Proposed Changes & Revisions to the 2017 National Electrical Code©

57
Proposed Changes & Revisions 2017 National Electrical Code © Sources: http://iaeimagazine.org/magazine/2015/04/30/analysis-of-changes-2017-nec/ http://iaeimagazine.org/magazine/2015/09/04/analysis-of-changes-2017-nec-part-2/ With the 2017 release of the NEC coming soon, there are some changes and revisions you will need to know. To prepare you for the upcoming changes, TPC Training Systems introduces some of the proposed and expected changes to come with this release. National Electrical Code 2017 NEC [email protected]

Transcript of Proposed Changes & Revisions to the 2017 National Electrical Code©

Page 1: Proposed Changes & Revisions to the 2017 National Electrical Code©

Proposed Changes & Revisions

2017 National Electrical Code©

Sources: http://iaeimagazine.org/magazine/2015/04/30/analysis-of-changes-2017-nec/http://iaeimagazine.org/magazine/2015/09/04/analysis-of-changes-2017-nec-part-2/

With the 2017 release of the NEC coming soon, there are some changes and revisions you will need to know. To prepare you for the upcoming changes, TPC Training Systems introduces some of the proposed and expected changes to come with this release.

National Electrical Code2017 NEC

REVISION: 840.48 - Unlisted Wires and Cables Entering Buildings for Premises-Powered Broadband Communications Systems

In order to expand the coverage of Article 840, there is a proposal to recognize both twisted pair and coaxial cable-based systems in addition to optical fiber-based systems.

[email protected]

Page 2: Proposed Changes & Revisions to the 2017 National Electrical Code©

Proposed New Articles2017 NEC

Article 712 - Direct-Current Microgrids

The current state of energy storage technology, which includes batteries, and the anticipated evolution of energy storage, support the need for a singular set of requirements in the NEC covering such systems.

Article 706 - Energy Storage Systems

The current state of energy storage technology, which includes batteries, and the anticipated evolution of energy storage, support the need for a singular set of requirements in the NEC covering such systems.

Article 691 - Large-Scale Photovoltaic (PV) Electric Supply Stations

1) elimination of AHJ professional risk when assessing compliance of large-scale PV electric supply stations

2) enabling system engineers to use engineering best practices in the design of large-scale PV electric supply stations.

According to the substantiation, the two main drivers for this proposed new article are:

Article 425 - Fixed Resistance and Electrode Industrial Process Heating Equipment

BoilersElectrode BoilersDuct HeatersStrip HeatersImmersion HeatersProcess Air HeatersOther Approved Fixed Electrical Equipment

Heating & Room Air-Conditioning for Personnel Space

Does not apply to:

Source: http://iaeimagazine.org/magazine/2015/04/30/analysis-of-changes-2017-nec/

Proposed New Articles2017 NEC

[email protected]

Page 3: Proposed Changes & Revisions to the 2017 National Electrical Code©

[email protected]

Proposed New Articles2017 NEC

Article 425 - Fixed Resistance and Electrode Industrial Process Heating Equipment

BoilersElectrode BoilersDuct HeatersStrip HeatersImmersion HeatersProcess Air HeatersOther Approved Fixed Electrical Equipment

Heating & Room Air-Conditioning for Personnel Space

Does not apply to:

Proposed New Articles2017 NEC

Page 4: Proposed Changes & Revisions to the 2017 National Electrical Code©

Proposed New Articles2017 NEC

Article 712 - Direct-Current Microgrids

The current state of energy storage technology, which includes batteries, and the anticipated evolution of energy storage, support the need for a singular set of requirements in the NEC covering such systems.

Article 706 - Energy Storage Systems

The current state of energy storage technology, which includes batteries, and the anticipated evolution of energy storage, support the need for a singular set of requirements in the NEC covering such systems.

Article 691 - Large-Scale Photovoltaic (PV) Electric Supply Stations

1) elimination of AHJ professional risk when assessing compliance of large-scale PV electric supply stations

2) enabling system engineers to use engineering best practices in the design of large-scale PV electric supply stations.

According to the substantiation, the two main drivers for this proposed new article are:

Article 425 - Fixed Resistance and Electrode Industrial Process Heating Equipment

BoilersElectrode BoilersDuct HeatersStrip HeatersImmersion HeatersProcess Air HeatersOther Approved Fixed Electrical Equipment

Heating & Room Air-Conditioning for Personnel Space

Does not apply to:

Proposed New Articles2017 NEC

[email protected]

Page 5: Proposed Changes & Revisions to the 2017 National Electrical Code©

Proposed New Articles2017 NEC

Article 712 - Direct-Current Microgrids

The current state of energy storage technology, which includes batteries, and the anticipated evolution of energy storage, support the need for a singular set of requirements in the NEC covering such systems.

Article 712 - Direct-Current Microgrids

The current state of energy storage technology, which includes batteries, and the anticipated evolution of energy storage, support the need for a singular set of requirements in the NEC covering such systems.

Article 706 - Energy Storage Systems

The current state of energy storage technology, which includes batteries, and the anticipated evolution of energy storage, support the need for a singular set of requirements in the NEC covering such systems.

Article 691 - Large-Scale Photovoltaic (PV) Electric Supply Stations

1) elimination of AHJ professional risk when assessing compliance of large-scale PV electric supply stations

2) enabling system engineers to use engineering best practices in the design of large-scale PV electric supply stations.

According to the substantiation, the two main drivers for this proposed new article are:

Article 425 - Fixed Resistance and Electrode Industrial Process Heating Equipment

BoilersElectrode BoilersDuct HeatersStrip HeatersImmersion HeatersProcess Air HeatersOther Approved Fixed Electrical Equipment

Heating & Room Air-Conditioning for Personnel Space

Does not apply to:

Proposed New Articles2017 NEC

[email protected]

Page 6: Proposed Changes & Revisions to the 2017 National Electrical Code©

Proposed New Articles2017 NEC

Article 712 - Direct-Current Microgrids

The current state of energy storage technology, which includes batteries, and the anticipated evolution of energy storage, support the need for a singular set of requirements in the NEC covering such systems.

Article 712 - Direct-Current Microgrids

The current state of energy storage technology, which includes batteries, and the anticipated evolution of energy storage, support the need for a singular set of requirements in the NEC covering such systems.

Article 706 - Energy Storage Systems

The current state of energy storage technology, which includes batteries, and the anticipated evolution of energy storage, support the need for a singular set of requirements in the NEC covering such systems.

Article 691 - Large-Scale Photovoltaic (PV) Electric Supply Stations

1) elimination of AHJ professional risk when assessing compliance of large-scale PV electric supply stations

2) enabling system engineers to use engineering best practices in the design of large-scale PV electric supply stations.

According to the substantiation, the two main drivers for this proposed new article are:

Article 425 - Fixed Resistance and Electrode Industrial Process Heating Equipment

BoilersElectrode BoilersDuct HeatersStrip HeatersImmersion HeatersProcess Air HeatersOther Approved Fixed Electrical Equipment

Heating & Room Air-Conditioning for Personnel Space

Does not apply to:

Proposed New Articles2017 NEC

[email protected]

Page 7: Proposed Changes & Revisions to the 2017 National Electrical Code©

Chapter ONE - General Requirements

2017 NEC

These working space signs would be required to meet the requirements of 110.21(B) for field-applied hazard markings and would need to read as follows:

NEW: 110.26(A)(4) - Working Space About Electrical Equipment - Clear Space Signs

“NOTICE - ELECTRICAL EQUIPMENT WORKING SPACE AND EGRESS AREA - NO OBSTRUCTION OR STORAGE ALLOWED.”

NEW: 110.26(A)(4) - Working Space About Electrical Equipment -Limited AccessAddresses equipment “located in a space with limited access,” such as above a suspended ceiling or in a crawl space.

There are four restrictions: Where equipment is located above a lay-in ceiling Width of the limited access working space Doors or hinged panels being capable of opening a minimum of 90° Space in front of the enclosure

NEW: 110.21(A)(2) - Equipment Marking - Reconditioned EquipmentRequires reconditioned equipment to be makred with the name, trademwark, or other descriptive marking, identifying the organization responsible for reconditioning the electrical equipment. It also requires the date of the reconditioning to be provided as well.

NEW: 110.16(B) - Arc-Flash Hazard Warning - Service EquipmentRequires additional information to be included in the arc-flash hazard warning label specifically addressing service equipment.

And at least one of the following: Available incident energy & corresponding working distance Minimum Arc Rating of Clothing Site-Specific Level of PPE

Nominal System Voltage Arc-Flash Boundaries

Requires Labels to Contain:

NEW: 110.14(D) - Electrical Equipment: Tightening Torque

Findings of a field study presented in 2011, indicated that installers incorrectly tighten electrical terminations at least 75% of the time when not using a torque wrench.

This proposed requirement would make it clear to installers and inspectors that using torque tools is required when a torque value is indicated on electrical equipment, such as a banelboard lug.

Changes to Chapter One: General Requirements

2017 NEC

Source: http://iaeimagazine.org/magazine/2015/04/30/analysis-of-changes-2017-nec/

[email protected]

Page 8: Proposed Changes & Revisions to the 2017 National Electrical Code©

Chapter ONE - General Requirements

2017 NEC

These working space signs would be required to meet the requirements of 110.21(B) for field-applied hazard markings and would need to read as follows:

NEW: 110.26(A)(4) - Working Space About Electrical Equipment - Clear Space Signs

“NOTICE - ELECTRICAL EQUIPMENT WORKING SPACE AND EGRESS AREA - NO OBSTRUCTION OR STORAGE ALLOWED.”

NEW: 110.26(A)(4) - Working Space About Electrical Equipment -Limited AccessAddresses equipment “located in a space with limited access,” such as above a suspended ceiling or in a crawl space.

There are four restrictions: Where equipment is located above a lay-in ceiling Width of the limited access working space Doors or hinged panels being capable of opening a minimum of 90° Space in front of the enclosure

NEW: 110.21(A)(2) - Equipment Marking - Reconditioned EquipmentRequires reconditioned equipment to be makred with the name, trademwark, or other descriptive marking, identifying the organization responsible for reconditioning the electrical equipment. It also requires the date of the reconditioning to be provided as well.

NEW: 110.16(B) - Arc-Flash Hazard Warning - Service EquipmentRequires additional information to be included in the arc-flash hazard warning label specifically addressing service equipment.

And at least one of the following: Available incident energy & corresponding working distance Minimum Arc Rating of Clothing Site-Specific Level of PPE

Nominal System Voltage Arc-Flash Boundaries

Requires Labels to Contain:

NEW: 110.14(D) - Electrical Equipment: Tightening Torque

Findings of a field study presented in 2011, indicated that installers incorrectly tighten electrical terminations at least 75% of the time when not using a torque wrench.

This proposed requirement would make it clear to installers and inspectors that using torque tools is required when a torque value is indicated on electrical equipment, such as a banelboard lug.

Changes to Chapter One: General Requirements

2017 NEC

[email protected]

Page 9: Proposed Changes & Revisions to the 2017 National Electrical Code©

Chapter ONE - General Requirements

2017 NEC

These working space signs would be required to meet the requirements of 110.21(B) for field-applied hazard markings and would need to read as follows:

NEW: 110.26(A)(4) - Working Space About Electrical Equipment - Clear Space Signs

“NOTICE - ELECTRICAL EQUIPMENT WORKING SPACE AND EGRESS AREA - NO OBSTRUCTION OR STORAGE ALLOWED.”

NEW: 110.26(A)(4) - Working Space About Electrical Equipment -Limited AccessAddresses equipment “located in a space with limited access,” such as above a suspended ceiling or in a crawl space.

There are four restrictions: Where equipment is located above a lay-in ceiling Width of the limited access working space Doors or hinged panels being capable of opening a minimum of 90° Space in front of the enclosure

NEW: 110.21(A)(2) - Equipment Marking - Reconditioned EquipmentRequires reconditioned equipment to be makred with the name, trademwark, or other descriptive marking, identifying the organization responsible for reconditioning the electrical equipment. It also requires the date of the reconditioning to be provided as well.

NEW: 110.16(B) - Arc-Flash Hazard Warning - Service EquipmentRequires additional information to be included in the arc-flash hazard warning label specifically addressing service equipment.

And at least one of the following: Available incident energy & corresponding working distance Minimum Arc Rating of Clothing Site-Specific Level of PPE

Nominal System Voltage Arc-Flash Boundaries

Requires Labels to Contain:

NEW: 110.14(D) - Electrical Equipment: Tightening Torque

Findings of a field study presented in 2011, indicated that installers incorrectly tighten electrical terminations at least 75% of the time when not using a torque wrench.

This proposed requirement would make it clear to installers and inspectors that using torque tools is required when a torque value is indicated on electrical equipment, such as a banelboard lug.

Changes to Chapter One: General Requirements

2017 NEC

[email protected]

Page 10: Proposed Changes & Revisions to the 2017 National Electrical Code©

Chapter ONE - General Requirements

2017 NEC

These working space signs would be required to meet the requirements of 110.21(B) for field-applied hazard markings and would need to read as follows:

NEW: 110.26(A)(4) - Working Space About Electrical Equipment - Clear Space Signs

“NOTICE - ELECTRICAL EQUIPMENT WORKING SPACE AND EGRESS AREA - NO OBSTRUCTION OR STORAGE ALLOWED.”

NEW: 110.26(A)(4) - Working Space About Electrical Equipment -Limited AccessAddresses equipment “located in a space with limited access,” such as above a suspended ceiling or in a crawl space.

There are four restrictions: Where equipment is located above a lay-in ceiling Width of the limited access working space Doors or hinged panels being capable of opening a minimum of 90° Space in front of the enclosure

NEW: 110.21(A)(2) - Equipment Marking - Reconditioned EquipmentRequires reconditioned equipment to be makred with the name, trademwark, or other descriptive marking, identifying the organization responsible for reconditioning the electrical equipment. It also requires the date of the reconditioning to be provided as well.

