PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

24
Safe and easy for operators Fully sealed for lifetime Virtually maintenance-free PRODUCT MANUAL SafeRing/SafePlus SF 6 insulated Ring Main Unit and Compact Switchgear

Transcript of PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

Page 1: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

• Safe and easy for operators• Fully sealed for lifetime• Virtually maintenance-free

—P R O D U C T M A N U A L

SafeRing/SafePlusSF6 insulated Ring Main Unit and Compact Switchgear

Page 2: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

2 S a f e R i n g / S a f e P l u s P r o d u c t m a n u a l

Page 3: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

C o n t e n t s 3

05

08

09

17

21

1. General description

2. Transport and handling

3. Installation

4. Operation

5. Maintenance

—Contents

Page 4: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

4 S a f e R i n g / S a f e P l u s P r o d u c t m a n u a l

—Your safety first - Always

That’s why our instruction manual begins with the following recommendations:• Only install/operate switchgear in an environment

suitable for the installation/operation of electrical equipment

• Ensure that installation, operation and maintenance are carried out by specialist electricians only

• Comply in full with the active standards (GB/IEC), the connection conditions of electrical utility and applicable safety at work regulations

• Observe the relevant regulations in the instruction manual for all actions involving switchgear

Danger!Pay special attention to the hazard notes in the instruction manual marked with this warning symbol.

• Make sure that the operating parameters of the switchgear are within the specified data

• Keep the instruction manual accessible to all persons concerned with installation, operation and maintenance

• The user’s personnel are to act responsibly in all operations affecting safety at work and the correct handling of the switchgear

If you have any further questions about this instruction manual, our technicians will be pleased to provide the required information.

Page 5: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

G e n e r a l d e s c r i p t i o n 5

—1 General description

SafeRing is a SF6 insulated ring main unit and SafePlus is a compact switchgear for applications in medium voltage distribution networks. SafeRing can be supplied as a 2, 3, 4 or 5 way standard configurations with additional equipment according to customer specification. DF, CCF, CCC, CCCF, CCFF, CV, CFC,FCC,CCCC, CFFC, CCVV,CCCCC,CCFFF, CCCFF,CCCCF.

SafePlus has a unique flexibility due to its extendibility and the possible combination of fully modular and semi modular configurations. Be、SL、 Sv 、M 、C 、De、D 、F、V、CB.

SafeRing and SafePlus offers a sealed stainless steel tank which contains all the live components and switching functions. The transformer is protected either by a switch fuse combination or a vacuum circuit-breaker.

The units/modules are delivered from the factory ready for installation.

Routine tests are carried out on all units/modules before dispatch.

No special tools are required for installing the equipment.

Available modules are:C - Cable switchF - Switch fuse disconnectorD - Direct cable connectionDe - Direct cable connection with earthingV - Vacuum circuit breakerCB - Circuit Breaker moduleSL - Busbar sectionalizer, load break switch

Busrise needed when SL on right side of SF6 tank

Sv - Busbar sectionalizer, vacuum circuit breaker Sv always together with busrise (total width=650 mm)

Be - Busbar earthingM - Metering cubicle

SafeRing 3 - way unit CCV

Page 6: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

6 S a f e R i n g / S a f e P l u s P r o d u c t m a n u a l

1.1 Table of locations

Upper front cover1. Manometer2. Nameplate module3. Short circuit indicator4. Capacitive voltage indication5. Load break/earthing switch position indicator6. Push buttons close/open operation7. Charged spring indicator8. Self-powered protection relay9. Vacuum circuit-breaker position10. Operation shaft11. Padlock device

Lower front cover12. Nameplate switchgear13. Fuse blown indicator14. Disconnector/earthing switch position indicator15. Capacitive voltage indication

Cable compartment cover16. Cable compartment cover standard17. Cable compartment cover with inspection

window18. Support bar (removable)

Side cover19. Lifting lug20. Operating handle (standard on right hand side)

��� SafePlus

19

10 11

1

2

3

4

12

13

5 6 7 8

9

20

14

15

16

18

17

Page 7: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

280

470

G e n e r a l d e s c r i p t i o n 7

1.2 Dimensional drawings

Unit

1-way

2-way

3-way

4-way

5-way

A

371

696

1021

1346

1671

124

260

Low voltage compartment-side view

Top entry box - side view

595

490

490

A

595

79

2256

2078

178

2

160

8

1336

272

450

146

0

180

6

SafeRing

107

107

325 325

107

107

107107

ABB

Page 8: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

8 S a f e R i n g / S a f e P l u s P r o d u c t m a n u a l

—2 Transport and handling

The units are delivered from the factory ready for installation.

