PVC, CPVC, PP & SS - Amazon S3 · PVC-DWV - ANSI/ASTM D2665 CPVC Schedule 40 - ANSI/ASTM F441 1.2.2...

42
2010-6 Prestige Vent Supl. This document is intended to be used by a qualified heating contractor or service technician. Read all instructions within this document and within the PRESTIGE Boiler Installation and Maintenance Manual, before proceeding with the installa- tion. It is recommended to follow the procedures in the steps given, skipping or missing procedural steps could result in severe personal injury, death or sub- stantial property damage. The installation must conform to the requirements of the authority having juris- diction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1/ NFPA 54, and/or Natural Gas and Propane Installation Code, CAN/CSA B149.1. Revised Date: 9/25/15 L I S T E D WARNING NOTICE PVC, CPVC, PP & SS Vent Supplement

Transcript of PVC, CPVC, PP & SS - Amazon S3 · PVC-DWV - ANSI/ASTM D2665 CPVC Schedule 40 - ANSI/ASTM F441 1.2.2...

  • 2010-6 Prestige Vent Supl.

    This document is intended to be used by a qualified heating contractor or servicetechnician. Read all instructions within this document and within the PRESTIGEBoiler Installation and Maintenance Manual, before proceeding with the installa-tion. It is recommended to follow the procedures in the steps given, skipping ormissing procedural steps could result in severe personal injury, death or sub-stantial property damage.

    The installation must conform to the requirements of the authority having juris-diction or, in the absence of such requirements, to the National Fuel Gas Code,ANSI Z223.1/ NFPA 54, and/or Natural Gas and Propane Installation Code,CAN/CSA B149.1.

    Revised Date: 9/25/15

    L I S T E D

    WARNING

    NOTICE

    PVC, CPVC, PP & SS Vent Supplement

  • Table of Contents

    i

    PRODUCT AND SAFETY INFORMATION

    Definitions ................................................................................................................1Installer Information .................................................................................................1Homeowner Information...........................................................................................1

    SECTION I - PRE-INSTALLATION REQUIREMENTS

    1.1 Removal of an Existing Boiler from a Common Vent System .......................21.2 Vent/Combustion Air Piping and Materials.....................................................3

    1.2.1 PVCand CPVC Vent and Combustion Air Piping and Fittings......31.2.2 PVCand CPVC Pipe Cement and Primer.....................................31.2.3 AL29-4C Stainless Steel Vent Piping and Fittings ......................41.2.4 Polypropylene (PP) Vent Piping and Fittings.................................4

    1.3 Vent/Combustion Air Equivalent Lengths.......................................................101.4 Vent Restrictions ............................................................................................10

    1.4.1 2 Inch Vent Systems Restrictions for thePRESTIGE Solo 80, 110 &Excellence 110...........................10

    1.4.2 3 Inch Vent Systems Restrictions ..................................................101.4.3 Rigid Polypropylene Vent System Restrictions..............................111.4.4 Flex Polypropylene Vent System Restrictions ...............................11

    1.5 Combustion Air Contamination.......................................................................12

    SECTION II - DIRECT VENT INSTALLATION OF VENT/AIR PIPING

    2.1 Direct Vent - Vertical - Through the Roof or Unused Chimney......................132.1.1 Determine Termination Location ....................................................132.1.2 Direct Vent - Vent Installation - Through the Roof .........................142.1.3 Termination Fittings - Through the Roof ........................................152.1.4 Direct Vent - Multiple Boiler Installation - Through the Roof..........15

    2.2 Direct Vent - Horizontal - Sidewall .................................................................172.2.1 Determine Termination Location ....................................................172.2.2 Direct Vent - Vent Installation - Sidewall........................................182.2.3 Termination Fittings -Sidewall .......................................................182.2.4 Direct Vent - Multiple Boiler Installation - Sidewall ........................20

    2.3 Direct Vent - Vertical Vent and Sidewall Combustion Air ...............................222.3.1 Determine Termination Location ....................................................222.3.2 Direct Vent - Vent Installation - Through the Roof .........................232.3.3 Direct Vent - Combustion Air Installation - Sidewall .....................232.3.4 Termination Fittings - Vertical &Sidewall.......................................242.3.5 Direct Vent - Multiple Boiler Installation -

    Vertical Vent and Sidewall Combustion Air............................24

    SECTION III - CATEGORY IV (INDOOR AIR) INSTALLATION OF VENT/AIR PIPING

    3.1 Category IV - Vertical - Through the Roof or Unused Chimney ....................253.1.1 Determine Termination Location ....................................................253.1.2 Category IV - Vent Installation - Through the Roof........................263.1.3 Termination Fittings - Sidewall .......................................................263.1.4 Category IV - Multiple Boiler Installation - Through the Roof ........27

    3.2 Category IV - Horizontal - Sidewall ................................................................273.2.1 Determine Termination Location ....................................................273.2.2 Category IV - Vent Installation - Sidewall ......................................293.2.3 Termination Fittings - Sidewall .......................................................293.2.4 Category IV - Multiple Boiler Installation - Sidewall .......................29

  • Table of Contents

    ii

    SECTION IV - INSTALLATION REQUIREMENT

    4.1 Vent/Combustion Air Transitions ....................................................................304.1.1 3 To 2 (60 mm) Vent/Combustion Air Transition..........................304.1.2 3 To 4 (100 mm) Vent/Combustion Air Transition........................31

    4.2 Insert Piping to PRESTIGE Adapters.............................................................314.3 Vent and Combustion Air Piping Installation Guidelines ................................32

    4.3.1 PVC/CPVC Vent System ...............................................................324.3.2 Polypropylene or Stainless Steel Vent Systems............................32

    SECTION V - MANIFOLD COMBUSTION AIR

    5.1 Manifold Combustion Air Option for Multiple Prestige Boilers .......................335.2 Equivalent Length of Combustion Air Manifold ..............................................335.3 Horizontal Termination....................................................................................345.4 InstallationGuidelines ....................................................................................345.5 Transition Boiler Air Piping to Manifold Guidelines ........................................35

    SECTION VI - COMMONWEALTH OF MASSACHUSETTS

    6.1 Installations with the Direct Vent Termination ElevationAt or Below 4 feet of Grade ...................................................36

    6.2 Installations with the Direct Vent Termination ElevationAbove 4 feet of Grade ...........................................................37

  • 1

    Product and Safety Information

    INSTALLER

    Read all instructions as outlined in this manual andin the boiler installation manual. Failure to complywith these instructions in the order presented couldresult in personal injury or death.

    This document is a supplement to the PRESTIGE boil-er installation and maintenance manual. The purposeof this supplement is for the proper installation of thevent and combustion air piping to the boiler.

    All PRESTIGE vent and combustion air piping mustbe installed, terminated and joints sealed as out-lined in this manual. Failure to comply with instal-lation procedures outlined in this manual can resultin severe personal injury, death or substantial prop-erty damage.

    This vent supplement outlines Direct Vent andCategory IV (Indoor Air) installations using PVC,CPVC, PP and SS materials, for other ventingoptions (materials, terminations, etc.) contact ACV-Triangle Tube.

    WARNING

    WARNING

    NOTICE

    The following terms are used throughout this manual tobring attention to the presence of potential hazards or toimportant information concerning the product.

    Indicates the presence of a hazardous situationwhich, if ignored, will result in death, serious injuryor substantial property damage.

    Indicates a potentially hazardous situation which, ifignored, can result in death, serious injury or sub-stantial property damage.

    Indicates a potentially hazardous situation which, ifignored, may result in minor injury or substantialproperty damage.

    Indicates special instructions on installation, opera-tion or maintenance, which are important to the equip-ment but not related to personal injury hazards.

    Indicates recommendations made by ACV-TriangleTube for the installers which will help to ensure opti-mum operation and longevity of the equipment.

    DANGER

    WARNING

    NOTICE

    CAUTION

    BEST PRACTICE

    DEFINITIONS

    ACV-Triangle Tube reserves the right to modify the technical specifications and components of its prod-ucts without prior notice.

    NOTICE

    HOMEOWNER This manual is intended for use by a qualified heat-

    ing contractor or service technician. Please reference the User Information manual for

    additional information.

    Ensure this document and all pertaining documentsare kept near the boiler to be used by the qualifiedheating contractor or service technician for future ref-erence.

  • 2

    1.0 Pre-Installation Requirements

    SECTION I - PRE-INSTALLATIONREQUIREMENTS

    1.1 Removal of an Existing Boiler from aCommon Vent System

    Do not install the PRESTIGE into a common ventwith any other gas or oil appliances. This will causeflue gas spillage or appliance malfunction, resultingin possible severe personal injury, death or sub-stantial property damage.

    When an existing boiler is removed from a commonventing system, the common venting system is likely tobe too large for proper venting of the remaining appli-ances. At the time of removal of an existing boiler, thefollowing steps shall be followed with each applianceremaining connected to the common venting systemplaced in operation, while the other appliances remain-ing connected to the common venting system are not inoperation.

    1. Seal any unused openings in the common ventingsystem.

    2. Visually inspect the venting system for proper sizeand horizontal pitch and determine there is noblockage or restriction, leakage, corrosion and otherdeficiencies which could cause an unsafe condition.

    3. Insofar as is practical close all building doors andwindows and all doors between the space in whichthe appliances remaining connected to the commonventing system are located and other spaces of thebuilding. Turn on clothes dryers and any appliancenot connected to the common venting system. Turnon any exhaust fans, such as range hoods andbathroom exhausts, so they will operate at maxi-mum speed. Do not operate a summer exhaust fan.Close fireplace dampers.

    DANGER

    4. Place in operation the appliance being inspected.Follow the lighting instructions. Adjust thermostat soappliance will operate continuously.

    5. Test for spillage at the draft hood relief opening after5 minutes of main burner operation. Use the flameof a match or candle, or smoke from a cigarette,cigar or pipe.

    6. After it has been determined that each applianceremaining connected to the common venting systemproperly vents when tested as outlined above,return doors, windows, exhaust fans, fireplacedampers and any other gas-burning appliance totheir previous condition of use.

    7. Any improper operation of the common venting sys-tem should be corrected so the installation conformswith the National Fuel Gas Code, ANSIZ223.1/NFPA 54 and/or CAN/CSA B149.1 ,Installation Codes. When resizing any portion of thecommon venting system, the common venting sys-tem should be resized to approach the minimumsize as determined using the appropriate tables inPart 11 of the National Fuel Gas Code, ANSIZ223.1/NFPA 54 and/or CAN/CSA B149.1,Installation Codes.

  • 3

    1.0 Pre-Installation Requirements

    1.2 Vent/Combustion Air Piping andMaterials

    The installation must conform to the requirements ofthe authority having jurisdiction or, in the absence ofsuch requirements, to the National Fuel Gas Code,ANSI Z223.1/ NFPA 54, and/or Natural Gas andPropane Installation Code, CAN/CSA B149.1.

    The Prestige is certified per ANSI Z21.13 as a CategoryIV (indoor air) or Direct Vent (sealed combustion) appli-ance. A Category IV appliance utilizes uncontaminatedindoor or outdoor air (surrounding the appliance) forcombustion. A Direct Vent appliance utilizes uncontami-nated outdoor air (piped directly to the appliance) forcombustion.

