ProtoNode FPC-N34 and ProtoNode FPC-N35 Start-up … · (Section 8) ClimateWorx ProtoNode Start-up...

46
Document Revision: 4.A Web Configurator Template Revision: 64 ProtoNode FPC-N34 and ProtoNode FPC-N35 Start-up Guide For Interfacing ClimateWorx Products: M52 Controller To Building Automation Systems: BACnet MS/TP, BACnet/IP, BACnet Ethernet, Modbus TCP/IP, Metasys N2 and LonWorks APPLICABILITY & EFFECTIVITY Explains ProtoNode hardware and how to install it. The instructions are effective for the above as of November 2016.

Transcript of ProtoNode FPC-N34 and ProtoNode FPC-N35 Start-up … · (Section 8) ClimateWorx ProtoNode Start-up...

Document Revision: 4.A Web Configurator

Template Revision: 64

ProtoNode FPC-N34 and ProtoNode FPC-N35 Start-up Guide

For Interfacing ClimateWorx Products: M52 Controller

To Building Automation Systems: BACnet MS/TP, BACnet/IP, BACnet Ethernet, Modbus TCP/IP, Metasys N2 and LonWorks

APPLICABILITY & EFFECTIVITY

Explains ProtoNode hardware and how to install it.

The instructions are effective for the above as of November 2016.

ClimateWorx ProtoNode Start-up Guide

Page 2 of 46

Technical Support

Thank you for purchasing the ProtoNode for ClimateWorx. Please call ClimateWorx for Technical support of the ProtoNode product. Sierra Monitor Corporation does not provide direct support. If ClimateWorx needs to escalate the concern, they will contact Sierra Monitor Corporation for assistance. Support Contact Information:

ClimateWorx 14 Chelsea Lane Brampton, Ontario

Customer Service: (905) 405-0800

Email: [email protected] Website: www.climateworxinternational.com

ClimateWorx ProtoNode Start-up Guide

Page 3 of 46

Quick Start Guide

1. Record the information about the unit. (Section 3.1)

2. Set the device’s COM settings and Node-ID’s for each of the devices that are to connect to

ProtoNode FPC-N34 or FPC-N35. (Section 3.3)

3. ProtoNode FPC-N34 units: Select the Field Protocol on the S Bank Dip Switches. (Section 3.4)

4. BACnet MS/TP (FPC-N34): Set the MAC Address on DIP Switch Bank A. (Section 3.5.1)

5. BACnet MS/TP (FPC-N34): Set the BAUD rate of the BACnet MS/TP Field Protocol on DIP Switch

Bank B. (Section 3.5.2)

6. Connect ProtoNode 6 pin RS-485 connector to the RS-485 network that is connected to each of the

devices. (Section 4.2)

7. Connect ProtoNode FPC-N34’s 3 pin RS-485 port to the Field Protocol cabling, (Section 4.3)

or connect ProtoNode FPC-N35’s 2 pin LonWorks port to the Field Protocol cabling. (Section 4.4)

8. Connect Power to ProtoNode 6 pin connector. (Section 4.5)

9. Use a browser to access the ProtoNode’s embedded tool, which is referred to in this manual as the

Web Configurator, to select the devices that are to attach to the ProtoNode and set the current

Modbus Node-ID for each these products. Once the devices are selected, the ProtoNode

Automatically builds and loads the Configuration for the devices. (Section 5)

10. BACnet/IP or Modbus TCP/IP (FPC-N34): Use a browser to access the ProtoNode Web Configurator

to change the IP Address. No changes to the configuration are necessary. (Section 5.4)

11. LonWorks (FPC-N35): The ProtoNode must be commissioned on the LonWorks Network. This needs

to be done by the LonWorks administrator using a LonWorks Commissioning tool. (Section 8)

ClimateWorx ProtoNode Start-up Guide

Page 4 of 46

TABLE OF CONTENTS

1 Certifications ........................................................................................................................................ 6 1.1 BTL Mark – BACnet

® Testing Laboratory ....................................................................................... 6

1.2 LonMark Certification ...................................................................................................................... 6

2 Introduction .......................................................................................................................................... 7 2.1 ProtoNode Gateway ....................................................................................................................... 7

3 Setup for ProtoNode ............................................................................................................................ 8 3.1 Record Identification Data .............................................................................................................. 8 3.2 Point Count Capacity and Registers per Device ............................................................................ 8 3.3 Configuring Device Communications ............................................................................................. 9

3.3.1 Input COM Settings on all Devices Connected to the ProtoNode ............................................ 9 3.3.2 Set Modbus Node-ID for each Device attached to the ProtoNode ........................................... 9

3.4 Selecting the Desired Field Protocol ............................................................................................ 10 3.5 BMS Network Settings: MAC Address, Device Instance and Baud Rate .................................... 11

3.5.1 BACnet MS/TP (FPC-N34): Setting the MAC Address for BMS Network .............................. 11 3.5.2 BACnet MS/TP (FPC-N34): Setting the Baud Rate for BMS Network .................................... 12

3.5.2.1 Baud Rate DIP Switch Selection ..................................................................................... 12

4 Interfacing ProtoNode to Devices .................................................................................................... 13 4.1 ProtoNode FPC-N34 and FPC-N35 Showing Connection Ports .................................................. 13 4.2 Device Connections to ProtoNode ............................................................................................... 14

4.2.1 Biasing the Modbus RS-485 Device Network ......................................................................... 15 4.2.2 End of Line Termination Switch for the Modbus RS-485 Device Network.............................. 16

4.3 BACnet MS/TP or Metasys N2 (FPC-N34): Wiring Field Port to RS-485 Network ...................... 17 4.4 LonWorks (FPC-N35): Wiring LonWorks Devices to the LonWorks Terminal ............................. 17 4.5 Power-Up ProtoNode.................................................................................................................... 18

5 Use ProtoNode Web Configurator to Setup the Gateway ............................................................. 19 5.1 Connect the PC to ProtoNode via the Ethernet Port .................................................................... 19 5.2 Connecting to ProtoNode Web Configurator ................................................................................ 20 5.3 Selecting Profiles for Devices Connected to ProtoNode .............................................................. 20 5.4 BACnet/IP and Modbus TCP/IP: Setting IP Address for Field Network ....................................... 22

6 BACnet MS/TP and BACnet/IP: Setting Node_Offset to Assign Specific Device Instances ..... 24

7 How to Start the Installation Over: Clearing Profiles ..................................................................... 25

8 LonWorks (FPC-N35): Commissioning ProtoNode on a lonworks Network ............................... 26 8.1 Commissioning ProtoNode FPC-N35 on a LonWorks Network ................................................... 26

8.1.1 Instructions to Download XIF File from ProtoNode FPC-N35 Using Browser ........................ 26

9 BACnet Explorer ................................................................................................................................ 28

Appendix A. Troubleshooting .................................................................................................................. 29 Lost or Incorrect IP Address ............................................................................................ 29 Appendix A.1. Viewing Diagnostic information ........................................................................................ 30 Appendix A.2. Check Wiring and Settings............................................................................................... 31 Appendix A.3. LED Diagnostics for Communications Between ProtoNode and Devices ....................... 32 Appendix A.4. Take Diagnostic Capture with the FieldServer Toolbox .................................................. 33 Appendix A.5. Update Firmware ............................................................................................................. 36 Appendix A.6. BACnet: Setting Network_Number for more than one ProtoNode on Subnet ................. 36 Appendix A.7. Securing ProtoNode with Passwords .............................................................................. 37 Appendix A.8.

Appendix B. Vendor Information - ClimateWorx ................................................................................... 38 M52 Controller Modbus RTU Mappings to BACnet, Metasys N2, Modbus TCP/IP and Appendix B.1.

LonWorks ................................................................................................................................................ 38

Appendix C. “A” Bank DIP Switch Settings ........................................................................................... 42 “A” Bank DIP Switch Settings .......................................................................................... 42 Appendix C.1.

ClimateWorx ProtoNode Start-up Guide

Page 5 of 46

Appendix D. Reference ............................................................................................................................. 45 Specifications ................................................................................................................... 45 Appendix D.1.

Appendix D.1.1. Compliance with UL Regulations ........................................................................... 45

Appendix E. Limited 2 Year Warranty ..................................................................................................... 46

LIST OF FIGURES

Figure 1: ProtoNode Part Numbers .............................................................................................................. 8 Figure 2: Supported Point Count Capacity ................................................................................................... 8 Figure 3: Registers per Device ..................................................................................................................... 8 Figure 4: COM Settings ................................................................................................................................. 9 Figure 5: S Bank DIP Switches ................................................................................................................... 10 Figure 6: MAC Address DIP Switches ........................................................................................................ 11 Figure 7: Baud Rate DIP Switches ............................................................................................................. 12 Figure 8: BMS Baud Rate ........................................................................................................................... 12 Figure 9: ProtoNode FPC-N34 (upper) and ProtoNode FPC-N35 (lower) ................................................. 13 Figure 10: RS-485 and Power Connections ............................................................................................... 14 Figure 11: Modbus RS-485 Biasing Switch on the ProtoNode N34 (left) and ProtoNode N35 (right)........ 15 Figure 12: Modbus RS-485 End-Of-Line Termination Switch on the ProtoNode N34 (left) and ................ 16 Figure 13: Connection from ProtoNode to RS-485 Field Network .............................................................. 17 Figure 14: RS-485 BMS Network EOL Switch ............................................................................................ 17 Figure 15: LonWorks Terminal .................................................................................................................... 17 Figure 16: Required current draw for the ProtoNode .................................................................................. 18 Figure 17: Power Connections .................................................................................................................... 18 Figure 18: Web Configurator Showing no Active Profiles ........................................................................... 20 Figure 19: Web Configurator Showing Active Profile Additions .................................................................. 21 Figure 20: Web Configurator Screen with Active Profiles ........................................................................... 22 Figure 21: Changing IP Address via Web GUI ........................................................................................... 23 Figure 22: Web Configurator Screen .......................................................................................................... 24 Figure 23: LonWorks Service Pin Location ................................................................................................. 26 Figure 24: Sample of Fserver.XIF File Generated ...................................................................................... 27 Figure 25: BACnet Explorer on a BACnet Network .................................................................................... 28 Figure 26: Ethernet Port Location ............................................................................................................... 29 Figure 27: Error Messages Screen ............................................................................................................. 30 Figure 28: Diagnostic LEDs ........................................................................................................................ 32 Figure 29: Ethernet Port Location ............................................................................................................... 33 Figure 30: Web Configurator – Setting Network Number for BACnet......................................................... 36 Figure 31: Specifications ............................................................................................................................. 45

ClimateWorx ProtoNode Start-up Guide

Page 6 of 46

1 CERTIFICATIONS

1.1 BTL Mark – BACnet®1 Testing Laboratory

1.2 LonMark Certif ication

1 BACnet is a registered trademark of ASHRAE

The BTL Mark on ProtoNode is a symbol that indicates that a product has

passed a series of rigorous tests conducted by an independent laboratory

which verifies that the product correctly implements the BACnet features

claimed in the listing. The mark is a symbol of a high-quality BACnet product.

