© PHOENIX CONTACT 2015-08-27 106509_en_01 PSR-MS and PSR-MC Application note 1 Description Our PSR safety relays demonstrate that innovative safety solutions do not necessarily have to be complex in order to meet the high requirements of machine building and sys- tems manufacturing. As well as offering easy integration and handling, the mod- ules are characterized by their compact, space-saving de- sign as well as their high quality, safety, and reliability. In particular, safety applications can be implemented under optimum cost-benefit conditions with the new PSRmini safety relay range. Solutions for all common applications Use the PSRmini safety relays, for example, to implement monitoring of the following safety equipment: Emergency stop Safety door Light grid Magnetic switch PSR-MS Single or two-channel control 1 enabling current path 6.8 mm housing width PSR-MC Single or two-channel control 2 or 3 enabling current paths 12.5 mm housing width Make sure you always use the latest documentation. It can be downloaded at phoenixcontact.net/products . This document is valid for the products listed in the "Ordering data". Applications using PSR-MS and PSR-MC safety relays from the PSRmini product range

Transcript of PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block...

Page 1: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

© PHOENIX CONTACT 2015-08-27106509_en_01

PSR-MS and PSR-MC

Application note

1 Description

Our PSR safety relays demonstrate that innovative safety

solutions do not necessarily have to be complex in order to

meet the high requirements of machine building and sys-

tems manufacturing.

As well as offering easy integration and handling, the mod-

ules are characterized by their compact, space-saving de-

sign as well as their high quality, safety, and reliability.

In particular, safety applications can be implemented under

optimum cost-benefit conditions with the new PSRmini

safety relay range.

Solutions for all common applications

Use the PSRmini safety relays, for example, to implement

monitoring of the following safety equipment:

– Emergency stop

– Safety door

– Light grid

– Magnetic switch

PSR-MS

– Single or two-channel control

– 1 enabling current path

– 6.8 mm housing width

PSR-MC

– Single or two-channel control

– 2 or 3 enabling current paths

– 12.5 mm housing width

Make sure you always use the latest documentation.

It can be downloaded at phoenixcontact.net/products.

This document is valid for the products listed in the "Ordering data".

Applications using PSR-MS and PSR-MC safety

relays from the PSRmini product range

Page 2: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

2 PHOENIX CONTACT 106509_en_01

Table of contents

Description ........................................................................................................................................1

Ordering data ....................................................................................................................................5

Documentation ..................................................................................................................................6

Applications with the PSR-MS20 .......................................................................................................7

Emergency stop monitoring/automatic start .............................................................................................................. 7

Safety door monitoring/automatic start ..................................................................................................................... 7

Connection to failsafe controller/automatic start ....................................................................................................... 8

Applications with the PSR-MS25 .......................................................................................................9

Emergency stop monitoring/manual, monitored start ................................................................................................ 9

Safety door monitoring/manual, monitored start ....................................................................................................... 9

Connection to failsafe controller/manual, monitored start ....................................................................................... 10

Applications with the PSR-MS30 .....................................................................................................11

Emergency stop monitoring/automatic start ............................................................................................................ 11

Safety door monitoring/automatic start ................................................................................................................... 11

Magnetic switch monitoring/automatic start ............................................................................................................ 12

Applications with the PSR-MS35 .....................................................................................................13

Emergency stop monitoring/manual, monitored start .............................................................................................. 13

Safety door monitoring/manual, monitored start ..................................................................................................... 13

Magnetic switch monitoring/manual, monitored start .............................................................................................. 14

Applications with the PSR-MS40 .....................................................................................................15

Emergency stop monitoring/automatic start ............................................................................................................ 15

Safety door monitoring/automatic start ................................................................................................................... 15

Magnetic switch monitoring/automatic start ............................................................................................................ 16

Applications with the PSR-MS45 .....................................................................................................17

Emergency stop monitoring/manual, monitored start .............................................................................................. 17

Safety door monitoring/manual, monitored start ..................................................................................................... 17

Magnetic switch monitoring/manual, monitored start .............................................................................................. 18

Applications with the PSR-MS50 .....................................................................................................19

Magnetic switch monitoring/automatic start ............................................................................................................ 19

Applications with the PSR-MS55 .....................................................................................................19

Magnetic switch monitoring/manual, monitored start .............................................................................................. 19

Applications with the PSR-MS60 .....................................................................................................20

Light grid monitoring/automatic start ....................................................................................................................... 20

Two-channel control via LPSDO module ................................................................................................................ 20

Single-channel control via failsafe controller ........................................................................................................... 21

Applications with the PSR-MC20 ....................................................................................................22

Emergency stop monitoring/automatic start ............................................................................................................ 22

Emergency stop monitoring/manual, monitored start .............................................................................................. 22

Safety door monitoring/automatic start ................................................................................................................... 23

Page 3: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 PHOENIX CONTACT 3

Safety door monitoring/manual, monitored start ..................................................................................................... 23

Connection to failsafe controller/automatic start ..................................................................................................... 24

Applications with the PSR-MC30 ....................................................................................................25

Emergency stop monitoring/automatic start ............................................................................................................ 25

Emergency stop monitoring/manual, monitored start .............................................................................................. 25

Safety door monitoring/automatic start ................................................................................................................... 26

Safety door monitoring/automatic start/without cross-circuit detection ................................................................... 26

Single-channel safety door monitoring/automatic start ........................................................................................... 27

Safety door monitoring/manual, monitored start ..................................................................................................... 27

Safety door monitoring/manual, monitored start/without cross-circuit detection ..................................................... 28

Single-channel safety door monitoring/manual, monitored start ............................................................................. 28

Magnetic switch monitoring/automatic start ............................................................................................................ 29

Magnetic switch monitoring/manual, monitored start .............................................................................................. 29

Applications with the PSR-MC34 ....................................................................................................30

Emergency stop monitoring/automatic start ............................................................................................................ 30

Emergency stop monitoring/manual, monitored start .............................................................................................. 30

Safety door monitoring/automatic start ................................................................................................................... 31

Safety door monitoring/automatic start/without cross-circuit detection ................................................................... 31

Single-channel safety door monitoring/automatic start ........................................................................................... 32

Safety door monitoring/manual, monitored start ..................................................................................................... 32

Safety door monitoring/manual, monitored start/without cross-circuit detection ..................................................... 33

Single-channel safety door monitoring/manual, monitored start ............................................................................. 33

Magnetic switch monitoring/automatic start ............................................................................................................ 34

Magnetic switch monitoring/manual, monitored start .............................................................................................. 34

Applications with the PSR-MC40 ....................................................................................................35

Emergency stop monitoring/automatic start ............................................................................................................ 35

Emergency stop monitoring/manual, monitored start .............................................................................................. 35

Safety door monitoring/automatic start ................................................................................................................... 36

Safety door monitoring/manual, monitored start ..................................................................................................... 36

Single-channel safety door monitoring/automatic start ........................................................................................... 37

Single-channel safety door monitoring/manual, monitored start ............................................................................. 37