    To reduce the potential risks associated with indoorcontaminates (listed on page 12), flammable vaporsand tight housing construction (little or no infiltra-tion air), it is recommended to pipe uncontaminatedcombustion air directly from the outdoors to theappliance.This practice also promotes higher sys-tem efficiency by reducing heated indoor air frombeing exhausted from the building and replaced bycold infiltration air.

    The Prestige requires a Category IV venting system whichis designed for pressurized venting and condensate.

    The vent and combustion air materials (piping, fit-tings and cement) must meet the listed require-ments in this manual. Failure to comply with thesematerial requirements could result in severe per-sonal injury, death or substantial property damage.

    NOTICE

    BEST PRACTICE

    WARNING

    1.2.1 PVC and CPVC Vent and Combustion AirPiping and Fittings

    PVC Schedule 40 - ANSI/ASTM D1785PVC-DWV - ANSI/ASTM D2665CPVC Schedule 40 - ANSI/ASTM F441

    1.2.2 PVC and CPVC Pipe Cement and PrimerPVC - ANSI/ASTM D2564CPVC - ANSI/ASTM F493

    For installations in Canada, all piping, fittings andcement/primer material must be certified and listedto ULC-S636. Ipex Inc. is an approved manufacturerof ULC S636 vent components.

    Use of cellular core PVC (ASTM F891) cellular coreCPVC, or Radel (polyphenolsulfone) in ventingsystems is prohibited. Cellular core pipe may beused for combustion air piping.

    DO NOT mix a PVC/CPVC vent system & componentswith other vent system materials & components. Sealall PVC andCPVC pipe and fittings with the appropri-ate primer and cement. Failure to comply with thisrequirement could cause the venting system to failresulting in leakage of flue products into the livingspace.

    NOTICE

    NOTICE

    WARNING

  • 4

    1.0 Pre-Installation Requirements

    1.2.3 AL29-4C Stainless Steel Vent Piping andFittings

    The following is a list of approved vent manufacturersand vent systems:

    - Heat-Fab - ProTech Systems - Z-FLEX U.S. Inc.

    Reference Table 1 for a listing of approved stainlesssteel vent adapters and terminations.

    A specific vent adapter is required to transition fromthe boiler vent outlet adapter to specific stainless steelvent system. Contact the appropriate AL29-4C ventmanufacturer for transition adapter information.

    The stainless steel AL29-4C vent system must beinstalled per the vent manufacturer instructions.Contact the vent manufacturer for appropriate ventadapters, materials, terminations, clearance andinstallation instructions.

    When using stainless steel for the vent system, PVCor CPVC pipe meeting the listed requirements in thismanual may be utilized for the combustion air piping.

    NOTICE

    NOTICE

    NOTICE

    1.2.4 Polypropylene (PP) Vent Piping and Fittings

    The following is a list of approved vent manufacturersand vent systems:

    - Centrotherm Eco Systems, LLC- Muelink and Grol B.V./Dura Vent- Z-Flex U.S. Inc.- ECCO Manufacturing

    Reference Table 2 through 7 pages 5 through 9 for a list-ing of approved polypropylene vent adapters, termina-tions and supports.

    A specific vent adapter may be required to transi-tion from the boiler vent outlet adapter to the spe-cific polypropylene vent system. Contact theappropriate PP vent manufacturer for transitionadapter information.

    When using Polypropylene for the vent system, PVCor CPVC pipe meeting the listed requirements in thismanual may be utilized for the combustion air piping.

    NOTICE

    NOTICE

    TABLE 1

    Description

    Approved Stainless Steel Vent Adapters and TerminationsHeatfab

    (SelKirk Corp.)Saf-T Vent, EZ Seal or

    Saf-T Vent SC

    ProTech Systems(M&G/DuraVent)

    FasNSealor FasNSeal CVS

    Z-Flex U.S. Inc.Z-Vent

    3" Vent Adapter 9301PVC FSA-ULT3 2SVSTTA033" Roof & Side Wall Straight Termination 9392 300186 2SVSTPF033" Side Wall & 45 Elbow Termination 9311TERM 300130 & 300186 2SVSTEX03453" Side Wall Tee Termination 9390TEE 300311 2SVSTTF033" to 4" Vent Adapter 9401PVC3 FSA-ULT3* 2SVSTTA044" Vent Adapter 9401PVC FSA-ULT4 SVSTTA04.54" Roof & Side Wall Straight Termination 9492 300187 2SVSTPF044" Side Wall & 45 Elbow Termination 9411TERM 300131 & 300187 2SVSTEX04454" Side Wall Tee Termination 9490TEE 300312 2SVSTTF04

  • 1.0 Pre-Installation Requirements

    5

    TABL

    E 2

    Descr

    iption

    Approved 2

    (60 m

    m) Rigid P

    olypropyle

    ne Vent A

    dapters, Term

    inations an

    d Supports

    Centrotherm Eco S

    ystem

    s,LL

    CMuelink a

    nd Grol B

    .V./Dura

    Vent

    Z-Flex U.S. In

    c.EC

    CO M

    anufacturin

    g

    3" (8

    0 mm)

    App

    lianc

    e Ven

    t Ada

    pter

    ISAA

    L030

    3 3P

    PS-03

    PVCM

    -3PPF

    2ZDC

    PVCG

    33P

    PSAD

    3 (8

    0 mm)

    to 2

    (60 m

    m) R

    educ

    er IS

    RD03

    02

    3PPS

    -R2

    2ZDR

    3230

    2PRE

    D

    2" (6

    0 mm)

    Roo

    f Term

    inatio

    n - U

    V Re

    sistan

    tIS

    EP02

    (20"

    or 51

    cm) o

    rIS

    EP02

    39

    (39" o

    r 99c

    m)

    2PPS

    -12B

    (12" o

    r 30c

    m) or

    2PPS

    -36B

    (36" o

    r 91c

    m)

    2ZDP

    210U

    V (10

    " or 2

    5cm)

    or2Z

    DP22

    0UV

    (20" o

    r 50 c

    m)

    24CV

    T (C

    once

    ntric)

    + 22

    024A

    D (S

    W to

    Con

    c.Ad

    apter

    )2"

    (60 m

    m) Si

    de W

    all, 4

    5 E

    lbow

    Term

    inatio

    n - U

    V Re

    sistan

    t IS

    ELL0

    245U

    V 2P

    PS-E

    45B

    2ZDE

    245U

    V24

    5PEL

    B2"

    (60 m

    m) Si

    de W

    all, T

    ee

    Term

    inatio

    n - U

    V Re

    sistan

    t IS

    TT02

    20

    2PPS

    -TB

    2ZDT

    T22P

    PWTK

    (Twi

    n Pipe

    Wall

    Kit)

    2" (6

    0 mm)

    Side

    Wall

    Pipe

    Le

    ngths

    - UV

    Resi

    stant

    ISVL

    022U

    V (26

    .5" or

    67cm

    ) 2P

    PS-12

    B (12

    " or 3

    0cm)

    or2P

    PS-36

    B (36

    " or 9

    1cm)

    2ZDP

    210U

    V (10

    " or 2

    5cm)

    or2Z

    DP22

    0UV

    (20" o

    r 50 c

    m)22

    4PPP

    B (24

    ") or

    212P

    PPB

    (12")

    2" (6

    0 mm)

    Side

    Wall

    , 90

    Elbo

    w -

    UV R

    esista

    nt IS

    ELL0

    287U

    V 2P

    PS-E

    90B

    or 2P

    PS-E

    90EB

    2ZDE

    287U

    V28

    7PEL

    B2"

    (60 m

    m) B

    ird G

    uard

    Scree

    n - U

    V Re

    sistan

    t or E

    nd Sc

    reen

    IASP

    P02

    2PPS

    -BG

    2ZDE

    S22P

    PWG

    2" (6

    0 mm)

    Loc

    king B

    and C

    lamp o

    r Co

    nnec

    tor R

    ing

    IANS

    02

    2PPS

    -LBC

    2ZDL

    C22P

    PLC

    2" (6

    0 mm)

    Wall

    Strap

    or Su

    pport

    Cl

    amp

    IASC

    02

    2PPS

    -WSM

    (galv

    anize

    d) &

    2PPS

    -WSM

    -SS (

    stainl

    essste

    el)2Z

    DFB2

    2PPB

    or 24

    PCB

    (for c

    once

    n-tri

    c term

    inatio

    n)

    2" (6

    0mm)

    Wall

    Plate

    IA

    WP0

    2B (b

    lack)

    22" (

    60mm

    )PPS

    -WPB

    (blac

    k)2Z

    DWPB

    224

    CWTP

    or 24

    CWP (

    white

    )

  • 1.0 Pre-Installation Requirements

    6

    TABL

    E 3

    Descr

    iption

    Approved 3

    (80 m

    m) Rigid P

    olypropyle

    ne Vent A

    dapters, Term

    inations an

    d Supports

    Centrotherm Eco S

    ystem

    s,LL

    CMuelink a

    nd Grol B

    .V./Dura

    Vent

    Z-Flex U.S. In

    c.EC

    O Manufacturin

    g

    3" (8

    0mm)

    App

    lianc

    e Ven

    t Ada

    pter

    ISAA

    L030

    3 3P

    PS-03

    PVCM

    -3PPF

    2ZDC

    PVCG

    33P

    PSAD

    3" (8

    0mm)

    Roo

    f Term

    inatio

    n - U

    V Re

    sistan

    tIS

    EP03

    (20"

    or 51

    cm) o

    rIS

    EP03

    39

    (39" o

    r 99c

    m)3P

    PS-12

    B (12

    " or 3

    0cm)

    or

    3PPS

    -36B

    (36" o

    r 91c

    m)2Z

    DP31

    0UV

    (10 o

    r 25c

    m) or

    2Z

    DP32

    0UV

    (20 o

    r 50c

    m)35

    CVT

    (Con

    centr

    ic) &

    33

    035A

    D (S

    W to

    Con

    c.Ad

    apter

    )3"

    (80m

    m) Si

    de W

    all, 4

    5 E

    lbow

    Term

    inatio

    n - U

    V Re

    sistan

    t IS

    ELL0

    345U

    V 3P

    PS-E

    45B

    2ZDE

    345U

    V34

    5PEL

    B3"

    (80m

    m) Si

    de W

    all, T

    ee Te

    rmina

    tion

    - UV

    Resis

    tant

    ISTT

    0320

    3P

    PS-T

    B2Z

    DTT3

    3PPW

    TK (T

    win P

    ipe W

    all K

    it)

    3" (8

    0mm)

    Side

    Wall

    Pipe

    Len

    gths -

    UV R

    esista

    nt IS

    VL03

    2UV

    (26.5"

    or 67

    cm)

    3PPS

    -12B

    (12" o

    r 30c

    m) or

    3PPS

    -36B

    (36" o

    r 91c

    m)2Z

    DP31

    0UV

    (10 o

    r 25c

    m) or

    2ZDP

    320U

    V (20

    or 5

    0cm)

