Proposal and Validation of a Model for the Dynamic Simulation of a Solar-Assisted Single-stage...

14
Proposal and validation of a model for the dynamic simulation of a solar-assisted single-stage LiBr/water absorption chiller G. Evola a , N. Le Pierre `s b, *, F. Boudehenn c , P. Papillon c a LEPMI, CNRS UMR 5279, 50 avenue du lac Le ´man, 73377 Le Bourget du Lac, France b LOCIE, CNRS UMR 5271, Universite ´ de Savoie, Polytech Annecy-Chambe ´ry, 73376 Le Bourget du Lac, France c CEA LITEN, BP 332, 50 avenue du lac Le ´man, 73377 Le Bourget du Lac, France article info Article history: Received 28 November 2011 Received in revised form 21 September 2012 Accepted 18 October 2012 Available online 1 November 2012 Keywords: Absorption chiller Lithium bromide Dynamic performance Simulation Experimental results abstract In this paper, a general mathematical model for the dynamic simulation of a single-effect LiBr/water absorption chiller is presented. The model is based on mass and energy balances applied to the internal components of the machine, and it accounts for the non- steady behaviour due to thermal and mass storage in the components. The validation of the mathematical model is performed through experimental data collected on a commer- cial small-capacity water-cooled unit. Due to the peculiar technology adopted in the real chiller, a special effort was made to identify the appropriate values of the main physical parameters. The validation of the model is based on the values of the water temperature at the outlet of the machine, as no measurement inside the machine was possible; anyway, a consistency analysis applied to the internal parameters is also presented. The agreement between experimental and simulated results is very good, both on a daily and on a seasonal basis. ª 2012 Elsevier Ltd and IIR. All rights reserved. Proposition et validation d’un mode ` le pour la simulation dynamique d’un refroidisseur a ` absorption au LiBr / eau solaire monoe ´ tage ´ Mots cle ´s : Refroidisseur a ` absorption ; Bromure de lithium ; Performance dynamique ; Simulation ; Re ´ sultats expe ´ rimentaux 1. Introduction Dynamic simulation plays a very important role in the description of the real performance of an energy conversion system, especially during the activation stage or part-load operation. Such a problem is extremely relevant for absorp- tion chillers, where the high mass of the internal components and the accumulation of the fluids inside the vessels usually make the transient phase longer than in mechanical compression chillers. * Corresponding author. Tel.: þ33 47 975 88 58; fax: þ33 47 975 81 44. E-mail address: [email protected] (N. Le Pierre ` s). www.iifiir.org Available online at www.sciencedirect.com journal homepage: www.elsevier.com/locate/ijrefrig international journal of refrigeration 36 (2013) 1015 e1028 0140-7007/$ e see front matter ª 2012 Elsevier Ltd and IIR. All rights reserved. http://dx.doi.org/10.1016/j.ijrefrig.2012.10.013

Transcript of Proposal and Validation of a Model for the Dynamic Simulation of a Solar-Assisted Single-stage...

  • Proposal and validation of a model for the dynamic simulation

    Mots cles : Refroidisseur a` absorption ; Bromure de lithium ; Performance dynamique ; Simulation ; Resultats experimentaux

    1. Introduction

    Dynamic simulation plays a very important role in the

    description of the real performance of an energy conversion

    system, especially during the activation stage or part-load

    operation. Such a problem is extremely relevant for absorp-

    tion chillers, where the high mass of the internal components

    and the accumulation of the fluids inside the vessels usually

    make the transient phase longer than in mechanical

    compression chillers.

    * Corresponding author. Tel.: 33 47 975 88 58; fax: 33 47 975 81 44.s).

    Available online at www.sciencedirect.com

    e:

    i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 0 1 5e1 0 2 8E-mail address: [email protected] (N. Le Pierre`Proposition et validation dun mode`le pour la simulationdynamique dun refroidisseur a` absorption au LiBr / eausolaire monoetageReceived 28 November 2011

    Received in revised form

    21 September 2012

    Accepted 18 October 2012

    Available online 1 November 2012

    Keywords:

    Absorption chiller

    Lithium bromide

    Dynamic performance

    Simulation

    Experimental results0140-7007/$ e see front matter 2012 Elsevhttp://dx.doi.org/10.1016/j.ijrefrig.2012.10.013LiBr/water absorption chiller is presented. The model is based on mass and energy

    balances applied to the internal components of the machine, and it accounts for the non-

    steady behaviour due to thermal and mass storage in the components. The validation of

    the mathematical model is performed through experimental data collected on a commer-

    cial small-capacity water-cooled unit. Due to the peculiar technology adopted in the real

    chiller, a special effort was made to identify the appropriate values of the main physical

    parameters. The validation of the model is based on the values of the water temperature at

    the outlet of the machine, as no measurement inside the machine was possible; anyway,

    a consistency analysis applied to the internal parameters is also presented. The agreement

    between experimental and simulated results is very good, both on a daily and on a seasonal

    basis.

    2012 Elsevier Ltd and IIR. All rights reserved.Article history: In this paper, a general mathematical model for the dynamic simulation of a single-effecta r t i c l e i n f o a b s t r a c tof a solar-assisted single-stage LiBr/water absorption chiller

    G. Evola a, N. Le Pierre`s b,*, F. Boudehenn c, P. Papillon c

    a LEPMI, CNRS UMR 5279, 50 avenue du lac Leman, 73377 Le Bourget du Lac, Franceb LOCIE, CNRS UMR 5271, Universite de Savoie, Polytech Annecy-Chambery, 73376 Le Bourget du Lac, FrancecCEA LITEN, BP 332, 50 avenue du lac Leman, 73377 Le Bourget du Lac, Francewww. i ifi i r .org

    journal homepagier Ltd and IIR. All rightswww.elsevier .com/locate/ i j refr igreserved.

  • i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 0 1 5e1 0 2 81016Nomenclature

    Variables

    A surface (m2)

    cp specific heat capacity (J kg1 K1)

    Cd discharge coefficient (e)

    D diameter (m)

    f specific backflow (e)

    F fouling factor (m2 kW1)h specific enthalpy (J kg1)H height difference between two components (m)

    H daily solar irradiation on the collector plane

    (kWhm2 day1)I solar irradiance on the collector plane (Wm2)_m mass flow rate (kg s1)M mass (kg)

    Nu Nusselt number (e)

    p pressure (Pa)

    Pr Prandtl number (e)

    Re Reynolds number (e)_Q thermal power (W)

    s thickness (m)

    S pipe section (m2)

    t time (s)Very interesting papers on this topic have been presented

    in scientific literature. Jeong et al. (1998) propose a dynamic

    model for the simulation of a steam-driven LiBr/water

    absorption heat pump that exploits low-grade waste heat. The

    model includes storage terms to take into account the thermal

    capacity of the container and the solution mass storage in the

    components, but no thermal inertia is attributed to the heat

    exchangers. Solution and vapour mass flow rates are not

    constant, as they are determined as a function of the pressure

    difference between the vessels. The simulation time step is

    automatically adjusted; the model has been verified, with

    good agreement, through operational data, but only by looking

    at the thermal power exchanged by the absorber and the

    condenser.

