00 (152.4)
42.53(1080.3)
28.38(720.8)
41.87(1063.5)
40.15(1019.8)
6.00 (152.4) Minimum
6.25 (158.8)Grade
8.61 (218.7)
14.00(355.6)
2.24 (56.9)
1.06(26.9)
R0.25 7.00 (177.8)
38.02(965.7)
4.15(105.4)
Figure 9. 200 A QCST switch (drawing 95-1962)
6
Technical Data TD008008ENEffective September 2020
Quick connect heavy-duty safety switches
EATON www.eaton.com
32.60(828.0)
Conduit entry allowed in top end wall
32.87(834.9)
60.69(1541.5)
74.34(1888.2)
Conduit entryallowed inthis area
Conduit entryallowed along left side
16.10 (408.9)
6.00 (152.4) Minimum
11.14 (283.0)
12.00(304.8) 73.79
(1874.3)
69.79(1772.7)
51.64(1311.6)
8.30 (210.8) Grade
ø0.56Mountingholes
24.00(609.6) 4.39
(111.5)
4.34(110.2)
65.80(1671.3)
Figure 10. 400–600 A QCST switch (drawing 95-1963)
ø0.56Mountingholes
32.87(834.9)
60.69(1541.5)
85.59(2174.0)
Conduit entry allowed along left side
Conduit entryallowed inthis area
21.73 (551.9)16.79 (426.5)
32.60 (828.0)
Conduit entryallowed in top end wall
12.00(304.8)
85.04(2160.0)
81.03(2058.2)
62.23(1580.6)
Grade
6.00 (152.4) Minimum
13.96 (354.6)
77.05(1957.1)
24.00(609.6)
4.34(110.2)
4.39(111.5)
Figure 11. 800 A QCST switch (drawing 95-1964)
ø0.56Mountingholes
43.82(1112.9)
66.70(1694.2)
90.60(2301.2)
Conduit entry allowed along left side
Conduit entryallowed inthis area
27.71 (703.8)20.47 (250.0)
42.32 (1075.0)
Conduit entryallowed in top end wall
22.61(574.2) 88.15
(2238.1)
84.56(2147.8)
58.28 (1480.3)
Grade
6.00 (152.4) Minimum
16.82 (427.2)
81.19(2062.3)
36.00(914.4)
3.37(85.6)
4.37(110.9)
Figure 12. 1200 A QCST switch (drawing 95-6181)
7
Technical Data TD008008ENEffective September 2020
Quick connect heavy-duty safety switches
EATON www.eaton.com
Technical data
Table 1. Available lug capacities of the double-throw switch assembly with Cam-LokE or Posi-LokE receptacles
Double-throw switch size—Cam-Lok or Posi-Lok receptacle
Standard fuse
Service terminal openings Cu/AI
Load terminal openings Cu/AI
Switched neutral pole load terminal openings Cu/AI
Solid neutral terminal openings Cu/AI
Ground terminal openings Cu/AI
Receptacle bypass terminal
100 H (1) 1/0–14 AWG (1) 1/0–14 AWG (1) 1/0–14 AWG (2) 1/0–14 AWG, (1) 2–14 AWG
(3) 2–14 AWG (1) 10–32 Screw mounting
200 H (1) 300 kcmil–6 AWG (1) 250 kcmil–6 AWG (1) 250 kcmil–6 AWG (2) 250 kcmil–6 AWG (1) 1/0–14 AWG, (1) 2–14 AWG
(3) 2–14 AWG (2) 1/4 studs 1.75-inch spacing
400 T (1) 750 kcmil–1/0 or (2) 300 kcmil–1/0
(1) 750 kcmil–1/0 or (2) 300 kcmil–1/0
(1) 750 kcmil–1/0 or (2) 300 kcmil–1/0
(6) 500 kcmil, (6) 250 kcmil–6 AWG
(4) 250 kcmil 6 AWG (2) 1/2-13 UNC studs, 1.75-inch spacing
600 T (4) 750 kcmil–1/0 (4) 750 kcmil–1/0 (4) 750 kcmil–1/0 (6) 500–250 kcmil, (4) 250 kcmil–6 AWG
(4) 250 kcmil 6 AWG (2) 1/2-13 UNC studs, 1.75-inch spacing
800 T (4) 750 kcmil–1/0 (4) 750 kcmil–1/0 (4) 750 kcmil–1/0 (6) 500–250 kcmil, (4) 250 kcmil–6 AWG
(4) 250 kcmil 6 AWG (2) 1/2-13 UNC studs, 1.75-inch spacing
1200 L (4) 750 kcmil–1/0 (4) 750 kcmil–1/0 (4) 750 kcmil–1/0 (6) 500–250 kcmil, (4) 250 kcmil–6 AWG
(4) 250 kcmil 6 AWG —
Table 2. Double-throw switch standard receptacles and corresponding connection plugs
Switch ampacity
Connector color
Cam-Lok connectors Posi-Lok connectors
Receptacle a Plug b Receptacle panel Plug c
240 Vac
100, 200 Ground (green)Neutral (white)A phase (black)B phase (red)C phase (blue)
