PROTECTA FR PIPE WRAP INSTALLATION …media.voog.com/0000/0041/4072/files/Protecta FR Pipe Wrap...
Transcript of PROTECTA FR PIPE WRAP INSTALLATION …media.voog.com/0000/0041/4072/files/Protecta FR Pipe Wrap...
PROTECTA® FR PIPE WRAP
INSTALLATION INSTRUCTIONS
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change product specifications without giving notice. All information contained in this document is given in good faith and is provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, are intended to be given as to the actual performance of the product mentioned or referred to herein and no liability whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
Installation Instructions to ETA 14/0247
www.protecta.euPolyseam Ltd
1 (7) 2014 8 22
Protecta® FR Pipe Wrap is designed to maintain the fire resistance of fire separating walls and floors when these are breached by continuous plastic pipes or metal pipes with combustible insulation, and may be used in gypsum, masonry or concrete walls and concrete floors. Each pipe wrap consists of a graphite based reactive intumescent strip which reacts to heat and closes the opening left by the softening plastic pipe or pipe insulation in fire. The pipe wrap is installed completely around the pipes or insulation and secured with the self-adhesive tab. The annular space around the pipe wrap is sealed with Protecta® EX Mortar or Protecta® FR Board.
Penetration type & max dimensions
Minimum width and number of layers of pipe wrap
Classification
FLEXIBLE AND RIGID WALL CONSTRUCTIONS ≥ 100MM ≤ Ø110mm PVC-U & PVC-C pipe
50 x 3.6mm (2 layers) both sides E 120 U/C, C/C EI 90 U/C, C/C
Ø125mm PVC-U & PVC-C pipe
50 x 5.4mm (3 layers) both sides E 120 U/C, C/C EI 90 U/C, C/C
Ø160mm PVC-U & PVC-C pipe
50 x 7.2mm (4 layers) both sides E 120 U/C, C/C EI 90 U/C, C/C
RIGID FLOOR CONSTRUCTIONS ≥ 150MM ≤ Ø110mm PVC-U & PVC-C pipe
75 x 1.8mm (1 layer), or 50 x 3.6mm (2 layers) soffit side
EI 180 C/C
Ø125mm PVC-U & PVC-C pipe
50 x 7.2mm (4 layers) soffit side EI 180 C/C
Ø160mm PVC-U & PVC-C pipe
50 x 10.8mm (6 layers), or 75 x 5.4mm (3 layers) soffit side
EI 180 C/C
Please note: The minimum permitted separation between adjacent seals/apertures is 20cm. An aperture can include several services, and they may also be different. Services should be a minimum of 30mm from seal edges or other services so that the fire seals can be correctly fitted around each service. Services in floors require a minimum separation of 10cm from other services. The total amount of cross sections of services (including insulation) should not exceed 60% of the penetration area. Please see the Installation Instructions for the fire stopping system used with this product. Supporting construction: Flexible walls must have a minimum thickness of 100 mm and comprise steel studs lined on both faces with minimum 2 layers of 12.5 mm thick boards. The walls must also incorporate a full fill core insulation of stone wool (35kg/m3 density). Rigid walls and floors must comprise concrete, aerated concrete or masonry, with a minimum density of 650 kg/m3. The service support must be classified in accordance with EN 13501-2 for the required fire resistance period.
This Installation Instruction is based on the product’s European Technical Assessment, issued in accordance with regulation (EU) No 305/2011, on the basis of ETAG 026-2 and 3, edition 2011, used as European Assessment Document (EAD).
1. Fix a suitable pipe wrap around the service penetration and
fasten with the tape as tightly as possible in order to prevent any excess opening between the pipe wrap and the service.
2. In floors, only one pipe wrap is required to be installed flush with the soffit so that the edge of the wrap is visible from the underside when back-filled. For walls it is normal to fit a wrap on both sides of the wall, again with the edge just visible.
3. Where wraps are installed in hollow core slabs or planks, the tubular voids should be filled with stone-wool insulation, normally the same thickness as the depth of the floor.
4. Once the wrap is securely installed, using a suitable shuttering board, cast around the pipe wrap with Protecta® EX Mortar to the required depth.