Go to http://www.BACnetInternational.net/btl/ for more information about the BACnet Testing Laboratory. Click here for BACnet PIC Statement.

LonMark International is the recognized authority for certification, education,

and promotion of interoperability standards for the benefit of manufacturers,

integrators and end users. LonMark International has developed extensive

product certification standards and tests to provide the integrator and user with

confidence that products from multiple manufacturers utilizing LonMark

devices work together. Sierra Monitor has more LonMark Certified gateways

than any other gateway manufacturer, including the ProtoCessor, ProtoCarrier

and ProtoNode for OEM applications and the full featured, configurable

gateways.

ClimateWorx ProtoNode Start-up Guide

Page 7 of 46

2 INTRODUCTION

2.1 ProtoNode Gateway

ProtoNode is an external, high performance Building Automation multi-protocol gateway that is

preconfigured to automatically communicate between ClimateWorx’s products (hereafter called

“device”) connected to the ProtoNode and automatically configures them for BACnet MS/TP,

BACnet/IP, BACnet Ethernet, Metasys®2

N2 by JCI, Modbus TCP/IP or LonWorks®3

.

It is not necessary to download any configuration files to support the required applications. The

ProtoNode is pre-loaded with tested Profiles/Configurations for the supported devices.

2 Metasys is a registered trademark of Johnson Controls Inc.

3 LonWorks is a registered trademark of Echelon Corporation

ClimateWorx ProtoNode Start-up Guide

Page 8 of 46

3 SETUP FOR PROTONODE

3.1 Record Identif ication Data

Each ProtoNode has a unique part number located on the side or the back of the unit. This number

should be recorded, as it may be required for technical support. The numbers are as follows:

Model Part Number

ProtoNode FPC-N34 FPC-N34-1088

ProtoNode FPC-N35 FPC-N35-1089

Figure 1: ProtoNode Part Numbers

FPC-N34 units have the following 3 ports: RS-485 + Ethernet + RS-485

FPC-N35 units have the following 3 ports: LonWorks + Ethernet + RS-485

3.2 Point Count Capacity and Registers per Device

The total number of Registers presented by all of the devices attached to the ProtoNode

cannot exceed:

Part number Total Registers

FPC-N34-1088 1,500

FPC-N35-1089 1,500

Figure 2: Supported Point Count Capacity

Devices Registers Per Device

M52 Controller 166

Figure 3: Registers per Device

ClimateWorx ProtoNode Start-up Guide

Page 9 of 46

3.3 Configuring Device Communications

3.3.1 Input COM Settings on all Devices Connected to the ProtoNode

All of the connected serial devices MUST have the same Baud Rate, Data Bits, Stop Bits,

and Parity settings as the ProtoNode.

Figure 4 specifies the device serial port settings required to communicate with the ProtoNode.

Port Setting Device

Protocol Modbus RTU

Baud Rate 9600

Parity None

Data Bits 8

Stop Bits 1

Figure 4: COM Settings

3.3.2 Set Modbus Node-ID for each Device attached to the ProtoNode

Set Modbus Node-ID for each of the devices attached to ProtoNode. The Modbus Node-ID’s

need to be uniquely assigned between 1 and 255.

o The Modbus Node-ID that is assigned for each device needs to be documented

The Modbus Node-ID’s assigned are used for designating the Device Instance

for BACnet/IP and BACnet MS/TP (Section 6)

The Metasys N2 and Modbus TCP/IP field protocol Node-IDs are automatically set to be the

same value as the Node-ID of the Modbus RTU device.

ClimateWorx ProtoNode Start-up Guide

Page 10 of 46

3.4 Selecting the Desired Field Protocol

ProtoNode FPC-N34 units use the “S” bank of DIP switches (S0 – S3) to select the Field

Protocol.

o See the table in Figure 5 for the switch settings to select

o The OFF position is when the DIP switches are set closest to the outside of the box

ProtoNode FPC-N35 units do not use the “S” bank DIP switches (S0 – S3) to select a Field

Protocol.

o On ProtoNode FPC-N35 units, these switches are disabled; the Field Protocol is always

LonWorks

ProtoNode FPC-N34 S Bank DIP Switches

Profile S0 S1 S2 S3

BACnet/IP Off Off Off Off

BACnet MS/TP On Off Off Off

Metasys N2 Off On Off Off

Modbus TCP/IP On On Off Off

BACnet Ethernet Off Off On Off

NOTE: When setting DIP Switches, ensure that power to the board is OFF.

S0 – S3 DIP Switches

S Bank DIP Switch Location

Profile Settings for ProtoNode

Figure 5: S Bank DIP Switches

S0

S1

S2

S3

Off On

ClimateWorx ProtoNode Start-up Guide

Page 11 of 46

3.5 BMS Network Settings: MAC Address, Device Instance and Baud Rate

3.5.1 BACnet MS/TP (FPC-N34): Setting the MAC Address for BMS Network

Only 1 MAC address is set for ProtoNode regardless of how many devices are connected to

ProtoNode.

Set the BACnet MS/TP MAC address of the ProtoNode to a value between 1 to 127 (Master MAC

address); this is so that the BMS Front End can find ProtoNode via BACnet auto discovery.

NOTE: Never set a BACnet MS/TP MAC Address of the ProtoNode to a value from 128 to 255.

Addresses from 128 to 255 are Slave Addresses and can not be discovered by BMS Front Ends

that support Auto-Discovery of BACnet MS/TP devices.

Set “A” bank DIP switches A0 – A7 to assign a MAC Address to the ProtoNode for BACnet

MS/TP.

Refer to Appendix C.1 for the complete range of MAC Addresses and DIP switch settings.

NOTE: When using Metasys N2 and Modbus TCP/IP, the A Bank of DIP switches are disabled and not used. They should be set to OFF.

A0

A1

A2

A3

A4

A5

A6

A7

Off On

NOTE: When setting DIP Switches, ensure that power to the board is OFF.

Figure 6: MAC Address DIP Switches

ClimateWorx ProtoNode Start-up Guide

Page 12 of 46

3.5.2 BACnet MS/TP (FPC-N34): Setting the Baud Rate for BMS Network

“B” bank DIP switches B0 – B3 can be used to set the Field baud rate of the ProtoNode to match

the baud rate required by the Building Management System for BACnet MS/TP.

The baud rate on ProtoNode for Metasys N2 is set for 9600. “B” bank DIP switches B0 – B3 are

disabled for Metasys N2 on ProtoNode FPC-N34.

“B” bank DIP switches B0 – B3 are disabled on ProtoNode FPC-N35 (LonWorks).

B0

B1

B2

B3

Off On

3.5.2.1 Baud Rate DIP Switch Selection

Baud B0 B1 B2 B3

9600 On On On Off

19200 Off Off Off On

38400* On On Off On

57600 Off Off On On

76800 On Off On On

Figure 8: BMS Baud Rate

* Factory default setting = 38400

Figure 7: Baud Rate DIP Switches

ClimateWorx ProtoNode Start-up Guide

Page 13 of 46

4 INTERFACING PROTONODE TO DEVICES

4.1 ProtoNode FPC-N34 and FPC-N35 Showing Connection Ports

Figure 9: ProtoNode FPC-N34 (upper) and ProtoNode FPC-N35 (lower)

ClimateWorx ProtoNode Start-up Guide

Page 14 of 46

4.2 Device Connections to ProtoNode

ProtoNode 6 Pin Phoenix connector for RS-485 Devices.

The 6 pin Phoenix connector is the same for ProtoNode FPC-N34 (BACnet) and FPC-N35

(LonWorks).

Pins 1 through 3 are for RS-485 devices.

o Use standard grounding principles for RS-485 GND

Pins 4 through 6 are for power. Do not connect power until Section 4.4.

Device Pins ProtoNode Pin

# Pin

Assignment

Pin RS-485 + Pin 1 RS-485 +

Pin RS-485 - Pin 2 RS-485 -

Pin GND Pin 3 RS-485 GND

Power In (+) Pin 4 V +

Power In (-) Pin 5 V -

Frame Ground Pin 6 FRAME GND

Figure 10: RS-485 and Power Connections

ClimateWorx ProtoNode Start-up Guide

Page 15 of 46

4.2.1 Biasing the Modbus RS-485 Device Network

An RS-485 network with more than one device needs to have biasing to ensure proper

communication. The biasing only needs to be done on one device.

The ProtoNode has 510 Ohm resistors that can be used to set the biasing. The ProtoNode’s

default positions from the factory for the biasing jumpers are OFF.

The OFF position is when the 2 RED biasing jumpers straddle the 4 pins closest to the outside of

the board of the ProtoNode. (Figure 11).

Only turn biasing ON:

o IF the BMS cannot see more than one device connected to the ProtoNode

o AND all the settings (Modbus COM settings, wiring, and DIP switches) have been

checked

To turn biasing ON, move the 2 RED biasing jumpers to straddle the 4 pins closest to the inside

of the board of the ProtoNode.

RS-485 Bias Switch

(off)

Figure 11: Modbus RS-485 Biasing Switch on the ProtoNode N34 (left) and ProtoNode N35 (right)

ClimateWorx ProtoNode Start-up Guide

Page 16 of 46

4.2.2 End of Line Termination Switch for the Modbus RS-485 Device Network

On long RS-485 cabling runs, the RS-485 trunk must be properly terminated at each end.