Connection to failsafe controller/automatic start ..................................................................................................... 38

Connection to failsafe controller/manual, monitored start ....................................................................................... 38

Single-channel connection to failsafe controller/automatic start ............................................................................. 39

Single-channel connection to failsafe controller/manual, monitored start ............................................................... 39

Light grid monitoring/automatic start ....................................................................................................................... 40

Light grid monitoring/manual, monitored start ......................................................................................................... 40

Transponder monitoring/automatic start ................................................................................................................. 41

Transponder monitoring/manual, monitored start ................................................................................................... 41

Applications with the PSR-MC50 ....................................................................................................42

Magnetic switch monitoring/automatic start ............................................................................................................ 42

Magnetic switch monitoring/manual, monitored start .............................................................................................. 42

Safety door monitoring/automatic start ................................................................................................................... 43

Safety door monitoring/manual, monitored start ..................................................................................................... 43

Page 4: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

4 PHOENIX CONTACT 106509_en_01

Revision history ...............................................................................................................................44

Page 5: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 PHOENIX CONTACT 5

2 Ordering data

Application note

Applications using PSR-MS and PSR-MC safety relays from the PSRmini product range

PSR-MS

PSR-MC

Designation: AH EN PSR-MS / PSR-MC

Revision: 01

MNR/Revision: 52007563/00

Description Type Order No. Pcs. / Pkt.

Safety relay for emergency stop and safety doors up to SIL 1, SILCL 1,

Cat. 1, PL c, depending on the application up to SIL 3, SILCL 3, Cat. 4,

PL e, 1-channel operation, automatic start, 1 enabling current path,

US = 24 V DC, fixed screw terminal block

PSR-MS20-1NO-1DO-24DC-SC 2904950 1

Safety relay for emergency stop and safety doors up to SIL 1, SILCL 1,

Cat. 1, PL c, depending on the application up to SIL 3, SILCL 3, Cat. 4,

PL e, 1-channel operation, manual, monitored start, 1 enabling current

path, US = 24 V DC, fixed screw terminal block

PSR-MS25-1NO-1DO-24DC-SC 2904951 1

Safety relay for emergency stop and safety doors up to SIL 3, SILCL 3,

Cat. 4, PL e, 2-channel operation, automatic start, cross-circuit detection,

1 enabling current path, US = 24 V DC, fixed screw terminal block

PSR-MS30-1NO-24DC-SC 2904952 1

Safety relay for emergency stop and safety doors up to SIL 3, SILCL 3,

Cat. 4, PL e, 2-channel operation, manual, monitored start, cross-circuit

detection, 1 enabling current path, US = 24 V DC, fixed screw terminal

block

PSR-MS35-1NO-24DC-SC 2904953 1

Safety relay for emergency stop and safety doors up to SIL 3, SILCL 3,

Cat. 4, PL e, 2-channel operation, automatic start, 1 enabling current path,

US = 24 V DC, fixed screw terminal block

PSR-MS40-1NO-1DO-24DC-SC 2904954 1

Safety relay for emergency stop and safety doors up to SIL 3, SILCL 3,

Cat. 4, PL e, 2-channel operation, manual, monitored start, 1 enabling cur-

rent path, US = 24 V DC, fixed screw terminal block

PSR-MS45-1NO-1DO-24DC-SC 2904955 1

Safety relay for monitoring non-equivalent signal generators up to SIL 3,

SILCL 3, Cat. 4, PL e, 2-channel, non-equivalent operation, automatic

start, 1 enabling current path, US = 24 V DC, fixed screw terminal block

PSR-MS50-1NO-1DO-24DC-SC 2904956 1

Safety relay for monitoring non-equivalent signal generators up to SIL 3,

SILCL 3, Cat. 4, PL e, 2-channel, non-equivalent operation, manual, mon-

itored start, 1 enabling current path, US = 24 V DC, fixed screw terminal

block

PSR-MS55-1NO-1DO-24DC-SC 2904957 1

Safety relay for emergency stop, safety doors and light grids up to SIL 3,

SILCL 3, Cat. 4, PL e, 2-channel operation, automatic start, 2 enabling cur-

rent paths (1-channel), US = 24 V DC, fixed screw terminal block

PSR-MS60-2NO-24DC-SC 2904958 1

Description Type Order No. Pcs. / Pkt.

Safety relay for emergency stop and safety doors up to SIL 1, SILCL 1,

Cat. 1, PL c, depending on the application up to SIL 3, SILCL 3, Cat. 4,

PL e, 1-channel operation, automatic/manual start, 3 enabling current

paths, US = 24 V DC, plug-in screw terminal block

PSR-MC20-3NO-1DO-24DC-SC 2700466 1

Safety relay for emergency stop and safety doors up to SIL 1, SILCL 1,

Cat. 1, PL c, depending on the application up to SIL 3, SILCL 3, Cat. 4,

PL e, 1-channel operation, automatic/manual start, 3 enabling current

paths, US = 24 V DC, plug-in spring-cage terminal block

PSR-MC20-3NO-1DO-24DC-SP 2700467 1

Safety relay for emergency stop and safety doors up to SIL 3, SILCL 3,

Cat. 4, PL e, 2-channel operation, automatic or manual, monitored start,

cross-circuit detection, 2 enabling current paths, US = 24 V DC, plug-in

screw terminal block

PSR-MC30-2NO-1DO-24DC-SC 2700498 1

Page 6: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

6 PHOENIX CONTACT 106509_en_01

3 Documentation

Safety relay for emergency stop and safety doors up to SIL 3, SILCL 3,

Cat. 4, PL e, 2-channel operation, automatic or manual, monitored start,

cross-circuit detection, 2 enabling current paths, US = 24 V DC, plug-in

spring-cage terminal block

PSR-MC30-2NO-1DO-24DC-SP 2700499 1

Safety relay for emergency stop and safety doors up to SIL 3, SILCL 3,

Cat. 4, PL e, 2-channel operation, automatic or manual, monitored start,

cross-circuit detection, 3 enabling current paths, US = 24 V DC, plug-in

screw terminal block

PSR-MC34-3NO-1DO-24DC-SC 2700540 1

Safety relay for emergency stop and safety doors up to SIL 3, SILCL 3,

Cat. 4, PL e, 2-channel operation, automatic or manual, monitored start,

cross-circuit detection, 3 enabling current paths, US = 24 V DC, plug-in

spring-cage terminal block

PSR-MC34-3NO-1DO-24DC-SP 2700548 1

Safety relay for emergency stop, safety doors and light grids up to SIL 3,

SILCL 3, Cat. 4, PL e, 2-channel operation, automatic or manual, moni-

tored start, 3 enabling current paths, US = 24 V DC, plug-in screw terminal

block

PSR-MC40-3NO-1DO-24DC-SC 2700569 1

Safety relay for emergency stop, safety doors and light grids up to SIL 3,

SILCL 3, Cat. 4, PL e, 2-channel operation, automatic or manual, moni-

tored start, 3 enabling current paths, US = 24 V DC, plug-in spring-cage

terminal block

PSR-MC40-3NO-1DO-24DC-SP 2700570 1

Safety relay for monitoring non-equivalent signal generators up to SIL 3,

SILCL 3, Cat 4, PL e, 2-channel, non-equivalent operation, automatic or

manual, monitored start, 3 enabling current paths, US = 24 V DC, plug-in

screw terminal block

PSR-MC50-3NO-1DO-24DC-SC 2700553 1

Safety relay for monitoring non-equivalent signal generators up to SIL 3,

SILCL 3, Cat. 4, PL e, 2-channel, non-equivalent operation, automatic or

manual, monitored start, 3 enabling current paths, US = 24 V DC, plug-in

spring-cage terminal block

PSR-MC50-3NO-1DO-24DC-SP 2700564 1

Description Type Order No. Pcs. / Pkt.

