PROPOSED PACKAGE CAPACITY: 2.0 MW (2500KVA) AGN Technology offers the full and complete 2.0 MW of electricity package as a turnkey solution. The enter package shall be install and test for client by AGN Technology engineering department.
Package Price for 2.8MW Synchronized Electricity: $1.545m**
Package Price for Grid Connected 2.0 MW Synchronized Electricity: Call For Details Price **Note: Synchronized 5 generator (Diesel Engine) and through power to one common bas-bar.
Payment Terms: 60% advance along with at the time of contract singing, Balance 30% payment after delivery materials to site and remaining 10% will be payment at the time of project handover to the client.
Payment Terms for War Zone Countries: 80% advance along with at the time of contract singing, Balance 20% will be payment after delivery materials to the site. Civil Construction and Site Preparation: Project related all civil construction and site preparation is the fully client responsibility. Material Transportation: Inside UAE: Transport all material from AGN Technology warehouse (in UAE) to site location is including with package price. Outside UAE: Transport all material from AGN Technology warehouse (in UAE) to site location is the client responsibility. Security and AGN Technical Staff Accommodations: Inside UAE: A security and AGN technical staff accommodations in UAE is the AGN Technology responsibility. Outside UAE and War Zone Countries: Security, Accommodation and Transportations of all AGN technical staff are the sole responsibility of the client in the war zone countries. It can be discussed in full details once the contract is signed between AGN & its clients. Price Change: All Price are subject to change and alternation without prior notice. Should the prices changes during the contract, AGN will not change price for existing client contract.
Contract Cancelation Terms: Once the contract is signed and fully discussed in details, the payment /deposit is for failed and non-refundable at any circumstance. Delay of payment shall be the same as the cancelation of the project the time both party agree up on.
LIST OF MATERIALS FOR PROPOSED PACKAGE
S/N Description of materials Quantity Required Remarks 1 Cummins Diesel Engine Generators
Capacity: 500KVA, 400 Volt & 50Hz 5x500=2500KVA
2 Synchronization Control Panel Model: ATSP09
5 No’s with common Bus-bar
3 MCCB Capacity: 1000Amps, 3 pole Brand: ABB/Schneider
5 No’s
4 Air Circuit Breaker (ACB) Capacity:4000 Amps, 3 pole Brand: ABB/ Schneider
1 No
5 Low Voltage Power Cable Voltage: 400 V Cable size: 630mm² or 400mm² Single core, Copper conductor Insulation: XLPE
As per required
6 Grounding Cable Size: 95mm², Y/G copper Conductor
As per required
7 Grounding Cable Size: 35mm², Y/G copper Conductor
As per required
8 Grounding Cable Size: 16mm², Y/G copper Conductor
As per required
9 Control Cable As per required
10
External Fuel Tank Capacity: 10K gallons
1 No
11 Fuel Pipes As per required
12 Fuel Filter 5 No
13 Accessories
Options For The Above Package
14 Step-up Power Transformer (0.4KV/33KV or 0.4KV/11KV or as per client requirements) Capacity: 2500 KVA, 50Hz
1 No As per client demand
15 SF6 RMU or SF6 Breaker or VCB Capacity: 630 Amps with all protection system
1 No As per client demand
16 High Voltage or Medium Voltage Power Cable Cable size: 300mm², Three core, Copper conductor Insulation: XLPE, Armored steel ware insulated
As per required As per client demand
17 20’ Container 5 No As per client demand
Civil constrictions are the client responsibility; AGN should be to quote, If requested by client.
SINGLE LINE DIAGRAM FOR 2 MW SYNCHRONIZED ELECTRICITY
TO LOAD TO LOAD
250A/5A/1ACT s
S1
S2
Step-up Power Transformer 0.4KV/20KV or 0.4KV/11KV or 0.4KV/33KV(2500KVA) YNd11
4000A/5ACT
P1
P2
GE
N-
2
GE
N-
3
GE
N-
4
GE
N-
5
Computerized Synchronization
control panel
Sf6 RMUCapacity: 630ACT Ratio: 100:1
With Over current &Earth fault protection
Cummins Diesel GeneratorCapacity: 500kVA, 400V, 50Hz
MCCB 1000A,4P,50KAWITH SCC, OC PROTECTIONWITH MOTOR OPERATOR
1000/1A1000/5A
CTCTCT
1000/5A
Computerized Synchronization Control Panel
Air Circuit Breaker (ACB)Capacity: 4000A
CT Ratio: 4000/1A/5A
With all metering & protection
Vacuum Circuit Breaker (VCB)Capacity: 630ACT Ratio: 100:1
With Over current &Earth fault protection
GE
N-
1
CT
Copyright © 1998-2009 agnenegy.comPlease note: All logos, trade marks and any other wording or pictures are used for illustration and display purposes only.
