Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The...

24
www.belimo.com 1 Turnkey automation station MONICO-.. • Forms an efficient fire protection system together with the motorisation sets BF(G)24MP • Completely wired controller in matching control cabinet • For control and monitoring of fire dampers via MP-Bus • As stand-alone or master/slave configuration Technical data Electrical data Power supply voltage AC 230 V ±15%, 50/60 Hz Internal supply voltage of controller 24 VAC Connection Terminal strips, max. 250 VAC Cable diameter 0.5…2.5 mm 2 Bus connection MP-Bus 2-wire, conductor length up to 800 m @ 0.75 mm 2 Connection of up to 8 Top Line fire protection actua- tors Inputs/outputs Digital inputs Connection of floating contacts from the fire alarm and ventilation system. Supply from controller, 6 mA Digital outputs 2 relay outputs for fan release and transmission of the fault report. Switching capacity 250 VAC, 2A Safety Protection class II totally insulated Degree of protection IP65 EMC CE according to 89/336/EEC Mode of operation Type 1 (acc. to EN 60730-1) Ambient temperature range –10 ... +60°C Non-operating temperature range –20 ... +70°C Ambient humidity range 5 ... 95% RH, non-condensating (EN 60730-1) Maintenance Maintenance-free Dimensions/weight Dimensions 420 x 314 x 143 mm (H x W x D) Weight approx. 4.8 kg Safety notes ! The MONICO system solution is not allowed to be used outside the specified field of application, especially in aircraft or in any other airborne means of transport. Please note: 230 V power supply voltage! Only components explicitly approved for this purpose by Belimo are allowed to be used for the MONICO system solution. The network may only be configured, and the system configuration changed, by suitably trained and authorised personnel! Check the relevant standards and national directives prior to planning the system. Consult a fire protection expert if necessary. Technical data sheet MONICO-.. Products no longer available

Transcript of Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The...

Page 1: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

www.belimo.com 1

Turnkey automation station MONICO-..• Forms an efficient fire protection

system together with the motorisation sets BF(G)24MP

• Completely wired controller in matching control cabinet

• For control and monitoring of fire dampers via MP-Bus

• As stand-alone or master/slave configuration

Technical data

Electrical data Power supply voltage AC 230 V ±15%, 50/60 HzInternal supply voltage of controller 24 VACConnection Terminal strips, max. 250 VAC

Cable diameter 0.5…2.5 mm2

Bus connection MP-Bus 2-wire, conductor length up to 800 m @ 0.75 mm2

Connection of up to 8 Top Line fire protection actua-tors

Inputs/outputs Digital inputs Connection of floating contacts from the fire alarm and ventilation system.Supply from controller, 6 mA

Digital outputs 2 relay outputs for fan release and transmission of the fault report.Switching capacity 250 VAC, 2A

Safety Protection class II totally insulatedDegree of protection IP65EMC CE according to 89/336/EECMode of operation Type 1 (acc. to EN 60730-1)Ambient temperature range –10 ... +60°CNon-operating temperature range –20 ... +70°CAmbient humidity range 5 ... 95% RH, non-condensating (EN 60730-1)Maintenance Maintenance-free

Dimensions/weight Dimensions 420 x 314 x 143 mm (H x W x D)Weight approx. 4.8 kg

Safety notes

!

• The MONICO system solution is not allowed to be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.

• Please note: 230 V power supply voltage!• Only components explicitly approved for this purpose by Belimo are allowed to be

used for the MONICO system solution.• The network may only be configured, and the system configuration changed, by suitably

trained and authorised personnel!• Check the relevant standards and national directives prior to planning the system. Consult

a fire protection expert if necessary.

Technical data sheet MONICO-..

Products no longer available

Page 2: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampers

2 www.belimo.com

Electrical installation

Master station connection(MONICO-1M)

Slave station connection(MONICO-1S)

System configuration

Controller in MONICO-.. automation station The controller is installed in the automation station and completely wired. After the fire dampers have been connected via the MP-Bus, the digital inputs/outputs and possibly further slave stations have been connected and the supply voltage has been applied, the MONICO-.. fire protection system is ready for parameterisation and commissioning.

Motorisation sets BF(G)24MP The motorisation sets (BF24MP and BFG24MP) consist of a communications-capable fire protection actuator of the Top Line series with an integrated thermoelectrical tripping device and a communication and power supply unit for connection to the MP-Bus® network.These motorisation sets are only provided to fire damper manufacturers!

External operating panel Z-PKT0FSW210 The optionally available operating panel Z-PKT0FSW210 allows the MONICO-.. fire protection system to be decentrally controlled and operated. The operating panel is connected to the pLAN bus of the controller.