    Kohlenbach and Ziegler (2008a, 2008b) paid a lot of atten-

    tion to the dynamic behaviour, by accounting for heat and

    mass storage, as well as to the solution transport delay

    between generator and absorber e and the way back; on the

    contrary, their model is over-simplified as far as the descrip-

    tion of the steady state is concerned: as an example, water and

    LiBr/water solution have constant property data, and

    a detailed enthalpy calculation for each state of the system is

    avoided. Hence, their model is able to describe very accurately

    the shape of the dynamic response to a change in the input

    conditions, but a low accuracy on the numerical values is

    obtained after verification with the experimental measure-

    ments on a commercial 10 kW single-stage absorption chiller.

    T temperature (K)

    U heat transfer coefficient (Wm2 K1)V volume (m3)_V volumetric flow rate (m3 s1)

    x concentration (e)

    z level of the liquid inside a component (m)Greek letters

    a convective coefficient (Wm2 K1)

    l thermal conductivity (Wm1 K1)r density (kgm3)z pressure loss coefficient (-)

    Subscripts and superscripts

    a absorber

    abs absorbed

    av average value

    c condenser

    d dissipated

    des desorbed

    ext external

    ev evaporator

    g generator

    hx heat exchanger

    in inlet

    int internal

    l liquid

    max maximum value

    o outdoor

    out outlet

    s solution

    sh shellThe work also includes a sensitivity analysis to some internal

    parameters, which is not supported by experimental

    verification.

    The model developed by Shin et al. (2009) applies to high-

    capacity double effect absorption chillers. It has been veri-

    fied against experimental data collected on a commercial

    direct-fired chiller of medium capacity during 370 min of

    operation, with an acquisition time step as high as 5 s. On the

    whole, the model proved to be quite reliable at steady opera-

    tion; on the contrary, during the first 90 min, i.e. when the

    transient behaviour was particularly pronounced, differences

    up to 10 C were observed between simulated and experi-mental values of the temperatures inside generator and

    absorber. Furthermore, during the same period the error on

    the determination of the instantaneous capacity reached 20%.

    Other works have been recently presented by Gomri (2010)

    and Bakhtiari et al. (2011); bothworks are based on a simplified

    steady-state model of a single or multiple effect absorption

    chiller. In the first case, the model is used for evaluating the

    performance sensitivity to the main operating parameters,

    even under a second law perspective, but no validation is

    presented, whereas in the second work the model is validated

    through experimental data and used for the optimization of

    the chiller design.

    Myat et al. (2011) presented an effective dynamic model for

    the evaluation of temperature and concentration profiles in

    a single stage LiBr/water absorption chiller; their model also

    v vapour

    w water

  • which is not steady, a dynamic model is necessary;

    (2008a) and Jeong et al. (1998);

    i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 0 1 5e1 0 2 8 1017- the aim of the model is not to get an extremely precise

    description of the transient response of the machine, but to

    describe with good accuracy the time profile of the chiller

    behaviour when subject to load variations in the time scale

    of a few minutes;

    - the model must determine the water outlet temperature

    and the thermal power at each section of the absorption

    chiller;

    - the model should also present good accuracy in the

    description of the average chiller performance (daily,

    weekly or even seasonal).

    For this reason, the validation of the dynamic model is not

    based on the application of a load perturbation starting from

    a steady state, but it is performed by means of real operating

    conditions, with a continuous change of all the external

    parameters over several days of operation.

    Section 2 describes the equations included in the mathe-

    matical model, as well as the hypotheses that justify such

    equations. Section 3 presents the calculation of the physical

    parameters to be adopted in the mathematical model to

    simulate the commercial single-stage absorption unit

    considered in this study. Section 4 comments on the experi-

    mental data and their comparison with the simulated results.

    Section 5 shows a consistency analysis that investigates into

    the capability of the model to correctly describe the internal

    behaviour of themachine and its response to a sudden change

    in the forcing conditions. Section 6 concerns the use of the

    proposed model to identify some improvements in the

    experimental solar-assisted cooling system.

    2. Description of the model

    A single-stage LiBr/water absorption chiller is made up of

    a generator, an absorber, an evaporator and a condenser;

    the circulation of the solution is assured by a solution

    pump, and a solution heat exchanger is normally used to

    internally recover thermal energy (see Fig. 1). At the gener-

    ator, a heat source is supplied, in order to desorb the

    refrigerant (water vapour) from the solution; the vapour

    moves towards the condenser, where it is condensed at

    a high pressure. The remaining solution, called strong as it is

    rich in LiBr, flows down via the heat exchanger to theincludes some relations for the calculation of the heat transfer

    coefficients and finally leads to an entropy analysis of the

    chiller, but it is not validated through experimental results.

    The model described in the present paper has been

    conceived in the framework of a research project where

    a commercial solar-assisted single-stage absorption chiller is

    being monitored to verify its performance in the air-

    conditioning of an office space. As a consequence, some

    specific features are needed:

    - the model must be suitable for the simulation of commer-

    cial units;

    - as the driving water flow is heated through solar energy,absorber; here it is exposed to the vapour coming from the

    evaporator, that is absorbed in the solution at low pressuref the LiBr/water solution leaving the generator and the

    absorber is saturated (Kohlenbach and Ziegler, 2008a);

    g the throttling valves between generator/absorber and

    condenser/evaporator are adiabatic;

    h the vapour produced in the evaporator is saturated, thus

    no superheating is allowed, as remarked by Shin et al.

    (2009) and Gomri (2010);

    i the volumetric flow rate of diluted solution conveyed by

    the solution pump from the absorber to the generator is

    assumed constant.

    Most of the above simplifying assumptions are quite

    reasonable (b, c, g, i) or well established in the literature on the

    topic (a, d, e, h). Only the assumption fmight be questionable:

    Myat et al. (2011) underline that in a well-designed absorber

    the solution inside the component and at its outlet is normally

    slightly sub-cooled. However, when simulating commercial

    absorption units, it is not possible to access the inside of the

    machine, thus there is no way to verify through experimental

    measurements the accuracy of this last assumption.

    2.1. Generator and absorber

    If looking at the scheme described in Fig. 1, the mass balance

    for the solution and the vapour in the generator can be

    respectively written as follows, by including the storage of

    both fluids in the vessel:

    _ms;in;g _ms;out;g _mv;des dMs;gdt (1)

    _mv;des _mv;out;g dMv;gdt (2)

    The ideal gas law can be used for the vapour, Eq. (3). This

    position is allowed as the vapour pressure inside a single-

    stage LiBr/water absorption chiller is normally between 1

    and 10 kPa, i.e. far lower than the critical pressure; in this

    conditions, the error made on the evaluation of the specific

    volume by using the ideal gas law is lower than 0.1%,whateverand temperature. The diluted solution is then conveyed to

    the generator by the solution pump. The cold production

    occurs at the evaporator.

    In order to simplify the formulation and the consequent

    implementation of the model, some assumptions are made:

    a temperature, pressure and LiBr concentration are

    homogenous inside each component (Myat et al., 2011);

    b the pressure inside the generator equals that in the

    condenser, and the same relation holds between absorber

    and evaporator;

    c the cooling water outlet temperature in the absorber

    corresponds to the cooling water inlet temperature at the

    condenser;

    d the fluid transport delay between two components is

    neglected;

    e each heat exchanger has a constant overall heat transfer

    coefficient, as already stated by Kohlenbach and Zieglerthe vapour temperature, as remarked in (Cengel, 1997). In Eq.

