PTAC Control Board Kit RSKP0013 Installation Instructions

20
ATTENTION INSTALLING PERSONNEL As a professional installer you have an obligation to know the product better than the customer. This includes all safety precautions and related items. Prior to actual installation, thoroughly familiarize yourself with this Instruction Manual. Pay special attention to all safety warnings. Often during installation or repair it is possible to place yourself in a position which is more hazardous than when the unit is in operation. Remember, it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use. Safety is a matter of common sense...a matter of thinking before acting. Most dealers have a list of specific good safety practices... follow them. The precautions listed in this Installation Manual are intended as supplemental to existing practices. However, if there is a direct conflict between existing practices and the content of this manual, the precautions listed here take precedence. RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION Only personnel that have been trained to install, adjust, service or repair (hereinafter, “service”) the equipment specified in this manual should service the equipment. The manufacturer will not be responsible for any injury or property damage arising from improper service or service procedures. If you service this unit, you assume responsibility for any injury or property damage which may result. In addition, in jurisdictions that require one or more licenses to service the equipment specified in this manual, only licensed personnel should service the equipment. Improper installation, adjustment, servicing or repair of the equipment specified in this manual, or attempting to install, adjust, service or repair the equipment specified in this manual without proper training may result in product damage, property damage, personal injury or death. WARNING Cancer and Reproducve Harm - www.P65Warnings.ca.gov PROP 65 WARNING FOR CALIFORNIA CONSUMERS 0140M00517-A WARNING DESCRIPTION Control board installation procedures are described in detail in these instructions. Read and follow these instructions carefully before replacing the control board. Failure to do so may result in control board damage. Pages 3 through 5 are procedures for programming the control board and the diagnostic codes for the control board. Important note: Damage to the control board can occur from failure to disconnect power supply or failure to set the master switch (located on the control board) to OFF before removing the low voltage terminal strip cover from an installed control board. Damage to this board by not following these instructions is considered misuse and not covered under either the standard unit warranty or any extended service contract. Important note: All warranty replaced boards must be returned to the parts source from which they were purchased to insure proper warranty credit. ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS Before removing the new control board from the static wrap, it is very important to discharge any static electricity. This can be accomplished in two methods. Servicer can wear a ground strap or by touching the metal chassis before replacing the board. EXISTING CONTROL BOARD REMOVAL PROCEDURES 1. Disconnect electrical power to the unit. 2. Remove front cover. 3. Remove the two mounting screws, one on each side of control board cover. Lift the cover up to gain access to the ribbon connector. Unplug ribbon connector from control board and remove cover completely. Remove the screw on right side of the control panel. 19001 Kermier Rd., Waller, TX 77484 www.amana-ptac.com IO-904B 1/2020 PTAC Control Board Kit RSKP0013 Installation Instructions is a registered trademark of Maytag Corporation or its related companies and is used under license to Goodman Company, L.P., Houston, TX, USA. All rights reserved. © 2015 - 2016, 2020 Goodman Company, L.P.

Transcript of PTAC Control Board Kit RSKP0013 Installation Instructions

Page 1: PTAC Control Board Kit RSKP0013 Installation Instructions

ATTENTION INSTALLING PERSONNELAs a professional installer you have an obligation to know the product better than the customer. This includes all safety precautions and related items.

Prior to actual installation, thoroughly familiarize yourself with this Instruction Manual. Pay special attention to all safety warnings. Often during installation or repair it is possible to place yourself in a position which is more hazardous than when the unit is in operation.

Remember, it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use.

Safety is a matter of common sense...a matter of thinking before acting. Most dealers have a list of specific good safety practices...follow them.

The precautions listed in this Installation Manual are intended as supplemental to existing practices. However, if there is a direct conflict between existing practices and the content of this manual, the precautions listed here take precedence.

RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION

Only personnel that have been trained to install, adjust, service or repair (hereinafter, “service”) the equipment specified in this manual should service the equipment. The manufacturer will not be responsible for any injury or property damage arising from improper service or service procedures. If you service this unit, you assume responsibility for any injury or property damage which may result. In addition, in jurisdictions that require one or more licenses to service the equipment specified in this manual, only licensed personnel should service the equipment. Improper installation, adjustment, servicing or repair of the equipment specified in this manual, or attempting to install, adjust, service or repair the equipment specified in this manual without proper training may result in product damage, property damage, personal injury or death.

WARNING

Cancer and Reproduc�ve Harm -www.P65Warnings.ca.gov

PROP 65 WARNINGFOR CALIFORNIA CONSUMERS

0140M00517-A

WARNING

DESCRIPTIONControl board installation procedures are described in detail in these instructions. Read and follow these instructions carefully before replacing the control board. Failure to do so may result in control board damage. Pages 3 through 5 are procedures for programming the control board and the diagnostic codes for the control board.

Important note:Damage to the control board can occur from failure to disconnect power supply or failure to set the master switch (located on the control board) to OFF before removing the low voltage terminal strip cover from an installed control board. Damage to this board by not following these instructions is considered misuse and not covered under either the standard unit warranty or any extended service contract.

Important note:All warranty replaced boards must be returned to the parts source from which they were purchased to insure proper warranty credit.

ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONSBefore removing the new control board from the static wrap, it is very important to discharge any static electricity. This can be accomplished in two methods. Servicer can wear a ground strap or by touching the metal chassis before replacing the board.

EXISTING CONTROL BOARD REMOVAL PROCEDURES

1. Disconnect electrical power to the unit.

2. Remove front cover.3. Remove the two mounting screws, one on each side of

control board cover. Lift the cover up to gain access to the ribbon connector. Unplug ribbon connector from control board and remove cover completely. Remove the screw on right side of the control panel.

19001 Kermier Rd., Waller, TX 77484www.amana-ptac.com

IO-904B1/2020

PTAC Control Board Kit RSKP0013Installation Instructions

is a registered trademark of Maytag Corporation or its related companies and is used under license to Goodman Company, L.P., Houston, TX, USA. All rights reserved.

© 2015 - 2016, 2020 Goodman Company, L.P.

Page 2: PTAC Control Board Kit RSKP0013 Installation Instructions

2

ODFANLOW

ODFAN

HIGHLINE 1

ON

24VAC-TR

ANSFO

RM

ER

IN1 GL GHB

RIBBON CONNECTOR

Left is ONPosition

REV.VALVE

BLU

EG

REE

NR

ED

YELL

OW

OR

ANG

E

YELLOW

BLUE

RED

BLACK

BLACK

IDFANLOW

IDFAN

HIGH

Heat PumpmodelsONLY.

Must notbe used on

PTC models.

4. If a remote thermostat or any low voltage accessory is being used, remove the low voltage pin connector from the low voltage terminal strip.

5. Remove the wires from the control board and unplug the thermistors from the control board. Remove the four screws that secure the control board to the control panel and remove the existing control board.

NEW CONTROL BOARD REMOVAL PROCEDURES

6. Set the new control board in place and reattach to control panel with the four screws removed in Step 5.

7. Re Reconnect the wires across the top terminals of the control board (Refer to Figure 1). They are as follows: RED 33 to Line 1 (either terminal), BROWN 34 to Heater 1, BROWN 34 to Heater 2, Power cord or BLACK 18 to Line 2 (either terminal), VIOLET 12 to Compressor, BLACK 16 to ID Fan High, RED 17 to ID Fan Low and BLACK 19 to Rev Valve. IMPORTANT NOTE: If installing on a unit with previous board refer to wiring diagrams for appropriate wiring beginning on page 8. IMPORTANT NOTE: If unit has a 2 speed relay, Remove the relay and all wires associated with it from the unit.

Note: Refer to the Serial Plate for voltage information.8. Install high and low voltage wires from the transformer to

the control board. GREY 21 from 230v or 265v to line 1, GREY 22 from COM to Line 2, BLACK 37 from LOAD to 24V Transformer Terminal and the second BLACK 37 from LOAD to the remaining 24V Transformer Terminal.

9. If Reconnect the thermistors to the control board. The BLACK thermistor connects to the IAT BLACK terminal and the RED Thermistor connects to the ICT RED terminal on the control board. The YELLOW Thermistor connects to the IDT YELLOW terminal on the control board. Note: If the unit is a heat pump, the BLUE Thermistor connects to the OCT BLUE terminal.

10. If a remote thermostat or any low voltage accessory is being used connect the low voltage pin connector to low voltage terminal strip. If replacing a previous version board you will need to use the 10 pin connector supplied with the board for low voltage accessories. Wires supplied with this kit have terminal ends on the wires. Insert the terminal end into the correctly labeled slot, push in and it will lock in place. After loading pin connector use the wire nuts supplied with the kit to wire nut the new wires onto the existing wires supplied for low voltage accessories. See Figure 2 on page 3.