    324P

    PPB

    (24")

    or 31

    2PPP

    B (12

    ")

    3" (8

    0mm)

    Side

    Wall

    , 90

    Elbo

    w -

    UV R

    esista

    nt IS

    ELL0

    387U

    V 3P

    PS-E

    90B

    or 3P

    PS-E

    90EB

    2ZDE

    387U

    V38

    7PEL

    B3"

    (80m

    m) B

    ird G

    uard

    Scree

    n -

    UV R

    esista

    nt or

    End S

    creen

    IASP

    P03

    3PPS

    -BG

    2ZDE

    S33P

    PWG

    3" (8

    0mm)

    Loc

    king B

    and C

    lamp o

    r Co

    nnec

    tor R

    ing

    IANS

    03

    3PPS

    -LBC

    2ZDL

    C33P

    PLC

    3" (8

    0mm)

    Wall

    Strap

    or Su

    pport

    Cl

    amp

    IASC

    03

    3PPS

    -WSM

    (galv

    anize

    d) &

    3PPS

    -WSM

    -SS (

    stainl

    essste

    el)2Z

    DFB3

    3PPB

    or 5P

    PB (f

    or co

    ncen

    tric

    termi

    natio

    n)

    3" (8

    0mm)

    Wall

    Plate

    IA

    WP0

    3B (b

    lack)

    orIA

    WP0

    3W (w

    hite)

    3PPS

    -WPB

    (blac

    k)2Z

    DWPB

    335

    CWTP

    or 35

    CWP (

    white

    )

  • 1.0 Pre-Installation Requirements

    7

    TABL

    E 4

    Descr

    iption

    Approved 4

    (100 mm)

    Rigid P

    olypropyle

    ne Vent A

    dapters, Term

    inations an

    d Supports

    Centrotherm Eco S

    ystem

    s,LL

    CMuelink a

    nd Grol B

    .V./Dura

    Vent

    Z-Flex U.S. In

    c.EC

    CO M

    anufacturin

    g

    3" (8

    0mm)

    App

    lianc

    e Ven

    t Ada

    pter

    ISAA

    L030

    3 3P

    PS-03

    PVCM

    -3PPF

    2ZDC

    PVCG

    33P

    PSAD

    3" (8

    0mm)

    to 4"

    (100

    mm) I

    ncrea

    serIS

    IA03

    04 or

    ISEI

    0304

    3PPS

    -X4

    2ZDI

    34

    304P

    INC

    4" (1

    10mm

    *) Ap

    plian

    ce V

    ent A

    dapte

    r IS

    AAL0

    404

    4PPS

    -04PV

    CM-4P

    PF2Z

    DCPV

    CG4

    4PPS

    AD

    4" (1

    10mm

    *) Ro

    of Te

    rmina

    tion -

    UV

    Resis

    tant

    ISEP

    04 (2

    0" or

    51cm

    ) or

    ISEP

    0439

    (39

    " or 9

    9cm)

    4PPS

    -12B

    (12" o

    r 30c

    m) or

    4P

    PS-36

    B (36

    " or 9

    1cm)

    2ZDP

    410 (

    10 o

    r 25c

    m),

    2ZDP

    420 (

    20 o

    r 50c

    m) or

    2Z

    DP44

    0 (40

    or 1

    00cm

    )

    46CV

    T (C

    once

    ntric)

    +44

    046A

    D (S

    W to

    Con

    c.Ad

    apter

    )4"

    (110

    mm*)

    Side W

    all, 4

    5 E

    lbow

    Term

    inatio

    n - U

    V Re

    sistan

    tIS

    ELL0

    445U

    V4P

    PS-E

    45B

    2ZDE

    445U

    V44

    5PEL

    4" (1

    10mm

    *) Sid

    e Wall

    , Tee

    Te

    rmina

    tion -

    UV

    Resis

    tant

    ISTT

    0420

    4PPS

    -TB

    2ZDT

    T446

    CWT

    (conc

    entri

    c) +

    4404

    6AD

    (SW

    to C

    onc.

    Adap

    ter)

    4" (1

    10mm

    *) Sid

    e Wall

    Pipe

    Len

    gths

    - UV

    Resis

    tant

    ISVL

    042U

    V (26

    .5" or

    67cm

    )4P

    PS-12

    B (12

    " or 3

    0cm)

    or4P

    PS-36

    B (36

    " or 9

    1cm)

    2ZDP

    410 (

    10 o

    r 25c

    m),

    2ZDP

    420 (

    20 o

    r 50c

    m) or

    2Z

    DP44

    0 (40

    or 1

    00cm

    )41

    2PPP

    (12"

    ) or 4

    24PP

    P(24

    ")

    4" (1

    10mm

    *) Sid

    e Wall

    , 90

    Elbo

    w -

    UV R

    esista

    nt IS

    ELL0

    487U

    V4P

    PS-E

    90B

    or 4P

    PS-E

    90EB

    2ZDE

    487U

    V48

    7PEL

    4" (1

    10mm

    *) Bi

    rd Gu

    ard Sc

    reen -

    UV R

    esista

    nt or

    End S

    creen

    IASP

    P04

    4PPS

    -BG

    2ZDE

    S44P

    PWG

    4" (1

    10mm

    *) Lo

    cking

    Ban

    d Clam

    por

    Conn

    ector

    Ring

    IA

    NS04

    4PPS

    -LBC

    2ZDL

    C44P

    PLC

    4" (1

    10mm

    *) W

    all St

    rap or

    Supp

    ortCl

    amp

    IASC

    044P

    PS-W

    SM (g

    alvan

    ized)

    & 4P

    PS-W

    SM-S

    S (sta

    inless

    stee

    l)2Z

    DFB4

    4PPB

    or 6P

    PB (f

    or co

    ncen

    tric

    termi

    natio

    n)

    4" (1

    10mm

    *) W

    all Pl

    ate

    IAW

    P04B

    (blac

    k)4P

    PS-W

    PB (b

    lack)

    2ZDW

    PB4

    46CW

    TP or

    46CW

    P (wh

    ite)

    *100

    mm fo

    r Mue

    link a

    nd G

    rol B

    .V./D

    urave

    nt

  • 8

    1.0 Pre-Installation Requirements

    DescriptionApproved 2 (60 mm) Flex Polypropylene Vent Adapters, Terminations and Supports

    Centrotherm EcoSystems, LLC

    Muelink and GrolB.V./Dura Vent Z-Flex U.S. Inc. ECCO Manufacturing

    3" (80 mm) Appliance VentAdapter ISAAL0303 3PPS-03PVCM-3PPF 2ZDCPVCG3 3PPSAD3 (80 mm) to 2 (60 mm)Reducer ISRD0302 3PPS-R2 2ZDR32 302PRED

    2" (60mm) Wall Plate IAWP02B (black) 2PPS-WPB (black) Included in Flex Base Kit 2ZDFBK2 202FCB or 3302FC

    2" (60mm) Chimney SupportElbow or Base Support or Flex Base Kit

    ISBS0287 2PPS-SE90X 2ZDFBK2 2PPELCS

    2" (60mm) Support Bracket -Bottom of Chimney or Chase

    Included with Base Support

    PPS-SUP or 2PPS-SUP (Chimney)

    Supported by Wall Plate Included in Flex Base Kit2ZDFBK2

    Included with SupportElbow

    2" (60mm) Flex Support Bracket - Top of Chimney or Chase

    N/A 2PPS-FSBIncluded in Flex

    Chimney Liner Kit 2ZD2FLK3

    2PPFFA

    2" (60mm) Spacer IASP02 2PPS-SIncluded in Flex

    Chimney Liner Kit 2ZD2FLK3

    2PPFS

    2" (60mm) Chimney Cap orCover & End Pipe - UV Resistant or Flex Chimney Liner Kit

    ISCP02 & IFEP02 2PPS-FCT 2ZD2FLK2 2PPFK (flex kit)

    TABLE 5

    TABLE 6

    DescriptionApproved 3 (80 mm) Rigid Polypropylene Vent Adapters, Terminations and SupportsCentrotherm EcoSystems, LLC

    Muelink and GrolB.V./Dura Vent Z-Flex U.S. Inc. ECCO Manufacturing

    3" (80mm) Appliance Vent Adapter ISAAL0303 3PPS-03PVCM-3PPF 2ZDCPVCG3 3PPSAD

    3" (80mm) Wall Plate IAWP03B (black) or IAWP03W (white) 3PPS-WPB (black) 2ZDWPB3 303FCB or 3303FC

    3" (80mm) Chimney Support Elbow or Base Support or Flex Base Kit

    ISBS0387 3PPS-SE90X Included in Flex Base Kit 2ZDFBK3 3PPELCS

    3" (80mm) Support Bracket - Bottom of Chimney or Chase h Base Support

    PPS-SUP or 3PPS-SUP(Chimney) 2ZDFBK3

    Included with SupportElbow

    3" (80mm) Flex SupportBracket - Top of Chimney or Chase

    N/A 3PPS-FSBSupported by Wall PlateIncluded in Flex Base

    Kit 2ZDFBK33PPFFA

    3" (80mm) Spacer IASP03 3PPS-SIncluded in Flex

    Chimney Liner Kit 2ZD2FLK3

    3PPFS

    3" (80mm) Chimney Cap or Cover & End Pipe - UV Resistant or Flex Chimney Liner Kit

    ISCP03 & IFEP03 3PPS-FCT 2ZD2FLK3 3PPFK (flex kit)

  • 1.0 Pre-Installation Requirements

    9

    Descr

    iption

    Approved 4

    (100 mm)

    Rigid P

    olypropyle

    ne Vent A

    dapters, Term

    inations an

    d Supports

    Centrotherm Eco S

    ystem

    s,LL

    CMuelink a

    nd Grol B

    .V./Dura

    Vent

    Z-Flex U.S. In

    c.EC

    CO M

    anufacturin

    g

    3" (8

    0mm)

    App

    lianc

    e Ven

    t Ada

    pter

    ISAA

    L030

    3 3P

    PS-03

    PVCM

    -3PPF

    2ZDC

    PVCG

    33P

    PSAD

    3" (8

    0mm)

    to 4"

    (110

    mm) I

    ncrea

    serIS

    IA03

    04 or

    ISEI

    0304

    3PPS

    -X4

    2ZDI

    34

    304P

    INC

    4" (1

    10mm

    *) Ap

    plian

    ce V

    ent A

    dapte

    r IS

    AAL0

    404

    4PPS

    -04PV

    CM-4P

    PF2Z

    DCPV

    CG4

    4PPS

    SAD

    4" (1

    10mm

    *) W

    all Pl

    ate

    IAW

    P04B

    (blac

    k)4P

    PS-W

    PB (b

    lack)

    2ZDW

    PB4

    N/A

    4" (1

    10mm

    *) Ch

    imne

    y Sup

    port

    Elbo

    w or

    Base

    Supp

    ort or

    Flex

    Base

    Kit

    ISBS

    0487

    4P

    PS-S

    E90X

    2ZDF

    BK4

    4PPE

    LCS

    4" (1

    10mm

    *) Su

    pport

    Brac

    ket -

    Botto

    m of

    Chim

    ney o

    r Cha

    se h B

    ase Su

    pport

    PP

    S-SU

    P or 4

    PPS-

    SUP

    (Chim

    ney)

    Includ

    ed in

    Flex

    Base

    Kit

    2ZDF

    BK4

    Includ

    ed w

    ith Su

    pport

    Elbo

    w4P

    PELC

    S4"

    (110

    mm*)

    Flex S

    uppo

    rt Br

    acke

    t -

    Top o

    f Chim

    ney o

    r Cha

    se N/

    A 4P

    PS-F

    SBInc

    luded

    in Fl

    ex C

    himne

    yLi

    ner K

    it 2ZD

    2FLK

    44P

    PFFA

    4" (1

    10mm

    *) Sp

    acer

    IASP

    04

    4PPS

    -SInc

    luded

    in Fl

    ex C

    himne

    yLi

    ner K

    it 2ZD

    2FLK

    44P

    PFS

    4" (1

    10mm

    *) Ch

    imne

    y Cap

    or C

    over

    & En

    d Pipe

    - UV

    Resi

    stant

    or Fle

    x Ch

    imne

    y Line

    r Kit

    ISCP

    04 &

    IFEP

    04

    4PPS

    -FCT

    2ZD2

    FLK4

    4PPF

    K (fl

    ex ki

    t)

    TABL

    E 7

    *100

    mm fo

    r Mue

    link a

    nd G

    rol B

    .V./D

    urave

    nt

  • 1.0 Pre-Installation Requirements

    10

    1.3 Vent/Combustion Air Equivalent Lengths- For all venting applications, PVC/CPVC, AL29-4C,

    SS or Polypropylene, the maximum allowable lengthshould not exceed those lengths listed in Table 8.