E1016-1635SE1016-1636SE1016-1600SE1016-1602SE1016-1612S
E-Z1016-8366E-Z1016-8367E-Z1016-8387E-Z1016-8389E-Z1016-8393
Two-pole, three-wire with Solid Neutral or three-pole, three-wire with Switched Neutral Pole (two-phase and one Neutral Pole): E0200-1672/ three-pole, three-wire (no Neutral): E0200-1661-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): E0200-1662
E0200-281E0200-282E0200-283E0200-284E0200-285
400 Ground (green)Neutral (white)A phase (black)B phase (red)C phase (blue)
E1016-1635SE1016-1636SE1016-1600SE1016-1602SE1016-1612S
E-Z1016-8366E-Z1016-8367E-Z1016-8387E-Z1016-8389E-Z1016-8393
Two-pole, three-wire with Solid Neutral or three-pole, three-wire with Switched Neutral Pole (two-phase and one Neutral Pole): E0400-1672/ three-pole, three-wire (no Neutral): E0400-1661-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): E0400-1662
E0400-281E0400-282E0400-283E0400-284E0400-285
600, 800 Ground (green)Neutral (white)A phase (black)B phase (red)C phase (blue)
(2) E1016-1635S(2) E1016-1636S(2) E1016-1600S(2) E1016-1602S(2) E1016-1612S
(2) E-Z1016-8366(2) E-Z1016-8367(2) E-Z1016-8387(2) E-Z1016-8389(2) E-Z1016-8393
Two-pole, three-wire with Solid Neutral or three-pole, three-wire with Switched Neutral Pole (two-phase and one Neutral Pole): (2) E0400-1672/ three-pole, three-wire (no Neutral): (2) E0400-1661-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): (2) E0400-1662
(2) E0400-281(2) E0400-282(2) E0400-283(2) E0400-284(2) E0400-285
1200 Ground (green)Neutral (white)A phase (black)B phase (red)C phase (blue)
(3) E1016-1635S(3) E1016-1636S(3) E1016-1600S(3) E1016-1602S(3) E1016-1612S
(3) E-Z1016-8366(3) E-Z1016-8367(3) E-Z1016-8387(3) E-Z1016-8389(3) E-Z1016-8393
Two-pole, three-wire with Solid Neutral or three-pole, three-wire with Switched Neutral Pole (two-phase and one Neutral Pole): (3) E0400-1672/ three-pole, three-wire (no Neutral): (3) E0400-1661-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): (3) E0400-1662
(3) E0400-281(3) E0400-282(3) E0400-283(3) E0400-284(3) E0400-285
600 Vac d
100, 200 Ground (green)Neutral (white)A phase (brown)B phase (orange)C phase (yellow)
E1016-1635SE1016-1636SE1016-1619SE1016-1603SE1016-1601S
E-Z1016-8366E-Z1016-8367E-Z1016-8394E-Z1016-8390E-Z1016-8388
Three-pole, three-wire (no Neutral): E0200-1891-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): E0200-1891
E0200-281E0200-282E0200-288E0200-289E0200-286
400 Ground (green)Neutral (white)A phase (brown)B phase (orange)C phase (yellow)
E1016-1635SE1016-1636SE1016-1619SE1016-1603SE1016-1601S
E-Z1016-8366E-Z1016-8367E-Z1016-8394E-Z1016-8390E-Z1016-8388
Three-pole, three-wire (no Neutral): E0400-1862-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): E0400-1703
E0400-281E0400-282E0400-299E0400-295E0400-292
600, 800 Ground (green)Neutral (white)A phase (brown)B phase (orange)C phase (yellow)
(2) E1016-1635S(2) E1016-1636S(2) E1016-1619S(2) E1016-1603S(2) E1016-1601S
(2) E-Z1016-8366(2) E-Z1016-8367(2) E-Z1016-8394(2) E-Z1016-8390(2) E-Z1016-8388
Three-pole, three-wire (no Neutral): (2) E0400-1862-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): (2) E0400-1703
(2) E0400-281(2) E0400-282(2) E0400-299(2) E0400-295(2) E0400-292