    (3) the volume Vv occupied by the vapour is calculated by

  • morp

    i n t e r n a t i o n a l j o u r n a l o f r e f r i1018subtracting the volume of the solution from that of the entire

    vessel, see Eq. (4).

    Q d,c

    CONDENSER

    M l,c

    M v,c

    m l

    m l,out,c

    M l,e

    Q d.e

    m w,cQ hx,c

    m v,in,c

    m ev

    Q hx,e

    M v,e

    m w,e

    m l,in,e

    High pressure

    Low pressure m v,out,e

    EVAPORATOR

    Fig. 1 e Description of the main components inside the absMv;g$Rv$Tg pg$Vv (3)

    Vv Vg Ms;g=rs;g (4)Furthermore, the mass balance on LiBr, see Eq. (5), and the

    energy balance on the solution, see Eq. (6), hold:

    _ms;in;g$xs;in;g _ms;out;g$xs;out;g Ms;g$dxs;gdt

    xs;g$dMs;gdt (5)

    _Qhx;g _Qd;g _mv;des$hv;des _ms;out;g$hs;out;g _ms;in;g$hs;in;g

    ddt

    Mcp;g$Tg

    (6)

    In Eq. (6), the convective and radiative heat transfer

    between vapour and solution is neglected. The solution is

    assumed to be fully mixed at each simulation step; as

    a consequence the enthalpy and the salt concentration in the

    solution leaving the vessel correspond to those inside the

    vessel. Furthermore, according to Alefeld and Radermacher

    (1993) the temperature of the vapour desorbed in the gener-

    ator corresponds to the saturation temperature associated

    with the diluted solution entering the component; as

    a consequence the vapourwill be super-heatedwith respect to

    the solution contained inside the vessel.

    In addition, the model takes into account the thermal

    inertia of the shell; the shell is assumed at thermal equilib-

    riumwith the solution (Tsh Tg), thus its thermal capacity canbe composed with that of the solution itself in Eq. (6), where

    MMshMs and cp is the average specific heat capacity (Shinet al., 2009), defined as:cp;g Msh$cp;sh Ms$cp;s (7)Msh Ms

    Pump

    Q hx,g

    m s,out,g

    M s,a

    Q d,a

    m w,g

    m s,in,gM v,g

    m v,in,a

    Q hx,a

    m s,out,a

    M v,a

    w,a

    m s,in,a

    Solution exch

    ABSORBER

    m v,abs

    m v,out,g

    m v,des

    GENERATOR

    Q d,g

    M s,g

    tion machine (white arrows: vapour, black arrows: liquid).

    g e r a t i o n 3 6 ( 2 0 1 3 ) 1 0 1 5e1 0 2 8The thermal power released into the environment can be

    assessed by introducing an overall thermal resistance Rgbetween the solution in the generator and the outdoor air:

    _Qd;g Tg To

    Rg (8)

    Suchaschemecanbeextendedtotheabsorber, justaccounting

    for the different direction of the vapour flow, which enters the

    component and is absorbed in the solution. The thermodynamic

    state of the vapour entering the absorber corresponds to that of

    thevapourproduced in theevaporator; itsenthalpy isassessedas

    a function of temperature and pressure through the relations

    available in (Florides et al., 2003), that are derived by fitting the

    data presented in (Rogers andMayhew, 1992).

    In the equations previously presented, the thermodynamic

    properties of the LiBr/water solution (enthalpy, density,

    specific heat, thermal conductivity, viscosity) are calculated

    through appropriate polynomial functions reported in

    (Florides et al., 2003).

    2.2. Condenser and evaporator

    Fig. 1 also shows the scheme used to describe the condenser.

    In this component the liquid phase is condensed vapour

    instead of LiBr/water solution; as a consequence, the mass

    balance on the condensate and the vapour can be written as:

    _ml _ml;out;c dMl;cdt (9)

    _mv;in;c _ml dMv;cdt (10)

  • i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 0 1 5e1 0 2 8 1019In addition, Eqs. (3) and (4) can be rewritten, whereas the

    energy balance applied to the vapour yields:

    _Qhx;c _Qd;c _mlhl _mv;in;chv;in;c ddt

    Mcp;c$Tc

    (11)

    Furthermore, the vapour and the condensate are saturated;

    the enthalpy of the inlet vapour is the same as for the vapour

    flowing out of the generator. As described before, the shell is

    assumed at thermal equilibrium with the working fluid, thus

    the specific heat capacity used in Eq. (11) is an average one

    (Shin et al., 2009).

    The equations can be easily extended to the evaporator by

    looking at the scheme in Fig. 1; as an example, the following

    energy balance holds:

    _Qhx;e _Qd;e _mev$hev _ml;in;e$hl;in;e ddt

    Mcp;e$Te

    (12)

    Here, the enthalpy of the saturated vapour produced inside

    theevaporator isdeterminedbymeansof therelationsavailable

    in (Florides et al., 2003) and already used for the generator.

    2.3. Heat exchangers

    In order to evaluate the heat flux conveyed by the hot water to

    the solution inside the generator, a model of the internal heat

    exchanger is also required. According to thismodel, a uniform

    temperature Thx can be assigned to the metal core of the heat

    exchanger, whose thermal capacity is Mchx. A distinction can

    then bemade between the heat flux released by the water and

    delivered to the surface of the exchanger, see Eq. (13), and that

    transferred from the exchanger to the solution, see Eq. (14).

    The latter depends on the internal (exchanger solution) heattransfer coefficient UAint, whereas the former can also be

    written as in Eq. (15), i.e. as a function of the external

    (water exchanger) heat transfer coefficient of the heatexchanger, UAext, and themean logarithmic temperature. The

    difference between such fluxes represents the thermal energy

    stored on the body of the heat exchanger (see Eq. (16)).

    The heat transfer coefficients UAint and UAext can be easily

    assessed as shown in Eq. (17); in order to understand this

    definition, one must remember that each heat exchanger

    consists of a bank of cylindrical tubes, and that a uniform

    temperature Thx is attributed to the tube itself. The simplifi-

    cation introduced in Eq. (17) is justified by the very low

    thermal resistance associated with the conductive heat

    transfer through the tube thickness: due to the high thermal

    conductivity of copper (l 387Wm1 K1) and the reducedthickness (normally not higher than 1 mm), the contribution

    of this term on the overall thermal resistance would be lower

    than 1%, as shown by a preliminary analysis carried out by the

    authors.

    _Qhx;w rw$ _Vw$cp;w$Tw;in Tw;out

    (13)

    _Qhx UAint$Thx Ts (14)

    _Qhx;w UAext$Tw;in Thx

    Tw;out Thx (15)

    ln

    Tw;in ThxTw;out Thx_Qhx;w _Qhx Mcp;hx$dThxdt

    (16)

    UAextAhx$

    0BBBBB@

    1ahx;ext

    Dhx=2lhx

    $lnDhxshx

    DhxFext

    |{z}overall thermal resistance

    1CCCCCA

    1

    zahx;ext$Ahx

    1ahx;ext$Fext

    (17)

    In the above equations, the density and the specific heat of

    water are determined as a function of the inlet temperature,

    according to the relations reported by Florides et al. (2003).

    Thanks to the model of the heat exchanger, it is possible to

    predict the outlet water temperature and the heat flux

    released to the solution once the water mass flow and its inlet

    temperature are known, as well as the temperature of the

    solution inside the generator.