    - For PVC/CPVC or AL29-4C vent systems reduce themaximum allowable length for each elbow as follows:- 3 Feet for every 45 elbow- 5 feet for every 90 elbow

    - For polypropylene vent systems reduce the maxi-mum allowable length for each elbow as follows:- 5 Feet for every 45 elbow- 10 feet for every 90 elbow

    1.4 Vent Restrictions1.4.1 Inch (60 mm) Vent Systems Restrictions forthe PRESTIGE 80 Solo, 110 Solo & Excellence.- Derate the maximum boiler input by 3% when using

    the maximum equivalent length of 2 inch (60 mm)vent piping on Solo 110 & Excellence 110.

    - The 2 inch vent system requires a 1 inch clearanceto combustibles

    - Use long sweep elbow to limit pressure drop and toavoid excessive vent temperatures.

    - In 2 inch PVC vent applications, the first 7 equivalentfeet of the vent system must utilize CPVC material.

    To avoid vent failure the installer must use CPVCvent material for the first 7 equivalent feet of a 2 inchPVC vent system. The installer must also utilizeprimer and glue that is certified for both PVC/CPVCmaterials. Failure to properly install the vent systemcan lead to carbon monoxide posoning or fire due tojoint separtion or pipe breakage.

    1.4.2 3 Inch Vent System Restrictions - Derate the maximum boiler input of the PRESTIGE

    Solo 250 by 3% when using the maximum equiva-lent length of 3 inch (80 mm) vent piping.

    WARNING

    TABLE 8

    Prestige Model

    Maximum Allowable Vent or Combustion Air Piping Length2 Inch [60 mm] Piping

    OR

    3 Inch [80 mm] Piping

    OR

    4 Inch [100 mm] PipingFeet Elbows Feet Elbows Feet Elbows

    Solo 60 55 0 100 0 100 0Solo 80 55 0 100 0 100 0Solo 110 45 0 100 0 100 0Solo 155

    Not Applicable

    100 0 100 0Solo 175 100 0 100 0Solo 250 60 0 80 0Solo 299

    Not Applicable100 0

    Solo 399 100 0Excellence 110 45 0 100 0 100 0

  • 1.0 Pre-Installation Requirements

    11

    1.4.4 Flex Polypropylene Vent SystemRestrictions- 3 Flex venting is limited up to the PRESTIGE Solo

    175.- 2 Flex venting is limited up to the PRESTIGE Solo

    110 & Excellence 110.

    Contact approved polypropylene vent manufacturerfor a copy of their installation instructions. Read,understand and follow all of the vent manufacturersinstructions before beginning the installation.Contact vent manufacturer if you require any techni-cal support. Failure to properly install and supportvent system can lead to carbon monoxide poisoningor fire due to joint separation or pipe breakage.- Approved for vertical installations only, where a

    clean, structurally sound unused chimney or chaseis used as a raceway.

    - Vertical offsets must not exceed 45 and are limitedto a maximum number of 2.

    - Requires rigid polypropylene vent pipe with lockingband clamps or connector rings and wall straps orsupport clamps from the appliance to the entrance ofthe chimney or chase.

    - Maintain 5/8" per foot slope back toward appliance onall horizontal runs of rigid polypropylene vent pipe.

    - The use of a wall plate is required to seal rigidpolypropylene vent pipe at the entrance of the chim-ney or chase to prevent mortar or cement from con-tacting the polypropylene vent pipe.

    - Requires supports (elbow or base, flex chimney andbracket), spacers, chimney cap and end pipe.Consult vent manufacturer for complete list of otherparts required.

    - Any termination piping external to the building mustbe UV resistant.

    - Do not apply insulation directly to vent. Maintainvent manufacturers clearances to combustibles.

    - Flex plastic venting systems shall not pass throughrated fire separations.

    - Prior to assembly of any joints, ensure joint gasket ispresent and properly installed. Contact vent manufac-turer if gasket is missing or damaged. Verify theintegrity of joints upon completion of the vent system.

    WARNING

    1.4.3 Rigid Polypropylene Vent SystemRestrictions

    Contact approved polypropylene vent manufacturerfor a copy of their installation instructions. Read,understand and follow all of the vent manufacturersinstructions before beginning the installation.Contact vent manufacturer if you require any techni-cal support. Failure to properly install and supportvent system can lead to carbon monoxide poisoningor fire due to joint separation or pipe breakage.- Rigid polypropylene vent pipe must be installed with

    locking band clamps or connector rings and sup-ports (wall strap or clamp, elbow or base, etc.).Consult vent manufacturer for complete list of otherparts required.

    - Maintain 5/8" per foot slope back toward applianceon all horizontal runs.

    - The use of a wall plate is required to seal rigidpolypropylene vent pipe at the entrance of the chim-ney or chase to prevent mortar or cement from con-tacting the polypropylene vent pipe.

    - Any termination piping external to the building mustbe UV resistant.

    - Do not apply insulation directly to vent. Maintainvent manufacturers clearances to combustibles.

    - Plastic venting systems shall not pass through ratedfire separations without approved fire stoppinginstalled in accordance with fire stopping manufac-turers instructions.

    - Prior to assembly of any joints, ensure joint gasket ispresent and properly installed. Contact vent manufac-turer if gasket is missing or damaged. Verify theintegrity of joints upon completion of the vent system.

    WARNING

  • 1.0 Pre-Installation Requirements

    12

    1.5 Combustion Air Contamination

    If the PRESTIGE combustion air inlet is located in anarea likely to cause or contain contamination, thecombustion air must be repiped and terminated atanother location. Contaminated combustion air willdamage the unit and its burner system, resulting inpossible severe personal injury, death or substantialproperty damage.

    Do not operate the PRESTIGE if its combustion airinlet is located near a laundry room or pool facility.These areas will always contain hazardous con-taminants.

    Pool and laundry products, common household andhobby products often contain fluorine or chlorinecompounds. When these chemicals pass throughthe burner and vent system, they can form strongacids. These acids will corrode the heat exchanger,burner components and vent system, causing seri-ous damage and presenting possible flue gasspillage or water leakage into the surrounding area.

    Please read the information listed below. If contam-inating chemicals are located near the area of thecombustion air inlet, the installer should pipe thecombustion air inlet to an outside area free of thesechemicals.

    DANGER

    WARNING

    Potential contaminating products- Spray cans containing chloro/fluorocarbons- Permanent Wave Solutions- Chlorinated wax - Chlorine - based swimming pool chemicals /

    cleaners- Calcium Chloride used for thawing ice- Sodium Chloride used for water softening- Refrigerant leaks- Paint or varnish removers- Hydrochloric acid / muriatic acid- Cements and glues- Antistatic fabric softeners used in clothe dryers- Chlorine-type bleaches, detergents, and clean-

    ing solvents found in household laundry rooms- Adhesives used to fasten building products and

    other similar productsAreas likely to contain these products- Dry cleaning / laundry areas and establishments- Beauty salons- Metal fabrication shops- Swimming pools and health spas- Refrigeration Repair shops- Photo processing plants- Auto body shops- Plastic manufacturing plants- Furniture refinishing areas and establishments- New building construction- Remodeling areas- Garages with workshops

  • 2.0 Direct Vent Installation of Vent/Air Piping

    13

    SECTION II - DIRECT VENT INSTALLATIONOF VENT/AIR PIPING

    A Direct Vent appliance utilizes uncontaminated outdoorair (piped directly to the appliance) for combustion.

    2.1 Direct Vent - Vertical - Through the Roofor Unused Chimney

    The installation must conform to the requirements ofthe authority having jurisdiction or, in the absenceof such requirements, to the National Fuel GasCode, ANSI Z223.1/ NFPA 54, and/or Natural Gas andPropane Installation Code, CAN/CSA B149.1.

    When using an inoperative chimney as a means of achase for the vent, the surrounding space within thechimney cannot be used to draw combustion air orvent another appliance.

    A gas vent extending through a roof should not ter-minate near an adjacent wall or below any buildingextensions such as roof eaves, balconies or decks.Failure to comply with the required clearances inthis manual could result in severe personal injury,death or substantial property damage.

    The information and diagrams outlining the fittingsand method of terminating the vent/combustion airare directly related to PVC/CPVC vent systems.When utilizing and AL29-4C or Polypropylene ventsystem there may be some variations. Consult theappropriate vent manufacturer for recommenda-tions and clarifications.

    2.1.1 Determine Termination Location

    Locate the vent and combustion air termination using thefollowing guidelines:1. The total length of the vent or combustion air piping

    must not exceed the limits given in Table 8 on page 10.

    WARNING

    NOTICE

    NOTICE

    NOTICE

    Do not include the two 90 elbows used to terminatethe combustion air inlet exterior of the buildingwhen determining the total length of pipe.2. The combustion air piping must terminate in an

    upside down U shape fashion using two 90elbows as shown in Fig. 1 page 14. The terminationmust be installed 12 [30.5 cm] (18 [45.7 cm]Canada) above the highest anticipated snow level.

    3. The vent must terminate vertically with a coupling toaccept the bird screen and must be located 12 to 24[30.5 cm to 61 cm] above the combustion air inlet asshown in Fig. 1 on page 14.

    4. The vent and combustion air terminations must belocated a radial distance of 12 to 24 [30.5 cm to 61cm] from centerline of vent termination to centerlineof air termination as shown in Fig. 1 on page 14.