NEW: 110.16(B) - Arc-Flash Hazard Warning - Service EquipmentRequires additional information to be included in the arc-flash hazard warning label specifically addressing service equipment.

And at least one of the following: Available incident energy & corresponding working distance Minimum Arc Rating of Clothing Site-Specific Level of PPE

Nominal System Voltage Arc-Flash Boundaries

Requires Labels to Contain:

NEW: 110.14(D) - Electrical Equipment: Tightening Torque

Findings of a field study presented in 2011, indicated that installers incorrectly tighten electrical terminations at least 75% of the time when not using a torque wrench.

This proposed requirement would make it clear to installers and inspectors that using torque tools is required when a torque value is indicated on electrical equipment, such as a banelboard lug.

Changes to Chapter One: General Requirements

2017 NEC

[email protected]

Page 11: Proposed Changes & Revisions to the 2017 National Electrical Code©

Chapter ONE - General Requirements

2017 NEC

These working space signs would be required to meet the requirements of 110.21(B) for field-applied hazard markings and would need to read as follows:

NEW: 110.26(A)(4) - Working Space About Electrical Equipment - Clear Space Signs

“NOTICE - ELECTRICAL EQUIPMENT WORKING SPACE AND EGRESS AREA - NO OBSTRUCTION OR STORAGE ALLOWED.”

NEW: 110.26(A)(4) - Working Space About Electrical Equipment -Limited AccessAddresses equipment “located in a space with limited access,” such as above a suspended ceiling or in a crawl space.

There are four restrictions: Where equipment is located above a lay-in ceiling Width of the limited access working space Doors or hinged panels being capable of opening a minimum of 90° Space in front of the enclosure

NEW: 110.21(A)(2) - Equipment Marking - Reconditioned EquipmentRequires reconditioned equipment to be makred with the name, trademwark, or other descriptive marking, identifying the organization responsible for reconditioning the electrical equipment. It also requires the date of the reconditioning to be provided as well.

NEW: 110.16(B) - Arc-Flash Hazard Warning - Service EquipmentRequires additional information to be included in the arc-flash hazard warning label specifically addressing service equipment.

And at least one of the following: Available incident energy & corresponding working distance Minimum Arc Rating of Clothing Site-Specific Level of PPE

Nominal System Voltage Arc-Flash Boundaries

Requires Labels to Contain:

NEW: 110.14(D) - Electrical Equipment: Tightening Torque

Findings of a field study presented in 2011, indicated that installers incorrectly tighten electrical terminations at least 75% of the time when not using a torque wrench.

This proposed requirement would make it clear to installers and inspectors that using torque tools is required when a torque value is indicated on electrical equipment, such as a banelboard lug.

Changes to Chapter One: General Requirements

2017 NEC

[email protected]

Page 12: Proposed Changes & Revisions to the 2017 National Electrical Code©

Chapter ONE - General Requirements

2017 NEC

These working space signs would be required to meet the requirements of 110.21(B) for field-applied hazard markings and would need to read as follows:

NEW: 110.26(A)(4) - Working Space About Electrical Equipment - Clear Space Signs

“NOTICE - ELECTRICAL EQUIPMENT WORKING SPACE AND EGRESS AREA - NO OBSTRUCTION OR STORAGE ALLOWED.”

NEW: 110.26(A)(4) - Working Space About Electrical Equipment -Limited AccessAddresses equipment “located in a space with limited access,” such as above a suspended ceiling or in a crawl space.

There are four restrictions: Where equipment is located above a lay-in ceiling Width of the limited access working space Doors or hinged panels being capable of opening a minimum of 90° Space in front of the enclosure

NEW: 110.21(A)(2) - Equipment Marking - Reconditioned EquipmentRequires reconditioned equipment to be makred with the name, trademwark, or other descriptive marking, identifying the organization responsible for reconditioning the electrical equipment. It also requires the date of the reconditioning to be provided as well.

NEW: 110.16(B) - Arc-Flash Hazard Warning - Service EquipmentRequires additional information to be included in the arc-flash hazard warning label specifically addressing service equipment.

And at least one of the following: Available incident energy & corresponding working distance Minimum Arc Rating of Clothing Site-Specific Level of PPE

Nominal System Voltage Arc-Flash Boundaries

Requires Labels to Contain:

NEW: 110.14(D) - Electrical Equipment: Tightening Torque

Findings of a field study presented in 2011, indicated that installers incorrectly tighten electrical terminations at least 75% of the time when not using a torque wrench.

This proposed requirement would make it clear to installers and inspectors that using torque tools is required when a torque value is indicated on electrical equipment, such as a banelboard lug.

Changes to Chapter One: General Requirements

2017 NEC

[email protected]

Page 13: Proposed Changes & Revisions to the 2017 National Electrical Code©

Chapter TWO - Wiring and Protection

2017 NEC

NEW: 250.52(B)(3) - Not Permitted For Use As Grounding ElectrodesDecisive language was proposed that would prohibit the structures and/or structural reinforcing steel of an in-ground swimming pool described at 680.26(B)(1) and (B)(2) from being used as a grounding electrode for a building or structure.

3.0m (10ft)or more

REVISION: 250.52(A)(2) - Grounding Electrodes - Metal In-Ground Support Structure(s)

Currently, two conditions exist in the 2014 NEC in order for a metal frame of a building or structure to qualify as a grounding electrode. The proposed text for the 2017 NEC leaves only one condition:

One or more metal in-ground support structure(s) in direct contact with the earth vertically for 3.0m (10ft) or more, with or without concrete encasement.

REVISION: 250.30(A)(4) - Grounding Separately Derived AC Systems - Grounding Electrode System

The new proposed text at 250.30(A)(4) will allow any of the building or structure grounding electrodes described at 250.52(A) to be used as the grounding electrode for the separately derived system without an order of preference.

NEW: 240.67 - Arc Energy Reduction (Fuses)The proposed requirements of 240.67 are based upon the requirements in 240.87 for circuit breakers, but modified to work with fusible switches. This arc energy reduction requirement for fusible switches has a proposed future effective date of January 1, 2020.

REVISION: 230.29 - Overhead Service Conductors - Supports Over BuildingsRevisions to 230.29 will require metal support racks or structures to be bonded by means of a bonding jumper and listed connector to the grounded overhead service conductor for grounded systems.

This proposed language will provide installers clear bonding provisions and the AHJ a clear requirement for enforcement.

NEW: 210.71 - Meeting Room ReceptaclesNew requirements for a minimum number of nonlocking-type 125-volt, 15-and 20-ampere receptacles to be installed in nondwelling unit meeting rooms have been proposed.

This proposal addresses the inherent concerns relating to inadequate access to electrial power in meeting rooms.

REVISION: 210.12(A) - Whole-House AFCI ProtectionThe proposed revision to 210.12(A) would require arc-fault circuit-interrupter (AFCI) protection for all 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets or devices installed in dwelling units.

NEW: 210.11(C)(4) - Dwelling Units - Garage Branch CircuitsA new requirement has been proposed to require at least one 20-ampere rated branch circuit to supply dwelling unit garage 125-volt receptable outlet(s).

Many appliances and tools used in dwelling unit garages are rated at 12-16-amperes or higher and demand at least a 20-ampere rated branch circuit.

NEW: 210.8(B)(2)(A) - SPGFCI ProtectionThe requirements in this section have been expanded to recognize the fact that shock hazards are not limited to 15- and 20-ampere, 125-volt circuits at nondwelling unit locations.

REVISION: 210.8(A) - GFCI Protection: Dwelling Units

All 250-volt, single-phase, 15-and 20-ampere receptables installed in the locations specificed in 210.8(A), present a shock hazard and should be included in the GFCI protection in dwelling units.

Changes to Chapter Two: Wiring and Protection

2017 NEC

Source: http://iaeimagazine.org/magazine/2015/04/30/analysis-of-changes-2017-nec/

[email protected]

Page 14: Proposed Changes & Revisions to the 2017 National Electrical Code©

Chapter TWO - Wiring and Protection

2017 NEC

NEW: 250.52(B)(3) - Not Permitted For Use As Grounding ElectrodesDecisive language was proposed that would prohibit the structures and/or structural reinforcing steel of an in-ground swimming pool described at 680.26(B)(1) and (B)(2) from being used as a grounding electrode for a building or structure.

3.0m (10ft)or more

REVISION: 250.52(A)(2) - Grounding Electrodes - Metal In-Ground Support Structure(s)

Currently, two conditions exist in the 2014 NEC in order for a metal frame of a building or structure to qualify as a grounding electrode. The proposed text for the 2017 NEC leaves only one condition:

One or more metal in-ground support structure(s) in direct contact with the earth vertically for 3.0m (10ft) or more, with or without concrete encasement.

REVISION: 250.30(A)(4) - Grounding Separately Derived AC Systems - Grounding Electrode System

The new proposed text at 250.30(A)(4) will allow any of the building or structure grounding electrodes described at 250.52(A) to be used as the grounding electrode for the separately derived system without an order of preference.

NEW: 240.67 - Arc Energy Reduction (Fuses)The proposed requirements of 240.67 are based upon the requirements in 240.87 for circuit breakers, but modified to work with fusible switches. This arc energy reduction requirement for fusible switches has a proposed future effective date of January 1, 2020.

REVISION: 230.29 - Overhead Service Conductors - Supports Over BuildingsRevisions to 230.29 will require metal support racks or structures to be bonded by means of a bonding jumper and listed connector to the grounded overhead service conductor for grounded systems.

This proposed language will provide installers clear bonding provisions and the AHJ a clear requirement for enforcement.

NEW: 210.71 - Meeting Room ReceptaclesNew requirements for a minimum number of nonlocking-type 125-volt, 15-and 20-ampere receptacles to be installed in nondwelling unit meeting rooms have been proposed.

This proposal addresses the inherent concerns relating to inadequate access to electrial power in meeting rooms.

REVISION: 210.12(A) - Whole-House AFCI ProtectionThe proposed revision to 210.12(A) would require arc-fault circuit-interrupter (AFCI) protection for all 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets or devices installed in dwelling units.

NEW: 210.11(C)(4) - Dwelling Units - Garage Branch CircuitsA new requirement has been proposed to require at least one 20-ampere rated branch circuit to supply dwelling unit garage 125-volt receptable outlet(s).

Many appliances and tools used in dwelling unit garages are rated at 12-16-amperes or higher and demand at least a 20-ampere rated branch circuit.

NEW: 210.8(B)(2)(A) - SPGFCI ProtectionThe requirements in this section have been expanded to recognize the fact that shock hazards are not limited to 15- and 20-ampere, 125-volt circuits at nondwelling unit locations.

REVISION: 210.8(A) - GFCI Protection: Dwelling Units

All 250-volt, single-phase, 15-and 20-ampere receptables installed in the locations specificed in 210.8(A), present a shock hazard and should be included in the GFCI protection in dwelling units.

Changes to Chapter Two: Wiring and Protection

2017 NEC

[email protected]

Page 15: Proposed Changes & Revisions to the 2017 National Electrical Code©

Chapter TWO - Wiring and Protection

2017 NEC

NEW: 250.52(B)(3) - Not Permitted For Use As Grounding ElectrodesDecisive language was proposed that would prohibit the structures and/or structural reinforcing steel of an in-ground swimming pool described at 680.26(B)(1) and (B)(2) from being used as a grounding electrode for a building or structure.

3.0m (10ft)or more

REVISION: 250.52(A)(2) - Grounding Electrodes - Metal In-Ground Support Structure(s)

Currently, two conditions exist in the 2014 NEC in order for a metal frame of a building or structure to qualify as a grounding electrode. The proposed text for the 2017 NEC leaves only one condition:

One or more metal in-ground support structure(s) in direct contact with the earth vertically for 3.0m (10ft) or more, with or without concrete encasement.

REVISION: 250.30(A)(4) - Grounding Separately Derived AC Systems - Grounding Electrode System

The new proposed text at 250.30(A)(4) will allow any of the building or structure grounding electrodes described at 250.52(A) to be used as the grounding electrode for the separately derived system without an order of preference.

NEW: 240.67 - Arc Energy Reduction (Fuses)The proposed requirements of 240.67 are based upon the requirements in 240.87 for circuit breakers, but modified to work with fusible switches. This arc energy reduction requirement for fusible switches has a proposed future effective date of January 1, 2020.

REVISION: 230.29 - Overhead Service Conductors - Supports Over BuildingsRevisions to 230.29 will require metal support racks or structures to be bonded by means of a bonding jumper and listed connector to the grounded overhead service conductor for grounded systems.

This proposed language will provide installers clear bonding provisions and the AHJ a clear requirement for enforcement.

NEW: 210.71 - Meeting Room ReceptaclesNew requirements for a minimum number of nonlocking-type 125-volt, 15-and 20-ampere receptacles to be installed in nondwelling unit meeting rooms have been proposed.

This proposal addresses the inherent concerns relating to inadequate access to electrial power in meeting rooms.

REVISION: 210.12(A) - Whole-House AFCI ProtectionThe proposed revision to 210.12(A) would require arc-fault circuit-interrupter (AFCI) protection for all 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets or devices installed in dwelling units.

NEW: 210.11(C)(4) - Dwelling Units - Garage Branch CircuitsA new requirement has been proposed to require at least one 20-ampere rated branch circuit to supply dwelling unit garage 125-volt receptable outlet(s).

Many appliances and tools used in dwelling unit garages are rated at 12-16-amperes or higher and demand at least a 20-ampere rated branch circuit.

NEW: 210.8(B)(2)(A) - SPGFCI ProtectionThe requirements in this section have been expanded to recognize the fact that shock hazards are not limited to 15- and 20-ampere, 125-volt circuits at nondwelling unit locations.

