    KAHALGAON STAGE-II 3x500 MW

    INDEXSG Side PAGE

    NO.1. Master fuel trip 12. Unit purge logic 13 Light oil valve 24 Heavy oil valve 25 Mills 36 Raw Coal feeder 67 ID fan 78 FD fan 9

    9 PA fan 1110 BCW pumps 1311 Secondary pre heater 1412 Primary air heater 1613 HPBP 1814 Scanner fan 2015 Seal Air fan 2116 LDO HFO pump 2217 ERV 23

    TG Side

    1 Turbine Protection 242 Turbine lub oil system 253 Turbine HPCF System 284 Evacuation system 325 Turbine fire protection 366 EHTC 387 GENERATOR AUXLIARIES 418 TDBFP 479 MDBFP 5410 CEP 5911 ACW PUMP 6112 ECW PUMP 6313 LPBP GSPC 6514 AUX PRDS 6615 LP HEATERS 7116 HP HEATERS 7417 DEAERATOR 8018 CW PUMP 8219 CONDENSATE TRANSFER SYSTEM 85

    20 LEVEL SETTINGS 86

  • 7/27/2019 Protection and Interlock-NTPC

    2/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 1

    1. MASTER FUEL TRIP

    1. Both ID Fan OFF

    2. Both FD Fan OFF

    3. Water Wall Circulation Incorrect

    4. Both EPB-1,2 Pressed

    5. Furnace Pressure Very Low < -175 mm WC

    6. Furnace Pressure Very High > 150 mm WC

    7. Drum LVL V High TD 10 Sec > 250 mm above NWL

    8. Drum LVL V Low TD 5 Sec < -375 mm below NWL

    9. Air Flow < 30 % < 600 TPH

    10. Loss Of Reheater Protection ( TD 10 Sec)

    11. Unit 24 V DC Not Available

    12. Unit 220 V DC Not Available ( TD 2 Sec)

    13. Less Than FB & Loss of AC in any Elevation in service

    14. Unit Flame Failure Trip

    15. Loss Of All Fuel Trip

    16. All Secondary Air Heaters Off

    17. All Boiler Feed Pumps Tripped TD 10 Sec

    18. MFT network failure

    19. Soft EPB trip

    2. UNIT PURGE LOGIC

    1 MFT DPUs unfreezed

    2 No Boiler Trip Conditions In all the Three Channels

    3 Both PA Fans Off.

    4 HOTV Closed.

    5 All Elevations HONV Closed.

    6 LOTV Closed

    7 EL AB All LONV Closed.

    8 All Feeders Off.

    9 All Hot Air Gates Closed.

    10 All Elevations Show No Flame.

    11 All Auxiliary Air Dampers Modulating.

    12 Air Flow < 40% & > 30 %

  • 7/27/2019 Protection and Interlock-NTPC

    3/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 2

    3. LIGHT OIL TRIP VALVE

    3.1 OPENING PERMISSIVES:

    1. Unit 24 V DC Power Available.

    2. No Close PB Command3. LO Supply Pressure OK > 15 Kg/cm2

    4. EL AB All LONV Closed

    5. No Auto Closing Conditions Present.

    6. NO MFT

    3.2 AUTO CLOSING CONDITIONS:

    1. LO Hdr Pr V Low (< 3 Kg/cm2) & EL AB any LONV not closed(

    TD 5 Sec) OR

    2. Atomising Air Pr. V Low < 3.5 Kg/cm2 ( TD 5 Sec) & EL AB any

    LONV not closed & No LO Start/Stop in EL AB OR

    3. Master Fuel Trip Operated. 2/3 Logic OR

    4. Loss of unit +24V power supply

    4.0 EQUIPMENT: HEAVY OIL TRIP VALVE

    4.1 OPENING PERMISSIVE:

    1. HO Supply Pressure Adequate > 21.2 Kg/cm2 &

    2. HO Supply Temperature Adequate > 110 C &

    3. No MFT &

    4. All Elevation HONV Closed &

    5. No Closing Command from APS or MMI &

    6. No Auto Closing Conditions

    7. Above Conditions Or condition below 8-9 & 24 V Power available

    8. HO Recirculation Valve Open &9. No Auto OR Manual close commands.

    4.2 AUTO CLOSING CONDITIONS:

    1. HO Hdr Temp V Low & Any HONV not closed

  • 7/27/2019 Protection and Interlock-NTPC

    4/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 3

    5. EQUIPMENT : MILLS

    5.1 MILL READY CONDITIONS :

    1. No Pulv Unsuccessful elevation start2. Bunker Outlet Gate open

    3. Feeder Inlet Gate open

    4. Mill Discharge Valve open

    5. Mill start permit from PLOS ( See Conditions Below)

    6. Mill Outlet temp not high < 90 C

    7. Cold Air Gate open

    8. Tramp Iron Hopper Valve open

    9. Mill/ Oil Elevation Start Permit

    10. No MILL Trip

    11. Primary Air Permit Yes

    12. All Burner Isolation Gates open

    5.2 MILL START PERMIT FROM PLOS:

    1. Any Lub Oil Pump ON

    2. Sump / Lube Oil Temperature not high < 80 O C

    3. LOP discharge pressure not low > 3.5 Kg/cm2

    4. Lube Oil Filter DP Not High < 1.5 Kg/cm2

    5. Sump Oil Level Adequate (10mm below CL)

    6. Lube Oil Pressure Not Very Low > 3 Kg/cm2

    5.3 MILL START PERMISSIVES:

    1. MILL Ready Conditions As Above

    2. SA HDR/ Pulv Bowl DP Adequate > 350 mm WC3. MILL Motor Switchgear Available

    4. MILL Status Off & Igntion Permit Available

  • 7/27/2019 Protection and Interlock-NTPC

    5/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 4

    MILL PROTECTIONS :

    1. Motor Winding Temp V high (TD 5 Sec) > 130 0 C

    2. Motor Brg Temp V high ( TD 5 Sec ) > 90 0 C

    3. Mill Brg Temp Very High ( TD 5 Sec ) > 90 0 C4. Mill Trip From PLOS

    5. Pulv H/W Trip from MCC

    6. Pulv on & SA HDR/Bowl DP low( TD 1 Min)< 200 mm WC

    7. MFT Acted

    8. Pulv. Ignition support required & permit NA

    9. Pulv. command On and failed to start TD 10 Sec

    10. Pulv. discharge valve not open

    11. Any burner isolating gates not open

    12. Loss of primary air ( See Conditions Below)

    13. PA Trip.( TD J0,H2,G4,F6,E8 Sec)

    14. Loss of elevation +24 V power supply

    15. EPB pressed

    5.4 MILL TRIP FROM PLOS :

    1. MILL On and LO Temp high (TD 60 Min)> 80 0 C

    2. MILL On & Both Lube Oil Pumps off ( TD 2 Sec)3. LO Pres V low & LOP In Service (TD 10 Sec)< 3 Ksc

    4. Lube oil level very low.

    5.5 LOSS OF PRIMARY AIR CONDITIONS (TRIP):

    1. PA HDR Pressure very low < 500 mm WC Or

    2. All PA or FD Fans off and fast cut back ONOr

    3. PA HDR pressure low (TD 5 Sec) < 625 mm WC

    5.6 START PERMISSIVES FOR LOP:

    1. Lube Oil Level Adequate

    2. No Lube Oil Trip Command

    5.7 STOP PERMISSIVES FOR LOP:

    1. MILL off > 5 min

  • 7/27/2019 Protection and Interlock-NTPC

    6/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 5

    5.8 STANDBY LOP AUTO START CONDITIONS:

    1. Lube oil pump running & pressure low < 3.5 kg/cm2

    2. Lube oil pump fail to start ( TD 5 Sec)

    DESCRIPTION OF PA TRIP : On fast cut back

    (Applicable to Mills J,H,G,F,E Progressive time Delay of 2 sec

    starting from Mill J whose trip is instantaneous)

    1. 5 Or More MILL On & any One Of the Following

    2. Any FD Fan Off

    3. Any PA Fan Off

    4. Loss of BFP - at least 2 BFPs - OFF

    5. Loss Of SAH - at least 1 SAH - OFF

    6. BCW pumping Not O.K - 2 P/Ps ON & DP 500 mm WC &

    2. [All PA or FD Fans off and Any Pulv On and No fast cut back OR

    Any PA fan ON and More than 5 Mills not ON] &3. PA HDR pressure low (TD 5 Sec) > 625 mm WC

  • 7/27/2019 Protection and Interlock-NTPC

    7/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 6

    6. RAW COAL FEEDER

    6.1 START PERMISSIVES:

    1. Feeder Switch In Remote &2. MFT Not Acted &

    3. Mill Outlet Temp Not low > 55 0 C &

    4. Mill Status On &

    5. Feeder Seal Air Valve Open &

    6. Fdr Speed Min &

    7. Mill Ready &

    8. Feeder Outlet Gate Open &

    9. Mill Ignition Permit Available or mill ignition support not required

    6.2 PROTECTIONS:

    1. Feeder Switch Not In Remote Or

    2. MFT Operated Or

    3. Mill Outlet Temp Low < 55 Deg C Or

    4. Mill Status Off Or

    5. Auto/Manual Stop Command Or

    6. Fdr Seal Air valve not open Or7. Fdr On > 5 sec & no coal on belt & Mill Motor current Not low Or

    8. Pulv Ignition Permit Not available and Ignition Support Required

  • 7/27/2019 Protection and Interlock-NTPC

    8/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 7

    7. ID FAN

    7.1 START PERMISSIVES FOR VFD CH-1:

    1. VFD CH-1 No Fault

    2. VFD Source Breaker On

    3. No VFD alarm persisting

    4. VFD CH-1 Ready

    5. VFD Start Permissive available.

    6. VFD CH-2 On Or 7,8 Below

    7. Fan Control Damper Posn Min

    8. Fan Inlet & Outlet Gates Closed

    9. Fan Either Lube Oil Pumps On.

    10. Fan Lube Oil Pressure > 0.8 Kg/cm2

    11. Fan Motor Temp Not high < 85 o C

    12. Fan Brg. Temp Not high < 90 o C

    13. Fan Motor & Exciter Winding Temp Not high < 125 o C

    14. Fan VFD Aux Supply OK

    15. FG Path Available or Other ID Fan On

    16. Lube Oil Temp Aft Cooler Not high < 50 o C

    17. ID Fan-B Lub oil tank level > MIN

    7.2 PROTECTIONS FOR VFD CH-1 :

    1. VFD Ch-1 FAULT

    2. ID Fan-B Ch-1 SRC Breaker Elect Trip

    3. Mtr Brg temp V HI>=90 deg C

    4. FAN Brg temp V HI, >=82 deg C

    5. Mtr Wdg temp V HI, >=130 deg C

    6. MTR Brg Vibration V HI, >=7.1 rms mm/sec TD-05 SEC

    7. FAN Brg Vibration V HI, >=19.8 0-p mm/sec TD-05 SEC

    8. Exciter Wdg temp V HI, >=130 deg C

    9. IDF-A Post Purge TRIP

    10. ID Fan-B ON for 30 sec & Disch damper CLSD, TD-05 sec

    11. ID Fan-B ON for 30 sec & I/L gate CLSD, TD-05 sec

    12. Both ID and both FD ON & FD-B trips

    13. EPB pressed

  • 7/27/2019 Protection and Interlock-NTPC

    9/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 8

    7.3. ID FAN LOP

    1 ON PERMISSIVE:

    1. Lub oil tank level not low.

    2. No MCC disturbance

    2 OFF PERMISSIVE:

    1. ID Fan off OR

    2. Other LOP on and Lube oil pressure > 0.8 Kg/cm2

    3 AUTO ON:

    1. ID Fan On & LOP-B trips

    2. ID fan ON and Lube oil pressure < 0.6 Kg/cm2

    3. LOP-B ON and Lube oil pressure < 0.6 Kg/cm2

  • 7/27/2019 Protection and Interlock-NTPC

    10/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 9

    8. FD FAN

    8.0.1 START PERMISSIVES:

    1. Fan L O Pressure Adequate > 0.8 Kg/cm2

    2. Fan Motor Winding Temp Not high < 125 o C

    3. Fan Brg Temp Not high < 90 o C

    4. Fan Motor Brg Temp Not high < 85 o C

    5. Fan Control Oil Pressure Adequate > 8 Kg/cm2

    6. Fan Control Damper Position Minimum

    7. Fan Outlet Damper Closed

    8. Either LOP on

    9. FAN Switchgear Available

    10. Lub Oil tank level not MIN

    11. Fan Lube Oil Cooler O/L Temp. Not High < 50 o C

    12. Both ID Fans On & I/L, O/L gates OPEN

    13. Either ID Fan On & I/L, O/L gates OPEN & Other FD Fan Off

    8.0.2 PROTECTIONS

    1. Fan On & O/L Damper Closed (TD 30 Sec)

    2. Both FD Fans On & both ID fans ON & ID Fan-B OFF3. Both ID Fans OFF

    4. Post Purge Trip From FSSS

    5. Fan Brg Temp Very High ( TD 5 Sec)> 110 o C

    6. Motor Brg Temp Very High ( TD 5 Sec )> 90 o C

    7. Fan Motor Winding Temp V High( TD 5 Sec)> 130 o C

    8. Fan/ Motor Vibration V High TD 05 Sec)> 7.1 rms mm/s /19.8 p-p

    mm/s

    9. EPB pressed

  • 7/27/2019 Protection and Interlock-NTPC

    11/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 10

    8.1 EQUIPMENT: FD FAN LOP

    ON PERMISSIVE:

    1. Lub oil tank level not low.

    OFF PERMISSIVE:

    1. FD Fan off OR

    2. Other LOP on and conditions at 3-4 below

    3. Lube oil pressure > 0.8 Kg/cm2 &

    4. Control Oil Pressure > 8 Kg/cm2

    AUTO ON:

    1. FD Fan On & LOP-B trips

    2. FD fan ON and (Lub oil pr < 0.6 Kg/cm2 OR cntrl oil pr < 6

    kg/cm2)

    3. LOP-B ON and (Lube oil pr < 0.6 Kg/cm2 OR control oil Pr < 6

    kg/cm2)

  • 7/27/2019 Protection and Interlock-NTPC

    12/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 11

    9 PA FAN

    1. START PERMISSIVES:

    1. Motor Winding temperature Not High < 125 Deg C

    2. Fan Bearing Temperature Not High < 85 Deg C

    3. Motor Bearing temperature Not High < 90 Deg C

    4. Lub Oil Pressure Adequate > 0.8 ata

    5. Control Oil Pressure Adequate > 8 ata

    6. Lub Oil Cooler O/L Temperature Not High < 50 Deg C

    7. Any Lub Oil Pump On

    8. Lub Oil Tank Level Not Low

    9. Blade Pitch Position Min < 2 %

    10. Fan O/L Damper Closed

    11. Both FDs On OR [Any FD ON & PA-B OFF]

    12. Both PAPH ON & Air path available OR [Any PAPH ON &

    Air path available & PA-B OFF]

    13. PA fan start permissible available OR Other pa fan ON

    2 PROTECTIONS:

    1. MFT Operated2. Temperature V. Hi [ DE & NDE] >=110 deg C

    3. Brg temp V HI >=90 deg C

    4. Mtr Wdg temp V HI >=130 deg C

    5. MTR Brg Vibration V HI [RMS] >=7.1 rms mm/sec TD-05 SEC

    6. FAN Brg Vibration V HI[Peak] >=19.8 0-p mm/sec TD-05 SEC

    7. Both FD Fans Off

    8. PA Fan-B On & O/L Damper Closed TD 35 SEC

    9. EPB pressed

  • 7/27/2019 Protection and Interlock-NTPC

    13/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 12

    9.1 PA FAN LOP

    ON PERMISSIVE:

    1. Lub oil tank level not low.

    OFF PERMISSIVE:

    1. PA Fan off OR

    2. Other LOP on and conditions at 3-4 below

    3. Lube oil pressure OK > 0.8 Kg/cm2 &

    4. Control Oil Pressure OK > 8 Kg/cm2

    OFF PERMISSIVE:

    1. PA Fan On & LOP-B trips

    2. PA fan ON and (Lube oil pr < 0.6 Kg/cm2 OR control oil pr < 6

    kg/cm2)

    3. LOP-B ON and (Lube oil pr < 0.6 Kg/cm2 OR control oil pr < 6

    kg/cm2)

  • 7/27/2019 Protection and Interlock-NTPC

    14/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 13

    10 EQUIPMENT: BOILER CIRCULATING PUMP

    10.1 START PERMISSIVE:

    1. BCW PUMP-C Disch. Valve-1 OPEN

    2. BCW PUMP-C Disch. Valve-2 OPEN

    3. BCW PUMP-C Cooling water flow Not low >=32 gpm

    4. BCW PUMP-C motor cavity Temp. O.K >2o C & 60C TD 5 Sec

    2. Discharge V/V Stem-1 Not Open

    3. Discharge V/V Stem-2 Not Open

    10.3 BCW CW BOOSTER P/P

    AUTO START CONDITIONS:

    1. Running Other Pump Tripped. Or

    2. Other P/P On & Discharge Pressure Low< 3.5 Kg/cm2

    3. MCC Disturbance Not Present

    4. Local Intervention Not There

    OFF PERMISSIVES:1. Boiler Not Working Or

    2. Other Pump On & Discharge Pressure Not Low.

    Auto OFF:

    1. Overhead tank level high

  • 7/27/2019 Protection and Interlock-NTPC

    15/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 14

    11 EQUIPMENT : SECONDARY AIR HEATER.

    START PERMISSIVES : Electrical Motor

    1. Guide Bearing oil temp Not high < 70 o C

    2. Support Bearing oil temp Not high < 70 o C

    START PERMISSIVES : Air Motor

    1. Thrust Brg Temp Not high < 70 o C

    2. Guide Brg Temp Not high < 70 o C

    3. Electrical motor OFF

    INTERLOCKS :

    AUTO ON:

    If SAH Electric Motor Trips Air Motor takes start in auto in 1.5 sec

    AUTO OFF:

    If SAH Electric Motor takes start , Air Motor Stops in auto.

    13.4 Air Motor running status from pr switch (setting 3.0 kg)

    13.5 Fire sensing alarm (setting 450C)

    11.1 SAH GUIDE BEARING LOP

    START PERMISSIVES:

    1. MCC Not Disturbed.

    AUTO ON:

    1. Other LOP OFF and start command

    2. LOP-B On & LUb oil flow low (

  • 7/27/2019 Protection and Interlock-NTPC

    16/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 15

    11.2 SAH SUPPORT BEARING LOP

    START PERMISSIVES:

    1. Guide Bearing Temperature not low > 35 o C

    2. No Auto Off Command3. MCC Not Disturbed.

    AUTO ON:

    1. Other LOP OFF and start command

    2. LOP-B On & LUb oil flow low (

  • 7/27/2019 Protection and Interlock-NTPC

    17/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 16

    12 PRIMARY AIR HEATER.

    START PERMISSIVES : Electrical Motor

    1. Guide Bearing oil temp Not high < 70 o C

    2. Support Bearing oil temp Not high < 70 o C

    3. No auto Off Command from SGC

    4. Electrical motor MCC Not Disturbed.

    START PERMISSIVES : Air Motor

    1. Thrust Brg Temp Not high < 70 o C

    2. Guide Brg Temp Not high < 70 o C

    INTERLOCKS :

    AUTO ON:

    If SAH Electric Motor Trips Air Motor takes start in auto in 1.5 sec

    AUTO OFF:

    If SAH Electric Motor takes start , Air Motor Stops in auto.

    19.4 Air Motor running status from pr switch (setting 3.0 kg)

    19.5 Fire sensing alarm (setting 450C)

    12.1 PAH GUIDE BEARING LOP

    START PERMISSIVES:

    1. Guide Bearing Temperature not low > 35 o C

    2. No Auto Off Command

    3. MCC Not Disturbed.

    AUTO ON:

    1. Other LOP OFF and start command

    2. LOP-B On & LUb oil flow low (

  • 7/27/2019 Protection and Interlock-NTPC

    18/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 17

    AUTO OFF:

    1. Bearing temp < 35C

    2. OFF CMD

    12.2 PAH SUPPORT BEARING LOP

    START PERMISSIVES:

    1. Guide Bearing Temperature not low > 35 o C

    2. No Auto Off Command

    3. MCC Not Disturbed.

    AUTO ON:

    1. Other LOP OFF and start command

    2. LOP-B On & LUb oil flow low (

  • 7/27/2019 Protection and Interlock-NTPC

    19/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 18

    13 HP BYPASS SYSTEM

    13.1 OIL SUPPLY PUMP FOR HP BYPASS

    1. Pump off: >150 Kg/cm2

    2. Pump on: 160 Kg/cm2

    4. Pressure too low: 8 Kg/cm2

    6. Any one of the above & No Priority close

    2 BP VALVE PRIORITY CLOSE CONDITIONS:

    1. Condenser vacuum low < 0.6 Kg/cm2 OR

    2. Selected Downstream temp signal v high > 480 0 C

    3 BP VALVE AUTO BLOCKING CONDITIONS:

    1. BP Valve Priority Close Command OR

    2. BP Valve Position Transmitter failed. OR3. OSU-1 & OSU-2 Oil Pressure Very Low. OR

    4. MSL PR TX Disturbed.

    4 BD VALVE AUTO OPEN CONDITIONS:

    1. BP Valve PI demand > 2% OR

    2. BP-1 OR BP-2 Valve open > 2%

  • 7/27/2019 Protection and Interlock-NTPC

    20/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 19

    5 BD VALVE AUTO CLOSE CONDITIONS:

    1. No auto open command AND

    2. BD valve LS FB Open.

    6 BPE VALVE AUTO BLOCKING CONDITIONS:

    1. BPE both DS Temp Signal disturbed

    2. BPE Valve Position TX failed

    3. BP-1 Auto Command blocking yes

    4. BPE-1 Temp TX Deviation high

  • 7/27/2019 Protection and Interlock-NTPC

    21/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 20

    14 EQUIPMENT: AC SCANNER AIR FAN

    AUTO START CONDITIONS:

    1. No MFT & Scan - Furnace DP Low( TD 10 Sec) < 150 mm WC

    2. ON Order from APS/SGC

    3. Scanner Air Fan B (DC fan) did not take start within 5 sec. after

    receiving the start command

    PERMISSIVE FOR OFF:

    1. Either MFT Operated or Scan Duct To Furnace DP Not Low &

    2. Both Scanner fans Running Or (MFT & Either Scanner fans On)

    PROTECTION OFF:

    1. If both the fans did not take start within 5 sec. Off command is

    generated, OFF command will be issued to the fan after 10

    sec.Either MFT Operated or Scan Duct To Furnace DP Not Low

    &

    14.1 DC SCANNER AIR FAN

    AUTO START CONDITIONS:

    1. No MFT & Scan - Furnace DP Low( TD 10 Sec) < 150 mm WC2. ON Order from APS/SGC

    3. Scanner Air Fan A (AC fan) did not take start within 5 sec. after

    receiving the start command

    PERMISSIVE FOR OFF:

    1. Either MFT Operated or Scan Duct To Furnace DP Not Low &

    2. Both Scanner fans Running Or (MFT & Either Scanner fans On)

    PROTECTION OFF:

    1. If both the fans did not take start within 5 sec. Off command is

    generated, OFF command will be issued to the fan after 10

    sec.Either MFT Operated or Scan Duct To Furnace DP Not Low

    &

  • 7/27/2019 Protection and Interlock-NTPC

    22/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 21

    15 EQUIPMENT: SEAL AIR FAN

    AUTO START CONDITIONS:

    Either PA Fan On & SA HDR/CA Duct DP Low(TD 10 Sec) < 100 mm

    WC

    PROTECTION OFF CONDITIONS:

    1. Both fan Started TD 10 Sec Or

    2. Fan Breaker Tripped On Overload Or

    3. Both PA Fans Off ( TD 15 Sec)

    PERMISSIVE OFF CONDITIONS:

    1. Both Fans Running &

    2. Scan-Furnace DP Not Low

    3. VPC/Pushbutton Off Command

    START PERMISSIVES:

    Outlet Damper LS Feedback Closed

  • 7/27/2019 Protection and Interlock-NTPC

    23/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 22

    16. LDO PUMP

    START PERMISSIVE

    1) MCC not disturbed

    2) Pump not running3) Suction pressure not low (>-0.1 ksc)

    4) LDO Storage tank level not very low

    TRIP PROTECTION

    1) Pump overload

    2) LDO tank level very low

    3) LDO suction pressure before strainer low (-0.1 ksc)

    4) LDO Storage tank level not very low

    TRIP PROTECTION

    1) Pump overload

    2) LDO tank level very low

    3) LDO suction pressure before strainer low (

  • 7/27/2019 Protection and Interlock-NTPC

    24/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 23

    17. ERV Settings

    Set pressure KSGSl.

    No.

    Location Valve Tag NO

    Open Close

    1 MS LINE (L) SV 9 185.5 180.3

    2 MS LINE (L SV 10 185.5 180.33 MS LINE (R) SV11 186.6 180.64 MS LINE (R) SV12 186.6 180.65 MS LINE (R) SV13 186.6 180.66 RH LINE (L) SV 22 48.0 46.67 RH LINE (L) SV23 48.0 46.68 RH LINE (R) SV24 48.5 47.19 RH LINE (R) SV25 48.5 47.1

  • 7/27/2019 Protection and Interlock-NTPC

    25/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 24

    1. TURBINE PROTECTIONS

    Sr.