MATERIAL DESCRIPTIONS AND DETAIL TECHNICAL SPECIFICATIONS
Generator Technical Specification
1500 rpm (50 Hz Ratings): Gross Engine Output Net Engine Output Typical Generator Set Output Stand by Prime Base Stand by Prime Base Stand by (ESP) Prime (PRP) Base (COP)
KWm/BHP KWm/BHP KWe KVA KWe KVA KWe KVA
500/670 444/595 317/425 477/639 426/571 299/400 440 550 400 500 281 351
Weight & Dimensions: Length Width Height Weight(dry) mm mm mm Kg
2269 1332 1669 1658
Fuel Consumption 1500 (50 Hz):
Engine Specification
Alternator Specification
Technical information and values are according to ISO8528, ISO3046, NEMA MG1.22, IEC 600341, BS 49995000, VDE 0530 standards. All products manufactured according to ISO9001, ISO14001, OHSAS18001, TSE, CE
standards. All information given in this specification set is intended for general purposes only. Due to a policy continuous improvement AGN Technology reserves the right to amend details and specifications without notice and all information given is subject to the AGN Technology current condition of sales.
TBA: To Be Ask TBD: To Be Determined NA: Not Available N/A: Not Applicable
% KWm BPH L/ph US gal/ph
Standby Power 100 500 670 123.0 32.4
100 444 595 103.0 27.3
Prime Power 75 333 447 78.7 20.8
50 222 298 54.7 14.5
25 111 149 30.0 8
Continues Power 100 317 425 75.7 20 Standby Power Standby power is defined as the maximum power available during a variable electrical power sequence, under the stated operating conditions, for which a generating set is capable of delivering in the event of a utility power outage or under test conditions for up to 500 hours of operation per year under average of 70% load. Overloading is not permissible.
Prime Power Prime power is defined as being the maximum power which a generating set is capable of delivering continuously whilst supplying a variable electrical load. Average load should be 70%. The generator can be overloaded 10% for 1 hour per 12 hours.
Design 4 cycle, in-line, Turbo Charged, Air-cooled
Bore 137 mm (5.39 in.)
Stroke 169 mm (6.65 in.)
Displacement 15 liter (912.3)
Cylinder Block Cast iron, 6 cylinders Battery Capacity 100A/hr Battery Charging Alternator35 amps Starting Voltage 24 volt, negative ground Fuel System Direct injection
Fuel Filter Spin on full flow filter
Air Cleaner Type Dry replaceable element with restriction indicator
Lube Oil Filter Type(s)
Spin on fuel filters with water separator
Standard Cooling System
122 F (50 C) ambient radiator
Design Brushless single bearing
Revolving field
Stator 2/3 pitch
Rotor Single bearing Flexible disc
Insulation System Class H
Standard Temperature Rise
125 - 163 C Stand by
Exciter Type Self Excited
Phase Rotation A (U), B (V), C (W)
Alternator Cooling Direct drive centrifugal blower fan
AC Waveform Total Harmonic Distortion
No load: 1.5% None distorting balanced linear load: 5%
SYNCHRONIZATION CONTROL PANEL SPECIFICATION ATSP09 SYNCHRONIZATION CONTROL PANEL SPECIFICATIONS LOAD PROPERTIES:
Automatic and manual synchronization Can synchronized until 10 generators among
them selves and feed the workload Load sharing at generators according to power
Automatically start and stop according to load
Automatically balancing work hours (co-aging)
COMMUNICATION PROPERTIES:
Communication over (AQ) bus-bar with electronic engine control units (optional)
Alarm message with SMS (optional)
Open communication over RS 232 or RS 485 interface
Support Motbus RTU protocol (concordant with scada system)
INDICATOR PROPERTIES: LCD text indicator
All engine and alternator parameters can be watched
Engine and alternator protection
Keep the records of generator alarms, last 25 records
Expansion modules (in and out)
With LCD screen in ATSP09 synchronization panels you can measure the following rates and with the stated protection, system reliability put in first place.