    The same approach can be easily extended to the heat

    exchanger inside the other components.

    2.4. Other devices

    As previously stated, the volumetric flow rate of the diluted

    solution conveyed by the solution pump is constant, and

    imposed as an input value. On the contrary, the strong solu-

    tion flow rate from the generator to the absorber cannot be

    held constant, as it depends on the pressure and the height

    difference between the generator and the absorber. According

    to this scheme, the mass flow rate of the strong solution can

    be assessed as:

    _ms;out;g Cd$S$

    2$rs;g$

    hpg pa

    rs;g$g$H z

    i

    z

    vuut(18)

    Here, the pressure losses in the solution heat exchanger and

    the corresponding piping are described through a resistance

    coefficient z. The level z of the solution inside the generator is

    continuously updated, as a function of the mass of solution

    actually contained inside the vessel; the vertical distance H

    between the bottom of the generator and the solution inlet of

    the absorber is also considered. The same expression is used

    to calculate the condensate mass flow rate from the

    condenser to the evaporator.

    In both cases, the pressure loss coefficient is not set

    constant, but it is assumed to change as a function of the fluid

    height inside the upper vessel.

    Such an assumption corresponds to the control logic which

    is often adopted in absorption chillers, where an increase in the

    resistanceof the throttlingvalve is inducedwhenthe levelof the

    liquid gets too low, in order to prevent the vessel from getting

    empty. In this work, the following formulation is proposed:

    z z0$z0=z2 (19)where z0 and z0 are nominal values. The use of such a condi-

    tion is a real novelty if compared to other models available in

    the literature, such as those proposed by Kohlenbach and

    Ziegler (2008a) or Shin et al. (2009), and it has relevantly

    improved the stability and the consistency of the model.As regards the solution heat exchanger between the

    generator and the absorber, no thermal inertia has been

  • proposed by Gnielinski (1976):

    adopted (aint 9000 Wm2 K1), as the latter is very similar to

    i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 0 1 5e1 0 2 81020f 0:079$ ln Re 1:642 (20a)

    0:125$f$Re 1000$Pr1 12:7$

    0:125f

    0:5$Pr2=3 1

    (20b)considered. Its heat transfer coefficient UAhx is assumed

    constant and assigned as an input; its efficiency can be easily

    assessed as a function of UAhx and the solution mass flow,

    through well-known relationships valid for counter-flow heat

    exchangers (Incropera et al., 2006).

    3. Definition of the parameters

    The mathematical model presented so far refers to a general

    LiBr/water single effect absorption machine. In this work the

    model will be applied to a commercial water-cooled unit with

    a nominal cooling capacity of 4.5 kW, manufactured by

    Rotartica. This chiller is installed at INES (Institut National de

    lEnergie Solaire) near Chambery (France), where it is used in

    the framework of a national research program aimed at

    assessing the performance of different solar-assisted refrig-

    eration systems.

    Actually, the Rotartica chiller is a very particular one, as the

    absorption cycle is carried out into an hermetically welded

    spheroid container of approximately 500 mm diameter by

    500mm long, rotated at 400 rpm about a horizontal axis, as

    described in (Monne et al., 2011) and also in (Gilchrist et al.,

    2002) for a similar model. The rotation of the components

    improves the heat transfer coefficients and the efficiency of the

    cooling production, but an additional electricity consumption

    of around 400W has to be accounted for to maintain the rota-

    tion. Furthermore, the solution pump is not electrically driven,

    as the pumping power is derived from rotation, by converting

    the kinetic energy at the outer radius of the vessel into pres-

    sure. Further information on the Rotartica chiller is reported by

    Izquierdo et al. (2008) and Garcia Cascales et al. (2011).

    In order to use the proposed model for the simulation of

    the Rotartica chiller, a special effort was devoted to the

    parameter identification. As a matter of fact, when dealing

    with commercial chillers the internal components are usually

    not accessible, thus the only way to determine their geometry

    is based on schemes of the chiller available on the technical

    sheets which is the approach followed in this work.

    In Table 1 the values of all the constant inlet parameters

    used in the model are reported.

    For the evaluation of the cumulated heat capacities, the

    materials are copper in the heat exchangers and iron in the

    vessel. The value of the discharge coefficient Cd is quite typical

    and commonly accepted in the case of circular sharp-edged

    orifices (Massey and Ward-Smith, 1998), whereas the thermal

    resistance R between each component and the outdoors was

    estimated roughly by knowing the geometry of the machine.

    Furthermore, in Eq. (17) the convective heat transfer coef-

    ficient aext between thewater flow and the surface of the tubes

    in each component is assessed by using the correlationsaext lwDhx (20c)the Rotartica machine.

    In addition, the heat transfer coefficient for both water

    boiling and condensation on a circular surface can be assessed

    through appropriate relations available in the literature

    (Incropera et al., 2006).

    It must be remembered that the thermodynamic proper-

    ties of the LiBr/water mixture as well as those of liquid water

    and water vapour can be calculated as a function of the

    temperature and pressure, thus they normally vary with time.

    However, in the determination of the heat transfer coeffi-

    cients a fixed average temperature was considered for each

    fluid, in order to get constant values and simplify the imple-

    mentation of the model.

    Finally, the volumetric flow rate of the diluted solution

    conveyed from the absorber to the generator is kept constant

    and equal to 0.0185 l s1. The mass flow rate changes at eachtime step as a function of the solution density. No calibration

    was applied to optimise the values reported in Table 1.

    4. Experimental verification

    In order to check the reliability of the proposed model for the

    simulation of the Rotartica absorption machine, the authors

    used the experimental results collected during a test

    campaign carried out at INES in summer 2009, fromMay 27 to

    September 10. The results of the simulations were compared

    to the experimental data and the agreement between them

    was verified.

    The Rotartica absorption chiller installed at INES is powered

    by thermal energy produced in a solar field composed of 30-m2

    flat plate solar collectors; a 400-l tank is used to store the hot

    water, and no backup is provided to drive the absorption

    machine when solar energy is not sufficient. The heat rejection

    is carried out by means of a water flow that is cooled down in

    a horizontal ground heat exchanger, made up of twenty-two

    polyethylene pipes divided into two layers, buried at a depth of

    0.75mand1.1 m, respectively; the lengthof everypipe isaroundAccording to Gnielinsky, the Eqs. (20a) and (20b) can be

    applied for Re> 3000, thus they are more general than the

    well-known Dittus-Boelter correlation, valid for Re> 10000.

    The viscosity and the thermal conductivity of water,

    respectively required to determine the Reynolds number and

    to solve Eq. (20c), are determined as a function of the

    temperature through appropriate relations available in

    (Florides et al., 2003).

    In addition, the value of the fouling factor F for the internal

    and external surface of the tubes can be assumed as high as

    0.09 m2 K kW1 (Howell et al., 2005).As concerns the convective heat transfer coefficient on the

    solution side in the absorber and the generator, some exper-

    imental values have been derived by Rivera and Xicale (2001).

