Product Specifications PSS 2A-1C13 F I/A Series … represent the latest Foxboro advancements in...

16
® Product Specifications PSS 2A-1C13 F I/A Series ® Electronic Pressure Transmitters Model IGP10 Gauge Pressure Transmitter for High Gauge Pressure Measurement These two-wire transmitters provide precise, reliable measurement of high gauge pressures, and provide a digital or analog output signal for local or remote configuration, monitoring, and control. FEATURES Gauge Pressure Ranges to 105 or 210 MPa (15 000 or 30 000 psi) Digital Output with either FoxCom, HART, or FOUNDATION Fieldbus Communication Protocol Analog Output can be either 4 to 20 mA, or 1 to 5 V dc for Low Power Installations Stainless Steel or Inconel Wetted Sensor for 105 MPa (15 000 psi) Transmitters, or High Strength 13-8 Molybdenum Stainless Steel for 210 MPa (30 000 psi) Transmitters Silicon Strain Gauge Sensors Successfully Field- Proven in Many Thousands of Installations Welded, Stainless Steel Pressure Capsule Assembly with bonded Strain Gauge Sensor provides an Airtight and Watertight Seal and Intrinsic Overpressure Protection Aluminum Housing has Durable, Corrosion- Resistant Epoxy Finish; 316 ss Housing also Available; both meet NEMA 4X and IEC IP66 Complies with NAMUR Part 1 Interference Immunity Requirement (EMC) CE marked; complies with EMC and ATEX European Directives Complies with Electromagnetic Compatibility Requirements of European EMC Directive 89/336/EEC by Conforming to following CENELEC and IEC Standards: EN 50081-2, EN 50082-2, IEC 801-2 through 801-6 Numerous Options and Accessories offered to expand the Capabilities of these Transmitters Standard 2-Year Warranty; 5-Year Optional

Transcript of Product Specifications PSS 2A-1C13 F I/A Series … represent the latest Foxboro advancements in...

Page 1: Product Specifications PSS 2A-1C13 F I/A Series … represent the latest Foxboro advancements in providing the greatest functionality for the largest number of applications at the

Product Specifications

PSS 2A-1C13 F

I/A Series® Electronic Pressure TransmittersModel IGP10 Gauge Pressure Transmitter forHigh Gauge Pressure Measurement

These two-wire transmitters provide precise, reliable measurement of high gauge pressures, and provide a digital or analog output signal for local or remote configuration, monitoring, and control.

FEATURES• Gauge Pressure Ranges to 105 or 210 MPa

(15 000 or 30 000 psi)

• Digital Output with either FoxCom, HART, or FOUNDATION Fieldbus Communication Protocol

• Analog Output can be either 4 to 20 mA, or 1 to 5 V dc for Low Power Installations

• Stainless Steel or Inconel Wetted Sensor for 105 MPa (15 000 psi) Transmitters, or High Strength 13-8 Molybdenum Stainless Steel for 210 MPa (30 000 psi) Transmitters

• Silicon Strain Gauge Sensors Successfully Field-Proven in Many Thousands of Installations

• Welded, Stainless Steel Pressure Capsule Assembly with bonded Strain Gauge Sensor provides an Airtight and Watertight Seal and Intrinsic Overpressure Protection

• Aluminum Housing has Durable, Corrosion-Resistant Epoxy Finish; 316 ss Housing also Available; both meet NEMA 4X and IEC IP66

• Complies with NAMUR Part 1 Interference Immunity Requirement (EMC)

• CE marked; complies with EMC and ATEX European Directives

• Complies with Electromagnetic Compatibility Requirements of European EMC Directive 89/336/EEC by Conforming to following CENELEC and IEC Standards: EN 50081-2, EN 50082-2, IEC 801-2 through 801-6

• Numerous Options and Accessories offered to expand the Capabilities of these Transmitters

• Standard 2-Year Warranty; 5-Year Optional

®

Page 2: Product Specifications PSS 2A-1C13 F I/A Series … represent the latest Foxboro advancements in providing the greatest functionality for the largest number of applications at the

PSS 2A-1C13 FPage 2

I/A Series PRESSURE TRANSMITTER FAMILY

The I/A Series Electronic Pressure Transmitters are a complete family of d/p Cell®, gauge, absolute, multirange, multivariable, and premium performance transmitters, as well as transmitters with remote or direct mount pressure seals, all using field-proven silicon strain gauge sensors and common topworks.

Select the electronics module you need to provide just the right level of intelligence for your application and budget. If your needs change, the modular design allows easy migration to standards including FoxCom, HART, FOUNDATION Fieldbus, and Analog 4 to 20 mA or 1 to 5 V dc.

DIGITAL OUTPUT VERSIONS

Electronic versions with a digital output include transmitters with FoxCom, HART, and FOUNDATION fieldbus communication protocols.

Digital FoxCom and/or 4 to 20 mA dc(Version “-D” Electronics)

FoxCom Digital Output

Provides Measurement Integration with I/A Series systems, transmission of multiple measurements, and workstation configuration and diagnostics. Also provides digital communications with a Hand-Held Terminal (HHT), Personal Computer (PC), or optional Liquid Crystal Display (LCD) Indicator with pushbuttons for local configuration and calibration.

FoxCom 4 to 20 mA Output

Allows direct analog connection to common receivers while still providing full Intelligent Transmitter Digital Communications with an HHT, PC, applicable I/A Series system FBMs, or optional LCD Indicator with pushbuttons for configuration and calibration.

Digital HART and 4 to 20 mA dc(Version “-T” Electronics)

4 to 20 mA with HART communications. Allows direct analog connection to common receivers while still providing full Intelligent Transmitter Digital Communications using a HART Model 275 Communicator.

Users having Model 275 HART Communicators for other devices can have them upgraded with Foxboro software to accommodate these transmitters. Also, Foxboro will make use of the HART Foundation library of registered DDs (Device Descriptors), and reload the Model 275 if the user desires to keep another supplier’s DD along with the Foxboro DD.