MONICO-..

Mechanical installation

Control cabinet installation The control cabinet is fastened directly to the wall with 4 screws (for dimensions / drill hole distances, see page 24).Protective caps must be attached (guarantees protection class II).Observe enclosed installation instructions!

TC1

QF1

XP1

XA

TC1

QF1

XP1

XA

FU3 / 4

TCONN

GND

FU3 / 4

TCONN

GND

Master and slave station designations

TC1 Transformer 230/24 V, 30 VAQF1 Automatic circuit breaker, primaryFU3 / 4 Fuse, secondary

XP1 Terminal strip for mains connection

XA Terminal strip for bus connection and digital inputs/outputs

TCONN pLAN connection stripGND Ground connection rail

Products no longer available

Page 3: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampers

www.belimo.com 3

PEXP1 L N

XA MP GND

pLANTCONN MONICO-1S

AC 230 V

PEXP1 L N

C4XA NO4 C5 NO5 IDC1 ID1 IDC1 ID2 MP GND

pLANTCONN MONICO-1M

AC 230 V

Electrical installation (Continued)

Wiring diagramMaster

Wiring diagramSlave

pLAN connection TCONN pLAN connection strip

Slave station connection

Relay outputs

Digital inputs

2-wire MP-Bus® (BF(G)24MP set)

Master station connection

2-wire MP-Bus® (BF(G)24MP set)

MONICO-..

Fan release

Fault

Fire alarm system

Ventilation system

The jumpers J14 and J15 must be attached at position 1 and 2.

6 5 4 3 2 1 0

1 2 3 1 2 3J14 J15

ConnectionsTerminal screw connection Telephone plug pin Function0 – Grounding for shielded cable1 12 2 GND3 3 Rx– / Tx–4 4 Rx+ / Tx+5 5 GND6 –

Products no longer available

Page 4: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampersMONICO-..

4 www.belimo.com

1 2 3 4 5 6 7

BKN230-24MP

BF(G)24TL-T-ST

AC 230 V

MP GND

MPGND

PC Tool

LED

M

24 V

24 V Ya

MP BUSTECHNOLOGY BY BELIMO

®

Electrical installation (Continued)

pLAN connection

Connection of fire damperto MP-Bus

User interface

Operation of the system

Master station operating panelThe master station has an operating panel, consisting of an LCD display and a keyboard with 6 keys.

MONICO-.. MONICO-.. MONICO-..

BF(G)24MP set

max. 200 m

2 x 2 wires twisted (0.5 mm2) shielded

Master Slave Slave

Optional smoke detector contact (floating)

Prg

1 2 3 4

5 6 7

Esc

Operating panel on master stationNo. Display / key Function1 LCD Display infos

2 Prg

1 2 3 4

5 6 7

EscDisplay and reset faults

3 Prg Open navigation menus4 Esc To overview / back5

Prg

1 2 3 4

5 6 7

Esc

Scroll down

6

Prg

1 2 3 4

5 6 7

Esc

Scroll up

7

Prg

1 2 3 4

5 6 7

Esc

Confirm entry

Key combinations on master Key combinations for external operating panel

Software information display Prg

1 2 3 4

5 6 7

Esc +

Prg

1 2 3 4

5 6 7

Esc

(> 3 s) Software information display

Prg

1 2 3 4

5 6 7

Esc

/

Prg

1 2 3 4

5 6 7

Esc

(> 10 s)

Call up addressing functions Prg

1 2 3 4

5 6 7

Esc +

Prg

1 2 3 4

5 6 7

Esc

+ Connect supply voltage Set display contrast Prg

1 2 3 4

5 6 7

Esc + Prg +

Prg

1 2 3 4

5 6 7

Esc

/

Prg

1 2 3 4

5 6 7

Esc

Call up addressing functions

Prg

1 2 3 4

5 6 7

Esc

/

Prg

1 2 3 4

5 6 7

Esc

(> 5 s)

Slave addressingPrg

1 2 3 4

5 6 7

Esc +

Prg

1 2 3 4

5 6 7

Esc

+ Connect supply voltage (controller) *

Jump between master / slave Prg + Esc

* Address of the operating panel must be 0!