    No.

    Description Alarm Set

    point

    Trip set point

    1) TG Lub oil pressure very low (< 4.5ksc) (< 1.2 ksc)

    2) Axial shift high (+/-0.5 mm) (+/- 1.0mm)

    3) HP exhaust temp. high (> 480 degc) (> 500 degc)

    4) Condenser vaccum low(VSP) --- ---

    5) Condenser vaccum low(FSP) AND

    Turbine speed > 240 rpm

    (> -0.8 ksc) (> -0.7 ksc)

    6) HP casing top/btm DT high AND Load

    >100MW

    (> 90 degc) (> 100 degc)

    7) IP casing front top/ btm DT high AND

    Load >100MW

    (> 90 degc) (> 45 degc)

    8) IP casing rear top/ btm DT high AND

    Load >100MW

    (> 90 degc) (> 45 degc)

    9) MFT S/W & H/W --- ---

    10) Generator electrical protection S/W &

    H/W

    --- ---

    11) Liquid in Generator Main leads top ----- (> 90 mm)

    12) Cold gas temp after cooler A&B high (> 55 degc) (> 60 degc)

    13) Cold gas temp after cooler C&D high (> 55 degc) (> 60 degc)

    14) Primary water temp after cooler high (> 55 degc) (> 60 degc)15) Seal oil temp after cooler high AS (> 50 degc) (> 60 degc)

    16) Hot air main exciter temp high (> 75 degc) (> 80 degc

    17) Stator winding flow very low (< 48 tph) (< 54 tph)

    18) Stator Main bushing R flow low (< 1.4 tph) (< 1.33 tph)

    19) Stator Main bushing S flow low (< 1.4 tph) (< 1.33 tph)

    20) Stator Main bushing T flow low (< 1.4 tph) (< 1.33 tph)

    21) Turbine over speed trip (electrical) (> 3300 rpm) (> 3330 rpm)

    22) Turbine over speed trip H/W

    23) Oil tank level very low ( 1000 mm

    from top)

    ( 1150 mm

    from top)

    24) Turbine trip from desk operated 90 degC 130 degC

    25) Turbine trip from bearing temp hi --- ---

    26) Turbine trip from ATRS --- ---

    27) Emergency trip from HMI --- ---

    28) Fire protection 1 or 2 operated --- ---

    29) Generator class B protection --- ---

    30) Low Vacuum Trip Device operated --- ---

    31) Manual Trip Device operated --- ---

  • 7/27/2019 Protection and Interlock-NTPC

    26/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 25

    2. TURBINE LUB OIL SYSTEM

    2.1 AOP - 1

    AUTO START1) SGC oil supply ON

    2) SLC AOP -1 ON AND [ AOP -2 trippd OR Oil Pr < 4.8 ksc ]

    AUTO STOP

    1) SGC Oil Supply start-up step - 9 command

    2) SGC Oil Supply shutdown step - 55 command

    PROTECTION STOP

    1) Oil tank level very low

    2) Fire protection - 2 operated

    2.2 AOP - 2

    AUTO START

    1) SLC AOP -2 ON AND [ AOP -1 tripped OR Oil Pr < 4.5 ksc ]

    AUTO STOP1) SGC Oil Supply start-up step - 9 command

    2) SGC Oil Supply shutdown step - 55 command

    PROTECTION STOP

    1) Oil tank level very low

    2) Fire protection - 2 operated

    2.3 EOP

    PROTECTION ON

    1) SLC EOP ON AND Lub oil pressure < 1.1 ksc

    2) Lub oil pressure < 1.1 ksc AND

    [ HP casing top mid temp > 120 degc OR

    HP casing bottom mid temp > 120 degc ]

    3) Lub oil press < 1.1 ksc ( Direct to DC Starter)

    ( Direct from Pr. Switch with SLC EOP-ON (MCM.Relay))

  • 7/27/2019 Protection and Interlock-NTPC

    27/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 26

    2.4 JOP -1

    START PERMISSIVE

    1) JOP -3 OFF

    AUTO START

    1) SLC JOP-1 ON AND Turbine Speed < 510 rpm

    AUTO STOP

    1) SLC JOP -1 ON AND Turbine Speed > 540 rpm

    2) Turbine Speed < 510 rpm AND

    Jacking oil pressure < 150 ksc AND

    SLC JOP -3 ON TD15s

    3) Turbine Speed < 2800 rpm ANDJOP -1 Voltage failed AND SLC JOP - 3 ON

    4) JOP -1 Tripped AND SLC JOP -3 ON

    5) SGC Oil Supply shutdown Step 54 command

    PROTECTION STOP

    1) Oil tank level very low

    2) Fire protection - 2 operated

    2.5 JOP - 3

    START PERMISSIVE

    1) JOP -1 OFF

    AUTO START

    1) JOP -1 Tripped AND SLC JOP -3 ON

    2) Turbine Speed < 510 rpm AND Jacking oil pressure < 150 ksc

    ANDSLC JOP -3 ON TD10s

    3) Turbine Speed < 2800 rpm AND

    JOP -1 Voltage failed AND SLC JOP - 3 ON

    PROTECTION STOP

    1) Oil tank level very low( > 1150 mm from top)

    2) Fire protection - 2 operated

  • 7/27/2019 Protection and Interlock-NTPC

    28/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 27

    2.6 TURNING GEAR

    OPEN PERMISSIVE

    1) Turbine speed > 15 rpm OR

    2) Seal oil pr. H2 side > 7.0 ksc AND

    Seal oil Air to H2 side DP TE > 1.2 ksc AND

    Seal oil Air to H2 side DP EE > 1.2 ksc

    AUTO OPEN

    1) SLC Turning gear ON AND Turbine Speed < 210 rpm

    AUTO CLOSE

    1) SLC Turning gear ON AND Turbine Speed > 240 rpm

    2) SGC Oil Supply shutdown step -51 command

    PROTECTION CLOSE

    1) Lub oil pressure < 1.2 ksc

    2.7 OIL TEMP CONTROL V/V

    AUTO OFF

    1) SGC oil supply shutdown step -55 command

    2.8 OIL VAPOUR EXTRACTOR -1

    AUTO START

    1) Other vapour extractor tripped

    2) SGC oil supply start-up step -2 command

    AUTO STOP

    1) Standby Oil vapour extractor ON

    2.9 OIL VAPOUR EXTRACTOR-2

    AUTO START

    1) OVE- 1 OFF and Disc

    2.10 LEAKAGE OIL PUMP

    AUTO START

    1) Leakage oil tank level > 50%

    AUTO STOP

    1) Leakage oil tank level < min

  • 7/27/2019 Protection and Interlock-NTPC

    29/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 28

    3 TURBINE HPCF SYSTEM

    3.1 HP CONTROL FLUID HEATER

    RELEASE ON1) Any HPCF circulation pumps ON AND

    HPCF temp control vlv closed

    AUTO ON

    1) Control flow heater temp < 50 degc

    2) SLC HPCF heating ON AND

    HPCF tank fluid temp < 55 degc AND

    HPCF temp control vlv closed

    AUTO OFF

    1) SGC HPCF shutdown step - 51 command

    2) Control flow heater temp > 65 degc

    3) SLC HPCF heating ON AND

    [ HPCF tank fluid temp > 57 degc OR HPCF temp control vlv not

    closed ]

    PROTECTION OFF1) Control flow heater temp > 75 degc

    2) Fire Protection-1 operated

    3) Fire Protection-2 operated

    4) Both HPCF circulation pumps OFF

    3.2 HP CONTROL FLUID PUMP - 1

    AUTO START

    1) SLC HPCF Pumps ON AND HPCF pump 2 discharge pr. < 26

    ksc

    2) SLC HPCF Pumps ON AND HPCF pump 2 tripped

    AUTO STOP

    1) SGC HPCF shutdown step - 51 command

    PROTECTION OFF

    1) Fire Protection-1 OR Fire Protection-2 operated

  • 7/27/2019 Protection and Interlock-NTPC

    30/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 29

    3.3 HP CONTROL FLUID PUMP- 2

    AUTO START

    1) SLC HPCF Pumps ON AND HPCF pump 1 discharge pr. 30 ksc

    2) HPCF Vapour Extractor - 2 tripped

    3.5 HPCF VAP EXTR-2

    AUTO START

    1) HPCF Vapour Extractor - 1 tripped

    3.6 HPCF CIRCULATION PUMP-1

    START PERMISSIVE

    1) HPCF Circulation pump-2 OFF

    AUTO START

    1) SGC HPCF on ANDHPCF press. > 30 ksc AND

    Any HPCF Vap Extractor ON

    AUTO STOP

    1) SGC HPCF shutdown step - 51 command

    PROTECTION OFF

    1) HPCF tank level < min

    2) Fire Protection -1 OR Fire Protection -2 operated

  • 7/27/2019 Protection and Interlock-NTPC

    31/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 30

    3.7 HPCF CIRCULATION PUMP-2

    START PERMISSIVE

    1) HPCF Circulation pump-1 OFF

    AUTO START

    1) HPCF press > 30 ksc AND

    HPCF pump-1 off TD5s

    AUTO STOP

    1) SGC HPCF shutdown step - 51 command

    PROTECTION OFF

    1) HPCF tank level < min2) Fire Protection -1 OR Fire Protection -2 operated

    3.8 HPCF TEMP CONTROL VALVE

    AUTO OFF

    1) SGC HPCF shutdown step - 51 command

  • 7/27/2019 Protection and Interlock-NTPC

    32/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 31

    3.9 HPCF ALARMS

    1) Leakage Level High

    Leak speed chang device >Min OR

    Leak press TRANS INJW >Min OR

    Over speed governor >Min

    2) Hydraulic control fluid pressure low.

    HPCF Pressure after pump -1 < 26 ksc AND

    HPCF Pressure after pump -2 < 26 ksc AND

    Turbine speed > 15 rpm

    3) HPCF Filter DP high

    Filter Supply Units DP > 0.6ksc OR

    CF filter DP > 0.6ksc OR

    LP Bypass filter DP > 0.6 ksc

    4) Water CF Tank High

    CF Conductivity High

    5) HPCF Temperature Low/Fault < 50 degc

    6) HPCF Temperature High/Fault > 60 degc

    7) HPCF Pumps Fault

    SLC HPCFs on with 10 sec delay AND

    Any HPCF auto on command

    8) HPCF Tank temp. low < 20 degc9) CONTIN Flow heater >75 degC

    9) HPCF Tank level high > 59 % < 650 mm from top

    10) HPCF Tank level low < 53 % > 800 mm from top

    11) HPCF Tank level very low < 50 % > 750 mm from top

    12) VAP EXTR System trouble

    Both HPCF VAP EXTR- NOT ON AND

    HPCF pr > 30 Ksc

  • 7/27/2019 Protection and Interlock-NTPC

    33/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 32

    4 EVACUATION SYSTEM

    4.1 VACCUM PUMP 1 & 2

    RELEASE START1) SEP water level > MIN

    RELEASE STOP

    1) System inlet valve closed

    AUTO START

    1) SGC Start-up Step-3 command

    2) SLC vacuum pumps on AND Condenser pressure > 0.15 ksc

    AUTO STOP

    1) Through SGC Evacuationstep-51 command

    2) SGC Evacuation start-up Step- 7 command AND Vacuum pump

    selected

    4.2 VACCUM PUMP SOL INLET VALVE 1 & 2

    RELEASE OPEN1) Differential pressure across Inlet valve 0.15 ksc

    AUTO CLOSE

    1) SGC Evacuation shutdown step-51 command

    2) SGC Evacuation start-up Step- 7 command AND Vacm pump

    selected

    4.3 SEAL WATER RECIRCULATION PUMP 1 & 2

    ON RELEASE1) Separator water level > 360 mm

    1) Vac p/p -2 ON

  • 7/27/2019 Protection and Interlock-NTPC

    34/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 33

    AUTO START

    1) SGC start-up Step 3 command

    2) SLC vacuum pumps on AND Condenser pressure > 0.15 ksc

    CLOSE RELEASE

    1) Vacuum pump OFF

    AUTO CLOSE

    1) SGC Evacuation shutdown step-51 command

    2) SGC Evacuation start-up Step- 7 command

    3) Vacuum pump OFF

    4.4 MAKE UP SOLENOID VALVE 1 & 2

    AUTO OPEN

    1) Level in separator tank < 330 mm

    AUTO CLOSE

    1) Level in separator Tank > 360 mm TD5s

    4.5 SEAL STEAM CONDENSER EXHAUST VALVE 1/2

    AUTO OPEN

    1) SGC evacuation start-up step 1 command

    2) Seal steam condenser other exhaust tripped (OFF or DISC)

    AUTO CLOSE

    1) SGC Evacuation Shutdown step 53 command

    ( Vacuum breaker open status is required).