    5. The following should be considered when deter-mining the location of the vent and combustion airterminations:a. Locate the vent termination where flue vapors

    will not damage surrounding shrubs, plants orair conditioning equipment or be objectionableto the homeowner.

    b. The flue products will form a noticeable plume ofwater vapor as they condense in colder air.Avoid terminating the vent in areas where theplume could obstruct window views.

    c. Prevailing winds could cause freezing of fluegas condensation and a buildup of water / ice onsurrounding plants, building surfaces or com-bustion air inlet.

    d. Avoid locations where prevailing winds couldaffect the performance of the boiler or causerecirculation of the flue gases, such as insidecorners of buildings, near adjacent buildings,vertical surfaces, window wells, stairwells,alcoves, courtyards, or other recessed areas.

    e. Do not terminate the vent above doors or win-dows: flue condensate could freeze causing iceformations.

    f. Locate the vent termination to prevent possiblecondensate damage to exterior finishes.

    g. Avoid locations of possible accidental contact offlue vapors with people or pets.

    NOTICE

  • 2.0 Direct Vent Installation of Vent/Air Piping

    14

    12" Min. [30.5 cm]

    Radial Distance

    12" [30.5 cm] (18 [ 45.7 cm] Canada)Above the HighestAnticipated Snow Level

    Vent Termination

    [30.

    5 cm

    to 6

    1 cm

    ]12

    " Min.

    - 24

    " Max

    Abov

    e Co

    mbu

    stion

    A

    ir In

    let

    Combustion Air Termination

    Direct Vent - Vertical Termination of Vent and Combustion Air Piping.Fig. 1:

    6. The vent termination must also maintain the follow-ing clearances; as shown in Fig.2.a. At least 3 feet [0.9 m] from adjacent wallsb. At least 3 feet [0.9 m] below roof over hangsc. At least 7 feet [2.1 m] above any public walk-

    waysd. At least 3 feet [0.9 m] above any forced air

    intake within 10 feet [3 m] (does not apply to thecombustion air inlet of a direct vent appliance).

    e. No closer than 12 [30.5 cm] below or horizon-tally from any door or window or gravity air inlet.

    f. Must be at least 4 feet [1.2 m] from any electricmeters, gas meters-regulators, relief valves orother equipment.Never terminate the ventabove or below any of these items within 4 feet[1.2 m] horizontally.

    g. A minimum 12 inches [30.5 cm] horizontal spacingfrom other fan assisted appliance vents such asclothes dryer vent, kitchen exhaust vent etc. Neverterminate the vent above or below any fan assist-ed vent within 12 inches [30.5 cm] horizontally.

    7. Locate the vent and combustion air terminations in amanner to protect from damage by foreign objects,such as stones, balls, or buildup of leaves or sediment.

    8. Do not connect any other appliance to the vent pipeor multiple boilers to a common vent pipe.

    2.1.2 Direct Vent - Vent Installation - Through theRoof1. Vent and Combustion Air Penetration

    - Vent pipe penetration through combustible ornon-combustible wall material should maintain aminimum 1/4 [6 mm] clearance for 3 and 4PVC/CPVC vent or 1 [2.5cm] for 2 PVC/CPVCvents. The diameter of the penetration holeshould be 4 [10.2 cm] minimum for 2 and 3pipe or 5 [12.7 cm] minimum for 4 pipe. Whenusing Polypropylene or Stainless Steel Ventrefer to vent manufactures installation instruc-tions, supplied with the vent for clearances.

    - Combustion air pipe penetration can maintainzero clearance. The diameter of the penetrationhole should be 2-3/8 [6 cm] minimum for 2 pipeor 3-1/2 [8.9 cm] minimum for 3 pipe or 4-1/2[11.4 cm] minimum for 4 pipe.

    2. The installer must use a galvanized metal thimble forthe vent pipe penetration.

    3. Locate the vent and combustion air pipe penetra-tions to provide clearances as described in Fig. 1 onpage 14.

  • 15

    2.1.4 Direct Vent - Multiple Boiler Installation -Through the Roof1. On installations of multiple PRESTIGE boilers, ter-

    minate the vent and combustion air piping asdescribed in this manual.

    2. The roof penetration of the vent and combustion airpiping should be such that the combustion air inlet isa minimum 12 [30.5 cm] from the adjacent vent pipeof the other boiler for installations in the U.S. asshown in Fig. 5 on page 16. For installations inCanada, provide clearances as required byCAN/CSA B149.1.

    The combustion air inlet of the PRESTIGE is definedas being part of a direct vent system. It is not con-sidered as a forced air intake. The required clear-ance of an adjacent boiler vent to a forced air inletdoes not apply in a multiple installation of PRES-TIGE boilers.

    NOTICE

    4. The installer must comply with all local codes for iso-lating the vent and combustion air pipes as theypass through floors, ceilings and roofs.

    5. The installer should provide adequate flashing andsealing boots sized for the vent pipe and combustionair pipe.

    2.1.3 Termination Fittings - Through the Roof1. The vent and combustion air terminations must include

    a factory supplied bird screen installed as shown inFigs. 3 & 4 on page 16.

    2. The combustion air piping must terminate in anupside down U shape fashion using two 90elbows as shown in Fig. 1 on page 14.

    3. The vent piping must terminate vertically with a cou-pling as shown in Fig. 1 on page 14.

    Do not extend the vent pipe above the roof beyondthe dimensions shown in Fig. 1 on page 14.Extended exposure of the vent pipe could causecondensate to freeze and block the vent pipe.

    WARNING

    2.0 Direct Vent Installation of Vent/Air Piping

    Termination Clearances of Direct VentSystem

    Fig. 2:

  • 16

    2.0 Direct Vent Installation of Vent/Air Piping

    Vent Termination

    Bird Screen

    Vertical Vent Bird Screen InstallationFig. 3:

    Installer must install the factory supplied birdscreens on the vent and combustion air termina-tions.

    NOTICE

    Combustion Air

    Termination

    Bird Screen

    Vertical Combustion Air Bird ScreenInstallation with 90 Elbow Termination

    Fig. 4:

    Vent Termination Typ.

    Combustion Air Termination Typ.

    12" [30.5 cm] (18

    [45.7 cm] Canada)

    Above the Highest

    Anticipated Snow L

    evel

    12" Min. [30.5 cm]

    Typ.

    12" Min. [30.5 cm] Radial Distance

    12" Min. - 24 Max.[30.5 cm - 61 cm] Above CombustionAir Inlet Typ.

    Direct Vent - Vertical Termination of Multiple BoilersFig. 5:

  • 17

    2.0 Direct Vent Installation of Vent/Air Piping

    DONOT include the 90 elbows used to terminatethe combustion air inlet and vent exterior of thebuilding when determining the total length of pipe.2. The combustion air pipe must terminate using a 90

    elbow directed away from the vent termination. Thecombustion air termination must be installed 12 [30.5cm] minimum above grade / highest anticipated snowlevel and as shown in Figs. 6 through 8 on page 19.

    The combustion air termination can be placed oneither side of the vent termination. The vent andcombustion air terminations must be a minimum 12[30.5 cm] apart. The vent and combustion air termi-nations are not required to be in the same pressurezone. The combustion air termination must bedirected away from the vent see Fig. 8 on page 19.The combustion air termination must be directeddown for Figs. 6 and 7 on page 19.3. The vent pipe can terminate:- Using a 90 elbow as shown in Figs. 6 or 8 on page 19.- Using coupling as shown in Fig. 7 on page 19.The

    vent termination must be installed 12 [30.5 cm]minimum above grade / highest anticipated snowlevel.

    Do not extend the vent pipe outside the sidewallbeyond the dimensions shown in Figs. 6 through 8.Extended exposure of the vent pipe could causecondensate to freeze and block the vent pipe.4. The combustion air and vent pipe center lines must

    be a minimum of 12 [30.5 cm] apart as shown inFigs. 6 through 8 on page 19.

    5. The following should be considered when determin-ing the location of the vent and combustion air ter-mination:a. Locate the vent termination where flue vapors

    will not damage surrounding shrubs, plants, airconditioning equipment or be objectionable tothe homeowner.

    b. The flue products will form a noticeable plumeof water vapor as they condense in colder air.Avoid terminating the vent in areas where theplume could obstruct window views.

    NOTICE

    NOTICE

    WARNING

    2.2 Direct Vent - Horizontal - Sidewall

    The installation must conform to the requirements ofthe authority having jurisdiction or, in the absenceof such requirements, to the National Fuel GasCode, ANSI Z223.1/ NFPA 54, and/or Natural Gas andPropane Installation Code, CAN/CSA B149.1.

    For direct vent (sidewall) installations in theCommonwealth of Massachusetts, the installer mustcomply with the additional requirements outlined onpage 37 and 38.

    A gas vent extending through a sidewall should notterminate near an adjacent wall or below any build-ing extensions such as roof eaves, balconies ordecks. Failure to comply with the required clear-ances in this manual could result in severe personalinjury, death or substantial property damage.

    To reduce the potential of the combustion air inletfreezing up it is recommended to separate the ventand air terminations in both a horizontal and verticalplain as shown in figures 6 through 8 on page 19.

    The information and diagrams outlining the fittingsand method of terminating the vent/combustion airare directly related to PVC/CPVC vent systems.When utilizing and AL29-4C or Polypropylene ventsystem there may be some variations. Consult theappropriate vent manufacturer for recommenda-tions and clarifications.

    2.2.1 Determine Termination Location

    Locate the vent and combustion air termination using thefollowing guidelines:1. The total length of the vent or combustion air piping

    must not exceed the limits given in Table 8 on page 10.

    NOTICE

    NOTICE

    WARNING

    BEST PRACTICE

    NOTICE

  • 18

    c. Prevailing winds could cause freezing of fluegas condensation and a buildup of water / ice onsurrounding plants, building surfaces or com-bustion air inlet.

    d. Avoid locations where prevailing winds couldaffect the performance of the boiler or causerecirculation of the flue gases, such as insidecorners of buildings, near adjacent buildings,vertical surfaces, window wells, stairwells,alcoves, courtyards, or other recessed areas.

    e. Do not terminate the vent above doors or win-dows: flue condensate could freeze causing iceformations.

    f. Locate the vent termination to prevent possiblecondensate damage to exterior finishes.

    g. Avoid locations of possible accidental contact offlue vapors with people or pets.

    6. The vent termination must also maintain the follow-ing clearances; as shown in Fig. 2 on page 15.a. At least 3 feet [0.9 m] from adjacent wallsb. At least 3 feet [0.9 m] below roof overhangsc. At least 7 feet [2.1 m] above any public walk-

    waysd. At least 3 feet [0.9 m] above any forced air intake

    within 10 feet [3 m] (does not apply to the com-bustion air inlet of a direct vent appliance).

    e. No closer than 12 [30.5 cm] below or horizon-tally from any door, window or gravity air inlet.

    f. Must be at least 4 feet [1.2 cm] from electricmeters, gas meters-regulators, relief valves orother equipment. Never terminate the ventabove or below any of these items or within 4feet [1.2 cm] horizontally.

    g. A minimum of 12 [30.5 cm] or a maximum of 24[61 cm] beyond the exterior wall.

    h. A minimum 12 inches [30.5 cm] horizontal spac-ing from other fan assisted appliance vents (seepage 13).