5. The Protecta® FR Pipe Wrap may be installed in a Protecta® FR Board. Cut the hole around the penetrating service to be sealed slightly oversize so that the pipe wrap may be slid in to the middle of the board. Finally the end of the pipe wrap is sealed with Protecta® FR Acrylic on both outer sides.
6. See the detail drawings of various installation methods on pages 2 to 7.
GENERAL PRODUCT DESCRIPTION
FIRE CLASSIFICATION - TABLE
INSTALLATION
TYPICAL DETAIL
CERTIFICATION
TYPICAL DETAIL
Detail Drawings Protecta® FR Pipe Wrap
Installation Guide to ETA 14/0247
www.protecta.euPolyseam Ltd tel.+44(0)1484421036
2 (7) 2014 8 22
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change product specifications without giving notice. All information contained in this document is given in good faith and is provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, are intended to be given as to the actual performance of the product mentioned or referred to herein and no liability whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
INSULATED STEEL PIPES FIRE RESISTANCE EI 180 (E 180)
RIGID FLOORS
INSULATED STEEL PIPES FIRE RESISTANCE EI 120 (E 180)
RIGID FLOORS
INSULATED STEEL PIPES FIRE RESISTANCE EI 45 (E 90)
RIGID FLOORS
INSULATED STEEL PIPES FIRE RESISTANCE EI 90 (E 90)
RIGID FLOORS
INSULATED STEEL PIPES FIRE RESISTANCE EI 120 (E180)
RIGID FLOORS
INSULATED COPPER PIPES FIRE RESISTANCE EI 180 (E 180)
RIGID FLOORS
Steel pipes ≤ Ø40mm
EX Mortar ≥ 100mm thick
Maximum aperture 1200 x 2400mm
Protecta Pipe Wrap 1 layer of 50mm wide fitted at soffit
13mm continuous elastomeric foam insulation
Steel pipes ≤ Ø165mm
EX Mortar ≥ 100mm thick
Maximum aperture 1200 x 2400mm
Protecta Pipe Wrap 1 layer of 50mm wide fitted at soffit
13-19mm continuous elastomeric foam insulation
Steel pipe ≤ Ø165mm
1 layer 60mm FR Board 2-SAll services and openings must be sealed with FR Acrylic both sides
Protecta Pipe Wrap 2 layers of 50mm wide
Maximum aperture 1200 x 2400mm
13mm continuous elastomeric foam insulation
Steel pipe ≤ Ø165mm
1 layer 60mm FR Board 2-SAll services and openings must be sealed with FR Acrylic both sides
Protecta Pipe Wrap 2 layers of 50mm wide
Maximum aperture 1200 x 2400mm
19mm continuous elastomeric foam insulation
Steel pipe ≤ Ø40mm
2 layers 60mm FR Board 2-SAll services and openings must be sealed with FR Acrylic both sides
Protecta Pipe Wrap 1 layer of 50mm wide
Maximum aperture 1200 x 2400mm
13mm continuous elastomeric foam insulation
Copper pipes≤ Ø12mm
EX Mortar ≥ 100mm thick
Maximum aperture 1200 x 2400mm
Protecta Pipe Wrap 2 layers of 50mm wide fitted at soffit
9mm continuous elastomeric foam insulation
Detail Drawings Protecta® FR Pipe Wrap
Installation Guide to ETA 14/0247
www.protecta.euPolyseam Ltd tel.+44(0)1484421036
3 (7) 2014 8 22
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change product specifications without giving notice. All information contained in this document is given in good faith and is provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, are intended to be given as to the actual performance of the product mentioned or referred to herein and no liability whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