    PROTECTION CLOSE

    1) Seal steam condenser level High.

    4.6 SEAL STEAM CONDENSER SEAL VALVES

    AUTO OPEN

    1) SGC evacuation start-up step 1 command

    RELEASE OPEN1) Integral bypass valve open TD-5sec.

  • 7/27/2019 Protection and Interlock-NTPC

    35/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 34

    PROTECTION CLOSE

    1) Seal steam condenser level-2 High

    4.7 INT BYPASS VALVE FOR SEAL STEAM CONDENSER

    SEAL VALVES

    AUTO OPEN

    1) Seal steam condenser seal valve

    AUTO CLOSE

    1) Seal steam condenser seal valve open

    4.8 SEAL STEAM CONDENSER SAFETY VALVE

    AUTO OPEN

    1) Seal steam condenser level-2 High.

    RELEASE OPEN

    1) Integral bypass valve open TD-5sec.

    AUTO CLOSE

    1) SGC evacuation start-up step 1 command

    4.9 INT BYPASS VALVE FOR SEAL STEAMCONDENSER

    SAFETY VALVES

    AUTO OPEN

    1) Seal steam condenser LEVEL -2 HIGH

    PROTECTION CLOSE

    1) Seal steam condenser SAFETY valve open

    4.10 SEAL STEAM VAP EXHAUST ISOL VALVE - 1/2

    AUTO OPEN

    1) Seal steam condenser exhaust ON

    AUTO CLOSE

    1) Seal steam condenser exhaust OFF

  • 7/27/2019 Protection and Interlock-NTPC

    36/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 35

    4.11 EVACUATION ALARMS

    1) Seal steam condenser level high

    Seal stm Cond lvl -1 high

    Seal stm Cond lvl -2 high

    2) Seal steam Condenser Valve Position Fault

    Seal stm cond SOV limit switch not open or not closed AND

    Seal stm Cond level -1 high AND

    Seal stm Cond level -2 high

    3) Seal Stm Cond Fault

    Seal stm cond lvl -2 high TD1m AND

    Seal stm cond SOV not open OR not closed

    4) Switch OFF Stand by Vaccum Pump

    Both Vacuum Pumps ON AND

    Generator Load > 5 % AND

    Condenser Press < 0.15 ksc

    5) Switch ON Stand by Vaccum Pump

    Generator Load > 5 % AND

    Condenser Press > 0.15 ksc

    6) Separator Water level < min

    Sep-1 water lvl < min

    Sep-2 water lvl < min7) SW Flow Low

    CW recirculation pump 1 ON AND

    SW Flow vac pump -1 < 14 m3/hr OR

    CW recirculation Pump 2 ON AND

    SW Flow vac pump -2 < 14 m3/hr

    8) SLC Vaccum pump not ON

    SLC Vaccum pumps OFF AND

    Turbine Speed > 15 rpm

    9) VP Seal stm temp hi

    VP-1 Seal stm temp 40 degC

    VP-2 Seal stm temp 40 degC

    10) Seal Stm Cond Exh tripped

    Seal stm cond Exh.1 tripped

    Seal stm cond Exh.2 tripped

  • 7/27/2019 Protection and Interlock-NTPC

    37/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 36

    5. TURBINE FIRE PROTECTIONS

    FIRE PROTECTION-1 OPERATED WILL COME WHEN

    [Fire Protection-1 PB pressed in UCR.Fire Protection-1 PB pressed in MBLD-1

    Fire Protection-1 PB pressed in MBLD-2] ] OR Fire protection -2

    initiated

    This will cause

    Opens the vacuum Breaker on Protection

    SGC HP CTRL FLUID OFF

    SLC CTRL FLUID HTG OFF

    SLC CTRL FLUID PUMPS OFF

    Stops HPCF P/Ps

    Stops HPCF Heater

    Stops HPCF Recirculation P/Ps

    Trips the Turbine

    * The vacuum Breaker will open on Protection if

    [Fire protection -1 initiated OR MOT level very low]

    AND Generator Breaker OFF

  • 7/27/2019 Protection and Interlock-NTPC

    38/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 37

    FIRE PROTECTION-2 OPERATED WILL COME WHEN

    1) MOT level very low OR

    [Fire Protection-2 PB pressed in UCR. OR

    Fire Protection-2 PB pressed in MBLD-1 ORFire Protection-2 PB pressed in MBLD-2]

    This will Cause

    Switch Off the SGC Oil Supply Program

    Stops AOP-1 on protection

    Auto OFF SLC AOP-1

    Stops AOP-2 on protection

    Auto OFF SLC AOP-2

    Auto ON SLC EOP

    Auto OFF SLC JOP-1

    Stops JOP-1 on protection

    Stops JOP-2 on protection

    Starts JOP-3 on protection

    Auto OFF SLC JOP-3

    Auto OFF SLC Turning Gear

    Trips the Turbine

  • 7/27/2019 Protection and Interlock-NTPC

    39/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 38

    6. EHTC

    SPEED REFRENCE TRACKS ACTUAL SPEED WHEN

    1) ( Load ctlr. o/p > speed ctlr. o/p + 5 % ) AND

    Speed actual < 3030 rpm AND

    Speed actual > 2940 rpm AND load ctlr. ON

    2) Turbine tripped

    SPEED REF DELAYED IS RESTRICTED IF

    1) Generator breaker not ON AND

    ( NrTD - Nactual ) > 50 rpm

    2) Generator breaker not ON AND

    [ Power set point block OR TSC on & faulty] AND

    Speed ref > speed ref delayed AND

    Speed actual > 2850 rpm

    DN/DT ACTS WHEN

    1) Speed slope value low ( < 108 rpm / min ) AND

    Speed ctlr. output > 0 % ANDSpeed actual Nact > 725 rpm AND

    Speed actual Nact > 2850 rpm AND

    Generator breaker not on AND

    HP ESV # 1 not close AND

    HP ESV # 2 not closed AND

    Speed set point not balanced AND

    Nr > 650 rpm

    LOAD REFERENCE TRACKS ACTUAL LOAD WHEN

    1) Pressure ctlr. in action AND IP mode selected AND Load actual

    < 30 %

    LOAD CTRLR BECOMES ON / OFF ONLY WHEN

    1) ( Speed ctlr. output > load ctlr. output ) AND Speed ctlr. in

    action

  • 7/27/2019 Protection and Interlock-NTPC

    40/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 39

    ISOLATED GRID IS DETECTED WHEN

    1) Speed > 84.33 % AND Load ctlr. not off AND

    Load error > 8.4 % for 6 sec. AND

    Speed ctlr. not in action AND Pressure ctlr. not in action

    ISOLATED GRID RESETS WHEN

    1) Generator breaker off

    2) load error < 8.4 % AND Reset command given

    LOAD CTLR.O/P TRACKS PR. CTLR.O/P+2% WHEN

    1) Press ctlr. in action AND

    Actual load > final load set pt AND Load < load ref.

    LOAD CTLR. O/P TRACKS SPEED CTLR. O/P WHEN

    1) ( Pact. < station load AND Load ctlr. error > 5 %)

    2) Generator Breaker off

    3) Load ctlr. off AND Pressure ctlr not on

    LIMIT PRESSURE MODE CAN BE SELECTED IF

    1) Boiler ctlr. not tripped to manual ( is in auto ) AND

    Turbine follow Boiler from CMC not selected AND

    IP mode not selected from OWS

    INITIAL PRESSURE MODE GETS SELECTED IF

    1) Boiler ctlr. is in manual

    2) Turbine follow Boiler from CMC not selected

    3) IP mode selected from OWS

    SPEED CTLR. IN ACTION IF

    1) Generator Breaker off

    2) Turbine Tripped Ch - 1/Ch -2

    3) Speed ctlr. o/p+100% < max(speed ctlr. o/p, load ctlr. o/p)

    4) Speed ctlr. o/p > Load ctlr. o/p

  • 7/27/2019 Protection and Interlock-NTPC

    41/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 40

    LOAD CTLR. IN ACTION IF

    1) Load ctlr. not off AND

    Isol. Grid not detected AND

    [ Speed OR Press. ctlr. not in action ]

    PRESS. CTLR. IN ACTION IF

    1) Press. ctlr. o/p < min [ (Speed ctlr. o/p + 100 %) ,

    max(speed ctlr. o/p , load ctlr. o/p) ]

    TRACKING DEVICE CAN BE MADE ON IF

    1) EHTC fault is not persisting ANDStarting device position healthy AND

    EHC posn. 1 and 2 healthy AND

    Speeder gear posn. Healthy AND

    Plunger coil healthy AND

    Tracking device no off cond. AND

    Turbine tripped not present AND

    No EHTC fault AND

    Speed signal no fault

  • 7/27/2019 Protection and Interlock-NTPC

    42/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 41

    7 GENERATOR AUXILIARIES

    7.0 PRIMARY WATER PUMP 1 & 2

    AUTO START1) SLC PW pumps on AND PW Tank level > 155mm

    AND Other PW pump off

    2) SLC PW pumps on AND

    PW Tank level > 155mm AND

    Other PW pump on AND Pressure after other PW pump < 5 ksc

    STOP PERMISSIVE

    1) Stand by PW Pump on AND PW press. after std by pump > 5

    ksc TD5s

    2) SLC PW pumps off.

    7.1 NaOH DOSING PUMP

    START RELEASE

    1) Treated water flow > min

    AUTO START

    1) Conductivity after ion exchanger < 1us/cm

    AUTO STOP

    1) Conductivity after ion exchanger > 3 us/cm TD10s OR

    2) Conductivity after main filter > 2.5 us/cm TD10s OR

    2) NaOH tank level < min

    PROTECTION STOP

    1) Treated water flow < min

    7.2 PW TEMP CONTROL VALVE

    PROTECTION OPEN

    1) PW inlet temp > 66 degc

  • 7/27/2019 Protection and Interlock-NTPC

    43/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 42

    7.3 SEAL OIL PUMP - 1 AIR SIDE

    AUTO START

    1) SLC SO Pump (AS) on AND

    SO storage tank level not low AND SO pump 2 (AS) off

    2) SLC SO Pump (AS) on AND

    SO storage tank level not low AND

    SO pump 2 (AS) on AND SO pr after SOP-2 (AS) < 05 ksc TD2s

    3) SO p/p-2 OFF and SO p/p-2 discrepancy

    4) SGC Gen seal oil Start-up step-1 command

    STOP PERMISSIVE

    1) SO pump 2 (AS) on AND SO pr after SOP-2 (AS) > 5 ksc TD5s

    2) SLC SO pump (AS) off

    7.4 SEAL OIL PUMP - 2 AIR SIDE

    AUTO START

    1) SLC SO Pump (AS) on AND

    SO storage tank level not low AND

    SO pump 1 (AS) on AND SO pr after SOP-1 (AS) < 5 ksc TD2s

    2) SLC SO Pump (AS) on AND SOP-1 (AS) OFF and

    discrepancy .

    STOP PERMISSIVE

    1) SO pump 1 (AS) on AND SO pr after SOP-1 (AS) > 5 ksc TD5s

    2) SLC SO pump (AS) off

    7.5 SEAL OIL PUMP - 3 AIR SIDE (DC)

    AUTO START

    1) DC SOP local PB On command with local selected

    2) SLC DC SOP - 3 On AND SO/H2 DP (TE/EE) < 0.9 ksc TD2s

    3) SLC DC SOP - 3 On AND

    [ SO pump 1 (AS) OFF OR SO pr after SOP -1 (AS)

  • 7/27/2019 Protection and Interlock-NTPC

    44/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 43

    STOP PERMISSIVE

    1) SO pump 1 (AS) on AND SO pr after SOP -1 (AS) > 5 ksc

    TD5s

    2) SO pump 2 (AS) on AND SO pr after SOP -2 (AS) > 5 ksc

    TD5s

    3) SLC DC SO pump 3 off.