Weight table for standard SafeRing2 - way CF 270 kg2 - way DF 260 kg3 - way CFC 320 kg3 - way CCF 320 kg3 - way CCC 300 kg3 - way FCC 320 kg4 - way CCVV 411 kg4 - way CCCC 390 kg4 - way CCCF 410 kg4 - way CCFF 430 kg4 - way CFFC 430 kg5 - way CCCCC 480 kg5 - way CCFFF 540 kg5 - way CCCFF 520 kg5 - way CCCCF 500 kg

SafePlusStandard 1-way 130 kg2,3 and 4-way as for SafeRing5-way approx. between 480-660 kgM-metering cubicle approx. 250 kg

The weights is without additional equipment

SafeRing/SafePlus is fitted with lifting lugs, but can also be moved on pallets with a forklift truck.

2.1 By receiving inspectionUpon receiving the SafeRing/SafePlus please check that the delivered equipment has not been damaged during transport. If any such damage has occurred, a claim must be submitted to the carrier immediately.

After unpacking, the following must be checked:1. Operating handle 1 piece should be included.2. Check that the pointer on the pressure

indicator is in the green area.3. Carry out a function test on the mechanical parts.

Any faults or omissions must be reported immediately to the supplier.

2.2 StorageSafeRing/SafePlus must be stored under cover in a dry and well-ventilated area until it is installed and put into operation.

Page 9: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

I n s t a l l a t i o n 9

—3 Installation

The base must be flat and fitted with anchor bolts in accordance with the dimensional drawing for the number of modules or units.

Unit

1-way

2-way

3-way

4-way

5-way

A

371

696

1021

1346

1671

B

297

622

947

1272

1597

C

336

663

988

1313

1636

D

371

696

1021

1346

1671

Foundation

Support Bottom Planform

Foundation Channel Steel Planform

10# Channel SteelPart

anchor bolt M12•

Safe-Plus Connection Drawing

A1431

751 250

680

Fuse

595

10

180

Min

10

00

Min

10

00

91.5

10

85

500

1345

107107107107

A475

81

81

64.5

253.

525

3.5

751 25

3.5

3025

3.5

30

27.527.5

M12

B

BD

CD

Ø15

Ø15

100

Page 10: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

10 S a f e R i n g / S a f e P l u s P r o d u c t m a n u a l

Planform of Foundation Channel Steel for Safe-Plus connectedwith 10 kV M or PT Cubicle

10 kV M Cubicle or PT Cubicle

10# Channel Steel

Bottom Assembling Drawingof 10 kV M or PT Cubicle

Foundation of SafePlus connected with 10 kV M or PT Cubicle

Safe Safe

B656B

D 704 D

61

24

0.5

61

656

30

253.

525

3.5

820

.5

695

24

0.5

751

30 30 30

107

253.

5

820

253.

5

253.

5

253.

525

3.5

253.

5

Ø15

Ø15 (6X)

Ø15

Ø15

Page 11: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

I n s t a l l a t i o n 11

Bottom Assembling Drawing of24 kV M Cubicle

Planform of Foundation Channel Steel for Safe-Plus connected with 24 kV M Cubicle

10# Channel Steel

24 kV M Cubicle

Foundation of SafePlus connected with 24 kV M Cubicle

Safe Safe

751

30

B

64

24

3.5 3.5

24

64

D

861

909

B

D

253.

5

1020

253.

530

861900

253.

525

3.5

1020

107

3010

7

253.

525

3.5

30 253.

525

3.5

Ø15

Ø15 (6X)

Ø15

Ø15

Page 12: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

12 S a f e R i n g / S a f e P l u s P r o d u c t m a n u a l

Notice:1. Four M12 expansion bolts should be provided

and used by the customer.2. The depth "H" must be larger than the cable

bending radium and suitable to work. The materials under the first layer RC foundation should be also RC or bricks. Cable channel should be kept between the cable well. the cable channel and the foundation in order that the cable can be connected with the equipment in the outdoor.