Digital FOUNDATION Fieldbus(Version “-F” Electronics)

The FOUNDATION fieldbus is an all digital, serial, two-way communication system which interconnects field devices, such as transmitters, actuators, and controllers. It is a Local Area Network (LAN) with built-in capability to distribute control application across the network. Fieldbus technology consists of a Physical Layer, a Communication Stack, and User Application Blocks.

ANALOG OUTPUT VERSIONS

Electronic versions with an analog output include transmitters with 4 to 20 mA dc and 1 to 5 V dc output signals.

4 to 20 mA dc Analog Output(Version “-A” Electronics)

Transmitters using the Electronics Version “-A” module are the most economical analog output transmitters available providing full configuration capability. They represent the latest Foxboro advancements in providing the greatest functionality for the largest number of applications at the least possible cost to you.

They even provide the ability to rerange to new calibrated ranges, using the standard LCD Indicator with on-board pushbuttons, without the need to apply calibration pressure.

They are explosionproof for use in Division 1 hazardous areas, and comply with Division 2 requirements.

1 to 5 V dc Analog Output(Version “-V” Electronics)

Used for low power, low voltage applications. This transmitter provides:

• 1 to 5 V dc Output Signal• 9 V dc Minimum Voltage• 3 mA maximum current

It is both explosionproof and intrinsically safe and provides a standard LCD Indicator with on-board pushbuttons for configuration and calibration.

ALL WELDED PRESSURE CAPSULE ASSEMBLY

All welded, stainless steel exterior pressure capsule assembly surfaces provide an airtight and watertight bottomworks ideal for corrosive environments. The capsule assembly features a bonded foil strain gauge sensor. The intrinsic overpressure protection in this design eliminates sensor damage when exposed to high pressure surges.

Page 3: Product Specifications PSS 2A-1C13 F I/A Series … represent the latest Foxboro advancements in providing the greatest functionality for the largest number of applications at the

PSS 2A-1C13 FPage 3

HIGH PERFORMANCE

These transmitters utilize microprocessor-based correction to achieve both excellent accuracy and ambient temperature compensation.

DEPENDABLE AND EFFICIENT DESIGN• Silicon Strain Gauge Technology has been Field-

Proven in Hundreds of Thousands of Successful Applications.

• Simple, Elegant Packaging uses a Minimum of Parts to Achieve Exceptionally High Reliability.

DIRECT PROCESS MOUNTING

Because of their light weight, these transmitters can be directly connected to the process piping without mounting brackets. However, for unique requirements, an optional mounting bracket is offered, and an interconnection to the process can be made using the transmitter process connection selected.

EASE OF INSTALLATION

Rotatable Topworks allows transmitter installation in tight places, allows indicator to be positioned in preferred direction, and eases field retrofit.

Two Conduit Entrances offer a choice of entry positions for ease of installation and self-draining of condensation regardless of mounting position and topworks rotation.

Wiring Guides and Terminations provide ease of wire entry and support, plenty of space to work and store excess wire, and large, rugged, rugged screw terminals for easy wire termination.

LCD INDICATOR (FIGURE 1)

A two-line indicator with on-board pushbuttons is available to display the measurement with a choice of units. The pushbuttons allow zero and span adjustments as well as local configuration without the need for a Hand-Held Terminal or PC-based Configurator. This indicator is optional with the Digital Output transmitters, and standard with the Analog Output transmitters. When used with Analog Output transmitters, if local process indication is not required or desired, an optional blind (solid) cover can be substituted for the standard window cover.

NOTEWhen an LCD Indicator is used, ensure that the URV (upper range value) in the selected pressure units does not exceed the character capacity on the top line of the display; i.e., five numeric characters, or four with the analog output transmitters. This is especially important with analog output transmitters since the LCD must be used for URV entry.

Figure 1. Topworks with LCD Indicator

FUNCTIONAL SPECIFICATIONS

Span and Range Limits

Maximum Overrange Pressure Rating

(a) Maximum overrange pressure is the maximum pressure that may be applied without causing damage to the transmitter. The ratings are in gauge pressure units.

Suppressed ZeroSuppressed zero ranges are acceptable as long as the Span and Range Limits are not exceeded.

Field Wiring ReversalNo transmitter damage.

Span Limit Code

Span Limits Range Limits (Gauge Pressure Units)MPa psi bar or kg/cm2 MPa psi bar or kg/cm2

G 35 and 105 5000 and 15 000 350 and 1050 0 and 105 0 and 15 000 0 and 1050H 70 and 210 10 000 and 30 000 700 and 2100 0 and 210 0 and 30 000 0 and 2100

Span Limit Code

Maximum Overrange Pressure(a)

MPa psi bar or kg/cm2

G 138 20 000 1380H 248 36 000 2480

Page 4: Product Specifications PSS 2A-1C13 F I/A Series … represent the latest Foxboro advancements in providing the greatest functionality for the largest number of applications at the

PSS 2A-1C13 FPage 4

FUNCTIONAL SPECIFICATIONS (Cont.)

Output Signal (as specified)VERSION “-D” ELECTRONICS

Digital FoxCom and/or 4 to 20 mA dc, configurableVERSION “-F” ELECTRONICS

Digital FOUNDATION fieldbusVERSION “-T” ELECTRONICS

Digital HART and 4 to 20 mA dcVERSION “-A” ELECTRONICS

Analog 4 to 20 mA dcVERSION “-V” ELECTRONICS

Analog 1 to 5 V dc, Low Power

Adjustable DampingVERSIONS “-D”, “-F”, AND “-T” ELECTRONICS

The transmitter response time is normally 0.75 s, or the electronically adjustable setting of 0.00 (none), 0.25, 0.50, 1, 2, 4, 8, 16, or 32 seconds, whichever is greater, for a 90% recovery from an 80% input step as defined in ANSI/ISA S51.1. (For a 63.2% recovery, 0.5 s with both Sensor Codes G and H.) For Version “-F” Electronics, additional damping is available because damping can be set in both the transducer and AI (Analog Input) function blocks.

VERSIONS “-A” AND “-V” ELECTRONICSThe transmitter response time is normally 0.75 s, or the electronically adjustable setting of 0 (none), 2, 4, or 8 seconds, whichever is greater, for a 90% recovery from an 80% input step as defined in ANSI/ISA S51.1. (For a 63.2% recovery, 0.5 s with both Sensor Codes G and H.)