Further documentation for individual products can be downloaded at phoenixcontact.net/products.

Page 7: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 PHOENIX CONTACT 7

4 Applications with the PSR-MS20

Key:

4.1 Emergency stop monitoring/automatic start

– Single-channel emergency stop monitoring

– Automatic start

– Monitoring of external contactors

– Suitable up to category 1, PL c (EN ISO 13849-1),

SIL 1 (EN 62061)

Figure 1 Emergency stop monitoring/automatic start

4.2 Safety door monitoring/automatic start

– Single-channel safety door monitoring

– Automatic start

– Monitoring of external contactors

– Suitable up to category 1, PL c (EN ISO 13849-1),

SIL 1 (EN 62061)

Figure 2 Safety door monitoring/automatic start

S1 = Emergency-stop button

B1 = Mechanical safety door switch

K1/K2 = Contactors

Contactor K2 is not essential in order to

achieve category 1.

24V

0V

K1

K2

N

L

S1K1

K2

A1

A2

13

14

PSR-MS20

S11S35 S12(+) ( )( )

M1( )

K1

K2

M

Contactor K2 is not essential in order to

achieve category 1.

K1

K2

M

0V

24V

K1

K2

N

L

M1( )

S11(+)

S12( )

A1

A2

13

14

PSR-MS20

S35( )

B1K1

K2

open

closed

Page 8: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

8 PHOENIX CONTACT 106509_en_01

4.3 Connection to failsafe controller/automatic

start

– Automatic start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if the digital output of the safety-relat-

ed controller meets PL e, SIL 3, and cross-circuits can

be ruled out

Figure 3 Connection to failsafe PLC/automatic start

WARNING: Loss of functional safety!

Make sure that the signal generator (e.g., PLC

output card or light grid) and the safety relay

have the same ground potential.

Cross-circuits in the cable installation can be

excluded if the failsafe PLC, safety relay, and

external contactors K1 and K2 are located in

the same electrical installation space.

FAIL-SAFE SPS/PLC

Q0

24V DC

0V

K1

K2

N

L

S11 M1(+)

S12( )

A1

A2

13

14

PSR-MS20

S35( )

K1

K2

M

GND

24V0V I0

K1

K2

( )

Page 9: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 PHOENIX CONTACT 9

5 Applications with the PSR-MS25

Key:

5.1 Emergency stop monitoring/manual, moni-

tored start

– Single-channel emergency stop monitoring

– Manual, monitored start

– Monitoring of external contactors

– Suitable up to category 1, PL c (EN ISO 13849-1),

SIL 1 (EN 62061)

Figure 4 Emergency stop monitoring/manual, moni-

tored start

5.2 Safety door monitoring/manual, monitored

start

– Single-channel safety door monitoring

– Manual, monitored start

– Monitoring of external contactors

– Suitable up to category 1, PL c (EN ISO 13849-1),

SIL 1 (EN 62061)

Figure 5 Safety door monitoring/manual, monitored

start

S1 = Emergency-stop button

S2 = Manual reset device

B1 = Mechanical safety door switch

K1/K2 = Contactors

Contactor K2 is not essential in order to

achieve category 1.

K1

K2

M

24V

0V

K1

K2

N

L

A1

A2

13

14

PSR-MS25

S11S34 S12(+) ( )( )

M1( )

S1K1

K2

S2

Contactor K2 is not essential in order to

achieve category 1.K1

K2

M

0V

24V

K1

K2

N

L

M1( )

S11(+)

S12( )

A1

A2

13

14

PSR-MS25

S34( )

B1open

closed

K1

K2

S2

Page 10: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

10 PHOENIX CONTACT 106509_en_01

5.3 Connection to failsafe controller/manual, moni-

tored start

– Manual, monitored start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if the digital output of the safety-relat-

ed controller meets PL e, SIL 3, and cross-circuits can

be ruled out

Figure 6 Connection to failsafe PLC/manual, monitored

start

WARNING: Loss of functional safety!

Make sure that the signal generator (e.g., PLC

output card or light grid) and the safety relay

have the same ground potential.

Cross-circuits in the cable installation can be

excluded if the failsafe PLC, safety relay, and

external contactors K1 and K2 are located in

the same electrical installation space.

FAIL-SAFE SPS/PLC

Q0

24V DC

0V

K1

K2

N

L

S11 M1(+)

S12( )

A1

A2

13

14

PSR-MS25

S34( )

K1

K2

M

GND

24V0V I0

K1

K2

( )

S2

Page 11: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 PHOENIX CONTACT 11

6 Applications with the PSR-MS30

Key:

6.1 Emergency stop monitoring/automatic start

– Two-channel emergency stop monitoring

– Automatic start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 7 Emergency stop monitoring/automatic start

6.2 Safety door monitoring/automatic start

– Two-channel safety door monitoring

– Automatic start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 8 Safety door monitoring/automatic start

S1 = Emergency-stop button

S3 = Magnetic switch

B1/B2 = Mechanical safety door switches

K1/K2 = Contactors

Cross-circuits in the cable installation can be

excluded if the safety relay and external con-

tactors K1 and K2 are located in the same

electrical installation space.

K1

K2

M

24V

K1

K2

N

L

0V

A1

A2

13

14

PSR-MS30

S11S35 S22(+) ( )( )

S12( )

(GND)

S1

K1

K2

K1

K2

M

24V

K1

K2

N

L

0V

B1K1

K2

open

B2

A1

A2

13

14

PSR-MS30

S11S35 S22(+) ( )( )

S12( )

(GND)

closed

Page 12: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

12 PHOENIX CONTACT 106509_en_01

6.3 Magnetic switch monitoring/automatic start

– Two-channel magnetic switch monitoring

– Automatic start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 9 Magnetic switch monitoring/automatic start

K1

K2

M

24V

K1

K2

N

L

0V

K1

K2

11 12 21 22

S3

A1

A2

13

14

PSR-MS30

S35 S22( )( )

S11(+)

S12( )

(GND)

Page 13: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 PHOENIX CONTACT 13

7 Applications with the PSR-MS35

Key:

7.1 Emergency stop monitoring/manual, moni-

tored start

– Two-channel emergency stop monitoring

– Manual, monitored start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 10 Emergency stop monitoring/manual, moni-

tored start

7.2 Safety door monitoring/manual, monitored

start

– Two-channel safety door monitoring

– Manual, monitored start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 11 Safety door monitoring/manual, monitored

start

S1 = Emergency-stop button

S2 = Manual reset device

S3 = Magnetic switch

B1/B2 = Mechanical safety door switches

K1/K2 = Contactors

Cross-circuits in the cable installation can be

excluded if the safety relay and external con-

tactors K1 and K2 are located in the same

electrical installation space.

