PV-systems.pdf
-
Upload
henrry-ochoa -
Category
Documents
-
view
217 -
download
0
Transcript of PV-systems.pdf
-
8/13/2019 PV-systems.pdf
1/41
Fraunhofer IWES Fraunhofer IWES
Slide 1, Power System Service Seminar, 31.03.2011
Power System Services of PV-systems:Requirements, testing and application in Germany
D. Geibel, Dr. G. Arnold, Dr. T. Degner
Fraunhofer Institute Wind Energy and Energy Systems Technology Fraunhofer IWES
DERlab Workshop on Power System Services31.03.2011, Risoe
-
8/13/2019 PV-systems.pdf
2/41
Fraunhofer IWES Fraunhofer IWES
Slide 2, Power System Service Seminar, 31.03.2011
Power System Services of PV-systems:Requirements, testing and application in Germany Introduction
Power System Services of PV-systems
Grid code requirements
Test procedures for PV-systems
Application of power system services Voltage control by reactive power
Voltage control by active network components
Conclusions
-
8/13/2019 PV-systems.pdf
3/41
Fraunhofer IWES Fraunhofer IWES
Slide 3, Power System Service Seminar, 31.03.2011
1. IntroductionGenerating capacities in Germany
Generation capacity inGermany
137.5 GW (in 2009) intotal
46 GW of RES
Wind
Increase since 1994
25 GW in 2009
PV
Increase since 2004
17.3 GW in 2010
52 GW in 20201 Diagram: Fraunhofer IWES, Data: Erneuerbare Energien in Zahlen, BMU, 2010
1: National development plan for renewable energies
-
8/13/2019 PV-systems.pdf
4/41
Fraunhofer IWES Fraunhofer IWES
Slide 4, Power System Service Seminar, 31.03.2011
1. IntroductionInterconnection of PV-systems
Interconnection of PV-systemsmainly to LV due to power
ratings
Interconnected of PV-systems toHV or MV
18%1 (end of 2008)
Jan. 2009 to Sept. 2010
9335 MWp new installed PV-power
Share of PV-systems withrated power > 100kWp: 3278MWp
Grid integration of PV ondistribution system level
Diagram: Fraunhofer IWES; Data: Information of new installed PV-systems of BNetzA
1EEG Statistikbericht 2008; BNetzA
-
8/13/2019 PV-systems.pdf
5/41
Fraunhofer IWES Fraunhofer IWES
Slide 5, Power System Service Seminar, 31.03.2011
1. IntroductionGrid integration constraints
Power System Stability
Rotor angle stability
Frequency stability
Voltage stability
Network Constraints
Capacity of lines, cables,transformers
Power quality
Steady-state voltage limits
Harmonics
Flicker
Source: Definition and Classification of Power System Stability, IEEE/CIGRE JointTask Force on Stability Terms and Definitions, IEEE Transactions on Power Systems,
Prabha Kundur et. al.