The ProtoNode has an End of Line (EOL) blue jumper. The default setting for this Blue EOL

switch is OFF with the jumper straddling the pins closest to the inside of the board of the

ProtoNode.

o On short cabling runs the EOL switch does not to need to be turned ON

If the ProtoNode is placed at one of the ends of the trunk, set the blue EOL jumper to the

ON position straddling the pins closest to the outside of the board of the ProtoNode.

Always leave the single Red Jumper in the A position (default factory setting).

Modbus RS-485 EOL Switch

(off)

Leave in Position A

Figure 12: Modbus RS-485 End-Of-Line Termination Switch on the ProtoNode N34 (left) and ProtoNode N35 (right)

ClimateWorx ProtoNode Start-up Guide

Page 17 of 46

4.3 BACnet MS/TP or Metasys N2 (FPC-N34): Wiring Field Port to RS-485

Network

Connect the BACnet MS/TP or Metasys N2 RS-485 network wires to the 3-pin RS-485 connector

on ProtoNode FPC-N34 as shown below in Figure 13.

o Use standard grounding principles for RS-485 GND

See Section 5.4 for information on connecting to BACnet/IP network.

If the ProtoNode is the last device on the BACnet MS/TP or Metasys N2 trunk, then the

End-Of-Line Termination Switch needs to be enabled (Figure 14).

o The default setting from the factory is OFF (switch position = right side)

o To enable the EOL Termination, turn the EOL switch ON (switch position = left

side)

4.4 LonWorks (FPC-N35): Wiring LonWorks Devices to the LonWorks Terminal

Wire the LonWorks device network to the ProtoNode LonWorks Terminal.

o Use approved cable per the FT-10 installation guidelines

LonWorks has no polarity.

BMS RS-485 Wiring

ProtoNode Pin #

Pin Assignment

RS-485 + Pin 1 RS-485 +

RS-485 - Pin 2 RS-485 -

- Pin 3 RS-485 GND

Figure 14: RS-485 BMS Network EOL Switch

Figure 13: Connection from ProtoNode to RS-485 Field Network

End-of-Line Switch

G

-

+

Figure 15: LonWorks Terminal

ClimateWorx ProtoNode Start-up Guide

Page 18 of 46

4.5 Power-Up ProtoNode

Check power requirements in the table below:

Power Requirement for ProtoNode External Gateway

Current Draw Type

ProtoNode Family 12V DC/AC 24V DC/AC 30V DC

FPC – N34 (Typical) 170mA 100mA 80mA

FPC – N34 (Maximum) 240mA 140mA 100mA

FPC – N35 (Typical) 210mA 130mA 90mA

FPC – N35 (Maximum) 250mA 170mA 110mA

NOTE: These values are ‘nominal’ and a safety margin should be added to the power supply of the host system. A safety margin of 25% is recommended.

Figure 16: Required current draw for the ProtoNode

Apply power to ProtoNode as show below in Figure 17. Ensure that the power supply used

complies with the specifications provided in Appendix D.1.

ProtoNode accepts either 9-30V DC or 12-24V AC on pins 4 and 5.

Frame GND should be connected.

Power to

ProtoNode

ProtoNode

Pin #

Pin

Assignment

Power In (+) Pin 4 V +

Power In (-) Pin 5 V -

Frame Ground Pin 6 FRAME GND

Figure 17: Power Connections

ClimateWorx ProtoNode Start-up Guide

Page 19 of 46

5 USE PROTONODE WEB CONFIGURATOR TO SETUP THE GATEWAY

5.1 Connect the PC to ProtoNode via the Ethernet Port

Connect a CAT5 Ethernet cable (Straight through or Cross-Over) between the local PC and

ProtoNode.

The Default IP Address of ProtoNode is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC

and ProtoNode are on different IP Networks, assign a static IP Address to the PC on the

192.168.1.xxx network.

For Windows XP:

Go to > >

Right-click on Local Area Connection > Properties

Highlight >

For Windows 7 or later:

Go to > >

> >

Right-click on Local Area Connection > Properties

Highlight >

For Windows XP and Windows 7, use the following IP Address:

Click twice.

ClimateWorx ProtoNode Start-up Guide

Page 20 of 46

5.2 Connecting to ProtoNode Web Configurator

After setting a local PC on the same subnet as the ProtoNode (Section 5.1), open a web browser

on the PC and enter the IP Address of the ProtoNode; the default address is 192.168.1.24.

NOTE: If the IP Address of the ProtoNode has been changed by previous configuration, the assigned IP

Address can be discovered using the FS Toolbox utility. See Appendix A.1 for instructions.

5.3 Selecting Profiles for Devices Connected to ProtoNode

NOTE: If Modbus TCP/IP was selected in Section 3.4 for the Field/BMS protocol, skip this section.

Device profiles are NOT used for Modbus TCP/IP.

In the Web Configurator, the Active Profiles section is shown on the lower left side of the screen.

The Active Profiles section lists the currently active device profiles, including previous Web

Configurator additions and any devices identified by Auto-Discovery configuration methods. This

list is empty for new installations, or after clearing all configurations. (Figure 18)

To add an active profile to support a device, click the ADD button under Active Profiles. This will

present a drop-down box underneath the Current Profile column that lists all the available profiles.

For every device that is added, assign a unique Modbus Node-ID. This specification must match

the device’s network settings.

NOTE: If multiple devices are connected to the ProtoNode, set the BACnet Virtual Server Nodes

field to “Yes”; otherwise leave the field on the default “No” setting.

Figure 18: Web Configurator Showing no Active Profiles

ClimateWorx ProtoNode Start-up Guide

Page 21 of 46

Once the Profile for the device has been selected from the drop-down list, enter the value of the

device’s Modbus Node-ID which was assigned in Section 3.3.2.

Then press the “Submit” button to add the Profile to the list of devices to be configured.

Repeat this process until all the devices have been added.

Completed additions are listed under “Active Profiles” as shown in Figure 19.

Figure 19: Web Configurator Showing Active Profile Additions

ClimateWorx ProtoNode Start-up Guide

Page 22 of 46

5.4 BACnet/IP and Modbus TCP/IP: Setting IP Address for Field Network

After setting a local PC to the same subnet as the ProtoNode (Section 5.1), open a web browser

on the PC and enter the IP Address of the ProtoNode; the default address is 192.168.1.24.

The Web Configurator is displayed as the landing page. (Figure 20)

To access the Web GUI, click on the “Diagnostics & Debugging” button in the bottom right

side of the page.

Figure 20: Web Configurator Screen with Active Profiles

ClimateWorx ProtoNode Start-up Guide

Page 23 of 46

From the Web GUI landing page, click on “Setup” to expand the navigation tree and then select

“Network Settings” to access the IP Settings menu. (Figure 21)

Modify the IP Address (N1 IP Address field) of the ProtoNode Ethernet port.

If necessary, change the Netmask (N1 Netmask field).

Type in a new Subnet Mask.

If necessary, change the IP Gateway (Default Gateway field).

Type in a new IP Gateway.

NOTE: If the ProtoNode is connected to a router, the IP Gateway of the ProtoNode should be set to the

IP Address of that router.

Reset ProtoNode.

Unplug Ethernet cable from PC and connect it to the network hub or router.

Record the IP Address assigned to the ProtoNode for future reference.

NOTE: For FieldPoP™ information, refer to the FieldPoP™ Device Cloud Start-up Guide online at

the Sierra Monitor.com Resource Center.

www.sierramonitor.com/customer-care/resource-center

Figure 21: Changing IP Address via Web GUI

ClimateWorx ProtoNode Start-up Guide

Page 24 of 46

6 BACNET MS/TP AND BACNET/IP: SETTING NODE_OFFSET TO ASSIGN

SPECIFIC DEVICE INSTANCES

After setting a local PC to the same subnet as the ProtoNode (Section 5.1), open a web browser

on the PC and enter the IP Address of the ProtoNode; the default address is 192.168.1.24.

o If the IP Address of the ProtoNode has been changed by previous configuration, the

assigned IP Address must be gathered from the network administrator.

o The Web Configurator is displayed as the landing page. (Figure 22)

Node_Offset field shows the current value (default = 50,000).

o The values allowed for a BACnet Device Instance can range from 1 to 4,194,303.

To assign a specific Device Instance (or range); change the Node_Offset value as needed using

the calculation below:

Device Instance (desired) = Node_Offset + Modbus Node_ID

For example, if the desired Device Instance for the 1st device is 1,001 and the following is true:

- Device 1 has a Modbus Node-ID of 1

- Device 2 has a Modbus Node-ID of 22

- Device 3 has a Modbus Node-ID of 33

Then plug the 1st device information into the formula to find the desired Node_Offset:

1,001 = Node_Offset + 1

1,000 = Node_Offset

Once the Node_Offset value is input, it will be applied to all devices as shown below:

- Device 1 Instance = 1,000 + Modbus Node_ID = 1,000 + 1 = 1,001

- Device 2 Instance = 1,000 + Modbus Node_ID = 1,000 + 22 = 1,022

- Device 3 Instance = 1,000 + Modbus Node_ID = 1,000 + 33 = 1,033

Click “Submit” once the desired value is entered.

Figure 22: Web Configurator Screen

ClimateWorx ProtoNode Start-up Guide

Page 25 of 46

7 HOW TO START THE INSTALLATION OVER: CLEARING PROFILES

After setting a local PC to the same subnet as the ProtoNode (Section 5.1), open a web browser

on the PC and enter the IP Address of the ProtoNode; the default address is 192.168.1.24.

If the IP Address of the ProtoNode has been changed by previous configuration, the assigned IP

Address must be gathered from the network administrator.

The Web Configurator is displayed as the landing page.

At the bottom-left of the page, click the “Clear Profiles and Restart” button.

Once restart is complete, all past profiles discovered and/or added via Web configurator are

deleted. The unit can now be reinstalled.

ClimateWorx ProtoNode Start-up Guide

Page 26 of 46

8 LONWORKS (FPC-N35): COMMISSIONING PROTONODE ON A LONWORKS NETWORK

Commissioning may only be performed by the LonWorks administrator.

8.1 Commissioning ProtoNode FPC-N35 on a LonWorks Network

During the commissioning process, the LonWorks Administrator will prompt the User to hit the

Service Pin on the ProtoNode FPC-N35 at a specific point (this step occurs at different points of the

commissioning process for each LonWorks Network Management Tool).