INSULATED COPPER PIPES FIRE RESISTANCE EI 60 (E 180)
RIGID FLOORS
INSULATED COPPER PIPES FIRE RESISTANCE EI 60 (E 240)
RIGID FLOORS
INSULATED COPPER PIPES FIRE RESISTANCE EI 45 (E 180)
RIGID FLOORS
INSULATED ALUPEX COMPOSITE PIPES FIRE RESISTANCE EI 180 (E 180)
RIGID FLOORS
INSULATED ALUPEX COMPOSITE PIPES FIRE RESISTANCE EI 90 (E 180)
RIGID FLOORS
INSULATED ALUPEX COMPOSITE PIPES FIRE RESISTANCE EI 120 (E 120)
RIGID FLOORS
Copper pipes ≤ Ø54mm
EX Mortar ≥ 100mm thick
Maximum aperture 1200 x 2400mm
Protecta Pipe Wrap 2 layers of 50mm wide fitted at soffit
13-25mm continuous elastomeric foam insulation
Copper pipe ≤ Ø54mm
2 layers 60mm FR Board 1-SAll services and openings must be sealed with FR Acrylic both sides
Protecta Pipe Wrap 2 layers of 50mm wide
Maximum aperture 1200 x 2400mm
9-13mm continuous elastomeric foam insulation
Copper pipe ≤ Ø54mm
2 layers 60mm FR Board 1-SAll services and openings must be sealed with FR Acrylic both sides
Protecta Pipe Wrap 2 layers of 50mm wide
Maximum aperture 1200 x 2400mm
14-25mm continuous elastomeric foam insulation
Alupex pipes ≤ Ø16mm
EX Mortar ≥ 100mm thick
Maximum aperture 1200 x 2400mm
Protecta Pipe Wrap 2 layers of 50mm wide fitted at soffit
9mm continuous elastomeric foam insulation
Alupex pipes ≤ Ø75mm
EX Mortar ≥ 100mm thick
Maximum aperture 1200 x 2400mm
Protecta Pipe Wrap 2 layers of 50mm wide fitted at soffit
13-25mm continuous elastomeric foam insulation
Alupex pipe ≤ Ø75mm
2 layers 60mm FR Board 1-SAll services and openings must be sealed with FR Acrylic both sides
Protecta Pipe Wrap 2 layers of 50mm wide
Maximum aperture 1200 x 2400mm
9mm continuous elastomeric foam insulation
Detail Drawings Protecta® FR Pipe Wrap
Installation Guide to ETA 14/0247
www.protecta.euPolyseam Ltd tel.+44(0)1484421036
4 (7) 2014 8 22
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change product specifications without giving notice. All information contained in this document is given in good faith and is provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, are intended to be given as to the actual performance of the product mentioned or referred to herein and no liability whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
INSULATED ALUPEX COMPOSITE PIPES FIRE RESISTANCE EI 45 (E 60)
RIGID FLOORS
PLASTIC PIPES FIRE RESISTANCE EI 90 (E 90)
RIGID FLOORS
PLASTIC PIPES FIRE RESISTANCE EI 60-240
RIGID FLOORS
INSULATED STEEL PIPES FIRE RESISTANCE EI 240 (E 240)
MASONRY OR CONCRETE - WALLS
INSULATED STEEL PIPES FIRE RESISTANCE EI 60 (E 180)
MASONRY OR CONCRETE - WALLS
Alupex pipe ≤ Ø75mm
2 layers 60mm FR Board 1-SAll services and openings must be sealed with FR Acrylic both sides
Protecta Pipe Wrap 2 layers of 50mm wide
Maximum aperture 1200 x 2400mm
13-25mm continuous elastomeric foam insulation
PVC-U plastic pipe ≤ Ø110mm
1 layer 60mm FR Board 2-SAll services and openings must be sealed with FR Acrylic both sides Protecta Pipe Wrap
2 layers of 50mm wide
Maximum aperture 1200 x 2400mm
Services Wrap Maximum aperture
Classification