-
8/13/2019 PV-systems.pdf
6/41
Fraunhofer IWES Fraunhofer IWES
Slide 6, Power System Service Seminar, 31.03.2011
1. IntroductionGrid integration challenges and approaches
Transmission network (HV/EHV)
Challenges Power generation not located to
load centers
Integration of offshore windparks
Approaches
Grid reinforcement
Power System Services of DERunits
Central storages
FACTS
Distribution network (MV/LV)
Challenges Bidirectional power flows
Voltage control
Approaches
Power System Services of DERunits
Active network components
Manageability of loads
Local storages
Grid reinforcement
-
8/13/2019 PV-systems.pdf
7/41
Fraunhofer IWES Fraunhofer IWES
Slide 7, Power System Service Seminar, 31.03.2011
2. Power System Services of PV-systemsGrid code requirements Overview
Pre-condition for connection
Fulfilling of technical minimum standards concerningelectrical behaviour (6 EEG)
Link to grid codes
Approval of Conformity by certificates (64 EEG)
Grid codes in Germany
Describe behaviour of DER units in order to meet systemneeds
High voltage / Extra high voltage
Transmission Code 2007
Medium voltage
BDEW MV-guideline
Low voltage
E VDE-AR-N 4105 (Draft version)
-
8/13/2019 PV-systems.pdf
8/41
Fraunhofer IWES Fraunhofer IWES
Slide 8, Power System Service Seminar, 31.03.2011
2. Power System Services of PV-systemsGrid code requirements Overview
Distribution code DER plants connected MVdistribution grid
Technical requirements for DER plants (steadystate / transient)
Basic procedure for approval of conformity
Link to Technical Guidelines of FGW for verification
of requested electrical behaviour
FGW TR3: Testing procedures
Link to IEC 61400-21
Adaptation of test procedures for PV
FGW TR4: Modelling
FGW TR8: Certification
-
8/13/2019 PV-systems.pdf
9/41
Fraunhofer IWES Fraunhofer IWESSlide 9, Power System Service Seminar, 31.03.2011
2. Power System Services of PV-systemsGrid code requirements Overview
Static requirements
Limitation of power-qualitycharacteristic parameters
Harmonics, interharmonics andhigher frequency components
Flicker
Switching operation
Active power control
Active power reduction bynetwork operator
Active power reduction at over-frequency
Reactive power control
Dynamic requirements
Fault-ride-through (FRT) capabilitywith no disconnection of DER plantsduring the voltage dip
No change of active powergeneration after faults
Feed-in of reactive power during thefault for voltage stabilization
Limitation of short-circuit current
-
8/13/2019 PV-systems.pdf
10/41
-
8/13/2019 PV-systems.pdf
11/41
Fraunhofer IWES Fraunhofer IWESSlide 11, Power System Service Seminar, 31.03.2011
2. Power System Services of PV-systemsGrid code requirements Active power control
Automatic active powerreduction depending on grid
frequency
Grid support in case ofpower surplus
Avoiding grid instabilities
due to immediatedisconnection of largegeneration capacities
Under normal gridconditions no impact on
energy yield For inverter no additional
hardware required
-
8/13/2019 PV-systems.pdf
12/41
Fraunhofer IWES Fraunhofer IWESSlide 12, Power System Service Seminar, 31.03.2011
2. Power System Services of PV-systemsGrid code requirements Active power control
Measurement results of aPower-One PVI-55.0 Central
inverter at Fraunhofer IWES
Start of reduction at fGrid >50.20 Hz
Instantaneously available
power at 50.20Hz is used foractive power reductioncalculations
Amount of active powerreduction is determined by
droop with of 40% per Hz Internal hysteresis: Rerise
of active power if fgrid 50.05 Hz
Power-One PVI-55.0 CentralMeasurement results Fraunhofer IWES
-
8/13/2019 PV-systems.pdf
13/41
Fraunhofer IWES Fraunhofer IWESSlide 13, Power System Service Seminar, 31.03.2011