Zero and Span AdjustmentsZero and span adjustments can be initiated from any of the following: I/A Series Workstation (with applicable FBMs), the Hand-Held Terminal, the PC-based Configurator, or the LCD Indicator with on-board pushbuttons.

Zeroing for Nonzero-Based Ranges for FoxCom and HART Versions Only

Dual Function Zeroing is provided to allow zeroing with the transmitter open to atmosphere, even when there is a nonzero-based range. This greatly simplifies position effect zeroing on many pressure and level applications. It also applies to the LCD Indicator Pushbuttons and Optional External Zero Adjustment (see Figure 3).

Supply VoltageDIGITAL OUTPUT

Version “-D” ElectronicsPower supplied through I/A Series System

Version “-F” ElectronicsPower supplied through a specially designed Fieldbus power supply

Version “-T” ElectronicsBidirectional digital signal superimposed on the 4 to 20 mA current signal. See 4 to 20 mA Output below.

4 TO 20 mA OUTPUTNominal minimum supply voltage shown in Figure 2 is 11.5 V dc. This value can be reduced to 11 V dc by using a jumper across test receptacles in the field wiring compartment terminal block. Foxboro offers an optional plug-in shorting bar with the “-D”, “-T”, and “-A” transmitter versions for this purpose. See Figure 8.

Figure 2. 4 to 20 mA Output,Supply Voltage vs. Output Load

TYPICAL SUPPLYVOLTAGE ANDLOAD LIMITS

V dc243032

LOAD 200 & 594200 & 880200 & 975

SEENOTE

BELOW

1500

1000

500

0

OPERATINGAREA

200250

1450

11.5 42 SUPPLY VOLTAGE, V dc

OU

TP

UT

LO

AD

,

NOTEThe Transmitter will function with an output load less than 200 with FoxCom, or 250 with HART provided that a Hand-Held Terminal or PC-based Configurator is not connected to it. Use of a Hand-Held Terminal or PC-based Configurator requires a 200 with FoxComor 250 minimum load with HART.

0 10 20 30 40 50

Page 5: Product Specifications PSS 2A-1C13 F I/A Series … represent the latest Foxboro advancements in providing the greatest functionality for the largest number of applications at the

PSS 2A-1C13 FPage 5

Standard Liquid Crystal Display (LCD) Indicator with On-Board Pushbuttons (Figure 3)

Indicator Provides:

• Two Lines; five numeric characters on top line (four when a minus sign is needed) and seven alphanumeric characters on bottom line.

• Measurement Readout; value on top line and units label on bottom line.

• Configuration and Calibration Prompts.

Figure 3. LCD Indicator with Pushbuttons

Optional External Zero AdjustmentAn external pushbutton mechanism (Figure 3) is isolated from the electronics compartment and magnetically activates an internal reed switch through the housing. This eliminates a potential leak path for moisture or contaminants to get into the electronics compartment. This zero adjustment can be disabled by a configuration selection.

Electronics and Sensor TemperaturesReadable from I/A Series system, Hand-Held Terminal, or PC-based Configurator only. Measurement is transmitter temperature, not necessarily process temperature.

Current Outputs for Overrange, Fail, and Offline Conditions - FoxCom and HART Only

Write Protect JumperCan be positioned to lock out all configurators from making transmitter database changes. This makes transmitter suitable for Safety Shutdown System Applications that require this feature.

Configuration and Calibration DataAll factory characterization data, and user configuration and calibration data are stored in the sensor. This means that the electronics module can be replaced or changed from one type to another. A module may be replaced without the need for reconfiguration or recalibration. Although module replacement can affect accuracy up to 0.20% of span, this error can be removed by an mA trim without application of pressure. Changing module types may require reconfiguration and recalibration.

Allowable Pressure Units for Calibrated RangeMPa, psig, bar, kg/cm2, and atm

FoxCom (Version “-D”) CommunicationsDIGITAL MODE (FIXED CURRENT)

Digital Output signal is updated 10 times per second and carries the pressure measurement, and sensor and electronics temperature measurements. Internal recalculation rate for temperature is one time per second. Communication between the transmitter and remote device is rated for distances up to 600 m (2000 ft). The digital communications rate is 4800 baud and requires a minimum loop load of 200 ohms. See Figure 4.

4 TO 20 mA ANALOG MODEAnalog output is updated a minimum of 30 times per second. Digital communication between the transmitter and remote device is rated for distances up to 1800 m (6000 ft). The digital communications rate is 600 baud and requires a minimum loop load of 200 ohms. See Figure 5.

HART (Version “-T”) Communications4 TO 20 mA ANALOG MODE

Analog output signal is updated 30 times per second. Digital communication between the transmitter and hand-held terminal (Model 275 Communicator) is rated for 3050 m (10 000 ft). The digital communication rate is 1200 baud and requires a minimum loop load of 250 ohms. See Figure 5.

Parameter FoxCom HART

OFFLINE User configurable between 4 and 20 mA

SENSOR FAILURE

User configurable to Fail LO or Fail HI

FAIL LO 3.60 mA 3.60 mAUNDERRANGE 3.75 mA 3.80 mAOVERRANGE 21.00 mA 20.50 mAFAIL HI 22.00 mA 21.00 mA

TOPWORKSWITH COVERREMOVED

LCDINDICATOR

"ENTER"PUSHBUTTON

"NEXT"PUSHBUTTON

NEXT ENTER

OPTIONALEXTERNALZEROPUSHBUTTON

Page 6: Product Specifications PSS 2A-1C13 F I/A Series … represent the latest Foxboro advancements in providing the greatest functionality for the largest number of applications at the

PSS 2A-1C13 FPage 6

FUNCTIONAL SPECIFICATIONS (Cont.)

HART (Version “-T”) Communications (Cont.)MULTIDROP MODE (FIXED CURRENT)

This Mode supports communications with up to 15 transmitters on a single pair of signal/power wires. The output signal is updated 4 times/second and carries not only the pressure measurement, but also the sensor and electronics temperatures (internal recalculation rate for temperature is one time/second). Communications between the transmitter and communicator is rated for distances up to 1525 m (5000 ft). The digital communications rate is 1200 baud and requires a minimum loop load of 250 ohms. See Figure 6.