11. The control board cover is now ready to be installed. The ribbon for the touch pad will need to be reconnected to the control board. Use caution not to bend or fold the ribbon (See Figure 1 for ribbon connection). Ensure that no wires are pinched or caught between the cover and the panel and then reinstall the screws removed in Step 3.

*CRITICAL STEP*This service control until it has been configured to control a heat pump or cooler. As long as the display shows Eo, the unit .

will not operate

will not operateFollow the directions on Pages 3 and 4 to set feature codes C3 and “dd”.

For C3, select option H if the unit is a heat pump or option C if the unit is a cooler with or without electric heat.For HE* and 32* models, configuration code “dd” must be set to correct cooling capacity: 7,000, 9,000, 12,000 15,000 or 17,000 btu’s.

Failure to set “C3” and “dd” configuration codes correctly will cause the unit to not operate properly.

12. Set the master switch to the ON position, restore electrical power and verify that the unit is functioning correctly.

Figure 1

Page 3: PTAC Control Board Kit RSKP0013 Installation Instructions

3

ORA

NGE

BLAC

K

RED

GRE

EN

WH

ITE

YELL

OW

BLU

E

GRE

EN w

/YEL

LOW

STR

IPE

Remote Thermostat

*Only load wires needed for accessories attached to unit.

Figure 1

CONFIGURATION SETTINGSThe control can be configured to operate a wide range of options. The options listed on the CONFIGURATION SETTINGS chart with the * are the factory default settings. If these are acceptable, then the unit does not require any additional configuration and is fully operable. To configure the unit, first select the configuration feature code setting and then an option code to change from the factory default setting.

To enter configuration feature mode:1. Press and continue to hold the up and down arrow keys

and quickly press the OFF key twice within a two (2) second time frame. The display will alternate between displaying the feature code C1, for example, and the option code 0 (factory default setting). The lower right dot on the display will flash. To select a configuration feature code, press the HEAT key until the desired configuration comes up. To scroll to a previously viewed configuration codes press the COOL key. Once you have scrolled to the correct feature, then to select the option code for your desired configuration, press either the up or down key to scroll through the options of the selected feature code.

To exit configuration mode:1. Press the OFF key. Configuration feature mode will also exit

if no keys are pressed for a period of two (2) minutes.

INITIAL BOARD PROGRAMMINGPress and continue to hold down the plus (+) and minus (-) keys at the same time. While holding the keys down, push the OFF button two (2) times, within a two (2) second time frame. The display will show two (2) dash lines and a flashing dot ( - - . ).

Release the plus (+) and minus (-) keys and press the HEAT button three (3) times. The display will alternate between C3 and O.

Press the plus (+) or minus (-) key until the display reads H (for models PTH*) or C (for models PTC*). Please check the serial plate of the PTAC to make sure you select the correct code. Once H or C is selected, press the OFF key to exit the programming.

Page 4: PTAC Control Board Kit RSKP0013 Installation Instructions

4

*Indicates factory defaultSee manufacturer for additional configuration options.

Configuration Code Configuration Feature Option Code Option

0 * Chassis Membrane *L5 Wired ThermostatrE Wireless Stat & 7-Button L0 Locked MembraneAu do not useOn do not usebP Button presentbA* Revert to CyclicA Always run fan (even if Off)C do not use

bC Revert to ContinuousC PTC (Standard Cooler)H* PTH (Standard Heat Pump)0 Service No Operation "Eo"

dC DRY (Dehumidification Cooler)dH do not useuC do not useuH do not useAC PMC (Cooler w/ Make-up Air)AH PMH (Heat Pump w/ Make-up Air)EC HEC (High Efficiency Cooler)EH HEH (High Efficiency Heat Pump)3C 32C (R-32 Cooler)3H 32H (R-32 Heat Pump)

C4 Room I.D. Digit 1 & 2 00* - 99 00* - 99C5 Room I.D. Digit 3 & 4 00* - 99 00* - 99

0* Off*1 On18 18 Hour Automatic Entry

C8 Temp. Limiting Cool 60* - 80 60* - 80C9 Temp. Limiting Heat 68 - 90, 80* 68 - 90, 80*

8* B*0 O

c3 Un-rent Cooling Temp. 45 - 95, 79* 45 - 95, 79*c4 Un-rent Heating Temp. 45 - 95, 63* 45 - 95, 63*

0* Not Twinned*5 TwinnedF* Fahrenheit Scale*C Celsius ScaleL* On, Low Fan*H On, High Fan0 Off

d6 Sensorless Un-Occ. Time 1 - 32, 18* 1 - 32, 18*d7 1st Un-Occ. Set Back Temp. 1 - 16, 2* 1 - 16, 2*d8 1st Un-Occ. Set Back Time .1, .5*, 1 - 24 .1 ,.5 ,1 - 24, .5*d9 2nd Un-Occ. Set Back Temp. 1 - 16, 3* 1 - 16, 3*dA 2nd Un-Occ. Set Back Time .5, 1* - 24 (d8) - 24, 1*db 3rd Un-Occ. Set Back Temp. 1 - 16, 6* 1 - 16, 6*dC 3rd Un-Occ. Set Back Time 1 - 24, 3* (dA) - 24, 3*dd Cooling Capacity 5 - 24 5,000 - 24,000 BTUdF Platform Group Code 00* - 99 00* - 99dH Electric Heater Size 00*, 15, 20, 25, 35, 50 00*, 15, 20, 25, 35, & 50dJ Operating Voltage 2, 3*, 4, 5 2, 3*, 4, 5r4 Room Prefix 00* - 99 00* - 99r5 Room Suffix 00* - 99 00* - 99

0* Dis-enabled*78 - 99 78 - 99

C6 Wired Occupancy

C1 Interface

C2 ID Fan Operation

C3 Model Prefix

Cd English / Metric Temp

CE Freeze Protection

C0 T-stat B/O Term.

CA Wireless Twin Unit

u3 Heat Protection

CONFIGURATION SETTINGS CHART

Page 5: PTAC Control Board Kit RSKP0013 Installation Instructions

5

Configuration Code Configuration Feature Option Code Option

0 Off1* On only when ID fan runs2 On when ID fan runs & room occupied3 Runs continuously4 On when room is occupiedE Economizer

EP Economizer with compressor assist0 Off1* May be on anytime2 Allowed on except in Off mode3 Allowed on when indoor fan runs4 Allowed on if room is occupied5 Allowed on if room is not occupied6 Allowed on when indoor humidity is high0* Door Switch1 Motion Sensor2 Front Desk3 Wired Un-rented Set Back4 Emergency Hydronic5 Load Shedding6 Alarm Sensor0* Door Switch1 Motion Sensor2 Front Desk3 Wired Un-rented Set Back4 Emergency Hydronic5 Load Shedding6 Alarm Sensor0 Not used

15-80, 25* % RH above which kit may run0 Not used

15-60, 25* % RH above which kit may run0 No affect on indoor fan1* Indoor fan forced to run with Kit

uL Config. Security Code 00* - 99 00* - 99

ub Indoor Humidity Activation

un Vent Dehumid Outdoor Humidity Level

uu Vent Dehumidification Kit Fan Force

u9 Input Pins UN2 & COM

u8 Input Pins UN1 & COM

Smart Vent OperationP0

Vent Dehumid Make-up Air Kit Operation

P2

CONFIGURATION SETTINGS CHART (CONT.)

Page 6: PTAC Control Board Kit RSKP0013 Installation Instructions

6

DIAGNOSTIC MAINTENANCE & STATUS REPORT

The Diagnostic Maintenance & Status Report provides detailed information on PTAC control operation and operational status including present modes, failures, airflow restriction warnings, operating temperatures, and past failures. The lower right hand dot on the center display flashes in this mode. In some cases the green LED located in the lower left hand corner of the touchpad below the OFF key will also be lit. This Green LED “Status Light“ only illuminates if there is an status code that has been activated and should be reviewed. In most cases, this light indicates that the indoor room filter is dirty should be cleaned or replaced. NOTE: Dirty filters cause the unit to consume more energy than normally needed to condition a room. Once the filter has been cleaned or replaced, the LED should go out. If the LED is still illuminated after the filter has been cleaned, activate the Diagnostic and Status mode to view any active codes. The unit may need additional cleaning or maintenance of the evaporator or condenser coils. Please perform this step before calling a servicer. A servicer should be called only if cleaning the filter or coils does not clear the status code or the code indicates that servicer should be called.

DIAGNOSTIC STATUS REPORT MODE.

To enter Diagnostic Status Report mode, press and hold the up and down arrows and, while holding, quickly press the COOL key twice.