2. Power System Services of PV-systemsGrid code requirements Reactive power capability
Maintenance of grid voltage
Generating unit must beable to provide reactivepower during normaloperation
Required power factor cos
at network connection pointof plant:
0.95underexcited to0.95overexcited
Impact on inverter design
Apparent power has to beincreased
Power-One PVI-55.0 CentralMeasurement results Fraunhofer IWES
-
8/13/2019 PV-systems.pdf
14/41
-
8/13/2019 PV-systems.pdf
15/41
Fraunhofer IWES Fraunhofer IWESSlide 15, Power System Service Seminar, 31.03.2011
2. Power System Services of PV-systemsGrid code requirements Fault-Ride-Through FRT)
Source: Erzeugungsanlagen am Mittelspannungsnetz. BDEW, Release June 2008
Generating units must stay connectedduring grid faults
Different FRT-curves
Type 1: Direct coupled synchronousgenerators
Type 2: all other generating units
Requested behaviour of generating unitdepends on mainly two factors:
Depth of voltage dip
Duration of voltage dip
Behaviour of unit:
Stay connected during fault
Short time disconnection withresynchronisation within 2s at most
Reactive current injection + shorttime disconnection
No requirements
-
8/13/2019 PV-systems.pdf
16/41
Fraunhofer IWES Fraunhofer IWESSlide 16, Power System Service Seminar, 31.03.2011
2. Power System Services of PV-systemsGrid code requirements Fault-Ride-Through FRT)
Reactive current injection of unitaccording to Transmission Code 2007
Amount of reactive power isdetermined by k-factor
k = Ib/In/ U/Un
Depth of grid fault
Reactive current before fault
Voltage before fault Response time 20 ms
Max. reactive current: Ib 1.0 In
Max. duration of reactive currentinjection: time of fault clearing +500ms
In terms of unsymmetrical faults arelease of overvoltage protection hasto be avoided
-
8/13/2019 PV-systems.pdf
17/41
Fraunhofer IWES Fraunhofer IWESSlide 17, Power System Service Seminar, 31.03.2011
2. Power System Services of PV-systemsGrid code requirements Fault-Ride-Through FRT)
Influence of reactivecurrent on grid
voltage during fault
For both cases thesame voltage dip isused
k-factor 0: noreactive current
k-factor 2: due toreactive currentvoltage is raised
Power-One PVI-55.0 CentralMeasurement results Fraunhofer IWES
-
8/13/2019 PV-systems.pdf
18/41
Fraunhofer IWES Fraunhofer IWESSlide 18, Power System Service Seminar, 31.03.2011
2. Power System Services of PV-systemsGrid code requirements Implementation
Source: SMA Solar Technology AG
-
8/13/2019 PV-systems.pdf
19/41
Fraunhofer IWES Fraunhofer IWES
Slide 19, Power System Service Seminar, 31.03.2011
2. Power System Services of PV-systemsTest procedures for PV-systems Testing environments
Recuperation unit
AC-network simulator
Impedance network
PV-simulator AC-network simulator
with additional
impedance network
90 kVA
Linear amplifiers
4-quadrant
operation PV-simulator 30kW
Special testingequipment for PV-systems with higher
power ratings
-
8/13/2019 PV-systems.pdf
20/41
Fraunhofer IWES Fraunhofer IWES
Slide 20, Power System Service Seminar, 31.03.2011
2. Power System Services of PV-systemsTest procedures for PV-systems Testing environments
-
8/13/2019 PV-systems.pdf
21/41
-
8/13/2019 PV-systems.pdf
22/41
Fraunhofer IWES Fraunhofer IWES
Slide 22, Power System Service Seminar, 31.03.2011
2. Power System Services of PV-systemsTest procedures for PV-systems Testing environments
6 MVA FRT-container (MV)
1 MVA AC-network simulator (LV)
1 MW DC-source
Signal generator
Loads (resistive, inductive, capacitive)
LV and MV test networks
-
8/13/2019 PV-systems.pdf
23/41
Fraunhofer IWES Fraunhofer IWES
Slide 23, Power System Service Seminar, 31.03.2011