1200 Ground (green)Neutral (white)A phase (brown)B phase (orange)C phase (yellow)
(3) E1016-1635S(3) E1016-1636S(3) E1016-1619S(3) E1016-1603S(3) E1016-1601S
(3) E-Z1016-8366(3) E-Z1016-8367(3) E-Z1016-8394(3) E-Z1016-8390(3) E-Z1016-8388
Three-pole, three-wire (no Neutral): (3) E0400-1862-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): (3) E0400-1703
(3) E0400-281(3) E0400-282(3) E0400-299(3) E0400-295(3) E0400-292
aFor non-standard receptacle options, please contact the Flex Center at 888-329-9272.bE/E-Z 1016 type plugs listed in above table accept 2/0–4/0 size cable.cE0200 type plugs listed in above table accept #2–2/0 size cable. E0400 type plugs listed accept 3/0–4/0 size cable.dFor Canadian switches, 600 Vac products have the same color configurations as the 240 Vac versions (green, white, black, red, blue).
8
Technical Data TD008008ENEffective September 2020
Quick connect heavy-duty safety switches
EATON www.eaton.com
Table 3. Company switch available lug capacities of the single-throw switch assembly with Cam-Lok or Posi-Lok receptacles
Switch ampacity
Service terminal openings Cu/AI
Load terminal openings Cu/AI
Switched neutral pole load terminal openings Cu/AI
Solid neutral terminal openings
Ground terminal openings Cu/AI
Receptacle bypass terminal
100 (1) 1/0–14 AWG (1) 1/0–14 AWG (1) 1/0–14 AWG (2) 14 AWG–1/0 and (2) 6–14 AWG
(1) 2–14 AWG (1) 1/0–14 AWG
200 (1) 300 kcmil–6 AWG (1) 300 kcmil–6 AWG (1) 300 kcmil–6 AWG (2) 6 AWG–300 kcmil and (2) 6–14 AWG
(2) 2–14 AWG (1) 300 kcmil–6 AWG
400 (1) 750 kcmil–1/0 or (2) 300 kcmil–1/0
(1) 750 kcmil–1/0 or (2) 300 kcmil–1/0
(1) 750 kcmil–1/0 or (2) 300 kcmil–1/0
(2x) (2) 1/0–300 kcmil or (1) 1/0–750 kcmil and (3) 6 AWG–250 kcmil
(2) 250 kcmil–6 AWG Crimp lug provisions
600 (1) 750 kcmil–1/0 or (1) 600 kcmil–2
(1) 750 kcmil–1/0 or (1) 600 kcmil–2
(1) 750 kcmil–1/0 or (1) 600 kcmil–2
(2) 2 AWG–600 kcmil and 1/0–750 kcmil and (3) 6 AWG–250 kcmil
(2) 250 kcmil–6 AWG Crimp lug provisions
800 (4) 750 kcmil–1/0 (4) 750 kcmil–1/0 (4) 750 kcmil–1/0 (2x) (4) 1/0–750 kcmil and (3) 6 AWG–250 kcmil
(2) 250 kcmil–6 AWG Crimp lug provisions
1200 (4) 750 kcmil–1/0 (4) 750 kcmil–1/0 (4) 750 kcmil–1/0 (2x) (4) 1/0–750 kcmil and (3) 6 AWG–250 kcmil
(2) 250 kcmil–6 AWG —
Table 4. Company switch standard receptacles and corresponding connection plugs
Switch ampacity
Connector color
Cam-Lok connectors Posi-Lok connectors
Receptacle a Plug b Receptacle panel Plug c
240 Vac
100, 200 Ground (green)Neutral (white)A phase (black)B phase (red)C phase (blue)
E1016-1604SE1016-1605SE1016-1631SE1016-1633SE1016-1643S
E-Z1016-8391E-Z1016-8392E-Z1016-8362E-Z1016-8364E-Z1016-8368
Two-pole, three-wire with Solid Neutral or three-pole, three-wire with Switched Neutral Pole (two-phase and one Neutral Pole): E0200-1696/ three-pole, three-wire (no Neutral): E0200-1686-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): E0200-1687
E0200-181E0200-182E0200-183E0200-184E0200-185
400 Ground (green)Neutral (white)A phase (black)B phase (red)C phase (blue)
E1016-1604SE1016-1605SE1016-1631SE1016-1633SE1016-1643S
E-Z1016-8391E-Z1016-8392E-Z1016-8362E-Z1016-8364E-Z1016-8368
Two-pole, three-wire with Solid Neutral or three-pole, three-wire with Switched Neutral Pole (two-phase and one Neutral Pole): E0400-1696/ three-pole, three-wire (no Neutral): E0400-1686-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): E0400-1687