REVISION: 210.8(A) - GFCI Protection: Dwelling Units

All 250-volt, single-phase, 15-and 20-ampere receptables installed in the locations specificed in 210.8(A), present a shock hazard and should be included in the GFCI protection in dwelling units.

Changes to Chapter Two: Wiring and Protection

2017 NEC

[email protected]

Page 16: Proposed Changes & Revisions to the 2017 National Electrical Code©

Chapter TWO - Wiring and Protection

2017 NEC

NEW: 250.52(B)(3) - Not Permitted For Use As Grounding ElectrodesDecisive language was proposed that would prohibit the structures and/or structural reinforcing steel of an in-ground swimming pool described at 680.26(B)(1) and (B)(2) from being used as a grounding electrode for a building or structure.

3.0m (10ft)or more

REVISION: 250.52(A)(2) - Grounding Electrodes - Metal In-Ground Support Structure(s)

Currently, two conditions exist in the 2014 NEC in order for a metal frame of a building or structure to qualify as a grounding electrode. The proposed text for the 2017 NEC leaves only one condition:

One or more metal in-ground support structure(s) in direct contact with the earth vertically for 3.0m (10ft) or more, with or without concrete encasement.

REVISION: 250.30(A)(4) - Grounding Separately Derived AC Systems - Grounding Electrode System

The new proposed text at 250.30(A)(4) will allow any of the building or structure grounding electrodes described at 250.52(A) to be used as the grounding electrode for the separately derived system without an order of preference.

NEW: 240.67 - Arc Energy Reduction (Fuses)The proposed requirements of 240.67 are based upon the requirements in 240.87 for circuit breakers, but modified to work with fusible switches. This arc energy reduction requirement for fusible switches has a proposed future effective date of January 1, 2020.

REVISION: 230.29 - Overhead Service Conductors - Supports Over BuildingsRevisions to 230.29 will require metal support racks or structures to be bonded by means of a bonding jumper and listed connector to the grounded overhead service conductor for grounded systems.

This proposed language will provide installers clear bonding provisions and the AHJ a clear requirement for enforcement.

NEW: 210.71 - Meeting Room ReceptaclesNew requirements for a minimum number of nonlocking-type 125-volt, 15-and 20-ampere receptacles to be installed in nondwelling unit meeting rooms have been proposed.

This proposal addresses the inherent concerns relating to inadequate access to electrial power in meeting rooms.

REVISION: 210.12(A) - Whole-House AFCI ProtectionThe proposed revision to 210.12(A) would require arc-fault circuit-interrupter (AFCI) protection for all 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets or devices installed in dwelling units.

NEW: 210.11(C)(4) - Dwelling Units - Garage Branch CircuitsA new requirement has been proposed to require at least one 20-ampere rated branch circuit to supply dwelling unit garage 125-volt receptable outlet(s).

Many appliances and tools used in dwelling unit garages are rated at 12-16-amperes or higher and demand at least a 20-ampere rated branch circuit.

NEW: 210.8(B)(2)(A) - SPGFCI ProtectionThe requirements in this section have been expanded to recognize the fact that shock hazards are not limited to 15- and 20-ampere, 125-volt circuits at nondwelling unit locations.

REVISION: 210.8(A) - GFCI Protection: Dwelling Units

All 250-volt, single-phase, 15-and 20-ampere receptables installed in the locations specificed in 210.8(A), present a shock hazard and should be included in the GFCI protection in dwelling units.

Changes to Chapter Two: Wiring and Protection

2017 NEC

[email protected]

Page 17: Proposed Changes & Revisions to the 2017 National Electrical Code©

Chapter TWO - Wiring and Protection

2017 NEC

NEW: 250.52(B)(3) - Not Permitted For Use As Grounding ElectrodesDecisive language was proposed that would prohibit the structures and/or structural reinforcing steel of an in-ground swimming pool described at 680.26(B)(1) and (B)(2) from being used as a grounding electrode for a building or structure.

3.0m (10ft)or more

REVISION: 250.52(A)(2) - Grounding Electrodes - Metal In-Ground Support Structure(s)

Currently, two conditions exist in the 2014 NEC in order for a metal frame of a building or structure to qualify as a grounding electrode. The proposed text for the 2017 NEC leaves only one condition:

One or more metal in-ground support structure(s) in direct contact with the earth vertically for 3.0m (10ft) or more, with or without concrete encasement.

REVISION: 250.30(A)(4) - Grounding Separately Derived AC Systems - Grounding Electrode System

The new proposed text at 250.30(A)(4) will allow any of the building or structure grounding electrodes described at 250.52(A) to be used as the grounding electrode for the separately derived system without an order of preference.

NEW: 240.67 - Arc Energy Reduction (Fuses)The proposed requirements of 240.67 are based upon the requirements in 240.87 for circuit breakers, but modified to work with fusible switches. This arc energy reduction requirement for fusible switches has a proposed future effective date of January 1, 2020.

REVISION: 230.29 - Overhead Service Conductors - Supports Over BuildingsRevisions to 230.29 will require metal support racks or structures to be bonded by means of a bonding jumper and listed connector to the grounded overhead service conductor for grounded systems.

This proposed language will provide installers clear bonding provisions and the AHJ a clear requirement for enforcement.

NEW: 210.71 - Meeting Room ReceptaclesNew requirements for a minimum number of nonlocking-type 125-volt, 15-and 20-ampere receptacles to be installed in nondwelling unit meeting rooms have been proposed.

This proposal addresses the inherent concerns relating to inadequate access to electrial power in meeting rooms.

REVISION: 210.12(A) - Whole-House AFCI ProtectionThe proposed revision to 210.12(A) would require arc-fault circuit-interrupter (AFCI) protection for all 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets or devices installed in dwelling units.

NEW: 210.11(C)(4) - Dwelling Units - Garage Branch CircuitsA new requirement has been proposed to require at least one 20-ampere rated branch circuit to supply dwelling unit garage 125-volt receptable outlet(s).

Many appliances and tools used in dwelling unit garages are rated at 12-16-amperes or higher and demand at least a 20-ampere rated branch circuit.

NEW: 210.8(B)(2)(A) - SPGFCI ProtectionThe requirements in this section have been expanded to recognize the fact that shock hazards are not limited to 15- and 20-ampere, 125-volt circuits at nondwelling unit locations.

REVISION: 210.8(A) - GFCI Protection: Dwelling Units

All 250-volt, single-phase, 15-and 20-ampere receptables installed in the locations specificed in 210.8(A), present a shock hazard and should be included in the GFCI protection in dwelling units.

Changes to Chapter Two: Wiring and Protection

2017 NEC

[email protected]

Page 18: Proposed Changes & Revisions to the 2017 National Electrical Code©

Chapter TWO - Wiring and Protection

2017 NEC

NEW: 250.52(B)(3) - Not Permitted For Use As Grounding ElectrodesDecisive language was proposed that would prohibit the structures and/or structural reinforcing steel of an in-ground swimming pool described at 680.26(B)(1) and (B)(2) from being used as a grounding electrode for a building or structure.

3.0m (10ft)or more

REVISION: 250.52(A)(2) - Grounding Electrodes - Metal In-Ground Support Structure(s)

Currently, two conditions exist in the 2014 NEC in order for a metal frame of a building or structure to qualify as a grounding electrode. The proposed text for the 2017 NEC leaves only one condition:

One or more metal in-ground support structure(s) in direct contact with the earth vertically for 3.0m (10ft) or more, with or without concrete encasement.

REVISION: 250.30(A)(4) - Grounding Separately Derived AC Systems - Grounding Electrode System

The new proposed text at 250.30(A)(4) will allow any of the building or structure grounding electrodes described at 250.52(A) to be used as the grounding electrode for the separately derived system without an order of preference.

NEW: 240.67 - Arc Energy Reduction (Fuses)The proposed requirements of 240.67 are based upon the requirements in 240.87 for circuit breakers, but modified to work with fusible switches. This arc energy reduction requirement for fusible switches has a proposed future effective date of January 1, 2020.

REVISION: 230.29 - Overhead Service Conductors - Supports Over BuildingsRevisions to 230.29 will require metal support racks or structures to be bonded by means of a bonding jumper and listed connector to the grounded overhead service conductor for grounded systems.

This proposed language will provide installers clear bonding provisions and the AHJ a clear requirement for enforcement.

NEW: 210.71 - Meeting Room ReceptaclesNew requirements for a minimum number of nonlocking-type 125-volt, 15-and 20-ampere receptacles to be installed in nondwelling unit meeting rooms have been proposed.

This proposal addresses the inherent concerns relating to inadequate access to electrial power in meeting rooms.

REVISION: 210.12(A) - Whole-House AFCI ProtectionThe proposed revision to 210.12(A) would require arc-fault circuit-interrupter (AFCI) protection for all 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets or devices installed in dwelling units.

NEW: 210.11(C)(4) - Dwelling Units - Garage Branch CircuitsA new requirement has been proposed to require at least one 20-ampere rated branch circuit to supply dwelling unit garage 125-volt receptable outlet(s).

Many appliances and tools used in dwelling unit garages are rated at 12-16-amperes or higher and demand at least a 20-ampere rated branch circuit.

NEW: 210.8(B)(2)(A) - SPGFCI ProtectionThe requirements in this section have been expanded to recognize the fact that shock hazards are not limited to 15- and 20-ampere, 125-volt circuits at nondwelling unit locations.

REVISION: 210.8(A) - GFCI Protection: Dwelling Units

All 250-volt, single-phase, 15-and 20-ampere receptables installed in the locations specificed in 210.8(A), present a shock hazard and should be included in the GFCI protection in dwelling units.

Changes to Chapter Two: Wiring and Protection

2017 NEC

[email protected]

Page 19: Proposed Changes & Revisions to the 2017 National Electrical Code©

Chapter TWO - Wiring and Protection

2017 NEC

NEW: 250.52(B)(3) - Not Permitted For Use As Grounding ElectrodesDecisive language was proposed that would prohibit the structures and/or structural reinforcing steel of an in-ground swimming pool described at 680.26(B)(1) and (B)(2) from being used as a grounding electrode for a building or structure.

3.0m (10ft)or more

REVISION: 250.52(A)(2) - Grounding Electrodes - Metal In-Ground Support Structure(s)

Currently, two conditions exist in the 2014 NEC in order for a metal frame of a building or structure to qualify as a grounding electrode. The proposed text for the 2017 NEC leaves only one condition:

One or more metal in-ground support structure(s) in direct contact with the earth vertically for 3.0m (10ft) or more, with or without concrete encasement.

REVISION: 250.30(A)(4) - Grounding Separately Derived AC Systems - Grounding Electrode System

The new proposed text at 250.30(A)(4) will allow any of the building or structure grounding electrodes described at 250.52(A) to be used as the grounding electrode for the separately derived system without an order of preference.

NEW: 240.67 - Arc Energy Reduction (Fuses)The proposed requirements of 240.67 are based upon the requirements in 240.87 for circuit breakers, but modified to work with fusible switches. This arc energy reduction requirement for fusible switches has a proposed future effective date of January 1, 2020.

REVISION: 230.29 - Overhead Service Conductors - Supports Over BuildingsRevisions to 230.29 will require metal support racks or structures to be bonded by means of a bonding jumper and listed connector to the grounded overhead service conductor for grounded systems.

This proposed language will provide installers clear bonding provisions and the AHJ a clear requirement for enforcement.

NEW: 210.71 - Meeting Room ReceptaclesNew requirements for a minimum number of nonlocking-type 125-volt, 15-and 20-ampere receptacles to be installed in nondwelling unit meeting rooms have been proposed.

This proposal addresses the inherent concerns relating to inadequate access to electrial power in meeting rooms.

REVISION: 210.12(A) - Whole-House AFCI ProtectionThe proposed revision to 210.12(A) would require arc-fault circuit-interrupter (AFCI) protection for all 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets or devices installed in dwelling units.

NEW: 210.11(C)(4) - Dwelling Units - Garage Branch CircuitsA new requirement has been proposed to require at least one 20-ampere rated branch circuit to supply dwelling unit garage 125-volt receptable outlet(s).

Many appliances and tools used in dwelling unit garages are rated at 12-16-amperes or higher and demand at least a 20-ampere rated branch circuit.

NEW: 210.8(B)(2)(A) - SPGFCI ProtectionThe requirements in this section have been expanded to recognize the fact that shock hazards are not limited to 15- and 20-ampere, 125-volt circuits at nondwelling unit locations.

REVISION: 210.8(A) - GFCI Protection: Dwelling Units

All 250-volt, single-phase, 15-and 20-ampere receptables installed in the locations specificed in 210.8(A), present a shock hazard and should be included in the GFCI protection in dwelling units.

Changes to Chapter Two: Wiring and Protection

2017 NEC

[email protected]

Page 20: Proposed Changes & Revisions to the 2017 National Electrical Code©

Chapter TWO - Wiring and Protection

2017 NEC

NEW: 250.52(B)(3) - Not Permitted For Use As Grounding ElectrodesDecisive language was proposed that would prohibit the structures and/or structural reinforcing steel of an in-ground swimming pool described at 680.26(B)(1) and (B)(2) from being used as a grounding electrode for a building or structure.

3.0m (10ft)or more

REVISION: 250.52(A)(2) - Grounding Electrodes - Metal In-Ground Support Structure(s)

Currently, two conditions exist in the 2014 NEC in order for a metal frame of a building or structure to qualify as a grounding electrode. The proposed text for the 2017 NEC leaves only one condition:

One or more metal in-ground support structure(s) in direct contact with the earth vertically for 3.0m (10ft) or more, with or without concrete encasement.

REVISION: 250.30(A)(4) - Grounding Separately Derived AC Systems - Grounding Electrode System

The new proposed text at 250.30(A)(4) will allow any of the building or structure grounding electrodes described at 250.52(A) to be used as the grounding electrode for the separately derived system without an order of preference.