If an XIF file is required, see steps in Section 8.1.1 to generate XIF.

8.1.1 Instructions to Download XIF File from ProtoNode FPC-N35 Using Browser

Connect a CAT5 Ethernet cable (Straight through or Cross-Over) between the PC and

ProtoNode.

The Default IP Address of ProtoNode is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC

and ProtoNode are on different IP Networks, assign a static IP Address to the PC on the

192.168.1.xxx network.

For Windows XP:

Go to > >

Right-click on Local Area Connection > Properties

Highlight >

For Windows 7 or later:

Go to > >

> >

Right-click on Local Area Connection > Properties

Highlight >

Figure 23: LonWorks Service Pin Location

ClimateWorx ProtoNode Start-up Guide

Page 27 of 46

For Windows XP and Windows 7, use the following IP Address:

Click twice.

Open a web browser and go to the following address: [IP Address of ProtoNode]/fserver.xif

o Example: 192.168.1.24/fserver.xif

If the web browser prompts to save the file, save the file onto the PC. If the web browser displays

the xif file as a web page, save the file onto the local PC as “fserver.xif”.

Figure 24: Sample of Fserver.XIF File Generated

ClimateWorx ProtoNode Start-up Guide

Page 28 of 46

9 BACNET EXPLORER

A typical working example of a BACnet Explorer on a BACnet Network:

For additional details related to the BACnet Explorer, go to the Sierra Monitor Resource Center

(www.sierramonitor.com/customer-care/resource-center) and download the BACnet Explorer Start-

up Guide.

For purchasing information, look up the BACnet Explorer page on the Sierra Monitor website

(www.sierramonitor.com/connect/all-protocol-gateway-products/bacnet-explorer) and click on the

“BUY NOW” tab.

Multi-Port Switch

BACnet MS/TP

BACnet/IP

PC Connected to BACnet

Explorer’s Web Browser

BACnet/IP

BACnet Explorer

Modbus RTU up to 32 BACnet

MS/TP devices

BACnet Router

up to 32

BACnet MS/TP

devices

Modbus RTU

Figure 25: BACnet Explorer on a BACnet Network

ClimateWorx ProtoNode Start-up Guide

Page 29 of 46

Appendix A. Troubleshooting

Lost or Incorrect IP Address Appendix A.1.

Ensure that FieldServer Toolbox is loaded onto the local PC. If not, download FieldServer-

Toolbox.zip on the Sierra Monitor webpage, under Customer Care-Resource Center, Software

Downloads:

http://www.sierramonitor.com/customer-care/resource-center?filters=software-downloads

Extract the executable file and complete the installation.

Disable firewall and virus protection software if possible.

Connect a standard CAT5 Ethernet cable between the PC and ProtoNode.

Double click on the FS Toolbox Utility.

Check IP Addresses from the Device listings.

Correct IP Address(es) by right clicking the settings icon and changing the IP Address.

Ethernet Port

Figure 26: Ethernet Port Location

ClimateWorx ProtoNode Start-up Guide

Page 30 of 46

Viewing Diagnostic information Appendix A.2.

Type the IP Address of the ProtoNode into the web browser or use the FieldServer Toolbox to

connect to the ProtoNode.

Click on Diagnostics and Debugging Button, then click on view, and then on connections.

If there are any errors showing on the Connection page, refer to Appendix A.3 for the relevant

wiring and settings.

Figure 27: Error Messages Screen

ClimateWorx ProtoNode Start-up Guide

Page 31 of 46

Check Wiring and Settings Appendix A.3.

No COMS on Modbus RTU side. If the Tx/Rx LEDs are not flashing rapidly then there is a COM

issue. To fix, check the following:

o Visual observations of LEDs on ProtoNode (Appendix A.4)

o Check baud rate, parity, data bits, stop bits

o Check device address

o Verify wiring

o Verify device is connected to the same subnet as the ProtoNode

o Verify the Modbus device was discovered in Web Configurator (Section 5.2)

Field COM problems:

o If Ethernet protocols are used, observe Ethernet LEDs on the ProtoNode (Appendix A.4)

o Check dipswitch settings (using correct baud rate and device instance)

o Verify IP Address setting

o Verify wiring

NOTE: If the problem persists, a Diagnostic Capture needs to be taken and sent to support.

(Appendix A.5)

ClimateWorx ProtoNode Start-up Guide

Page 32 of 46

LED Diagnostics for Communications Between ProtoNode and Devices Appendix A.4.

See the diagram below for ProtoNode FPC-N34 and FPC-N35 LED Locations.

Tag Description

SPL The SPL LED will light if the unit is not getting a response from one or more of the configured devices.

For LonWorks units, LED will light until the unit is commissioned on the LonWorks network.

RUN The RUN LED will start flashing 20 seconds after power indicating normal operation.

ERR The SYS ERR LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady red light will indicate there is a system error on the unit. If this occurs, immediately report the related “system error” shown in the error screen of the GUI interface to support for evaluation.

RX The RX LED will flash when a message is received on the serial port on the 6 pin connector.

If the serial port is not used, this LED is non-operational.

TX The TX LED will flash when a message is sent on the serial port on the 6 pin connector.

If the serial port is not used, this LED is non-operational.

PWR This is the power light and should show steady green at all times when unit is powered.

Figure 28: Diagnostic LEDs

Diagnostic LEDs

ClimateWorx ProtoNode Start-up Guide

Page 33 of 46

Take Diagnostic Capture with the FieldServer Toolbox Appendix A.5.

Once the Diagnostic Capture is complete, email it to [email protected].

The Diagnostic Capture will accelerate diagnosis of the problem.

Ensure that FieldServer Toolbox is Loaded on the PC that is currently being used, or download

FieldServer-Toolbox.zip on the Sierra Monitor webpage, under Customer Care: Resource Center,

Software Downloads:

http://www.sierramonitor.com/customer-care/resource-center?filters=software-downloads

Extract the executable file and complete the installation.

Disable firewall and virus protection software if possible.

Connect a standard CAT5 Ethernet cable between the PC and ProtoNode.

Double click on the FS Toolbox Utility.

Step 1: Take a Log

o Click on the diagnose icon of the desired device

Ethernet Port

Figure 29: Ethernet Port Location

ClimateWorx ProtoNode Start-up Guide

Page 34 of 46

o Select “Full Diagnostic"

NOTE: If desired, the default capture period can be changed

o Click on “Start Diagnostic”

o When the capture period is finished, the “Diagnostic Test Complete” window will appear

ClimateWorx ProtoNode Start-up Guide

Page 35 of 46

Step 2: Send Log

o Once the diagnostic test is complete, a .zip file is saved on the PC

o Choose “Open” to launch explorer and have it point directly at the correct folder

o Send the Diagnostic zip file to [email protected]

ClimateWorx ProtoNode Start-up Guide

Page 36 of 46

Update Firmware Appendix A.6.

To load a new version of the firmware, follow these instructions:

1. Extract and save the new file onto the local PC.

2. Open a web browser and type the IP Address of the FieldServer in the address bar.

o Default IP Address is 192.168.1.24

o Use the FS Toolbox utility if the IP Address is unknown (Appendix A.1)

3. Click on the “Diagnostics & Debugging” button.

4. In the Navigation Tree on the left hand side, do the following:

a. Click on “Setup”

b. Click on “File Transfer”

c. Click on the “Firmware” tab

5. In the Firmware tab, click on “Choose Files” and select the firmware file extracted in step 1.

6. Click on the orange “Submit” button.

7. When the download is complete, click on the “System Restart” button.

BACnet: Setting Network_Number for more than one ProtoNode on Subnet Appendix A.7.

For both BACnet MS/TP and BACnet/IP, if more than one ProtoNode is connected to the same subnet,

they must be assigned unique Network_Number values.

On the main Web Configuration screen, update the Network Number with the “network_nr” field and click

submit. The default value is 50.

Figure 30: Web Configurator – Setting Network Number for BACnet

ClimateWorx ProtoNode Start-up Guide

Page 37 of 46

Securing ProtoNode with Passwords Appendix A.8.

Access to the ProtoNode can be restricted by enabling a password. There are 2 access levels defined by

2 account names: Admin and User.

The Admin account has unrestricted access to the ProtoNode.

The User account can view any ProtoNode information, but cannot make any changes or restart

the ProtoNode.

The password needs to be a minimum of eight characters and is case sensitive.

If the password is lost, click cancel on the password authentication popup window, and email the

password recovery token to [email protected] to receive a temporary password from the

support team. Access the ProtoNode to set a new password.

ClimateWorx ProtoNode Start-up Guide

Page 38 of 46

Appendix B. Vendor Information - ClimateWorx

NOTE: All Modbus TCP/IP registers are the same as the Modbus RTU registers for the serial device. If this point list is needed, contact the OEM. The

Modbus TCP/IP node address of the device is also the same as the Modbus RTU node address.

M52 Controller Modbus RTU Mappings to BACnet, Metasys N2, Modbus TCP/IP and LonWorks Appendix B.1.