≤ Ø75mm PP 50 x 3.6mm (2 layers) 300x300mm EI 240 C/C ≤ Ø75mm PP 50 x 3.6mm (2 layers) 1200x2400mm EI 180 C/C ≤ Ø110mm PE, ABS & SAN+PVC 50 x 1.8mm (1 layer) 1200x2400mm EI 60 C/C ≤ Ø110mm PVC-U & PVC-C 75 x 1.8mm (1 layer) 1200x2400mm EI 180 C/C ≤ Ø110mm PVC-U & PVC-C 50 x 3.6mm (2 layers) 200x200mm EI 240 C/C ≤ Ø110mm PVC-U & PVC-C 50 x 3.6mm (2 layers) 1200x2400mm EI 180 C/C ≤ Ø125mm PE, ABS & SAN+PVC 75 x 3.6mm (2 layers) 1200x2400mm EI 180 C/C Ø125mm PVC-U & PVC-C 50 x 7.2mm (4 layers) 300x300mm EI 240 C/C Ø125mm PVC-U & PVC-C 50 x 7.2mm (4 layers) 1200x2400mm EI 180 C/C Ø160mm PE, ABS & SAN+PVC 75 x 7.2mm (4 layers) 1200x2400mm EI 180 C/C Ø160mm PVC-U & PVC-C 50 x 10.8mm (6 layers) 300x300mm EI 240 C/C Ø160mm PVC-U & PVC-C 50 x 10.8mm (6 layers) 1200x2400mm EI 180 C/C Ø160mm PVC-U & PVC-C 75 x 7.2mm (4 layers) 300x300mm EI 240 C/C Ø160mm PVC-U & PVC-C 75 x 5.4mm (3 layers) 1200x2400mm EI 180 C/C Ø200-250mm PE, ABS & SAN+PVC 75 x 12.6mm (7 layers) 1200x2400mm EI 180 C/C
Protecta FR Pipe Wrap to the bottom of the seal
Plastic pipe
Protecta EX Mortar ≥ 100mm thick
Steel pipes ≤ Ø40mm
13mm continuous elastomeric foam insulation
Maximum aperture 2400mm wide and 1200mm high
Protecta Pipe Wrap 2 layers of 50mm wide fitted central
EX Mortar ≥ 100mm thick
Steel pipes ≤ Ø165mm
13-25mm continuouselastomeric foam insulation
Maximum aperture 2400mm wide and 1200mm high
Protecta Pipe Wrap 2 layers of 50mm wide fitted central
EX Mortar ≥ 100mm thick
Detail Drawings Protecta® FR Pipe Wrap
Installation Guide to ETA 14/0247
www.protecta.euPolyseam Ltd tel.+44(0)1484421036
5 (7) 2014 8 22
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change product specifications without giving notice. All information contained in this document is given in good faith and is provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, are intended to be given as to the actual performance of the product mentioned or referred to herein and no liability whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
INSULATED STEEL PIPES FIRE RESISTANCE EI 45 (E 120)
MASONRY OR CONCRETE - WALLS
PLASTIC PIPES FIRE RESISTANCE EI 120 (E 120)
MASONRY OR CONCRETE - WALLS
INSULATED STEEL PIPES FIRE RESISTANCE EI 120 (E 120)
GYPSUM, MASONRY OR CONCRETE - WALLS
INSULATED STEEL PIPES FIRE RESISTANCE EI 60 (E 120)
GYPSUM, MASONRY OR CONCRETE - WALLS
INSULATED STEEL PIPES FIRE RESISTANCE EI 60 (E 120)
GYPSUM, MASONRY OR CONCRETE - WALLS
INSULATED STEEL PIPES FIRE RESISTANCE EI 120 (E 120)
GYPSUM, MASONRY OR CONCRETE - WALLS
Steel pipe ≤ Ø165mm
1 layer 60mm FR Board 2-S
9-25mm continuous elastomeric foam insulation
All services and openings must be sealed with FR Acrylic both sides
Maximum aperture 2400mm wide and 1200mm high
Protecta Pipe Wrap 1 layer of 50mm wide
PVC-U pipesØ315mm
Maximum aperture 2400mm wide and 1200mm high
Protecta Pipe Wrap 10 layers of 75mm wide fitted central
EX Mortar ≥ 100mm thick
Steel pipes ≤ Ø40mm
13mm continuous elastomeric foam insulation
Maximum aperture 2400mm wide and 1200mm high
Protecta Pipe Wrap 1 layer of 50mm wide fitted to both faces
EX Mortar ≥ 25mm thick on both sides 50mm stone wool
shutter ≥ 150kg/m3
Steel pipes ≤ Ø165mm
13mm continuous elastomeric foam insulation
Maximum aperture 2400mm wide and 1200mm high