    7. The edge of the combustion air termination couplingmust extend 1 [2.5 cm] beyond the exterior wall asshown in Figs. 6 through 8 on page 19.

    8. Locate the vent and combustion air terminations ina manner so as to protect from damage by foreignobjects, such as stones, balls, buildup of leaves orsediment.

    9. Do not connect any other appliance to the vent pipeor multiple boilers to a common vent pipe.

    2.2.2 Direct Vent - Vent Installation - Sidewall1. Vent and Combustion Air Penetration

    - Vent pipe penetration through combustible ornon-combustible wall material should maintain aminimum 1/4 [6mm] clearance for 3 and 4PVC/CPVC vents or 1 for 2 PVC/CPVC Vents.The diameter of the penetration hole should be4 [10.2 cm] minimum for 2 and 3 pipe or 5[12.7 cm] minimum for 4 pipe. When usingPolypropylene or Stainless Steel vent refer tovent manufactures installation instructions, sup-plied with the vent for clearances.

    - Combustion air pipe penetration can maintainzero clearance. The diameter of the penetrationhole should be 2-3/8 [6 cm] minimum for 2 pipeor 3-1/2 [8.9 cm] minimum for 3 pipe or 4-1/2[11.4 cm] minimum for 4 pipe.

    2. The installer must use a galvanized metal thimble forthe vent pipe penetration.

    3. Locate the vent and combustion air pipe penetra-tions to provide clearances as described in Figs. 6through 8 on page 19.

    4. The installer must comply with all local codes for iso-lating the vent pipe as it passes through floors andwalls.

    5. The installer should seal all exterior openingsaround penetration with an exterior silicon caulk.

    2.2.3 Termination Fittings - Sidewall1. The vent and combustion air terminations must

    include a factory supplied bird screen installed asshown in Figs. 9 & 10 on page 20.

    2. The combustion air pipe must terminate using a 90elbow as shown in Figs. 6 through 8 on page 19.

    3. The vent pipe can terminate:- Using a 90 elbow as shown in Fig. 6 on page 19.- Using coupling as shown in Fig. 8 on page 19.

    The vent termination must be installed 12 [30.5 cm]minimum above grade / highest anticipated snow level.

    Do not extend the vent pipe outside the sidewallbeyond the dimensions shown in Figs. 6 through 8on page 19. Extended exposure of the vent pipecould cause condensate to freeze and block the ventpipe.

    WARNING

    2.0 Direct Vent Installation of Vent/Air Piping

  • 19

    2.0 Direct Vent Installation of Vent/Air Piping

    12 Min. - 24 Max. [ 30.5 cm - 61 cm]From Wall To Vent

    12" [

    30.5

    cm] M

    in. A

    bove

    Gra

    de /

    High

    est

    Ant

    icipa

    ted

    Snow

    Lev

    el

    12" Max.

    [30.5 cm]

    12" Min.[30.5 cm]

    12" Min. 24" Max.

    [30.5 cm - 61 cm]

    1" [2.5 cm] From Wall To Edge of Coupling - Air

    Combustion AirTermination

    Vent Termination

    Direct Vent - Sidewall SnorkelTermination of Vent and Combustion AirPiping

    Fig. 8:

    Combustion AirTermination

    12" Min. - 24 Max.[30.5 - 61 cm] From Wall to Vent

    1" [2.5 cm] From Wall To Edge of Coupling - Air

    12" [30.5 cm] M

    in.

    Above Grade / H

    ighest

    Anticipated Sno

    w Level

    12" Min. [30.5 cm] Ty

    p.

    12"

    Min

    - 24

    Max

    .[3

    0.5

    cm -

    61 cm

    ]

    Vent Termination

    Direct Vent - Sidewall Termination of Ventand Combustion Air Piping

    Fig. 6:

    12" Min.[30.5 cm]

    Horizontally from Vent to Air

    1" [2.5 cm] From Wall To Edge of Coupling - Air

    12 Min. - 24 Max. [ 30.5 cm - 61 cm] From Wall To Vent12" Min. - 2

    4 Max.

    [30.5 cm - 61 cm]

    12" Min. [30.5 cm ]

    Above Grade/Highest

    Anticipated Snow Level

    Direct Vent - Alternate Sidewall Terminationof Vent and Combustion Air Piping

    Fig. 7:

  • 20

    2.0 Direct Vent Installation of Vent/Air Piping

    2.2.4 Direct Vent - Multiple Boiler Installation -Sidewall1. On installations of multiple PRESTIGE boilers, ter-

    minate each vent and combustion air pipe asdescribed in this manual.

    2. The wall penetration of the vent and combustion airpipe should be such that the combustion air inlet isa minimum 12 [30.5 cm] from the adjacent vent pipeof the other boiler for installations in the U.S asshown in Fig. 20 on page 21. For installations inCanada, provide clearances as required byCAN/CSA B149.1.

    The combustion air inlet of the PRESTIGE is definedas being part of a direct vent system. It is not con-sidered as a forced air intake. The required clear-ance of an adjacent boiler vent to a forced air inletdoes not apply in a multiple installation of PRES-TIGE boilers.

    NOTICE

    Fig. 11 on page 21 shows one option for vent andcombustion air terminations of multiple PRESTIGEboilers. Either termination option shown in Fig. 6 or7 on page 19 can be used for multiple PRESTIGEboilers. The 12 [30.5 cm] minimum distancebetween centerlines of the combustion air and ventpiping must be maintained for any chosen option.

    Reference Fig. 6 or 7 on page 19 for the configura-tion dimensions for the vent and combustion airinlet terminations for each unit installed in a multi-ple installation.

    NOTICE

    NOTICE

    Vent Termination

    Bird Screen

    Horizontal Vent Bird Screen Installation withCoupling Termination

    Fig. 9:

    Combustion Air Termination

    Bird Screen

    Horizontal Combustion Air Bird ScreenInstallation with 90 Elbow Termination

    Fig. 10:

    Installer must install the factory supplied birdscreens on the vent and combustion air termina-tions.

    NOTICE

  • 21

    2.0 Direct Vent Installation of Vent/Air Piping

    Combustion AirTerminations

    Vent Terminations

    24" [ 61 cm] Max. 12" [30.5

    cm] Min.

    12 Min. - 24 Max. [ 30.5 cm - 61 cm]From Wall To VentTyp.

    1" [2.5 cm] From Wall To Edge of Coupling - AirTyp.

    12" Min. [30.5 cm]

    Horizontally Between

    All Terminations

    12" [30.5 cm]

    Min. Above Grade/High

    est

    Anticipated

    Snow Level, Typ.

    Direct Vent - Horizontal Termination of Multiple BoilersFig. 11:

  • 22

    2.3 Direct Vent - Vertical Vent and SidewallCombustion Air

    The installation must conform to the requirements ofthe authority having jurisdiction or, in the absenceof such requirements, to the National Fuel GasCode, ANSI Z223.1/ NFPA 54, and/or Natural Gas andPropane Installation Code, CAN/CSA B149.1.

    When using an inoperative chimney as a means of achase for the vent, the surrounding space within thechimney cannot be used to draw combustion air orvent another appliance.

    A gas vent extending through a roof should not ter-minate near an adjacent wall or below any buildingextensions such as roof eaves, balconies or decks.Failure to comply with the required clearances inthis manual could result in severe personal injury,death or substantial property damage.

    NOTICE

    NOTICE

    WARNING

    2.3.1 Determine Termination Location

    Locate the vent and combustion air termination using thefollowing guidelines:1. The total length of the vent or combustion air piping

    must not exceed the limits given in Table 8 on page 10.

    Do not include the 90 elbow or coupling used to ter-minate the combustion air inlet or vent exterior ofthe building when determining the total length ofpipe.2. The combustion air piping must terminate with a 90

    elbow. Fig. 12 shows a snorkel termination option.The combustion air pipe can also terminate using a90 elbow directed down as shown in Fig. 6 on page19. The termination must be installed 12 [30.5 cm]minimum above grade / highest anticipated snowlevel and as shown in Fig. 6 on page 19.

    3. The vent must terminate vertically with a coupling toaccept the bird screen and must be located 12 [30.5cm] (18 [45.7 cm] Canada) above the highest anticipat-ed snow level.

    NOTICE

    2.0 Direct Vent Installation of Vent/Air Piping

    1" Min. [2.5 cm] From Wall To Edge of Coupling-Air

    36" Max.[91.4 cm]

    12"

    [30.

    5 cm

    ] Min.

    Abo

    ve

    Grad

    e / H

    ighes

    t A

    ntici

    pate

    d Sn

    ow L

    evel

    12" [30.5 cm] (18 [45.7 cm] Canada)Above the Highest

    Anticipated Snow Level

    Combustion Air Termination

    Vent Termination

    Direct Vent - Vertical Vent and Side Wall Combustion AirFig. 12:

  • 23

    2.0 Direct Vent Installation of Vent/Air Piping

    4. The following should be considered when deter-mining the location of the vent and combustion airtermination:a. Locate the vent termination where flue vapors

    will not damage surrounding shrubs, plants orair conditioning equipment or be objectionableto the homeowner.

    b. The flue products will form a noticeable plume ofwater vapor as they condense in colder air.Avoid terminating the vent in areas where theplume could obstruct window views.

    c. Prevailing winds could cause freezing of fluegas condensation and a buildup of water / ice onsurrounding plants, building surfaces or com-bustion air inlet.

    d. Avoid locations where prevailing winds couldaffect the performance of the boiler or causerecirculation of the flue gases, such as insidecorners of buildings, near adjacent buildings,vertical surfaces, window wells, stairwells,alcoves, courtyards, or other recessed areas.

    e. Do not terminate the vent above doors or win-dows: flue condensate could freeze causing iceformations.

    f. Locate the vent termination to prevent possiblecondensate damage to exterior finishes.

    g. Avoid locations of possible accidental contact offlue vapors with people or pets.

    5. The vent termination must also maintain the follow-ing clearances; as shown in Fig. 2 on page 15.a. At least 3 feet [0.9 m] from adjacent wallsb. At least 3 feet [0.9 m] below roof over hangsc. At least 7 feet [2.1 m] above any public walk-

    waysd. At least 3 feet [0.9 m] above any forced air

    intake within 10 feet [3 m] (does not apply to thecombustion air inlet of a direct vent appliance).

    e. No closer than 12 [30.5 cm] below or horizon-tally from any door or window or gravity air inlet.

    f. Must be at least 4 feet [1.2 m] from any electricmeters, gas meters-regulators, relief valves orother equipment.Never terminate the ventabove or below any of these items within 4 feet[1.2 m] horizontally.

    6. The edge of the combustion air termination couplingmust extend to 1 [2.5 cm] beyond the exterior wall,as shown in Fig. 12 page 22.

    7. Locate the vent termination and combustion air inlet ina manner to protect from damage by foreign objects,such as stones, balls, or buildup of leaves or sediment.