2. Power System Services of PV-systemsTest procedures for PV-systems Testing procedures
Test of behaviour of DER unitsduring grid faults normally donewith FRT-containers
FRT containers designed for highpower ratings (100 kW < P < 6 MVA)
Not applicable for string inverters (P< 20kW)
NS-FRT tests with network simulator
Calculation of voltage phasors at
LV network for faults (3phaseand 2 phase) in HV and MVnetworks
Real reproduction of voltagecurves with low ohmicprogrammable AC-networksources
Real emulation of networkimpedance by adjustable R-L-network
1_HS
1_MS
2_MS 2_NS
110
kV
Netz
20 kV
Kabel
0,4 kV
Kabel
110 kV
FL
EUT
-
8/13/2019 PV-systems.pdf
24/41
Fraunhofer IWES Fraunhofer IWES
Slide 24, Power System Service Seminar, 31.03.2011
2. Power System Services of PV-systemsTest procedures for PV-systems Testing procedures
Unbalanced 2 phase fault
MV/LV transformer: Dd
Unbalanced 2 phase fault
MV/LV transformer: Dy
-
8/13/2019 PV-systems.pdf
25/41
Fraunhofer IWES Fraunhofer IWES
Slide 25, Power System Service Seminar, 31.03.2011
3. Application of power system servicesVoltage Control
Source: Fraunhofer IWES, Project Aktives, intelligentes Niederspannungsnetz
-
8/13/2019 PV-systems.pdf
26/41
Fraunhofer IWES Fraunhofer IWES
Slide 26, Power System Service Seminar, 31.03.2011
3. Application of power system servicesVoltage Control
Source: Fraunhofer IWES, Project Aktives, intelligentes Niederspannungsnetz
-
8/13/2019 PV-systems.pdf
27/41
Fraunhofer IWES Fraunhofer IWES
Slide 27, Power System Service Seminar, 31.03.2011
3. Application of power system servicesVoltage Control
Source: Fraunhofer IWES, Project Aktives, intelligentes Niederspannungsnetz
-
8/13/2019 PV-systems.pdf
28/41
-
8/13/2019 PV-systems.pdf
29/41
-
8/13/2019 PV-systems.pdf
30/41
Fraunhofer IWES Fraunhofer IWES
Slide 30, Power System Service Seminar, 31.03.2011
3. Application of power system servicesVoltage Control
Source: Fraunhofer IWES, Project Aktives, intelligentes Niederspannungsnetz
-
8/13/2019 PV-systems.pdf
31/41
Fraunhofer IWES Fraunhofer IWES
Slide 31, Power System Service Seminar, 31.03.2011
3. Application of power system servicesVoltage Control
Source: Fraunhofer IWES, Project Aktives, intelligentes Niederspannungsnetz
-
8/13/2019 PV-systems.pdf
32/41
Fraunhofer IWES Fraunhofer IWES
Slide 32, Power System Service Seminar, 31.03.2011
3. Application of power system servicesVoltage Control Reactive power
Selective voltage changeby power factor control of
DER unit
k: network impedanceangle
SSC: Short circuit power
SA,max: nominal power ofDER unit
( )
SC
kVA
aVS
S
u
+
=
cosmax,
Source: B. Valov, Volle Nutzung der Netzkapazitt und Spannungsstabilisierung durch neues Auslegungskonzept fr PV-Kraftwerke, 24.Symposium Photovoltaische Solarenergie, Bad Staffelstein, 2009
-
8/13/2019 PV-systems.pdf
33/41
Fraunhofer IWES Fraunhofer IWES
Slide 33, Power System Service Seminar, 31.03.2011
3. Application of power system servicesVoltage Control Case studies
Generic network case studies
Case A: Single feeder network,
single PV-system
Case B: Single feeder network, fivePV-systems
Case C: Four feeders, each with 5 PV-
systems Different feeders length are
considered (100m, 300, 600, 900m)
-
8/13/2019 PV-systems.pdf
34/41
Fraunhofer IWES Fraunhofer IWES
Slide 34, Power System Service Seminar, 31.03.2011
3. Application of power system servicesVoltage Control Potential of reactive power
Case C: 4 feeder, 5 PV-systems perfeeder, cos =0.9, max. voltage rise3%
Relative increase of connectable PVsystems due to reactive powervoltage control varies between 1.5and more than 2.
At larger network impedance angles
(resp. short feeder) the thermallimits of the network transformer orthe cables may be reached.