    MANUAL STOP

    1) DC SOP local PB off command with local selected

    2) Remote selected & Remote off command

    7.6 SEAL OIL PUMP - 4 H2 SIDE

    START PERMISSIVE1) Any Seal oil pump (AS) on AND Seal oil tank level > min

    AUTO START

    1) SGC Gen seal oil start-up Step 3 Command

    PROTECTION STOP

    1) Seal oil tank level low

    2) SOP Pressure air side < 4.5 ksc TD3s

    7.7 BEARING EXHAUST FAN 1 & 2

    AUTO START

    1) SLC Brg exhaust fan on AND

    Other Brg exhaust Fan on AND

    Press at respective Brg exhaust fan > -5 mbar TD2s

    2) SLC Brg exhaust fan on AND Other Beg exhaust Fan off

    3) SGC Gen seal oil start-up step-1 command

    STOP PERMISSIVE

    1) Other Brg exhaust fan on AND

    Press at respective Brg exhaust < -5 mbar TD5s

    2) SLC Brg exhaust fan Off

    7.8 EXCITER AIR DRIER

    AUTO ON1) SLC Air Drier on AND Turbine speed < 210 rpm

  • 7/27/2019 Protection and Interlock-NTPC

    45/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 44

    OFF PERMISSIVE

    1) Exciter Shut down Heater off

    AUTO OFF

    1) Turbine speed > 240 rpm AND

    Exciter Shut down Heater Off AND SLC Air Drier On

    7.9 EXCITER SHUT DOWN HEATER

    ON PERMISSIVE

    1) Air drier on

    AUTO ON

    1) SLC air drier on AND Air Drier On ANDTurbine speed 240 rpm OR Cold air temp >50 degc]

    PROTECTION OFF

    1) Cold air temp > 90 degc

    2) Air drier off

    7.10 CO2 FLASH EVAPORATOR

    AUTO ON

    1) SLC CO2 Flash Evaporator On AND

    CO2 Flash Evaporator temp. < 145 degc

    AUTO OFF:1) SLC CO2 flash evaporator off

    PROTECTION OFF:

    1) CO2 Flash Evaporator temp. > 150 degc

    7.11 COLD GAS TEMP CONTROL VALVE

    PROTECTION ON

    1) Cold gas temp > 55 degc

  • 7/27/2019 Protection and Interlock-NTPC

    46/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 45

    7.12 GAS DRIER HEATER

    START PERMISSIVE:

    1) Gas drier blower ON for 10 min

    AUTO ON

    1) SLC gas drier ON AND Air temp at drier outlet < 60 degc

    TD10s

    AUTO OFF

    1) Air temp. at Gas exhaust > 100 degc

    PROTECTION OFF

    1) Gas drier blower off2) Gas drier heater temp > 150 degc

    3) Gas drier blower ON for 4 hrs

    7.13 GAS DRIER BLOWER

    START PERMISSIVE

    1) Gas drier blower LS-1 OR 2 open

    AUTO ON

    1) SLC gas drier ON

    OFF PERMISSIVE

    1) Gas drier heater off

    AUTO OFF

    1) SLC gas drier ON AND Air temp. at drier O/L < 60 C AND Htr

    not On

  • 7/27/2019 Protection and Interlock-NTPC

    47/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 46

    7.14 GAMP ALARMS

    1) Oil level in Pre chamber (TE/EE) High

    2) Liquid at main leads bottom High

    3) Liquid at main leads top High

    4) Level in SOST low

    5) Pressure after AC SOP -1/2 (AS) low ( < 5 ksc)

    6) Pressure after DC SOP -3 (AS) low ( < 5 ksc)

    7) Pressure after AC SOP -4 (H2S) low ( < 5 ksc)

    8) DP across SO filter AS/H2S High ( > 0.9 ksc)

    9) SO Pr. (TE/EE) Air side Low ( < 4.5 ksc)

    10) SO temp after cooler (AS) High (> 50 degc)

    11) SO temp after cooler (H2S) High (> 50 degc)

    12) SO temp after cooler V High (> 55 degc)

    13) SO/H2 Diff Pr (TE AND EE ) High (>1.7 ksc)

    14) SO/H2 Diff Pr (TE AND EE ) low (< 0.9 ksc)

    15) H2 Pressure in Manifold low ( < 15 ksc)

    16) H2 Pressure in Gen Casing low ( < 3.3 ksc)

    17) H2 Pressure in Gen Casing High ( > 3.8 ksc)

    18) H2 purity in Gen Casing low ( < 95 %)

    19) PW Pr. after Pump low (< 5 ksc)

    20) DP Pr. Winding High ( > 1.5 ksc)

    21) PW temp after cooler V High ( > 55 degc)

    22) Stator Wdg Flow low ( < 54 m3/hr)

    23) Stator Wdg Flow V low ( < 48 m3/hr)

    24) Flow through R bush V low ( < 1.33 m3/hr)

    25) Flow through S bush V low ( < 1.33 m3/hr)

    26) Flow through T bush V low ( < 1.33 m3/hr)

    27) PW Pr. at stator Wdg I/L High ( > 3.8 ksc)

    28) Hot Gas temp. Coolers A AND B High ( > 60 degc)

    29) Hot Gas temp. Coolers C AND D High ( > 60 degc)

    30) Cold Gas temp. Coolers A AND B High ( > 55 degc)

    31) Cold Gas temp. Coolers C AND D High ( > 55 degc)

    32) Cold Gas temp. Coolers V High ( > 60 degc)

    33) Temperature Hot Air Main Exciter High ( > 75 degc)

    34) Temperature Hot Air Main Exciter V High ( > 80 degc)

    35) PW press. Stator I/L Low ( < 2.8 ksc)

    36) SO Pr. AS (TE/EE) Low ( < 4.9 ksc)

    37) PW temp at o/l High ( > 60 degc)

    38) Conductivity after Winding High ( > 3 uS/cm) TD5m

    39) Conductivity after main filter High ( > 3 uS/cm) TD5m

    40) Conductivity after Ion exchanger low (< 1uS/cm) TD5m

  • 7/27/2019 Protection and Interlock-NTPC

    48/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 47

    8 TDBFP

    8.1 PROTECTION

    1) TDBFP working AND suction flow very low ( < 100 tph )

    2) Deaerator level very low ( < -1610 mmwc)

    3) TDBFP Lub oil header press. very low ( < 1.0 ksc)

    4) TDBFP Suction valve not open

    5) TDBFP Exhaust stm temp very high ( > 120 degc)

    6) TDBFP Live steam pressure very high ( > 12.5 ksc)

    7) TDBFP Exhaust steam pr. very high ( > -0.6 ksc)

    8) Governing oil press. very low ( < 4.5 ksc)

    9) Trip oil press. very low ( < 2 ksc)

    10) Turbine Axial shift high ( > 0.7 mm)

    11) Turbine eccentricity very high ( > 92 mic)

    12) Trip PB operated

    13) Trip command from OWS

    14) Turbine over speed ( > 6300 rpm )

    15) Turbine GB i/p vibration very high ( > 70 mic)

    16) Turbine GB o/p vibration very high ( > 70 mic)

    17) Turbine FJB vibration very high ( > 70 mic)

    18) Turbine RJB vibration very high ( > 70 mic)19) Turbine GB brg temp very high ( > 120 degc)

    20) Turbine bearing temp very high ( > 120 degc)

    21) Booster pump brg temp very high ( > 95 degc)

    22) Booster pump thrust brg temp very high ( > 105 degc)

    23) BFP thrust brg temp metal very high ( > 105 degc)

    24) BFP brg temp very high ( > 95 degc)

    25) FW Suction / disch DT high ( > 15 degc )

    26) TDBFP working AND suc flow < Variable set point trip

  • 7/27/2019 Protection and Interlock-NTPC

    49/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 48

    8.2 TDBFP PERMISSIVES

    TDBFP Suction valve open AND

    Deaerator level adequate AND

    TDBFP Casing top/ btm DT < 20 degc AND

    Condenser press. < -0.5 ksc AND

    Lub oil header press. > 1.5 ksc AND

    BFP LOP p/p disch pr > 12.5 kg

    Lub oil temp after clr < 45 degc AND

    Governing oil press. > 6.5 ksc AND

    TDBFP gearbox brg temp < 105 degc AND

    TDBFP turbine brg temp < 105 degc AND

    TDBFP journal brg temp < 90 degc AND

    TDBFP thrust brg temp < 100 degc ANDTDBFP BP journal brg temp < 90 degc AND

    TDBFP BP thrust brg temp < 100 degc AND

    Any LOP ON AND

    TDBFP not working AND

    TDBFP Speed > 30 rpm AND

    TDBFP Aux steam block vlv open AND

    Aux steam press. > 12 ksc AND

    Aux steam temp >280 degc ANDAux steam superheat > 50 degc AND

    TDBFP suction / disch DT > 10 degc

    8.3 TDBFP DISCHARGE VALVE

    OPEN PERMISSIVE

    1) TDBFP discharge IBV open

    AUTO OPEN

    1) SGC TDBFP turbine start-up step 34 cmd

    2) TDBFP working AND Discharge press. > 40 ksc

    3) TDBFP discharge IBV open and OPEN cmd from OWS

    AUTO CLOSE

    1) SGC TDBFP turbine start-up step 21 cmd

    2) SGC TDBFP turbine shutdown step 55 cmd

    3) TDBFP Tripped

    4) TDBFP not working ANDDischarge header press > 60 ksc

  • 7/27/2019 Protection and Interlock-NTPC

    50/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 49

    TDBFP WORKING

    1) TDBFP ESV open AND

    Speed > 800 rpm AND

    Remote engagement oil press > 3.5 ksc AND

    [ Main CV >=2 % open OR CRH/Aux CV >=2 % open ]

    8.4 TDBFP RECIRCULATION VALVE

    CLOSE PERMISSIVE

    1) TDBFP suction flow >550 tph AND

    FW suction / disch. DT < 10 degc AND

    No auto open command

    2) TDBFP not working AND No auto open command

    AUTO OPEN

    1) TDBFP Working. AND

    [ Suction flow < 400 tph OR FW suc./disch. DT > 10 degc OR

    Suction flow measurement fault ]

    3) SGC TDBFP turbine start-up step 20 cmd

    4) SGC TDBFP turbine shutdown step 55 cmd

    PROTECTION OPEN

    1) TDBFP suction flow < 250 tph

    2) TDBFP not working

    AUTO CLOSE

    1) TDBFP suction flow > 850 tph AND

    FW suc./disch. DT < 10 degc TD- 5 sec

    2) SGC TDBFP turbine start-up step-39 cmd3) TDBFP var set point: CLOSE TD- 5 sec

    TDBFP variable set point: CLOSE

    1) Diff between Calc Flow and suction flow > 50 t/hr

    2) TDBFP FW suc flow >=550 t/hr

    3) TDBFP speed meas NO fault

    4) TDBFP suc & disch temp not HI 10 deg C

  • 7/27/2019 Protection and Interlock-NTPC

    51/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 50

    8.5 TDBFP REMOTE ENGAGEMENT SOLENOID V/V

    OPEN / ENERGISE PERMISSIVE

    1) TDBFP remote engagement oil pressure < 3.5 ksc AND

    TDBFP journal brg temp < 90 degc AND

    TDBFP thrust brg temp < 100 degc AND

    TDBFP BP journal brg temp < 90 degc AND

    TDBFP BP thrust brg temp < 100 degc AND

    TDBFP turbine brg temp < 105 degc AND

    TDBFP gearbox brg temp < 105 degc AND

    Discharge vlv closed AND

    Recirculation vlv open AND

    Lub oil temp after cooler < 45 degc AND

    Control oil header press. > 6.5 ksc AND

    Lub oil press. > 1.5 ksc AND

    Condenser press. < -0.5 ksc AND

    TDBFP Casing top/ btm DT < 20 degc AND

    TDBFP Suction / Disch. DT < 10 degc AND

    Deaerator level adequate AND

    TDBFP SUC valve open

    AUTO OPEN / ENERGISE1) SGC TDBFP turbine start-up step 23 cmd

    AUTO CLOSE / DEENERGISE

    1) TDBFP remote engagement oil pressure > 3.5 ksc

    2) SGC TDBFP turbine start-up step 24 cmd

    8.6 TDBFP OIL VAPOUR EXTRACTOR FAN- A & B

    AUTO START

    2) Other OVE tripped

    3) Other OVE off AND SGC TDBFP oil supply start-up step-1 cmd

    AUTO STOP

    1) SGC TDBFP oil supply shutdown step-58 cmd.