K1

K2

M

24V

K1

K2

N

L

0V

A1

A2

13

14

PSR-MS35

S11S34 S22(+) ( )( )

S12( )

(GND)

S1K2

K1

S2

K1

K2

M

24V

K1

K2

N

L

0V

B1open

B2K2

K1

S2

A1

A2

13

14

PSR-MS35

S11S34 S22(+) ( )( )

S12( )

(GND)

closed

Page 14: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

14 PHOENIX CONTACT 106509_en_01

7.3 Magnetic switch monitoring/manual, moni-

tored start

– Two-channel magnetic switch monitoring

– Manual, monitored start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 12 Magnetic switch monitoring/manual, moni-

tored start

K1

K2

M

24V

K1

K2

N

L

0V

K1

K2

11

S3

12 21 22

S2

A1

A2

13

14

PSR-MS35

S11S34 S22(+) ( )( )

S12( )

(GND)

Page 15: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 PHOENIX CONTACT 15

8 Applications with the PSR-MS40

Key:

8.1 Emergency stop monitoring/automatic start

– Two-channel emergency stop monitoring

– Automatic start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator and the sensor circuit can be ruled out

Figure 13 Emergency stop monitoring/automatic start

8.2 Safety door monitoring/automatic start

– Two-channel safety door monitoring

– Automatic start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator and the sensor circuit can be ruled out

Figure 14 Safety door monitoring/automatic start

S1 = Emergency-stop button

S3 = Magnetic switch

B1/B2 = Mechanical safety door switches

K1/K2 = Contactors

Cross-circuits in the cable installation can be

excluded if the safety relay and external con-

tactors K1 and K2 are located in the same

electrical installation space.

K1

K2

M

24V

K1

K2

N

L

0V

S1

K1

K2

A1

A2

13

14

PSR-MS40

S35 S22( )( )

S12( )

M1( )

K1

K2

M

24V

K1

K2

N

L

0V

A1

A2

13

14

PSR-MS40

S35 S22( )( )

S12( )

M1( )

B1K1

K2

open

closed

B2

Page 16: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

16 PHOENIX CONTACT 106509_en_01

8.3 Magnetic switch monitoring/automatic start

– Two-channel magnetic switch monitoring

– Automatic start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator and the sensor circuit can be ruled out

Figure 15 Magnetic switch monitoring/automatic start

K1

K2

M

24V

K1

K2

N

L

0V

K1

K2

11 12 21 22

S3

A1

A2

13

14

PSR-MS40

S35 S22( )( )

S12( )

M1( )

Page 17: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 PHOENIX CONTACT 17

9 Applications with the PSR-MS45

Key:

9.1 Emergency stop monitoring/manual, moni-

tored start

– Two-channel emergency stop monitoring

– Manual, monitored start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator and the sensor circuit can be ruled out

Figure 16 Emergency stop monitoring/manual, moni-

tored start

9.2 Safety door monitoring/manual, monitored

start

– Two-channel safety door monitoring

– Manual, monitored start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator and the sensor circuit can be ruled out

Figure 17 Safety door monitoring/manual, monitored

start

S1 = Emergency-stop button

S2 = Manual reset device

S3 = Magnetic switch

B1/B2 = Mechanical safety door switches

K1/K2 = Contactors

Cross-circuits in the cable installation can be

excluded if the safety relay and external con-

tactors K1 and K2 are located in the same

electrical installation space.

K1

K2

M

24V

K1

K2

N

L

0V

S1K2

K1

S2

A1

A2

13

14

PSR-MS45

S34 S22( )( )

S12( )

M1( )

K1

K2

M

24V

K1

K2

N

L

0V

A1

A2

13

14

PSR-MS45

S34 S22( )( )

S12( )

M1( )

B1open

closed

B2

K1

S2

K2

Page 18: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

18 PHOENIX CONTACT 106509_en_01

9.3 Magnetic switch monitoring/manual, moni-

tored start

– Two-channel magnetic switch monitoring

– Manual, monitored start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator and the sensor circuit can be ruled out

Figure 18 Magnetic switch monitoring/manual, moni-

tored start

K1

K2

M

24V

K1

K2

N

L

K1

K2

11 12 21 22

S3S2

0V

A1

A2

13

14

PSR-MS45

S34 S22( )( )

S12( )

M1( )

Page 19: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 PHOENIX CONTACT 19

10 Applications with the PSR-MS50

Key:

10.1 Magnetic switch monitoring/automatic start

– Two-channel, non-equivalent magnetic switch monitor-

ing

– Automatic start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 19 Magnetic switch monitoring/automatic start

11 Applications with the PSR-MS55

Key:

11.1 Magnetic switch monitoring/manual, moni-

tored start

– Two-channel, non-equivalent magnetic switch monitor-

ing

– Manual, monitored start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out Figure 20 Magnetic switch monitoring/manual, moni-

tored start

S1 = Emergency-stop button

S3 = Magnetic switch

K1/K2 = Contactors

Cross-circuits in the cable installation can be

excluded if the safety relay and external con-

tactors K1 and K2 are located in the same

electrical installation space.

K1

K2

M

24V

K1

K2

N

L

0V

A1

A2

13

14

PSR-MS50

S35( )

M1( )

S13( )

S12( )

K1

K2

11

S3

12 13 14

S1 = Emergency-stop button

S2 = Manual reset device

S3 = Magnetic switch

K1/K2 = Contactors

Cross-circuits in the cable installation can be

excluded if the safety relay and external con-

tactors K1 and K2 are located in the same

electrical installation space.

K1

K2

M

24V

K1

K2

N

L

K1

K2

11

S3

12 13 14

S2

0V

A1

A2

13

14

PSR-MS55

S34 S13( )( )

S12( )

M1( )

Page 20: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

20 PHOENIX CONTACT 106509_en_01

12 Applications with the PSR-MS60

Key:

12.1 Light grid monitoring/automatic start

– Two-channel light grid monitoring

– Automatic start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061)

Figure 21 Light grid monitoring/automatic start

12.2 Two-channel control via LPSDO module

– Two-channel control

– Cross-circuit detection by means of LPSDO module

– Automatic start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061)

Figure 22 Two-channel control via LPSDO module

K1/K2 = Contactors

WARNING: Loss of functional safety!

Make sure that the signal generator (e.g., PLC

output card or light grid) and the safety relay

have the same ground potential.

