PV-systems.pdf

download PV-systems.pdf

of 41

Transcript of PV-systems.pdf

  • 8/13/2019 PV-systems.pdf

    1/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 1, Power System Service Seminar, 31.03.2011

    Power System Services of PV-systems:Requirements, testing and application in Germany

    D. Geibel, Dr. G. Arnold, Dr. T. Degner

    Fraunhofer Institute Wind Energy and Energy Systems Technology Fraunhofer IWES

    DERlab Workshop on Power System Services31.03.2011, Risoe

  • 8/13/2019 PV-systems.pdf

    2/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 2, Power System Service Seminar, 31.03.2011

    Power System Services of PV-systems:Requirements, testing and application in Germany Introduction

    Power System Services of PV-systems

    Grid code requirements

    Test procedures for PV-systems

    Application of power system services Voltage control by reactive power

    Voltage control by active network components

    Conclusions

  • 8/13/2019 PV-systems.pdf

    3/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 3, Power System Service Seminar, 31.03.2011

    1. IntroductionGenerating capacities in Germany

    Generation capacity inGermany

    137.5 GW (in 2009) intotal

    46 GW of RES

    Wind

    Increase since 1994

    25 GW in 2009

    PV

    Increase since 2004

    17.3 GW in 2010

    52 GW in 20201 Diagram: Fraunhofer IWES, Data: Erneuerbare Energien in Zahlen, BMU, 2010

    1: National development plan for renewable energies

  • 8/13/2019 PV-systems.pdf

    4/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 4, Power System Service Seminar, 31.03.2011

    1. IntroductionInterconnection of PV-systems

    Interconnection of PV-systemsmainly to LV due to power

    ratings

    Interconnected of PV-systems toHV or MV

    18%1 (end of 2008)

    Jan. 2009 to Sept. 2010

    9335 MWp new installed PV-power

    Share of PV-systems withrated power > 100kWp: 3278MWp

    Grid integration of PV ondistribution system level

    Diagram: Fraunhofer IWES; Data: Information of new installed PV-systems of BNetzA

    1EEG Statistikbericht 2008; BNetzA

  • 8/13/2019 PV-systems.pdf

    5/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 5, Power System Service Seminar, 31.03.2011

    1. IntroductionGrid integration constraints

    Power System Stability

    Rotor angle stability

    Frequency stability

    Voltage stability

    Network Constraints

    Capacity of lines, cables,transformers

    Power quality

    Steady-state voltage limits

    Harmonics

    Flicker

    Source: Definition and Classification of Power System Stability, IEEE/CIGRE JointTask Force on Stability Terms and Definitions, IEEE Transactions on Power Systems,

    Prabha Kundur et. al.

  • 8/13/2019 PV-systems.pdf

    6/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 6, Power System Service Seminar, 31.03.2011

    1. IntroductionGrid integration challenges and approaches

    Transmission network (HV/EHV)

    Challenges Power generation not located to

    load centers

    Integration of offshore windparks

    Approaches

    Grid reinforcement

    Power System Services of DERunits

    Central storages

    FACTS

    Distribution network (MV/LV)

    Challenges Bidirectional power flows

    Voltage control

    Approaches

    Power System Services of DERunits

    Active network components

    Manageability of loads

    Local storages

    Grid reinforcement

  • 8/13/2019 PV-systems.pdf

    7/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 7, Power System Service Seminar, 31.03.2011

    2. Power System Services of PV-systemsGrid code requirements Overview

    Pre-condition for connection

    Fulfilling of technical minimum standards concerningelectrical behaviour (6 EEG)

    Link to grid codes

    Approval of Conformity by certificates (64 EEG)

    Grid codes in Germany

    Describe behaviour of DER units in order to meet systemneeds

    High voltage / Extra high voltage

    Transmission Code 2007

    Medium voltage

    BDEW MV-guideline

    Low voltage

    E VDE-AR-N 4105 (Draft version)

  • 8/13/2019 PV-systems.pdf

    8/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 8, Power System Service Seminar, 31.03.2011

    2. Power System Services of PV-systemsGrid code requirements Overview

    Distribution code DER plants connected MVdistribution grid

    Technical requirements for DER plants (steadystate / transient)

    Basic procedure for approval of conformity

    Link to Technical Guidelines of FGW for verification

    of requested electrical behaviour

    FGW TR3: Testing procedures

    Link to IEC 61400-21

    Adaptation of test procedures for PV

    FGW TR4: Modelling

    FGW TR8: Certification

  • 8/13/2019 PV-systems.pdf

    9/41

    Fraunhofer IWES Fraunhofer IWESSlide 9, Power System Service Seminar, 31.03.2011

    2. Power System Services of PV-systemsGrid code requirements Overview

    Static requirements

    Limitation of power-qualitycharacteristic parameters

    Harmonics, interharmonics andhigher frequency components

    Flicker

    Switching operation

    Active power control

    Active power reduction bynetwork operator

    Active power reduction at over-frequency

    Reactive power control

    Dynamic requirements

    Fault-ride-through (FRT) capabilitywith no disconnection of DER plantsduring the voltage dip