  • 7/27/2019 Protection and Interlock-NTPC

    52/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 51

    8.7 TDBFP LUB OIL PUMP - A & B

    AUTO START

    1) Other LOP tripped

    2) Other LOP start cmd given AND pump not ON TD2s

    3) [ TDBFP working OR Other LOP ON ] AND

    [ Lub oil disch. hdr. press. < 1.5 ksc OR LOP disch. press. < 7

    ksc ]

    4) Other LOP off AND SGC TDBFP oil supply start-up stp-2

    cmd

    RELEASE STOP

    1) TDBFP not working

    2) TDBFP speed zero and TDBFP speed 1.5 ksc AND

    LOP disch. press. > 7 ksc

    AUTO STOP

    1) SGC TDBFP oil supply shutdown step-57 cmd

    8.8 TDBFP EMERGENCY OIL PUMP

    AUTO START

    1) EOP Auto on selected AND

    TDBFP lub oil hdr. press. very low

    RELEASE STOP

    1) [ EOP Auto on not selected OR TDBFP lub oil hdr. press. not

    very low ] AND[ Any LOP on OR TDBFP speed zero ]

    AUTO STOP

    1) SGC TDBFP oil supply shutdown Step-57 cmd

  • 7/27/2019 Protection and Interlock-NTPC

    53/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 52

    8.9 TDBFP JACK OIL PUMP

    AUTO START

    1) TDBFP Turbine speed < 510 rpm

    2) SGC TDBFP oil supply start-up step-7 cmd

    3) SGC TDBFP oil supply shutdown step-53 cmd

    STOP PERMISSIVE

    1) Speed zero and TDBFP speed 540 rpm

    AUTO STOP

    1) SGC TDBFP oil supply start-up step-9 cmd

    2) SGC TDBFP oil supply shutdown step-56 cmd

    3) TDBFP Turbine speed > 540 rpm

    8.10 TDBFP TURNING GEAR VALVE

    AUTO OPEN

    1) [TDBFP turbine Speed < 510 rpm

    SGC TDBFP oil supply start-up step-6 cmd

    SGC TDBFP oil supply shutdown step-52 cmd] AND2) LO to turning gear valve closed OR Speed 540 rpm

    2) TDBFP turbine Casing temp < 85 degc

    AUTO CLOSE:

    1) TDBFP turbine Speed > 540 rpm2) SGC TDBFP oil supply start-up step-9 cmd

    3) SGC TDBFP oil supply shutdown step-55 cmd

    4) LO to turning gear valve Open AND Speed >=200 rpm

    8.11 TDBFP ENGAGE SOLENOID VALVE

    RELEASE OPEN / ENERGISE

    1) TDBFP Speed zero AND Speed < 10 rpm AND

    TDBFP Engage / diseng oil pump on

  • 7/27/2019 Protection and Interlock-NTPC

    54/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 53

    AUTO OPEN / ENERGISE

    1) SGC TDBFP oil supply start-up step-5 cmd

    RELEASE CLOSE / DEENERGISE

    1) TDBFP Speed zero AND Speed < 10 rpm AND

    TDBFP Engage / diseng oil pump on

    AUTO CLOSE / DEENERGISE

    1) SGC TDBFP oil supply start-up step-6 cmd

    8.12 TDBFP DISENGAGE SOLENOID VALVE

    RELEASE OPEN

    1) TDBFP turb. Speed < 300 rpm AND

    TDBFP engage / diseng oil pump ON

    8.13 TDBPF ENGAGE / DISENGAGE OIL PUMP

    START PERMISSIVE

    1) TDBFP LOP discharge hdr. press. not low >1.5 kg

    AUTO START:1) SGC TDBFP oil supply start-up step-5 cmd

    AUTO STOP :

    1) TDBFP pump engaged OR disengaged TD5s

  • 7/27/2019 Protection and Interlock-NTPC

    55/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 54

    9. MDBFP

    START PERMISSIVES

    [ AOP ON AND Lub oil press. > 2 ksc 2/3 ] TD2s AND

    MDBFP Suction valve open AND

    D/A level not low (> +20 mm) 2/3 AND

    Working oil temp. upstream clrs < 110 degc 2/3 AND

    Working oil temp. down stream clrs < 75 degc AND

    HC lub oil temp down stream clrs < 55 degc 2/3 AND

    MDBFP casing top / bottom DT < 22 degc AND

    MDBFP journal bearing temp < 90 degc AND

    MDBFP thrust bearing temp < 100 degc AND

    Hydraulic coupling bearing temp < 90 degc AND

    MDBFP motor journal bearing temp < 85 degc AND

    MDBFP motor winding temp < 125 degc AND

    Booster pump journal bearing temp < 90 degc AND

    Booster pump thrust bearing temp < 100 degc AND

    MDBFP CW header press. > 3.5 ksc AND

    MDBFP HC tank level not low AND

    MDBFP Recirculation Valve open AND

    MDBFP CW Valve close AND[ [MDBFP discharge v/v AND IBV Close] OR MDBFP Standby

    Selected ] AND

    [ [MDBFP Rapid Start Up Solenoid SOV92 AND SOV93 ON

    AND

    Scoop position min. (0%) ] OR Hyd. coupling min/cls (50 tph)

    2) MDBFP suction flow low ( < 100 tph) TD30s

    3) HC lub oil header press. very low (< 0.8 ksc) 2/3

    4) HC working oil temp very high (>130 degc) 2/3

    5) HC working oil press very low (

  • 7/27/2019 Protection and Interlock-NTPC

    56/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 55

    7) MDBFP suction & discharge DT >15 degc 2/3

    8) Lub oil temp. downstream clr very high (> 60 degc) 2/3

    9) MDBFP journal bearing temp very high (> 95 degc)

    10) MDBFP thrust bearing temp. very high ( >105 degc)

    11) MDBFP motor winding temp very high ( >130 degc)

    12) D/A level very low (< -1610 mm) 2/3

    13) MDBFP motor journal bearing temp very high (> 90 degc)

    14) Hyd. coupling bearing temp very high (> 95 degc)

    15) Booster pump thrust bearing temp very high (> 105 degc)

    16) Booster pump journal bearing temp very high (> 95degc)

    17) EPB acted

    MDBFP AUTO START

    1) [ MD BFP in Standby AND

    [ TD BFP-A tripped OR TD BFP-B tripped ] ]

    2) Command from MDBFP Startup Sequence Step # 07

    MDBFP AUTO STOP

    1) Command from MDBFP Shutdown Sequence step # 51

    9.1 MDBFP AOP

    AOP AUTO START

    1) MDBFP Auto Start

    2) MDBFP ON AND Lub oil press. low ( 15ksc) AND BFP OFF

    5) MDBFP OFF AND MDBFP Reverse Rotation Acted

    6) Command from Startup Sequence Step # 06

    7) MDBFP OFF AND 30 minutes hasn't elapsed to BFP OFF

    status.

    *Auto start command of A.O.P will persist for 30.min.

    AOP AUTO STOP

    1) MDBFP ON AND LO press. high (> 2.5 ksc) 2/3 TD2s

    2) Command from Startup sequence step # 13- A

    3) Command from Shutdown sequence step # 54- A

    4) MDBFP OFF for 30 min AND Any bearing temp. not high

  • 7/27/2019 Protection and Interlock-NTPC

    57/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 56

    9.2 MDBFP RECIRCULATION VALVE

    AUTO OPEN

    1) MDBFP flow measurement fault

    2) MDBFP ON AND

    Suction flow < 400 tph AND

    Its Variable Set point Fault

    3) MDBFP ON AND

    Its Variable Set Point no fault AND

    Diff of MDBFP Suction flow and Corrected Spd less than 5 tph

    4) MDBFP ON AND Discharge / Suction DT >10 degc

    5) Command from Startup sequence step # 02- A

    6) Command from Shutdown sequence step # 52- B

    PROTECTION OPEN

    1) MDBFP Suction flow low ( 50 tph ] ORMDBFP Suction flow > 850 tph ] AND

    MDBFP Disch / Suction DT 50 tph ] OR

    MDBFP Suction flow more (>850 tph) ] AND

    MDBFP Disch /Suction DT 40 ksc TD2s

    2) Command from Startup Sequence Step # 16

    3) Any TDBFP ON AND MDBFP Standby Selected AND

    Disch. header press. > 60 ksc

  • 7/27/2019 Protection and Interlock-NTPC

    58/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 57

    OPEN RELEASE

    1) Discharge Valve I.B.V Opened AND Reverse Rotation Not

    Acted

    AUTO CLOSE

    1) MDBFP OFF AND in Stdby AND MDBFP Reverse rotation

    acted

    2) MDBFP OFF AND in Stdby AND MDBFP Suction press. > 15

    ksc

    3) MDBFP OFF

    4) Command from Sequence Startup Step # 06-A

    5) Command from Sequence Shutdown Step # 53-A

    6) MDBFP OFF AND in standby AND Discharge press. < 40 ksc

    TD2m

    CLOSE RELEASE

    1) MDBFP OFF

    9.4 MDBFP DISCHARGE IBV

    AUTO OPEN1) MDBFP ON AND MDBFP Disch header. press. > 40 ksc TD1s

    2) Command from Startup Sequence Step # 15- A

    3) MDBFP Selected standby AND

    Any TDBFP ON AND Discharge header press. > 60 ksc TD2s

    AUTO CLOSE

    1) Command from Startup Sequence Step # 06- B

    2) Command from Startup Sequence Step # 17- B

    3) MD BFP Discharge valve opened

    4) Command from Shutdown Sequence Step # 53- B

    9.5 MDBFP RAPID START-UP SOLENOID - 91/92

    AUTO OPEN

    1) MD BFP Auto Start

    2) Command from Startup Sequence Step # 05- A

  • 7/27/2019 Protection and Interlock-NTPC

    59/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 58

    AUTO CLOSE

    1) MD BFP ON for 5.sec

    2) MD BFP Reverse Rotation Acted

    3) Command from Startup Sequence Step # 11- A

    2) MD BFP STDBY SELECTED & MD BFP Reverse Rotation Acted

    3) MD BFP STDBY SELECTED & SUC PR >15 KG

    OPEN RELEASE

    1) MD BFP standby selected AND Its Reverse Rotation Not Acted

    9.6 MDBFP CW VALVE

    AUTO OPEN

    1) MD BFP ON

    2) Command from Startup Sequence Step # 10- A

    CLOSE RELEASE

    1) MD BFP OFF

    AUTO CLOSE

    1) MD BFP Selected standby AND

    Discharge header press. > 60 ksc TD2s ANDAny TDBFP ON

    2) Command from Startup Sequence Step # 01-A

    3) Command from Shutdown Sequence Step # 53- C

    4) MD BFP OFF

  • 7/27/2019 Protection and Interlock-NTPC

    60/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 59

    10 CEP

    START PERMISSIVE

    CEP Suction valve open AND

    Hotwell level not low (>-250 mm) 2/3 AND

    Swgr. available AND

    Thrust bearing temp < 100 degc AND

    Motor bearing temp. < 85 degc AND

    Motor winding temp. < 125 degc AND

    Recirculation valve 40% open AND

    Vent valve open AND

    [[CEP Standby selected AND Its disch v/v open ] OR

    CEP discharge valve closed ]

    TRIP PROTECTION

    1) Hotwell Level very low ( < - 1850 mm ) 2/3

    2) CEP ON AND Discharge press. low ( < 18 ksc )

    3) CEP ON for 10 sec AND Flow through CEP low ( < 300 tph)

    TD5s

    4) Thrust bearing temp. very high ( > 105 degc)5) Motor bearing temp. very high ( > 90 degc)

    6) Motor winding temp. very high ( > 130 degc)

    7) Suction valve not open

    AUTO START

    1) Pump Selection Standby AND

    Other Running pump Tripped

    2) Pump Selection Standby ANDAny other pump ON for 30 sec AND

    Discharge header press. low (

  • 7/27/2019 Protection and Interlock-NTPC

    61/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 60

    10.1 CEP DISCHARGE VALVE

    AUTO OPEN

    1) CEP ON AND Discharge press. > 18 ksc TD2s

    2) CEP Discharge press. > 18 ksc AND

    Any other CEP ON AND CEP Standby Selected TD5s

    3) Command from CEP Startup sequence step # 106

    OPEN RELEASE

    1) Discharge Valve I.B.V Open

    CLOSE RELEASE

    1) CEP OFF

    AUTO CLOSE

    1) CEP Stdby Selected AND Disch hdr. press. < 20 ksc TD2m

    2) CEP OFF

    3) Command from CEP Startup sequence step # 102

    4) Command from CEP Shutdown sequence step # 202

    DISCHARGE VALVE I.B.V AUTO OPEN

    1) CEP ON AND Discharge press. > 18 ksc TD2s

    2) CEP discharge press. > 18 ksc AND

    Any other CEP ON AND CEP Standby Selected TD5s

    DISCHARGE VALVE I.B.V AUTO CLOSE

    1) Discharge valve opened

    10.2 CEP VENT VALVE

    AUTO OPEN

    1) CEP discharge press. > 18 ksc AND

    Any other CEP ON AND CEP Standby Selected TD5s

    2) CEP OFF

    3) Command from CEP Startup sequence step # 103

    4) Command from CEP Shutdown sequence step # 202

    AUTO CLOSE

    1) CEP ON

    OPEN RELEASE

    1) CEP OFF

  • 7/27/2019 Protection and Interlock-NTPC

    62/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 61

    11. ACW PUMP

    START PERMISSIVES

    1) Suction header press. > 1 ksc 2/3 AND

    Suction valve open AND

    [ Pump Selected Stdby AND Dischg vlv open ] OR Discg vlv clsd

    TRIP PROTECTIONS

    1) Pump ON for 08 sec AND Discharge press. high (>4.5 ksc )

    2) Pump ON for 120sec AND Discharge valve not open

    3) Pump ON and Suction Valve Not Open TD- 30 sec

    4) Pump ON AND Any other ACW ON ANDCommon discharge hdr. press. > 4.5 ksc 2/3 TD30s

    5) Suction header press. < 0.2 ksc 2/3 TD5s

    AUTO START

    1) Pump Selected Standby AND Any other ACW tripped

    2) P/p Selected Stdby AND Any other p/p ON AND Dischg hdr. pr

    < 2.3 ksc

    3) Command from ACW Startup Sequence Step # 3-A

    11.1 ACW PUMP DISCHARGE VALVE

    AUTO OPEN

    1) Pump Stdby Selected AND any other ACW ON AND Discharge

    header press. > 2.3 ksc AND ACW-A OFF

    2) Pump ON AND Discharge press. > 2.3 ksc

    3) Command from ACW Startup Sequence Step # 4-A

    AUTO CLOSE

    1) Pump Selected stdby AND Disch hdr pr < 2.3 ksc AND ACW

    OFF TD10s

    2) ACW OFF

    3) Command from ACW Startup Sequence Step # 1-A

    4) Command from ACW Shutdown Sequence Step # 52-A

    PERMISSIVE TO CLOSE

    1) ACW-A OFF

  • 7/27/2019 Protection and Interlock-NTPC

    63/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 62

    11.2 ACW PUMP SUCTION VALVE

    AUTO OPEN

    1) Pump Stdby Selected.