    However, these values refer to a geometry that is quite

    different from that of the Rotartica chiller, where the heat

    exchangers rotate with the vessel at 550 rpm (58 rad s1). Forthis reason, in this work the heat transfer coefficients deter-

    mined by Gilchrist et al. (2002) for the Interotex machine are100 m. The chilled water produced by the absorption chiller is

    stored ina300-l tankand thenused to feed three fancoils for the

  • ptio

    i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 0 1 5e1 0 2 8 1021Table 1 e Constant inlet parameters for the Rotartica absor

    Parameter Unit Value

    Cd e 0.61

    Fint, Fext m2 kW1 0.09 103

    Hc m 0

    Hg m 0

    Mcp,a kJ K1 58.5

    Mcp,c kJ K1 33.0

    Mcp,e kJ K1 38.0

    Mcp,g kJ K1 58.5

    Mcp,hx,a kJ K1 4.94

    Mcp,hx,c kJ K1 3.04

    Mcp,hx,e kJ K1 2.66

    Mcp,hx,g kJ K1 2.66

    Ra KW1 4

    Rc KW1 4

    Re KW1 4

    Rg KW1 4

    Rv J kg1 K1 455

    Sc m2 2 105

    Sg m2 2 104

    UAint,a WK1 13970

    UAint,c WK1 9720air conditioning of some office rooms. It is worth mentioning

    that the systemwasnot designed for insuring standard comfort

    conditions in the offices (e.g. indoor temperature always below

    26 C), but rather for refreshing theoffices, sokeeping the indoortemperature at 5e8 C below outdoor air. Hence, no controlsystem has been implemented in the conditioned spaces: the

    system keeps working as long as sufficient thermal energy is

    available to drive the absorption machine.

    During the experimental campaign only the water

    temperatures at the inlet and at the outlet of the machine

    were measured, together with the water flow rates at each

    component. The temperatures were measured by means of

    Pt1000 temperature sensors calibrated together with the

    whole measurement chain (sensor, wire, acquisition system),

    with an absolute uncertainty of 0.15 C. The uncertainty in themeasure of the volumetric flow rates was 2% according to the

    manufacturer of the flow meters. All the data were acquired

    every 120 s; it was not possible to reduce the acquisition time

    step, due to the need of storing the experimental data for long

    periods (up to 1 week) without saturating the memory of the

    acquisition system.

    No data were acquired inside the machine, such as pres-

    sure, temperature and LiBr concentration in each component,

    UAint,e WK1 6620

    UAint,g WK1 7290

    UAext,a WK1 4780

    UAext,c WK1 3320

    UAext,e WK1 2240

    UAext,g WK1 2890

    UAhx WK1 42

    Va m3 0.024

    Vc m3 0.014

    Ve m3 0.024

    Vg m3 0.024

    z0,c M 0.2

    z0,g M 0.2

    z0,c e 1400

    z0,g e 1400n machine.

    Description

    Discharge coefficient

    Fouling factors

    Height between condenser bottom and evaporator inlet

    Height between generator bottom and absorber inlet

    Cumulated heat capacity of the absorber

    Cumulated heat capacity of the condenser

    Cumulated heat capacity of the evaporator

    Cumulated heat capacity of the generator

    Cumulated heat capacity of the absorber heat exchanger

    Cumulated heat capacity of the condenser heat exchanger

    Cumulated heat capacity of the evaporator heat exchanger

    Cumulated heat capacity of the generator heat exchanger

    Thermal resistance between absorber and outdoors

    Thermal resistance between condenser and outdoors

    Thermal resistance between evaporator and outdoors

    Thermal resistance between generator and outdoors

    Gas constant for water vapour

    Pipe section between condenser and evaporator

    Pipe section between generator and absorber

    Internal heat transfer coefficient of the absorber

    Internal heat transfer coefficient of the condenserbecause the interior of themachine was not accessible and no

    internal sensors had been installed by the manufacturers. For

    this reason, the agreement between simulated and experi-

    mental results was verified based on the outlet water

    temperatures and on the thermal power exchanged by the

    absorption chiller at each section.

    Figs. 2 and 3 report the behaviour of the absorption

    machine during two sunny days (14th of August and 8th of

    September). These days are representative of the greatest part

    of the experimental campaign: actually, during cloudy days

    the absorption machine did not normally switch on, because

    of the insufficient driving temperature provided by the solar

    plant. Themain climatic data registered during both the afore-

    mentioned days and the whole experimental campaign are

    reported in Table 2.

    As shown in the graphs, at around 11:00, as soon as the

    water available at the generator inlet reaches 80 C, theabsorptionmachine turns on (see Fig. 2); the cold production is

    almost immediate, as can be noticed from the profile of the

    inlet and outlet temperatures at the evaporator. The chiller

    produces cold water at mild temperatures, with a minimum

    value of 13.7 C on August the 14th and 18.1 C on Septemberthe 8th, respectively. The highest driving temperature is

    Internal heat transfer coefficient of the evaporator

    Internal heat transfer coefficient of the generator

    External heat transfer coefficient of the absorber

    External heat transfer coefficient of the condenser

    External heat transfer coefficient of the evaporator

    External heat transfer coefficient of the generator

    Overall heat transfer coefficient of the solution exchanger

    Volume of the absorber

    Volume of the condenser

    Volume of the evaporator

    Volume of the generator

    Nominal height of the liquid inside the condenser

    Nominal height of the solution inside the generator

    Pressure loss coefficient (condenser/evaporator)

    Pressure loss coefficient (generator/absorber)

  • Te

    mp

    eratu

    re

    [C

    ]

    Te

    mp

    eratu

    re

    [C

    ]

    Inlet Outlet Inlet Outleta b

    r th

    i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 0 1 5e1 0 2 81022around 90 C. On the heat rejection loop, the water inlettemperature keeps in the range 30e35 C on August the 14thand 37e42 C on September the 8th.

    The reason for the different performance during these 2

    days is that during a short period of the experimental

    campaign (from the 25th of August to the 8th of September),

    a section of the ground heat exchanger was closed for exper-

    imental reasons. As expected, due to the lower surface avail-

    able for heat rejection, the water temperature in the rejection

    loop raised in comparison with normal operation days, such

    as the 14th of August. This induced a reduction in the cooling

    capacity, hence an increase in the outlet temperature of the

    chilled water.

    The machine eventually stops when the driving tempera-

    ture gets lower than 76 C, which occurs at around 17:40 onSeptember the 8th.

    In addition, one can notice that the cooling power keeps

    almost constant between 11:30 and 15:30 (around 6 kW on

    August 14th and 4 kW on September 8th, see Fig. 3), but an

    important reduction occurs during the last hours of operation.

    Time [h]

    Fig. 2 e Experimental inlet and outlet temperature profiles foFurthermore, the thermal COP, defined as the ratio of the

    cooling power produced at the evaporator to the thermal

    power required at the generator, is quite stable and suffi-

    ciently high (0.71e0.75 and 0.65e0.7 in the two representative

    days, respectively).

    CO

    P [-]

    Th

    erm

    alp

    ow

    er[k

    W]

    a

    Fig. 3 e Experimental energy performance of the absorpHere again, the better performance of the machine in the

    first day, where the cooling power is almost 30% higher than

    the machine nominal capacity, can be justified by the more

    favourable operating conditions (lower temperature on the

    heat rejection side).

    Afterwards, the same representative days discussed above

    were used to run the simulations, by using the water inlet

    temperature profiles shown in Fig. 2 as an input to the

    mathematical model, as well as the experimental values of

    the water flow rate.