Tra

ns

mit

ter

L 4ight grid type

K1

K2

M

24V DC

K1

K2

N

L

0V

A1

A2

13 23

14 24

PSR-MS60

S22( )

S12( )

K1

K2

OSSD1 OSSD2

ED

M

Re

ce

ive

r 0V 24V

WARNING: Loss of functional safety!

Make sure that the signal generator (e.g., PLC

output card or light grid) and the safety relay

have the same ground potential.

The bright pulses (test pulses generated by

switching on briefly) sent by the controller can

lead to the brief, unwanted activation of the

safety relay. You should therefore deactivate

the bright pulses of the failsafe controller.

K1

K2

M

24 V DC

K1

K2

N

L

A1

A2

13 23

14 24

PSR-MS60

S22( )

S12( )

LPSDO 8

DO

V2/V3DO DI

PSDI 8V2/V3

K1

K2

0V

Page 21: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 PHOENIX CONTACT 21

12.3 Single-channel control via failsafe controller

– Single-channel control

– Automatic start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if the digital output of the safety-relat-

ed controller meets PL e, SIL 3, and cross-circuits can

be ruled out

Figure 23 Single-channel control via failsafe PLC

WARNING: Loss of functional safety!

Make sure that the signal generator (e.g., PLC

output card or light grid) and the safety relay

have the same ground potential.

FAIL-SAFE SPS/PLC

Q0

24V DC

0V

GND

24V0V I0

A1

A2

PSR-MS60

S22( )

S12( )

K1

K2

MK1

K2

N

L

13 23

14 24

K1

K2

Page 22: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

22 PHOENIX CONTACT 106509_en_01

13 Applications with the PSR-MC20

Key:

13.1 Emergency stop monitoring/automatic start

– Single-channel emergency stop monitoring

– Automatic start

– Monitoring of external contactors

– Suitable up to category 1, PL c (EN ISO 13849-1),

SIL 1 (EN 62061)

Figure 24 Emergency stop monitoring/automatic start

13.2 Emergency stop monitoring/manual, moni-

tored start

– Single-channel emergency stop monitoring

– Manual, monitored start

– Monitoring of external contactors

– Suitable up to category 1, PL c (EN ISO 13849-1),

SIL 1 (EN 62061)

Figure 25 Emergency stop monitoring/manual, moni-

tored start

S1 = Emergency-stop button

S2 = Manual reset device

B1/B2 = Mechanical safety door switches

K1/K2 = Contactors

Contactor K2 is not essential in order to

achieve category 1.

K1

K2

M

24V

K1

K2

N

L

S1

A1

A2

13

14

PSR-MC20

S11 S12(+) ( )

M1( )

23

24

33

34S34( )

0V

K1

K2

Contactor K2 is not essential in order to

achieve category 1.

K1

K2

M

24V

0V

K1

K2

N

L

S1K1

K2

S2

A1

A2

13

14

PSR-MC20

S11S34 S12(+) ( )( )

M1( )

23

24

33

34

Page 23: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 PHOENIX CONTACT 23

13.3 Safety door monitoring/automatic start

– Single-channel safety door monitoring

– Automatic start

– Monitoring of external contactors

– Suitable up to category 1, PL c (EN ISO 13849-1),

SIL 1 (EN 62061)

Figure 26 Safety door monitoring/automatic start

13.4 Safety door monitoring/manual, monitored

start

– Single-channel safety door monitoring

– Manual, monitored start

– Monitoring of external contactors

– Suitable up to category 1, PL c (EN ISO 13849-1),

SIL 1 (EN 62061)

Figure 27 Safety door monitoring/manual, monitored

start

Contactor K2 is not essential in order to

achieve category 1.

K1

K2

M

24V

K1

K2

N

L

B1open

closed

M1( )

S11(+)

S12( )

A1

A2

13

14

PSR-MC20

23

24

33

34S34( )

0V

K1

K2

Contactor K2 is not essential in order to

achieve category 1.K1

K2

M

0V

24V

K1

K2

N

L

B1open

closed

K1

K2

S2

M1( )

S11(+)

S12( )

A1

A2

13

14

PSR-MC20

S34( )

23

24

33

34

Page 24: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

24 PHOENIX CONTACT 106509_en_01

13.5 Connection to failsafe controller/automatic

start

– Automatic start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if the digital output of the safety-relat-

ed controller meets PL e, SIL 3, and cross-circuits can

be ruled out

Figure 28 Connection to failsafe PLC/automatic start

WARNING: Loss of functional safety!

Make sure that the signal generator (e.g., PLC

output card or light grid) and the safety relay

have the same ground potential.

Cross-circuits in the cable installation can be

excluded if the failsafe PLC, safety relay, and

external contactors K1 and K2 are located in

the same electrical installation space.

FAIL-SAFE SPS/PLC

Q0

24V DC

0V

K1

K2

N

L

S11 M1(+)

S12( )

A1

A2

PSR-M 20C

( )

K1

K2

M

GND

24V0V I0

K1

K2

( )

S34

13

14

23

24

33

34

Page 25: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 PHOENIX CONTACT 25

14 Applications with the PSR-MC30

Key:

14.1 Emergency stop monitoring/automatic start

– Two-channel emergency stop monitoring

– Automatic start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 29 Emergency stop monitoring/automatic start

14.2 Emergency stop monitoring/manual, moni-

tored start

– Two-channel emergency stop monitoring

– Manual, monitored start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 30 Emergency stop monitoring/manual, moni-

tored start

S1 = Emergency-stop button

S2 = Manual reset device

S3 = Magnetic switch

B1/B2 = Mechanical safety door switches

K1/K2 = Contactors

Cross-circuits in the cable installation can be

excluded if the safety relay and external con-

tactors K1 and K2 are located in the same

electrical installation space.

K1

K2

M

24V

K1

K2

N

L

0V

A1

A2

13

14

PSR-MC30

S12 S34S22( ) ( )

S21

( )

(GND)

M1( )

23

24

S11(+) ( )

S1K2

K1

K1

K2

M

24V

K1

K2

N

L

0V

A1

A2

13

14

PSR-MC30

S12S34 S22( )( )

S21

( )

(GND)

M1( )

23

24

S11(+) ( )

S1K2

K1

S2

Page 26: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

26 PHOENIX CONTACT 106509_en_01

14.3 Safety door monitoring/automatic start

– Two-channel safety door monitoring

– Automatic start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 31 Safety door monitoring/automatic start

14.4 Safety door monitoring/automatic start/without

cross-circuit detection

– Two-channel safety door monitoring

– Automatic start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator and the sensor circuit can be ruled out

Figure 32 Safety door monitoring/automatic start/without

cross-circuit detection

K1

K2

M

24V

K1

K2

N

L

0V

K1

K2

B1open

closed

B2

A1

A2

13

14

PSR-MC30

S12 S34S22( ) ( )

S21

(GND)

M1( )

23

24

S11(+) ( )

( )

K1

K2

M

24V

K1

K2

N

L

0V

K1

K2

B1open

closed

B2

A1

A2

13

14

PSR-MC30

S12 S34S22( ) ( )

S21

(GND)

M1( )

23

24

S11(+) ( )

( )

Page 27: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 PHOENIX CONTACT 27

14.5 Single-channel safety door monitoring/auto-

matic start

– Single-channel safety door monitoring

– Automatic start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 1, PL c (EN ISO 13849-1),

SIL 1 (EN 62061)

Figure 33 Single-channel safety door monitoring/auto-

matic start

14.6 Safety door monitoring/manual, monitored

start

– Two-channel safety door monitoring

– Manual, monitored start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 34 Safety door monitoring/manual, monitored

start

Contactor K2 is not essential in order to

achieve category 1.