Figure 4. Digital Output Block Diagram

(FoxCom)

Figure 5. 4 to 20 mA Output Block Diagram

(FoxCom and HART)

FOUNDATION fieldbus (Version “-T”) Communications

This serial, two-way communication system runs at 31.25 kbits/s. The digital output signal is superimposed on the dc power signal on the bus, and controlled by a strict cycle schedule and protocol. Supply voltage, 9 to 32 V dc, is by a specially designed fieldbus power source. The maximum number of devices on a bus is 32 for non-intrinsically safe locations, and 6 when in an intrinsically safe location. The maximum cable length (including spurs) between the device and the host computer is 1900 m (6234 ft). See Figure 7 for typical installation topologies.

Figure 6. Typical Multidrop Block Diagram

(HART – Up to Fifteen Transmitters)

Figure 7. Miscellaneous Installation Topologies

(FOUNDATION Fieldbus)

SINGLE ORREDUNDANTPOWERSUPPLY

FOXBORO PC-BASED CONFIGURATOROR HAND-HELD TERMINAL

INTELLIGENT PRESSURE TRANSMITTER

REFER TO PSS 21H-2D5 B4AND TO PSS 21H-2C4 B4

TWISTED PAIR(POWER ANDCOMMUNICATIONS)

OTHERINTELLIGENTTRANSMITTERS

INTELLIGENTTRANSMITTER

INTERFACEMODULE

INDICATORPOWERSUPPLY

IGP10TRANSMITTER

CONTROLLEROR RECORDER

+

+

+

+FoxCom: 200 Ω MINIMUM HART: 250 MINIMUM

FoxCom OR HARTHAND-HELDTERMINAL, OR PC-BASEDCONFIGURATOR

HARTCOMPATIBLE

MODEM

HOSTCOMP.

GAUGEPRESSXMTR

POWERSUPPLY

d/p CellXMTR

TEMP.XMTR

250 MIN.

FIELDBUSINTERFACEELECTRONICS

JUNCTION BOX

BUS WITH SPURS DAISY CHAIN TREE

HOSTCOMPUTER

NOTETerminators and Power Supply not shown

Page 7: Product Specifications PSS 2A-1C13 F I/A Series … represent the latest Foxboro advancements in providing the greatest functionality for the largest number of applications at the

PSS 2A-1C13 FPage 7

OPERATING, STORAGE, AND TRANSPORTATION CONDITIONS

(a) Although the LCD will not be damaged at any temperature within the “Storage and Transportation Limits”, updates will be slowed and readability decreased at temperatures outside the “Normal Operating Conditions”.

(b) Selection of Option “-J” extends the low temperature operative limit of transmitters down to -50°C (-58°F).(c) With topworks covers on and conduit entrances sealed.(d) 11.5 V dc can be reduced to 11 V dc by using a plug-in shorting bar with “-D”, “-T”, “-A”, and “-I” electronic versions. See Figure 8.(e) 200 Ω minimum load required for proper communication with FoxCom Protocol, and 250 Ω minimum load required for proper

communication with HART Protocol.

Influence

Reference OperatingConditions

Normal Operating Conditions Operative Limits

Storage and Transportation

Limits

Sensor Body Temperature 24 ±2°C(75 ±3°F)

-40 to + 88°C(-40 to +190°F)

-40 and +104°C (b)(-40 and +220°F) (b)

Not Applicable

Electronics Temperature

with LCD Indicator (Note a)

• 24 ±2°C(75 ±3°F)

• 24 ±2°C(75 ±3°F)

• -29 to + 82°C(-20 to +180°F)

• -20 to + 82°C(-4 to +180°F)

• -40 and +85°C (b)(-40 and +185°F) (b)

• -40 and +85°C(-40 and +185°F)

• -54 and +85°C(-65 and +185°F)

• -54 and +85°C(-65 and +185°F)

Relative Humidity (Note c) 50 ±10% 0 to 100% 0 and 100% 0 and 100%Noncondensing

Supply Voltage - mA Output 30 ±0.5 V dc 11.5 to 42 V dc (d) 11.5 and 42 V dc (d) Not Applicable

Output Load - mA Output 650 Ω 0 to 1450 Ω (e) 0 and 1450 Ω (e) Not Applicable

Vibration 1 m/s2 (0.1 “g”) 6.3 mm (0.25 in) Double Amplitude:from 5 to 15 Hz with Aluminum Housing and from 5 to 9 Hz with 316 ss Housing- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -0 to 30 m/s2 (0 to 3 “g”) from 15 to 500 Hz with Aluminum Housing; and 0 to 10 m/s2 (0 to 1 “g”) from 9 to 500 Hz with 316 ss Housing

11 m/s2 (1.1 “g”)from 2.5 to 5 Hz

(in Shipping Package)

Mounting Position Upright Upright No Limit Not Applicable

Page 8: Product Specifications PSS 2A-1C13 F I/A Series … represent the latest Foxboro advancements in providing the greatest functionality for the largest number of applications at the

PSS 2A-1C13 FPage 8

PERFORMANCE SPECIFICATIONSZero-Based Calibrations; Under Reference Operating Conditions Unless Otherwise Specified;

URL = Upper Range Limit; Span = Calibrated Span

Accuracy (Includes Linearity, Hysteresis, and Repeatability)

±0.20% of Span (factory configured with 2.0 seconds user-adjustable damping)

Power-Up TimeLess than 5 seconds for output to reach first valid measurement.

Supply Voltage EffectThe output changes less than 0.005% of span for each 1 V change within the specified supply voltage requirements.

Vibration EffectTotal effect is ±0.2% of URL per “g” for vibrations in the frequency range of 5 to 500 Hz; with double amplitudes of 6.3 mm (0.25 in) in the range of 5 to 15 Hz, or accelerations of 3 “g” in the range of 15 to 500 Hz, whichever is smaller, for aluminum housings; and with double amplitudes of 6.3 mm (0.25 in) in the range of 5 to 9 Hz, or accelerations of 1 “g” in the range of 9 to 500 Hz, whichever is smaller, for 316 ss housings.