    Themodel provides as output the values of thewater outlet

    temperatures and the thermal powers, calculated as:

    _Q j rw$ _Vj$cp;w$Tout Tinj (21)

    Here, the density r of water is calculated as a function of the

    inlet temperature (Florides et al., 2003). The water flow rates

    measured on the real system are:

    Hot water flow rate at the generator: _Vw;g 0:82 [m3 h1] Cold water flow rate at the evaporator: _Vw;e 1:34 [m3 h1] Cooling water flow rate at the condenser: _Vw;c 2:20 [m3 h1]

    e absorption chiller (a: 14th of August, b: 8th of September).Time [h]Furthermore, the control logic of the absorption machine

    were implemented, according to which the machine switches

    onwhen the driving temperature gets higher than 80 C, and itturns off below 76 C.

    CO

    P [-]

    Th

    erm

    alp

    ow

    er[k

    W]

    b

    tion chiller (a: 14th of August, b: 8th of September).

  • The system of equations is solved on the simulation tool

    SimSpark by using a NewtoneRaphson procedure with

    forward finite difference approximation; the simulation is

    performed with a time step as long as 5 s.

    after calculating the profile of the thermal power exchanged at

    each component, one can integrate over time in order to obtain

    the overall thermal energy during a certain time interval. Table 3

    reports the results of this procedure performed both over the

    representative days previously described and over the whole

    test campaign (107 days). The results are very encouraging,

    as the absolute error on the cumulated daily and seasonal

    cold production is lower than 0.3%; the error on the average

    thermal COP is also very low. The highest discrepancy e around

    5% e between experimental and simulated data occurs on the

    heat rejection side (condenser absorber).If lookingmore in detail, one can notice that the sum of the

    simulated values of the overall thermal energy provided at the

    generator and evaporator does not correspond to that rejected

    by the machine, as one would expect, but the latter is around

    The results in Table 3 show that the proposed model not

    only can be used to followwith a good approximation the daily

    Table 2 e Main climatic data for the experimentalcampaign.

    Tavext[C]

    Tmaxext[C]

    Imax

    [Wm2]H [kWhm2

    day1]

    14th of August 23.4 33.5 827.3 6.36

    8th of September 18.0 28.6 813.2 5.93

    Whole period

    (27/05e10/09)

    21.8 40.6 1053.0 5.42

    i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 0 1 5e1 0 2 8 1023The discrepancy between experimental and simulated

    results is shown in Figs. 4 and 5. In the first diagram, it is

    possible to see the profile of the difference between simulated

    andmeasured outlet temperatures during the chosen days. As

    regards the evaporator outlet temperature (see Fig. 4), this

    discrepancy keeps always very low (between 0.2 C and0.2 C). The precision of the model is also good for the gener-ator and the condenser outlet temperatures, as the discrep-

    ancy with the experimental results never exceeds 0.4 C.Furthermore, the percentage error on the evaluation of the

    thermal and cooling power is moderate, as shown in Fig. 5.

    Here, each point in the graphs allows the comparison between

    an experimental acquisition and its corresponding simulated

    value (there is one point every 120 s of machine operation).

    The deviation between experimental value and simulated

    result is measured by the distance from the diagonal line,

    where a perfect match between the two values holds. One can

    remark that the absolute deviation is always lower than 10%

    for all the components, but during the greatest part of the

    operation time it is even lower than 5%. The error at the

    evaporator (Fig. 5a) and the generator (Fig. 5b) tends to be

    higher at low capacity, whereas it is almost negligible at high

    capacity. The average error seems to be higher at the heat

    rejection section (Fig. 5c). Because of such discrepancies, an

    error on the evaluation of the thermal COP is expected, which

    keeps however always lower than 5% (Fig. 5d).

    Apart from verifying the capability of the model to describe

    the dynamic performance of the absorption machine, it is also

    important to test its reliability on a long time basis. To this aim,

    aErro

    r [C

    ]

    Time [h]

    Fig. 4 e Discrepancy between simulated and experimental oudynamic behaviour of the Rotartica absorption machine, but

    also to evaluate its overall performance over a long period. In

    any case, due to the amplitude of the acquisition time step

    used in the experimental test rig (120 s), nothing can be said

    about the precision of the model for transient phenomena

    whose duration is shorter than that.

    5. Consistency analysis

    As shown before, the verification of the agreement between

    simulated and experimental data was carried out through the

    temperatures measured at the outlet of the absorption

    machine, due to the impossibility to make measurements

    inside the chiller. Nonetheless, the model is able to reproduce

    the profile of pressure, temperature and LiBr concentration

    inside the components, as well as the vapour and solution

    Erro

    r [C

    ]

    Time [h]

    b1e2% lower than the former. As amatter of fact, the process is

    not adiabatic, and the thermal energy stored in the generator

    is partially dissipated to the environment. On the contrary,

    when looking at the experimental data, the thermal energy

    rejected by the machine is always higher than the sum of that

    measured at generator and evaporator, and the difference can

    even reach 5%. This discrepancy might be attributed to the

    heat produced by the electricmotor placed inside themachine

    to maintain the rotation.tlet temperatures (a: 14th of August, b: 8th of September).

  • a b

    i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 0 1 5e1 0 2 81024cmass flow rates. The values of these parameters are shown in

    Fig. 6 for the first day used in the previous analysis (14th of

    August).

    The parameter f represented in Fig. 6c is known as specific

    backflow, and is defined as the ratio of the diluted solution e

    which is rich in refrigerant e to the vapour produced in the

    evaporator (Eicker, 2003):

    Fig. 5 e Comparison between simulated and experimental energ

    5% error.

    Table 3 e Experimental and simulated values for daily and sea

    Generator [kWh] Evaporator [kWh] Gene

    Daily performance (14th of August)

    Experimental 46.8 34.7

    Simulated 47.1 34.6

    Error 0.6% 0.1%Daily performance (8th of September)

    Experimental 34.7 23.4

    Simulated 34.0 23.4

    Error 2.0% 0.0%Full test campaign (27/05e10/09)

    Experimental 3278 2354

    Simulated 3251 2362

    Error 0.8% 0.3%df _ms;out;amev

    xgxg xa (22)

    It must be underlined that the diluted solution mass flow

    rate pumped from the absorber to the generator is not

    constant (see Fig. 6c), even though the volumetric flow rate

    was set constant, due to the variation in the solution density.

    y performance (both days). Solid line: 10% error; dotted line:

    sonal energy performance.

    r Evap [kWh] Heat rejection [kWh] Thermal COP [e]

    81.5 85.0 0.741

    81.7 80.9 0.735

    e 4.8% 0.7%

    58.1 58.7 0.674

    57.4 56.2 0.688

    e 4.2% 2.0%

    5632 5849 0.718

    5613 5559 0.727

    e 4.9% 1.2%

  • a transient period of at least 400 s is needed by the chiller to

    reach new steady-state operation.

    6. Use of the simulations for the systemimprovement

    Themodel presented and validated in the previous sections is

    b

    c

    Fig. 6 e Simulated values for the main internal parameters

    (14th of August). (a): Pressure and LiBr concentration, (b):

    temperature, (c): mass flow rates.

    i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 0 1 5e1 0 2 8 1025This density is highly influenced by the LiBr concentration,

    according to the relation proposed in (Florides et al., 2003).