Active Failures.• If there are no active failures or lockouts, the display will show a double dash, “- -”. If there is a code listed, see the unit “Diagnostic

Codes” chart for a list of definitions. Operating Temperatures.

• If not in Diagnostic Status Report Mode, enter as instructed above and press the Fan Speed key.

• If already in Diagnostic Status Report mode, press the Fan Speed key. The display will show the temperature of the desired set point, SP; the temperature at the wireless thermostat, rL; the indoor ambient temperature behind the filter, IA; the indoor coil temperature, IC; the indoor discharge air temperature, Id; the outdoor coil temperature, OC; the outdoor ambient temperature, OA; and the spare probe temperature, IH. If any of the probes are not populated the display will show the corresponding failure code.

Past Failure Log

• If not in Diagnostic Status Report Mode, enter as instructed above and press the Fan Speed key twice.

• If already in Diagnostic Status Report mode, press the Fan Speed key. While the display is showing operating temperatures,

the last 10 failure codes active or past can be requested by pressing the Fan Speed key again. The codes are displayed last entry first followed subsequently by each preceding code.

Note that modes F1 and Fd are also displayed in the normal control operation (see “Diagnostic Codes” chart).

To exit Diagnostic Status Report mode, press the OFF key.

Page 7: PTAC Control Board Kit RSKP0013 Installation Instructions

7

STATUS DISPLAY ERROR LIGHT

SUGGESTED ACTION

FPFreeze Protection Engaged. The room temperature measured by the wireless remote thermostat or indoor ambient thermistor active sensor falls below 40°F.

Y N No Action required. This setting will disengage when the room temperature rises above 43°F.

Fd Front Desk switch is closed. All outputs are switched off. Y N Open front desk switch to allow occupant unit operation.

Eo Un-Configured Service Board -All operation held awaiting configuration

Y Y Enter Configuration Menu and set "C3" to "C" for coolers with electric heat or "H" for heat pumps.

EH Emergency Hydronic Engaged. The EHH switch is closed.Compressor is switched off.

Y N Open front emergency hydronic switch to allow occupant unit operation.

LS Load Shedding Engaged. The LS switch is closed.Compressor and Electric heat is switched off.

Y N Open load shedding switch to allow occupant unit operation.

On Control is configured to respond to a wired thermostat Y N No action if a wired thermostat is being used.Otherwise, see Configuration Settings.

oP Open Door Lockout(DS1 & DS2 open; wireless)

Y Y Close Room Door.Unit will not condition space with door open.

nP Window Switch Lockout -(LS & INN open)

Y Y Close Room Door or Window.Unit will not condition space with door or window open.

HP Heat Sentinel -(WIAT > u3)

Y N No action required. This setting will disengage when the room temperature falls.

UR Un-Rented Status(EHH & INN or wireless)

Y N Front Desk needs to set to Rented mode (if applicable).

Indoor Ambient Thermistor reads outside therange -20°F to 200°F & the wireless thermostat is notcommunicating to the unit control or

Indoor Ambient Thermistor (IAT) without a wireless remotethermostat reads outside the range -20°F to 200°F.

F2 Wireless Remote Thermostat failure N N Replace Wireless Thermostat.

F3 Indoor Ambient Thermistor readsoutside the range -20°F to 200°F

Y N Replace black Indoor Ambient Thermistor.

F4 Indoor Coil Thermistor either aboveor below operating tolerances.

N Y Replace Red Indoor Coil Thermistor.

F5 Wireless Thermostat failure. N Y Attempt to rebind Wireless Thermostat or Replace Wireless Thermostat.

F6 Indoor Discharge Thermistor either aboveor below operating tolerances.

N Y Replace Yellow Indoor Discharge Thermistor.

Fb Low Remote Battery Warning. N Y Replace Batteries in Wireless Devices.

H1 High Voltage Protection engaged.Power supply voltage is to high.

Y N Check for incoming power at correct voltage.

br Brown Out Protection engaged.Power was lost or voltage is low.

N N Check for incoming power at correct voltage.

L6 Discharge Air Too Hot. N Y Clean Filter or Remove Air Blockage.

LC Outdoor Coil Thermistor temperature high. N Y Clean Condenser Coils, Check Fan for fault. Code will reset after cleaning.

C2Indoor Air Recirculation. Large delta between thermostat andreturn.

N Y Clean Filter or Remove Air Blockage or CloseVent Door or Improve indoor to outdoor seal.

C5 Outdoor Coil temperature too high for outdoor ambienttemperature.

N Y Check for Blocked Outdoor Air or Clean Coil.

C1 Indoor Coil is freezing up. N Y Clean filter, Check for fan and blower operation,Check for Refrigerant loss or Restricted capillary tube.

C3 Indoor Coil is freezing up. N Y Clean filter, Check for fan and blower operation,Check for Refrigerant loss or Restricted capillary tube.

C4 Indoor Coil froze up. N Y Clean filter, Check for fan and blower operation,Check for Refrigerant loss or Restricted capillary tube.

C6 Poor Unit Performance. N Y Check for blower motor, compressor, or electric heat operation.

C7 Indoor Freezing Lockout (ICT - IAT > 20) +10 Min N Y Clean filter, Check for fan and blower operation,Check for Refrigerant loss or Restricted capillary tube.

MOD

ESM

ODES

Y Y Replace black Indoor Ambient Thermistor or Wireless Remote Thermostat.

F1

CODEM

ODES

MOD

ES

DIAGNOSTIC CODES

Page 8: PTAC Control Board Kit RSKP0013 Installation Instructions

8

HIG

H V

OLT

AG

E!D

ISC

ON

NEC

T A

LL P

OW

ER B

EFO

RE

SER

VIC

ING

OR

INST

ALL

ING

TH

ISU

NIT

. M

ULT

IPLE

PO

WER

SO

UR

CES

MAY

BE

PRES

ENT.

FA

ILU

RE

TOD

O S

O M

AY C

AU

SE P

RO

PER

TY D

AM

AG

E, P

ERSO

NA

L IN

JURY

OR

DEA

TH.

WIRING DIAGRAMS

Single motor

TO

UNIT

MUST

BE

PROPERLY

POLARIZED

(FOR

5V)

AND

GROUNDED.

R

TO:

G,

W2

COOL

UNIT

G,

Y/W1

4

ON

UNITS

WITH

FRONT

DESK

CONTROL

SWITCH.

R

TO:

G,

W2

-----

2ND STAGE

G,

Y/W1

G

CURRENT:

.1FUNCTION

1ST STAGE

NOTES:

1ST

STAGEHEAT

HEAT

THERMOSTAT

USED

HEAT

POWER

CORD

TO

LINE

2.

CURRENT:

.1

OFF

NOTES:

W/ELECTRIC HEAT

5

BK18

ON

LINE

2

WITH

FUSE

SHOWN

CONNECTED

FOR

265V.

FOR

230V

&

11 5 V,

CONNECT

4

ON

UNITS

WITH

FRONT

DESK

CONTROL

SWITCH.

2ND

STAGE

ON

A

STRAIGHT

1ST STAGE

FUNCTION

CURRENT: .1ANTICIPATOR

3

ON

HEAT

PUMP

MODELS

ONLY.

OFF

2ND

STAGE

G,B,Y/W1

HEAT

1

WARNING:

DISCONNECT

POWER

BEFORE

SERVICING.

WIRING

-----

HEAT PUMP W/AUXILIARY

REMOTE THERMOSTAT OPERATION

TO

UNIT

MUST

BE

PROPERLY

POLARIZED

(FOR

265 )

AND

GROUNDED.

6

FOR

REMOTE

OPERATION,

SEE

CONFIGURATION

CHART.

ANTICIPATOR

FUNCTION

1

ARNING:

DISCONNECT

POWER

BEFORE

SERVICING.

WIRING

*

ELECTRIC HEAT

2

RIBBED

WIRE

MUST

BE

CONNECTED

AS

SHOWN

COOLING UNIT

G,

Y/W1

ELECTRIC HEAT

G

3

ON

HEAT

PUMP

MODELS

ONLY.