Products no longer available

Page 5: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampers MONICO-..

www.belimo.com 5

Prg

Esc

M01…M07

Menu structure

Keys Menu tree

Main menu

Installation(password)

Maintenance(password)

History Clock Inputs/Outputs

Info Network

Language selection

Networkconfiguration

Fanrelease

Actuator section

Addressing

Scenariomanagement

Configuration offire alarmand ventilation input

Configuration ofreports

pLANmanagement

Reset to basic setting

Manualsystem test

Automatic system test

Test of local actuator

Adaptation

Display switch-off delay

Actuator info

Faults

Manualsystem test

Automaticsystem test

Test of localactuator

Addressing

Adaptation

Display switch-off list

Actuator info

Storedfaults

Test results

Faults of entiresystem

Test results ofentire system

Setdate / time

Setday of the week

Statusdisplay

Reset buffer

System info Actuatorstatus

Lasttest result

pLANstatus

System status

Interface / modem / printer configuration

Text designation for system

Products no longer available

Page 6: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampersMONICO-..

6 www.belimo.com

Commissioning

System configurationchecklist

Procedure1) Check electrical connection of system and

switch on entire system2) Select language3) Address stations and external operating

panel (if present), see below4) Reset all stations to basic setting5) Set the number of stations connected to

the network on the master6) Release necessary digital inputs on

the master (for fire alarm system, input of ventilation system)

7) Set time of day

8) If desired, set parameters for automatic system test

9) If GSM modem is present, set SMS configuration

10) Set number of connected actuators at all stations

11) Address digital actuators12) Set desired scenario at each station13) Set groups and system status to “On”14) Trigger system test to test entire system

Systems with slave For systems with slave(s), an external operating panel(Z-PKT0FSW210) is required for commissioning!

Software parameter factory settings See table on page 21

Application software Same software for master and slaveThe stations are supplied with preinstalled application software. The same software is installed in the master and the slave.

Addressing System division and network addressesMaster and slave are addressed from 1 to max. 12 or 32 for one operating panel.

32

Master Slave Slave

MP

BU

ST

EC

HN

OL

OG

Y B

Y B

EL

IMO

®

MP

BU

ST

EC

HN

OL

OG

Y B

Y B

EL

IMO

®

MP

BU

ST

EC

HN

OL

OG

Y B

Y B

EL

IMO

®

230

VAC

230

VAC

230

VAC

BF24MP set orBFG24MP set

BF24MP set orBFG24MP set

BF24MP set orBFG24MP set

MP1

MP2

MP3

to MP8

MP1

MP2

MP3

MP1

MP2

MP3

RS232

Group 1 Group 2 Group 3

to MP8 to MP8

pLAN

Products no longer available

Page 7: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampers MONICO-..

www.belimo.com 7

Commissioning (Continued)

Addressing of the controllers Addressing of the master:– Keep “UP” and “ALARM” key pressed– Switch on power supply of the master– The following display will appear after a few seconds:

PLAN ADDRESS: 1

UP: INCREASE

DOWN: DECREASE

ENTER: SAVE & EXIT

The master always has address 1!(This is the factory setting!)

– The desired address can be set with the “UP” and “DOWN” key and saved with the “ENTER” key.

Addressing of external operating panel:Address 32 is already set for the external operating panel upon delivery (default value)!– Keep all 3 “arrow keys” pressed for at least 5 s

Display address

setting………………… :32

I/O Board address:02

Address of the external operating panel

Shows the address of the controller to which the operating panel is connected

P:01 Adr Priv/Shared

Trm1 32 Sh

Trm2 None --

Trm3 None -- Ok?YES

Should always be set to “Sh” (Shared)

Confirm any changes by entering “YES”

See also the separate documentation (data sheet) of the external operating panel.

Addressing of slave (factory setting: address 2):– Connect external operating panel to slave– Keep all 3 “arrow keys” pressed for at least 5 s

Display address

setting………………… : 0

Set address of external operating panel to 0!

The following display appears:

Display ADDRESS

Changed

– Switch off power supply of slave– Keep “UP” and “ALARM” key on the external operating panel pressed– Switch power supply on again– The following display will appear after a few seconds:

PLAN ADDRESS: 2

UP: INCREASE

DOWN: DECREASE

ENTER: SAVE & EXIT

Set address for the slave

– The desired address can be set with the “UP” and “DOWN” key and saved with the “ENTER” key.

Important:After the slaves have been addressed, set the address of the external operating panel back to 32!

Products no longer available

Page 8: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampersMONICO-..

8 www.belimo.com

Main menu

Main menuThe main menu is accessed by pressing the “Esc” key several times.

Display

Group: 00/00 M01

Function: SLAVE

Group status : OFF

System status: OFF

Shows in which group you are / how many groups are present in total.

Shows function of the respective station (master / slave).

Switches the individual groups on and off. Factory setting: ON

Switches the overall system on and off. Factory setting: OFF

Display

Group: 00/00 M02

Local configuration

Actuators num.:

Enter number of connected digital and standard actuators.