    8. Do not connect any other appliance to the vent pipeor multiple boilers to a common vent pipe.

    2.3.2 Direct Vent - Vent Installation - Through theRoof1. Vent pipe penetration through combustible or non-

    combustible wall material should maintain a mini-mum 1/4 [6 mm] clearance for 3 or 4 PVC/CPVCvents or 1 [2.5 cm] for 2 PVC/CPVC vents. Thediameter of the penetration hole should be 4 [10.2cm] minimum for 2 and 3 pipe or 5 [12.7 cm] min-imum for 4 pipe. When using Polypropylene orStainless Steel vent refer to the vent manufacturesinstallation instructions, supplied with the vent forclearances.

    2. The installer must use a galvanized metal thimble forthe vent pipe penetration.

    3. The vent must terminate 12 [30.5 cm] (18 [45.7 cm]Canada) above the highest anticipated snow level.

    4. The installer must comply with all local codes for iso-lating the vent pipe as it passes through floors, ceil-ings and roofs.

    5. The installer should provide adequate flashing andsealing boots sized for the vent pipe.

    2.3.3 Direct Vent - Combustion Air Installation -Sidewall1. Combustion air pipe penetration can maintain zero

    clearance. The diameter of the penetration holeshould be 2 3/8 [6 cm] minimum for 2 pipe or 3 1/2[8.9 cm] minimum for 3 pipe or 4 1/2 [11.4 cm] min-imum for 4 pipe.

    2. The combustion air termination must be installed 12[30.5 cm] minimum above grade / highest anticipat-ed snow level and as shown in Fig. 6 or 8 on page19.

    3. The installer must comply with all local codes for iso-lating the combustion air pipe as it passes throughfloors and walls.

    4. The installer should seal all exterior openingsaround penetration with an exterior silicon caulk.

  • 24

    2.0 Direct Vent Installation of Vent/Air Piping

    2.3.5 Direct Vent - Multiple Boiler Installation -Vertical Vent and Sidewall Combustion Air1. On installations of multiple PRESTIGE boilers, ter-

    minate each vent and combustion air piping asdescribed in this manual.

    2. Each vent and combustion air termination must be aminimum 12 [30.5 cm] from the adjacent termina-tion for installations in the U.S. as shown in Fig. 13.For installations in Canada, provide clearances asrequired by CAN/CSA B149.1.

    The combustion air inlet of the PRESTIGE is definedas being part of a direct vent system. It is not con-sidered as a forced air intake. The required clear-ance of an adjacent boiler vent to a forced air inletdoes not apply in a multiple installation of PRES-TIGE boilers.

    NOTICE

    2.3.4 Termination Fittings - Vertical &Sidewall1. The vent and combustion air terminations must include

    a factory supplied bird screen installed as shown inFig. 3 on page 16 &Fig. 10 on page 20.

    2. The combustion air piping must terminate throughthe sidewall using a 90 elbow as shown in Fig. 6 or8 on page 19.

    3. The vent piping must terminate vertically through theroof with a coupling to accept the bird screen andmust be located 12 [30.5 cm] (18 [45.7 cm]Canada) above the highest anticipated snow level.

    Do not extend the vent pipe above the roof beyondthe dimension shown in Fig. 12 on page 22.Extended exposure of the vent pipe could causecondensate to freeze and block the vent pipe.

    WARNING

    12" Min.[30.5 cm]

    36" Max. [91.4 cm]

    12" Min.

    [30.5 cm]

    12" [3

    0.5 cm

    ] Min.

    Above

    Grade

    / High

    estAn

    ticipat

    ed Sn

    ow Le

    vel

    12" [30.5 cm] (18 [45.7 cm] Canada) Above Highest Anticipated Snow Level Typ.

    1" [2.5 cm]From Wall toEdge of Coupling-Air

    Combustion Air Terminations

    Vent Terminations

    Direct Vent - Vertical Termination of Vent and SidewallTermination of Combustion Air of Multiple Boilers

    Fig. 13:

  • 25

    3.0 Direct Vent Installation of Vent/Air Piping

    SECTION III - CATEGORY IV (INDOOR AIR)INSTALLATION OF VENT/AIR PIPING

    A Category IV appliance utilizes uncontaminated indoor oroutdoor air (surrounding the appliance) for combustion.

    3.1 Category IV - Vertical - Through the Roofor Unused Chimney

    The installation must conform to the requirements ofthe authority having jurisdiction or, in the absenceof such requirements, to the National Fuel GasCode, ANSI Z223.1/ NFPA 54, and/or Natural Gas andPropane Installation Code, CAN/CSA B149.1.

    When using an inoperative chimney as a means of achase for the vent, the surrounding space within thechimney cannot be used to draw combustion air orvent another appliance.

    A gas vent extending through a roof should not ter-minate near an adjacent wall or below any buildingextensions such as roof eaves, balconies or decks.Failure to comply with the required clearances inthis manual could result in severe personal injury,death or substantial property damage.

    The information and diagrams outlining the fittingsand method of terminating the vent/combustion airare directly related to PVC/CPVC vent systems.When utilizing an AL 29-4C or Polypropylene ventsystem there maybe some variations. Consult theappropriate vent manufacturer for recommenda-tions and clarifications.

    3.1.1 Determine Termination Location

    Locate the vent and combustion air termination using thefollowing guidelines:1. The total length of the vent must not exceed the limits

    given in Table 8 on page 8.

    WARNING

    NOTICE

    NOTICE

    NOTICE

    Do not include the coupling used to terminate thevent exterior of the building when determining thetotal length of pipe.2. The combustion air piping must terminate at the boil-

    er with a 90 elbow.3. The vent must terminate vertically with a coupling

    and must be located 12 [30.5 cm] (18 [45.7 cm]Canada) above the highest anticipated snow levelas shown in Fig. 14.

    4. The following should be considered when determin-ing the location of the vent termination:a. Locate the vent termination where flue vapors

    will not damage surrounding shrubs, plants orair conditioning equipment or be objectionableto the homeowner.

    b. The flue products will form a noticeable plumeas they condense in colder air. Avoid terminat-ing the vent in areas where the plume couldobstruct window views.

    c. Prevailing winds could cause freezing of fluecondensation and a buildup of water / ice on sur-rounding plants or building surfaces.

    d. Avoid locations where prevailing winds couldaffect the performance of the boiler or causerecirculation of the flue gases, such as insidecorners of buildings or near adjacent buildingsor vertical surfaces, window wells, stairwells,alcoves, courtyards, or other recessed areas.

    NOTICE

    Vent Termination

    12" [30.5 cm] (18 [45.7 cm] Canada)

    Above the HighestAnticipated Snow Level

    Category - IV - Vertical Termination ofVent Pipe

    Fig. 14:

  • e. Do not terminate the vent above any doors orwindows: flue condensate could freeze causingice formations.

    f. Locate the vent termination to prevent possiblecondensate damage to exterior finishes.

    g. Avoid locations of possible accidental contact offlue vapors with people or pets.

    5. The vent termination must also maintain the follow-ing clearances; as shown in Fig. 15.a. At least 3 feet [0.9 m] from adjacent wallsb. At least 3 feet [0.9 m] below roof over hangsc. At least 7 feet [2.1 cm] above any public walk-

    waysd. At least 3 feet [0.9 m] above any forced air

    intake within 10 feet [3 m].e. No closer than 4 feet [1.2 m] below or horizon-

    tally from any door or window or gravity air inlet.6. Locate the vent termination in a manner to protect

    from damage by foreign objects, such as stones,balls, or to buildup of leaves and sediment.

    7. Do not connect any other appliance to the vent pipeor multiple boilers to a common vent pipe.

    3.1.2 Category IV - Vent Installation - Through theRoof1. Vent Penetration

    - Vent pipe penetration through combustible ornon-combustible wall material should maintain aminimum 1/4 [6 mm] clearance for 3 or 4PVC/CPVC vents or 1 [2.5 cm] for 2 PVC/CPVCvents. The diameter of the penetration holeshould be 4 [10.2 cm] minimum for 2 and 3 pipeor 5 [12.7 cm] minimum for 4 pipe. When usingPolypropylene or Stainless Steel Vent refer tovent manufactures installation instructions, sup-plied with the vent for clearances.

    2. The installer must use a galvanized metal thimble forthe vent pipe penetration.

    3. Locate the vent pipe penetration to provide clear-ances as described in Fig. 14 on page 25.

    4. The installer must comply with all local codes for iso-lating the vent pipe as it passes through floors, ceil-ings and roofs.

    5. The installer should provide adequate flashing and asealing boot sized for the vent pipe.

    3.1.3 Termination Fittings - Through the Roof1. The vent pipe and combustion air pipe terminations

    must include a factory supplied bird screen installed asshown in Figs. 3 & 4 on page 16.

    2. The combustion air piping must terminate at the boil-er with a 90 elbow.

    3. The vent piping must terminate vertically with a cou-pling as shown in Fig. 14 on page 25.

    Do not extend the vent pipe above the roof beyondthe given dimensions shown in Fig. 14 on page 25.Extended exposure of the vent pipe could causecondensate to freeze and block the vent pipe.

    WARNING

    26

    3.0 Category IV Installation of Vent/Air Piping

    Termination Clearances of Category IVSystem

    Fig. 15:

  • 27

    3.0 Category IV Installation of Vent/Air Piping

    3.1.4 Category IV - Multiple Boiler Installation -Through the Roof1. On installations of multiple PRESTIGE boilers, termi-

    nate each vent pipe as described in this manual.2. Each vent termination must be a minimum 12 [30.5

    cm] from the adjacent termination for installations inthe U.S. as shown in Fig. 16. For installations inCanada, provide clearances as required byCAN/CSA B149.1.

    3.2 Category IV - Horizontal - Sidewall

    The installation must conform to the requirements ofthe authority having jurisdiction or, in the absenceof such requirements, to the National Fuel GasCode, ANSI Z223.1/ NFPA 54, and/or Natural Gas andPropane Installation Code, CAN/CSA B149.1.

    For direct vent (sidewall) installations in theCommonwealth of Massachusetts, the installer mustcomply with the additional requirements outlined onpages 37 and 38.

    A gas vent extending through a sidewall should notterminate near an adjacent wall or below any build-ing extensions such as roof eaves, balconies ordecks. Failure to comply with the required clear-ances in this manual could result in severe personalinjury, death or substantial property damage.

    The information and diagrams outlining the fittingsand method of terminating the vent/combustion airare directly related to PVC/CPVC vent systems.When utilizing and AL29-4C or Polypropylene ventsystem there may be some variations. Consult theappropriate vent manufacturer for recommenda-tions and clarifications.

    3.2.1 Determine Termination Location

    Locate the vent and combustion air termination using thefollowing guidelines:1. The combustion air must terminate at the boiler with

    a 90 elbow.

    2. The total length of the vent must not exceed the limitsgiven in Table 8 on page 10.

    DO NOT include the 90 elbow used to terminate thevent exterior of the building when determining thetotal length of pipe.

    NOTICE

    NOTICE

    WARNING

    NOTICE

    NOTICE

    Vent Termination

    12" [30.5 cm] (18 [45.7 cm] Canada)

    Above the HighestAnticipated Snow Level

    12" Min.