Position EffectThe transmitter may be mounted in any position. Any zero effect caused by the mounting position can be eliminated by rezeroing. There is no span effect.

Ambient Temperature EffectTotal effect for a 55°C (100°F) change within Normal Operating Condition limits is:

RFI EffectThe output error is less than 0.1% of span for radio frequencies in the range of 27 to 1000 MHz and field intensity of 30 V/m when the transmitter is properly installed with shielded conduit and grounding, and housing covers are in place. (Per IEC Std. 801-3.)

Switching and Indirect Lightning TransientsThe transmitter can withstand a transient surge up to 2000 V common mode or 1000 V normal mode without permanent damage. The output shift is less than 1.0%. (Per ANSI/IEEE C62.41-1980 and IEC Std. 801-5.)

Span Limit Code Ambient Temperature Effect

for “-D” FoxCom TransmittersG and H ±(0.155% URL + 0.045% Span)

for “-T” HART TransmittersG and H ±(0.155% URL + 0.045% Span)

for “-F” Fieldbus TransmittersG and H ±(0.155% URL + 0.045% Span)

for “-A” Analog TransmittersG and H ±(0.155% URL + 0.30% Span)

for “-V” Analog TransmittersG and H ±(0.155% URL + 0.10% Span)

Page 9: Product Specifications PSS 2A-1C13 F I/A Series … represent the latest Foxboro advancements in providing the greatest functionality for the largest number of applications at the

PSS 2A-1C13 FPage 9

PHYSICAL SPECIFICATIONS

Environmental ProtectionTransmitter is dusttight and weather resistant per IEC IP66 and provides the environmental and corrosion resistant protection of NEMA Type 4X.

Electronics Housing and Housing CoversHousing has two compartments to separate the electronics from the field connections. The housing and covers are made from low copper, die-cast aluminum alloy with an epoxy finish, or from 316 ss. Buna-N O-ring seals are used to seal the threaded housing covers, housing neck, and terminal block.

Process Wetted PartsFOR SPAN LIMIT CODE G

15-5 ss or Inconel X-750FPR SPAN LIMIT CODE H

13-8 Molybdenum Stainless Steel

Process Connections

Electronics ModulePrinted wiring assemblies are conformally coated for moisture and dust protection.

Mounting PositionThe transmitter may be mounted in any orientation.

Electrical Conduit Connections1/2 NPT conduit connection on both sides of transmitter housing. Unused connection must be plugged (plug supplied by Foxboro) to ensure moisture and RFI protection. Optional 1/2 NPT cable gland and M20 (1/2 NPT to M20) connector are also available for cable entry.

Electrical TerminationsField wires enter through the conduit connections described above and terminate under screw terminals and washers on the terminal block in the field terminals compartment. See Figure 8 for the terminal block configuration for the different transmitter electronic versions offered.

Approximate MassWITH ALUMINUM HOUSING

1.5 kg (3.3 lb)WITH 316 ss HOUSING

2.6 kg (5.7 lb)WITH LCD INDICATOR

Add 0.2 kg (0.4 lb)

Figure 8. Field Terminals Compartment for the Electronic Versions Offered

Structure Code

Span Limit Code

Process Connection

1/4 NPT Internal

G 1/2(a) External

Autoclave F-250-C(b)

24 G Standard Optional Optional26 G Standard Optional Optional28 H N/A N/A Standard

(a) Option “-G” = G 1/2 Form B ext. thread manometer connection.(b) Option “-G1” = Autoclave F-250-C connection with a 9/16-18

internal gland thread.

+

-

EARTH (GROUND)TERMINAL SCREW,0.164-32

(+) AND (-)POWERTERMINALSCREWS,0.164-32

TERMINAL BLOCKLOCATED IN FIELDTERMINAL SIDE OFTRANSMITTER

OUTPUT VOLTAGETERMINAL SCREWS0.164-32 A=(POS.) B=(NEG.)

A

B

EARTH (GROUND)TERMINAL SCREW,0.164-32

POLARITYINDEPENDENTTERMINALS:0.164-32SCREWS

TERMINAL BLOCKLOCATED IN FIELDTERMINAL SIDE OFTRANSMITTER

-

EARTH (GROUND)TERMINAL SCREW,0.164-32

(+) AND (-) POWER TERMINAL SCREWS, 0.164-32

RECEPTACLES (3)FOR STANDARDBANANA PLUGS

HHT

CAL+

TERMINAL BLOCKLOCATED IN FIELDTERMINAL SIDE OFTRANSMITTER

USED TO CHECK TRANSMITTER 4 TO 20 mA OUTPUT

OPTIONAL SHORTING BAR (SB-11) REDUCESMINIMUM VOLTAGEFROM 11.5 TO 11 V dc

"-D" FoxCom VERSIONFOR HHT OR PC-BASED CONFIGURATOR PLUGS

"-T" HART VERSIONFOR HART MODEL 275 COMMUNICATOR PLUGS

"-A" ANALOG VERSIONNO REMOTE COMMUNICATION,UPPER BANANA RECEPTACLE IS PLUGGED

"-D" FoxCom, "-T" HART, AND "-A" ANALOG TRANSMITTER VERSIONS

"-F" FOUNDATION Fieldbus VERSION "-V" ANALOG VERSION

+

Page 10: Product Specifications PSS 2A-1C13 F I/A Series … represent the latest Foxboro advancements in providing the greatest functionality for the largest number of applications at the

PSS 2A-1C13 FPage 10

SPECIFICATIONS COMMON TO ALL TRANSMITTERS (Cont.)

ELECTRICAL SAFETY SPECIFICATIONS

NOTETransmitter has been designed to meet the electrical safety descriptions listed. Contact Foxboro for information or status of testing laboratory approvals or certifications.

Testing Laboratory, Types ofProtection, and Area Classification Application Conditions

ElectricalSafetyDesign Code

ATEX intrinsically safe; II 1 G, EEx ia IIC, Zone 0; or II 1/2 G EEx ib IIC, Zone 0/Zone 1; hazardous locations.

Not available with Electronics Version “-A”.Temperature Class T4-T6. See certificate KEMA 00ATEX1009 X for conditions.