FAN

ANTICIPATOR

G,B,Y/W1

CURRENT: .1COOLING UNIT

FUNCTION

-----

*

FOR

A

HEAT

PUMP

OFF

2

RIBBED

WIRE

MUST

BE

CONNECTED

AS

SHOWN

-----

ANTICIPATOR

R

TO:

HEAT PUMP W/AUXILIARY

REMOTE THERMOSTAT OPERATION

FAN

W/ELECTRIC HEAT

R

TO:

2ND STAGE

1ST

STAGE

G,

Y/W1

HEAT

OFF

230

265

CO

M

TRANSFORMER

LOA

D

R

BK18

YL10

ELECTRIC

GY22

C

H

HEATER

1

2

F

19

WIRE

RD13

S

C

GN

RIBBED

CAP

ODFAN/COMP

5

20

FUSE

BK37 BK37

GY21

RD33

7 IF SUPPLY VOLTAGE IS 208V/230V USE THE 230V TAP ON TRAN SFORMER. IF SUPPLY VOLTA GE IS 265V USE THE 265V TAP ON TR ANSFORMER. 115V TRANSFORMER NOT SHOWN.

7

LINE 1

E1

HEATER 1 HEATER 2

E2 E3 E4 E5 E6 E7

LINE 2 COMPRESSOR

K4 K5 K6

E11E12

ON / OFFMASTER SWITCH

CP4

SW2 P10

P2

P5CR11

X1

X3

X2

X4

M2M1

P1

P4

P8

P9

IDT

YE

LLO

WG

RE

EN

OC

TB

LUE

ICT

RE

D

24VAC

~TR

AN

SFO

RM

ER

12VA

CLA

SS 2 ON

LY

OR

AN

GE

VT12BR34 BR34

(FACTORY OR FIELD)

(FACTORY)HIGH VOLTAGE

LOW VOLTAGELOW VOLTAGE

HIGH VOLTAGE(FACTORY OR FIELD)

(FACTORY)

WIRE LEGENDWIRE LEGEND

HIGH VOLTAGE

HIGH VOLTAGE

(FACTORY OR FIELD)

(FACTORY OR FIELD)

GN1

GN1CHASSISCHASSIS

CONDUCTORS ONLY

USE COPPER

PANELPANELCONTRO LCONTRO L

CONNECCONNECT

COOLCOOL

COMP

SOLENOIDVALVE 3RE V

COOLCOOL

CONNECCONNECT

FOR CONTINUOUS FAN OPERATION SEE CONFIGURATION CHART.8

IN1 COM IN2

AUXILIARYC R GL W2 Y/W1 B GH

REMOTE THERMOSTATIAT

BLACKIN1 COM IN2

AUXILIARYC R GL W2 Y/W1 B GH

REMOTE THERMOSTATIAT

BLACK

BR14

RD17

BK16

WH15

MOTORFAN

Page 9: PTAC Control Board Kit RSKP0013 Installation Instructions

9

WIRING DIAGRAMS

Single Motor Power Vent Door

BK37

BK37

GY22GY21

LINE

265

230

RD33

VT12

5

BK18

1

HEATERELECTRIC

2

GN

WIRERIBBED

H C

YL10

RD13

S

C

R

8

LINE 1

E1

HEATER 1 HEATER 2

E2 E3 E4 E5 E6

LINE 2 COMPRESSORE

11E

12

ON / OFF

MASTER SWITCH

SW2 P10

X1

X3

M1

24VAC

~TR

AN

SFOR

MER

12VA C

LASS 2 O

NLY

P1P4

P8

P9

IDT

YE

LLO

WG

REE

NO

CT

BLU

EIC

TR

ED

OR

AN

GE

BR34BR34

CO

M

(PV)BU2

(PV)BU15

(PV)RD14

B

36

98

52

A

7

41

(PV)BK17

6

(PV)BU4

(PV)WH7

(PV)BK11

(PV)BU9

(PV)BU10

(PV)BK12

(PV)WH8

1

2

3

SWITCHON/OFF

MO ORT

LINE CO

M

208

240

FANMUFFIN

20

PCAP

FAN/COMOD

BR14

19

F

K4 K5 K6

CP4

P2

P5CR11

E7

X2

X4

POWERTVE N

VENTPOWER

3

SOLE

NO

IDVA

LVE

REV

RD17BK16

BTE

LOCKRMINAL

COMP

1ST

STAGEANTICIPATORCURRENT:

.12ND

STAGEANTICIPATORCURRENT:

.1

1ST

STAGEANTICIPATOR

REMOTE

THERMOSTAT

OPERATION

R

TO:

-----

G, Y/W1

G,B,Y/W1

G, W2

FUNCTION

OFF

1ST STAGEHEAT2ND STAGEHEAT

R

TO:

G, Y/W1

FUNCTION

OFF -----

HEAT

G**FANG**FAN

*

*

FOR

A

HEAT

PUMPTHERMOSTAT USEDON A STRAIGHTCOOL UNIT

** GL- low speedGH- high speed

W/ELECTRIC

HEATCOOLING

UNITELECTRIC

HEATHEAT

PUMP

W/AUXILIARY

CONNECT

COOLCOOL

CONNECT CONNECT

IN1 COM IN2

AUXILIARY

C R GL W2 Y/W1 B GH

REMOTE THERMOSTAT

IATBLACK

IN1 COM IN2

AUXILIARY

C R GL W2 Y/W1 B GH

REMOTE THERMOSTAT

IATBLACK

MOTORFAN

WH15

M2

(FACTORY OR FIELD)

(FACTORY)HIGH VOLTAGE

LOW VOLTAGELOW VOLTAGE

HIGH VOLTAGE(FACTORY OR FIELD)

(FACTORY)

WIRE LEGENDWIRE LEGEND

HIGH VOLTAGE

HIGH VOLTAGE

(FACTORY OR FIELD)

(FACTORY OR FIELD)

GN1

GN1CHASSISCHASSIS

CONDUCTORS ONLY

USE COPPER

PANELPANELCONTRO LCONTRO L

2

RIBBED

WIRE

MUST

BE

CONNECTED

AS

SHOWN.

NOTES1

WARNING:

DISCONNECT

POWER

BEFORE

SERVICING.

WIRING

TO

UNIT

MUST

BE

PROPERLY

POLARIZED

(FOR

265V)

AND

GROUNDED.

3

ON

HEAT

PUMP

MODELS

ONLY.

4

ON

UNITS

WITH

FRONT

DESK

CONTROL

SWITCH.

2

RIBBED

WIRE

MUST

BE

CONNECTED

AS

SHOWN.

NOTES:

1

WARNING:

DISCONNECT

POWER

BEFORE

SERVICING.

WIRING

TO

UNIT

MUST

BE

PROPERLY

POLARIZED

(FOR

265V)

AND

GROUNDED.

3

ON

HEAT

PUMP

MODELS

ONLY.

4

ON

UNITS

WITH

FRONT

DESK

CONTROL

SWITCH.

5

BK18

ON

LINE

2

WITH

FUSE

SHOWN

CONNECTED

FOR

265V.

FOR

230V

AND

115V,

CONNECT

POWER

CORD

TO

LINE

2.

7

FOR

REMOTE

OPERATION,

SEE

CONFIGARATION

CHART.

6

IF SUPPLY

VOLTAGE

IS

208V

MOVE

240V

LEAD

TO

208V

TAP

ON

TRANSFORMER.

265V

AND

115V

TRANSFORMER

NOT

SHOWN.

9

8 IF

SUPPLY

VOLTAGE

IS

208V/230V

USE

THE

230V

TAP

ON

TRANSFORMER.

IF SUPPLY VOLTAGE IS 265V USE THE 265V TAP ON TRANSFORMER.

115V TRANSFORMER NOT SHOWN.

FOR CONTINUOUS FAN OPERATION SEE CONFIGURATION CHART.

HIG

H V

OLT

AG

E!D

ISC

ON

NEC

T A

LL P

OW

ER B

EFO

RE

SER

VIC

ING

OR

INST

ALL

ING

TH

ISU

NIT

. M

ULT

IPLE

PO

WER

SO

UR

CES

MAY

BE

PRES

ENT.

FA

ILU

RE

TOD

O S

O M

AY C

AU

SE P

RO

PER

TY D

AM

AG

E, P

ERSO

NA

L IN

JURY

OR

DEA

TH.