B

B+200

AA

1064

±2

A±2

A-A B-B

200 H

100 200600

1200

1650

/175

0/1

850

/215

0

1000

160

Housing profile anchor bolt M12

C C

C C

100

C20 RC foundation

1:201:20 1:20 1:20

B

Cable fixing

Cable fixing

Hole dimension (B-200) X600

3 way safe

1275

1350

4 way safe

1625

1700

5 way safe

1925

2000

5 way+1 way safe

2225

2300

A

B

Foundation of Outdoor

Page 13: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

I n s t a l l a t i o n 13

3.1 Cable compartmentRemoval of cable cover:

NB!The cable cover can be supplied with interlocking to earthing switches. When interlocking is fitted, the cable cabinet can only be accessed when the earthing switch is in the closed position.

A

B

1. Loosen the screws on the cable cover, pull out and lift cover off.

2. Removal of front section.

3. Front section removed. 4. The panel can be removed by unscrewing A and B.

Page 14: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

14 S a f e R i n g / S a f e P l u s P r o d u c t m a n u a l

3.2 Cable connectionSafeRing/SafePlus is equipped with external bushings which comply with DIN47636T1 & T2/EDF HN 525-61 for termination of cables.

All bushings are situated in the same height from the floor and are protected by the cable cover.

Please see supplier documentation for details.

The manufacturer’s installation instructions must be followed. Be sure to lubricate the bushings thoroughly with the silicone supplied.

NB!Where cables are not connected, the earthing switch must be locked in closed position or the bushings must be fitted with deadend recepticals before the unit is put into operation.

Adjustable cable support beam (additional equipment).

Cable support beam

Cable clamp

Earthing bar

Page 15: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

I n s t a l l a t i o n 15

3.3 current transformers for relay protectionInstalling current transformers. The cable shielding is led back through the centre hole and earthed.

A protection relay is installed in each vacuum circuit breaker module. The cables from the protection relay to the current transformers are placed in the cable compartment, ready forconnection to the three current transformers supplied.

Before installation:• Check that the three current transformers have

been delivered and that they are all of the same type

• Check that the current transformers are of the correct type, with the correctly rated transformer ratio, for the distribution transformer’s rated current and for the adjustment range on the protection relay (see protection relay manual)

Each current transformer must be mounted onto its high voltage cable before the cable termination is fitted.

The earth shield on the cable must be led back through the centre hole in the current transformer (see figure on left) and earthed on the earthing bar in the cable compartment. A mounting plate for the current transformers is fitted in the cable compartment.

After the current transformers have been installed in the unit, the cables from the protection relay are connected. Consult the manual supplied with the protection relay for a description of the connections.

SafeRing with vacuum circuit breakers are prepared for protection relay: REJ603. It is designed so that there is no need for external auxiliary voltage for correct functioning.

Separate manuals have been prepared for each of these protection relay, with examples of adjustments.

It is essential for correct functioning that the current transformers are properly connected and that the protection relay is properly adjusted.

The cable shielding is led back through the centre hole and earthed.

Page 16: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

16 S a f e R i n g / S a f e P l u s P r o d u c t m a n u a l

Refilling of SF6 gas in SafeRing/SafePlusFollowing equipment is needed gas bottle with manometer and reduction valve adapter pressure measuring device.1. Remove front cover and unscrew manometer

as shown.2. Screw (tightening the torque.45 Nm) the

adapter to the valve.3. Before connecting the hose from the gas bottle

to the adapter, the air in the hose must be removed by running SF6 gas through the hose.

4. When gas is flowing into the RMU/switchgear, the manometer on the gas bottle has to be observed. When it shows 0.4 bar at ambient temperature 20°C, (14 bar absolute) the gas filling must be stopped. See table for filling pressure above.

5. Remove the filling hose and connect the pressure device to check the pressure inside the RMU/switchgear.

6. When the correct pressure of 0.4 bar (14 bar absolute) is obtained, remove the adapter and screw with tightening torque 45 Nm the manometer to the RMU/switchgear as shown above. Observe that the sealing between the manometer and the valve is smooth and clean.