Units

Vari

ab

le B

ac N

et

Ty

pe

Vari

ab

le N

um

be

r

Ch

ille

d W

ate

r M

ach

ine

s

Air

Co

ole

d

Wate

r/g

lyco

l co

ole

d

Fre

e C

oo

l

Du

al

Co

ole

d

Notes Point Name

BA

Cn

et

Ob

ject

Ty

pe

BA

Cn

et

Ob

ject

ID

N2 D

ata

Ty

pe

N2 P

oin

t A

dd

ress

Lon Name Lon SNVT

Mo

db

us

Reg

iste

r

Analog Values (Read Only) Software Version AI 1 x x x x x Current Firmware Version Software ver. AI 1 AI 1 nvoSW_Ver_XXX SNVT_count_f 30001

Voltage % AI 2 x x x x x Voltage AI 2 AI 2 nvoVoltage_XXX SNVT_count_f 30002

Refrigeration Circuit 1 Suction Pressure psia AI 3

o o o o

Requires pressure transducer

Pressure.Low1 AI 3 AI 3 nvoPrs_Lo1_XXX SNVT_count_f 30003

Refrigeration Circuit 1 Head Pressure psig AI 4

o o o o Pressure.High1 AI 4 AI 4 nvoPrs_Hi1_XXX SNVT_count_f 30004

Refrigeration Circuit 2 Suction Pressure psia AI 5

do do do do Pressure.Low2 AI 5 AI 5 nvoPrs_Lo2_XXX SNVT_count_f 30005

Refrigeration Circuit 2 Head Pressure psig AI 6

do do do do Pressure.High2 AI 6 AI 6 nvoPrs_Hi2_XXX SNVT_count_f 30006

Chilled Water Entering Temperature 1 10 x C/F AI 7 o

o o o

Requires sensor kit

CW.EWT1 AI 7 AI 7 nvoCW__wt1_XXX SNVT_count_f 30007

Chilled Water Leaving Temperature 1 10 x C/F AI 8 o

o o o CW.LWT1 AI 8 AI 8 nvoCW_Lwt1_XXX SNVT_count_f 30008

Chilled Water Entering Temperature 2 10 x C/F AI 9 o

o o o CW.EWT2 AI 9 AI 9 nvoCW_Ewt2_XXX SNVT_count_f 30009

Chilled Water Leaving Temperature 2 10 x C/F AI 10 o

o o o CW.LWT2 AI 10 AI 10 nvoCW_Lwt2_XXX SNVT_count_f 30010

Circuit 1 Filter Drier Entering Temp 10 x C/F AI 11

o o o o Temp.FilterDriveA1 AI 11 AI 11 nvoTpFlDrA1_XXX SNVT_count_f 30011

Circuit 1 Filter Drier Leaving Temp 10 x C/F AI 12

o o o o Temp.FilterDriveB1 AI 12 AI 12 nvoTpFlDrB1_XXX SNVT_count_f 30012

Circuit 1 Filter Drier Entering Temp 10 x C/F AI 11

do do do do Temp.FilterDriveA2 AI 13 AI 13 nvoTpFlDrA2_XXX SNVT_count_f 30013

Circuit 1 Filter Drier Leaving Temp 10 x C/F AI 12

do do do do Temp.FilterDriveB2 AI 14 AI 14 nvoTpFlDrB2_XXX SNVT_count_f 30014

Return Air Temperature 10 x C/F AI 15 x x x x x Temp.ReturnAir AI 15 AI 15 nvoTmpRetAr_XXX SNVT_count_f 30015

Return Air Humidity 10 x %RH AI 16 x x x x x Hum.ReturnAir AI 16 AI 16 nvoHumRetAr_XXX SNVT_count_f 30016

Supply Air Temperature 10 x C/F AI 17 o o o o o Requries sensor designated as supply air

Temp.SupplyAir AI 17 AI 17 nvoTmpSupAr_XXX SNVT_count_f 30017

Supply Air Humidity 10 x %RH AI 18 o o o o o Hum.SupplyAir AI 18 AI 18 nvoHumSupAr_XXX SNVT_count_f 30018

Fan Run Time Hours AI 19 x x x x x Fan runtime AI 19 AI 19 nvoFanRunTm_XXX SNVT_count_f 30019

Compressor 1 Run Time Hours AI 20

x x x x Comp.1 runtime AI 20 AI 20 nvoCmp1RnTm_XXX SNVT_count_f 30020

Compressor 2 Run Time Hours AI 21

d d d d Comp.2 runtime AI 21 AI 21 nvoCmp2RnTm_XXX SNVT_count_f 30021

Heater 1 Run Time Hours AI 22 o o o o o For Staged Reheat only, not on machines with SCR control

Heater1 runtime AI 22 AI 22 nvoHt1RunTm_XXX SNVT_count_f 30022

Heater 2 Run Time Hours AI 23 o o o o o Heater2 runtime AI 23 AI 23 nvoHt2RunTm_XXX SNVT_count_f 30023

Heater 3 Run Time Hours AI 24 o o o o o Heater3 runtime AI 24 AI 24 nvoHt3RunTm_XXX SNVT_count_f 30024

Humidifier Run Time Hours AI 25 o o o o o Humid. Runtime AI 25 AI 25 nvoHumRunTm_XXX SNVT_count_f 30025

Cooling Run Time Hours AI 26 x x x x x Cooling runtime AI 26 AI 26 nvoCoolRnTm_XXX SNVT_count_f 30026

Unit Type 0,1,2 AI 27 x x x x x Single, Dual, CHW UnitStatus AI 27 AI 27 nvoUnitStat_XXX SNVT_count_f 30027

EC Fan Speed % AI 28 o o o o o Machines with EC fans Main-AO01 AI 28 AI 28 nvoMainAO01_XXX SNVT_count_f 30028

Reheat Demand % AI 29 o o o o o Main-AO02 AI 29 AI 29 nvoMainAO02_XXX SNVT_count_f 30029

De-humidification/ Cooling Demand % AI 30 o o o o o Main-AO03 AI 30 AI 30 nvoMainAO03_XXX SNVT_count_f 30030

Humidification Demand % AI 31 o o o o o Main-AO04 AI 31 AI 31 nvoMainAO04_XXX SNVT_count_f 30031

Circuit 1 Water Regulating Valve Signal % AI 32

o o o Requires pressure transducer & modulating valve

EX-AO01 AI 32 AI 32 nvoEx_AO01_XXX SNVT_count_f 30032

ClimateWorx ProtoNode Start-up Guide

Page 39 of 46

Free Cooling 1 Valve Signal % AI 33

x

EX-AO02 AI 33 AI 33 nvoEx_AO02_XXX SNVT_count_f 30033

Circuit 2 Water Regulating Valve Signal % AI 34

do do do Requires pressure transducer & modulating valve

EX-AO03 AI 34 AI 34 nvoEx_AO03_XXX SNVT_count_f 30034

Free Cooling 2 Valve Signal % AI 35

do

EX-AO04 AI 35 AI 35 nvoEx_AO04_XXX SNVT_count_f 30035

Analog Variables (Read Write)

Duty Unit Number AV 1 c c c c c DutyUnitNum AV 1 AO 1 nvi/nvoDtyUnNum_XXX SNVT_count_f 40001

Temperature Setpoint (in C) 10 x C AV 2 x x x x x variables are independent but function the same

TempSetpoint1 AV 2 AO 2 nvi/nvoTmpSP1_XXX SNVT_count_f 40002

Temperature Setpoint (in F) 10 x F AV 3 x x x x x TempSetpoint2 AV 3 AO 3 nvi/nvoTmpSP2_XXX SNVT_count_f 40003

Humidity Setpoint % AV 4 o o o o o HumidSetpoint AV 4 AO 4 nvi/nvoHumidSP_XXX SNVT_count_f 40004

Stand by Number number AV 5 c c c c c StandbyNum AV 5 AO 5 nvi/nvoStndbyNum_XXX SNVT_count_f 40005

Fan Speed in Reheat, Dehumidification and Humidification Mode

% AV 6 o o o o o Only machines with EC fans, or VFD fan control

NormalFan AV 6 AO 6 nvi/nvoNormalFan_XXX SNVT_count_f 40006

Fan Speed in Standby Mode % AV 7 o o o o o

BackUpFan AV 7 AO 7 nvi/nvoBackupFan_XXX SNVT_count_f 40007

Fan Minimum Speed in Cooling Mode % AV 8 o o o o o

CoolingMinFan AV 8 AO 8 nvi/nvoCoolMinFn_XXX SNVT_count_f 40008

Fan Maximum Speed in Cooling Mode % AV 9 o o o o o

CoolingMaxFan AV 9 AO 9 nvi/nvoCoolMaxFn_XXX SNVT_count_f 40009

Auto Change Over Hours AV 15 c c c c c AutoChangeOver AV 15 AO 15 nvi/nvoAutoChgov_XXX SNVT_count_f 40015

Warm Up Period Seconds AV 16 x x x x x WarmupPeriod AV 16 AO 16 nvi/nvoWarmupPer_XXX SNVT_count_f 40016

Fan Purge Delay Seconds AV 17 x x x x x FanPurgeDelay AV 17 AO 17 nvi/nvoFanPrgDel_XXX SNVT_count_f 40017

Compressor Mimimum Off Time Seconds AV 18

x x x x CompElapse AV 18 AO 18 nvi/nvoCompElpse_XXX SNVT_count_f 40018

Compressor Minimum Run Time Seconds AV 19

x x x x CompMinTime AV 19 AO 19 nvi/nvoCompMinTm_XXX SNVT_count_f 40019

Positive Start Delay Seconds AV 20

x x x x PosStartDelay AV 20 AO 20 nvi/nvoPsStrtDel_XXX SNVT_count_f 40020

Humid Alarm Delay Seconds AV 21 o o o o o HumidSerDelay AV 21 AO 21 nvi/nvoHumSerDel_XXX SNVT_count_f 40021

Pump Ser Delay (high limit alarm delay) Seconds AV 22 o o o o o PumpSerdelay AV 22 AO 22 nvi/nvoPmpSerDel_XXX SNVT_count_f 40022

Temperature Units (C/F) 0,1 AV 23 x x x x x 0: Celsius, 1: Fahrenheit TempUnits AV 23 AO 23 nvi/nvoTmpUnits_XXX SNVT_count_f 40023

Sensor Display 0,1 AV 24 x x x x x 0: Unit, 1: Site SensorDisplay AV 24 AO 24 nvi/nvoSensDisp_XXX SNVT_count_f 40024

Temperature Dead Band 10 x C AV 26 x x x x x Control loop PID variables TempDeadBand1 AV 26 AO 26 nvi/nvoTmpDdBnd1_XXX SNVT_count_f 40026