Enter number of digital actuators (BF-Top). Factory setting: 0

Display

Group: 00/00 M03

Actuators status:

1 2 3 4 5 6 7 8

C C C C C C C C

Display of the actuator positions.

1…8: digital actuators.

C = closed, O = open

Display

Group: 00/00 M04

Safety function act.

1 2 3 4 5 6 7 8

N N N N N N N N

Safety function display(triggered by BAE, smoke detector, excess temperature of actuator).

Has safety function been triggered?

N = no, Y = yes

Display

Group: 00/00 M05

Dig. act. fault:

1 2 3 4 5 6 7 8

N N N N N N N N

Display for fault in actuator.(overload, MP-Bus, etc.)

Is a fault present?

N = no, Y = yes

Display

Group: 00/00 M06

Last test result:

1 2 3 4 5 6 7 8

N N N N N N N N

Display of the last test result. Was a fault determined during the last test run?

N = no, Y = yes

Display

Group: 00/00 M07

Fault reset:

1 2 3 4 5 6 7 8

N N N N N N N N

Allows a pending fault message to be reset. Remark: If the fault is still present, it cannot be reset.

Reset fault?

N = no, Y = yes

Esc

Main menu

Products no longer available

Page 9: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampers MONICO-..

www.belimo.com 9

Main menu (Continued)

Display

Group: 00/00 M08

Fan status : OFF

Fault status: OFF

Status display of the digital outputs.

Digital output contact for fan release: Status

Digital output contact for collective fault: Status

Display

Group reset: M09

01:0 02:0 03:0 04:0

05:0 06:0 07:0 08:0

09:0 10:0 11:0 12:0

Status display of the stations connected to the network. Non-connected stations are not displayed.

0 = inactive, not present, 1 = active

Display

Group on/off: M12

01:0 02:0 03:0 04:0

05:0 06:0 07:0 08:0

09:0 10:0 11:0 12:0

Slave on = 1

Slave off = 0

Installation

Password entry

Display

Installation Menu

Password: 0000

The installation menu is protected by a password.

Enter passwords using the scroll keys.

Language selection

Display

Language: C01

DEUTSCH

Select menu language.

Select menu language.

Network configuration

Display

Contr. config. C02

Num. of controllers

(pCOxs) present in

the pLan: 00 Enter number of controllers connected to the network. Factory setting: 00

Fan release

Display

C03

Delay of actions

on startup:

30 s Enter fan startup delay. Factory setting: 30 s

Installation

Languageselection

Networkconfig.

Installation

Fanrelease

Installation

Products no longer available

Page 10: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampersMONICO-..

10 www.belimo.com

Installation (Continued)

Actuator selection

Display

MPBUS Act. conf. C04

Actuators num.: 0 Enter number of connected actuators.

AddressingThe actuators can only be addressed if “Group config.” in display C05 is set to “Yes”. After the actuators have been addressed, “Group config.” must be set to “OFF” again!The digital actuators can be addressed in two ways: – manually (MAN, with hand crank)– automatically (AUTO, with serial number of the actuator).

Manual addressing

Display

MPBUS Act. conf. C05

Group config: No

Current act.:

Configuration group: Yes = addressing of the actuators possible, No = standard operation of the system

No / Yes

Actuator that is currently being queried

Display

Actuator 1/ C06

Address. type: MAN

Set address : No

Display of the current actuator (act. 1 = MP1).

Select method: manual (MAN) / automatic (AUTO).

Start manual addressing (select “Yes”) *.

* NoteAfter “Yes” has been selected, the hand crank of the respective actuator must be operated within 5 min-utes. The corresponding actuator then sends its serial number to the controller and is programmed with the corresponding MP address (here MP1). After the addressing has taken place, the display changes from “Yes” to “No”.

Automatic addressing

Display

Actuator 1/ C06

Address. type: AUTO

Set address : No Select automatic addressing.

Display

Actuator 1/ C07

Serial number:

00000-00000-000-000

Set address: No

Assigns the address (in this case MP1) to the actuator.

Enter the serial number of the respective actuator (with scroll and “ENTER” keys).

Yes = Save address in actuator.

Manualaddressing

Installation

Actuatorselection

Installation

Automaticaddressing

Installation

Products no longer available

Page 11: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampers MONICO-..

www.belimo.com 11

Installation (Continued)

Scenario management3 predefined scenarios are available: 1) 1:1: Only the fire damper whose sensor (temperature, smoke) is triggered will close. 2) All: As soon as a sensor (temperature or smoke) in the network is triggered, all fire dampers in the entire network will close. 3) 2: Dependence between each two fire dampers (MP1-MP2, MP3-MP4, MP5-MP6, MP7-MP8).