MEASUREMENTS: DIRECT MEASURES:
Oil pressure
Coolant temperature
Fuel level (optional)
Oil temperature (optional)
Accumulator voltage
Engine circulation
Generator frequency
Generator phase-neutral voltage
Generator inter-phase voltage
Generator phase current
Generator earth current (optional)
Generator phase sequence
EXPANDABLE MEASUREMENTS:
Generator total active power (KW)
Generator total visible power (KVA)
Generator total reactive power (KVAr)
Generator average power factor (cosΦ)
HIDDEN MEASUREMENTS: Actual time
Left time for the next (maintenance)
Generator positive KWh
Generator negative KWh
Generator KVAh
Generator KVArh
Number of starter
Maximum positive vector slide
Maximum negative vector slide
PROTECTION SYSTEM: ENGINE PROTECTION:
Low oil pressure
High coolant water temperature
High oil temperature (optional)
Low/high frequency cycle
Battery charger rectifier error
Low/high accumulator voltage
Low/high fuel level (optional)
ALTERNATOR PROTECTION:
Low/high voltage
Low/high frequency
Extreme voltage
Earthling error (optional)
Reverse power
Wrong phase rotation of alternator
Excitation loss
CIRCUIT BREAKER PROTECTION:
Generator switching off error
Generator switching on error
Technical information and values are according to ISO8528, ISO3046, NEMA MG1.22, IEC 600341, BS 49995000, VDE 0530 standards. All products manufactured according to ISO9001, ISO14001, OHSAS18001, TSE, CE standards. All information given in this specification set is intended for general purposes only. Due to a policy continuous improvement AGN Technology reserves the right to amend details and specifications without
notice and all information given is subject to the AGN Technology current condition of sales.
TBA: To Be Ask TBD: To Be Determined NA: Not Available N/A: Not Applicable
MCCB TECHNICAL SPECIFICATION
Technical information and values are according to ISO8528, ISO3046, NEMA MG1.22, IEC 600341, BS 49995000, VDE 0530 standards. All products manufactured according to ISO9001, ISO14001, OHSAS18001, TSE, CE standards. All information given in this specification set is intended for general purposes only. Due to a policy continuous improvement AGN Technology reserves the right to amend details and specifications without notice and all information given is subject to the AGN Technology current condition of sales.
TBA: To Be Ask TBD: To Be Determined NA: Not Available N/A: Not Applicable
Brand Name ABB
Capacity 1000Amps
P Pole Three
Frequency 50Hz
Design Compact
Serial number 034798
NS 100N
Vi 750
Uimp 8KV
Vc-389/240
Icu 50 (V) 380/415~KA 50
440~50 500/525 ~ 40
660
690 ~ 30 Ics 75% Icu
Icw 25 KA/.5s Cat-B
Protection system
Generator switching off error
Generator switching on error
Over load
AIR CIRCUIT BREAKER SPECIFICATION
Technical information and values are according to ISO8528, ISO3046, NEMA MG1.22, IEC 600341, BS 49995000, VDE 0530 standards. All products manufactured according to ISO9001, ISO14001, OHSAS18001, TSE, CE standards. All information given in this specification set is intended for general purposes only. Due to a policy continuous improvement AGN Technology reserves the right to amend details and specifications without notice and all information given is subject to the AGN Technology current condition of sales.