NEW: 240.67 - Arc Energy Reduction (Fuses)The proposed requirements of 240.67 are based upon the requirements in 240.87 for circuit breakers, but modified to work with fusible switches. This arc energy reduction requirement for fusible switches has a proposed future effective date of January 1, 2020.

REVISION: 230.29 - Overhead Service Conductors - Supports Over BuildingsRevisions to 230.29 will require metal support racks or structures to be bonded by means of a bonding jumper and listed connector to the grounded overhead service conductor for grounded systems.

This proposed language will provide installers clear bonding provisions and the AHJ a clear requirement for enforcement.

NEW: 210.71 - Meeting Room ReceptaclesNew requirements for a minimum number of nonlocking-type 125-volt, 15-and 20-ampere receptacles to be installed in nondwelling unit meeting rooms have been proposed.

This proposal addresses the inherent concerns relating to inadequate access to electrial power in meeting rooms.

REVISION: 210.12(A) - Whole-House AFCI ProtectionThe proposed revision to 210.12(A) would require arc-fault circuit-interrupter (AFCI) protection for all 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets or devices installed in dwelling units.

NEW: 210.11(C)(4) - Dwelling Units - Garage Branch CircuitsA new requirement has been proposed to require at least one 20-ampere rated branch circuit to supply dwelling unit garage 125-volt receptable outlet(s).

Many appliances and tools used in dwelling unit garages are rated at 12-16-amperes or higher and demand at least a 20-ampere rated branch circuit.

NEW: 210.8(B)(2)(A) - SPGFCI ProtectionThe requirements in this section have been expanded to recognize the fact that shock hazards are not limited to 15- and 20-ampere, 125-volt circuits at nondwelling unit locations.

REVISION: 210.8(A) - GFCI Protection: Dwelling Units

All 250-volt, single-phase, 15-and 20-ampere receptables installed in the locations specificed in 210.8(A), present a shock hazard and should be included in the GFCI protection in dwelling units.

Changes to Chapter Two: Wiring and Protection

2017 NEC

[email protected]

Page 21: Proposed Changes & Revisions to the 2017 National Electrical Code©

Chapter TWO - Wiring and Protection

2017 NEC

NEW: 250.52(B)(3) - Not Permitted For Use As Grounding ElectrodesDecisive language was proposed that would prohibit the structures and/or structural reinforcing steel of an in-ground swimming pool described at 680.26(B)(1) and (B)(2) from being used as a grounding electrode for a building or structure.

3.0m (10ft)or more

REVISION: 250.52(A)(2) - Grounding Electrodes - Metal In-Ground Support Structure(s)

Currently, two conditions exist in the 2014 NEC in order for a metal frame of a building or structure to qualify as a grounding electrode. The proposed text for the 2017 NEC leaves only one condition:

One or more metal in-ground support structure(s) in direct contact with the earth vertically for 3.0m (10ft) or more, with or without concrete encasement.

REVISION: 250.30(A)(4) - Grounding Separately Derived AC Systems - Grounding Electrode System

The new proposed text at 250.30(A)(4) will allow any of the building or structure grounding electrodes described at 250.52(A) to be used as the grounding electrode for the separately derived system without an order of preference.

NEW: 240.67 - Arc Energy Reduction (Fuses)The proposed requirements of 240.67 are based upon the requirements in 240.87 for circuit breakers, but modified to work with fusible switches. This arc energy reduction requirement for fusible switches has a proposed future effective date of January 1, 2020.

REVISION: 230.29 - Overhead Service Conductors - Supports Over BuildingsRevisions to 230.29 will require metal support racks or structures to be bonded by means of a bonding jumper and listed connector to the grounded overhead service conductor for grounded systems.

This proposed language will provide installers clear bonding provisions and the AHJ a clear requirement for enforcement.

NEW: 210.71 - Meeting Room ReceptaclesNew requirements for a minimum number of nonlocking-type 125-volt, 15-and 20-ampere receptacles to be installed in nondwelling unit meeting rooms have been proposed.

This proposal addresses the inherent concerns relating to inadequate access to electrial power in meeting rooms.

REVISION: 210.12(A) - Whole-House AFCI ProtectionThe proposed revision to 210.12(A) would require arc-fault circuit-interrupter (AFCI) protection for all 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets or devices installed in dwelling units.

NEW: 210.11(C)(4) - Dwelling Units - Garage Branch CircuitsA new requirement has been proposed to require at least one 20-ampere rated branch circuit to supply dwelling unit garage 125-volt receptable outlet(s).

Many appliances and tools used in dwelling unit garages are rated at 12-16-amperes or higher and demand at least a 20-ampere rated branch circuit.

NEW: 210.8(B)(2)(A) - SPGFCI ProtectionThe requirements in this section have been expanded to recognize the fact that shock hazards are not limited to 15- and 20-ampere, 125-volt circuits at nondwelling unit locations.

REVISION: 210.8(A) - GFCI Protection: Dwelling Units

All 250-volt, single-phase, 15-and 20-ampere receptables installed in the locations specificed in 210.8(A), present a shock hazard and should be included in the GFCI protection in dwelling units.

Changes to Chapter Two: Wiring and Protection

2017 NEC

Source: http://iaeimagazine.org/magazine/2015/04/30/analysis-of-changes-2017-nec/

[email protected]

Page 22: Proposed Changes & Revisions to the 2017 National Electrical Code©

Chapter TWO - Wiring and Protection

2017 NEC

NEW: 250.52(B)(3) - Not Permitted For Use As Grounding ElectrodesDecisive language was proposed that would prohibit the structures and/or structural reinforcing steel of an in-ground swimming pool described at 680.26(B)(1) and (B)(2) from being used as a grounding electrode for a building or structure.

3.0m (10ft)or more

REVISION: 250.52(A)(2) - Grounding Electrodes - Metal In-Ground Support Structure(s)

Currently, two conditions exist in the 2014 NEC in order for a metal frame of a building or structure to qualify as a grounding electrode. The proposed text for the 2017 NEC leaves only one condition:

One or more metal in-ground support structure(s) in direct contact with the earth vertically for 3.0m (10ft) or more, with or without concrete encasement.

REVISION: 250.30(A)(4) - Grounding Separately Derived AC Systems - Grounding Electrode System

The new proposed text at 250.30(A)(4) will allow any of the building or structure grounding electrodes described at 250.52(A) to be used as the grounding electrode for the separately derived system without an order of preference.

NEW: 240.67 - Arc Energy Reduction (Fuses)The proposed requirements of 240.67 are based upon the requirements in 240.87 for circuit breakers, but modified to work with fusible switches. This arc energy reduction requirement for fusible switches has a proposed future effective date of January 1, 2020.

REVISION: 230.29 - Overhead Service Conductors - Supports Over BuildingsRevisions to 230.29 will require metal support racks or structures to be bonded by means of a bonding jumper and listed connector to the grounded overhead service conductor for grounded systems.

This proposed language will provide installers clear bonding provisions and the AHJ a clear requirement for enforcement.

NEW: 210.71 - Meeting Room ReceptaclesNew requirements for a minimum number of nonlocking-type 125-volt, 15-and 20-ampere receptacles to be installed in nondwelling unit meeting rooms have been proposed.

This proposal addresses the inherent concerns relating to inadequate access to electrial power in meeting rooms.

REVISION: 210.12(A) - Whole-House AFCI ProtectionThe proposed revision to 210.12(A) would require arc-fault circuit-interrupter (AFCI) protection for all 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets or devices installed in dwelling units.

NEW: 210.11(C)(4) - Dwelling Units - Garage Branch CircuitsA new requirement has been proposed to require at least one 20-ampere rated branch circuit to supply dwelling unit garage 125-volt receptable outlet(s).

Many appliances and tools used in dwelling unit garages are rated at 12-16-amperes or higher and demand at least a 20-ampere rated branch circuit.

NEW: 210.8(B)(2)(A) - SPGFCI ProtectionThe requirements in this section have been expanded to recognize the fact that shock hazards are not limited to 15- and 20-ampere, 125-volt circuits at nondwelling unit locations.

REVISION: 210.8(A) - GFCI Protection: Dwelling Units

All 250-volt, single-phase, 15-and 20-ampere receptables installed in the locations specificed in 210.8(A), present a shock hazard and should be included in the GFCI protection in dwelling units.

Changes to Chapter Two: Wiring and Protection

2017 NEC

[email protected]

Page 23: Proposed Changes & Revisions to the 2017 National Electrical Code©

Chapter TWO - Wiring and Protection

2017 NEC

NEW: 250.52(B)(3) - Not Permitted For Use As Grounding ElectrodesDecisive language was proposed that would prohibit the structures and/or structural reinforcing steel of an in-ground swimming pool described at 680.26(B)(1) and (B)(2) from being used as a grounding electrode for a building or structure.

3.0m (10ft)or more

REVISION: 250.52(A)(2) - Grounding Electrodes - Metal In-Ground Support Structure(s)

Currently, two conditions exist in the 2014 NEC in order for a metal frame of a building or structure to qualify as a grounding electrode. The proposed text for the 2017 NEC leaves only one condition:

One or more metal in-ground support structure(s) in direct contact with the earth vertically for 3.0m (10ft) or more, with or without concrete encasement.

REVISION: 250.30(A)(4) - Grounding Separately Derived AC Systems - Grounding Electrode System

The new proposed text at 250.30(A)(4) will allow any of the building or structure grounding electrodes described at 250.52(A) to be used as the grounding electrode for the separately derived system without an order of preference.

NEW: 240.67 - Arc Energy Reduction (Fuses)The proposed requirements of 240.67 are based upon the requirements in 240.87 for circuit breakers, but modified to work with fusible switches. This arc energy reduction requirement for fusible switches has a proposed future effective date of January 1, 2020.

REVISION: 230.29 - Overhead Service Conductors - Supports Over BuildingsRevisions to 230.29 will require metal support racks or structures to be bonded by means of a bonding jumper and listed connector to the grounded overhead service conductor for grounded systems.

This proposed language will provide installers clear bonding provisions and the AHJ a clear requirement for enforcement.

NEW: 210.71 - Meeting Room ReceptaclesNew requirements for a minimum number of nonlocking-type 125-volt, 15-and 20-ampere receptacles to be installed in nondwelling unit meeting rooms have been proposed.

This proposal addresses the inherent concerns relating to inadequate access to electrial power in meeting rooms.

REVISION: 210.12(A) - Whole-House AFCI ProtectionThe proposed revision to 210.12(A) would require arc-fault circuit-interrupter (AFCI) protection for all 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets or devices installed in dwelling units.

NEW: 210.11(C)(4) - Dwelling Units - Garage Branch CircuitsA new requirement has been proposed to require at least one 20-ampere rated branch circuit to supply dwelling unit garage 125-volt receptable outlet(s).

Many appliances and tools used in dwelling unit garages are rated at 12-16-amperes or higher and demand at least a 20-ampere rated branch circuit.

NEW: 210.8(B)(2)(A) - SPGFCI ProtectionThe requirements in this section have been expanded to recognize the fact that shock hazards are not limited to 15- and 20-ampere, 125-volt circuits at nondwelling unit locations.

REVISION: 210.8(A) - GFCI Protection: Dwelling Units

All 250-volt, single-phase, 15-and 20-ampere receptables installed in the locations specificed in 210.8(A), present a shock hazard and should be included in the GFCI protection in dwelling units.

Changes to Chapter Two: Wiring and Protection

2017 NEC

[email protected]

Page 24: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Three: Wiring Methods

2017 NEC

Source: http://iaeimagazine.org/magazine/2015/04/30/analysis-of-changes-2017-nec/

Chapter THREE - Wiring Methods

2017 NEC

NEW: 366.20 - Auxiliary Gutters - Conductors Connected in ParallelSpecific language requires parallel conductors to be installed in groups consisting of not more than one conductor per phase, neutral, or grounded conductor to prevent current imbalance in the paralleled conductors due to inductive reactance.

The same parallel provisions were also proposed for metal wireways at 376.20 and for nonmetallic wireways at 378.20.

REVISION: 338.10(B)(4) - Uses Permitted - Type SE CableProvisions have been proposed to limit the restriction of service-entrance (SE) cables ampacity ratings to the 60ºC(140ºF) conductor temperature rating.

This change will align smaller Type SE cables wi th Type NM cables as related to heat dissipation when installed in thermal insulation.

NEW: 320.6 - Listing Requirements - Cable Wiring MethodsNew provisions have been proposed to be added at .06 of several of the cable-type wiring method articles that would require the wiring method (cable) and associated fittings to be listed and labeled.

This new listing requirement was proposed for:320.6 Type AC cable322.6 Type FC cable324.6 Type FCC cable328.6 Type MV cable330.6 Type MC cable

332.6 Type MI cable334.6 Type NM cable336.6 Type TC cable338.6 Type SE cable340.6 Type UF cable.

NEW: 314.27(E) - Outlet Boxes - Separable Attachment FittingsAddresses new technology incorporating listed power supply devices, and listed locking support, and mounting receptacles and supporting means for luminaires and ceiling-suspended paddle fans to be installed in or to boxes designed for the purpose.

REVISION: 310.15(B)(7) - Sizing Dwelling Unit Services and FeedersFor the 2017 NEC, a First Revision will allow the reduction in size for dwelling unit service conductors and a feeder that supplies the entire dwelling to also include systems of a 120/208-volt system to qualify as well.

REVISION: Table 300.5 - Minimum Cover Requirements

A new “General Note” to Table 300.5 has been recommended to resolve a potential conflict between UL 1838 and Table 300.5. The proposed footnote would read:

“A lesser depth [other than specified by Table 300.5] shall be permitted where specified in the installation instructrions of a listed low-voltage lighting system.”