Temperatue Relax Band 10 x C AV 27 x x x x x

TempRelaxBand1 AV 27 AO 27 nvi/nvoTpRlxBnd1_XXX SNVT_count_f 40027

Temperature Dead Band 10 x F AV 28 x x x x x

TempDeadBand2 AV 28 AO 28 nvi/nvoTmpDdBnd2_XXX SNVT_count_f 40028

Temperatue Relax Band 10 x F AV 29 x x x x x

TempRelaxBand2 AV 29 AO 29 nvi/nvoTpRlxBnd2_XXX SNVT_count_f 40029

Humidifier Dead Band %RH AV 30 o o o o o

HumDeadBand AV 30 AO 30 nvi/nvoHumDdbnd_XXX SNVT_count_f 40030

Humidifier Relax Band %RH AV 31 o o o o o

RelaxBandHumid AV 31 AO 31 nvi/nvoRelBndHum_XXX SNVT_count_f 40031

Cooling Proportional Band 10 x C AV 32 x x x x x

PropBandCool1 AV 32 AO 32 nvi/nvoPrpBndCl1_XXX SNVT_count_f 40032

Heating Proportional Band 10 x C AV 33 o o o o o

PropBandHeat1 AV 33 AO 33 nvi/nvoPrpBndHt1_XXX SNVT_count_f 40033

Cooling Proportional Band 10 x F AV 34 x x x x x

PropBandCool2 AV 34 AO 34 nvi/nvoPrpBndCl2_XXX SNVT_count_f 40034

Heating Proportional Band 10 x F AV 35 o o o o o

PropBandHeat2 AV 35 AO 35 nvi/nvoPrpBndHt2_XXX SNVT_count_f 40035

Humidification Proportional Band %RH AV 36 o o o o o

PropBandHumid AV 36 AO 36 nvi/nvoPrpBndHum_XXX SNVT_count_f 40036

De-humidification Proportional Band %RH AV 37 o o o o o

PropBandDehum AV 37 AO 37 nvi/nvoPrpBndDeh_XXX SNVT_count_f 40037

Temperature Integral Time Seconds AV 38 x x x x x

TempITime AV 38 AO 38 nvi/nvoTmpiTime_XXX SNVT_count_f 40038

Humidification Integral Time Seconds AV 39 o o o o o

HumidITime AV 39 AO 39 nvi/nvoHumidiTme_XXX SNVT_count_f 40039

Temperature Differential Time Seconds AV 40 x x x x x

TempDTime AV 40 AO 40 nvi/nvoTmpdTime_XXX SNVT_count_f 40040

Humidification Differential Time Seconds AV 41 o o o o o

HumidDTime AV 41 AO 41 nvi/nvoHumiddTme_XXX SNVT_count_f 40041

Humidification Control 0,1 AV 42 o o o o o 0:Disable,1:Enable HumidControl AV 42 AO 42 nvi/nvoHumidCtrl_XXX SNVT_count_f 40042

Re Heat Control 0,1 AV 43 o o o o o 0:Disable,1:Enable ReHaetControl AV 43 AO 43 nvi/nvoRehtCtrl_XXX SNVT_count_f 40043

De-humidification Control 0,1 AV 44 o o o o o 0:Disable,1:Enable DeHumControl AV 44 AO 44 nvi/nvoDeHumCtrl_XXX SNVT_count_f 40044

Free Cooling Control 0,1 AV 45

x

0:Disable,1:Enable FreeCoolingControl AV 45 AO 45 nvi/nvoFreClCtrl_XXX SNVT_count_f 40045

Free-cooling Temperature Difference 10 x C AV 47

x

Free-cooling T/D AV 47 AO 47 nvi/nvoFreeClT_D_XXX SNVT_count_f 40047

Free Cooling High Limit 10 x C AV 48

x

Free-cooling H/L AV 48 AO 48 nvi/nvoFreeClH_L_XXX SNVT_count_f 40048

Free-cooling Temperature Difference 10 x F AV 49

x

Free-cooling T/D_2 AV 49 AO 49 nvi/nvoFreClT_D2_XXX SNVT_count_f 40049

Free Cooling High Limit 10 x F AV 50

x

Free-cooling H/L_2 AV 50 AO 50 nvi/nvoFreClH_L2_XXX SNVT_count_f 40050

Damper End Switch Delay Seconds AV 51 o o o o o DamperEndSwitchDelay AV 51 AO 51 nvi/nvoDmpEdSwDl_XXX SNVT_count_f 40051

Operating Mode 0,1,2 AV 52 x x x x x 0:Local,1:Remote,2:Timer On/Off Mode AV 52 AO 52 nvi/nvoOnOffMode_XXX SNVT_count_f 40052

Control Sensor 0,1,2 AV 54 x x x x x 0:Return,1:Supply,2:Mix, Control Sensor AV 54 AO 54 nvi/nvoCtrlSens_XXX SNVT_count_f 40054

ClimateWorx ProtoNode Start-up Guide

Page 40 of 46

Regulating Valve Start Positon % AV 55

o o o o Used in systems with PID control on condenser water valve

M-AoCoolingFirst AV 55 AO 55 nvi/nvoM_AOCl1st_XXX SNVT_count_f 40055

Head Pressure Setpoint psig AV 56

o o o o HighPressureSetValue AV 56 AO 56 nvi/nvoHiPrStVal_XXX SNVT_count_f 40056

Head Pressure Control Deadband psi AV 57

o o o o HighPressureDeadBand AV 57 AO 57 nvi/nvoHiPrDdBnd_XXX SNVT_count_f 40057

Water Reg Valve Minimum Position % AV 58

o o o o E-AO01ValueMin AV 58 AO 58 nvi/nvoE_AO1VlMn_XXX SNVT_count_f 40058

Temperature Control 0,1 AV 59 o o o o o 0: Average, 1: Maximum Reserve58 AV 59 AO 59 nvi/nvoReserve58_XXX SNVT_count_f 40059

Return Temperature High Limit 10 x C AV 61 x x x x x Temp1HiLimit1 AV 61 AO 61 nvi/nvoTp1HiLim1_XXX SNVT_count_f 40061

Temperature Low Limit 10 x C AV 62 x x x x x Temp1LowLimit1 AV 62 AO 62 nvi/nvoTp1LoLim1_XXX SNVT_count_f 40062

Temperature High Limit 10 x F AV 63 x x x x x Temp1HiLimit2 AV 63 AO 63 nvi/nvoTp1HiLim2_XXX SNVT_count_f 40063

Temperature Low Limit 10 x F AV 64 x x x x x Temp1LowLimit2 AV 64 AO 64 nvi/nvoTp1LoLim2_XXX SNVT_count_f 40064

Compressor Restart Delay Seconds AV 65

x x x x RestartDelay AV 65 AO 65 nvi/nvoRestrtDel_XXX SNVT_count_f 40065

Humidification High Limit %RH AV 66 o o o o o HumidHiLimit1 AV 66 AO 66 nvi/nvoHumHiLim1_XXX SNVT_count_f 40066

Humidification Low Limit %RH AV 67 o o o o o HumidLoLimit AV 67 AO 67 nvi/nvoHumLoLim_XXX SNVT_count_f 40067

Temperature 2 High Limit 10 x C AV 68 x x x x x Temp2HiLimit1 AV 68 AO 68 nvi/nvoTp2HiLim1_XXX SNVT_count_f 40068

Temperature 2 Low Limit 10 x C AV 69 x x x x x Temp2LoLimit1 AV 69 AO 69 nvi/nvoTp2LoLim1_XXX SNVT_count_f 40069

Temperature 2 High Limit 10 x F AV 70 x x x x x Temp2HiLimit2 AV 70 AO 70 nvi/nvoTp2HiLim2_XXX SNVT_count_f 40070

Temperature 2 Low Limit 10 x F AV 71 x x x x x Temp2LoLimit2 AV 71 AO 71 nvi/nvoTp2LoLim2_XXX SNVT_count_f 40071

Humidity High Limit 2 (supply) %RH AV 73 o o o o o Humid2HiLimit AV 73 AO 73 nvi/nvoHum2HiLim_XXX SNVT_count_f 40073

Humidity Low Limit 2 (supply) %RH AV 74 o o o o o Humid2LoLimit AV 74 AO 74 nvi/nvoHum2LoLim_XXX SNVT_count_f 40074

Voltage High Limit % AV 75 x x x x x VoltHiLimit AV 75 AO 75 nvi/nvoVoltHiLim_XXX SNVT_count_f 40075

Voltage Low Limit % AV 76 x x x x x VoltLoLimit AV 76 AO 76 nvi/nvoVoltLoLim_XXX SNVT_count_f 40076

Heater Minimum On AV 80 o o o o o HeaterMinOn AV 80 AO 80 nvi/nvoHtrMinOn_XXX SNVT_count_f 40080

Cooling Minimum On AV 81 x o o o o CoolMinOn AV 81 AO 81 nvi/nvoCoolMinOn_XXX SNVT_count_f 40081

EC Fan Speed % AV 82 o o o o o Main-AO01 AV 82 AO 82 nvi/nvoMain_AO01_XXX SNVT_count_f 40082

Heating Output % AV 83 o o o o o Main-AO02 AV 83 AO 83 nvi/nvoMain_AO02_XXX SNVT_count_f 40083

Cooling Demand (Valve Position) % AV 84 x

x x Main-AO03 AV 84 AO 84 nvi/nvoMain_AO03_XXX SNVT_count_f 40084

Water Reg Valve 1 Position % AV 85

o o o EX-AO01 AV 85 AO 85 nvi/nvoEx_AO01_XXX SNVT_count_f 40085

Free Cooling Valve 1 Position % AV 86

x

EX-AO02 AV 86 AO 86 nvi/nvoEx_AO02_XXX SNVT_count_f 40086

Water Reg Valve 2 Position % AV 87

d d d EX-AO03 AV 87 AO 87 nvi/nvoEx_AO03_XXX SNVT_count_f 40087

Free Cooling Valve 2 Position % AV 88

x

EX-AO04 AV 88 AO 88 nvi/nvoEx_AO04_XXX SNVT_count_f 40088

Humidifier Output Signal % AV 89 o o o o o Main-AO04 AV 89 AO 89 nvi/nvoMain_AO04_XXX SNVT_count_f 40089

Sensor Mode 0,1,2 AV 91 x x x x x 0:Local,1:Remote,2:Disable SensorMode AV 91 AO 91 nvi/nvoSensorMod_XXX SNVT_count_f 40091

Control Mode 0, 1 AV 109 x x x x x 0:Auto,1:Manual ControlMode AV 109 AO 109 nvi/nvoCtrlMode_XXX SNVT_count_f 40109

Voltage Reference (Calibration) AV 110 x x x x x VoltageRefrence AV 110 AO 110 nvi/nvoVoltRef_XXX SNVT_count_f 40110

Return Temperature Offset 10 x C AV 111 x x x x x Used to adjust sensor readings ReturnTempratureOffset AV 111 AO 111 nvi/nvoRetTmpOff_XXX SNVT_count_f 40111

