Product Overview - Systemair...Product type Dimensions range (mm) Fire resistivity Supporting...

6
Fire Safety Products Product Overview Fans | Air Handling Units | Air Distribution Products | Fire Safety | Air Conditioning | Air Curtains and Heating Products | Tunnel Fans

Transcript of Product Overview - Systemair...Product type Dimensions range (mm) Fire resistivity Supporting...

Page 1: Product Overview - Systemair...Product type Dimensions range (mm) Fire resistivity Supporting construction Installation - tested at underpressure (Pa) Wet Dry Soft crossing Instal.

Fire Safety ProductsProduct Overview

Fans | Air Handling Units | Air Distribution Products | Fire Safety | Air Conditioning | Air Curtains and Heating Products | Tunnel Fans

Page 2: Product Overview - Systemair...Product type Dimensions range (mm) Fire resistivity Supporting construction Installation - tested at underpressure (Pa) Wet Dry Soft crossing Instal.

FIREDAMPER

EVACUATIONDAMPER

FIRE AIRGRILLE

MULTI-COMPARTMENTSMOKE DAMPER

FIREDAMPER

FIREDAMPER

EVACUATIONDAMPER

FIREDAMPER

MULTI-COMPARTMENTSMOKE DAMPER

FIRE SAFETY PRODUCTSprevent the spread of toxic gases, smoke and fire, help with evacuation, increase the effectivness of active fire protection systems and minimize the property damage.

Page 3: Product Overview - Systemair...Product type Dimensions range (mm) Fire resistivity Supporting construction Installation - tested at underpressure (Pa) Wet Dry Soft crossing Instal.

PKIR3GCircular Fire Damper

Available in an explosion-proof versionDimension range (mm)

DN 100 up to 1000

PKIS3GRectangular Fire Damper

Available in an explosion-proof versionDimension range (mm)

W × H = 100 × 100 up to 1200 × 800

PKIS3GARectangular Fire Damper

Available in an explosion-proof versionDimension range (mm)

800 < W ≤ 1200& 100 ≤ H ≤ 300

PKIR-E60SCircular Fire Damper

Dimension range (mm) DN 100 up to 630

PKIS-EI90SRectangular Fire Damper

Available in an explosion-proof versionDimension range (mm)

W > 1200 and/or H > 800 up to 1600 × 1000

PKIS-EI120SRectangular Fire Damper

Available in an explosion-proof versionDimension range (mm)

W > 1200 and/or H > 800 up to 1600 × 1000

PKI-CCartridge Fire Damper

Dimension range (mm) DN 100 up to 200

Fire resistivity* II 2/- G IIB1396-CPR-0077

II 2/- G IIB1396-CPR-0077 Fire resistivity*

Fire resistivity* II 2/- G IIB1396-CPR-00761396-CPD-0061

II 2/- G IIB1396-CPD-0062 Fire resistivity*

1396-CPD-0069 Fire resistivity*

II 2/- G IIB1396-CPD-0062 Fire resistivity*

1396-CPD-0050 Fire resistivity*

* Detailed information about fire resistivity is on the back page.

FIRE DAMPERSSafety position: closed

Page 4: Product Overview - Systemair...Product type Dimensions range (mm) Fire resistivity Supporting construction Installation - tested at underpressure (Pa) Wet Dry Soft crossing Instal.

DKIR1Single-compartment Circular Smoke DamperDimension range (mm) DN 100 up to 630

DKIS1Single-compartment Rectangular Smoke DamperDimension range (mm) W × H = 200 × 200 up to 1500 × 800

DKISMAMulti-compartment Smoke DamperDimension range (mm) W × H = 200 × 200 up to 1600 × 1000

EKIR-E60SCircular Evacuation DamperDimension range (mm) DN 100 up to 630

FGSFire Air GrilleDimension range (mm) 200 × 200 up to 800 × 1000

Fire resistivity*

1396-CPD-0069 Fire resistivity*

1396-CPD-0058 Fire resistivity*1396-CPR-0058 Fire resistivity*

1396-CPR-0112 Fire resistivity*

* Detailed information about fire resistivity is on the back page.

SMOKE DAMPERSSafety position: open or closed

EVACUATION DAMPERSSafety position: open

FIRE AIR GRILLESSafety position: closed

Page 5: Product Overview - Systemair...Product type Dimensions range (mm) Fire resistivity Supporting construction Installation - tested at underpressure (Pa) Wet Dry Soft crossing Instal.