E0400-181E0400-182E0400-183E0400-184E0400-185
600, 800 Ground (green)Neutral (white)A phase (black)B phase (red)C phase (blue)
(2) E1016-1604S(2) E1016-1605S(2) E1016-1631S(2) E1016-1633S(2) E1016-1643S
(2) E-Z1016-8391(2) E-Z1016-8392(2) E-Z1016-8362(2) E-Z1016-8364(2) E-Z1016-8368
Two-pole, three-wire with Solid Neutral or three-pole, three-wire with Switched Neutral Pole (two-phase and one Neutral Pole): (2) E0400-1696/ three-pole, three-wire (no Neutral): (2) E0400-1686-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): (2) E0400-1687
(2) E0400-181(2) E0400-182(2) E0400-183(2) E0400-184(2) E0400-185
1200 Ground (green)Neutral (white)A phase (black)B phase (red)C phase (blue)
(3) E1016-1604S(3) E1016-1605S(3) E1016-1631S(3) E1016-1633S(3) E1016-1643S
(3) E-Z1016-8391(3) E-Z1016-8392(3) E-Z1016-8362(3) E-Z1016-8364(3) E-Z1016-8368
Two-pole, three-wire with Solid Neutral or three-pole, three-wire with Switched Neutral Pole (two-phase and one Neutral Pole): (3) E0400-1696/ three-pole, three-wire (no Neutral): (3) E0400-1686-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): (3) E0400-1687
(3) E0400-181(3) E0400-182(3) E0400-183(3) E0400-184(3) E0400-185
600 Vac d
100, 200 Ground (green)Neutral (white)A phase (brown)B phase (orange)C Phase (yellow)
E1016-1604SE1016-1605SE1016-1687SE1016-1634SE1016-1632S
E-Z1016-8391E-Z1016-8392E-Z1016-8369E-Z1016-8365E-Z1016-8363
Three-pole, three-wire (no Neutral): E0200-1892-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): E0200-1890
E0200-181E0200-182E0200-199E0200-195E0200-192
400 Ground (green)Neutral (white)A phase (brown)B phase (orange)C phase (yellow)
E1016-1604SE1016-1605SE1016-1687SE1016-1634SE1016-1632S
E-Z1016-8391E-Z1016-8392E-Z1016-8369E-Z1016-8365E-Z1016-8363
Three-pole, three-wire (no Neutral): E0400-1833-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): E0400-1702
E0400-181E0400-182E0400-199E0400-195E0400-192
600, 800 Ground (green)Neutral (white)A phase (brown)B phase (orange)C phase (yellow)
(2) E1016-1604S(2) E1016-1605S(2) E1016-1687S(2) E1016-1634S(2) E1016-1632S
(2) E-Z1016-8391(2) E-Z1016-8392(2) E-Z1016-8369(2) E-Z1016-8365(2) E-Z1016-8363
Three-pole, three-wire (no Neutral): (2) E0400-1833-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): (2) E0400-1702
(2) E0400-181(2) E0400-182(2) E0400-199(2) E0400-195(2) E0400-192
1200 Ground (green)Neutral (white)A phase (brown)B phase (orange)C phase (yellow)
(3) E1016-1604S(3) E1016-1605S(3) E1016-1687S(3) E1016-1634S(3) E1016-1632S
(3) E-Z1016-8391(3) E-Z1016-8392(3) E-Z1016-8369(3) E-Z1016-8365(3) E-Z1016-8363
Three-pole, three-wire (no Neutral): (3) E0400-1833-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): (3) E0400-1702
(3) E0400-181(3) E0400-182(3) E0400-199(3) E0400-195(3) E0400-192
aFor non-standard receptacle options, please contact the Flex Center at 888-329-9272.bE/E-Z 1016 type plugs listed in above table accept 2/0–4/0 size cable.cE0200 type plugs listed in above table accept #2–2/0 size cable. E0400 type plugs listed accept 3/0–4/0 size cable.dFor Canadian switches, 600 Vac products have the same color configurations as the 240 Vac versions (green, white, black, red, blue).