Display

Scenario Manag. C22

Enable scenario ALL

in the pLAN: No Activate scenario “All”? Factory setting: No

Display

Scenario Manag. C23

Enable scenario 2

on the pLAN: No Yes = Scenario 2 is selected for this station.

Display

C24

Configure local or

remote controller?

LOCAL

Selects the controller in which the scenario is to be set.

Local = master, distributed = slaves

Display

C25

Read scenario’s conf

of controller: 02

Read status: STOP

Reads out the scenario settings of the slaves from the master.

Read in a scenario from a slave.

Reading status

Display

Actuator 1 C26

Scenario : CUSTOM

Group dep.: 02

Actuat.dep: 08

The scenario “CUSTOM” is activated for actuator 1.

A customer-specific scenario could be set here.

Actuator 1 is dependent on actuator 8 in group 2.

Display

Save the current C36

scenario configurat.

in the controller:00

Write status: STOP

Saves a set scenario in the corresponding slave.

Enter controller address.

STOP / START

Display

Scenario Manag. C37

All actuators are

configurated with

scenario ALL!

Display indicating that the scenario “ALL” has been activated for all actuators.

Scenario “ALL” is active.

Scenariomanagement

Installation

Products no longer available

Page 12: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampersMONICO-..

12 www.belimo.com

Installation (Continued)

Configuration of the inputs of the fire alarm and ventilation system

Display

Master Control. C49

Enable F&S alarm

from D.I.: Yes

Is a fire alarm system connected to the master?

Yes / No. Factory setting: Yes

Display

Master Control. C50

Enable D.I. from

ventilation sys: No

Close fire dampers when the ventilation system is switched off? (Protection of tangible assets when ventilation system is switched off)

No / Yes. Factory setting: No

Configuration of the actuator messages

Display

Actuator 1/ C51

Enable indication of

Safety message : Yes

Gen. fault msg.: Yes

You can define for each actuator whether the respective messages and faults are to be output. These settings may only be changed after consultation with the person responsible for safety!

Transmit safety message? Factory setting: Yes

Transmit fault message? Factory setting: Yes

pLAN management

Display

pLan Management C61

Enable fault detect

offline loc.: Yes

offline pLAN: Yes

The pLAN messages can be switched off if necessary.

Local message display: Yes / No. Factory setting: Yes

pLAN message display: Yes / No. Factory setting: Yes

Config. offire alarm and ventila-tion input

Installation

Messageconfig.

Installation

pLANmanage-ment

Installation

Products no longer available

Page 13: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampers MONICO-..

www.belimo.com 13

Installation (Continued)

Display

pLan Management C62

Delay fault detect.

offline loc.: 000s

offline pLAN: 000s

A fault is displayed when the network is interrupted. The delay time “Disconnection until fault display” can be set here.

Local delay time in s. Factory setting: 30 s

pLAN delay time in s. Factory setting: 30 s

Reset to basic setting

Display

C64

Reset values

to default: No

Reset parameters of the respective station to their basic setting?

No / Yes. Factory setting: See Appendix

Manual system test

Display

Manual test C65

Start test: No

A test run of the entire network can be manually triggered here. All actuators move into the safety position (Closed) and then open again.

Trigger test run? No / Yes

Automatic system test

Display

C66

Enable automatic

self-test: No

Interval: EVERY 24h

The system can be set here so that it automatically carries out a periodic self-test of the entire network. The period type and the time can also be set.

Every 24 hours / monthly / weekly / every 48 hours

Display

Self-test config C67

Start on : Monday

Time : 00 : 00

Setting of start day and time.

Enter start day.

Enter time.

Reset to basicsetting

Installation

Manual system test

Installation

Automaticsystem test

Installation

Products no longer available

Page 14: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampersMONICO-..

14 www.belimo.com

Installation (Continued)

Display

Delay before C68

save the result of

self-test: 300s

Saves the test result in the history file.

Set delay time in s. Factory setting: 300 s

Test of local actuator

Display

Local act. test: C69

A1:0 A2:0 A3:0 A4:0

A5:0 A6:0 A7:0 A8:0

Possibility of testing a single actuator within the network.

0 = Standard operation1 = Start test run

When the test run has been successfully completed, the display automatically returns to 0.

Adaptation

Display

Adaptation C70

A1:0 A2:0 A3:0 A4:0

A5:0 A6:0 A7:0 A8:0

Adaptation of a new actuator to the fire damper.

0 = Standard operation1 = Start adaptation

When the adaptation has been successfully completed, the display automatically returns to 0.

Display switch-off delay

Display

C71

LCD Backlight-off

delay: 000s

The switch-off delay time of the display background lighting can be set.