Page 10: PTAC Control Board Kit RSKP0013 Installation Instructions

10

R

C

S

RD13

YL10

FCH

BR34BR34RD33

RIBBEDWIRE

GN

2

19

REV

VALV

ESO

LEN

OID

3

BR14

WH15

COMP

ODFAN/COMP

CAP

1ST

STAGEANTICIPATORCURRENT:

.12ND

STAGEANTICIPATORCURRENT:

.1

ELECTRIC

HEATER

20

13

5

A

24

6

B1

VT12

240

208

CO

M

LINE

OR8(CP)

6

YL1(CP)

YL5(CP)

YL3(CP)

BK16 RD17

WH 6(CP)

HEAT

PUMP

W/AUXILIARYELECTRIC

HEAT

R

TO:

-----

G,

Y/W1

G,B,Y/W1

G, W2

FUNCTION

OFF

COOL

1ST STAGEHEAT2ND STAGEHEAT

COOLING

UNITW/ELECTRIC

HEAT

CONNECTR

TO:

G,

Y/W1

FUNCTION

OFF -----

REMOTE

THERMOSTAT

OPERATION

HEAT

GFANGFAN

*

*

FOR

A

HEAT

PUMP

THERMOSTAT

USED

ON

A

STRAIGHT

COOL

UNIT

1ST

STAGEANTICIPATORCURRENT:

.12ND

STAGEANTICIPATORCURRENT:

.1

240

208

CO

M

LINE8

GY21

GY22BK37

LINE 1

E1

HEATER 1 HEATER 2

E2 E3 E4 E5 E6 E7

LINE 2 COMPRESSOR

K4 K5 K6

E11E

12

ON / OFFMASTER SWITCH

CP4

SW2 P10 P11

X1

X3

X2

X4

M2M1

24VAC

~TR

AN

SFOR

MER

12VA C

LASS 2 O

NLY

P2

P5CR11

BK18

5

BK37

CONNECT CONNECT

COOL

2

RIBBED

WIRE

MUST

BE

CONNECTED

AS

SHOWN.

NOTES1

WARNING:

DISCONNECT

POWER

BEFORE

SERVICING.

WIRING

TO

UNIT

MUST

BE

PROPERLY

POLARIZED

(FOR

265V)

AND

GROUNDED.

3

ON

HEAT

PUMP

MODELS

ONLY.

4

ON

UNITS

WITH

FRONT

DESK

CONTROL

SWITCH.

2

RIBBED

WIRE

MUST

BE

CONNECTED

AS

SHOWN.

NOTES1

WARNING:

DISCONNECT

POWER

BEFORE

SERVICING.

WIRING

TO

UNIT

MUST

BE

PROPERLY

POLARIZED

(FOR

265V)

AND

GROUNDED.

3

ON

HEAT

PUMP

MODELS

ONLY.

4

ON

UNITS

WITH

FRONT

DESK

CONTROL

SWITCH.

5

BK18

ON

LINE

2

WITH

FUSE

SHOWN

CONNECTED

FOR

265V.

FOR

230V

AND

115V,

CONNECT

POWER

CORD

TO

LINE

2.

6

IF

SUPPLY

VOLTAGE

IS

208V

MOVE

240V

LEAD

TO

208V

TAP

ON

TRANSFORMER.

265V

AND

115V

TRANSFORMER

NOT

SHOWN.

7

FOR

REMOTE

OPERATION,

SEE

CONFIGURATION

CHART.

8

IF

SUPPLY

VOLTAGE

IS

208V,

MOVE

204V

LEAD

TO

208V

TAP

ON

TRANSFORMER.

265V

AND

115V

TRANSFORMER

NOT

SHOWN.

9 FOR CONTINUOUS FAN OPERATION SEE CONFIGURATION CHART.

IN1 COM IN2

AUXILIARYC R GL W2 Y/W1 B GH

REMOTE THERMOSTATIAT

BLACKIN1 COM IN2

AUXILIARYC R GL W2 Y/W1 B GH

REMOTE THERMOSTATIAT

BLACK

FAN

MOTOR

(FACTORY OR FIELD)

(FACTORY)HIGH VOLTAGE

LOW VOLTAGELOW VOLTAGE

HIGH VOLTAGE(FACTORY OR FIELD)

(FACTORY)

WIRE LEGENDWIRE LEGEND

HIGH VOLTAGE

HIGH VOLTAGE

(FACTORY OR FIELD)

(FACTORY OR FIELD)

GN1

GN1CHASSISCHASSIS

CONDUCTORS ONLY

USE COPPER

PANELPANELCONTRO LCONTRO L

HIG

H V

OLT

AG

E!D

ISC

ON

NEC

T A

LL P

OW

ER B

EFO

RE

SER

VIC

ING

OR

INST

ALL

ING

TH

ISU

NIT

. M

ULT

IPLE

PO

WER

SO

UR

CES

MAY

BE

PRES

ENT.

FA

ILU

RE

TOD

O S

O M

AY C

AU

SE P

RO

PER

TY D

AM

AG

E, P

ERSO

NA

L IN

JURY

OR

DEA

TH.

WIRING DIAGRAMS

Single Motor Condensate Pump

Page 11: PTAC Control Board Kit RSKP0013 Installation Instructions

11

WIRING DIAGRAMS

* FOR A HEAT PUMP THERMOSTAT USED ON A STRAIGHT COOL UNIT.

** GL - LOW SPEED GH - HIGH SPEED

CM COMPDBEMFCFHPSHTRMC

RCCF

RVCTRTBVSMVSTM

R

OUTDOOR FAN MOTORCOMPRESSORDAUGHTER BOARDEVAPORATOR MOTORFAN CAPACITORFUSEHIGH PRESSURE SWITCHHEATER ELEMENTMAIN CONTROLRELAYRUN CAPACITORFOR COMPRESSOR AND FANREVERSING VALVETRANSFORMERTERMINAL BLOCKVARIABLE SPEED MOTORVARIABLE SPEEDTERMINAL BOARD

R

YL

GY

BU BR

RD

GY

TR 1

To MCBURD

PK

ALTERNATEHYDRONICHEAT

HEATER 1 HEATER 2

DANGER HIGH

MC

L1

WH

ALTERNATEOUTDOORMOTORWIRING

COM

GND

INPUTAC

TO MOTOR

VSTM OD

R 485S

VSMCMFAN

MOTOR

1650 1500 1350 1170

MC

ODFAN

LOWHIGH

L1

L2

10

10

ALTERNATEINDOORMOTORWIRING

COM

GND

INPUTAC

TO MOTOR

VSTM ID

R 485S

VSMEM

EVAPMOTOR

1400 1250 1200 1000

L1

MC

LOWHIGH

IDFAN

L2

11

11

REVVALVELOW

OPTIONALPOWERVENT/DOOR

TR 2

L1

WHOR

1

2

3

ON/OFFSWITCH

S

L2

DB

14

OPTIONALCONDENSATEPUMP

TR 3

TR 1To MC

L2

L1

BU

RD

ORGY

WH8

S

BU

DB

120

PK

PK

CO

M

NO

C

BK

DANGER HIGH VOLTAGE

24VAC

TRA

NSFO

RM

ER

12VA C

LAS

S 2 ON

LY

ON OFF

MASTER SWITCH

HEATER 1 HEATER 2LINE 1

IN1 COM IN2

AUXILIARY

C R GL W2 Y/W1 B GH

REMOTE THERMOSTAT

IATBLACK

ICT

RE

DO

CT

BLU

EIH

DO

RA

NG

EO

AT

GR

EE

NID

TY

ELL

OW

REV.VALVE

FAN

HIGH LOW

ODFAN

HIGH LOWLINE 2 COMPRESSOR

L2

L1

MC

9

BKBK

7OR

RD

TB

EMFAN

MOTOR

CMFAN

MOTOR

TR 1

265

230

S

ID

OR

13

BK

DANGER HIGH VOLTAGE

24VAC

TRA

NSFO

RM

ER

12VA C

LAS

S 2 ON

LY

ON OFF

MASTER SWITCH

HEATER 1 HEATER 2LINE 1

IN1 COM IN2

AUXILIARY

C R GL W2 Y/W1 B GH

REMOTE THERMOSTAT

IATBLACK

ICT

RE

DO

CT

BLU

EIH

DO

RA

NG

EO

AT

GR

EE

NID

TY

ELL

OW

REV.VALVE

FAN

HIGH LOW

ODFAN

HIGH LOWLINE 2 COMPRESSOR

L2

L1

MC

9

BKBK

7OR

RD

TB

EMFAN

MOTOR

CMFAN

MOTOR

TR 1

265

230

S

ID

OR

13

13

14

10

11

7

8

9

12

15!

HIG

H V

OLT

AG

E!D

ISC

ON

NEC

T A

LL P

OW

ER B

EFO

RE

SER

VIC

ING

OR

INST

ALL

ING

TH

ISU

NIT

. M

ULT

IPLE

PO

WER

SO

UR

CES

MAY

BE

PRES

ENT.

FA

ILU

RE

TOD

O S

O M

AY C

AU

SE P

RO

PER

TY D

AM

AG

E, P

ERSO

NA

L IN

JURY

OR

DEA

TH.

Dual Motor Wiring is subject to change.