9
Technical Data TD008008ENEffective September 2020
Quick connect heavy-duty safety switches
EATON www.eaton.com
Table 5. Generator switch available lug capacities of the single-throw switch assembly with Cam-Lok or Posi-Lok receptacles
Switch ampacity
Service terminal openings Cu/AI
Load terminal openings Cu/AI
Switched neutral pole load terminal openings Cu/AI
Solid neutral terminal openings
Ground terminal openings Cu/AI
Receptacle bypass terminal
100 (1) 1/0–14 AWG (1) 1/0–14 AWG (1) 1/0–14 AWG (2) 14 AWG–1/0 and (2) 6–14 AWG
(1) 2–14 AWG (1) 1/0–14 AWG
200 (1) 300 kcmil–6 AWG (1) 300 kcmil–6 AWG (1) 300 kcmil–6 AWG (2) 6 AWG–300 kcmil and (2) 6–14 AWG
(2) 2–14 AWG (1) 300 kcmil–6 AWG
400 (1) 750 kcmil–1/0 or (2) 300 kcmil–1/0
(1) 750 kcmil–1/0 or (2) 300 kcmil–1/0
(1) 750 kcmil–1/0 or (2) 300 kcmil–1/0
(2x) (2) 1/0–300 kcmil or (1) 1/0–750 kcmil and (3) 6 AWG–250 kcmil
(2) 250 kcmil–6 AWG (1) 750 kcmil–1/0 or (2) 300 kcmil–1/0
600 (4) 750 kcmil–1/0 (4) 750 kcmil–1/0 (4) 750 kcmil–1/0 2x) (4) 1/0–750 kcmil and (3) 6 AWG–250 kcmil
(2) 250 kcmil–6 AWG (4) 750 kcmil–1/0
800 (4) 750 kcmil–1/0 (4) 750 kcmil–1/0 (4) 750 kcmil–1/0 (2x) (4) 1/0–750 kcmil and (3) 6 AWG–250 kcmil
(2) 250 kcmil–6 AWG (4) 750 kcmil–1/0
1200 (4) 750 kcmil–1/0 (4) 750 kcmil–1/0 (4) 750 kcmil–1/0 (2x) (4) 1/0–750 kcmil and (3) 6 AWG–250 kcmil
(2) 250 kcmil–6 AWG —
Table 6. Generator switch standard receptacles and corresponding connection plugs
Switch ampacity
Connector color
Cam-Lok connectors Posi-Lok connectors
Receptacle a Plug b Receptacle panel Plug c
240 Vac
100, 200 Ground (green)Neutral (white)A phase (black)B phase (red)C phase (blue)
E1016-1635SE1016-1636SE1016-1600SE1016-1602SE1016-1612S
E-Z1016-8366E-Z1016-8367E-Z1016-8387E-Z1016-8389E-Z1016-8393
Two-pole, three-wire with Solid Neutral or three-pole, three-wire with Switched Neutral Pole (two-phase and one Neutral Pole): E0200-1672/ three-pole, three-wire (no Neutral): E0200-1661-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): E0200-1662
E0200-281E0200-282E0200-283E0200-284E0200-285
400 Ground (green)Neutral (white)A phase (black)B phase (red)C phase (blue)
E1016-1635SE1016-1636SE1016-1600SE1016-1602SE1016-1612S
E-Z1016-8366E-Z1016-8367E-Z1016-8387E-Z1016-8389E-Z1016-8393
Two-pole, three-wire with Solid Neutral or three-pole, three-wire with Switched Neutral Pole (two-phase and one Neutral Pole): E0400-1672/ three-pole, three-wire (no Neutral): E0400-1661-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): E0400-1662
E0400-281E0400-282E0400-283E0400-284E0400-285
600, 800 Ground (green)Neutral (white)A phase (black)B phase (red)C phase (blue)
(2) E1016-1635S(2) E1016-1636S(2) E1016-1600S(2) E1016-1602S(2) E1016-1612S
(2) E-Z1016-8366(2) E-Z1016-8367(2) E-Z1016-8387(2) E-Z1016-8389(2) E-Z1016-8393