K1

K2

M

24V

K1

K2

N

L

0V

A1

A2

13

14

PSR-MC30

S12 S34S22( ) ( )

S21

( )

(GND)

M1( )

23

24

S11(+) ( )

K1

K2

B1open

closed

K1

K2

M

24V

K1

K2

N

L

0V

A1

A2

13

14

PSR-MC30

S12S34 S22( )( )

S21

( )

(GND)

M1( )

23

24

S11(+) ( )

K1

K2

S2B1

open

closed

B2

Page 28: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

28 PHOENIX CONTACT 106509_en_01

14.7 Safety door monitoring/manual, monitored

start/without cross-circuit detection

– Two-channel safety door monitoring

– Manual, monitored start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator and the sensor circuit can be ruled out

Figure 35 Safety door monitoring/manual, monitored

start/without cross-circuit detection

14.8 Single-channel safety door monitoring/manual,

monitored start

– Single-channel safety door monitoring

– Manual, monitored start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 1, PL c (EN ISO 13849-1),

SIL 1 (EN 62061)

Figure 36 Single-channel safety door monitoring/man-

ual, monitored start

K1

K2

M

24V

K1

K2

N

L

0V

A1

A2

13

14

PSR-MC30

S12S34 S22( )( )

S21

( )

(GND)

M1( )

23

24

S11(+) ( )

K1

K2

S2B1

open

closed

B2

Contactor K2 is not essential in order to

achieve category 1.

K1

K2

M

24V

K1

K2

N

L

0V

A1

A2

13

14

PSR-MC30

S12S34 S22( )( )

S21

( )

(GND)

M1( )

23

24

S11(+) ( )

K1

K2

S2B1

open

closed

Page 29: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 PHOENIX CONTACT 29

14.9 Magnetic switch monitoring/automatic start

– Two-channel magnetic switch monitoring

– Automatic start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 37 Magnetic switch monitoring/automatic start

14.10 Magnetic switch monitoring/manual, moni-

tored start

– Two-channel magnetic switch monitoring

– Manual, monitored start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 38 Magnetic switch monitoring/manual, moni-

tored start

K1

K2

M

24V

K1

K2

N

L

0V

A1

A2

13

14

PSR-MC30

S12 S22( )

S21

( )

(GND)

M1( )

23

24

S11(+) ( )

S34( )

11 12 21 22

S3

K1

K2

K1

K2

M

24V

K1

K2

N

L

0V

A1

A2

13

14

PSR-MC30

S12S34 S22( )( )

S21

( )

(GND)

M1( )

23

24

S11(+) ( )

K1

K2

11 12 21 22

S3S2

Page 30: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

30 PHOENIX CONTACT 106509_en_01

15 Applications with the PSR-MC34

Key:

15.1 Emergency stop monitoring/automatic start

– Two-channel emergency stop monitoring

– Automatic start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 39 Emergency stop monitoring/automatic start

15.2 Emergency stop monitoring/manual, moni-

tored start

– Two-channel emergency stop monitoring

– Manual, monitored start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 40 Emergency stop monitoring/manual, moni-

tored start

S1 = Emergency-stop button

S2 = Manual reset device

S3 = Magnetic switch

B1/B2 = Mechanical safety door switches

K1/K2 = Contactors

Cross-circuits in the cable installation can be

excluded if the safety relay and external con-

tactors K1 and K2 are located in the same

electrical installation space.

K1

K2

M

24V

K1

K2

N

L

S1

A1

A2

13

14

PSR-MC34

S12 S22( )

(GND)

M1( )

23

24

S11(+) ( )

34S34( )

0V

K2

K1

K1

K2

M

24V

K1

K2

N

L

A1

A2

13

14

PSR-MC34

S12S34 S22( )

(GND)

( )

M1( )

23

24

S11(+) ( )

34

0V

S1K2

K1

S2

Page 31: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 PHOENIX CONTACT 31

15.3 Safety door monitoring/automatic start

– Two-channel safety door monitoring

– Automatic start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 41 Safety door monitoring/automatic start

15.4 Safety door monitoring/automatic start/without

cross-circuit detection

– Two-channel safety door monitoring

– Automatic start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator and the sensor circuit can be ruled out

Figure 42 Safety door monitoring/automatic start/without

cross-circuit detection

K1

K2

M

24V

K1

K2

N

L

B1open

closed

B2

A1

A2

13

14

PSR-MC34

S12 S22( )

M1( )

23

24

S11(+) ( )

34S34( )

0V

K2

K1

K1

K2

M

24V

K1

K2

N

L

A1

A2

13

14

PSR-MC34

S12 S22( )

M1( )

23

24

S11(+) ( )

34S34( )

0V

K2

K1

B1open

closed

B2

Page 32: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

32 PHOENIX CONTACT 106509_en_01

15.5 Single-channel safety door monitoring/auto-

matic start

– Single-channel safety door monitoring

– Automatic start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 1, PL c (EN ISO 13849-1),

SIL 1 (EN 62061)

Figure 43 Single-channel safety door monitoring/auto-

matic start

15.6 Safety door monitoring/manual, monitored

start

– Two-channel safety door monitoring

– Manual, monitored start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 44 Safety door monitoring/manual, monitored

start

Contactor K2 is not essential in order to

achieve category 1.

K1

K2

M

24V

K1

K2

N

L

B1open

A1

A2

13

14

PSR-MC34

S12 S22( )

M1( )

23

24

S11(+) ( )

34

closed

S34( )

0V

K2

K1

K1

K2

M

24V

K1

K2

N

L

0V

K1

K2

S2B1

open

closed

B2

A1

A2

13

14

PSR-MC34

S12 S22( )

M1( )

23

24

S11(+) ( )

34

S34( )

Page 33: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 PHOENIX CONTACT 33

15.7 Safety door monitoring/manual, monitored

start/without cross-circuit detection

– Two-channel safety door monitoring

– Manual, monitored start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator and the sensor circuit can be ruled out

Figure 45 Safety door monitoring/manual, monitored

start/without cross-circuit detection

15.8 Single-channel safety door monitoring/manual,

monitored start

– Single-channel safety door monitoring

– Manual, monitored start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 1, PL c (EN ISO 13849-1),

SIL 1 (EN 62061)

Figure 46 Single-channel safety door monitoring/man-

ual, monitored start

K1

K2

M

24V

K1

K2

N

L

0V

A1

A2

13

14

PSR-MC34

S12 S22( )

M1( )

23

24

S11(+) ( )

34

S34( )

K1

K2

S2B1

open

closed

B2

Contactor K2 is not essential in order to

achieve category 1.