Page 12: PTAC Control Board Kit RSKP0013 Installation Instructions

12

Model Starts WithHigh SpeedVSTM Tap

(Black Wire)

Low SpeedVSTM Tap(Red Wire)

PTH07*G (00 to 35) 1350 1170

PMH07*G (00 to 35) 1650 1450

PMC07*G (00 to 35) 1350 1170

PMC09*G (00 to 35) 1350 1170

PMC12*G (00 to 35) 1500 1350

PMH074/PTH073H/PTH074H (00 to 35) 1650 1500

PMH094/PTH093H/PTH094H (00 to 35) 1650 1500

PMH124/PTH123H/PTH124H (00 to 35) 1350 1170

PTH153H/PTH154H (00 to 35) 1350 1170

PMC154/PMH153G/PMH154G (00 to 35) 1350 1170

PTC072G/PTC092G (00 to 35) 1650 1500

Indoor Motor Speed Selection

1

2

3

ON/OFFSWITCH

S

DB

R

TR 1

R

TR 4

DB

L1

OPTIONALAIRDEHUMIDIFICATIONKIT

6

14

14

>>

>>

L2

OPTIONAL ELECTRIC HEATER

OPTIONALTRANSFERFAN

R

6

8

7

2

4

3

1 0

TR 1

To MC

DB

14

S

>>

>>

YL

RD

BL

OPTIONALLIGHTINGCONTROL

TR 1

To MC

7

A B

BL

DB

14

S

>>

>>

2

5

RD

R

Model Starts WithHigh SpeedVSTM Tap

(Black Wire)

Low SpeedVSTM Tap(Red Wire)

DRY093/DRY094 1350 1170

PTC173 1650 1450

HEC073/PTH073/PTH074 1350 1170

PMH094/HEC093/PTH093/PTH094 1350 1170

HEC123/PTH123/PTH124 1500 1350

PTH153/PTH154 1650 1500

PMH153/PMH154 1650 1500

PTC073/PTC074 1350 1170

PTC093/PTC094 1350 1170

PTC123/PTC124 1350 1170

PTC153/PTC154 1650 1500

Outdoor Motor Speed Selection

DIP SWITCH1 2 3 4 5

ON • • • • •

OFF • • • • •

Daughter Board Device Address Switch 1 Switch 2 Switch 3 Switch 4 Switch 5

Smart Vent/Door operations for Power Door/Vent, Economizer and Economizer(+) Board

17 0 0 0 0 1

Transfer Fan 20 0 0 1 0 0

Condensate Pump 21 0 0 1 0 1

Lighting Control 24 0 1 0 0 0

DigiAIR™ Compressor 25 0 1 0 0 1

DigiAIR™ Heater 26 0 1 0 1 0

DigiAIR™ Fan 28 0 1 1 0 0

1110

14

WIRING DIAGRAMSDual Motor (continued)

HIG

H V

OLT

AG

E!D

ISC

ON

NEC

T A

LL P

OW

ER B

EFO

RE

SER

VIC

ING

OR

INST

ALL

ING

TH

ISU

NIT

. M

ULT

IPLE

PO

WER

SO

UR

CES

MAY

BE

PRES

ENT.

FA

ILU

RE

TOD

O S

O M

AY C

AU

SE P

RO

PER

TY D

AM

AG

E, P

ERSO

NA

L IN

JURY

OR

DEA

TH.

Page 13: PTAC Control Board Kit RSKP0013 Installation Instructions

13

HIG

H V

OLT

AG

E!D

ISC

ON

NEC

T A

LL P

OW

ER B

EFO

RE

SER

VIC

ING

OR

INST

ALL

ING

TH

ISU

NIT

. M

ULT

IPLE

PO

WER

SO

UR

CES

MAY

BE

PRES

ENT.

FA

ILU

RE

TOD

O S

O M

AY C

AU

SE P

RO

PER

TY D

AM

AG

E, P

ERSO

NA

L IN

JURY

OR

DEA

TH.

WIRING DIAGRAMS

Dual Motor, 2 Speed Relay

24VAC

TRA

NSFO

RM

ER12VA C

LASS 2 ON

LY

ON OFF

MASTER SWITCH IN1 COM IN2

AUXILIARYC R GL W2 Y/W1 B GH

REMOTE THERMOSTATIAT

BLACKIC

TR

EDO

CT

BLU

EIH

DO

RAN

GE

OAT

GRE

ENID

TYE

LLO

W

REV.VALVE

IDFAN

HIGH LOW

ODFAN

HIGH LOWLINE 2 COMPRESSORHEATER 1 HEATER 2LINE 1

DANGER HIGH VOLTAGE

DUAL MOTOR, 2 SPEED RELAY

RVC

COMPS

CR

EMFAN

MOTOR

YL

RD

BK

BK

TR

6

RDGY

HTR

F 4

WH

GN

WHITEWIRE

2

1FC

BR

BR

RD

BK

WH WH

BK

CM OUTDOOR FAN MOTORCOMP COMPRESSOREM EVAPORATOR MOTORFC FAN CAPACITORF FUSEHPS HIGH PRESSURE SWITCHHTR HEATER ELEMENTRCCF RUN CAPACITOR FOR COMPRESSOR, ANY FANRVC REVERSING VALVETR TRANSFORMER

HPS

REMOTE THERMOSTATOPERATION

COOLING UNITW / ELECTRIC HEAT

FUNCTION CONNECT R TO:

OFF -----------

FAN G **

COOL G, Y / W1

HEAT G, W2 OR G, B, Y / W1*

HEAT PUMP W / AUXILIARYELECTRIC HEAT

FUNCTION CONNECT R TO:

OFF -----------

FAN G **

COOL G, Y / W1

1ST STAGE HEAT G, B, Y / W1

2ND STAGE HEAT G, W2

USE COPPERCONDUCTORS ONLY

CHASSIS GN1 CONTROL PANEL

WIRE LEGEND

HIGH VOLTAGE(FACTORY)

HIGH VOLTAGE(FACTORY OR FIELD

LOW VOLTAGE(FACTORY OR FIELD)

VT

* FOR A HEAT PUMP, THERMOSTAT USED ON A STRAIGHT COOL UNIT

** GL - LOW SPEED GH - HIGH SPEED

5

1

2

3

4

5

6

LOAD

CO

M

265

230

H

RCCF

FC

WH

BR

WARNING: DISCONNECT POWER BEFORE SERVICING. WIRING TO UNIT MUST BE PROPERLY POLARIZED (FOR 265V) AND GROUNDED.

WHITE WIRE MUST BE CONNECTED AS SHOWN.

ON HEAT PUMP MODELS ONLYBK ON LINE 2 WITH FUSE SHOWN CONNECTED FOR 265VFOR 230 V &115 V, CONNECTED POWER CORD TO LINE 2

FOR REMOTE OPERATION, SEE CONFIGURATION CHART.

IF SUPPLY VOLTAGE IS 208V / 230V, USE THE 230V TAPON TRANSFORMER.IF SUPPLY VOLTAGE IS 265V, USE THE 265V TAPON TRANSFORMER.115V TRANSFORMER NOT SHOWN.

WIRE CODE

BR BROWNBK BLACKGN GREENGY GRAYRD REDVT VIOLETWH WHITEYL YELLOW

RD

3

NOTES:

7 BOARD SHOWS R AND C, PLEASE IGNORE.

7

7

UI CONNECTION

BK

RD

CMFAN

MOTOR

Page 14: PTAC Control Board Kit RSKP0013 Installation Instructions

14

24VAC

TRA

NSFO

RM

ER12VA C

LASS 2 ON

LY

ON OFF

MASTER SWITCH IN1 COM IN2

AUXILIARYC R GL W2 Y/W1 B GH

REMOTE THERMOSTATIAT

BLACKIC

TR

EDO

CT

BLU

EIH

DO

RAN

GE

OAT

GRE

ENID

TYE

LLO

W

REV.VALVE

IDFAN

HIGH LOW

ODFAN

HIGH LOWLINE 2 COMPRESSORHEATER 1 HEATER 2LINE 1

DANGER HIGH VOLTAGE

DUAL MOTOR, NO SPEED RELAY SINGLE SPEED CONDENSER FAN

RVC

COMPS

CR

EMFAN

MOTOR

BK

YL

RD

BK

BK

TR

6

RDGY

HTR

F 4

WH

GN

WHITEWIRE

2

1FC

BR

BR

RD

BK

WH WH

BK

CM OUTDOOR FAN MOTORCOMP COMPRESSOREM EVAPORATOR MOTORFC FAN CAPACITORF FUSEHPS HIGH PRESSURE SWITCHHTR HEATER ELEMENTRCCF RUN CAPACITOR FOR COMPRESSOR, ANY FANRVC REVERSING VALVETR TRANSFORMER

HPS

USE COPPERCONDUCTORS ONLY

WIRE LEGEND

HIGH VOLTAGE(FACTORY)

HIGH VOLTAGE(FACTORY OR FIELD

LOW VOLTAGE(FACTORY OR FIELD)

VT

* FOR A HEAT PUMP, THERMOSTAT USED ON A STRAIGHT COOL UNIT

** GL - LOW SPEED GH - HIGH SPEED

5

1

2

3

4

5

6

LOAD

CO

M

265

230

H

RCCF

FC

CMFAN

MOTOR

WH

BR

WARNING: DISCONNECT POWER BEFORE SERVICING. WIRING TO UNIT MUST BE PROPERLY POLARIZED (FOR 265V) AND GROUNDED.

