Vacuum Test for the Tank Bottom PlateWe will specify the location of the opening through which bubbles are vacuumed, by applying bubbles to the
flange parts etc. and conducting suction from the lower side of the bottom plate.On September 20, vacuum test for the tank bottom plate was conducted, and we found leak from caulking
and mortar installed around the bottom-plate (in-leak), therefore we found no bubble suction.On September 25, after treating the accumulated water under the tank bottom plate, and re-conducting
sealing, we found the two adjacent bolts through which bubbles were vacuumed up.We continue the investigation into leakage.
Bottom plate
Side plate
Inside Outside
Bottom-plate flange partsBottom-plate reinforcement member
Suction from the lower side of the
bottom plate(0.03MPa)
Bottom plateBottom plate
Water-expandable waterproof materialWater-expandable sealing materialSealing material
Concrete foundation Concrete foundation
Sealing*
Suction from the lower side of the bottom plate
Bubbles
Bubbles are vacuumed up through an opening.
Sealing
*We replaced caulking and mortar with sealing of water-proof tapes
180
90270
0
Bubble suction was found here.
September 25, 2013
Tokyo Electric Power Company
Bolts where bubble suction was found.
Approx.
10m
Approx. 12m