    [30.5 cm]

    Category IV- Vertical Vent Termination ofMultiple Boilers

    Fig. 16:

  • 28

    3.0 Category IV Installation of Vent/Air Piping

    3. The vent pipe can terminate:- Using a coupling as shown in Fig. 17.- Using a 90 elbow as shown in Fig. 18.

    The vent termination must be installed 12 [30.5 cm] min-imum above grade / highest anticipated snow level.

    Do not extend the vent pipe outside the sidewallbeyond the dimensions shown in Figs. 17 & 18.Extended exposure of the vent pipe could causecondensate to freeze and block the vent pipe.4. The following should be considered when determin-

    ing the location of the vent termination:a. Locate the vent termination where flue vapors

    will not damage surrounding shrubs, plants orair conditioning equipment or be objectionableto the homeowner.

    b. The flue products will form a noticeable plumeas they condense in colder air. Avoid terminat-ing the vent in areas where the plume couldobstruct window views.

    c. Prevailing winds could cause freezing of fluecondensation and a buildup of water / ice on sur-rounding plants or building surfaces.

    d. Avoid locations where prevailing winds couldaffect the performance of the boiler or causerecirculation of the flue gases, such as insidecorners of buildings or near adjacent buildingsor vertical surfaces, window wells, stairwells,alcoves, courtyards, or other recessed areas.

    e. Do not terminate the vent above any doors orwindows: flue condensate could freeze causingice formations.

    f. Locate the vent termination to prevent possiblecondensate damage to exterior finishes.

    g. Avoid locations of possible accidental contact offlue vapors with persons or pets.

    5. The vent termination must also maintain the follow-ing clearances; as shown in Fig. 15 on page 26.a. At least 3 feet [0.9 m] from adjacent wallsb. At least 3 feet [0.9 m] below roof overhangsc. At least 7 feet [2.1 m] above any public walk-

    ways

    WARNING

    d. At least 3 feet [0.9 m] above any forced airintake within 10 feet [3 m].

    e. No closer than 4 feet [1.2 m] below or horizon-tally from any door or window or gravity air inlet.

    f. Must be at least 4 feet [1.2 m] from any electricmeters, gas meters-regulators, relief valves orother equipment. Never terminate the ventabove or below any of these items within 4 feet[1.2 m] horizontally.

    g. A minimum 12 [30.5 cm] or a maximum 24 [61cm] beyond the exterior wall.

    7. Locate the vent termination in a matter to protectfrom damage by foreign objects, such as stones orballs or subject to buildup of leaves or sediment.

    8. Do not connect any other appliance to the vent pipeor multiple boilers to a common vent pipe.

    12" Min. - 24 Max.[30.5 cm - 61 cm] To Wall

    12" [30.5 cm

    ] Min.

    Above Gra

    de / Highes

    t

    Anticipated

    Snow Leve

    l

    Vent Termination

    Category IV - Sidewall Termination ofVent Pipe with Coupling Termination

    Fig. 17:

    12"

    [30.

    5 cm

    ] Min.

    Abo

    ve G

    rade

    / Hi

    ghes

    tAn

    ticipa

    ted

    Sno

    w Le

    vel

    12" Min. -

    24" Max.

    [30.5 cm -

    61 cm]

    To Wall 3

    6 Max.

    [91.4 cm]

    Vent Termination

    Category IV - Sidewall SnorkelTermination of Vent Pipe with 90 ElbowTermination

    Fig. 18:

  • 29

    3.0 Category IV Installation of Vent/Air Piping

    3.2.4 Category IV - Multiple Boiler Installation -Sidewall1. On installations of multiple PRESTIGE boilers, ter-

    minate each vent pipe as described in this manual.2. The wall penetration of the vent should be a mini-

    mum 12 [30.5 cm] from the adjacent vent pipe ofanother boiler for installations in the U.S as shownFig. 19. For installations in Canada, provide clear-ances as required by CAN/CSA B149.1.

    Fig. 19 shows one option for vent terminations ofmultiple PRESTIGE boilers. Any vent terminationoption shown in Figs. 17 & 18 on page 28 can beused for multiple PRESTIGE boilers. The 12 [30.5cm] minimum distance between centerlines of thevent piping must be maintained for any chosenoption.

    Reference Figs. 17 & 18 on page 28 for the configu-ration dimensions of the vent for each unit installedin a multiple installation.

    NOTICE

    NOTICE

    3.2.2 Category IV - Vent Installation - Sidewall1. Vent Penetration

    - Vent pipe penetration through combustible ornon-combustible wall material should maintain aminimum 1/4 [6 mm] clearance for 3 and 4PVC/CPVC vents or 1 for 2 PVC/CPVC vents.The diameter of the penetration hole should be4 [10.2 cm] minimum for 2 and 3 pipe or 5[12.7 cm] minimum for 4 pipe. When usingPolypropylene or Stainless Steel vent, refer tothe vent manufactures installation instructions,supplied with the vent for clearances.

    2. The installer must use a galvanized metal thimble forthe vent pipe penetration.

    3. Locate the vent pipe penetration to provide minimumclearances as described in Figs. 17 & 18 on page28.

    4. The installer must comply with all local codes for iso-lating the vent pipe as it passes through floors andwalls.

    5. The installer should seal all exterior openingsaround penetrations with an exterior silicon caulk.

    3.2.3 Termination Fittings - Sidewall1. The vent and combustion air terminations must

    include a factory supplied bird screen installed asshown in Figs. 9 & 10 on page 20.

    2. The combustion air piping must terminate at the boil-er with a 90 elbow.

    3. The vent pipe can terminate:- Using a coupling as shown in Fig. 17 on page 28.- Using a 90 elbow as shown in Fig. 18 on page 28.

    The vent termination must be installed 12 [30.5 cm] min-imum above grade / highest anticipated snow level.

    Do not extend the vent pipe outside the sidewallbeyond the dimensions shown in Figs. 17 & 18 onpage 28. Extended exposure of the vent pipe couldcause condensate to freeze and block the vent pipe.

    WARNING

    12" [3

    0.5 cm

    ] Min.

    Above

    Grad

    e / Hi

    ghest

    Antici

    pated

    Snow

    Level

    Vent Termination

    12" Min.

    [30.5 cm]

    36" Max.

    [91.4 cm]

    12" Min. -24 Max.[30.5 cm - 61 cm] To Wall Typ.

    Category IV - Sidewall Vent Terminationsof Multiple Boilers

    Fig. 19:

  • 30

    4.0 InstallationRequirements

    SECTION IV- INSTALLATION REQUIREMENTS

    4.1 Vent/Combustion Air Transitions

    4.1.1 3 to 2 (60 mm) Transitions

    This section outlines the installation of Venting andCombustion Air for the PRESTIGE Solo 80, 110 andEXCELLENCE 110 when the vent system must tran-sition from the 3 outlet of the boiler to the 2 (60mm) vent system. The transition from 3 vent system to 2 (60 mm)

    vent system must occur at the boiler vent outlet. The transition from 3 vent to 2 (60 mm) vent must

    occur in a vertical run only.

    Transition of 3 vent to 2 (60 mm) vent in a horizon-tal run may result in pooling of the condensate andpotential vent blockage. Failure to comply can resultin death, serious injury or substantial property dam-age. Use a 3 x 2 bell reducer to make the transition to 2

    CPVC/PVC vent, see Figures 20 and 21.* Use a 3 (80 mm) appliance vent adapter and 3 (80

    mm) to 2 (60 mm) reducer to make the transition to2 (60 mm) Polypropylene vent see Table 2 on page5.

    The 2 (60 mm) vent should not transition back to 3(80 mm) vent at any point in the vent system.

    The PVC combustion air piping shall transition from 3to 2 using a 3 x 2 bell reducer and shall transition ina similar manner as the vent system.

    The total equivalent length of the 3 (80 mm) ventand 2 (60 mPVC m) vent combined shall notexceed the length listed for a 2 (60 mm) vent sys-tem Table 8 on page 10.

    The total equivalent length of 3 (80 mm) and 2 (60mm) combustion air piping combined shall notexceed the length listed for combustion air in Table8 on page 10.

    NOTICE

    WARNING

    2 Inch Vent PipePVC or CPVC

    Material

    2 Inch Vent PipeMin. 7 Feet LengthCPVC Material

    3 x 2 Bell ReducerCPVC Material

    3 Inch Stub Vent PipeCPVC Material

    2 CPVC/PVC Venting System VerticalFig. 20:

    2 Inch Vent PipePVC or CPVC

    Material

    2 Inch Stub Vent PipeCPVC Material

    2 Inch 90 Long Sweep ElbowCPVC Material

    3 x 2 Bell ReducerCPVC Material

    3 Inch Stub Vent PipeCPVC Material

    2 CPVC/PVC Venting System HorizontalFig. 21:

  • 31

    4.0 Installation Requirements

    4.1.2 3 to 4 (100 mm) Transitions

    This section outlines the installation of Venting andCombustion Air for the PRESTIGE Solo 80, 110, 155,175, 250 and EXCELLENCE 110 when the vent sys-tem must transition from the 3 outlet of the boiler tothe 4 (100 mm) vent system. The transition from 3 vent system to 4 (100 mm) vent

    system must occur within 5 feet [1.5 m] of the boilervent outlet.

    The transition from 3 vent to 4 (100 mm) vent mustoccur in a vertical run only.

    Transition of 3 vent to 4 (100 mm) vent in a hori-zontal run may result in pooling of the condensateand potential vent blockage. Failure to comply canresult in death, serious injury or substantial propertydamage. The 4 (100 mm) vent should not transition back to

    3 (80 mm) vent at any point in the vent systemexcept when using ACV - Triangle Tubes optionalPVC concentric vent termination kit, see kit instruc-tions for details.

    The combustion air piping shall transition from 3 to4 (100 mm) in the same manner as the vent sys-tem.

    The total equivalent length of the 3 (80 mm) ventand 4 (100 mm) vent combined shall not exceed thelength listed for a 4 (100 mm) vent system Table 8on page 10.

    The total equivalent length of 3 (80 mm) and 4(100 mm) combustion air piping combined shall notexceed the length listed for combustion air in Table8 on page 10.

    WARNING

    NOTICE

    4.2 Insert Piping to PRESTIGE Adapters1. The installer must clean, deburr and chamfer the

    pipe ends.

    The pipe ends must be smooth, free of sharp edgeschamfer and wiped clean to prevent possible dam-age to the sealing gasket in the vent and combustionair adapters. Failure to comply with this require-ment could result in leakage of flue products caus-ing possible severe personal injury or death.2. Prior to inserting the pipe, inspect the vent and com-

    bustion air adapters to verify there are no obstruc-tions or packing material inside the adapters and thegaskets are in place.

    3. Ensure the adapter banding strap is loose prior toinserting the pipe.

    4. Apply a small amount of silicon grease or water tothe insertion end of the pipe to ease insertion intothe adapter.

    5. Insert the pipe into the adapter until it is fully seated.

    Do not apply excessive force, twist or bend theadapter or vent / combustion air pipe when insert-ing. The adapter gasket could be damaged resultingin possible flue gas leakage.

    6. Secure the vent and combustion air pipe by tighten-ing the adapter banding strap. Do not over tightenthe strap. The seal is made with gasket inside theadapter.