E

ATEX protection n; II 3 G, EEx nL IIC, Zone 2; hazardous locations.

Not available with Electronics Version “-A”.Temperature Class T4-T6. See certificate KEMA 00ATEX1060 X for conditions.

N

CSA intrinsically safe for Class I, Division 1, Groups A, B, C, and D; Class II, Division 1, Groups E, F, and G; and Class III, Division 1 hazardous locations.

Not available with Electronics Version “-A”.Connect per MI 020-427. Temperature Class T4A at 40°C (104°F), and T3C at 85°C (185°F) maximum ambient.

C

CSA explosionproof for Class I, Division 1, Groups B, C, and D; and dust-ignitionproof apparatus for Class II, Division 1, Groups E, F, and G; and Class III, Division 1 hazardous locations.

Temperature Class T6 at 80°C (176°F) and T5 at 85°C (185°F) maximum ambient.

CSA for Class I, Division 2, Groups A, B, C, and D; Class II, Division 2, Groups F and G; and Class III, Division 2 hazardous locations.

Connect to source not exceeding 42.4 V. Temperature Class T6 at 40°C (104°F), and T4A at 85°C (185°F) maximum ambient.

FM intrinsically safe for Class I, Division 1, Groups A, B, C, and D; Class II, Division 1, Groups E, F, and G; and Class III, Division 1 hazardous locations.

Not available with Electronics Version “-A”.Connect per MI 020-427. Temperature Class T4A at 40°C (104°F), and T4 at 85°C (185°F) maximum ambient.

F

FM explosionproof for Class I, Division 1, Groups B, C, and D; and dust-ignitionproof apparatus for Class II, Division 1, Groups E, F, and G; and Class III, Division 1 hazardous locations.

Temperature Class T6 at 80°C (176°F) and T5 at 85°C (185°F) maximum ambient.

FM nonincendive apparatus for Class I, Division 2, Groups A, B, C, and D; Class II, Division 2, Groups F and G; and Class III, Division 2 hazardous locations.

Connect to source not exceeding 42.4 V. Temperature Class T6 at 40°C (104°F), and T4A at 85°C (185°F) maximum ambient.

SAA Ex d IIC. Flameproof, Gas Group IIC, Zone 1. Temperature Class T6. A

Page 11: Product Specifications PSS 2A-1C13 F I/A Series … represent the latest Foxboro advancements in providing the greatest functionality for the largest number of applications at the

PSS 2A-1C13 FPage 11

(a)Refer to PSSs 2A-1C13A, 2A-1C13 B, 2A-1C13 C, 2A-1C13 D, and 2A-1C13 E for Gauge Pressure Transmitters with span limits less than 105 MPa (15 000 psi) for all of the Electronic Versions listed above. See the PSS Summary Table on the last page of this document.

(b)Refer to “LCD INDICATOR” section regarding URV character limitation with selected measurement units.(c)Autoclave F-250-C Connection with a 9/16-18 internal gland thread.(d) Intrinsically Safe (ia) or ATEX protection “n” not applicable to transmitters with “–A” Electronics Version..

MODEL CODE

IGP10 Series for High Gauge Pressure Measurement (a)Description ModelI/A Series, Electronic, Direct Connected, High Gauge Pressure Transmitter IGP10

Electronics Versions and Output Signal(a)Intelligent; Digital FoxCom and/or 4 to 20 mA dc, Configurable (Version –D) –DIntelligent; Digital FOUNDATION fieldbus (Version –F) –FIntelligent; Digital HART and 4 to 20 mA (Version –T) –TElectronic; 4 to 20 mA Analog Output, (Version –A) –A (b)Electronic; 1 to 5 V dc Analog Output, Low Power (Version –V) –V (b)

Structure Code – Process Connection, Sensor, and Fill FluidConnectionMaterial

ConnectionThread Sensor Fill Fluid Used with

15-5 ss 1/4 NPT, Internal 15-5 ss None Span Limit Code “G” only 24Inconel X-750 1/4 NPT, Internal Inconel X-750 None Span Limit Code “G” only 2613-8 Mo ss Autoclave F-250-C (c) 13-8 Mo ss None Span Limit Code “H” only 28

Span Limits – Gauge Pressure UnitsMPa psi bar or kg/cm2 Used with35 and 105 5000 and 15 000 350 and 1050 Structure Codes “24” and “26” only G70 and 210 10 000 and 30 000 700 and 2100 Structure Code “28” only H

Conduit Connection and Housing Material1/2 NPT, Aluminum HousingPG 13.5, Aluminum Housing (Available with Electrical Safety Codes “E” and “N” only)1/2 NPT, 316 ss HousingPG 13.5, 316 ss Housing (Available with Electrical Safety Codes “E” and “N” only)

1234

Electrical Safety (See Electrical Safety Specifications Section for Description and Approval Status)ATEX II 1 G, EEx ia IIC, or II 1/2 G, EEx ib IIC (d)ATEX II 3 G, EEx nL IIC (d)CSA Certified ia, d, and Division 2FM Approved ia, d, and nSAA Certified Ex, d, IIC

ENCFA

Optional SelectionsRefer to “Optional Selections Codes” section on next page for options available with these transmitters.

Page 12: Product Specifications PSS 2A-1C13 F I/A Series … represent the latest Foxboro advancements in providing the greatest functionality for the largest number of applications at the

PSS 2A-1C13 FPage 12

(a) Not available with Span Limit Code H.(b) Autoclave Connection is standard construction with Span Limit Code H; and optional with Span Limit Code G.