    2) Command from ACW Startup Sequence Step # 02-A

    AUTO CLOSE

    1) Command from ACW Shutdown Sequence Step # 52-A.

    2) ACW-A OFF

    PERMISSIVE TO CLOSE

    1) ACW-A OFF

  • 7/27/2019 Protection and Interlock-NTPC

    64/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 63

    12. ECW PUMP

    START PERMISSIVE

    1) Motor winding temp. < 125 degc AND

    Motor bearing temp. < 85 degc AND

    ECW standby condition & Discharge valve open AND

    Discharge valve Closed AND

    Suction header press > 2.5 ksc 2/3 AND

    Any ECW p/p ON OROverhead tank level not low ( > 950 mm)

    ECW STANDBY CONDITION

    1) Discharge v/v closed2) ECW standby selected AND Discharge v/v open

    3) Motor winding temp. < 125 degc AND

    4) Motor bearing temp. < 85 degc AND

    5) Overhead tank level not low ( > 950 mm)

    TRIP PROTECTIONS

    1) ECW ON for 60sec AND Discharge valve not open

    2) Suction valve not open

    3) ECW ON AND Discharge hdr. press. very high (> 8.5 ksc)

    4) Suction header press. very low (< 0.2 ksc) 2/3

    5) Motor winding temp very high (> 130 degc)

    6) Motor bearing temp very high (> 90 degc)

    AUTO START

    1) Pump Selection Standby AND Any other pump Tripped2) Pump Selection Standby AND Any other pump ON AND

    Discharge hdr. pr. low

    3) Command from Startup Sequence Step # 3

    AUTO STOP

    1) Command from Shutdown Sequence Step # 51

  • 7/27/2019 Protection and Interlock-NTPC

    65/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 64

    12.1 ECW PUMP DISCHARGE VALVE

    AUTO OPEN

    1) Pump Standby Selected AND Its Start Permissive Available

    AND

    Any other pump ON AND Discharge header press. > 3 ksc

    2) Pump ON AND Its Discharge press. > 5.4 ksc

    3) Command from Start Up Sequence step # 04 - A

    AUTO CLOSE

    1) Pump Selected standby AND Discharge header press. < 3 ksc

    2) Pump OFF

    3) Command from Shutdown Sequence Step # 202

    4) Command from Startup Sequence Step # 101

    12.2 ECW O/H TANK MAKE UP VALVES (SG + TG)

    EMG MU VALVE AUTO OPEN

    1) ECW O/H Tank Level low (

  • 7/27/2019 Protection and Interlock-NTPC

    66/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 65

    13 LP BYPASS

    1) LP Bypass Reset Trip SOV Protection valve will act

    at condenser wall temp > 90 C

    2) Injection water v/v open command will be issued at

    steam pressure before bypass v/v 1/2 > 6.8 ksc

    Closure of LPBP , in vase of:

    a) Condenser vacuum is low

    b) Spray water pressure is low

    c) Temperature of condenser body is high

    Malfunctions of the turbine bypass, i.e. failure of the bypass valves to

    open on demand, have to be counteracted by opening of the reheat

    safety valves to ensure flow through the reheater. This prevents a heat

    accumulation in the reheater tubes. For this purpose, the measure of

    flow through reheater is the magnitude of the deviation between actual

    and set pressure. The following conditions prevail.

    1. If the control deviation rises above a set limit value (>30%) and

    neither all bypass stop valves are fully open (25 %)

    and all LP bypass stop valves are fully open, the command for opening

    the reheater safety valves is also given on a time delay of 30 Seconds.

    13.1 SEAL STEAM

    1) Turbine Seal Steam Supply valve will get auto closed

    on temperature interlock at

    Seal Steam Header temp < 190 C

    2) Gland steam press abnormal : > 450 mmwc OR

    < 50 mmwc

  • 7/27/2019 Protection and Interlock-NTPC

    67/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 66

    14. AUX PRDS

    14.1 HT PRDS INLET ISOLATING VALVE ASV 21

    OPEN PERMISSIVE

    1) HT PRDS Isolating vlv ASV 21 IBV open

    AUTO OPEN

    1) HT PR control valve ASV 22 > 2 % open

    2) HT PRDS Isolating vlv ASV 21 IBV open

    AUTO CLOSE

    1) HT PR control valve ASV 22 < 2 % open TD-1.5 sec

    PROTECTION CLOSE

    1) HT PRDS Temperature V High > 350 degc

    2) LT PRDS Temperature V High > 285 degc

    14.2 HT PRDS ISOL. VALVE ASV 21 IBV

    AUTO OPEN

    1) HT PRDS Isolating vlv ASV 21 IBV open

    2) HT PR control valve ASV 22 > 2 % open

    AUTO CLOSE

    1) HT PRDS Isolating vlv ASV 21 open

    2) HT PR control valve ASV 22 < 2 % open

    PROTECTION CLOSE

    1) HT PRDS Temperature V High > 350 degc

    2) LT PRDS Temperature V High > 285 degc

    14.3 HT PR CONTROL VLV ASV 22

    PROTECTION CLOSE

    1) MFT operated

    2) HT PRDS Temperature V High > 350 degc

    3) LT PRDS Temperature V High > 285 degc

    4) CRH press > 18 ksc AND ASV 22

  • 7/27/2019 Protection and Interlock-NTPC

    68/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 67

    14.4 LT PRDS INLET ISOLATING VLV ASV 25

    AUTO OPEN

    1) LT PR control valve ASV 26 > 2% open

    AUTO CLOSE

    1) LT PR control valve ASV 26 285 degc

    14.5 LT PRDS CV BYP VLV ASV 28

    CLOSE PERMISSIVE

    1) LT PR CV bypass valve ASV 29 close

    PROTECTION CLOSE

    1) HT PRDS Temperature V High > 350 degc

    2) LT PRDS Temperature V High > 285 degc

    14.6 LT PR CONTROL VLV ASV 26

    AUTO CLOSE

    1) CRH press < 18 ksc

    PROTECTION CLOSE

    1) MFT operated

    2) HT PRDS Temperature V High > 350 degc

    3) LT PRDS Temperature V High > 240 degc

    14.7 LT PRDS DESH. VALVE ASV 181

    AUTO OPEN

    1) HT PR control valve ASV 22 > 2% open

    2) LT PR control valve ASV 26 > 2% open

    AUTO CLOSE

    1) HT PR control valve ASV 22 < 2% open AND

    LT PR control valve ASV 26 < 2% open

  • 7/27/2019 Protection and Interlock-NTPC

    69/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 68

    14.8 SPRAY BLOCK VALVE to PRDS FDV 43

    AUTO OPEN

    1) HT PR control valve ASV 22 > 2% open

    2) LT PR control valve ASV 26 > 2% open

    RELEASE CLOSE

    1) HT PR control valve ASV 22 < 2% open AND

    LT PR control valve ASV 26 < 2% open

    AUTO CLOSE

    1) HT PR control valve ASV 22 < 2% CLOSE

    2) LT PR control valve ASV 26 < 2% CLOSE

    3) LT PR control valve ASV 29 < 2% CLOSE

    PROTECTION CLOSE

    1) MFT operated

    14.9 HT PRDS SPRAY ISOLATING VLV FDV 29

    AUTO OPEN

    1) [HT PR control valve ASV 22 > 2% open OR

    HT APRDS spray control vlv FDV 30 >2 % open] AND

    2) Main line selected

    AUTO CLOSE

    1) HT PR control valve ASV 22

  • 7/27/2019 Protection and Interlock-NTPC

    70/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 69

    FORCED AUTO

    1) HT PR control valve ASV 22 > 2 % open AND

    2) Main line selected

    14.11 HT PRDS SPRAY CONTROL VALVE FDV 31

    AUTO CLOSE

    1) HT PR control valve ASV 22 < 2% close

    PROTECTION CLOSE

    1) MFT operated

    FORCED AUTO

    1) HT PR control valve ASV 22 > 2 % open AND

    2) Main line selected

    14.12 LT PRDS SPRAY ISOLATING VLV FDV 33

    AUTO OPEN

    1) [LT PR control valve ASV 26 > 2% open OR

    HT PR control valve ASV 22 > 2% open] and

    2) Main line selected

    RELEASE CLOSE

    1) LT PR control valve ASV 26 < 2% open AND

    HT PR control valve ASV 22

  • 7/27/2019 Protection and Interlock-NTPC

    71/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 70

    AUTO OPEN

    1) [LT PR control valve ASV 26 > 2% open OR

    HT PR control valve ASV 22 > 2% open] and

    2) Bypass line selected

    RELEASE CLOSE

    1) LT PR control valve ASV 26 < 2% open AND

    HT PR control valve ASV 22 2% open] AND

    2) Main line selected

    14.15 LT PRDS SPRAY CONTROL VALVE FDV 46

    AUTO CLOSE

    1) HT PR control valve ASV 22 < 2% close ANDLT PR control valve ASV 26 < 2% close AND

    ASV 29 < 2% open

    PROTECTION CLOSE

    1) MFT operated

    FORCED AUTO

    1) [HT PR control valve ASV 22 > 2 % open OR

    LT PR control valve ASV 26 > 2% open] AND

    2) Main line selected

  • 7/27/2019 Protection and Interlock-NTPC

    72/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 71

    15 LP HEATERS

    15.1 LPH CONDENSATE INLET ISO. VALVE

    OPEN RELEASE

    1) LPH Cond. I/L Isolating valve I.B.V Open ANDLPH Level Not HI

    AUTO OPEN

    1) Command from Startup Sequence Step # 02- A

    CLOSE RELEASE

    1) LPH Bypass Valve Opened

    AUTO CLOSE

    1) Command from Shutdown Sequence Step # 52- A

    PROTECTION CLOSE

    1) LPH Bypass Valve Not ClosedAND

    LPH Level very high 2/3

    15.2 LPH CONDENSATE OUTLET ISO. VALVE

    OPEN RELEASE

    1) LPH Level Not HI

    AUTO OPEN

    1) Command from Startup Sequence Step # 02- A

    CLOSE RELEASE

    1) LPH Bypass Valve Open

    AUTO CLOSE

    1) Command from Shutdown Sequence Step # 52- B

    PROTECTION CLOSE

    1) LPH Bypass Valve Not Closed AND LPH Level very high 2/3

  • 7/27/2019 Protection and Interlock-NTPC

    73/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 72

    15.3 LPH CONDENSATE INLET ISO. IBV

    OPEN RELEASE

    1) LPH Level Not HI

    AUTO OPEN

    1) Command from Startup Sequence Step # 01-A

    AUTO CLOSE

    1) Command from Startup Sequence Step # 03-A

    2) Command from Shutdown Sequence Step # 52-D

    3) LPH Cond. I/L Isolating valve open

    PROTECTION CLOSE

    1) LPH Level very high 2/3

    15.4 LPH BYPASS VALVE

    AUTO OPEN

    1) Command from Shutdown Sequence Step # 51-A

    CLOSE RELEASE

    1) LPH Cond. I/L AND O/L Isolating valve Open

    AUTO CLOSE

    1) LPH Cond. I/L AND O/L Isolating valve Open

    2) Command from Startup Sequence Step # 03- B

    PROTECTION OPEN

    1) LPH Level very high 2/3

  • 7/27/2019 Protection and Interlock-NTPC

    74/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 73

    15.5 LPH 2 & 3 EXT STM VALVES

    EXT STM ISOLATING VALVE OPEN RELEASE

    1) LPH I/L Isolating valve open AND

    O/L Isolating valve open AND

    LPH level not high AND Turbine Not Tripped

    EXT STM ISOLATING VALVE AUTO OPEN

    1) Command from Start Sequence Step # 04- A

    EXT STM ISOLATING VALVE AUTO CLOSE

    1) Command from Shutdown Sequence Step # 52- A

    EXT STM ISOLATING VALVE PROTECTION CLOSE

    1) Turbine Tripped

    2) LPH Level very high 2/3

    3) LPH Cond. I/L Isolating valve Not Open

    4) LPH Cond. O/L Isolating valve Not Open

    5) LPH Cond. Bypass Valve Not Close

    EXT STM DRN VALVE AUTO OPEN

    1) Command from Startup Sequence Step # 01- B

    2) Command from Shutdown Sequence Step # 51- A3) LPH EXT STM Isolating valve close