Protecta Pipe Wrap 2 layers of 50mm wide fitted to both faces
EX Mortar ≥ 25mm thick on both sides 50mm stone wool
shutter ≥ 150kg/m3
Steel pipes ≤ Ø165mm
13-32mm continuous elastomeric foam insulation
Maximum aperture 2400mm wide and 1200mm high
Protecta Pipe Wrap 2 layers of 50mm wide fitted to both faces
EX Mortar ≥ 50mm thick on both sides
Steel pipe ≤ Ø40mm
13mm continuous elastomeric foam insulation
2 layers 50mm FR Board 1-S
All services or openings must be sealed with FR Acrylic both sides
Protecta Pipe Wraps 1 layer of 50mm wide middle or both sides
Maximum aperture 2400mm wide and 1200mm high
Detail Drawings Protecta® FR Pipe Wrap
Installation Guide to ETA 14/0247
www.protecta.euPolyseam Ltd tel.+44(0)1484421036
6 (7) 2014 8 22
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change product specifications without giving notice. All information contained in this document is given in good faith and is provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, are intended to be given as to the actual performance of the product mentioned or referred to herein and no liability whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
INSULATED STEEL PIPES FIRE RESISTANCE EI 60 (E 120)
GYPSUM, MASONRY OR CONCRETE - WALLS
INSULATED COPPER PIPES FIRE RESISTANCE EI 120 (E 120)
GYPSUM, MASONRY OR CONCRETE - WALLS
INSULATED COPPER PIPES FIRE RESISTANCE EI 120 (E 120)
GYPSUM, MASONRY OR CONCRETE - WALLS
INSULATED COPPER PIPES FIRE RESISTANCE EI 90 (E 120)
GYPSUM, MASONRY OR CONCRETE - WALLS
INSULATED COPPER PIPES FIRE RESISTANCE EI 60 (E 120)
GYPSUM, MASONRY OR CONCRETE - WALLS
INSULATED ALUPEX COMPOSITE PIPES FIRE RESISTANCE EI 120 (E 120)
GYPSUM, MASONRY OR CONCRETE - WALLS
Steel pipe ≤ Ø165mm
13-32mm continuous elastomeric foam insulation
2 layers 50mm FR Board 1-S
All services or openings must be sealed with FR Acrylic both sides
Protecta Pipe Wraps 2 layers of 50mm wide both sides
Maximum aperture 2400mm wide and 1200mm high
Copper pipe ≤ Ø54mm
9-25mm continuous elastomeric foam insulation
Maximum aperture 2400mm wide and 1200mm high
Protecta Pipe Wrap 2 layers of 50mm wide fitted to both faces
EX Mortar ≥ 25mm thick on both sides 50mm stone wool
shutter ≥ 150kg/m3
Copper pipe ≤ Ø12mm
9mm continuous elastomeric foam insulation
2 layers 50mm FR Board 1-S
All services or openings must be sealed with FR Acrylic both sides
Protecta Pipe Wraps 2 layers of 50mm wide both sides
Maximum aperture 2400mm wide and 1200mm high
Copper pipe ≤ Ø54mm
9-13mm continuous elastomeric foam insulation
2 layers 50mm FR Board 1-S
All services or openings must be sealed with FR Acrylic both sides
Protecta Pipe Wraps 2 layers of 50mm wide both sides
Maximum aperture 2400mm wide and 1200mm high
Copper pipe ≤ Ø54mm
14-25mm continuous elastomeric foam insulation
2 layers 50mm FR Board 1-S
All services or openings must be sealed with FR Acrylic both sides
Protecta Pipe Wraps 2 layers of 50mm wide both sides
Maximum aperture 2400mm wide and 1200mm high
Alupex pipe ≤ Ø75mm
9-25mm continuous elastomeric foam insulation
Maximum aperture 2400mm wide and 1200mm high
Protecta Pipe Wrap 2 layers of 50mm wide fitted to both faces