ORDERING INSTRUCTIONS

Optional Selection Codes for IGP10-...G and -...H(Also see PSS 2A-1Z9 E for Additional Options and Accessories)

OptionCode

Mounting Bracket SetPainted Steel Bracket with Plated Steel Bolts, 1/2 NPTStainless Steel Bracket with Stainless Steel Bolts, 1/2 NPTPainted Steel Bracket with Plated Steel Bolts, PG 13.5Stainless Steel Bracket with Stainless Steel Bolts, PG 13.5

-M1-M2-M3-M4

Digital Indicator with Pushbuttons or Solid (Blind) Cover over Standard IndicatorDigital Indicator, Pushbuttons, and Window Cover (Electronic Versions -D, -F, and -T only)Substitute Solid (Blind) Cover over Standard Indicator (Electronic Versions -A and -V only)

-L1-L2

Conduit ConnectorsHawke-Type 1/2 NPT Cable Gland for use with Conduit Connection Codes “1” and “3”Plastic PG 13.5 Cable Gland for use with Conduit Connection Codes “2” and “4”M20 Conduit Thread Adapter for use with Conduit Connection Codes “1” and “3”Brass PG 13.5 Cable Gland (Trumpet-Shaped) for use w/Conduit Connection Codes “2” and “4”

-A1-A2-A3-A4

Electronics Housing FeaturesExternal Zero AdjustmentCustody Transfer Lock and SealExternal Zero Adjustment and Custody Transfer Lock and Seal

-Z1-Z2-Z3

Custom Factory ConfigurationDigital Output (4 to 20 mA Default if not selected) - Electronic Version -D onlyFull Factory Configuration (Requires Configuration Form to be filled out)

-C1-C2

Process ConnectionsG 1/2 Form B Manometer Process Connection, External Thread (a)Autoclave F-250-C (with Span Limit Code G only) (b)

-G-G1

Instruction Books (Common MI, Brochure, and Full Documentation Set on CD-ROM is Standard)Without Instruction Book and CD (“Getting Started” document only provided)Full Instruction Book in Paper; Traditional Book with all MIs, PLs, DPs, etc. provided

-K1-K4

Miscellaneous Optional SelectionsLow Temperature Operative Limits extended down to -50°C (-58°F)Supplemental Customer Tag (Stainless Steel Tag wired onto Transmitter)Five Year Warranty

-J-T-W

Example: IGP10-D24G1F-L1Z1C1

1. Model Number2. Calibrated Pressure Range3. Configuration Data Form when Factory Configuration Option “-C2” is specified4. Optional Features not Included in Model Code (see PSS 2A-1Z9 E)5. Accessories (see PSS 2A-1Z9 E)6. User Tag Data

Page 13: Product Specifications PSS 2A-1C13 F I/A Series … represent the latest Foxboro advancements in providing the greatest functionality for the largest number of applications at the

PSS 2A-1C13 FPage 13

SUGGESTED RFQ SPECIFICATIONS

The manufacturer shall provide direct connected pressure transmitters featuring 4 to 20 mA or 1 to 5 V dc remote digital communications capability for measuring high gauge pressures and transmitting a digital or analog output signal for use in a standard two-wire dc supply voltage system. The specifications for these transmitters are as follows:

Digital Output Signal: FoxCom digital and/or 4 to 20 mA dc output signal;HART digital signal superimposed on a 4 to 20 mA output signal;FOUNDATION fieldbus digital signal, 31.25 bits/s.

Analog Output Signal: 4 to 20 mA dc or 1 to 5 V dcRemote Communications: FoxCom, HART, or Fieldbus Remote Communications must not

interfere with the output signal.RFI Protection: 0.1% error between 27 and 1000 MHz at 30 V/m field intensity

Span Limits: From 35 to 210 MPa (5000 to 30 000 psi)Proof Pressure: 1.5 times Full Scale Pressure Range or 140 MPa (20 000 psi),

whichever is less, for the 105 MPa (15 000 psi) transmitters; and 1.2 times Full Scale Pressure Range for the 210 MPa (30 000 psi) transmitters.

Process Connection: Direct to process piping: 1/4-18 NPT internal thread is standard for the 105 MPa (15 000 psi) transmitters; and 9/16-18 internal gland thread (conforms to Autoclave Type F250C) is standard for the 210 MPa (30 000 psi) transmitters.

Sensor Materials: 15-5 ss and Inconel X-750 for the 105 MPa (15 000 psi) transmitters; and 13-8 Molybdenum stainless steel for the 210 MPa (30 000 psi) transmitters.

Housing: 316 ss, or Aluminum housing with Epoxy finishElectronics: Enclosed in a NEMA 4X (IEC IP66) housing sealed with O-rings for

double protection against moisture or other contaminants. Integral LCD Digital Indicator with on-board configuration pushbuttons; standard with analog output transmitters, and optional with digital output transmitters.

Mounting: Direct to process or bracket mounted to pipe.Electrical Classification: Nonincendive for Class I and Class II, Division 2 locations; intrinsically

safe or explosionproof for Class I and Class II, Division 1 locations. Designed to comply with applicable European Union Directives.

Approximate Mass: Direct Connected Transmitter: 1.5 kg (3.3 lb)With 316 ss Electronics Housing: Add 1.1 kg (2.4 lb)With LCD Indicator: Add 0.2 kg (0.4 lb)

Model Code: Foxboro I/A Series IGP10 Direct Connected, High Gauge Pressure Transmitter with FoxCom Communication Protocol, HART Communication Protocol, FOUNDATION fieldbus Communication Protocol, 4 to 20 mA dc Analog Output Signal, or a Low Power Transmitter with a 1 to 5 V dc Analog Output Signal, or equivalent

Page 14: Product Specifications PSS 2A-1C13 F I/A Series … represent the latest Foxboro advancements in providing the greatest functionality for the largest number of applications at the

PSS 2A-1C13 FPage 14

DIMENSIONS-NOMINAL

843.3

1475.8

FIE

LDT

ER

MIN

ALS +

1375.4

1244.9

CONDUITCONNECTION(SEE NOTE 1)

EXTENDED COVERUSED WITH "-L1"LCD INDICATOROPTION.

CONDUITCONNECTION(SEE NOTE 1)

OPTIONALCUSTODYTRANSFERLOCK (SEAL)BOTH ENDS

EXTERNALEARTH(GROUND)

SEE REPLACEMENTSENSOR ASSEMBLIES BELOW.

FIELD TERMINALCONNECTIONS

ALLOW 50 mm (2 in)CLEARANCE FORCOVER REMOVALBOTH ENDS (NOTE 2)

1/4 NPTPROCESS CONNECTIONSTANDARD WITH SPAN

LIMIT CODE G; NOT AVAILABLE WITHSPAN LIMIT CODE H.