Product type

Dimensions range (mm)

Fire resistivity

Supporting construction

Installation - tested at underpressure (Pa)

Wet Dry Soft crossing Instal. kit On a wall Out of a wall

PKIR3GATEX

100 ≤ DN ≤ 400

EI60 (ve ho i ↔ o)S

ve 500 300 300 500 300 W 300 W

ho 500 300 300

EI90 (ve ho i ↔ o)S

ve 500 300 300 500 300 W 300 W

ho 500 300 300

EI120 (ve ho i ↔ o)S

ve 500 500

ho 500

400 < DN ≤ 630

EI60 (ve ho i ↔ o)S

ve 500 300 300 500 300 W 300 W

ho 500 300 300

EI90 (ve ho i ↔ o)S

ve 500 300 300 500

ho 500 300 300

EI120 (ve ho i ↔ o)S

ve 500 500

ho 500

630 < DN ≤ 1000

EI60 (ve ho i ↔ o)S

ve 500 300

ho 500

EI90 (ve ho i ↔ o)S

ve 500 300

ho 500

EI120 (ve ho i ↔ o)S

ve 500

ho 500

PKIR-E60S DN 100 up to 630 E60

(ve ho i ↔ o)S

ve 300 NOINS 300 NOINS

ho 300 NOINS 300 NOINS

PKI-C DN 100 up to 200

EI60 (ve ho i ↔ o)S

ve 300 300

ho 300

EI90 (ve ho i ↔ o)S

ve 300 300

ho 300

EI120 (ve ho i ↔ o)S

ve 300 300

ho 300

PKIS3GATEX

100 × 100 up to 1200 × 800

EI60 (ve ho i ↔ o)S

ve 500 300 300 500 KIT 300 W, P 300 W, P

ho 500 300 300

EI90 (ve ho i ↔ o)S

ve 500 300 300 500 KIT 300 W, P 300 W, P

ho 500 300 300

EI120 (ve ho i ↔ o)S

ve 500 500 KIT 300i→o W, P 300i←o W, P

ho 500 300

PKIS3GAATEX

800 < W ≤ 1200& 100 ≤ H ≤ 300

EI60 (ve ho i ↔ o)S

ve 300 300 P 300 P

ho

EI90 (ve ho i ↔ o)S

ve 300 300 P 300 P

ho

PKIS-EI90S MULTI, ATEX

W > 1200 and/or

H > 800 up to 1600 × 1000

EI90 (ve ho i ↔ o)S

ve 300 300 300 300 W 300 W

ho 300 300 300

PKIS-EI120SATEX

EI120 (ve ho i ↔ o)S

ve 300

ho 300 300

FGS200 × 200 up to

800 × 1000EI60Sa , EI90Sa * ve

Sa = 33 m3/

(hm2) at 50 Pa

Sa = 33 m3/

(hm2) at 50 Pa

DKIR1 DN 100 up to 630E600120 (ved i ↔ o)

S500 C10000 AA singleve 500

DKIS1200 × 200 up to

1500 × 800E600120 (ved i ↔ o)

S1500 C10000 AA single **ve

500 & 1500 **

DKISMA200 × 200 up to

1600 × 1000EI120 (vew i ↔ o)

S1500 Cmod AA multive 1500

EKIR-E60S DN 100 up to 630E60

(ve ho i ↔ o)S

ve 300 NOINS 300 NOINS

ho 300 NOINS 300 NOINS

www.systemair.com

Page 6: Product Overview - Systemair...Product type Dimensions range (mm) Fire resistivity Supporting construction Installation - tested at underpressure (Pa) Wet Dry Soft crossing Instal.

E828

3 . I

MO

S-Sy

stem

air .

May

201

7

ATEX All ATEX fire dampers are designed for explosion hazardous areas classified as

MULTI Multi-installation in a wall: multiple neighbouring dampers always aligned horizontally and/or vertically with blade axis in horizontal orientation

KIT Up to dimensions W × H = 800 × 600 mm only

* The FGS has resistivity EI60Sa in the upper part & EI90Sa in the lower part of a vertical building element according to ETAG 026 Part 4 art. 2.4.2.1 par. 6

** DKIS1 has resistivity E600 120(ved i↔o)S500 C10000 AA single, for dimensions bigger than W × H = 1200 × 800 mm

P Installation on a wall or out of a wall with Promatect boards insulation for lower ceilings with resistivity EI30/45/60/90S; all PKIS3G and PKIS3GA up to dimensions W × H = 800 × 600 mm only

W Installation on a wall or out of a wall with mineral wool insulation, installation with EI90S up to DN = 400 mm, installation with EI60S up to DN = 500 mm

NOINS Installation on a wall or out of a wall without insulation

The tightness of the blade and the casing according to EN 1751:- 3C for PKIR3G as standard- 2C for other fire damper types as standard- 3C for other fire damper types for extra charge

Modulated fire dampers (the activation mechanism DV9-T-SR) are manufactured: - PKIR3G with DN ≥ 160 mm- PKIR-E60S in all dimensions- PKIS3G with H ≥ 160 mm

RIGID/FLEXIBLE WALL ONLY RIGID WALL/CEILING ONLY IN/ON THE DUCT

Legend

GOOD TO KNOWCurrent information on all fire safety products are available at www.systemair.com/FSPoverview