Return Humidity Offset %RH AV 112 x x x x x

ReturnHumidtyOffset AV 112 AO 112 nvi/nvoRetHumOff_XXX SNVT_count_f 40112

Supply Temperature Offset 10 x C AV 113 o o o o o

SupplyTempratureOffset AV 113 AO 113 nvi/nvoSupTmpOff_XXX SNVT_count_f 40113

Supply Humidity Offset %RH AV 114 o o o o o

SupplyHumidtyOffset AV 114 AO 114 nvi/nvoSupHumOff_XXX SNVT_count_f 40114

Return Temperature Offset 10 x F AV 115 x x x x x

ReturnTempratureOffset2 AV 115 AO 115 nvi/nvoRetTpOff2_XXX SNVT_count_f 40115

Supply Temperature Offset 10 x F AV 116 o o o o o

SupplyTempratureOffset2 AV 116 AO 116 nvi/nvoSupTpOff2_XXX SNVT_count_f 40116

Binary Output (Read Only) Fan Fault BI 1 x x x x x Fan Fault BI 1 DI 1 nvoFanFault_XXX SNVT_switch 10001

Low Airflow Alarm BI 2 x x x x x Low Airflow BI 2 DI 2 nvoLoAirFlow_XXX SNVT_switch 10002

Humidifier Alarm BI 3 o o o o o Humidifier Fault BI 3 DI 3 nvoHumFault_XXX SNVT_switch 10003

Heater High Limit Alarm (Overheat) BI 4 o o o o o Heater Overheat BI 4 DI 4 nvoHtrOvrht_XXX SNVT_switch 10004

Dirty Filter Alarm BI 5 x x x x x Filter dirty BI 5 DI 5 nvoFltrDirty_XXX SNVT_switch 10005

Fire Alarm/ Emergency Power Off BI 6 x x x x x Fire Alarm/Emergency Power Off

BI 6 DI 6 nvoFireAlarm_XXX SNVT_switch 10006

Liquid Detection Alarm BI 7 o o o o o Liquid Detection BI 7 DI 7 nvoLiqDet_XXX SNVT_switch 10007

Condensate Overflow/ Condensate Pump Alarm

BI 8 o o o o o Condensate overflow/pump alarm

BI 8 DI 8 nvoCndOvrFlo_XXX SNVT_switch 10008

Power Phase Loss Alarm BI 9 o o o o o Power Phase Lose BI 9 DI 9 nvoPwrPhsLos_XXX SNVT_switch 10009

Compressor 1 High Pressure Alarm BI 10

x x x x Comp.1 H pressure BI 10 DI 10 nvoComp1HPrs_XXX SNVT_switch 10010

Compressor 1 Low Pressure Alarm BI 11

x x x x Comp.1 L pressure BI 11 DI 11 nvoComp1LPrs_XXX SNVT_switch 10011

ClimateWorx ProtoNode Start-up Guide

Page 41 of 46

Compressor 1 Overload Alarm BI 12

x x x x Comp.1 Overload BI 12 DI 12 nvoComp1Over_XXX SNVT_switch 10012

Compressor 2 High Pressure BI 13

d d d d Comp.2 H pressure BI 13 DI 13 nvoComp2HPrs_XXX SNVT_switch 10013

Compressor 2 Low Pressure Alarm BI 14

d d d d Comp.2 L pressure BI 14 DI 14 nvoComp2LPrs_XXX SNVT_switch 10014

Compressor 2 Overload Alarm BI 15

d d d d Comp.2 Overload BI 15 DI 15 nvoComp2Over_XXX SNVT_switch 10015

High Return Temperature Alarm BI 16 x x x x x High R.Temp BI 16 DI 16 nvoHiRTmp_XXX SNVT_switch 10016

Low Return Temperature Alarm BI 17 x x x x x Low R.Temp BI 17 DI 17 nvoLoRTmp_XXX SNVT_switch 10017

High Return Humidity Alarm BI 18 x x x x x High R.Humidity BI 18 DI 18 nvoHiRHum_XXX SNVT_switch 10018

Loss of Return Air Sensor BI 19 x x x x x Low R.Humidity BI 19 DI 19 nvoLoRHum_XXX SNVT_switch 10019

High Supply Temperature Alarm BI 20 o o o o o Lose of R.Sensor BI 20 DI 20 nvoLossofRSn_XXX SNVT_switch 10020

High Supply Air Temp BI 21 o o o o o High S.Temp BI 21 DI 21 nvoHiSTmp_XXX SNVT_switch 10021

Low Supply AirTemp BI 22 o o o o o Low S.Temp BI 22 DI 22 nvoLoSTmp_XXX SNVT_switch 10022

High Supply Air Humidity BI 23 o o o o o High S.Humidity BI 23 DI 23 nvoHiSHum_XXX SNVT_switch 10023

Low Supply Air Humidity BI 24 o o o o o Low S.Humidity BI 24 DI 24 nvoLoSHum_XXX SNVT_switch 10024

Lose of Supply Air Sensor BI 25 o o o o o Lose of S.Sensor BI 25 DI 25 nvoLossofSSn_XXX SNVT_switch 10025

High voltage BI 26 x x x x x High voltage BI 26 DI 26 nvoHiVolt_XXX SNVT_switch 10026

Low voltage BI 27 x x x x x Low voltage BI 27 DI 27 nvoLoVolt_XXX SNVT_switch 10027

Custom Fault 1 BI 28 x x x x x Custom Fault 1 BI 28 DI 28 nvoCustmFlt1_XXX SNVT_switch 10028

Custom Fault 2 BI 29 x x x x x Custom Fault 2 BI 29 DI 29 nvoCustmFlt2_XXX SNVT_switch 10029

Lose of Comp.EX1 BI 30

x x x x Lose of Comp.EX1 BI 30 DI 30 nvoLosCmpEx1_XXX SNVT_switch 10030

Lose of Comp.EX2 BI 31

d d d d High S.Temp BI 31 DI 31 nvoHiSTmp_XXX SNVT_switch 10031

Filter Drier Drity BI 32

o o o o Requires Filter Drier Sensor Package Low S.Temp BI 32 DI 32 nvoLoSTmp_XXX SNVT_switch 10032

Binary Inputs (Read Write) Standby enable BV 1 x x x x x 1

General Alarm BV 2 x x x x x 2

Critical Alarm BV 3 x x x x x 3

Fan Motor BV 4 x x x x x 4

Humidifier BV 5 o o o o o 5

Reheat Stage 1 BV 6 o o o o o These values require staged reheat 6

Reheat Stage 2 BV 7 o o o o o

7

Reheat Stage 3 BV 8 o o o o o

8

Pump BV 9 x

x x x 9

Humidifier 25% Output BV 10 o o o o o 10

SetManualMode BV 12 x x x x x Sets manual mode 12

On/Off BV 13 x x x x x Turns Unit On or Off 13

Restore Default Settings BV 41 x x x x x 41

Restore Default Alarm Settings BV 42 x x x x x 42

ClimateWorx ProtoNode Start-up Guide

Page 42 of 46

Appendix C. “A” Bank DIP Switch Settings

“A” Bank DIP Switch Settings Appendix C.1.