    In order to check the internal consistency of themathemat-

    ical model, a further test was carried out (see also Kohlenbach

    and Ziegler, 2008b). A new simulation was run by adopting

    constant cooling and chilled water inlet temperatures 30 Cand 18 C, respectivelye and a step changefrom80 C to 90 Ce to the driving temperature. In this case the simulation time

    step was set at 1 s. The duration of the simulation is 2000 s; the

    temperature step occurs at 1000 s after the beginning, as

    a certain delay is needed to wait for the system to reach steady

    operation in the initial operating conditions. Such an analysis is

    alsohelpful to investigate intomassandthermalstorageeffects.

    AsshowninFig.7, thetemperaturestep is followedbyasteep

    increase of the thermal power released to the solution in the

    generator (see graphg), hence by an increase of themassflowof

    vapour desorbed (see graph e). As a consequence of the higher

    vapour production rate, the LiBr concentration of the diluted

    solution inside the generator starts growing (see graph d).

    A more important vapour flow rate is then conveyed to the

    condenser but actually, due to the storage effects, the increase

    of the condensation rate follows in a slower fashion (see the

    curvem_l in graph e). Therefore, the condenser pressure rises,

    which is also communicated to the generator (see graph d); as

    saturation holds in the condenser, such a pressure increase

    also induces a temperature rise (see graph b).

    Fig. 7g also shows that the thermal power delivered to the

    generator tends to decrease after the initial step; such an

    effect is due to the growing temperature of the solution (see

    graph a), and then to the reduced heat transfer potential. It is

    interesting to underline that, despite the reduced thermal

    power, the vapour production keeps rising (see graph e): as

    a matter of fact, at higher pressure and temperature the

    energy needed to release an unit mass of vapour is lower.

    Again from Fig. 7e, one can notice that during the transient

    stage, the evaporation rate at the evaporator keeps higher

    than the liquid production rate at the condenser; this implies

    a fall in the evaporator absorber pressure (see graph d) anda consequent reduction in the evaporator temperature (see

    graph c). Furthermore, due to the time lag between vapour

    production in the generator and in the evaporator, a higher

    generator thermal power is not immediately followed by an

    equivalent rise in cooling production (see graph g, time 1000),

    thus the thermal COP initially shows a sudden decrease.

    However, such a fall is progressively recovered as long as the

    cooling power grows and the thermal power decreases.

    As far as the solution mass flow is concerned, the strong

    solution conveyed from the generator to the absorber initially

    decreases (see graph f), as a consequence of the higher vapour

    production. However, as far as the temperature and the LiBr

    concentration at generator rise, the density of the strong

    solution gets higher, and this implies, at around 1040 s, an

    inversion in the curve representing the strong solution rate

    (see graph f). In the absorber, temperature and LiBr concen-

    tration also rise (see graphs b and d), due to the same tendency

    previously identified at the generator.

    The simulated behaviour of the absorption chiller after

    a step of 10 K in the driving temperature is then coherent withwhat would be expected from thermodynamics. Such a test

    also showed that, due to thermal and mass storage effects,auseful to simulate the performance of the Rotartica chiller

    when integrated into a solar-assisted air-conditioning system,

  • bi n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 0 1 5e1 0 2 81026aas it is able to describe with good accuracy the dynamic

    response of the chiller both to load variations and to

    a continuous change in the driving temperature. In a solar-

    assisted system, the latter are strictly connected with the

    c d

    e

    g

    Fig. 7 e Simulated response of the absorption chilleenvironmental conditions, especially if no back-up is avail-

    able, as occurs in the plant considered in this study.

    In order to show the usefulness of the model in a practical

    case, several simulations were carried out to investigate into

    f

    r to a step variation in the driving temperature.

  • climatic data registered during the experimental campaign.

    The corresponding profiles of the outdoor temperature and of

    the solar irradiance on the surface of the collectors are re-

    ported in Fig. 8

    The results of such parametric analysis are shown in

    Table 4. In order to justify them, it is useful to remind that the

    absorption unit starts working when the driving temperature

    reaches 80 C, and eventually stops when the latter gets lowerthan 76 C.

    As a rule, the higher the volume of the hot storage is, the

    longer it takes for the hot water to reach theminimumdriving

    temperature needed to run the absorption unit: as a conse-

    quence, the unit starts working late in the morning. However,

    a higher storage volume also allows a slower thermal

    In this paper, a dynamic model for the simulation of

    Fig. 8 e Experimental values of the climatic data for the

    period considered in the simulations (from the 11th to the

    i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 0 1 5e1 0 2 8 1027the effect of the size of the storage tanks on the chiller

    performanceemeasured by its cold production and its thermal

    COP e when the chiller is used in a solar-assisted air-condi-

    tioning system like the one installed at INES and described in

    Section 4. This system contains two storage tanks:

    - the hot storage tank (400 l) is used to collect the hot water

    produced by the solar section, and provides the hot water

    flow that drives the absorption unit;

    - the cold storage tank (300 l) is used to store the chilled water

    produced by the absorption unit, and provides cold water to

    feed the fan-coil units.

    More details concerning the layout of the system, the

    models used to simulate the other components (solar collec-

    tors, storage tanks) and the reliability of such models can be

    found in (Evola et al., 2010).

    Afirstseriesof simulationswasperformedbyvaryingthesize

    of the hot storage tank (from 200 to 1000 l) and keeping the

    volume of the cold storage tank at the real value. Then, in

    asecondseriesofsimulations, thevolumeof thehotstoragetank

    was kept constant (400 l) and the cold storage tank was varied

    between 200 and 600 l. In all the simulations an insulating layer

    17th of August).madeupof 40mmof polystyrene is applied to the storage tanks.

    The simulations were run over one week (from the 11th to

    the 17th of August) by using, as input values for themodel, the

    Table 4 e Influence of the storage volume (up: hot storage e bochiller.

    Storage volume (hot water) [l] 200

    Chiller activation time from 10:10

    to 17:00

    Average daily cold production [kWh/day] 39.2

    Average daily thermal COP [] 0.705COP variation 1.0%

    Storage volume (cold water) [l] 200

    Chiller activation time from 10:50

    to 17:30

    Average daily cold production [kWh/day] 38.6

    Average thermal COP [] 0.708COP variation 0.6%a commercial single-effect LiBr/water absorption chiller has

    been described. The structure of the model makes it suitable

    for a general use, but in this context it has been applied to the

    absorption unit distributed by Rotartica, which is different

    from common LiBr absorption chillers as the thermal cycle is

    performed inside a rotating vessel. After defining the values of

    the parameters which best describe the geometry of the

    Rotartica chiller, the reliability of the model has been verified

    by comparing the simulated results to those collected in an

    experimental installation. The comparison was based on the

    values of the outlet water temperature and on the thermal

    power exchanged at each section, as no internal parameters

    ttom: cold storage) on the performance of the absorption

    400 600 800 1000

    10:50 11:20 11:50 12:20

    17:30 18:00 18:20 18:50

    39.0 38.9 38.8 38.7

    0.712 0.718 0.724 0.728

    d 0.8% 1.6% 2.3%

    300 400 500 600

    10:50 10:50 10:50 10:50

    17:30 17:30 17:30 17:30

    39.0 39.2 39.4 39.6

    0.712 0.716 0.719 0.722discharge, thus the daily operation has a duration that does

    not change noticeably as a function of the hot storage volume.