[email protected]

Page 25: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Three: Wiring Methods

2017 NEC

Chapter THREE - Wiring Methods

2017 NEC

NEW: 366.20 - Auxiliary Gutters - Conductors Connected in ParallelSpecific language requires parallel conductors to be installed in groups consisting of not more than one conductor per phase, neutral, or grounded conductor to prevent current imbalance in the paralleled conductors due to inductive reactance.

The same parallel provisions were also proposed for metal wireways at 376.20 and for nonmetallic wireways at 378.20.

REVISION: 338.10(B)(4) - Uses Permitted - Type SE CableProvisions have been proposed to limit the restriction of service-entrance (SE) cables ampacity ratings to the 60ºC(140ºF) conductor temperature rating.

This change will align smaller Type SE cables wi th Type NM cables as related to heat dissipation when installed in thermal insulation.

NEW: 320.6 - Listing Requirements - Cable Wiring MethodsNew provisions have been proposed to be added at .06 of several of the cable-type wiring method articles that would require the wiring method (cable) and associated fittings to be listed and labeled.

This new listing requirement was proposed for:320.6 Type AC cable322.6 Type FC cable324.6 Type FCC cable328.6 Type MV cable330.6 Type MC cable

332.6 Type MI cable334.6 Type NM cable336.6 Type TC cable338.6 Type SE cable340.6 Type UF cable.

NEW: 314.27(E) - Outlet Boxes - Separable Attachment FittingsAddresses new technology incorporating listed power supply devices, and listed locking support, and mounting receptacles and supporting means for luminaires and ceiling-suspended paddle fans to be installed in or to boxes designed for the purpose.

REVISION: 310.15(B)(7) - Sizing Dwelling Unit Services and FeedersFor the 2017 NEC, a First Revision will allow the reduction in size for dwelling unit service conductors and a feeder that supplies the entire dwelling to also include systems of a 120/208-volt system to qualify as well.

REVISION: Table 300.5 - Minimum Cover Requirements

A new “General Note” to Table 300.5 has been recommended to resolve a potential conflict between UL 1838 and Table 300.5. The proposed footnote would read:

“A lesser depth [other than specified by Table 300.5] shall be permitted where specified in the installation instructrions of a listed low-voltage lighting system.”

[email protected]

Page 26: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Three: Wiring Methods

2017 NEC

Chapter THREE - Wiring Methods

2017 NEC

NEW: 366.20 - Auxiliary Gutters - Conductors Connected in ParallelSpecific language requires parallel conductors to be installed in groups consisting of not more than one conductor per phase, neutral, or grounded conductor to prevent current imbalance in the paralleled conductors due to inductive reactance.

The same parallel provisions were also proposed for metal wireways at 376.20 and for nonmetallic wireways at 378.20.

REVISION: 338.10(B)(4) - Uses Permitted - Type SE CableProvisions have been proposed to limit the restriction of service-entrance (SE) cables ampacity ratings to the 60ºC(140ºF) conductor temperature rating.

This change will align smaller Type SE cables wi th Type NM cables as related to heat dissipation when installed in thermal insulation.

NEW: 320.6 - Listing Requirements - Cable Wiring MethodsNew provisions have been proposed to be added at .06 of several of the cable-type wiring method articles that would require the wiring method (cable) and associated fittings to be listed and labeled.

This new listing requirement was proposed for:320.6 Type AC cable322.6 Type FC cable324.6 Type FCC cable328.6 Type MV cable330.6 Type MC cable

332.6 Type MI cable334.6 Type NM cable336.6 Type TC cable338.6 Type SE cable340.6 Type UF cable.

NEW: 314.27(E) - Outlet Boxes - Separable Attachment FittingsAddresses new technology incorporating listed power supply devices, and listed locking support, and mounting receptacles and supporting means for luminaires and ceiling-suspended paddle fans to be installed in or to boxes designed for the purpose.

REVISION: 310.15(B)(7) - Sizing Dwelling Unit Services and FeedersFor the 2017 NEC, a First Revision will allow the reduction in size for dwelling unit service conductors and a feeder that supplies the entire dwelling to also include systems of a 120/208-volt system to qualify as well.

REVISION: Table 300.5 - Minimum Cover Requirements

A new “General Note” to Table 300.5 has been recommended to resolve a potential conflict between UL 1838 and Table 300.5. The proposed footnote would read:

“A lesser depth [other than specified by Table 300.5] shall be permitted where specified in the installation instructrions of a listed low-voltage lighting system.”

[email protected]

Page 27: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Three: Wiring Methods

2017 NEC

Chapter THREE - Wiring Methods

2017 NEC

NEW: 366.20 - Auxiliary Gutters - Conductors Connected in ParallelSpecific language requires parallel conductors to be installed in groups consisting of not more than one conductor per phase, neutral, or grounded conductor to prevent current imbalance in the paralleled conductors due to inductive reactance.

The same parallel provisions were also proposed for metal wireways at 376.20 and for nonmetallic wireways at 378.20.

REVISION: 338.10(B)(4) - Uses Permitted - Type SE CableProvisions have been proposed to limit the restriction of service-entrance (SE) cables ampacity ratings to the 60ºC(140ºF) conductor temperature rating.

This change will align smaller Type SE cables wi th Type NM cables as related to heat dissipation when installed in thermal insulation.

NEW: 320.6 - Listing Requirements - Cable Wiring MethodsNew provisions have been proposed to be added at .06 of several of the cable-type wiring method articles that would require the wiring method (cable) and associated fittings to be listed and labeled.

This new listing requirement was proposed for:320.6 Type AC cable322.6 Type FC cable324.6 Type FCC cable328.6 Type MV cable330.6 Type MC cable

332.6 Type MI cable334.6 Type NM cable336.6 Type TC cable338.6 Type SE cable340.6 Type UF cable.

NEW: 314.27(E) - Outlet Boxes - Separable Attachment FittingsAddresses new technology incorporating listed power supply devices, and listed locking support, and mounting receptacles and supporting means for luminaires and ceiling-suspended paddle fans to be installed in or to boxes designed for the purpose.

REVISION: 310.15(B)(7) - Sizing Dwelling Unit Services and FeedersFor the 2017 NEC, a First Revision will allow the reduction in size for dwelling unit service conductors and a feeder that supplies the entire dwelling to also include systems of a 120/208-volt system to qualify as well.

REVISION: Table 300.5 - Minimum Cover Requirements

A new “General Note” to Table 300.5 has been recommended to resolve a potential conflict between UL 1838 and Table 300.5. The proposed footnote would read:

“A lesser depth [other than specified by Table 300.5] shall be permitted where specified in the installation instructrions of a listed low-voltage lighting system.”

[email protected]

Page 28: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Three: Wiring Methods

2017 NEC

Chapter THREE - Wiring Methods

2017 NEC

NEW: 366.20 - Auxiliary Gutters - Conductors Connected in ParallelSpecific language requires parallel conductors to be installed in groups consisting of not more than one conductor per phase, neutral, or grounded conductor to prevent current imbalance in the paralleled conductors due to inductive reactance.

The same parallel provisions were also proposed for metal wireways at 376.20 and for nonmetallic wireways at 378.20.

REVISION: 338.10(B)(4) - Uses Permitted - Type SE CableProvisions have been proposed to limit the restriction of service-entrance (SE) cables ampacity ratings to the 60ºC(140ºF) conductor temperature rating.

This change will align smaller Type SE cables wi th Type NM cables as related to heat dissipation when installed in thermal insulation.

NEW: 320.6 - Listing Requirements - Cable Wiring MethodsNew provisions have been proposed to be added at .06 of several of the cable-type wiring method articles that would require the wiring method (cable) and associated fittings to be listed and labeled.

This new listing requirement was proposed for:320.6 Type AC cable322.6 Type FC cable324.6 Type FCC cable328.6 Type MV cable330.6 Type MC cable

332.6 Type MI cable334.6 Type NM cable336.6 Type TC cable338.6 Type SE cable340.6 Type UF cable.

NEW: 314.27(E) - Outlet Boxes - Separable Attachment FittingsAddresses new technology incorporating listed power supply devices, and listed locking support, and mounting receptacles and supporting means for luminaires and ceiling-suspended paddle fans to be installed in or to boxes designed for the purpose.

REVISION: 310.15(B)(7) - Sizing Dwelling Unit Services and FeedersFor the 2017 NEC, a First Revision will allow the reduction in size for dwelling unit service conductors and a feeder that supplies the entire dwelling to also include systems of a 120/208-volt system to qualify as well.

REVISION: Table 300.5 - Minimum Cover Requirements

A new “General Note” to Table 300.5 has been recommended to resolve a potential conflict between UL 1838 and Table 300.5. The proposed footnote would read:

“A lesser depth [other than specified by Table 300.5] shall be permitted where specified in the installation instructrions of a listed low-voltage lighting system.”

[email protected]

Page 29: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Three: Wiring Methods

2017 NEC

Chapter THREE - Wiring Methods

2017 NEC

NEW: 366.20 - Auxiliary Gutters - Conductors Connected in ParallelSpecific language requires parallel conductors to be installed in groups consisting of not more than one conductor per phase, neutral, or grounded conductor to prevent current imbalance in the paralleled conductors due to inductive reactance.

The same parallel provisions were also proposed for metal wireways at 376.20 and for nonmetallic wireways at 378.20.

REVISION: 338.10(B)(4) - Uses Permitted - Type SE CableProvisions have been proposed to limit the restriction of service-entrance (SE) cables ampacity ratings to the 60ºC(140ºF) conductor temperature rating.

This change will align smaller Type SE cables wi th Type NM cables as related to heat dissipation when installed in thermal insulation.

NEW: 320.6 - Listing Requirements - Cable Wiring MethodsNew provisions have been proposed to be added at .06 of several of the cable-type wiring method articles that would require the wiring method (cable) and associated fittings to be listed and labeled.

This new listing requirement was proposed for:320.6 Type AC cable322.6 Type FC cable324.6 Type FCC cable328.6 Type MV cable330.6 Type MC cable

332.6 Type MI cable334.6 Type NM cable336.6 Type TC cable338.6 Type SE cable340.6 Type UF cable.

NEW: 314.27(E) - Outlet Boxes - Separable Attachment FittingsAddresses new technology incorporating listed power supply devices, and listed locking support, and mounting receptacles and supporting means for luminaires and ceiling-suspended paddle fans to be installed in or to boxes designed for the purpose.

REVISION: 310.15(B)(7) - Sizing Dwelling Unit Services and FeedersFor the 2017 NEC, a First Revision will allow the reduction in size for dwelling unit service conductors and a feeder that supplies the entire dwelling to also include systems of a 120/208-volt system to qualify as well.

REVISION: Table 300.5 - Minimum Cover Requirements

A new “General Note” to Table 300.5 has been recommended to resolve a potential conflict between UL 1838 and Table 300.5. The proposed footnote would read:

“A lesser depth [other than specified by Table 300.5] shall be permitted where specified in the installation instructrions of a listed low-voltage lighting system.”

[email protected]

Page 30: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Three: Wiring Methods

2017 NEC

Chapter THREE - Wiring Methods

2017 NEC

NEW: 366.20 - Auxiliary Gutters - Conductors Connected in ParallelSpecific language requires parallel conductors to be installed in groups consisting of not more than one conductor per phase, neutral, or grounded conductor to prevent current imbalance in the paralleled conductors due to inductive reactance.

The same parallel provisions were also proposed for metal wireways at 376.20 and for nonmetallic wireways at 378.20.

REVISION: 338.10(B)(4) - Uses Permitted - Type SE CableProvisions have been proposed to limit the restriction of service-entrance (SE) cables ampacity ratings to the 60ºC(140ºF) conductor temperature rating.

This change will align smaller Type SE cables wi th Type NM cables as related to heat dissipation when installed in thermal insulation.

NEW: 320.6 - Listing Requirements - Cable Wiring MethodsNew provisions have been proposed to be added at .06 of several of the cable-type wiring method articles that would require the wiring method (cable) and associated fittings to be listed and labeled.

This new listing requirement was proposed for:320.6 Type AC cable322.6 Type FC cable324.6 Type FCC cable328.6 Type MV cable330.6 Type MC cable

332.6 Type MI cable334.6 Type NM cable336.6 Type TC cable338.6 Type SE cable340.6 Type UF cable.

NEW: 314.27(E) - Outlet Boxes - Separable Attachment FittingsAddresses new technology incorporating listed power supply devices, and listed locking support, and mounting receptacles and supporting means for luminaires and ceiling-suspended paddle fans to be installed in or to boxes designed for the purpose.

REVISION: 310.15(B)(7) - Sizing Dwelling Unit Services and FeedersFor the 2017 NEC, a First Revision will allow the reduction in size for dwelling unit service conductors and a feeder that supplies the entire dwelling to also include systems of a 120/208-volt system to qualify as well.

REVISION: Table 300.5 - Minimum Cover Requirements

A new “General Note” to Table 300.5 has been recommended to resolve a potential conflict between UL 1838 and Table 300.5. The proposed footnote would read:

“A lesser depth [other than specified by Table 300.5] shall be permitted where specified in the installation instructrions of a listed low-voltage lighting system.”

[email protected]

Page 31: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Four: Equipment for General Use

2017 NEC

Source: http://iaeimagazine.org/magazine/2015/09/04/analysis-of-changes-2017-nec-part-2/

Chapter FOUR - Equipment for

General Use

2017 NEC

NEW: 404.22 - Electronic Lighting Control SwitchesThis new provision prohibits electronic lighting control switches from introducing current on the equipment groundign conductor during normal operation.

This proposal would have a future effective date of January 1, 2020.

NEW: 406.3(F) - Receptacle With USB ChargerNew provisions would require 125-volt 15- or 20-ampere receptacles that additionally provide Class 2 power in the form of a USB charger to be listed and constructed such that the Class 2 circuitry is integral with the receptacle.