Two-pole, three-wire with Solid Neutral or three-pole, three-wire with Switched Neutral Pole (two-phase and one Neutral Pole): (2) E0400-1672/ three-pole, three-wire (no Neutral): (2) E0400-1661-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): (2) E0400-1662
(2) E0400-281(2) E0400-282(2) E0400-283(2) E0400-284(2) E0400-285
1200 Ground (green)Neutral (white)A phase (black)B phase (red)C phase (blue)
(3) E1016-1635S(3) E1016-1636S(3) E1016-1600S(3) E1016-1602S(3) E1016-1612S
(3) E-Z1016-8366(3) E-Z1016-8367(3) E-Z1016-8387(3) E-Z1016-8389(3) E-Z1016-8393
Two-pole, three-wire with Solid Neutral or three-pole, three-wire with Switched Neutral Pole (two-phase and one Neutral Pole): (3) E0400-1672/ three-pole, three-wire (no Neutral): (3) E0400-1661-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): (3) E0400-1662
(3) E0400-281(3) E0400-282(3) E0400-283(3) E0400-284(3) E0400-285
600 Vac d
100, 200 Ground (green)Neutral (white)A phase (brown)B phase (orange)C phase (yellow)
E1016-1635SE1016-1636SE1016-1619SE1016-1603SE1016-1601S
E-Z1016-8366E-Z1016-8367E-Z1016-8394E-Z1016-8390E-Z1016-8388
Three-pole, three-wire (no Neutral): E0200-1891-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): E0200-1891
E0200-281E0200-282E0200-288E0200-289E0200-286
400 Ground (green)Neutral (white)A phase (brown)B phase (orange)C phase (yellow)
E1016-1635SE1016-1636SE1016-1619SE1016-1603SE1016-1601S
E-Z1016-8366E-Z1016-8367E-Z1016-8394E-Z1016-8390E-Z1016-8388
Three-pole, three-wire (no Neutral): E0400-1862-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): E0400-1703
E0400-281E0400-282E0400-299E0400-295E0400-292
600, 800 Ground (green)Neutral (white)A phase (brown)B phase (orange)C phase (yellow)
(2) E1016-1635S(2) E1016-1636S(2) E1016-1619S(2) E1016-1603S(2) E1016-1601S
(2) E-Z1016-8366(2) E-Z1016-8367(2) E-Z1016-8394(2) E-Z1016-8390(2) E-Z1016-8388
Three-pole, three-wire (no Neutral): (2) E0400-1862-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): (2) E0400-1703
(2) E0400-281(2) E0400-282(2) E0400-299(2) E0400-295(2) E0400-292
1200 Ground (green)Neutral (white)A phase (brown)B phase (orange)C phase (yellow)
(3) E1016-1635S(3) E1016-1636S(3) E1016-1619S(3) E1016-1603S(3) E1016-1601S
(3) E-Z1016-8366(3) E-Z1016-8367(3) E-Z1016-8394(3) E-Z1016-8390(3) E-Z1016-8388
Three-pole, three-wire (no Neutral): (3) E0400-1862-NN/ three-pole, four-wire with Solid Neutral or four-pole, four-wire with Solid Neutral or four-pole, four-wire with Switched Neutral Pole (three-phase and one Neutral Pole): (3) E0400-1703
(3) E0400-281(3) E0400-282(3) E0400-299(3) E0400-295(3) E0400-292
aFor non-standard receptacle options, please contact the Flex Center at 888-329-9272.bE/E-Z 1016 type plugs listed in above table accept 2/0–4/0 size cable.cE0200 type plugs listed in above table accept #2–2/0 size cable. E0400 type plugs listed accept 3/0–4/0 size cable.dFor Canadian switches, 600 Vac products have the same color configurations as the 240 Vac versions (green, white, black, red, blue).
