Products for fixing to Steelwork and Decking
8.0 2019
-10
Products
Beam clamp TCS 0 Beam clamp TCS 1/ TCS 2 Beam clamp TCS 41
Clamping End SKLBulb Flat Steel Beam ClampThreaded Hook GHHook Sleeve SP
Roof Hanger Piercing ToolTRH LOT
Universal Joint UG Beam Clip P U-Holder SB 41
Toggle Stud Hole SawKD LS
Wedge Bolt ClampKB VBO C 40
-
Products for fixing to Steelwork and Decking
8.12019
-10
Beam Clamp - Single Support
The safety strap is bent on site to the form of the beam, so that it securely encompasses the edge of the beam flange.
Counter Nut
Basic application Application with Safety Strap
Inverted applicationStanding arrangement
Projecting length of rod not to exceed 10 x rod diameter diameter
Caution!a According to VdS-directive
the use of the Safety Strap is specified for pipes from DN 80 onwards!
Recommendation: Use Safety Strap also, when vibrations are expected.
Caution!a This arrangement is
allowed for parallel-flange beams only
1 2
Caution!a Take note of the torque:
TCS 0: Rotate 1 revolutionTCS 1 and TCS 2: Rotate min. 1 up to max. 1 1/2 revolutions.Then tighten locking nut.
-
Products for fixing to Steelwork and Decking
8.2 2019
-10
Universal Joint for any variable Angle Adjustment
Application as a brace
Application on an inclined beam
Braces can be installed with variable angles to their supporting surfaces. The combination with adapters al-lows for bracing arms with cross-sec-tions up to Threaded Tube G1".
Application on an inclinded beamThe pivot head in the Universal Joint can rotate freely, allowing adjustment to any angle.Tightening the locking nut against the adapter plate locks the position.
Caution!a In cases of dynamic loads it is
necessary to secure the Beam Clamp TCS using a Safety Strap, possible in connection with another Beam Clamp TCS.
A B
UGM8 - M16
UG FPM12 and M16
Figure A: Figure B:
Type: Type:UG M8 UG M12UG M10 UG M16
UG FP M12UG FP M16
During installation, make sure the correct side of the adapter plate faces towards the body of the Universal Joint.
Nominal size(NW)
Thread
DN 50 M 8> DN 50 - DN 100 M10> DN 100 - DN 150 M12> DN 150 - DN 200 M16
Note:a The Threaded Rod must be
clearly visible after being screwed into the pivot head.
Note:a Refer to VdS CEA directives
for the recommendation of supporting thread sizes for Sprinkler pipes.
-
Products for fixing to Steelwork and Decking
8.32019
-10
Beam Clamp TCS for Header Rails
with Beam ClampTCS 41
perm 160 N/mm²f perm 2 mm
Sample:Beam shape IPB 160 and distance A = 50 cm
Cantilever arrangement with Beam Clamp TCS 1
Channel from size 41/21/2.0 onwards
Beam permissible bending moment
Mb [Nm] IPB 100 50IPB 140 115IPB 160 180IPB 200 310IPB 240 540IPB 300 970IPB 340 1350
Note:a In cantilever arrangements,
the permissible bending moment of the beam must not be exceeded.
= =5 m
a
F
Fperm 180Nm0 5 m,
-------------------- 360N= =
FzulMba
---------=
with Beam Clamp TCS 0; 1; 2
Beam clamps can attach into either the open face or rear slots of the channel, leaving the channel unobstructed for further installations.
Vertical pipe on vertical beam -single support-
Horizontal pipe -twin mounting-Caution!
a T-Head Bolt and Holding Bracket must be used! This arrangement requires Sikla Channel 41/21 or larger. Check permissible loadings by referring to the catalogue!
-
Products for fixing to Steelwork and Decking
8.4 2019
-10
Beam Clip for Cross Support/ Dimensioning of Bolts
A B
Bolts used with Beam Clip:
P1: M 8 or M 10P2: M 12P3: M 16P4: M 16
… on thick flangesInstallation within the flange width
When dealing with very thick flanges, use shim plates.Shim plates exceeding 10 mm height must be tack welded to the crossmember!Sliding connection using Slide Set 41
(alternatively, if necessary, rigid connection using Blockset CC 41).
Installation
Determination of the required bolt length Lmin:
Arrangement A Arrangement B (with Hexagon Bolt) (with T-Head Bolt)
P1: Lmin = a + b + 37 [mm] P1: Lmin = b + 40 [mm]P2: Lmin = a + b + 43 [mm] P2: Lmin = b + 45 [mm]P3: Lmin = a + b + 48 [mm] P3: Lmin = b + 50 [mm]P4: Lmin = a + b + 55 [mm] P4: Lmin = b + 60 [mm]
-
Products for fixing to Steelwork and Decking
8.52019
-10
Beam Clip for Cross Member Support
Tandem cross support using Channel 41-75/65/3.0 D
Cross member supported by opposing web faces of 2 beams
Installation of a duct -suspended arrangement-
Installation of a duct -directly below the beam-
Note:a When using Beam Clips,
always make sure that - the wider side is located at the Channel and- the smaller side at the beam.
-
Products for fixing to Steelwork and Decking
8.6 2019
-10
Beam Clip for Cantilever Support
Double-sided cantilever crossmember
Arrangement with U Bolt
Caution!a The permissible bending
moment of the beam must not be exceeded!
Note:a Use U Bolts only as guides.
If they have to bear some vertical loads, U Bolts type DIN 3570 must be used.