3.4 Gas pressureSafeRing/SafePlus contains SF6 gas with a nominal pressure of 1.4 bar at 20°C.

SafeRing/SafePlus is sealed for life and is fitted with a temperature-compensated pressure indicator.

A temperature-compensated device that emits an electrical signal to indicate lower pressure can be supplied on request.

Pointer in green area-unit has correct pressurePointer in red area-pressure is too low.

SF6Air

Valve NOTE! Screw/unscrewon this hexagonal nut only

Fillingpressurembar

Atm.pressurembar

30°C25°C20°C15°C10°C

amb

ient

tem

p.

1400

1300

1200

900 925 950 975 1000 1025 1050 1075 1100

NHP 408025

Page 17: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

O p e r a t i o n 17

—4 Operation

4.1 Operating conditionsNormal ambient conditionsSafeRing/SafePlus is generally equipped for operation/service in normal indoor conditions in accordance with IEC 60694.

The following limitations apply:Ambient temperatureMax. temperature +40°CMax. temperature (24-hour average) +35°CMin. temperature -40°C

HumidityMax. average relative humiditymeasured over 24 hours 95%Max. average relative humiditymeasured over 1 month 90%

Max height above sea level for installation without reducing gas pressure 1,500 metres

Special conditionsIn accordance with IEC 60694, the manufacturer and end-user must agree about special operating conditions which deviate from operation under normal conditions.

The manufacturer/supplier must be consulted in advance if especially difficult operating conditions are involved. When electrical equipment is installed at more than 1,500 metres above sea level, for example, the atmospheric pressure will be lower and the overpressure in the tank will have to be reduced.

AirfreightUnits/modules delivered with redused overpressure-see procedure for refilling.

4.2 OperationAll switches can be operated with the included operating handle.

Internal mechanical interlocking between the switch disconnector/circuit breaker and the associated earthing switches prevents incorrect operation. The operation of the switch disconnector/circuit breaker and earthing switches can be further interlocked by means of a padlock. The earthing switches are operated by a snap action mechanism, which ensures fast closing.

The earthing switch is closed by turning the operating handle clockwise. Turning the operating handle anti-clockwise opens the switch.

For closing the transformer switch the spring mechanism must be charged. Turning the operating handle clockwise does this. Then the green on button must be pressed to close the switch/breaker.

An anti-reflex system, standard on all operating handles, prevents the immediate re-operation of switches.

Page 18: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

18 S a f e R i n g / S a f e P l u s P r o d u c t m a n u a l

D

A

C

B

Switch disconnector:Close: Turn the operating handle clockwise.Open: Turn the operating handle anti-clockwise.

Mechanical position indicators:C: Transformer breaker open D: Earthing switch closed

Earthing switch:Close: Turn the operating handle clockwise.Open: Turn the operating handle anti-clockwise.

Fuse switch disconnector.Close: Turn the operating handle clockwise to

charge the close/open spring. Then push the green button. (A)

Open: Push the red button. (B)In circuit breaker configurations, the transformer circuit breaker can be tripped by the protection relay, while in switch fuse configurations fuse switch disconnector can be triggered by the fuse striker pin if an over current or short-circuit occurs.

Page 19: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

O p e r a t i o n 19

4.3 Installation and replacement of fusesA red indicator below the fuse symbol on the lower front panel indicates a fuse trip. Fuses are replaced as shown in the sequence of illustrations. Switch fuse configurations are supplied without fuses installed.

When installing fuses for the first time, follow the sequence of illustrations 1-9.

1. Fuse trip indicator.

2. Close earthing switch by turning operating handle clockwise.

3. Unscrew fuse cover.

4. Tilt out the fusepanel to gain access to fuse canisters.

5. Applying the operating handle and turning anti-clockwise opens the fuse canisters.

Page 20: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

20 S a f e R i n g / S a f e P l u s P r o d u c t m a n u a l

6. Pull out the fuse handle. The fuses are firmly fixed in the fuse cover.

8. Turn the handle on the fuse cover clockwise to close and seal the fuse canister. Use the operating handle.

9. Close the fuse panel.The switches are ready for operation.

7. Fix the fuses to the fuse cover using the contact screw• The striker must point out from the fuse canister for

the fuse to function properly.

Fuse

Striker

Fasten the contactscrew on thelocking ring.