    No change of active powergeneration after faults

    Feed-in of reactive power during thefault for voltage stabilization

    Limitation of short-circuit current

  • 8/13/2019 PV-systems.pdf

    10/41

  • 8/13/2019 PV-systems.pdf

    11/41

    Fraunhofer IWES Fraunhofer IWESSlide 11, Power System Service Seminar, 31.03.2011

    2. Power System Services of PV-systemsGrid code requirements Active power control

    Automatic active powerreduction depending on grid

    frequency

    Grid support in case ofpower surplus

    Avoiding grid instabilities

    due to immediatedisconnection of largegeneration capacities

    Under normal gridconditions no impact on

    energy yield For inverter no additional

    hardware required

  • 8/13/2019 PV-systems.pdf

    12/41

    Fraunhofer IWES Fraunhofer IWESSlide 12, Power System Service Seminar, 31.03.2011

    2. Power System Services of PV-systemsGrid code requirements Active power control

    Measurement results of aPower-One PVI-55.0 Central

    inverter at Fraunhofer IWES

    Start of reduction at fGrid >50.20 Hz

    Instantaneously available

    power at 50.20Hz is used foractive power reductioncalculations

    Amount of active powerreduction is determined by

    droop with of 40% per Hz Internal hysteresis: Rerise

    of active power if fgrid 50.05 Hz

    Power-One PVI-55.0 CentralMeasurement results Fraunhofer IWES

  • 8/13/2019 PV-systems.pdf

    13/41

    Fraunhofer IWES Fraunhofer IWESSlide 13, Power System Service Seminar, 31.03.2011

    2. Power System Services of PV-systemsGrid code requirements Reactive power capability

    Maintenance of grid voltage

    Generating unit must beable to provide reactivepower during normaloperation

    Required power factor cos

    at network connection pointof plant:

    0.95underexcited to0.95overexcited

    Impact on inverter design

    Apparent power has to beincreased

    Power-One PVI-55.0 CentralMeasurement results Fraunhofer IWES

  • 8/13/2019 PV-systems.pdf

    14/41

  • 8/13/2019 PV-systems.pdf

    15/41

    Fraunhofer IWES Fraunhofer IWESSlide 15, Power System Service Seminar, 31.03.2011

    2. Power System Services of PV-systemsGrid code requirements Fault-Ride-Through FRT)

    Source: Erzeugungsanlagen am Mittelspannungsnetz. BDEW, Release June 2008

    Generating units must stay connectedduring grid faults

    Different FRT-curves

    Type 1: Direct coupled synchronousgenerators

    Type 2: all other generating units

    Requested behaviour of generating unitdepends on mainly two factors:

    Depth of voltage dip

    Duration of voltage dip

    Behaviour of unit:

    Stay connected during fault

    Short time disconnection withresynchronisation within 2s at most

    Reactive current injection + shorttime disconnection

    No requirements

  • 8/13/2019 PV-systems.pdf

    16/41

    Fraunhofer IWES Fraunhofer IWESSlide 16, Power System Service Seminar, 31.03.2011

    2. Power System Services of PV-systemsGrid code requirements Fault-Ride-Through FRT)

    Reactive current injection of unitaccording to Transmission Code 2007

    Amount of reactive power isdetermined by k-factor

    k = Ib/In/ U/Un

    Depth of grid fault

    Reactive current before fault

    Voltage before fault Response time 20 ms

    Max. reactive current: Ib 1.0 In

    Max. duration of reactive currentinjection: time of fault clearing +500ms

    In terms of unsymmetrical faults arelease of overvoltage protection hasto be avoided

  • 8/13/2019 PV-systems.pdf

    17/41

    Fraunhofer IWES Fraunhofer IWESSlide 17, Power System Service Seminar, 31.03.2011

    2. Power System Services of PV-systemsGrid code requirements Fault-Ride-Through FRT)

    Influence of reactivecurrent on grid

    voltage during fault

    For both cases thesame voltage dip isused

    k-factor 0: noreactive current

    k-factor 2: due toreactive currentvoltage is raised

    Power-One PVI-55.0 CentralMeasurement results Fraunhofer IWES

  • 8/13/2019 PV-systems.pdf

    18/41

    Fraunhofer IWES Fraunhofer IWESSlide 18, Power System Service Seminar, 31.03.2011

    2. Power System Services of PV-systemsGrid code requirements Implementation

    Source: SMA Solar Technology AG

  • 8/13/2019 PV-systems.pdf

    19/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 19, Power System Service Seminar, 31.03.2011