    EXT STM DRN VALVE AUTO CLOSE

    1) Command from Startup Sequence Step # 05- A

    2) LPH EXT STM Isolating valve open

    EXT STM DRN VALVE PROTECTION OPEN

    1) LPH Level very high 2/3

    2) Turbine Tripped

  • 7/27/2019 Protection and Interlock-NTPC

    75/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 74

    16. HP HEATERS

    16.1 HPH 5A FW INLET ISOLATING VALVE

    OPEN RELEASE

    1) HPH-5A FW I/L isolating valve I.B.V opened AND

    2) HPH-5A/6A level < 135 mm 2/3 (Not Hi)

    AUTO OPEN

    1) Command from Startup Sequence Step # 03-A

    CLOSE RELEASE

    1) [HPH FW 50% BYP Valve Opened AND

    HPH-5B FW I/L Iso. Valve Opened ANDHPH-6B FW O/L isolating valve opened] OR

    2) HPH FW 100% bypass valve opened

    AUTO CLOSE

    1) Command from Shutdown Sequence Step # 62-C

    PROTECTION CLOSE

    1) Release to Auto Close available AND

    HPH-5A/6A Level > 415 mm 2/3 (HI HI)

    16.2 HPH 5A FW INLET ISOLATING IBV

    AUTO OPEN

    1) Command from Startup Sequence Step # 1-A

    2) HPH -5A iso valve open CMD

    PERMISSIVE OPEN

    1) HPH -5A/6A level not high

    AUTO CLOSE

    1) Command from Startup Sequence Step # 62-E

    2) HPH-5A FW I/L isolating valve open

    3) HPH-5A FW I/L isolating valve Close CMD

    PROTECTION CLOSE

    1) HPH-5A/6A Level > 415 mm 2/3 (Hi Hi)

  • 7/27/2019 Protection and Interlock-NTPC

    76/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 75

    16.3 HPH 6A FW OUTLET ISOLATING VALVE

    OPEN RELEASE

    1) HPH-6A FW O/L isolating valve I.B.V opened AND

    HPH-5A/6A level < 135 mm 2/3

    AUTO OPEN

    1) Command from Startup Sequence Step # 03- B

    CLOSE RELEASE

    1) HPH FW 50% BYP Valve Opened AND

    HPH-5B FW I/L Iso. Valve Opened AND

    HPH-6B FW O/L Iso. Valve Opened OR

    HPH FW 100% bypass Valve Opened

    AUTO CLOSE

    1) Command from Shutdown Sequence Step # 62 -D

    PROTECTION CLOSE

    1) Release to Auto Cls Available AND HPH-5A/6A Level > 415 mm

    2/3

    16.4 HPH 6A FW OUTLET ISOLATING IBV

    AUTO OPEN

    1) Command from Startup Sequence Step # 01-B

    2) HPH -6A O/L iso valve open CMD

    PERMISSIVE OPEN

    1) HPH -5A/6A level not high

    AUTO CLOSE1) Command from Startup Sequence step# 04-B

    2) HPH-5A FW I/L isolating valve open

    3) HPH-5A FW I/L isolating valve Close CMD Step # 62-F

    PROTECTION CLOSE

    1) HPH-5A/6A Level > 415 mm 2/3

  • 7/27/2019 Protection and Interlock-NTPC

    77/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 76

    16.5 HPH 5A(6A) EXT. STM VALVE AND NRV

    OPEN PERMISSIVE

    1) HPH-5A/6A LVL NOT HI

    2) HPH-5A I/L isolating Valve Open AND

    HPH-6A O/L isolating Valve Open

    3) Turbine Not Tripped

    4) [ HPH-5B FW I/L Iso. valve Closed AND

    HPH-6B FW O/L Iso. valve Closed AND

    HPH FW 50% BYP Valve Opened AND

    HPH FW 100% bypass Valve Closed ] OR

    [ HPH FW 100% bypass valve closed AND

    HPH-5B FW I/L Iso. valve Opened AND

    HPH-6B FW O/L Iso. valve Opened ANDHPH FW 50% bypass valve Closed ]

    AUTO OPEN

    1) Command from Startup Sequence Step # 10- A

    AUTO CLOSE

    1) Command from Shut down Sequence Step # 51- A

    PROTECTION CLOSE

    1) Turbine Not Tripped

    2) HPH-5A FW I/L isolating valve Closed

    3) HPH-6A FW O/L isolating valve Closed

    4) HPH FW 100% BYP valve open

    5) HPH-5A/6A level very high

    HPH-5A EXT STM I/L NRV AUTO OPEN

    1) Command from Startup Sequence Step # 11

    HPH-5A EXT STM I/L NRV AUTO CLOSE

    1) Command from Shutdown Sequence Step # 51

    HPH-5A EXT STM I/L NRV PROTECTION CLOSE

    1) Turbine Tripped

    2) HPH-5A FW I/L isolating valve not opened

    3) HPH-6A FW O/L isolating valve not opened

    4) HPH FW 100% bypass valve not closed

    5) HPH-5A/6A Level very high

  • 7/27/2019 Protection and Interlock-NTPC

    78/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 77

    HPH-5A/5B EXT STM DRN VALVE AUTO OPEN

    1) Command from HPH-5A/6A Shutdown Seq Step # 202

    2) Command from HPH-5B/6B Start-up Seq Step # 102

    3) Command from HPH-5B/6B Shutdown Seq Step # 202

    4) HPH-5A EXT STM Valve Closed AND

    HPH-5B EXT STM Valve Closed

    HPH-5A/5B EXT STM DRN VALVE AUTO CLOSE

    1) Command from HPH-5A/6A Startup Seq Step # 112

    2) Command from HPH-5B/6B Startup Seq Step # 112

    3) HPH-5A EXT STM Valve opened

    4) HPH-5B EXT STM Valve opened

    HPH-5A/5B EXT STM DRN V/V PROTECTION OPEN

    1) HPH-5A/6A Level very high

    2) HPH-5B/6B Level very high

    HPH-6A EXT STM DRN VALVE AUTO OPEN

    1) Command from HPH-5A/6A Shutdown Seq Step # 201

    2) Command from HPH-5A/6A Startup Seq Step # 101

    3) HPH-6A EXT STM Valve

    HPH-6A EXT STM DRN VALVE AUTO CLOSE

    1) Command from HPH-5A/6A Startup Seq Step # 112

    2) HPH-6A EXT STM Valve opened

    HPH-6A EXT STM DRN V/V PROTECTION OPEN

    1) HPH-5A/6A Level very high

    16.6 HPH FW 50% BYPASS VALVE

    OPEN RELEASE

    1) HPH FW 50% BYP Valve I.B.V Open

    AUTO OPEN

    1) Command from HPH Startup Seq Step # 107

    2) Command from HPH Shutdown Seq Step # 204

    AUTO CLOSE

    1) Command from HPH Startup Seq Step # 5- A

    2) Command from HPH Shutdown Seq Step # 06- A

  • 7/27/2019 Protection and Interlock-NTPC

    79/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 78

    PROTECTION OPEN

    1) HPH-5A/6A Level > 415 mm 2/3

    2) HPH-5B/6B Level > 415 mm 2/3

    CLOSE PERMISSIVE

    1) [ HPH-5A I/L Iso. Valve Opened AND

    HPH-6A O/L Iso. Valve Opened AND

    HPH-5B I/L Iso. Valve Opened AND

    HPH-6B O/L Iso. Valve Opened ] OR [ HPH FW 100% bypass

    Valve Opened ]

    BYP.VALVE I.B.V AUTO OPEN

    1) Command from HPH Startup Seq Step # 06- A

    2) Command from HPH Shutdown Seq Step # 54- A

    BYP.VALVE I.B.V AUTO CLOSE

    1) Command from HPH Startup Sequence Step # 08-B

    2) Command from HPH Shutdown Sequence Step # 05- B

    3) HPH FW 50% bypass Valve opened

    4) Command from HPH Shutdown Sequence Step # 60-B

    BYP.VALVE I.B.V PROTECTION OPEN

    1) HPH-5A/6A Level > 415 mm

    2) HPH-5B/6B Level > 415 mm

    16.7 HPH FW 100% BYPASS VALVE

    CLOSE PERMISSIVE

    1) [ HPH-5A I/L Iso. Valve Opened AND

    HPH-6A O/L Iso. Valve Opened AND

    HPH-5B I/L Iso. Valve Opened AND

    HPH-6B outlet Iso. Valve Opened ] OR

    [ HPH-5A FW I/L Iso.Valve Opened AND

    HPH-6A FW O/L Iso.Valve Opened OR

    HPH-5B FW I/L Iso. Valve Opened AND

    HPH-6B FW O/L Iso. Valve Opened AND

    HPH FW 50% bypass Valve Opened ]

    OPEN RELEASE

    1) HPH FW 100% BYP Valve I.B.V Open

  • 7/27/2019 Protection and Interlock-NTPC

    80/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 79

    AUTO OPEN

    1) Command from HPH Shut down Seq Step # 58- A

    AUTO CLOSE

    1) Command from HPH Startup Seq Step # 09- A

    PROTECTION OPEN

    1) [ HPH-5A FW I/L Iso. Valve Not Open OR

    HPH-6A FW O/L Iso. Valve Not Open OR

    HPH-5A/6A Level > 415 mm ] AND

    [ HPH-5B FW I/L Iso. Valve Not Open OR

    HPH-6B FW O/L Iso. Valve Not Open OR

    HPH-5B/6B Level > 415 mm ]

    BYP.VALVE I.B.V AUTO OPEN

    1) Command from HPH Shut down Seq Step # 57- A

    BYP.VALVE I.B.V AUTO CLOSE

    1) Command from HPH Startup Sequence Step # 09-A

    2) Command from HPH Shutdown Sequence Step # 59- A

    3) HPH FW 100% bypass Valve opened

    BYP.VALVE I.B.V PROTECTION OPEN

    1) [ HPH-5A FW I/L Iso. Valve Not Open OR

    HPH-6A FW O/L Iso. Valve Not Open OR

    HPH-5A/6A Level > 415 mm ] AND

    [ HPH-5B FW I/L Iso. Valve Not Open OR

    HPH-6B FW O/L Iso. Valve Not Open OR

    HPH-5B/6B Level > 415 mm ]

  • 7/27/2019 Protection and Interlock-NTPC

    81/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 80

    17. DEAERATOR

    1 AS TO D/A PEGGING CV BP VALVEASV 10

    PROTECTION CLOSE:

    1) Deaerator level very high

    2 D/A OVERFLOW CONTROL VALVE DRV 48

    AUTO OPEN

    1) Deaerator level high

    PROTECTION OPEN

    1) Deaerator level very high

    AUTO CLOSE

    1) Deaerator level low

    3 CRH TO D/A PEGGING CV BP VALVE CRHV 8

    PROTECTION CLOSE:

    1) Deaerator level very high

    4 D/A EXTRACTION VALVE EXV 13

    OPEN PERMISSIVE

    1) D/A level not High.

    AUTO OPEN

    1) Extraction steam pressure >3.5 ksc

    PROTECTION CLOSE1) D/A level V High

    2) Turbine tripped

  • 7/27/2019 Protection and Interlock-NTPC

    82/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 81

    5 D/A EXTRACTION LINE DRAIN VALVE EXV 15

    AUTO OPEN

    1) Turbine tripped

    AUTO CLOSE

    1) Extraction steam flow to D/A >10%

    6 Main Cond CS CV ( CD-22) I/L iso valve

    Auto open: CD-22 is opened by >2%

    AutoClose: CD-22 is closed by 2%

    AutoClose: CD-25 is closed by

  • 7/27/2019 Protection and Interlock-NTPC

    83/89

    PROTECTIONS AND INTERLOCKS DIARY

    KAHALGAON STAGE II 3 X 500 MW 82

    18. CW PUMP

    1 CW PUMP START PERMISSIVES

    Sump level not low (>34.7 m) AND

    Motor thrust bearing temp < 100 degc AND

    Motor upper guide bearing temp NDE < 100 degc AND

    Motor lower g