REVISION: 406.12 - Tamper-Resistant ReceptaclesThe proposed requirement expansion would bring tamper-resistant safety devices to areas that small children frequently occupy.

New locations include: PreschoolsElementary EducationBusiness officesCorridors

Waiting roomsClinicsMedical OfficesDental OfficesOutpatient facilities

GymnasiumsSkating RinksAuditoriumsDormitories

REVISION: 408.3(A)(2) - Barriers at Service Panelboards, Switchboards, and SwitchgearPanelboards have been added to the type of service equipment, along with switchboards and switchgear, that will require barriers to be placed in these service enclosures to prohibit uninsulated, ungrounded service busbars or service terminals from being exposed to inadvertent contact by persons or maintenance equipment while servicing load terminations.

NEW: 409.23 - Available Fault Current (Industrial Control Panels)New provisions were proposed for a field marking requirement for industrial control panels indicating the available fault current. This proposed field marking would be similar to the available fault-current field marking requirements of 110.24(A).

REVISION: 422.16(B)(2) - Built-in Dishwashers

Proposed revisions would allow only the receptace outlet for a cord- and plug-connected dishwaster to be located in the space adjacent to the dishwasher.

REVISION: 445.11 - Marking (Generators)

The marking and nameplate requirements for all stationary generators and portable generators rated more than 15kW have been proposed to be revised to include not only the power factor, the subtransient, and the insulation system class but also the transient reactances, and the maximum short-circuit current.

[email protected]

Page 32: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Four: Equipment for General Use

2017 NEC

Chapter FOUR - Equipment for

General Use

2017 NEC

NEW: 404.22 - Electronic Lighting Control SwitchesThis new provision prohibits electronic lighting control switches from introducing current on the equipment groundign conductor during normal operation.

This proposal would have a future effective date of January 1, 2020.

NEW: 406.3(F) - Receptacle With USB ChargerNew provisions would require 125-volt 15- or 20-ampere receptacles that additionally provide Class 2 power in the form of a USB charger to be listed and constructed such that the Class 2 circuitry is integral with the receptacle.

REVISION: 406.12 - Tamper-Resistant ReceptaclesThe proposed requirement expansion would bring tamper-resistant safety devices to areas that small children frequently occupy.

New locations include: PreschoolsElementary EducationBusiness officesCorridors

Waiting roomsClinicsMedical OfficesDental OfficesOutpatient facilities

GymnasiumsSkating RinksAuditoriumsDormitories

REVISION: 408.3(A)(2) - Barriers at Service Panelboards, Switchboards, and SwitchgearPanelboards have been added to the type of service equipment, along with switchboards and switchgear, that will require barriers to be placed in these service enclosures to prohibit uninsulated, ungrounded service busbars or service terminals from being exposed to inadvertent contact by persons or maintenance equipment while servicing load terminations.

NEW: 409.23 - Available Fault Current (Industrial Control Panels)New provisions were proposed for a field marking requirement for industrial control panels indicating the available fault current. This proposed field marking would be similar to the available fault-current field marking requirements of 110.24(A).

REVISION: 422.16(B)(2) - Built-in Dishwashers

Proposed revisions would allow only the receptace outlet for a cord- and plug-connected dishwaster to be located in the space adjacent to the dishwasher.

REVISION: 445.11 - Marking (Generators)

The marking and nameplate requirements for all stationary generators and portable generators rated more than 15kW have been proposed to be revised to include not only the power factor, the subtransient, and the insulation system class but also the transient reactances, and the maximum short-circuit current.

[email protected]

Page 33: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Four: Equipment for General Use

2017 NEC

Chapter FOUR - Equipment for

General Use

2017 NEC

NEW: 404.22 - Electronic Lighting Control SwitchesThis new provision prohibits electronic lighting control switches from introducing current on the equipment groundign conductor during normal operation.

This proposal would have a future effective date of January 1, 2020.

NEW: 406.3(F) - Receptacle With USB ChargerNew provisions would require 125-volt 15- or 20-ampere receptacles that additionally provide Class 2 power in the form of a USB charger to be listed and constructed such that the Class 2 circuitry is integral with the receptacle.

REVISION: 406.12 - Tamper-Resistant ReceptaclesThe proposed requirement expansion would bring tamper-resistant safety devices to areas that small children frequently occupy.

New locations include: PreschoolsElementary EducationBusiness officesCorridors

Waiting roomsClinicsMedical OfficesDental OfficesOutpatient facilities

GymnasiumsSkating RinksAuditoriumsDormitories

REVISION: 408.3(A)(2) - Barriers at Service Panelboards, Switchboards, and SwitchgearPanelboards have been added to the type of service equipment, along with switchboards and switchgear, that will require barriers to be placed in these service enclosures to prohibit uninsulated, ungrounded service busbars or service terminals from being exposed to inadvertent contact by persons or maintenance equipment while servicing load terminations.

NEW: 409.23 - Available Fault Current (Industrial Control Panels)New provisions were proposed for a field marking requirement for industrial control panels indicating the available fault current. This proposed field marking would be similar to the available fault-current field marking requirements of 110.24(A).

REVISION: 422.16(B)(2) - Built-in Dishwashers

Proposed revisions would allow only the receptace outlet for a cord- and plug-connected dishwaster to be located in the space adjacent to the dishwasher.

REVISION: 445.11 - Marking (Generators)

The marking and nameplate requirements for all stationary generators and portable generators rated more than 15kW have been proposed to be revised to include not only the power factor, the subtransient, and the insulation system class but also the transient reactances, and the maximum short-circuit current.

[email protected]

Page 34: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Four: Equipment for General Use

2017 NEC

Chapter FOUR - Equipment for

General Use

2017 NEC

NEW: 404.22 - Electronic Lighting Control SwitchesThis new provision prohibits electronic lighting control switches from introducing current on the equipment groundign conductor during normal operation.

This proposal would have a future effective date of January 1, 2020.

NEW: 406.3(F) - Receptacle With USB ChargerNew provisions would require 125-volt 15- or 20-ampere receptacles that additionally provide Class 2 power in the form of a USB charger to be listed and constructed such that the Class 2 circuitry is integral with the receptacle.

REVISION: 406.12 - Tamper-Resistant ReceptaclesThe proposed requirement expansion would bring tamper-resistant safety devices to areas that small children frequently occupy.

New locations include: PreschoolsElementary EducationBusiness officesCorridors

Waiting roomsClinicsMedical OfficesDental OfficesOutpatient facilities

GymnasiumsSkating RinksAuditoriumsDormitories

REVISION: 408.3(A)(2) - Barriers at Service Panelboards, Switchboards, and SwitchgearPanelboards have been added to the type of service equipment, along with switchboards and switchgear, that will require barriers to be placed in these service enclosures to prohibit uninsulated, ungrounded service busbars or service terminals from being exposed to inadvertent contact by persons or maintenance equipment while servicing load terminations.

NEW: 409.23 - Available Fault Current (Industrial Control Panels)New provisions were proposed for a field marking requirement for industrial control panels indicating the available fault current. This proposed field marking would be similar to the available fault-current field marking requirements of 110.24(A).

REVISION: 422.16(B)(2) - Built-in Dishwashers

Proposed revisions would allow only the receptace outlet for a cord- and plug-connected dishwaster to be located in the space adjacent to the dishwasher.

REVISION: 445.11 - Marking (Generators)

The marking and nameplate requirements for all stationary generators and portable generators rated more than 15kW have been proposed to be revised to include not only the power factor, the subtransient, and the insulation system class but also the transient reactances, and the maximum short-circuit current.

[email protected]

Page 35: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Four: Equipment for General Use

2017 NEC

Chapter FOUR - Equipment for

General Use

2017 NEC

NEW: 404.22 - Electronic Lighting Control SwitchesThis new provision prohibits electronic lighting control switches from introducing current on the equipment groundign conductor during normal operation.

This proposal would have a future effective date of January 1, 2020.

NEW: 406.3(F) - Receptacle With USB ChargerNew provisions would require 125-volt 15- or 20-ampere receptacles that additionally provide Class 2 power in the form of a USB charger to be listed and constructed such that the Class 2 circuitry is integral with the receptacle.

REVISION: 406.12 - Tamper-Resistant ReceptaclesThe proposed requirement expansion would bring tamper-resistant safety devices to areas that small children frequently occupy.

New locations include: PreschoolsElementary EducationBusiness officesCorridors

Waiting roomsClinicsMedical OfficesDental OfficesOutpatient facilities

GymnasiumsSkating RinksAuditoriumsDormitories

REVISION: 408.3(A)(2) - Barriers at Service Panelboards, Switchboards, and SwitchgearPanelboards have been added to the type of service equipment, along with switchboards and switchgear, that will require barriers to be placed in these service enclosures to prohibit uninsulated, ungrounded service busbars or service terminals from being exposed to inadvertent contact by persons or maintenance equipment while servicing load terminations.

NEW: 409.23 - Available Fault Current (Industrial Control Panels)New provisions were proposed for a field marking requirement for industrial control panels indicating the available fault current. This proposed field marking would be similar to the available fault-current field marking requirements of 110.24(A).

REVISION: 422.16(B)(2) - Built-in Dishwashers

Proposed revisions would allow only the receptace outlet for a cord- and plug-connected dishwaster to be located in the space adjacent to the dishwasher.

REVISION: 445.11 - Marking (Generators)

The marking and nameplate requirements for all stationary generators and portable generators rated more than 15kW have been proposed to be revised to include not only the power factor, the subtransient, and the insulation system class but also the transient reactances, and the maximum short-circuit current.

[email protected]

Page 36: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Four: Equipment for General Use

2017 NEC

Chapter FOUR - Equipment for

General Use

2017 NEC

NEW: 404.22 - Electronic Lighting Control SwitchesThis new provision prohibits electronic lighting control switches from introducing current on the equipment groundign conductor during normal operation.

This proposal would have a future effective date of January 1, 2020.

NEW: 406.3(F) - Receptacle With USB ChargerNew provisions would require 125-volt 15- or 20-ampere receptacles that additionally provide Class 2 power in the form of a USB charger to be listed and constructed such that the Class 2 circuitry is integral with the receptacle.

REVISION: 406.12 - Tamper-Resistant ReceptaclesThe proposed requirement expansion would bring tamper-resistant safety devices to areas that small children frequently occupy.

New locations include: PreschoolsElementary EducationBusiness officesCorridors

Waiting roomsClinicsMedical OfficesDental OfficesOutpatient facilities

GymnasiumsSkating RinksAuditoriumsDormitories

REVISION: 408.3(A)(2) - Barriers at Service Panelboards, Switchboards, and SwitchgearPanelboards have been added to the type of service equipment, along with switchboards and switchgear, that will require barriers to be placed in these service enclosures to prohibit uninsulated, ungrounded service busbars or service terminals from being exposed to inadvertent contact by persons or maintenance equipment while servicing load terminations.

NEW: 409.23 - Available Fault Current (Industrial Control Panels)New provisions were proposed for a field marking requirement for industrial control panels indicating the available fault current. This proposed field marking would be similar to the available fault-current field marking requirements of 110.24(A).

REVISION: 422.16(B)(2) - Built-in Dishwashers

Proposed revisions would allow only the receptace outlet for a cord- and plug-connected dishwaster to be located in the space adjacent to the dishwasher.

REVISION: 445.11 - Marking (Generators)

The marking and nameplate requirements for all stationary generators and portable generators rated more than 15kW have been proposed to be revised to include not only the power factor, the subtransient, and the insulation system class but also the transient reactances, and the maximum short-circuit current.

[email protected]

Page 37: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Four: Equipment for General Use

2017 NEC

Chapter FOUR - Equipment for

General Use

2017 NEC

NEW: 404.22 - Electronic Lighting Control SwitchesThis new provision prohibits electronic lighting control switches from introducing current on the equipment groundign conductor during normal operation.

This proposal would have a future effective date of January 1, 2020.

NEW: 406.3(F) - Receptacle With USB ChargerNew provisions would require 125-volt 15- or 20-ampere receptacles that additionally provide Class 2 power in the form of a USB charger to be listed and constructed such that the Class 2 circuitry is integral with the receptacle.

REVISION: 406.12 - Tamper-Resistant ReceptaclesThe proposed requirement expansion would bring tamper-resistant safety devices to areas that small children frequently occupy.

New locations include: PreschoolsElementary EducationBusiness officesCorridors

Waiting roomsClinicsMedical OfficesDental OfficesOutpatient facilities

GymnasiumsSkating RinksAuditoriumsDormitories

REVISION: 408.3(A)(2) - Barriers at Service Panelboards, Switchboards, and SwitchgearPanelboards have been added to the type of service equipment, along with switchboards and switchgear, that will require barriers to be placed in these service enclosures to prohibit uninsulated, ungrounded service busbars or service terminals from being exposed to inadvertent contact by persons or maintenance equipment while servicing load terminations.

NEW: 409.23 - Available Fault Current (Industrial Control Panels)New provisions were proposed for a field marking requirement for industrial control panels indicating the available fault current. This proposed field marking would be similar to the available fault-current field marking requirements of 110.24(A).

REVISION: 422.16(B)(2) - Built-in Dishwashers

Proposed revisions would allow only the receptace outlet for a cord- and plug-connected dishwaster to be located in the space adjacent to the dishwasher.

REVISION: 445.11 - Marking (Generators)

The marking and nameplate requirements for all stationary generators and portable generators rated more than 15kW have been proposed to be revised to include not only the power factor, the subtransient, and the insulation system class but also the transient reactances, and the maximum short-circuit current.

[email protected]

Page 38: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Four: Equipment for General Use

2017 NEC

Chapter FOUR - Equipment for

General Use

2017 NEC

NEW: 404.22 - Electronic Lighting Control SwitchesThis new provision prohibits electronic lighting control switches from introducing current on the equipment groundign conductor during normal operation.