Address A0 A1 A2 A3 A4 A5 A6 A7

1 On Off Off Off Off Off Off Off

2 Off On Off Off Off Off Off Off

3 On On Off Off Off Off Off Off

4 Off Off On Off Off Off Off Off

5 On Off On Off Off Off Off Off

6 Off On On Off Off Off Off Off

7 On On On Off Off Off Off Off

8 Off Off Off On Off Off Off Off

9 On Off Off On Off Off Off Off

10 Off On Off On Off Off Off Off

11 On On Off On Off Off Off Off

12 Off Off On On Off Off Off Off

13 On Off On On Off Off Off Off

14 Off On On On Off Off Off Off

15 On On On On Off Off Off Off

16 Off Off Off Off On Off Off Off

17 On Off Off Off On Off Off Off

18 Off On Off Off On Off Off Off

19 On On Off Off On Off Off Off

20 Off Off On Off On Off Off Off

21 On Off On Off On Off Off Off

22 Off On On Off On Off Off Off

23 On On On Off On Off Off Off

24 Off Off Off On On Off Off Off

25 On Off Off On On Off Off Off

26 Off On Off On On Off Off Off

27 On On Off On On Off Off Off

28 Off Off On On On Off Off Off

29 On Off On On On Off Off Off

30 Off On On On On Off Off Off

31 On On On On On Off Off Off

32 Off Off Off Off Off On Off Off

33 On Off Off Off Off On Off Off

34 Off On Off Off Off On Off Off

35 On On Off Off Off On Off Off

36 Off Off On Off Off On Off Off

37 On Off On Off Off On Off Off

38 Off On On Off Off On Off Off

39 On On On Off Off On Off Off

40 Off Off Off On Off On Off Off

41 On Off Off On Off On Off Off

42 Off On Off On Off On Off Off

43 On On Off On Off On Off Off

44 Off Off On On Off On Off Off

45 On Off On On Off On Off Off

46 Off On On On Off On Off Off

Address A0 A1 A2 A3 A4 A5 A6 A7

47 On On On On Off On Off Off

48 Off Off Off Off On On Off Off

49 On Off Off Off On On Off Off

50 Off On Off Off On On Off Off

51 On On Off Off On On Off Off

52 Off Off On Off On On Off Off

53 On Off On Off On On Off Off

54 Off On On Off On On Off Off

55 On On On Off On On Off Off

56 Off Off Off On On On Off Off

57 On Off Off On On On Off Off

58 Off On Off On On On Off Off

59 On On Off On On On Off Off

60 Off Off On On On On Off Off

61 On Off On On On On Off Off

62 Off On On On On On Off Off

63 On On On On On On Off Off

64 Off Off Off Off Off Off On Off

65 On Off Off Off Off Off On Off

66 Off On Off Off Off Off On Off

67 On On Off Off Off Off On Off

68 Off Off On Off Off Off On Off

69 On Off On Off Off Off On Off

70 Off On On Off Off Off On Off

71 On On On Off Off Off On Off

72 Off Off Off On Off Off On Off

73 On Off Off On Off Off On Off

74 Off On Off On Off Off On Off

75 On On Off On Off Off On Off

76 Off Off On On Off Off On Off

77 On Off On On Off Off On Off

78 Off On On On Off Off On Off

79 On On On On Off Off On Off

80 Off Off Off Off On Off On Off

81 On Off Off Off On Off On Off

82 Off On Off Off On Off On Off

83 On On Off Off On Off On Off

84 Off Off On Off On Off On Off

85 On Off On Off On Off On Off

86 Off On On Off On Off On Off

87 On On On Off On Off On Off

88 Off Off Off On On Off On Off

89 On Off Off On On Off On Off

90 Off On Off On On Off On Off

91 On On Off On On Off On Off

92 Off Off On On On Off On Off

ClimateWorx ProtoNode Start-up Guide

Page 43 of 46

Address A0 A1 A2 A3 A4 A5 A6 A7

93 On Off On On On Off On Off

94 Off On On On On Off On Off

95 On On On On On Off On Off

96 Off Off Off Off Off On On Off

97 On Off Off Off Off On On Off

98 Off On Off Off Off On On Off

99 On On Off Off Off On On Off

100 Off Off On Off Off On On Off

101 On Off On Off Off On On Off

102 Off On On Off Off On On Off

103 On On On Off Off On On Off

104 Off Off Off On Off On On Off

105 On Off Off On Off On On Off

106 Off On Off On Off On On Off

107 On On Off On Off On On Off

108 Off Off On On Off On On Off

109 On Off On On Off On On Off

110 Off On On On Off On On Off

111 On On On On Off On On Off

112 Off Off Off Off On On On Off

113 On Off Off Off On On On Off

114 Off On Off Off On On On Off

115 On On Off Off On On On Off

116 Off Off On Off On On On Off

117 On Off On Off On On On Off

118 Off On On Off On On On Off

119 On On On Off On On On Off

120 Off Off Off On On On On Off

121 On Off Off On On On On Off

122 Off On Off On On On On Off

123 On On Off On On On On Off

124 Off Off On On On On On Off

125 On Off On On On On On Off

126 Off On On On On On On Off

127 On On On On On On On Off

128 Off Off Off Off Off Off Off On

129 On Off Off Off Off Off Off On

130 Off On Off Off Off Off Off On

131 On On Off Off Off Off Off On

132 Off Off On Off Off Off Off On

133 On Off On Off Off Off Off On

134 Off On On Off Off Off Off On

135 On On On Off Off Off Off On

136 Off Off Off On Off Off Off On

137 On Off Off On Off Off Off On

138 Off On Off On Off Off Off On

139 On On Off On Off Off Off On

140 Off Off On On Off Off Off On

141 On Off On On Off Off Off On

Address A0 A1 A2 A3 A4 A5 A6 A7

142 Off On On On Off Off Off On

143 On On On On Off Off Off On

144 Off Off Off Off On Off Off On

145 On Off Off Off On Off Off On

146 Off On Off Off On Off Off On

147 On On Off Off On Off Off On

148 Off Off On Off On Off Off On

149 On Off On Off On Off Off On

150 Off On On Off On Off Off On

151 On On On Off On Off Off On

152 Off Off Off On On Off Off On

153 On Off Off On On Off Off On

154 Off On Off On On Off Off On

155 On On Off On On Off Off On

156 Off Off On On On Off Off On

157 On Off On On On Off Off On

158 Off On On On On Off Off On

159 On On On On On Off Off On

160 Off Off Off Off Off On Off On

161 On Off Off Off Off On Off On

162 Off On Off Off Off On Off On

163 On On Off Off Off On Off On

164 Off Off On Off Off On Off On

165 On Off On Off Off On Off On

166 Off On On Off Off On Off On

167 On On On Off Off On Off On

168 Off Off Off On Off On Off On

169 On Off Off On Off On Off On

170 Off On Off On Off On Off On

171 On On Off On Off On Off On

172 Off Off On On Off On Off On

173 On Off On On Off On Off On

174 Off On On On Off On Off On

175 On On On On Off On Off On

176 Off Off Off Off On On Off On

177 On Off Off Off On On Off On

178 Off On Off Off On On Off On

179 On On Off Off On On Off On

180 Off Off On Off On On Off On

181 On Off On Off On On Off On

182 Off On On Off On On Off On

183 On On On Off On On Off On

184 Off Off Off On On On Off On

185 On Off Off On On On Off On

186 Off On Off On On On Off On

187 On On Off On On On Off On

188 Off Off On On On On Off On

189 On Off On On On On Off On

190 Off On On On On On Off On

ClimateWorx ProtoNode Start-up Guide

Page 44 of 46

Address A0 A1 A2 A3 A4 A5 A6 A7

191 On On On On On On Off On

192 Off Off Off Off Off Off On On

193 On Off Off Off Off Off On On

194 Off On Off Off Off Off On On

195 On On Off Off Off Off On On

196 Off Off On Off Off Off On On

197 On Off On Off Off Off On On

198 Off On On Off Off Off On On

199 On On On Off Off Off On On

200 Off Off Off On Off Off On On

201 On Off Off On Off Off On On

202 Off On Off On Off Off On On

203 On On Off On Off Off On On

204 Off Off On On Off Off On On

205 On Off On On Off Off On On

206 Off On On On Off Off On On

207 On On On On Off Off On On

208 Off Off Off Off On Off On On

209 On Off Off Off On Off On On

210 Off On Off Off On Off On On

211 On On Off Off On Off On On

212 Off Off On Off On Off On On

213 On Off On Off On Off On On

214 Off On On Off On Off On On

215 On On On Off On Off On On

216 Off Off Off On On Off On On

217 On Off Off On On Off On On

218 Off On Off On On Off On On

219 On On Off On On Off On On

220 Off Off On On On Off On On

221 On Off On On On Off On On

222 Off On On On On Off On On

223 On On On On On Off On On

224 Off Off Off Off Off On On On

225 On Off Off Off Off On On On

226 Off On Off Off Off On On On

227 On On Off Off Off On On On

228 Off Off On Off Off On On On

229 On Off On Off Off On On On

230 Off On On Off Off On On On

231 On On On Off Off On On On

232 Off Off Off On Off On On On

233 On Off Off On Off On On On

234 Off On Off On Off On On On

235 On On Off On Off On On On

236 Off Off On On Off On On On

237 On Off On On Off On On On

238 Off On On On Off On On On

239 On On On On Off On On On

Address A0 A1 A2 A3 A4 A5 A6 A7

240 Off Off Off Off On On On On

241 On Off Off Off On On On On

242 Off On Off Off On On On On

243 On On Off Off On On On On

244 Off Off On Off On On On On

245 On Off On Off On On On On

246 Off On On Off On On On On

247 On On On Off On On On On

248 Off Off Off On On On On On

249 On Off Off On On On On On

250 Off On Off On On On On On

251 On On Off On On On On On

252 Off Off On On On On On On

253 On Off On On On On On On

254 Off On On On On On On On

255 On On On On On On On On

ClimateWorx ProtoNode Start-up Guide

Page 45 of 46

Appendix D. Reference

Specifications Appendix D.1.

ProtoNode FPC-N34 ProtoNode FPC-N35

Electrical Connections

One 6-pin Phoenix connector with:

RS-485 port (+ / - / gnd)

Power port (+ / - / Frame-gnd)

One 3-pin Phoenix connector with

RS-485 port (+ / - / gnd)

One Ethernet 10/100 BaseT port

One 6-pin Phoenix connector with:

RS-485 port (+ / - / gnd) Power port (+ / - / Frame-gnd)

One 2-pin Phoenix connector with:

One FTT-10 LonWorks port

One Ethernet 10/100 BaseT port

Approvals

CE Certified; TUV approved to UL 916, EN 60950-1,

EN 50491-3 and CSA C22-2 standards; FCC Class A Part 15;

DNP 3.0 Conformance Tested; RoHS Compliant; CSA 205 Approved

BTL Marked LonMark Certified

Power Requirements Multi-mode power adapter: 9-30V DC or 12 - 24V AC

Physical Dimensions 11.5 cm L x 8.3 cm W x 4.1 cm H (4.5 x 3.2 x 1.6 in.)

Weight 0.2 kg (0.4 lbs)

Operating Temperature -40°C to 75°C (-40°F to167°F)

Surge Suppression EN61000-4-2 ESD EN61000-4-3 EMC EN61000-4-4 EFT

Humidity 5 - 90% RH (non-condensing)

(Specifications subject to change without notice) Figure 31: Specifications

Appendix D.1.1. Compliance with UL Regulations

For UL compliance, the following instructions must be met when operating ProtoNode.

The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating temperature range.

The interconnecting power connector and power cable shall:

o Comply with local electrical code

o Be suited to the expected operating temperature range

o Meet the current and voltage rating for ProtoNode

Furthermore, the interconnecting power cable shall:

o Be of length not exceeding 3.05m (118.3”)

o Be constructed of materials rated VW-1, FT-1 or better

If the unit is to be installed in an operating environment with a temperature above 65 °C, it should be installed in a Restricted Access Area requiring a key or a special tool to gain access.

This device must not be connected to a LAN segment with outdoor wiring.

ClimateWorx ProtoNode Start-up Guide

Page 46 of 46

Appendix E. Limited 2 Year Warranty

Sierra Monitor Corporation warrants its products to be free from defects in workmanship or

material under normal use and service for two years after date of shipment. Sierra Monitor

Corporation will repair or replace any equipment found to be defective during the warranty

period. Final determination of the nature and responsibility for defective or damaged equipment

will be made by Sierra Monitor Corporation personnel.

All warranties hereunder are contingent upon proper use in the application for which the product

was intended and do not cover products which have been modified or repaired without Sierra

Monitor Corporation’s approval or which have been subjected to accident, improper

maintenance, installation or application, or on which original identification marks have been

removed or altered. This Limited Warranty also will not apply to interconnecting cables or wires,

consumables or to any damage resulting from battery leakage.

In all cases Sierra Monitor Corporation’s responsibility and liability under this warranty shall be

limited to the cost of the equipment. The purchaser must obtain shipping instructions for the

prepaid return of any item under this warranty provision and compliance with such instruction

shall be a condition of this warranty.

Except for the express warranty stated above, Sierra Monitor Corporation disclaims all

warranties with regard to the products sold hereunder including all implied warranties of

merchantability and fitness and the express warranties stated herein are in lieu of all obligations

or liabilities on the part of Sierra Monitor Corporation for damages including, but not limited to,

consequential damages arising out of/or in connection with the use or performance of the

product.