    On the whole, higher storage volume means lower average

    temperatures, which induces for the Rotartica absorption unit

    a slight decrease in the cold production but also a slight

    increase in the average thermal COP.

    On the other hand, a variation in the volume of the cold

    storage tank does not affect the driving conditions, thus the

    chiller activation time stays the same. However, in this case,

    higher storage volumemeans higher average temperatures for

    the chilled water, which improves the average thermal COP of

    the absorption unit and reduces the overall cold production.

    7. Conclusionsd 0.5% 1.0% 1.4%

  • (pressure, salt concentration, temperature) could be Bakhtiari, B., Fradette, L., Legros, R., Paris, J., 2011. A model for

    i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 6 ( 2 0 1 3 ) 1 0 1 5e1 0 2 81028measured inside the machine.

    Themodel shows a good agreement with the experimental

    data: the transient performance during two typical operation

    days is simulated with a satisfying accuracy, since the devia-

    tion between the instantaneous simulated and experimental

    values of cooling power and COP never exceeds 5%. The paper

    also verifies the capability of the model to describe the system

    performance on a long time basis: the results are very

    encouraging, as the error on the overall test campaign is

    around 1%.

    A fundamental condition to obtain such a high reliability

    is the good estimation of the chiller design parameters,

    based on the availability of design data and schemes

    provided by the manufacturers. In the paper, these results

    were obtained without any tuning or calibration of the input

    parameters.

    In addition, a consistency analysis was also performed to

    investigate the response of the model to a 10 K temperature

    step applied to the driving temperature. According to this test,

    the behaviour of the chiller is perfectly consistent with ther-

    modynamics; the time needed to reach steady-state operation

    after the temperature step is around 8 min.

    Finally, an example of practical application of the model is

    presented, where simulations are used to investigate into the

    influence of the storage volume on the chiller performance,

    in the specific case of the solar-assisted air-conditioning

    system installed at INES (Institut National de lEnergie Sol-

    aire, France) for the air-conditioning of some offices. The

    simulations allowed to understand that increasing the

    volume of the hot storage is beneficial in order to improve the

    average thermal COP, even though a slight reduction in the

    cold production and a shift in the operating time must be

    accounted for.

    The dynamic model presented in this paper is then a reli-

    able tool to evaluate the long-term behaviour of a single-effect

    LiBr/water absorption chiller, but also to follow its daily

    operational profile with good precision. Its use is suggested to

    study the interaction of the absorption unit with the other

    components of a solar-assisted cooling plant, with the aim of

    optimizing both the layout of the system and the control logic

    of the chiller.

    Acknowledgements

    The experimental installation has been financed in the

    framework of the European project SOLERA (FP6), coordinated

    by Fraunhofer ISE. The study of its performance has been

    conducted in the framework of the research project ORASOL

    ANR 06-PBAT-009-01.

    r e f e r e n c e s

    Alefeld, G., Radermacher, R., 1993. Heat Conversion Systems.CRC, USA.analysis and design of H2OeLiBr absorption heat pumps.Energy Convers. Manage. 52, 1439e1448.

    Cengel, Y., 1997. Introduction to Thermodynamics and HeatTransfer. Mc Graw Hill, USA.

    Eicker, U., 2003. Solar Technologies for Buildings. John Wiley &Sons, USA.

    Evola, G., Le Pierres, N., Boudehenn, F., Papillon, P., 2010.Description and validation of a dynamic tool for the modelingof a solar-assisted absorption cooling machine. In:Proceedings of EUROSUN International Conference, Graz.

    Florides, G.A., Kalogirou, S.A., Tassou, S.A., Wrobel, L.C., 2003.Design and construction of a LiBrewater absorption machine.Energy Convers. Manage. 44, 2483e2508.

    Garcia Cascales, J.R., Vera Garcia, F., Cano Izquierdo, J.M., DelgadoMarin, J.P., Martinez Sanchez, R., 2011. Modeling an absorptionsystem assisted by solar energy. Appl. Therm. Eng. 31,112e118.

    Gilchrist, K., Lorton, R., Green, J.R., 2002. Process intensificationapplied to an aqueous LiBr rotating absorption chiller with dryheat rejection. Appl. Therm. Eng. 22, 847e854.

    Gnielinski, V., 1976. New equations for heat and mass transfer inturbulent pipe and channel flow. Int. J. Chem. Eng. 16,359e367.

    Gomri, R., 2010. Investigation of the potential of application ofsingle effect and multiple effect absorption cooling systems.Energy Convers. Manage. 51, 1629e1636.

    Howell, R.H., Sauer, J.H., Coad, J.W., 2005. Principles of Heating,Ventilation and Air Conditioning. American Society ofHeating, Refrigeration and Air Conditioning Engineers.

    Incropera, F., De Witt, D., Bergman, T., 2006. Introduction to HeatTransfer. John Wiley & Sons, USA.

    Izquierdo, M., Lizarte, R., Marcos, J.D., Gutierrez, G., 2008. Airconditioning using an air-cooled single-effect lithium bromideabsorption chiller: results of a trial conducted in Madrid inAugust 2005. Appl. Therm. Eng. 28, 1074e1081.

    Jeong, S., Kang, B.H., Karng, S.W., 1998. Dynamic simulation of anabsorption heat pump for recovering low-grade waste heat.Appl. Therm. Eng. 18, 1e12.

    Kohlenbach, P., Ziegler, F., 2008a. A dynamic simulation modelfor transient absorption chiller performance. Part I: the model.Int. J. Refrigeration 31, 217e225.

    Kohlenbach, P., Ziegler, F., 2008b. A dynamic simulation modelfor transient absorption chiller performance. Part II:numerical results and experimental verification. Int. J.Refrigeration 31, 226e233.

    Massey, B., Ward-Smith, J., 1998. Mechanics of Fluids. Taylor &Francis, UK.

    Monne, C., Alonso, S., Palacin, F., Guallar, J., 2011. Stationaryanalysis of a solar LiBr e H2O absorption refrigeration system.Int. J. Refrigeration 34, 518e526.

    Myat, A., Thu, K., Kim, Y.D., Chakraborty, A., Chun, W.G., Ng, K.C.,2011. A second law analysis and entropy generationminimization of an absorption chiller. Appl. Therm. Eng. 31,2405e2413.

    Rivera, W., Xicale, A., 2001. Heat transfer coefficient in two phaseflow for the water/lithium bromide mixture used in solarabsorption refrigeration systems. Solar Energy Mater. SolarCells 70, 309e320.

    Rogers, G., Mayhew, Y., 1992. Thermodynamic and TransportProperties of Fluids: SI Units, fourth ed. BlackwellPublishers, UK.

    Shin, Y., Seo, J.A., Cho, H.W., Nam, S.C., Jeong, J.H., 2009.Simulation of dynamics and control of a double-effectLiBreH2O absorption chiller. Appl. Therm. Eng. 29, 2718e2725.

    Proposal and validation of a model for the dynamic simulation of a solar-assisted single-stage LiBr/water absorption chiller1. Introduction2. Description of the model2.1. Generator and absorber2.2. Condenser and evaporator2.3. Heat exchangers2.4. Other devices

    3. Definition of the parameters4. Experimental verification5. Consistency analysis6. Use of the simulations for the system improvement7. ConclusionsAcknowledgementsReferences