This proposal would have a future effective date of January 1, 2020.

NEW: 406.3(F) - Receptacle With USB ChargerNew provisions would require 125-volt 15- or 20-ampere receptacles that additionally provide Class 2 power in the form of a USB charger to be listed and constructed such that the Class 2 circuitry is integral with the receptacle.

REVISION: 406.12 - Tamper-Resistant ReceptaclesThe proposed requirement expansion would bring tamper-resistant safety devices to areas that small children frequently occupy.

New locations include: PreschoolsElementary EducationBusiness officesCorridors

Waiting roomsClinicsMedical OfficesDental OfficesOutpatient facilities

GymnasiumsSkating RinksAuditoriumsDormitories

REVISION: 408.3(A)(2) - Barriers at Service Panelboards, Switchboards, and SwitchgearPanelboards have been added to the type of service equipment, along with switchboards and switchgear, that will require barriers to be placed in these service enclosures to prohibit uninsulated, ungrounded service busbars or service terminals from being exposed to inadvertent contact by persons or maintenance equipment while servicing load terminations.

NEW: 409.23 - Available Fault Current (Industrial Control Panels)New provisions were proposed for a field marking requirement for industrial control panels indicating the available fault current. This proposed field marking would be similar to the available fault-current field marking requirements of 110.24(A).

REVISION: 422.16(B)(2) - Built-in Dishwashers

Proposed revisions would allow only the receptace outlet for a cord- and plug-connected dishwaster to be located in the space adjacent to the dishwasher.

REVISION: 445.11 - Marking (Generators)

The marking and nameplate requirements for all stationary generators and portable generators rated more than 15kW have been proposed to be revised to include not only the power factor, the subtransient, and the insulation system class but also the transient reactances, and the maximum short-circuit current.

[email protected]

Page 39: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Five: Special Occupancies

2017 NEC

Source: http://iaeimagazine.org/magazine/2015/09/04/analysis-of-changes-2017-nec-part-2/

Chapter FIVE - Special Occupancies

2017 NEC

RELOCATION: 500.2 - Definitions: Hazardous (Classified) LocationsThe existing definitions presently located at 500.2 have been proposed to be relocated to Article 100 to comply with the NEC Style Manual, which states that:

A definition used in two or more articles is required to be located in Article 100.

REVISION: 501.10(B)(1) - Wiring Methods for Class 1, Division 2The wiring methods permitted for Class 1, Division 2 locations have been proposed to be expanded to include rigid metal conduit (RMC) and intermediate metal conduit (IMC) with listed threadless fittings, along with the addition of electrical metallic tubuting (EMT) with listed fittings.

NEW: Tables 511.3(C) and 511.3(D): Tables for Major and Minor Repair GaragesIn order to align with NFPA 30A, 511.3(C) and 511.3(D) are proposed to be replaced respectively in their entiretey with new tables.

511.3(C): Covering both major and minor repair garages where heavier than air gaseous Class 1 liquirds are transferred or dispensed.

511.3(D): Covering major repair garages where vehicles using lighter than air gaseous fuels are repaired or stored.

REVISION: 517.2 - Definitions: Health Care FacilitiesHealth Care Facilities will now include buildings, portions of buildings, or “mobile enclosures” in which human medical, dental, psychiatric, nursing, obstetrical, or surgical care is provided.

REVISION: 517.31(B) - Essential Electrical Systems Transfer SwitchesAssuring that all transfer switches of all of the branches of the essential electrical system meet the same requirements as emergency systems found in other types of occupancies will help the health care facility’s essential electrical system protect paitients and health care personnel during times of emergencies and/or disasters.

[email protected]

Page 40: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Five: Special Occupancies

2017 NEC

Chapter FIVE - Special Occupancies

2017 NEC

RELOCATION: 500.2 - Definitions: Hazardous (Classified) LocationsThe existing definitions presently located at 500.2 have been proposed to be relocated to Article 100 to comply with the NEC Style Manual, which states that:

A definition used in two or more articles is required to be located in Article 100.

REVISION: 501.10(B)(1) - Wiring Methods for Class 1, Division 2The wiring methods permitted for Class 1, Division 2 locations have been proposed to be expanded to include rigid metal conduit (RMC) and intermediate metal conduit (IMC) with listed threadless fittings, along with the addition of electrical metallic tubuting (EMT) with listed fittings.

NEW: Tables 511.3(C) and 511.3(D): Tables for Major and Minor Repair GaragesIn order to align with NFPA 30A, 511.3(C) and 511.3(D) are proposed to be replaced respectively in their entiretey with new tables.

511.3(C): Covering both major and minor repair garages where heavier than air gaseous Class 1 liquirds are transferred or dispensed.

511.3(D): Covering major repair garages where vehicles using lighter than air gaseous fuels are repaired or stored.

REVISION: 517.2 - Definitions: Health Care FacilitiesHealth Care Facilities will now include buildings, portions of buildings, or “mobile enclosures” in which human medical, dental, psychiatric, nursing, obstetrical, or surgical care is provided.

REVISION: 517.31(B) - Essential Electrical Systems Transfer SwitchesAssuring that all transfer switches of all of the branches of the essential electrical system meet the same requirements as emergency systems found in other types of occupancies will help the health care facility’s essential electrical system protect paitients and health care personnel during times of emergencies and/or disasters.

[email protected]

Page 41: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Five: Special Occupancies

2017 NEC

Chapter FIVE - Special Occupancies

2017 NEC

RELOCATION: 500.2 - Definitions: Hazardous (Classified) LocationsThe existing definitions presently located at 500.2 have been proposed to be relocated to Article 100 to comply with the NEC Style Manual, which states that:

A definition used in two or more articles is required to be located in Article 100.

REVISION: 501.10(B)(1) - Wiring Methods for Class 1, Division 2The wiring methods permitted for Class 1, Division 2 locations have been proposed to be expanded to include rigid metal conduit (RMC) and intermediate metal conduit (IMC) with listed threadless fittings, along with the addition of electrical metallic tubuting (EMT) with listed fittings.

NEW: Tables 511.3(C) and 511.3(D): Tables for Major and Minor Repair GaragesIn order to align with NFPA 30A, 511.3(C) and 511.3(D) are proposed to be replaced respectively in their entiretey with new tables.

511.3(C): Covering both major and minor repair garages where heavier than air gaseous Class 1 liquirds are transferred or dispensed.

511.3(D): Covering major repair garages where vehicles using lighter than air gaseous fuels are repaired or stored.

REVISION: 517.2 - Definitions: Health Care FacilitiesHealth Care Facilities will now include buildings, portions of buildings, or “mobile enclosures” in which human medical, dental, psychiatric, nursing, obstetrical, or surgical care is provided.

REVISION: 517.31(B) - Essential Electrical Systems Transfer SwitchesAssuring that all transfer switches of all of the branches of the essential electrical system meet the same requirements as emergency systems found in other types of occupancies will help the health care facility’s essential electrical system protect paitients and health care personnel during times of emergencies and/or disasters.

[email protected]

Page 42: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Five: Special Occupancies

2017 NEC

Chapter FIVE - Special Occupancies

2017 NEC

RELOCATION: 500.2 - Definitions: Hazardous (Classified) LocationsThe existing definitions presently located at 500.2 have been proposed to be relocated to Article 100 to comply with the NEC Style Manual, which states that:

A definition used in two or more articles is required to be located in Article 100.

REVISION: 501.10(B)(1) - Wiring Methods for Class 1, Division 2The wiring methods permitted for Class 1, Division 2 locations have been proposed to be expanded to include rigid metal conduit (RMC) and intermediate metal conduit (IMC) with listed threadless fittings, along with the addition of electrical metallic tubuting (EMT) with listed fittings.

NEW: Tables 511.3(C) and 511.3(D): Tables for Major and Minor Repair GaragesIn order to align with NFPA 30A, 511.3(C) and 511.3(D) are proposed to be replaced respectively in their entiretey with new tables.

511.3(C): Covering both major and minor repair garages where heavier than air gaseous Class 1 liquirds are transferred or dispensed.

511.3(D): Covering major repair garages where vehicles using lighter than air gaseous fuels are repaired or stored.

REVISION: 517.2 - Definitions: Health Care FacilitiesHealth Care Facilities will now include buildings, portions of buildings, or “mobile enclosures” in which human medical, dental, psychiatric, nursing, obstetrical, or surgical care is provided.

REVISION: 517.31(B) - Essential Electrical Systems Transfer SwitchesAssuring that all transfer switches of all of the branches of the essential electrical system meet the same requirements as emergency systems found in other types of occupancies will help the health care facility’s essential electrical system protect paitients and health care personnel during times of emergencies and/or disasters.

[email protected]

Page 43: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Five: Special Occupancies

2017 NEC

Chapter FIVE - Special Occupancies

2017 NEC

RELOCATION: 500.2 - Definitions: Hazardous (Classified) LocationsThe existing definitions presently located at 500.2 have been proposed to be relocated to Article 100 to comply with the NEC Style Manual, which states that:

A definition used in two or more articles is required to be located in Article 100.

REVISION: 501.10(B)(1) - Wiring Methods for Class 1, Division 2The wiring methods permitted for Class 1, Division 2 locations have been proposed to be expanded to include rigid metal conduit (RMC) and intermediate metal conduit (IMC) with listed threadless fittings, along with the addition of electrical metallic tubuting (EMT) with listed fittings.

NEW: Tables 511.3(C) and 511.3(D): Tables for Major and Minor Repair GaragesIn order to align with NFPA 30A, 511.3(C) and 511.3(D) are proposed to be replaced respectively in their entiretey with new tables.

511.3(C): Covering both major and minor repair garages where heavier than air gaseous Class 1 liquirds are transferred or dispensed.

511.3(D): Covering major repair garages where vehicles using lighter than air gaseous fuels are repaired or stored.

REVISION: 517.2 - Definitions: Health Care FacilitiesHealth Care Facilities will now include buildings, portions of buildings, or “mobile enclosures” in which human medical, dental, psychiatric, nursing, obstetrical, or surgical care is provided.

REVISION: 517.31(B) - Essential Electrical Systems Transfer SwitchesAssuring that all transfer switches of all of the branches of the essential electrical system meet the same requirements as emergency systems found in other types of occupancies will help the health care facility’s essential electrical system protect paitients and health care personnel during times of emergencies and/or disasters.

[email protected]

Page 44: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Five: Special Occupancies

2017 NEC

Chapter FIVE - Special Occupancies

2017 NEC

RELOCATION: 500.2 - Definitions: Hazardous (Classified) LocationsThe existing definitions presently located at 500.2 have been proposed to be relocated to Article 100 to comply with the NEC Style Manual, which states that:

A definition used in two or more articles is required to be located in Article 100.

REVISION: 501.10(B)(1) - Wiring Methods for Class 1, Division 2The wiring methods permitted for Class 1, Division 2 locations have been proposed to be expanded to include rigid metal conduit (RMC) and intermediate metal conduit (IMC) with listed threadless fittings, along with the addition of electrical metallic tubuting (EMT) with listed fittings.

NEW: Tables 511.3(C) and 511.3(D): Tables for Major and Minor Repair GaragesIn order to align with NFPA 30A, 511.3(C) and 511.3(D) are proposed to be replaced respectively in their entiretey with new tables.

511.3(C): Covering both major and minor repair garages where heavier than air gaseous Class 1 liquirds are transferred or dispensed.

511.3(D): Covering major repair garages where vehicles using lighter than air gaseous fuels are repaired or stored.

REVISION: 517.2 - Definitions: Health Care FacilitiesHealth Care Facilities will now include buildings, portions of buildings, or “mobile enclosures” in which human medical, dental, psychiatric, nursing, obstetrical, or surgical care is provided.

REVISION: 517.31(B) - Essential Electrical Systems Transfer SwitchesAssuring that all transfer switches of all of the branches of the essential electrical system meet the same requirements as emergency systems found in other types of occupancies will help the health care facility’s essential electrical system protect paitients and health care personnel during times of emergencies and/or disasters.

[email protected]

Page 45: Proposed Changes & Revisions to the 2017 National Electrical Code©

Source: http://iaeimagazine.org/magazine/2015/09/04/analysis-of-changes-2017-nec-part-2/

Changes to Chapter Six: Special Equipment

2017 NEC

Chapter SIX - Special Equipment

2017 NEC

NEW: 600.34 - Photovoltaic (PV) Powered Signs This new section of NEC Article 600 will provide rules for field wiring and the installation and safe usage of PV-powered signs. This section is also intended to harmonize Article 600 with Article 690 and the end use of PV signs constructed per UL 48.

DELETION: Table 680.10 - Minimum Cover Depths - Swimming PoolsCMP-17 determined that all underground wiring should be installed per the burial depths of Table 300.5, thus eliminating the requirement for Table 680.10.

NEW: Article 680 Part VIII - Electrically Powered Pool LiftsThis proposed new part to Article 680 attempts to permit a compliant installation with adequate safety requirements for all swimming pool users, and would cover:

Listing & Labeling Requirements GFCI Protection for Personnel Bonding Requirements Switching Devices Nameplate Info. & Requirements

REVISION: 690.8(A)(1) - Calculation of Maximum PV Sourse Circuit CurrentThe substantiation of this revision points out that an engineer qualified to design PV systems is capable of making the necessary calculations or running the necessary simulations to develop accurate maximum circuit currents of PV sourse cicruits based on the specifics of an installation location.

NEW: 695.15 - Surge Protection for Fire PumpsA new provision was proposed for fire pumps that would require a listed surge protection device to be installed in or on the fire pump controllers.

The NFPA Fire Protection Research Foundation discovered that 12% of the fire pumps tested had damage due to voltage surges.