Switch-off delay in s. Factory setting: 120 s

Actuator info

Display

Actuator 1/ C72

ver.HW : 00000

ver.BIOS: 0000000000

00000-00000-000-000

Display of hardware / software version.

Display of hardware version.

Display of BIOS and software version.

Display of actuator serial number.

New password

Display

INSTALL. Menu C80

New password: 0000

Set new password using the scroll keys.Confirm with “ENTER” key.

Enter new password.

Automaticsystem test

Installation

Adaptation

Installation

Display switch-offdelay

Installation

Actuator info

Installation

Test of localactuator

Installation

Products no longer available

Page 15: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampers MONICO-..

www.belimo.com 15

Maintenance

Password entry

Display

Maintenance Menu

Password: 0000

Enter the password using the scroll keys.Confirm with “ENTER” key.

Enter password.

Manual system test

Display

Manual test A01

Start test: No

A test run of the entire network can be manually triggered here. All actuators move into the safety position (Closed) and then open again.

Trigger test run? No / Yes

Automatic system test

Display

A02

Enable automatic

self-test: No

Interval: EVERY 24h

The system can be set here so that it automatically carries out a periodic self-test of the entire network. The period type and the time can also be set.

Every 24 hours / monthly / weekly / every 48 hours

Display

Self-test config A03

Start on : Monday

Time : 00 : 00

Setting of start day and time.

Enter start day.

Enter time.

Display

Delay before A04

save the result of

self-test: 000s

Saves the test result in the history file.

Set delay time in s. Factory setting: 300 s

Test of local actuator

Display

Local act. test: A05

A1:0 A2:0 A3:0 A4:0

A5:0 A6:0 A7:0 A8:0

Possibility of testing a single actuator within the network.

0 = Standard operation1 = Start test run

When the test run has been successfully completed, the display automatically returns to 0.

Manualsystem test

Maintenance

Automaticsystem test

Maintenance

Test of local actuator

Maintenance

Products no longer available

Page 16: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampersMONICO-..

16 www.belimo.com

Maintenance (Continued)

AddressingThe actuators can only be addressed if “Group config.” in display A06 is set to “Yes”. After the actuators have been addressed, “Group config” must be set to “OFF” again!The digital actuators can be addressed in two ways: – manually (MAN, with hand crank)– automatically (AUTO, with serial number of the actuator).

Display

MPBUS Act. conf. A06

Group config: No

Current act.:

Display of the current actuator (Act. 1 = MP1).

Configure group: Yes / No.

Manual addressing

Display

Actuator 1/ A07

Address. type: MAN

Set address : NoSelect method: manual (MAN) / automatic (AUTO).

Start manual addressing (select “Yes”) *.

* NoteAfter “Yes” has been selected, the hand crank of the respective actuator must be operated within 5 min-utes. The corresponding actuator then sends its serial number to the controller and is programmed with the corresponding MP address (here MP1). After the addressing has taken place, the display changes from “Yes” to “No”.

Automatic addressing

Display

Actuator 1/ A07

Address. type: AUTO

Set address : No

Select automatic addressing.

Display

Actuator 1/ A08

Serial number:

00000-00000-000-000

Set address: No

Assigns the address (in this case MP1) to the actuator.

Enter the serial number of the respective actuator (with scroll and “ENTER” keys).

Yes = Save address in actuator.

Adaptation

Display

Adaptation A23

A1:0 A2:0 A3:0 A4:0

A5:0 A6:0 A7:0 A8:0

Adaptation of a new actuator to the fire damper.

0 = Standard operation1 = Start adaptation

When the adaptation has been successfully completed, the display automatically returns to 0.

Display switch-off delay

Display

A24

LCD Backlight-off

delay: 120s

The switch-off delay time of the display background lighting can be set.

Switch-off delay in s. Factory setting: 120 s

Adaptation

Maintenance

Automaticaddressing

Maintenance

Display switch-offdelay

Maintenance

Manualaddressing

Maintenance

Products no longer available

Page 17: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampers MONICO-..

www.belimo.com 17

Maintenance (Continued)

Actuator info

Display

Display of software number / serial number of the actuator.

Display of BIOS and software version.

Display of actuator serial number.

New password

Display

MAINTENANCE Menu A33

New password: 0000

Set new password using the scroll keys.Confirm with “ENTER” key.

Enter new password.

Actuatorinfo

Maintenance

History

Viewing local fault history

Display

Fault history: H01

N°00 00:00 00/00/00

NO FAULTS!

Fault number Time / date

Fault in plain text.

Display

H02

Erase local faults

history memory: No

Delete fault history at this station.

Delete? No / Yes.