WHITE WIRE MUST BE CONNECTED AS SHOWN.

ON HEAT PUMP MODELS ONLYBK ON LINE 2 WITH FUSE SHOWN CONNECTED FOR 265VFOR 230 V &115 V, CONNECTED POWER CORD TO LINE 2

FOR REMOTE OPERATION, SEE CONFIGURATION CHART.

IF SUPPLY VOLTAGE IS 208V/230V, USE THE 230V TAPON TRANSFORMER.IF SUPPLY VOLTAGE IS 265V, USE THE 265V TAPON TRANSFORMER.115V TRANSFORMER NOT SHOWN.

WIRE CODE

BR BROWNBK BLACKGN GREENGY GRAYRD REDVT VIOLETWH WHITEYL YELLOW

RD

3

CHASSIS GN1 CONTROL PANEL

REMOTE THERMOSTATOPERATION

COOLING UNITW / ELECTRIC HEAT

FUNCTION CONNECT R TO:

OFF -----------

FAN G **

COOL G, Y / W1

HEAT G, W2 OR G, B, Y / W1*

HEAT PUMP W / AUXILIARYELECTRIC HEAT

FUNCTION CONNECT R TO:

OFF -----------

FAN G **

COOL G, Y / W1

1ST STAGE HEAT G, B, Y / W1

2ND STAGE HEAT G, W2

UI CONNECTION

7

7

7 BOARD SHOWS R AND C, PLEASE IGNORE.

NOTES:

HIG

H V

OLT

AG

E!D

ISC

ON

NEC

T A

LL P

OW

ER B

EFO

RE

SER

VIC

ING

OR

INST

ALL

ING

TH

ISU

NIT

. M

ULT

IPLE

PO

WER

SO

UR

CES

MAY

BE

PRES

ENT.

FA

ILU

RE

TOD

O S

O M

AY C

AU

SE P

RO

PER

TY D

AM

AG

E, P

ERSO

NA

L IN

JURY

OR

DEA

TH.

WIRING DIAGRAMS

Dual Motor No Speed Relay Single Speed Condenser Fan

Page 15: PTAC Control Board Kit RSKP0013 Installation Instructions

15

HIG

H V

OLT

AG

E!D

ISC

ON

NEC

T A

LL P

OW

ER B

EFO

RE

SER

VIC

ING

OR

INST

ALL

ING

TH

ISU

NIT

. M

ULT

IPLE

PO

WER

SO

UR

CES

MAY

BE

PRES

ENT.

FA

ILU

RE

TOD

O S

O M

AY C

AU

SE P

RO

PER

TY D

AM

AG

E, P

ERSO

NA

L IN

JURY

OR

DEA

TH.

WIRING DIAGRAMS

Dual Motor No Speed Relay Single Speed Condenser Fan

24VAC TRANSFORMER12VA CLASS 2 ONLY

ON

OFF

MAS

TER

SW

ITC

HIN

1C

OM

IN2

AUXI

LIAR

YC

RG

LW

2Y/

W1

BG

H

REM

OTE

THER

MO

STAT

IAT

BLAC

K

ICTRED

OCTBLUE

IHDORANGE

OATGREEN

IDTYELLOW

REV

.VA

LVE

ID FAN

HIG

HLO

W

OD

FAN

HIG

HLO

WLI

NE

2C

OM

PRES

SOR

HEA

TER

1H

EATE

R 2

LIN

E 1

DAN

GER

HIG

H

VO

LTAG

E

DU

AL M

OTO

R, D

C O

D M

OTO

R

RV

C

CO

MP

SC

R

YL

RD

BK

BK

TR

6

RD

GY

HTR

F4

WH

GN

WH

ITE

WIR

E2

1

RD

BK

WH

WH

BK

3

HPS

* F

OR

A H

EAT

PUM

P,

TH

ERM

OS

TAT

USE

D

ON

A S

TRAI

GH

T

CO

OL

UN

IT

** G

L -

LOW

SPE

ED

GH

- H

IGH

SPE

ED

5

1 2 3 4 5 6

LOAD

COM

265

230

HR

CC

FC

WAR

NIN

G: D

ISC

ON

NEC

T PO

WER

BEF

OR

E SE

RV

ICIN

G.

WIR

ING

TO

UN

IT M

UST

BE

PRO

PER

LY P

OLA

RIZ

ED (F

OR

265

V) A

ND

GR

OU

ND

ED.

WH

ITE

WIR

E M

UST

BE

CO

NN

ECTE

D A

S SH

OW

N.

ON

HEA

T PU

MP

MO

DEL

S O

NLY

BK O

N L

INE

2 W

ITH

FU

SE S

HO

WN

CO

NN

ECTE

D F

OR

265

VFO

R 2

30 V

&11

5 V,

CO

NN

ECTE

D P

OW

ER C

OR

D T

O L

INE

2

FOR

REM

OTE

OPE

RAT

ION

, SEE

CO

NFI

GU

RA

TIO

N C

HAR

T.

IF S

UPP

LY V

OLT

AGE

IS 2

08V

/ 230

V, U

SE T

HE

230V

TAP

ON

TR

ANSF

OR

MER

.IF

SU

PPLY

VO

LTAG

E IS

265

V, U

SE T

HE

265V

TA

PO

N T

RAN

SFO

RM

ER.

115V

TR

ANSF

OR

MER

NO

T SH

OW

N.

RD

CO

M

1650

150

0 1

350

117

0

77

230

/ 265

BK

GN

DTO

MO

TOR

VSTM

ID

RS4

85

OU

TDO

OR

MO

TOR

SPE

ED S

ELEC

TIO

N

MO

DEL

STA

RTS

WIT

HH

IGH

SPE

EDVS

TM B

LAC

KLO

W S

PEED

VSTM

RED

PTH

073G

(00

TO 3

5)13

5011

70

DR

Y093

G (0

0 TO

35)

1350

1170

DR

Y094

G(0

0 TO

35)

1350

1170

PTC

173G

(00

TO 3

5)15

0013

50

CM

OU

TDO

OR

FAN

MO

TOR

CO

MP

CO

MPR

ESSO

REM

EV

APO

RAT

OR

MO

TOR

FC

FAN

CAP

ACIT

OR

F

FU

SEH

PS

H

IGH

PR

ESSU

RE

SWIT

CH

HTR

HEA

TER

ELE

MEN

TR

CC

F

RU

N C

APA

CIT

OR

FO

R C

OM

PRES

SOR

, AN

Y FA

NR

VC

R

EVER

SIN

G V

ALVE

TR

TRAN

SFO

RM

ERVS

M

V

ARIA

BLE

SPEE

D M

OTO

RVS

TM

VAT

IABL

E SP

EED

TER

MIN

AL B

OAR

D

USE

CO

PPER

CO

ND

UC

TOR

S O

NLY

CH

ASSI

SG

N1

CO

NTR

OL

PAN

EL

WIR

E LE

GEN

DH

IGH

VO

LTAG

E(F

ACTO

RY)

HIG

H V

OLT

AGE

(FAC

TOR

Y O

R F

IELD

LOW

VO

LTAG

E(F

ACTO

RY

OR

FIE

LD)

HIG

H V

OLT

AGE

DC

HAR

NES

S(F

ACTO

RY)

7SE

E T

ABLE

FO

R M

OTO

R S

PEED

SEL

ECTI

ON

GN

VT

EM FAN

MO

TOR

FC

BR

BR

VSM

CM

FAN

MO

TOR

BKR

D

BK

RD

WH

REM

OTE

TH

ERM

OST

ATO

PER

ATIO

N

CO

OLI

NG

UN

ITW

/ EL

ECTR

IC H

EAT

FUN

CTI

ON

C

ON

NEC

T

R T

O:

O

FF

-----

------

F

AN

G **

C

OO

L

G, Y

/ W

1

H

EAT

G

, W2

OR

G

, B, Y

/ W

1*

HEA

T PU

MP

W /

AUXI

LIAR

YEL

ECTR

IC H

EAT

FUN

CTI

ON

C

ON

NEC

T

R T

O:

O

FF

-----

------

F

AN

G **

C

OO

L

G, Y

/ W

1

1

ST S

TAG

E

HEA

T

G, B

, Y /

W1

2

ND

STA

GE

H

EAT

G

, W2

8BO

ARD

SH

OW

S R

AN

D C

, PLE

ASE

IGN

OR

E.