EX Mortar ≥ 25mm thick on both sides 50mm stone wool
shutter ≥ 150kg/m3
Detail Drawings Protecta® FR Pipe Wrap
Installation Guide to ETA 14/0247
www.protecta.euPolyseam Ltd tel.+44(0)1484421036
7 (7) 2014 8 22
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change product specifications without giving notice. All information contained in this document is given in good faith and is provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, are intended to be given as to the actual performance of the product mentioned or referred to herein and no liability whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
INSULATED ALUPEX COMPOSITE PIPES FIRE RESISTANCE EI 120 (E 120)
GYPSUM, MASONRY OR CONCRETE - WALLS
PLASTIC PIPES FIRE RESISTANCE EI 60-120
GYPSUM, MASONRY OR CONCRETE - WALLS
PLASTIC PIPES FIRE RESISTANCE EI 90-120
GYPSUM, MASONRY OR CONCRETE - WALLS
Alupex pipe ≤ Ø75mm
9-25mm continuous elastomeric foam insulation
2 layers 50mm FR Board 1-S
All services or openings must be sealed with FR Acrylic both sides
Protecta Pipe Wraps 2 layers of 50mm wide both sides
Maximum aperture 2400mm wide and 1200mm high
Protecta Pipe Wraps to both sides
Plastic pipe
Services Wrap Classification ≤ Ø40mm PVC-U & PVC-C 50 x 1.8mm (1 layer) E 120 U/C, C/U & EI 60 U/C, C/C ≤ Ø40mm PE, ABS & SAN+PVC 50 x 1.8mm (1 layer) EI 120 U/C, C/C ≤ Ø40mm PP 50 x 1.8mm (1 layer) EI 120 U/C, C/C ≤ 110mm PVC-U & PVC-C 50 x 3.6mm (2 layers) E 120 U/C, C/C & EI 90 U/C, C/C Ø41-110mm PE, ABS & SAN+PVC 50 x 3.6mm (2 layers) EI 60 U/C, C/C Ø41-110mm PP 50 x 3.6mm (2 layers) E 120 U/C, C/C & EI 90 U/C, C/C ≤ Ø125mm PVC-U & PVC-C 50 x 5.4mm (3 layers) EI 120 U/C, C/C ≤ Ø125mm PE, ABS & SAN+PVC 50 x 5.4mm (3 layers) EI 120 U/C, C/C Ø125mm PP 50 x 5.4mm (3 layers) E 120 U/C, C/C & EI 90 U/C, C/C Ø160mm PVC-U & PVC-C 50 x 7.2mm (4 layers) EI 60 U/C, C/C Ø160mm PE, ABS & SAN+PVC 50 x 7.2mm (4 layers) E 120 U/C, C/C & EI 90 U/C, C/C Ø160mm PP 50 x 7.2mm (4 layers) E 120 U/C, C/C & EI 60 U/C, C/C
Maximum aperture 2400mm wide and 1200mm high
2 layers 50mm FR Board 1-S
Protecta Pipe Wraps to both sides
Plastic pipe
All services or openings must be sealed with FR Acrylic both sides
Services Wrap Classification ≤ Ø40mm PVC-U & PVC-C 50 x 1.8mm (1 layer) EI 120 U/U, C/U, U/C, C/C ≤ Ø40mm PE, ABS & SAN+PVC 50 x 1.8mm (1 layer) EI 120 U/U, C/U, U/C, C/C ≤ Ø40mm PP 50 x 1.8mm (1 layer) EI 120 U/U, C/U, U/C, C/C Ø41-110mm PVC-U & PVC-C 50 x 3.6mm (2 layers) E 120 U/C, C/C & EI 90 U/C, C/C Ø41-110mm PE, ABS & SAN+PVC 50 x 3.6mm (2 layers) E 120 U/C, C/C & EI 90 U/C, C/C Ø41-110mm PP 50 x 3.6mm (2 layers) EI 90 U/U, C/U, U/C, C/C Ø125mm PVC-U & PVC-C 50 x 5.4mm (3 layers) E 120 U/C, C/C & EI 90 U/C, C/C Ø125mm PE, ABS & SAN+PVC 50 x 5.4mm (3 layers) E 120 U/C, C/C & EI 90 U/C, C/C Ø125mm PP 50 x 5.4mm (3 layers) E 120 U/C, C/C & EI 90 U/C, C/C Ø160mm PVC-U & PVC-C 50 x 7.2mm (4 layers) E 120 U/C, C/C & EI 90 U/C, C/C Ø160mm PE, ABS & SAN+PVC 50 x 7.2mm (4 layers) E 120 U/C, C/C & EI 90 U/C, C/C Ø160mm PP 50 x 7.2mm (4 layers) E 120 U/C, C/C & EI 90 U/C, C/C
Maximum aperture 2400mm wide and 1200mm high
EX Mortar ≥ 25mm thick on both sides of 50mm stone wool shutter ≥ 150kg/m3