Viewing local test history

Display

Test history: H03

n°00 00:00 00/00/00

1 2 3 4 5 6 7 8

N N N N N N N N

Fault number Time / date

Fault determined during test run? No / Yes (N / Y).

Display

H04

Erase local test

history memory: No

Delete test history at this station?

No / Yes

Stored faults

History

Testresults

History

Actuator 1/ A25

ver.BIOS: 0000000000

00000-00000-000-000

Products no longer available

Page 18: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampersMONICO-..

18 www.belimo.com

History (Continued)

Viewing fault history of entire system

Display

Stored Master H05

Fault history:

Last update

status: wait...

Load histories of slaves into master.

The slaves send their history data to the master.

Display

Mast. al. hist.: H06

Group:00 N°00

00:00 00/00/00

NO FAULTS!

Select group and fault number.

Time / date

Fault in plain text.

Faults of entire system

History

Viewing test history of entire system

Display

Stored Master H07

Test history:

Last update

Status: wait...

Load saved test results of the slaves into the master.

The slaves send their history data to the master.

Display

Mast.test grp:00 H08

00/00/00 00:00

1 2 3 4 5 6 7 8

N N N N N N N N

Select group and fault number.

Date / time

Fault determined during test run? No / Yes (N / Y).

Test results of entire system

History

Clock

Setting date, time and day of week

Display

Today: K01

00:00 00/00/00

Shows set time and date.

Time / date

Display

Change time: K02

00:00 00/00/00

Day of week:

Set time and date.

Set day of week.

Set date, time

Clock

Set day of week

Clock

Products no longer available

Page 19: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampers MONICO-..

www.belimo.com 19

Status display

Inputs/outputs

External modem: For installation and parameterisation, see separate modem documentation

Inputs/outputs

Status display

Display

Digital Input I01

1: C 2: C 3: C

4: C 5: C 6: C

Shows the status of the digital inputs of the station.

C = closed, O = open

C = closed, O = open

Display

Digital Output I02

1: O 2: O 3: O

4: O 5: O

Shows the status of the digital outputs of the station.

C = closed, O = open

C = closed, O = open

Display

I03

BMS ID : 000

Speed : 1200 bps

Protocol : Carel

Shows ID number, transmission speed and transmission protocol

ID number of the system

Transmission speed

Transmission protocol

Display

Erase message I04

queue?

No

Shows inquiry to delete the internal buffer of the interface

Delete internal buffer of the interface: No / Yes

Display

Identification I09

Site ID: 01

Name: Building A

Shows text designation for the system

Text designation for system

Display

Groupe 01 I10

Name: Ground Floor

Shows text designation for the group

Text designation for group

Products no longer available

Page 20: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampersMONICO-..

20 www.belimo.com

Info

System info

Display

CAREL S.p.A. F01

Brugine (PD) Italia

Cod.: FLBELMFS0A

Ver.: 2.9 04/07/07

Information on the version of the installed application software.

Belimo application code

Version of the application software

Display

System info F02

Card type: pCO1xs

Bios:04.10 20/02/07

Boot:04.03 03/07/06

Display of the BIOS and boot version number.

BIOS version number

Boot version number

System info

Info

Network

Remark: The network menu is only displayed when at least one slave is connected to the master!

Actuator status

Display

Network status N01

Call group: 02

Selection of the group.

Select group number.

Display

Group: 02/04 N02

Actuators status:

1 2 3 4 5 6 7 8

C C C C C C C C

Status display of the actuators (group 02).

O = open / C = closed

Display

Group: 02/04 N03

Safety funct. active

1 2 3 4 5 6 7 8

N N N N N N N N

Status display of the safety function of the actuators.

A = active / N = not active

Last test result

Display

Group: 02/04 N04

Last test result:

1 2 3 4 5 6 7 8

N N N N N N N N

Status display of last test result: A = active / N = not active

Fault with digital actuator MP7, group 02.

Display

Group: 02/04 N05

Actuators fault:

1 2 3 4 5 6 7 8

N N N N N N N N

Fault with digital actuator MP7, group 02.

