Protection modules for scroll and reciprocating compressors · Lodam electronics a/s Kærvej 77...

2
Lodam electronics a/s Kærvej 77 6400 Sønderborg Denmark Tel. +45 73 42 37 37 Fax +45 73 42 37 30 [email protected] www.lodam.com Protection modules for scroll and reciprocating compressors SE-B1/SE-B2/SE-B3 Temperature monitoring The SE-B1/SE-B2/SE-B3 opens the relay contact in the control circuit and locks out immediately if the allowable temperatures for motor or discharge gas (optional PTC sensor) are exceeded. Reset Interrupt supply voltage (L/N) for at least 5 seconds. All Bitzer reciprocating and scroll compressors of the ESH7 and ESH9 series have as standard equip- ment the motor protection devices SE-B1, SE-B2 or SE-B3 (Signal Evaluation - Basic). Protection modules for scroll and reciprocating compressors SE-B1/SE-B2/SE-B3

Transcript of Protection modules for scroll and reciprocating compressors · Lodam electronics a/s Kærvej 77...

Lodam electronics a/sKærvej 776400 SønderborgDenmark

Tel. +45 73 42 37 37Fax +45 73 42 37 30

[email protected]

Protection modules for scroll and reciprocating compressors SE-B1/SE-B2/SE-B3

Temperature monitoring

The SE-B1/SE-B2/SE-B3 opens the relay contact in

the control circuit and locks out immediately if the

allowable temperatures for motor or discharge gas

(optional PTC sensor) are exceeded.

Reset

Interrupt supply voltage (L/N) for at least 5

seconds.

All Bitzer reciprocating and scroll compressors of

the ESH7 and ESH9 series have as standard equip-

ment the motor protection devices SE-B1, SE-B2 or

SE-B3 (Signal Evaluation - Basic).

Protection modules for scroll and reciprocating compressorsSE-B1/SE-B2/SE-B3

Lodam electronics a/sKærvej 776400 SønderborgDenmark

Tel. +45 73 42 37 37Fax +45 73 42 37 30

[email protected]

4,5

±0,2

7,0 ±0,5

29,2

1

32,5

1

68,3 ±1

55,5 ±0,5

10,0

±0,5 50

,0±1

2x Mountinghole

Shown without wire

SE-B1/SE-B2/SE-B3 connection diagram

111412B2

NB1

L

M1 M2L1

L2 L3

Terminal board

oran

ge

oran

ge

Reset

1

Terminal box

C

NO

NC

Lock out

Relay

Supply

Technical specifications:

Description SE-B1 SE-B2 SE-B3Operation voltage 230 V; +10% ~ -15%, 50/60 Hz, 2VA 115 V-230 V; +10% ~ -15%, 50/60 Hz, 2VA

Permitted ambient temperature -30 °C – +70 °C -30 °C – +60 °C

PTC sensor cable length 120 mm 350 mm

PTC sensor cable terminals Flag terminal 250T (6,35*0,8)

Relative humidity 5 %RH - 95 %RH, non-condensing

Relay Switch voltage 250 V ~ Continuous current max 2.5A Switching capacity 300 VA, C300.

PTC measuring circuit Sensor type:Thermistors according to DIN 44081/82,Thermistor type:1..9 in series R total < 1,8 KΩSwitching point:Relay off > 4,5 KΩ +/- 5%Relay on < 2,7 KΩ +/- 5%

Fuse required 4A, fast-blow

Enclosure class Terminals IP00

Terminal torque rating 6 lb-in.” / 0.7 Nm or equivalent.

Terminal wire range Cu 60°C only. 20-14 AWG / 0.5 mm2 - 2,0 mm2