AUTOCLAVE F-250-CPROCESS CONNECTIONSTANDARD WITH SPAN

LIMIT CODE H;OPTIONAL WITH SPAN

LIMIT CODE G.

G 1/2 FORM B MANOMETERPROCESS CONNECTION

OPTIONAL WITH SPANLIMIT CODE G;

NOT AVAILABLE WITHSPAN LIMIT CODE H.

1. CONDUIT CONNECTION 1/2 NPT OR PG 13.5, BOTH SIDES: PLUG UNUSED CONNECTION WITH METAL PLUG (SUPPLIED).2. TOPWORKS ROTATABLE TO ANY POSITION WITHIN ONE TURN COUNTERCLOCKWISE OF FULLY TIGHTENED POSITION.

NOTES

mmin

Page 15: Product Specifications PSS 2A-1C13 F I/A Series … represent the latest Foxboro advancements in providing the greatest functionality for the largest number of applications at the

PSS 2A-1C13 FPage 15

DIMENSIONS-NOMINAL (Cont.)

EXTERNALEARTH(GROUND)

VERTICAL PIPEMOUNTNG

FOR HORIZONTALPIPE MOUNTING(U-BOLT IS ROTATED 90˚)

SPACER THREADSINTO CONDUITCONNECTION

OPTIONAL MOUNTING BRACKET SET (-M1, -M2, -M3 AND -M4)

CABLEGLAND

1/2 NPT

CABLEGLAND

PG 13.5

CABLEGLAND

PG 13.5

M20

TRANSMITTER WITH CONDUIT CONNECTOR OPTIONS "-A1" TO "-A4"

(-A1) (-A4)(-A3)(-A2)

1/2 NPT

mmin

Page 16: Product Specifications PSS 2A-1C13 F I/A Series … represent the latest Foxboro advancements in providing the greatest functionality for the largest number of applications at the

PSS 2A-1C13 FPage 16

I/A Series INTELLIGENT TRANSMITTERS

PRODUCT SPECIFICATION SHEETS (PSSs) FOR INTELLIGENT FIELD DEVICES

(1) For low power voltage output (1 to 5 V) pressure transmitter family, refer to PSS 2A-1C13 D.(2) Options/Accessories: see PSS 2A-1Z9 E for Pressure and Multivariable Transmitters, and PSS 2A-1Z9 F for Temperature Transmitters.(3) For Modbus protocol mass meter Model CFT15, refer to PSS 1-2B3 D.(4) For pulse output vortex meter, refer to PSS 1-8A1 D (for 83F and 83W) or PSS 1-8A2 D (for 83S).(5) For Profibus Pa protocol valve positioner Model SRD991, refer to PSS EVE0105 A-(en).

Category Device Types Models4-20 mAAnalog

4-20 mA with FoxCom

4-20 mA with HART

FOUNDATION fieldbus Notes

Pressure Transmitter - AP IAP10 & 20 2A-1C13 C 2A-1C13 A 2A-1C13 B 2A-1C13 E (1)(2)Transmitter - GP IGP10 & 20 2A-1C13 C 2A-1C13 A 2A-1C13 B 2A-1C13 E (1)(2)Transmitter - DP IDP10 2A-1C14 C 2A-1C14 A 2A-1C14 B 2A-1C13 E (1)(2)

Pressure -Multirange

Transmitter - GP IGP25 – 2A-1C13 G 2A-1C13 G 2A-1C13 G (2)Transmitter - DP IDP25 – 2A-1C14K 2A-1C14K 2A-1C14K (2)

Pressure -Premium Perf.

Transmitter - GP IGP50 – 2A-1C13 H 2A-1C13 H 2A-1C13 H (2)Transmitter - DP IDP50 – 2A-1C14L 2A-1C14L 2A-1C14L (2)

Multivariable Transmitter - P/T/Flow IMV30 – 2A-1C15 A – – (2)Transmitter - P/T IMV25 – 2A-1C15 B 2A-1C15 B 2A-1C15 B (2)

Temperature Transmitter RTT20 2A-1F4 A 2A-1F4 A 2A-1F4 A – (2)Transmitter RTT25 – – – 2A-1F4 C (2)

Mass Flow Transmitter CFT10 – 1-2B3 C – – –Transmitter CFT15 – – – – (3)Transmitter CFT30 – – 1-2B5 A – –

Magnetic Flow Transmitter IMT25 – 1-6F5 A 1-6F5 A 1-6F5 B –Transmitter IMT25L – 1-6F6 A – – –Transmitter IMT96 – 1-6F8 A – – –

Vortex Flow Flanged/Wafer 83F/83W 1-8A1 D 1-8A1 E 1-8A1 E 1-8A1 F (4)Sanitary 83S 1-8A2 E 1-8A2 D 1-8A2 D N/A (4)

Electrochem.Transmitters

pH, ORP, ISE 870ITPH 6-1B1 B 6-1B1 B – – –CC & R 870ITCR 6-3C1 B 6-3C1 B – – –EC 870ITEC 6-3N2 A 6-3N2 A – – –

Electrochem.Analyzers

pH, ORP, ISE 875PH 6-3A1 E – 6-3A1 E – –CC & R 875CR 6-3A1 B – 6-3A1 B – –EC 875EC 6-3N1 C – 6-3N1 C – –

Buoyancy Transmitter 144LD – EML0610 A-(en) EML0160 A-(en) – –Transmitter 144LVD – EML1610 A-(en) EML1610 A-(en) – –

Valves Positioner SRD991 EVE0106 A-(en) EVE0105 A-(en) EVE0105 A-(en) EVE0105 A-(en) (5)

33 Commercial StreetFoxboro, MA 02035-2099United States of Americawww.foxboro.comInside U.S.: 1-866-PHON-IPS

(1-866-746-6477)Outside U.S.: 1-508-549-2424 or contact your local Foxboro representative.Facsimile: 1-508-549-4999

Foxboro and I/A Series are registered trademarks of Invensys Systems, Inc.Invensys is a trademark of Invensys plc.All other brand names may be trademarks of their respective companies.

Copyright 2001 Invensys Systems, Inc.All rights reserved

MB 010 Printed in U.S.A. 1201