NO

TES:

88

UI C

ON

NEC

TIO

N

WIR

E C

OD

E

BR

BR

OW

NBK

B

LAC

KG

N

GR

EEN

GY

G

RAY

RD

R

EDVT

V

IOLE

TW

H

WH

ITE

YL

YEL

LOW

Page 16: PTAC Control Board Kit RSKP0013 Installation Instructions

16

HIG

H V

OLT

AG

E!D

ISC

ON

NEC

T A

LL P

OW

ER B

EFO

RE

SER

VIC

ING

OR

INST

ALL

ING

TH

ISU

NIT

. M

ULT

IPLE

PO

WER

SO

UR

CES

MAY

BE

PRES

ENT.

FA

ILU

RE

TOD

O S

O M

AY C

AU

SE P

RO

PER

TY D

AM

AG

E, P

ERSO

NA

L IN

JURY

OR

DEA

TH.

WIRING DIAGRAMS

Dual Motor No Speed Relay Single Speed Condenser Fan

24VAC TRANSFORMER12VA CLASS 2 ONLY

ON

OFF

MAS

TER

SW

ITC

HIN

1C

OM

IN2

AUXI

LIAR

YC

RG

LW

2Y/

W1

BG

H

REM

OTE

THER

MO

STAT

IAT

BLAC

K

ICTRED

OCTBLUE

IHDORANGE

OATGREEN

IDTYELLOW

REV

.VA

LVE

ID FAN

HIG

HLO

W

OD

FAN

HIG

HLO

WLI

NE

2C

OM

PRES

SOR

HEA

TER

1H

EATE

R 2

LIN

E 1

DAN

GER

HIG

H

VO

LTAG

E

DU

AL M

OTO

R, D

C ID

MO

TOR

RVC

CO

MP

SC

R

BK

RD

YL

RD

BK

BK

TR

6

RD

GY

HTR

F4

WH

GN

WH

ITE

WIR

E2

1

RD

BK

WH

WH

BK

HPS

VT

* F

OR

A H

EAT

PUM

P,

TH

ERM

OS

TAT

USE

D

ON

A S

TRAI

GH

T

CO

OL

UN

IT

** G

L -

LOW

SPE

ED

GH

- H

IGH

SPE

ED

5

1 2 3 4 5 6

LOAD

COM

265

230

H

RC

CF

FC

CM

FAN

MO

TOR

WH

BR

WAR

NIN

G: D

ISC

ON

NEC

T PO

WER

BEF

OR

E SE

RVI

CIN

G.

WIR

ING

TO

UN

IT M

UST

BE

PRO

PER

LY P

OLA

RIZ

ED (F

OR

265

V) A

ND

GR

OU

ND

ED.

WH

ITE

WIR

E M

US

T BE

CO

NN

ECTE

D A

S SH

OW

N.

ON

HEA

T PU

MP

MO

DEL

S O

NLY

BK O

N L

INE

2 W

ITH

FU

SE S

HO

WN

CO

NN

ECTE

D F

OR

265

VFO

R 2

30 V

&11

5 V,

CO

NN

ECTE

D P

OW

ER C

OR

D T

O L

INE

2

FOR

REM

OTE

OPE

RAT

ION

, SEE

CO

NFI

GU

RAT

ION

CH

ART.

IF S

UPP

LY V

OLT

AGE

IS 2

08V

/ 230

V, U

SE T

HE

230V

TAP

ON

TR

ANSF

OR

MER

.IF

SU

PPLY

VO

LTAG

E IS

265

V, U

SE T

HE

265V

TAP

ON

TR

A NSF

OR

MER

.11

5V T

RAN

SFO

RM

ER N

OT

SHO

WN

.

RD

CO

M

1400

125

0 1

200

100

0

77

230

/ 265

BK

GN

DTO

MO

TOR

VSTM

ID

RS4

85

VSM

EM EVAP

MO

TOR

IND

OO

R M

OTO

R S

PEED

SEL

ECTI

ON

MO

DEL

STA

RTS

WIT

HH

IGH

SPE

EDVS

TM B

LAC

KLO

W S

PEED

VSTM

RED

M/P

TH07

4G (0

0 TO

35)

1250

1000

M/P

TH09

3G (0

0 TO

35)

1200

1000

M/P

TH09

3G50

1400

1250

M/P

TH09

4G (0

0 TO

35)

1200

1000

M/P

TH09

4G50

1400

1250

M/P

TH12

3G (0

0 TO

35)

1250

1000

M/P

TH12

3G50

1400

1250

M/P

TH12

4G (0

0 TO

35)

1250

1000

M/P

TH12

4G50

1400

1250

CM

OU

TDO

OR

FAN

MO

TOR

CO

MP

CO

MPR

ESSO

REM

EV

APO

RAT

OR

MO

TOR

FC

FAN

CAP

ACIT

OR

F

FU

SEH

PS

H

IGH

PR

ESSU

RE

SWIT

CH

HTR

HEA

TER

ELE

MEN

TR

CC

F

RU

N C

APA

CIT

OR

FO

R C

OM

PRES

SOR

, AN

Y FA

NR

VC

R

EVER

SIN

G V

ALVE

TR

TRAN

SFO

RM

ERVS

M

V

ARIA

BLE

SPEE

D M

OTO

RVS

TM

VAT

IABL

E SP

EED

TER

MIN

AL B

OAR

D

USE

CO

PPER

CO

ND

UC

TOR

S O

NLY

CH

ASSI

S

WIR

E LE

GEN

DH

IGH

VO

LTAG

E(F

ACTO

RY)

HIG

H V

OLT

AGE

(FAC

TOR

Y O

R F

IELD

LOW

VO

LTAG

E(F

ACTO

RY

OR

FIE

LD)

HIG

H V

OLT

AGE

DC

HAR

NES

S(F

ACTO

RY)

7SE

E TA

BLE

FOR

MO

TOR

SPE

ED S

ELEC

TIO

N

GN

REM

OTE

TH

ERM

OST

AT

OPE

RAT

ION

CO

OLI

NG

UN

ITW

/ EL

ECTR

IC H

EAT

FUN

CTI

ON

C

ON

NEC

T

R T

O:

O

FF

-----

------

F

AN

G **

C

OO

L

G, Y

/ W

1

H

EAT

G

, W2

OR

G

, B, Y

/ W

1*

HEA

T PU

MP

W /

AUXI

LIAR

YEL

ECTR

IC H

EAT

FUN

CTI

ON

C

ON

NEC

T

R T

O:

O

FF

-----

------

F

AN

G **

C

OO

L

G, Y

/ W

1

1

ST S

TAG

E

HEA

T

G, B

, Y /

W1

2

ND

STA

GE

H

EAT

G

, W2

GN

1C

ON

TRO

L PA

NE

L

UI C

ON

NEC

TIO

N

88

8BO

ARD

SH

OW

S R

AN

D C

, PLE

ASE

IGN

OR

E.

NO

TES:

WIR

E C

OD

E

BR

BR

OW

NBK

B

LAC

KG

N

GR

EEN

GY

G

RAY

RD

R

EDVT

V

IOLE

TW

H

WH

ITE

YL

YEL

LOW

3

Page 17: PTAC Control Board Kit RSKP0013 Installation Instructions

17

THIS PAGE INTENTIONALLY LEFT BLANK

Page 18: PTAC Control Board Kit RSKP0013 Installation Instructions

18

THIS PAGE INTENTIONALLY LEFT BLANK

Page 19: PTAC Control Board Kit RSKP0013 Installation Instructions

19

THIS PAGE INTENTIONALLY LEFT BLANK

Page 20: PTAC Control Board Kit RSKP0013 Installation Instructions

20

is a registered trademark of Maytag Corporation or its related companies and is used under license to Goodman Company, L.P., Houston, TX, USA. All rights reserved.

© 2015 - 2016, 2020 Goodman Company, L.P.

19001 Kermier Rd. • Waller, TX 77484 • www.amana-ptac.com

CUSTOMER FEEDBACKWe are very interested in all product comments.Please fill out the feedback form on one of the following links:Goodman® Brand Products: (http://www.goodmanmfg.com/about/contact-us).Amana® Brand Products: (http://www.amana-hac.com/about-us/contact-us).You can also scan the QR code on the right for the product brandyou purchased to be directed to the feedback page.

GOODMAN® BRAND AMANA® BRAND