TBA: To Be Ask TBD: To Be Determined NA: Not Available N/A: Not Applicable
Brand name ABB
Model E4S/f
Rated uninterrupted current (at 40 °C) Iu [A] 4000
Number of poles 4
Rated service voltage Ue [V ~] 690
Rated ultimate short-circuit breaking capacity Icu
220/230/380/400/415 V ~ [kA] 80
440 V ~ [kA] 80
500/660/690 V ~ [kA] 75
Rated short-time withstand current Icw 80
(1s) [kA] 75
(3s) [kA]
Rated short-circuit making capacity (peak value) Icm [kA] 176
Application category (in accordance with IEC 60947-2) B
Isolation behavior (in accordance with IEC 60947-2)
Overall Dimensions
Fixed: H = 418 mm - D = 302 mm L [mm] 746 Withdraw able: H = 461 - D = 396.5 mm L [mm] 774 Weights (circuit-breaker complete with releases and CT, not including accessories) Fixed [kg] 120 Withdraw able (including fixed part) [kg] 170 250
STEP- UP POWER TRANSFORMER SPECIFICATION
Technical information and values are according to ISO8528, ISO3046, NEMA MG1.22, IEC 600341, BS 49995000, VDE 0530 standards. All products manufactured according to ISO9001, ISO14001, OHSAS18001, TSE, CE standards. All information given in this specification set is intended for general purposes only. Due to a policy continuous improvement AGN Technology reserves the right to amend details and specifications without notice and all information given is subject to the AGN Technology current condition of sales.
TBA: To Be Ask TBD: To Be Determined NA: Not Available N/A: Not Applicable
Capacity of power transformer 2500kVA
1 Duty Continuous to suit Max. Ambient 50°C
2 Type Oil immersed Conservator type
3 Cooling ONAN
4 Primary Voltage 0.4KV
5 Secondary Voltage 33kV or 20KV or 11 KV or as per client demand
6 Frequency 50 Hz
7 No. of phase 3
8 Winding Cu wound
9 Vector Group YNd11
10 Primary Connection Delta
11 Secondary Connection Star
12 Tapping ± 7.5% in steps of 2.5%
13 Insulation class of winding Class A
14 Temperature rise Deg. C
Top oil 50 ∙C
Winding 55 .C
15 % Impedance 7.5% +IEC TOL.
16 No load losses 4.5 KW + IEC TOL.
17 HV termination Side mounted cable box
18 LV termination Side mounted cable box
19 Applicable Standards IEC 60076
20 Over all dimension 1350*1500*1500 mm
21 Total Weight 7312 KG
22 Accessories Terminal marking plates
Tap Switch (Off- load)
Rating Plate
Cooling fan/Radiators
2 No’s earthling terminals
Lifting lugs
Oil level gauge
Drain valve
Top filling hole & plug
Thermometer with max. pointer
Pressure relief device
OTI, WTI, Bucholz Relay
SF6 RMU TECHNICAL DETAILS
Technical information and values are according to ISO8528, ISO3046, NEMA MG1.22, IEC 600341, BS 49995000, VDE 0530 standards. All products manufactured according to ISO9001, ISO14001, OHSAS18001, TSE, CE standards. All information given in this specification set is intended for general purposes only. Due to a policy continuous improvement AGN Technology reserves the right to amend details and specifications without notice and all information given is subject to the AGN Technology current condition of sales.
TBA: To Be Ask TBD: To Be Determined NA: Not Available N/A: Not Applicable
2 no’s of 630Amp triple pole, single break, 3- position (“ON”, “OFF” and “EARTH”) ring main switches, each with independent manually charged spring mechanism and fully rated earth switch with provision for earth and test of the cable.
2 no’s of air insulated cable boxes and cable clams suitable for a 3 – core cable up to 300mm². 1 no 250 Amps triple pole, vacuum circuit breaker, with independent manually charged spring mechanism and fully rated earth switch with provision for earth and test of the cable.
1 no air insulated cable box and clamp suitable for a 3- core cable up to 185mm².
1 no mimic diagram on front panel, complete with status indicator. 1 set of positive standard mechanical interlocks. 1 set of current transformer for relay protection.
1 no ABEVA make self powered relay type: MICOM P124 for O/C & E/F protection.
1 no 24V DC shunt trip coil for remote tripping of circuit breaker.
1 set of fully interlocked test access cover.
2 no’s of neon indicator lamps /phase comparator sockets for each ring switch.
1 no stud for earthling connection.
1 no pressure indicator and SF6 recharging facility.
1 no “PULL TO TRIP” mechanism (Suitable shrouded).
1 set of auxiliary terminal.
1 no operating handle.
1 no earth fault indicator, electrical Auto reset (240V AC), complete with solid core current transformer.