K1

K2

M

24V

K1

K2

N

L

0V

A1

A2

13

14

PSR-MC34

S12 S22( )

M1( )

23

24

S11(+) ( )

34

S34( )

K1

K2

S2B1

open

closed

Page 34: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

34 PHOENIX CONTACT 106509_en_01

15.9 Magnetic switch monitoring/automatic start

– Two-channel magnetic switch monitoring

– Automatic start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 47 Magnetic switch monitoring/automatic start

15.10 Magnetic switch monitoring/manual, moni-

tored start

– Two-channel magnetic switch monitoring

– Manual, monitored start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 48 Magnetic switch monitoring/manual, moni-

tored start

K1

K2

M

24V

K1

K2

N

L

11

S3

12 21 22

0V

K2

K1

A1

A2

13

14

PSR-MC34

S12 S22( )

M1( )

23

24

S11(+) ( )

34S34( )

K1

K2

M

24V

K1

K2

N

L

K1

K2

S2

11 12 21 22

S3

A1

A2

13

14

PSR-MC34

S12S34 S22( )( )

M1( )

23

24

S11(+) ( )

34

0V

Page 35: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 PHOENIX CONTACT 35

16 Applications with the PSR-MC40

Key:

16.1 Emergency stop monitoring/automatic start

– Two-channel emergency stop monitoring

– Automatic start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator and the sensor circuit can be ruled out

Figure 49 Emergency stop monitoring/automatic start

16.2 Emergency stop monitoring/manual, moni-

tored start

– Two-channel emergency stop monitoring

– Manual, monitored start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator and the sensor circuit can be ruled out

Figure 50 Emergency stop monitoring/manual, moni-

tored start

S1 = Emergency-stop button

S2 = Manual reset device

B1/B2 = Mechanical safety door switches

K1/K2 = Contactors

Cross-circuits in the cable installation can be

excluded if the safety relay and external con-

tactors K1 and K2 are located in the same

electrical installation space.

K1

K2

M

24V

K1

K2

N

L

S1

0V

K2

K1

A1

A2

13

14

PSR-MC40

S12 S22( )

M1( )

23

24

( )

34

33

S34( )

K1

K2

M

24V

K1

K2

N

L

0V

S1K2

K1

S2

A1

A2

13

14

PSR-MC40

S12S34 S22( )( )

M1( )

23

24

( )

34

33

Page 36: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

36 PHOENIX CONTACT 106509_en_01

16.3 Safety door monitoring/automatic start

– Two-channel safety door monitoring

– Automatic start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator and the sensor circuit can be ruled out

Figure 51 Safety door monitoring/automatic start

16.4 Safety door monitoring/manual, monitored

start

– Two-channel safety door monitoring

– Manual, monitored start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator and the sensor circuit can be ruled out

Figure 52 Safety door monitoring/manual, monitored

start

K1

K2

M

24V

K1

K2

N

L

B1open

closed

B2

0V

K2

K1

A1

A2

13

14

PSR-MC40

S12 S22( )

M1( )

23

24

( )

34

33

S34( )

K1

K2

M

24V

K1

K2

N

L

0V

A1

A2

13

14

PSR-MC40

S12 S22( )

M1( )

23

24

( )

34

S34( )

33

K1

K2

S2B1

open

closed

B2

Page 37: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 PHOENIX CONTACT 37

16.5 Single-channel safety door monitoring/auto-

matic start

– Single-channel safety door monitoring

– Automatic start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 1, PL c (EN ISO 13849-1),

SIL 1 (EN 62061)

Figure 53 Single-channel safety door monitoring/auto-

matic start

16.6 Single-channel safety door monitoring/manual,

monitored start

– Single-channel safety door monitoring

– Manual, monitored start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 1, PL c (EN ISO 13849-1),

SIL 1 (EN 62061)

Figure 54 Single-channel safety door monitoring/man-

ual, monitored start

Contactor K2 is not essential in order to

achieve category 1.

K1

K2

M

24V

K1

K2

N

L

B1open

closed

0V

K2

K1

A1

A2

13

14

PSR-MC40

S12 S22( )

M1( )

23

24

( )

34

33

S34( )

Contactor K2 is not essential in order to

achieve category 1.

K1

K2

M

24V

K1

K2

N

L

0V

A1

A2

13

14

PSR-MC40

S12 S22( )

M1( )

23

24

( )

34

S34( )

33

K1

K2

S2B1

open

closed

Page 38: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

38 PHOENIX CONTACT 106509_en_01

16.7 Connection to failsafe controller/automatic

start

– Two-channel connection to the failsafe PLC

– Automatic start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if the two-channel digital output of the

safety-related controller meets PL e, SIL 3

Figure 55 Connection to failsafe PLC/automatic start

16.8 Connection to failsafe controller/manual, moni-

tored start

– Two-channel connection to the failsafe PLC

– Manual, monitored start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if the two-channel digital output of the

safety-related controller meets PL e, SIL 3

Figure 56 Connection to failsafe PLC/manual, monitored

start

WARNING: Loss of functional safety!

Make sure that the signal generator (e.g., PLC

output card or light grid) and the safety relay

have the same ground potential.

K1

K2

M

A1 13

14

PSR-MC40

23

24 34

33

24V DC L

0V

K1

K2

N

A2

( )

K1

K2

S34

S12 S22( )( )

M1( )

FAIL-SAFE SPS/PLC

Q0GND

24V0V I0Q1

WARNING: Loss of functional safety!

Make sure that the signal generator (e.g., PLC

output card or light grid) and the safety relay

have the same ground potential.

K1

K2

M

A1

A2

13

14

PSR-MC40

S12 S22( )

23

24

( )

34

33M1( )

FAIL-SAFE SPS/PLC

Q0

24V DC L

S34( )

GND

24V0V I0

K1

K2

S2

0V

K1

K2

N

Q1

Page 39: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 PHOENIX CONTACT 39

16.9 Single-channel connection to failsafe control-

ler/automatic start

– Single-channel connection to the failsafe PLC

– Automatic start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if the digital output of the safety-relat-

ed controller meets PL e, SIL 3, and cross-circuits can

be ruled out

Figure 57 Single-channel connection to failsafe PLC/au-

tomatic start

16.10 Single-channel connection to failsafe control-

ler/manual, monitored start

– Single-channel connection to the failsafe PLC

– Manual, monitored start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if the digital output of the safety-relat-

ed controller meets PL e, SIL 3, and cross-circuits can

be ruled out

Figure 58 Single-channel connection to failsafe PLC/

manual, monitored start

WARNING: Loss of functional safety!

Make sure that the signal generator (e.g., PLC

output card or light grid) and the safety relay

have the same ground potential.