Example (Sk = 1,2 MVA, k = 25 ,4x5 PV-systems)
cos = 1.0: 216 kW in total
cos = 0.9: 378 kW in total(factor of 1.75)
0
0.5
1
1.5
2
2.5
3
3.5
4
15202530354045network impedance angle []
max.PVpow
er@
cos
=0.9/
max.PVpower@cos
=1
[k
W/kW] cos0,9u
cos= 1
P_PV > thermal limit ofcables
P_PV > SrT (630kVA)
-
8/13/2019 PV-systems.pdf
35/41
Fraunhofer IWES Fraunhofer IWES
Slide 35, Power System Service Seminar, 31.03.2011
3. Application of power system servicesVoltage Control Active network components
Source: Fraunhofer IWES, Project Aktives, intelligentes Niederspannungsnetz
-
8/13/2019 PV-systems.pdf
36/41
Fraunhofer IWES Fraunhofer IWES
Slide 36, Power System Service Seminar, 31.03.2011
3. Application of power system servicesVoltage Control Active network components
Extended Use of the available voltageband
Case C: 4 feeder, 5 PV-systems per
feeder Switchable MV/LV transformers provide an
alternative way to control the voltage inLV networks.
transformer with steps 2x 2.5%
allowed voltage rise increases from 3%to 8%
max. connection power increase by afactor of 2.7
In particular useful for longer feeders
Example (Sk = 1,2 MVA, k = 25 , 4x5 PV-systems)
cos = 1.0: 216 kW in total
cos = 0.9: 378 kW in total
Smart transformer: 538 kW in total
10
20
30
40
50
60
70
80
15202530354045
network impedance angle []
P_
PV
/Sk[%]
cos = 0,9u
switchable MV/LV
transformer
cos = 1
P_PV > SrT transformer
thermal lim it of cable NAYY
-
8/13/2019 PV-systems.pdf
37/41
-
8/13/2019 PV-systems.pdf
38/41
Fraunhofer IWES Fraunhofer IWES
Slide 38, Power System Service Seminar, 31.03.2011
Backup
-
8/13/2019 PV-systems.pdf
39/41
-
8/13/2019 PV-systems.pdf
40/41
Fraunhofer IWES Fraunhofer IWES
Slide 40, Power System Service Seminar, 31.03.2011
3. Application of power system servicesVoltage Control Effect of network parameters Effect of different cable types
Sk and k decrease with increasing distance to the substation
The cable type determines how fast Sk and k decrease
At long distances the effect of the cable type dominates
Example: 600m distance, NAYY 4x150mm Sk = 1,2 MVA; k = 25
0
1
2
3
4
5
6
0 200 400 600 800 1000
distance [m]
netw
orkshort-crcuitpower[MV
A]
NA2XRY 4x70mm
NAYY 2x4x150mm
NAYY 4x95mm
NAYY 4x150mm
NAYY 4x240mm
10
15
20
25
30
35
40
45
50
0 200 400 600 800 1000
distance [m]
networkimpedanceangle[
NA2XRY 4x70mm
NAYY 2x4x150mm
NAYY 4x95mm
NAYY 4x150mm
NAYY 4x240mm
-
8/13/2019 PV-systems.pdf
41/41
Fraunhofer IWES Fraunhofer IWES
Slide 41, Power System Service Seminar, 31.03.2011
3. Application of power system servicesVoltage Control Maximum permissible connection power Power factor cos =1, max.
voltage rise 3%)
Sk
and K
at the end of thefeeder are sufficient todescribe maximumpermissible PV power
The serial placement of PVsystems leads to a higheramount of connectable
power because of the lowervoltage rise of the PVsystems connected tostronger network points
Case C (parallel feeders)results in similar curves, but
per feeder PV power islower, because of thevoltage rise in thesubstations LV-busbar
1
2
3
4
5
6
7
8
15202530354045
network impedance angle []
(feeder length 100m to 900m)
P_PV
max/Sk[%]
5 PV Systems, Transf.
630kVA uk 6% and cables 5 PV Systems, Transf. 630kVA,
uk 4%, and cables 4x150mm
5 PV Systems, Transf.
630kVA, uk 4% and cables
4x95mm1 PV-System, transformer
630kVA, uk 4% and cables
4x150mm1 PV System, transf. 630kVA, uk
4% and cables 4x95mm