VACUUM CIRCUIT BREAKER (VCB) TECHNICAL SPECIFICATIONS
Technical information and values are according to ISO8528, ISO3046, NEMA MG1.22, IEC 600341, BS 49995000, VDE 0530 standards. All products manufactured according to ISO9001, ISO14001, OHSAS18001, TSE, CE standards. All information given in this specification set is intended for general purposes only. Due to a policy continuous improvement AGN Technology reserves the right to amend details and specifications without notice and all information given is subject to the AGN Technology current condition of sales.
TBA: To Be Ask TBD: To Be Determined NA: Not Available N/A: Not Applicable
DESCRRIPTION UNIT SPECIFICATION
Rated voltage KV 20
Service voltage KV 20
Rated frequency HZ 50
Rated insulation level (one min. 50Hz withstand voltage)
KV rms 28
Impulse withstand voltage (1.2/50 micro-sec. wave) KV peak
KV peak 75
3 second withstand current KA rms 20
Peak withstand current KA peak 63
Internal arc withstand current (IEC 60298 app. A) (1 second)
KA rms 25
Bus-bar rated current A 630
Auxiliary voltage
for spring loading 220V 50HZ
For protective relays, control, signaling
24V 50 HZ
For heating 220V 50HZ
Current transformer (CT) 3 No. ring type (Multiple CT)
150/5A(for metering) and 150/1A(for protection)
Potential Transformer (PT) 2 No.
20/0.4KV (Class0.5,50 VA)
Protection system
Earth fault relay Over Current relay for 3 phase (RED, YELLOW, BLUE) Master trip relay (VAJ relay) Trip current supervision relay
LOW VOLTAGE CABLE TECHNICAL DETAILS
Technical information and values are according to ISO8528, ISO3046, NEMA MG1.22, IEC 600341, BS 49995000, VDE 0530 standards. All products manufactured according to ISO9001, ISO14001, OHSAS18001, TSE, CE standards. All information given in this specification set is intended for general purposes only. Due to a policy continuous improvement AGN Technology reserves the right to amend details and specifications without notice and all information given is subject to the AGN Technology current condition of sales.
TBA: To Be Ask TBD: To Be Determined NA: Not Available N/A: Not Applicable
1 Cable Type Low voltage cable
2 Size of cable(Core*Area in mm²)
1*630
3 Applicable Standard IEC60502
4 Suitable of earthed/Unearthed system
Earthed/unearthed system
5 Voltage grade (KV) KV 0.6/1 KV
6 Maximum rated conductor temperature
∙C 105 ∙C
7 Max. Allowed conductor temperature during short current
∙C 250 ∙C
8 Continuous current carrying capacity when Load In
In Air 745
In Ground 1050
In Duct 1050
9 Conductor
Material Annelid copper
Shape Standard circular conductor
Cross section area 630
10 Insulation
Materials XLPE compound, as per ISO7098
Normal thickness of insulation mm 2.00
11 Outer Sheath
Materials PVC
Extruded or Wrapped Extruded
Thickness of sheath (Min.) mm 2.10
Color of sheath Black
12 Overall diameter of cable mm 37.0
13 Approx. Net Weight of cable Kg/Km
3869.0
14 Overall quantity tolerance % ±5%
15 Recommended minimum bending radius
mm 740
16 Max. DC resistance at 20∙C Ohm/Km
0.047
17 Max. AC resistance at 70∙C Ohm/Km
FUEL TANK DESIGN SPECIFICATION
Technical information and values are according to ISO8528, ISO3046, NEMA MG1.22, IEC 600341, BS 49995000, VDE 0530 standards. All products manufactured according to ISO9001, ISO14001, OHSAS18001, TSE, CE standards. All information given in this specification set is intended for general purposes only. Due to a policy continuous improvement AGN Technology reserves the right to amend details and specifications without notice and all information given is subject to the AGN Technology current condition of sales.
TBA: To Be Ask TBD: To Be Determined NA: Not Available N/A: Not Applicable
Capacity 10,000 Gallons
Shape Cylindrical
Thickness 8mm
Port Inlet, Outlet (For Overflow)
Bottom stand 1000mm Ht.
Material Grade A-36, Mild Steel
Painting System
The fuel tank shall be light in color to minimize heating of the fuel by radiant heat sources. Any plating or paint materials shall not be degraded by contact with the fuel
Accessories
Fuel drain (The fuel drain assembly shall be constructed at the bottom side of the fuel tank) Fuel Gauge Man hole Air Vent Ladder Walking Platform at the top