[email protected]

Page 46: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Six: Special Equipment

2017 NEC

Chapter SIX - Special Equipment

2017 NEC

NEW: 600.34 - Photovoltaic (PV) Powered Signs This new section of NEC Article 600 will provide rules for field wiring and the installation and safe usage of PV-powered signs. This section is also intended to harmonize Article 600 with Article 690 and the end use of PV signs constructed per UL 48.

DELETION: Table 680.10 - Minimum Cover Depths - Swimming PoolsCMP-17 determined that all underground wiring should be installed per the burial depths of Table 300.5, thus eliminating the requirement for Table 680.10.

NEW: Article 680 Part VIII - Electrically Powered Pool LiftsThis proposed new part to Article 680 attempts to permit a compliant installation with adequate safety requirements for all swimming pool users, and would cover:

Listing & Labeling Requirements GFCI Protection for Personnel Bonding Requirements Switching Devices Nameplate Info. & Requirements

REVISION: 690.8(A)(1) - Calculation of Maximum PV Sourse Circuit CurrentThe substantiation of this revision points out that an engineer qualified to design PV systems is capable of making the necessary calculations or running the necessary simulations to develop accurate maximum circuit currents of PV sourse cicruits based on the specifics of an installation location.

NEW: 695.15 - Surge Protection for Fire PumpsA new provision was proposed for fire pumps that would require a listed surge protection device to be installed in or on the fire pump controllers.

The NFPA Fire Protection Research Foundation discovered that 12% of the fire pumps tested had damage due to voltage surges.

[email protected]

Page 47: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Six: Special Equipment

2017 NEC

Chapter SIX - Special Equipment

2017 NEC

NEW: 600.34 - Photovoltaic (PV) Powered Signs This new section of NEC Article 600 will provide rules for field wiring and the installation and safe usage of PV-powered signs. This section is also intended to harmonize Article 600 with Article 690 and the end use of PV signs constructed per UL 48.

DELETION: Table 680.10 - Minimum Cover Depths - Swimming PoolsCMP-17 determined that all underground wiring should be installed per the burial depths of Table 300.5, thus eliminating the requirement for Table 680.10.

NEW: Article 680 Part VIII - Electrically Powered Pool LiftsThis proposed new part to Article 680 attempts to permit a compliant installation with adequate safety requirements for all swimming pool users, and would cover:

Listing & Labeling Requirements GFCI Protection for Personnel Bonding Requirements Switching Devices Nameplate Info. & Requirements

REVISION: 690.8(A)(1) - Calculation of Maximum PV Sourse Circuit CurrentThe substantiation of this revision points out that an engineer qualified to design PV systems is capable of making the necessary calculations or running the necessary simulations to develop accurate maximum circuit currents of PV sourse cicruits based on the specifics of an installation location.

NEW: 695.15 - Surge Protection for Fire PumpsA new provision was proposed for fire pumps that would require a listed surge protection device to be installed in or on the fire pump controllers.

The NFPA Fire Protection Research Foundation discovered that 12% of the fire pumps tested had damage due to voltage surges.

[email protected]

Page 48: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Six: Special Equipment

2017 NEC

Chapter SIX - Special Equipment

2017 NEC

NEW: 600.34 - Photovoltaic (PV) Powered Signs This new section of NEC Article 600 will provide rules for field wiring and the installation and safe usage of PV-powered signs. This section is also intended to harmonize Article 600 with Article 690 and the end use of PV signs constructed per UL 48.

DELETION: Table 680.10 - Minimum Cover Depths - Swimming PoolsCMP-17 determined that all underground wiring should be installed per the burial depths of Table 300.5, thus eliminating the requirement for Table 680.10.

NEW: Article 680 Part VIII - Electrically Powered Pool LiftsThis proposed new part to Article 680 attempts to permit a compliant installation with adequate safety requirements for all swimming pool users, and would cover:

Listing & Labeling Requirements GFCI Protection for Personnel Bonding Requirements Switching Devices Nameplate Info. & Requirements

REVISION: 690.8(A)(1) - Calculation of Maximum PV Sourse Circuit CurrentThe substantiation of this revision points out that an engineer qualified to design PV systems is capable of making the necessary calculations or running the necessary simulations to develop accurate maximum circuit currents of PV sourse cicruits based on the specifics of an installation location.

NEW: 695.15 - Surge Protection for Fire PumpsA new provision was proposed for fire pumps that would require a listed surge protection device to be installed in or on the fire pump controllers.

The NFPA Fire Protection Research Foundation discovered that 12% of the fire pumps tested had damage due to voltage surges.

[email protected]

Page 49: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Six: Special Equipment

2017 NEC

Chapter SIX - Special Equipment

2017 NEC

NEW: 600.34 - Photovoltaic (PV) Powered Signs This new section of NEC Article 600 will provide rules for field wiring and the installation and safe usage of PV-powered signs. This section is also intended to harmonize Article 600 with Article 690 and the end use of PV signs constructed per UL 48.

DELETION: Table 680.10 - Minimum Cover Depths - Swimming PoolsCMP-17 determined that all underground wiring should be installed per the burial depths of Table 300.5, thus eliminating the requirement for Table 680.10.

NEW: Article 680 Part VIII - Electrically Powered Pool LiftsThis proposed new part to Article 680 attempts to permit a compliant installation with adequate safety requirements for all swimming pool users, and would cover:

Listing & Labeling Requirements GFCI Protection for Personnel Bonding Requirements Switching Devices Nameplate Info. & Requirements

REVISION: 690.8(A)(1) - Calculation of Maximum PV Sourse Circuit CurrentThe substantiation of this revision points out that an engineer qualified to design PV systems is capable of making the necessary calculations or running the necessary simulations to develop accurate maximum circuit currents of PV sourse cicruits based on the specifics of an installation location.

NEW: 695.15 - Surge Protection for Fire PumpsA new provision was proposed for fire pumps that would require a listed surge protection device to be installed in or on the fire pump controllers.

The NFPA Fire Protection Research Foundation discovered that 12% of the fire pumps tested had damage due to voltage surges.

[email protected]

Page 50: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Six: Special Equipment

2017 NEC

Chapter SIX - Special Equipment

2017 NEC

NEW: 600.34 - Photovoltaic (PV) Powered Signs This new section of NEC Article 600 will provide rules for field wiring and the installation and safe usage of PV-powered signs. This section is also intended to harmonize Article 600 with Article 690 and the end use of PV signs constructed per UL 48.

DELETION: Table 680.10 - Minimum Cover Depths - Swimming PoolsCMP-17 determined that all underground wiring should be installed per the burial depths of Table 300.5, thus eliminating the requirement for Table 680.10.

NEW: Article 680 Part VIII - Electrically Powered Pool LiftsThis proposed new part to Article 680 attempts to permit a compliant installation with adequate safety requirements for all swimming pool users, and would cover:

Listing & Labeling Requirements GFCI Protection for Personnel Bonding Requirements Switching Devices Nameplate Info. & Requirements

REVISION: 690.8(A)(1) - Calculation of Maximum PV Sourse Circuit CurrentThe substantiation of this revision points out that an engineer qualified to design PV systems is capable of making the necessary calculations or running the necessary simulations to develop accurate maximum circuit currents of PV sourse cicruits based on the specifics of an installation location.

NEW: 695.15 - Surge Protection for Fire PumpsA new provision was proposed for fire pumps that would require a listed surge protection device to be installed in or on the fire pump controllers.

The NFPA Fire Protection Research Foundation discovered that 12% of the fire pumps tested had damage due to voltage surges.

[email protected]

Page 51: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Seven: Special Conditions

2017 NEC

Source: http://iaeimagazine.org/magazine/2015/09/04/analysis-of-changes-2017-nec-part-2/

Chapter SEVEN - Special Conditions

2017 NEC

NEW: 700.3(F) - Temporary Source of Power for Maintenance or Repair of the Alternate Source of Power for Emergency Systems

New perscriptive language was proposed to be added to 700.3 detailing requirements, along with an exception, that recognizes whether a permanent switching means to connect temporarily an alternate source of power (such as a generator) is or is not required.

NEW: 700.25 - Branch Circuit Emergency Lighting Transfer SwitchThis would permit emergency lighting loads supplied by branch circuits, rated at not greater than 20 amperes, to be transferred from the normal branch circuit to an emergency branch circuit using a listed branch-circuit emergency-lighting transfer switch.

NEW: Article 680 Part VIII - Electrically Powered Pool LiftsThis proposed new part to Article 680 attempts to permit a compliant installation with adequate safety requirements for all swimming pool users, and would cover:

Listing & Labeling Requirements GFCI Protection for Personnel Bonding Requirements Switching Devices Nameplate Info. & Requirements

REVISION: 690.8(A)(1) - Calculation of Maximum PV Sourse Circuit CurrentThe substantiation of this revision points out that an engineer qualified to design PV systems is capable of making the necessary calculations or running the necessary simulations to develop accurate maximum circuit currents of PV sourse cicruits based on the specifics of an installation location.

NEW: 695.15 - Surge Protection for Fire PumpsA new provision was proposed for fire pumps that would require a listed surge protection device to be installed in or on the fire pump controllers.

The NFPA Fire Protection Research Foundation discovered that 12% of the fire pumps tested had damage due to voltage surges.

[email protected]

Page 52: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Seven: Special Conditions

2017 NEC

Chapter SEVEN - Special Conditions

2017 NEC

NEW: 700.3(F) - Temporary Source of Power for Maintenance or Repair of the Alternate Source of Power for Emergency Systems

New perscriptive language was proposed to be added to 700.3 detailing requirements, along with an exception, that recognizes whether a permanent switching means to connect temporarily an alternate source of power (such as a generator) is or is not required.

NEW: 700.25 - Branch Circuit Emergency Lighting Transfer SwitchThis would permit emergency lighting loads supplied by branch circuits, rated at not greater than 20 amperes, to be transferred from the normal branch circuit to an emergency branch circuit using a listed branch-circuit emergency-lighting transfer switch.

REVISION: 770.24 - Mechanical Execution of Work: Optical Fiber CablesRevisions to 770.24 were proposed to require protection against physical damage to optical fiber cables in accordance to all of 300.4 - not just 300.4(D) through (G) as is currently required.

[email protected]

Page 53: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Seven: Special Conditions

2017 NEC

Chapter SEVEN - Special Conditions

2017 NEC

NEW: 700.3(F) - Temporary Source of Power for Maintenance or Repair of the Alternate Source of Power for Emergency Systems

New perscriptive language was proposed to be added to 700.3 detailing requirements, along with an exception, that recognizes whether a permanent switching means to connect temporarily an alternate source of power (such as a generator) is or is not required.

NEW: 700.25 - Branch Circuit Emergency Lighting Transfer SwitchThis would permit emergency lighting loads supplied by branch circuits, rated at not greater than 20 amperes, to be transferred from the normal branch circuit to an emergency branch circuit using a listed branch-circuit emergency-lighting transfer switch.

REVISION: 770.24 - Mechanical Execution of Work: Optical Fiber CablesRevisions to 770.24 were proposed to require protection against physical damage to optical fiber cables in accordance to all of 300.4 - not just 300.4(D) through (G) as is currently required.

[email protected]

Page 54: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Seven: Special Conditions

2017 NEC

Chapter SEVEN - Special Conditions

2017 NEC

NEW: 700.3(F) - Temporary Source of Power for Maintenance or Repair of the Alternate Source of Power for Emergency Systems

New perscriptive language was proposed to be added to 700.3 detailing requirements, along with an exception, that recognizes whether a permanent switching means to connect temporarily an alternate source of power (such as a generator) is or is not required.

NEW: 700.25 - Branch Circuit Emergency Lighting Transfer SwitchThis would permit emergency lighting loads supplied by branch circuits, rated at not greater than 20 amperes, to be transferred from the normal branch circuit to an emergency branch circuit using a listed branch-circuit emergency-lighting transfer switch.

REVISION: 770.24 - Mechanical Execution of Work: Optical Fiber CablesRevisions to 770.24 were proposed to require protection against physical damage to optical fiber cables in accordance to all of 300.4 - not just 300.4(D) through (G) as is currently required.

[email protected]

Page 55: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Eight: Communication Systems

2017 NEC

Source: http://iaeimagazine.org/magazine/2015/09/04/analysis-of-changes-2017-nec-part-2/

Chapter EIGHT - Communication

Systems

2017 NEC

REVISION: 840.48 - Unlisted Wires and Cables Entering Buildings for Premises-Powered Broadband Communications Systems

In order to expand the coverage of Article 840, there is a proposal to recognize both twisted pair and coaxial cable-based systems in addition to optical fiber-based systems.

[email protected]

Page 56: Proposed Changes & Revisions to the 2017 National Electrical Code©

Changes to Chapter Eight: Communication Systems

2017 NEC

Chapter EIGHT - Communication

Systems

2017 NEC

REVISION: 840.48 - Unlisted Wires and Cables Entering Buildings for Premises-Powered Broadband Communications Systems

In order to expand the coverage of Article 840, there is a proposal to recognize both twisted pair and coaxial cable-based systems in addition to optical fiber-based systems.

[email protected]

Page 57: Proposed Changes & Revisions to the 2017 National Electrical Code©

2017 National Electrical Code© A Preview of Proposed Changes

Join TPC Training Systems and TPC Trainco as veteran electrical instructor Bob Clukey provides an overview of the key areas of change and expansion coming in the 2017 National Electrical Code©.

Infomational Webinar: Thursday, July 28th, 201611:00AM - 12:00PM CDT

Register Here

National Electrical Code2017 NEC

REVISION: 840.48 - Unlisted Wires and Cables Entering Buildings for Premises-Powered Broadband Communications Systems

In order to expand the coverage of Article 840, there is a proposal to recognize both twisted pair and coaxial cable-based systems in addition to optical fiber-based systems.

[email protected]