10
Technical Data TD008008ENEffective September 2020
Quick connect heavy-duty safety switches
EATON www.eaton.com
Quick connect double-throw
Table 7. Fuse class provision
Ampere rating Standard
Short circuit rating (amperes)
Optional
Short circuit rating (amperes)Non-fusible
Short circuit rating (amperes) a
240 Vac 480 Vac 600 Vac 240 Vac 480 Vac 600 Vac 240 Vac 480 Vac 600 Vac
100 H 10,000 10,000 10,000 R 200,000 200,000 200,000 N/A 10,000 10,000 10,000200 H 10,000 10,000 10,000 R 200,000 200,000 200,000 N/A 10,000 10,000 10,000400 T 100,000 100,000 100,000 — — — — N/A 10,000 10,000 10,000600 T 100,000 100,000 100,000 J, R 100,000 100,000 100,000 N/A 10,000 10,000 10,000800 T 100,000 200,000 200,000 — — — — N/A 10,000 10,000 10,0001200 L 200,000 200,000 200,000 — — — — N/A 10,000 10,000 10,000
aNon-fusible values shown are the minimum. Higher ratings may be achieved based on combination rating with upstream device (see TD00801005E).
Table 8. Fuse adapter kits
Ampere rating
Class R Class J Class T
240 Vac 600 Vac 240 Vac 600 Vac 240 Vac 600 Vac
100 DS36FK a DS36FK a b b — —200 DS46FK a DS46FK a b b DS426TK a DS466TK b
400 — — b b DS526TK c DS566TK c
600 — — DS600JK c DS600JK c DS626TK c DS666TK c
800 — — — — DS726TK c DS766TK c
1200 — — — — N/A d N/A d
aOrder one kit for three-pole.bNo kit required—simply adjust fuse base to proper fuse spacing.cOrder one kit for each pole.dCurrently not available. Contact the factory for updated information.
Quick connect single-throw
Table 9. Fuse class provision
Ampere rating Standard
Short circuit rating (amperes)
Optional
Short circuit rating (amperes)Non-fusible
Short circuit rating (amperes) a
240 Vac 480 Vac 600 Vac 240 Vac 480 Vac 600 Vac 240 Vac 480 Vac 600 Vac
100 H 10,000 10,000 10,000 R 200,000 200,000 200,000 N/A 10,000 10,000 10,000200 H 10,000 10,000 10,000 R 200,000 200,000 200,000 N/A 10,000 10,000 10,000400 H 10,000 10,000 10,000 R 200,000 200,000 200,000 N/A 10,000 10,000 10,000600 H 10,000 10,000 10,000 J, T, R 100,000 200,000 200,000 N/A 10,000 10,000 10,000800 L 200,000 200,000 200,000 T 100,000 200,000 200,000 N/A 10,000 10,000 10,0001200 L 200,000 200,000 200,000 T 100,000 200,000 200,000 N/A 10,000 10,000 10,000
aNon-fusible values shown are the minimum. Higher ratings may be achieved based on combination rating with upstream device (see TD00801005E).
Table 10. Fuse adapter kits
Ampere Rating
Class R Class J Class T
240 Vac 600 Vac 240 Vac 600 Vac 240 Vac 600 Vac
100 DS36FK a DS36FK a b b — —200 DS46FK a DS46FK a b b DS426TK a DS466TK b
400 DS56FK a DS56FK a b b DS526TK c DS566TK c
600 DS66FK a DS66FK a DS600JK c DS600JK c DS626TK c DS666TK c
800 — — — — DS726TK c DS766TK c
1200 — — — — N/A d N/A d
aOrder one kit for three-pole.bNo kit required—simply adjust fuse base to proper fuse spacing.cOrder one kit for each pole.dCurrently not available. Contact the factory for updated information.
11
Technical Data TD008008ENEffective September 2020
Quick connect heavy-duty safety switches
EATON www.eaton.com
Eaton1000 Eaton BoulevardCleveland, OH 44122United StatesEaton.com
© 2020 EatonAll Rights ReservedPrinted in USAPublication No. TD008008EN / Z24278September 2020
Eaton is a registered trademark.
All other trademarks are property of their respective owners.
Quick connect heavy-duty safety switches
Technical Data TD008008ENEffective September 2020