Cross-circuits in the cable installation can be

excluded if the failsafe PLC, safety relay, and

external contactors K1 and K2 are located in

the same electrical installation space.

K1

K2

M

A1 13

14

PSR-MC40

S12 S22( )

23

24

( )

34

33M1( )

FAIL-SAFE SPS/PLC

Q0

24V DC L

GND

24V0V I0

0V

K1

K2

N

A2

( )

K1

K2

S34

WARNING: Loss of functional safety!

Make sure that the signal generator (e.g., PLC

output card or light grid) and the safety relay

have the same ground potential.

Cross-circuits in the cable installation can be

excluded if the failsafe PLC, safety relay, and

external contactors K1 and K2 are located in

the same electrical installation space.

K1

K2

M

A1

A2

13

14

PSR-MC40

S12 S22( )

23

24

( )

34

33M1( )

FAIL-SAFE SPS/PLC

Q0

24V DC L

S34( )

GND

24V0V I0

K1

K2

S2

0V

K1

K2

N

Page 40: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

40 PHOENIX CONTACT 106509_en_01

16.11 Light grid monitoring/automatic start

– Two-channel light grid monitoring

– Automatic start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 59 Light grid monitoring/automatic start

16.12 Light grid monitoring/manual, monitored start

– Two-channel light grid monitoring

– Manual, monitored start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 60 Light grid monitoring/manual, monitored start

WARNING: Loss of functional safety!

Make sure that the signal generator (e.g., PLC

output card or light grid) and the safety relay

have the same ground potential.

K1

K2

M

24V DC

K1

K2

N

L

A1 13

14

PSR-MC40

S12 S22( )

M1( )

23

24

( )

34S34( )

33

Tra

ns

mit

ter

Light grid type 4

OSSD1 OSSD2

Re

ce

ive

r 0V 24V

0V

A2

K2

K1

WARNING: Loss of functional safety!

Make sure that the signal generator (e.g., PLC

output card or light grid) and the safety relay

have the same ground potential.

K1

K2

M

24V DC

K1

K2

N

L

K1

K2

S2

A1 13

14

PSR-MC40

S12 S22( )

M1( )

23

24

( )

34

S34( )

33

Tra

ns

mit

ter

Light grid type 4

OSSD1 OSSD2

Re

ce

ive

r 0V 24V

0V

A2

Page 41: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 PHOENIX CONTACT 41

16.13 Transponder monitoring/automatic start

– Two-channel transponder monitoring

– Automatic start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 61 Transponder monitoring/automatic start

16.14 Transponder monitoring/manual, monitored

start

– Two-channel transponder monitoring

– Manual, monitored start

– Monitoring of external contactors

– No cross-circuit detection in the sensor circuit

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 62 Transponder monitoring/manual, monitored

start

WARNING: Loss of functional safety!

Make sure that the signal generator (e.g., PLC

output card or light grid) and the safety relay

have the same ground potential.

K1

K2

M

24V DC

K1

K2

N

L

0V

A1

A2

13

14

PSR-MC40

S12 S22( )

M1( )

23

24

( )

34

33

OSSD 1 OSSD 2

PLe

Cat.4

Tra

ns

po

nd

er 0V 24V

K2

K1

S34( )

WARNING: Loss of functional safety!

Make sure that the signal generator (e.g., PLC

output card or light grid) and the safety relay

have the same ground potential.

K1

K2

M

24V DC

K1

K2

N

L

0V

A1

A2

13

14

PSR-MC40

S12 S22( )

M1( )

23

24

( )

34

S34( )

33

K1

K2

S2

OSSD 1 OSSD 2

PLe

Cat.4

Tra

ns

po

nd

er 0V 24V

Page 42: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

42 PHOENIX CONTACT 106509_en_01

17 Applications with the PSR-MC50

Key:

17.1 Magnetic switch monitoring/automatic start

– Two-channel, non-equivalent magnetic switch monitor-

ing

– Automatic start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 63 Magnetic switch monitoring/automatic start

17.2 Magnetic switch monitoring/manual, moni-

tored start

– Two-channel, non-equivalent magnetic switch monitor-

ing

– Manual, monitored start

– Monitoring of external contactors

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out

Figure 64 Magnetic switch monitoring/manual, moni-

tored start

S1 = Emergency-stop button

S2 = Manual reset device

S3 = Magnetic switch

K1/K2 = Contactors

Cross-circuits in the cable installation can be

excluded if the safety relay and external con-

tactors K1 and K2 are located in the same

electrical installation space.

K1

K2

M

24V

K1

K2

N

L

0V

K2

K1

A1

A2

13

14

PSR-MC50

S12 S13( )

M1( )

23

24

( )

34

33

S34( )

11 12 13 14

S3

K1

K2

M

24V

K1

K2

N

L

0V

K1

K2

S2S3

11 12 13 14

A1

A2

13

14

PSR-MC50

S12S34 S13( )( )

M1( )

23

24

( )

34

33

Page 43: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 PHOENIX CONTACT 43

17.3 Safety door monitoring/automatic start

– Non-equivalent safety door monitoring

– Automatic start

– Monitoring of external contactors

– Suitable up to category 1, PL c (EN ISO 13849-1),

SIL 1 (EN 62061)

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out and two switches of Type 1

are used

Figure 65 Safety door monitoring/automatic start

17.4 Safety door monitoring/manual, monitored

start

– Non-equivalent safety door monitoring

– Manual, monitored start

– Monitoring of external contactors

– Suitable up to category 1, PL c (EN ISO 13849-1),

SIL 1 (EN 62061)

– Suitable up to category 4, PL e (EN ISO 13849-1),

SIL 3 (EN 62061), if cross-circuits in the control to the

actuator can be ruled out and two switches of Type 1

are used

Figure 66 Safety door monitoring/manual, monitored

start

K1

K2

M

24V

K1

K2

N

L

S1

0V

K2

K1

A1

A2

13

14

PSR-MC50

S12 S13( )

M1( )

23

24

( )

34

33

S34( )

K1

K2

M

24V

K1

K2

N

L

0V

S1K1

K2

S2

A1

A2

13

14

PSR-MC50

S12S34 S13( )( )

M1( )

23

24

( )

34

33

Page 44: PSR-MS and PSR-MC€¦ · 1 enabling current path, US = 24 V DC, fixed screw terminal block PSR-MS30-1NO-24DC-SC 2904952 1 Safety relay for emergency stop and safety doors up to SIL

PSR-MS and PSR-MC

106509_en_01 44PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany

phoenixcontact.com

52

00

75

63

/20

15

-08

-27

/00

18 Revision history

Revision Date Content

00 2015-01-14 First publication

01 2015-08-27 Ordering data changed: Article number 2992239 replaced by material number

52007563

Application examples revised: 4.3, 5.3, 12.1, 12.2, 12.3, 13.5, 16.7, 16.8, 16.9, 16.10,

16.11, 16.12, 16.13, 16.14

Infobox inserted for all application examples up to Cat. 1