    2. Power System Services of PV-systemsTest procedures for PV-systems Testing environments

    Recuperation unit

    AC-network simulator

    Impedance network

    PV-simulator AC-network simulator

    with additional

    impedance network

    90 kVA

    Linear amplifiers

    4-quadrant

    operation PV-simulator 30kW

    Special testingequipment for PV-systems with higher

    power ratings

  • 8/13/2019 PV-systems.pdf

    20/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 20, Power System Service Seminar, 31.03.2011

    2. Power System Services of PV-systemsTest procedures for PV-systems Testing environments

  • 8/13/2019 PV-systems.pdf

    21/41

  • 8/13/2019 PV-systems.pdf

    22/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 22, Power System Service Seminar, 31.03.2011

    2. Power System Services of PV-systemsTest procedures for PV-systems Testing environments

    6 MVA FRT-container (MV)

    1 MVA AC-network simulator (LV)

    1 MW DC-source

    Signal generator

    Loads (resistive, inductive, capacitive)

    LV and MV test networks

  • 8/13/2019 PV-systems.pdf

    23/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 23, Power System Service Seminar, 31.03.2011

    2. Power System Services of PV-systemsTest procedures for PV-systems Testing procedures

    Test of behaviour of DER unitsduring grid faults normally donewith FRT-containers

    FRT containers designed for highpower ratings (100 kW < P < 6 MVA)

    Not applicable for string inverters (P< 20kW)

    NS-FRT tests with network simulator

    Calculation of voltage phasors at

    LV network for faults (3phaseand 2 phase) in HV and MVnetworks

    Real reproduction of voltagecurves with low ohmicprogrammable AC-networksources

    Real emulation of networkimpedance by adjustable R-L-network

    1_HS

    1_MS

    2_MS 2_NS

    110

    kV

    Netz

    20 kV

    Kabel

    0,4 kV

    Kabel

    110 kV

    FL

    EUT

  • 8/13/2019 PV-systems.pdf

    24/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 24, Power System Service Seminar, 31.03.2011

    2. Power System Services of PV-systemsTest procedures for PV-systems Testing procedures

    Unbalanced 2 phase fault

    MV/LV transformer: Dd

    Unbalanced 2 phase fault

    MV/LV transformer: Dy

  • 8/13/2019 PV-systems.pdf

    25/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 25, Power System Service Seminar, 31.03.2011

    3. Application of power system servicesVoltage Control

    Source: Fraunhofer IWES, Project Aktives, intelligentes Niederspannungsnetz

  • 8/13/2019 PV-systems.pdf

    26/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 26, Power System Service Seminar, 31.03.2011

    3. Application of power system servicesVoltage Control

    Source: Fraunhofer IWES, Project Aktives, intelligentes Niederspannungsnetz

  • 8/13/2019 PV-systems.pdf

    27/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 27, Power System Service Seminar, 31.03.2011

    3. Application of power system servicesVoltage Control

    Source: Fraunhofer IWES, Project Aktives, intelligentes Niederspannungsnetz

  • 8/13/2019 PV-systems.pdf

    28/41

  • 8/13/2019 PV-systems.pdf

    29/41

  • 8/13/2019 PV-systems.pdf

    30/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 30, Power System Service Seminar, 31.03.2011

    3. Application of power system servicesVoltage Control

    Source: Fraunhofer IWES, Project Aktives, intelligentes Niederspannungsnetz

  • 8/13/2019 PV-systems.pdf

    31/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 31, Power System Service Seminar, 31.03.2011

    3. Application of power system servicesVoltage Control

    Source: Fraunhofer IWES, Project Aktives, intelligentes Niederspannungsnetz

  • 8/13/2019 PV-systems.pdf

    32/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 32, Power System Service Seminar, 31.03.2011

    3. Application of power system servicesVoltage Control Reactive power

    Selective voltage changeby power factor control of

    DER unit

    k: network impedanceangle

    SSC: Short circuit power

    SA,max: nominal power ofDER unit

    ( )

    SC

    kVA

    aVS

    S

    u

    +

    =

    cosmax,

    Source: B. Valov, Volle Nutzung der Netzkapazitt und Spannungsstabilisierung durch neues Auslegungskonzept fr PV-Kraftwerke, 24.Symposium Photovoltaische Solarenergie, Bad Staffelstein, 2009

  • 8/13/2019 PV-systems.pdf

    33/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 33, Power System Service Seminar, 31.03.2011

    3. Application of power system servicesVoltage Control Case studies

    Generic network case studies

    Case A: Single feeder network,

    single PV-system

    Case B: Single feeder network, fivePV-systems

    Case C: Four feeders, each with 5 PV-

    systems Different feeders length are

    considered (100m, 300, 600, 900m)

  • 8/13/2019 PV-systems.pdf

    34/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 34, Power System Service Seminar, 31.03.2011

    3. Application of power system servicesVoltage Control Potential of reactive power

    Case C: 4 feeder, 5 PV-systems perfeeder, cos =0.9, max. voltage rise3%

    Relative increase of connectable PVsystems due to reactive powervoltage control varies between 1.5and more than 2.