A = active / N = not active

Last test result

Network

Actuator status

NetworkProducts no longer available

Page 21: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampers MONICO-..

www.belimo.com 21

Software parameter factory settings

Parameters Menu page Factory setting (Range)

Group status M01 on

System status M01 off

Number of digital actuators M02 0 (0...8)Number of stations in pLAN C02 0 (1...15)Ventilation delay C03 30 s (0...999 s)Number of standard actuators C04 0 (0...2)Delay of standard actuators during startup C04 80 s (0...99 s)Scenario management C22, C23 no

Input of fire alarm system C49 yes

Input of ventilation system C50 no

Safety-relevant messages of the actuators C51 – C60 yes

Fault messages of the actuators C51 – C60 yes

pLAN management C61 yes

pLAN delay of fault display C62 30 s (0...99 s)Save test results of the automatic test run: Delay C68 300 s (0...999 s)LCD Backlight-off delay C71 120 s (0...999 s)

Status of the digital output contacts

Status of the digital outputs

Condition Selected scenario

“Fan release” Contact Fault Contact

System test (test of all dampers) 1, 2, or all OFF Open OFF OpenTest of an individual damper 1, 2, or all ON Closed OFF OpenpLAN interruption 1, 2, or all ON Closed ON ClosedSensor (channel, excess temperature, smoke detector) triggered 1 OFF Open ON ClosedSensor (channel, excess temperature, smoke detector) triggered 2 ON 1) Closed ON ClosedSensor (channel, excess temperature, smoke detector) triggered all OFF Open ON ClosedVentilation system off (dig. input open) 1, 2, or all ON Closed OFF OpenVentilation system on (dig. input closed) 1, 2, or all OFF 2) Open OFF OpenFire alarm system triggered (dig. input open) 1, 2, or all OFF Open OFF OpenFire alarm system in standard operation (dig. input closed) 1, 2, or all ON Closed OFF Open

1) Changes to OFF as soon as the last damper of the master controller has closed

2) Changes to ON as soon as the first damper of the master controller is open

Products no longer available

Page 22: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampersMONICO-..

22 www.belimo.com

Troubleshooting

Checking / maintenance Please consult the following table before calling the responsible maintenance service!

Display Meaning Solution

System ok!

System works perfectly, no further steps necessary.

System: Off

Group: Off

The overall system and the current group are switched off.

Select system and group and switch them on.

Fault display Possible cause Solution

System alarms

01: 02:■ 03: 04:

05: 06:

Shows in which group a fault is present (example: group 2).

= No fault■ = Fault

Update the faults stored in the History menu of the master (screen H5). Select group 2 in screen H6 and read out the detailed fault description. Carry out further steps according to the displayed fault.

Fault display Possible cause Solution

AL01

Fire&Smoke alarm

from D.I. (master)

External fire alarm system reports fire alarm and has closed all fire dampers.

Check the status of the fire alarm system.

Fault display Possible cause Solution

AL04

Fault messages

not available

actuator 1

The bus connection or the supply voltage to the corresponding actuator is interrupted.

Check the bus connection and the supply voltage at the actuator.

Products no longer available

Page 23: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

Automation station for fire dampers MONICO-..

www.belimo.com 23

Troubleshooting (Continued)

Fault display Possible cause Solution

AL20

Fault: local unit

off-line pLAN

The local controller can no longer communi-cate via the pLAN bus.

Check pLAN bus connection.

Fault display Possible cause Solution

AL21

Fault: Group 02

off-line pLAN

The first slave (group 02) can no longer communicate via pLAN bus.

Check pLAN connection.

Fault display Possible cause Solution

AL52

Warning:

Actuator 1 closed

in dependence

Digital actuator 1 (MP1) has been closed in dependence on an other actuator.

Scroll further using the scroll keys until the responsible fault is displayed, e.g. “Channel temperature > 72°C digital actuator 2”. This means that actuator 1 has been closed in dependence on actuator 2 (scenario 2 is active).

Fault display Possible cause Solution

Group: 00/00 M03

Actuators status:

1 2 3 4 5 6 7 8

O O O O O * O O

Actuator is not correctly addressed. The display “* ” means that digital actuator 6 (MP6) has not been correctly addressed; the MP-Bus line or the power supply to the actuator is interrupted.

1) Check MP-Bus connection2) Check power supply of the actuator3) Address actuator 6 again

Products no longer available

Page 24: Products no longer - BELIMO automation station MONICO-.. ... Dimensions 420 x 314 x 143 mm ... The control cabinet is fastened directly to the wall with 4 screws ...

T3-M

ON

ICO

• en

• 09

.200

7 • S

ubje

ct to

cha

nges

Automation station for fire dampersMONICO-..

24 www.belimo.com

Dimensions

Dimensional diagram of MONICO-.. automation station

200

31492

4841

14 75119

330

420

128

143

Accessories

External operating panel Z-PKT0FSW210 See separate documentation.

Telephone cable Z-S90CONN000

Z-PLW0PGSM00 GSM kit

Cable with telephone plugs.

Dual-band modem kit with antenna, connecting cable and power pack (see separate documentation).

Z-PCO100MDM0 RS232 interface card for connecting GSM modem or serial protocol printer.

Products no longer available