Combination of Support Bracket and Channel with horizontal pipes running parallel to the IPB beam. When using this arrangement, make sure that no axial forces from the pipes exist, which may cause the supporting frame to twist.
-
Products for fixing to Steelwork and Decking
8.72019
-10
Beam Clip for Supports on Building Structures
Installation to cast-in channel Installation with anchors
Installation on a timber support Fixing of a timber joist to a steel beam
Fixing two beams crossing each other
Pipe running directly below the beam
Simotec Base Plate GPL can be used between the two beams.
-
Products for fixing to Steelwork and Decking
8.8 2019
-10
U-Holder SB 41
For secure support a minimal overhang of 50 mm is necessary.
Arrangement above or below the beam
In all arrangements, the loading capacity of the beam has to be considered. In cantilever arrange-ments especially the torsional stiffness has to be considered
Calculation of loading capacity for horizontal beam with Sikla Structural Analysis Software SiPlan.
Loading capacity per U-Holder SB 41 M10 on horizontal beam up to max. 5kN.
Lateral arrangement on the beam
Due to the geometry of the U-Holder, it is also possible to install Channels MS 41/41 and 41/21 D 90° rotated.
Caution!a In lateral arrangement
secure U-Holders against slipping (e.g. with 2 x TCS).
Type 41 D for profiles as of 41/41 D.
Direct installation of all rectangular single and double channels system 41 on steel beams with flange height up to max. 16 mm.
Note:a U-Holder SB should always
be used in pairs.
-
Products for fixing to Steelwork and Decking
8.92019
-10
Threaded Hooks GH for Cross Supports
... hooked onto angle irons ... hooked onto steel C-sections
Flange Nut NT Threaded Hook
Channel MS
Holding Bracket HK
Beam Clip
-
Products for fixing to Steelwork and Decking
8.10 2019
-10
Hook Sleves SP and Bulb Flat Steel Beam Clamp for single supports
Hook sleeves may be attached to flanges of C-section or Ibeam steelwork in cases when the beam is rotated through 90°
Installation to Bulb Flat steel (HP-profile)
M10
Combined arrangement as a base plate to a vertical cantilever down post.
The Threaded Hook has a hole Ø13mm and is therefore suitable for Threaded Rods GST M8, M10, M12.If used with a M8 Threaded Rod, a Flange Nut NT is required.
The Bulb Flat Beam Clamp is a solid connection element to fix pipework and electrical containment services to bulb flats HP (80 x 6 up to 160 x 6).
Caution!The load values stated in the catalogue refer only to the Hook Sleeves. The load capa-cities of the supporting beam or building structure must be checked separately.
-
Products for fixing to Steelwork and Decking
8.112019
-10
Hook Sleeves and Bulb Flat Beam Clamp for bracket installation
Note:a In cantilever arrangements,
the permissible bending moment of the supporting beam must not be exceeded.
Arrangements to C-section steelwork mounted above or below the beam
Cantilevers to C-section steelwork or angle irons
Suspended header rail to bulb flat steel (HP-profile).
-
Products for fixing to Steelwork and Decking
8.12 2019
-10
Clamping End set SKL for Installation to I-beam and C-section profiles between flanges
Cross-member support from webs between two opposing beam faces
Cutting length of the Channel = A - 25 mm
A = clearance between the flanges
Suitable for beams withA = 150 ... 800 mm
To be used in combination with Channels 41/41/2.5 or 41/45/2.5 and Holding Brackets HK 41.
Vertical beam and horizontal pipe run
Pipe run parallel to the beam
Note:a Each Clamping End set SKL
consists of two identical clamping plates. The support Channel between the end plates has to be cut to length on site. Fix the SKL set as deep as possible within the beam profile.
Note:a Bolting torque: min. 1 up to
max. 1 1/2 rotations
Lock after tightening!
A
Caution!a Excess tightening of the point
screws may result in deforma-tion of the beam.
-
Products for fixing to Steelwork and Decking
8.132019
-10
Toggle Stud KD for Installation to profiled Metal Decks
1 2
Crossmember mounting
Note:a Based on EN12845:
Pipes > Ø 50 mm must not be attached to trapezoidal steel roof panels.
Hole Saw LS with Centre Drill
Single support
Height adjustment
The Toggle Stud KD is completely pre-assemb-led, making installation safer and faster.
Weatherproof gasket and large washer reliably seals the opening
-
Products for fixing to Steelwork and Decking
8.14 2019
-10
Roof Hangers TRH for Installation to Profiled Metal Decking
Type RM
Type MS (with sound absorption) not allowed for sprinkler installations
only 2.5 kg
After piercing, ejector springs ensure a safe return stroke of the hole punches
Adjustable height stopper
Adjustable cut-ting width40 ... 100 mm
Piercing Tool LOT 3
Type M
Roof Hanger TRH RM with knurled nut for height adjustment
Locking nutHexagon Bolt SKT e.g. M8 x 100
Height of perforation does not affect the loading capacity of the Roof Han-ger TRH.
The greater the distance between the perforation and the bottom edge of the profile, the greater the stability of the Metal Decking Sheet.
Note:a Based on EN12845:
Pipes > Ø 50 mm must not be attached to trapezoidal steel roof panels.
Note:a According to the VdS guide-
lines for sprinkler installations, all bolting has to be locked, e.g. with a locking nut at the horizontal bolt.
-
Products for fixing to Steelwork and Decking
8.152019
-10
Fixing to Holorib and Cofrastra composite floors
Crossmember mounting
Wedge Bolt KB
Single support
Header Rail InstallationSingle support
Clamp VBO C 40