    At larger network impedance angles

    (resp. short feeder) the thermallimits of the network transformer orthe cables may be reached.

    Example (Sk = 1,2 MVA, k = 25 ,4x5 PV-systems)

    cos = 1.0: 216 kW in total

    cos = 0.9: 378 kW in total(factor of 1.75)

    0

    0.5

    1

    1.5

    2

    2.5

    3

    3.5

    4

    15202530354045network impedance angle []

    max.PVpow

    er@

    cos

    =0.9/

    max.PVpower@cos

    =1

    [k

    W/kW] cos0,9u

    cos= 1

    P_PV > thermal limit ofcables

    P_PV > SrT (630kVA)

  • 8/13/2019 PV-systems.pdf

    35/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 35, Power System Service Seminar, 31.03.2011

    3. Application of power system servicesVoltage Control Active network components

    Source: Fraunhofer IWES, Project Aktives, intelligentes Niederspannungsnetz

  • 8/13/2019 PV-systems.pdf

    36/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 36, Power System Service Seminar, 31.03.2011

    3. Application of power system servicesVoltage Control Active network components

    Extended Use of the available voltageband

    Case C: 4 feeder, 5 PV-systems per

    feeder Switchable MV/LV transformers provide an

    alternative way to control the voltage inLV networks.

    transformer with steps 2x 2.5%

    allowed voltage rise increases from 3%to 8%

    max. connection power increase by afactor of 2.7

    In particular useful for longer feeders

    Example (Sk = 1,2 MVA, k = 25 , 4x5 PV-systems)

    cos = 1.0: 216 kW in total

    cos = 0.9: 378 kW in total

    Smart transformer: 538 kW in total

    10

    20

    30

    40

    50

    60

    70

    80

    15202530354045

    network impedance angle []

    P_

    PV

    /Sk[%]

    cos = 0,9u

    switchable MV/LV

    transformer

    cos = 1

    P_PV > SrT transformer

    thermal lim it of cable NAYY

  • 8/13/2019 PV-systems.pdf

    37/41

  • 8/13/2019 PV-systems.pdf

    38/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 38, Power System Service Seminar, 31.03.2011

    Backup

  • 8/13/2019 PV-systems.pdf

    39/41

  • 8/13/2019 PV-systems.pdf

    40/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 40, Power System Service Seminar, 31.03.2011

    3. Application of power system servicesVoltage Control Effect of network parameters Effect of different cable types

    Sk and k decrease with increasing distance to the substation

    The cable type determines how fast Sk and k decrease

    At long distances the effect of the cable type dominates

    Example: 600m distance, NAYY 4x150mm Sk = 1,2 MVA; k = 25

    0

    1

    2

    3

    4

    5

    6

    0 200 400 600 800 1000

    distance [m]

    netw

    orkshort-crcuitpower[MV

    A]

    NA2XRY 4x70mm

    NAYY 2x4x150mm

    NAYY 4x95mm

    NAYY 4x150mm

    NAYY 4x240mm

    10

    15

    20

    25

    30

    35

    40

    45

    50

    0 200 400 600 800 1000

    distance [m]

    networkimpedanceangle[

    NA2XRY 4x70mm

    NAYY 2x4x150mm

    NAYY 4x95mm

    NAYY 4x150mm

    NAYY 4x240mm

  • 8/13/2019 PV-systems.pdf

    41/41

    Fraunhofer IWES Fraunhofer IWES

    Slide 41, Power System Service Seminar, 31.03.2011

    3. Application of power system servicesVoltage Control Maximum permissible connection power Power factor cos =1, max.

    voltage rise 3%)

    Sk

    and K

    at the end of thefeeder are sufficient todescribe maximumpermissible PV power

    The serial placement of PVsystems leads to a higheramount of connectable

    power because of the lowervoltage rise of the PVsystems connected tostronger network points

    Case C (parallel feeders)results in similar curves, but

    per feeder PV power islower, because of thevoltage rise in thesubstations LV-busbar

    1

    2

    3

    4

    5

    6

    7

    8

    15202530354045

    network impedance angle []

    (feeder length 100m to 900m)

    P_PV

    max/Sk[%]

    5 PV Systems, Transf.

    630kVA uk 6% and cables 5 PV Systems, Transf. 630kVA,

    uk 4%, and cables 4x150mm

    5 PV Systems, Transf.

    630kVA, uk 4% and cables

    4x95mm1 PV-System, transformer

    630kVA, uk 4% and cables

    4x150mm1 PV System, transf. 630kVA, uk

    4% and cables 4x95mm