Page 21: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

M a i n t e n a n c e 21

—5 Maintenance

All components in the SF6 tank are maintenance-free for the declared life expectancy of the product. The tank is made of stainless steel.

If the panels substain any scratches or damage, these must be repaired with paint to prevent corrosion.

Mechanical parts are positioned outside the tank and behind the front panel. This enables easy access and replacement if required.

Mechanical parts are surface-treated to prevent corrosion. Moving parts are lubricated at the factory for the product’s life expectancy. In extreme conditions (dust, sand and pollution), inspection and maintenance will be imperative, and in some cases replacements will be necessary. Check that the lubricant is not washed or wiped away from the mechanical moving parts.

5.1 Control and monitoring the gasSafeRing/SafePlus is a pressure-sealed system that normally does not require special inspections. However the gas pressure on the manometer should always be checked prior to operation.

Page 22: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

22 S a f e R i n g / S a f e P l u s P r o d u c t m a n u a l

5.2 Environmental certification1. Life expectancy of productThe product is developed in compliance with the requirements denoted by IEC 62271-200. The design incorporates a life span under indoor service conditions exceeding 30 years.

3. End-of-lifeABB Distribusjon is committed to the protection of the environment and adhere to ISO 14001 standards. It is our obligation to facilitate end-of-life recycling for our products.

There exist no explicit requirements for how to handle discarded switchgears at end-of-life. ABB’s recycling service is accordi ng to IEC 1634 edition 1995 section 6: End of life of SF6 filled equipment

The switchgear is gas-tight with an expected diffusion rate of less than 0.1 % per annum. Referring to the reference-pressure of 1.4 bar,the switchgear will maintain gas-tightness and a gas-pressure better than 1.3 bar* throughout its designed life span.

*) at 20°C.

2. Recycling capability

Raw Material

Iron

Stainless steel

Copper

Brass

Aluminium

Zinc

Silver

Thermoplastic

Epoxy incl.

60% quartz

Rubber

Dielectric oil

SF6 gas

Total for recycling

Not specified *

Total weight **

Packing foil

Wooden pallet

Amount

132.80 kg

83.20 kg

43.98 kg

2.30 kg

8.55 kg

3.90 kg

0.075 kg

5.07 kg

26.75 kg

1.35 kg

0.21 kg

3.24 kg

311.44 kg

9.00 kg

320.00 kg

0.2 kg

21.5 kg

% of total

weight

320 kg

42.53%

24.93%

14.09%

0.74%

2.74%

1.25%

0.024%

1.63%

8.35%

0.42%

0.066%

1.04%

97.25%

100%

Re-cycle

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Environmental effects & recycle/reuse processes

Separate, utilise in favour of new source (ore)

Separate, utilise in favour of new source (ore)

Separate, utilise in favour of new source (ore)

Separate, utilise in favour of new source (ore)

Separate, utilise in favour of new source (ore)

Separate, utilise in favour of new source (ore)

Electrolysis, utilise in favour of new source

Make granulate, re-use or apply as energy superior

additive in refuse incineration

Grind to powder and use as high-grade energy additive

in cement mill

High-grade energy additive in refuse incineration

Reclaim or use as High-grade energy additive

in refuse incineration

Reclaim

* Stickers, Film-foils, powder coating, screws, nuts,

tiny components, grease.

High-grade energy additive in refuse incineration

Re-use or use as energy additive in refuse incineration

**) All figures are collected from CCF 3-way unit with arc suppresser.

and in particular 6.5.2.a: Low decomposition: No special action is required; nonrecoverableparts can be disposed of normally according to local regulations.

We also recommend ABB’s website : http://www.abb.com/sf6 .

Page 23: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

23

Page 24: PRODUCT MANUAL SafeRing/SafePlus SF insulated Ring Main ...

1YV

A0

00

24_E

N R

EV

D 0

2-20

21

© Copyright 2019 ABB. All rights reserved. Specifications subject to change without notice.

— ABB Beijing Switchgear Limited3F, Building No. 2, No. 12 Jingyuan Street, Beijing Economic and Technological Development Zone, Beijing, ChinaTel: 010-8709 9199Fax: 010-8709 9299

ABB China Customer Service Hot LineTEL: 800-820-9696 / 400-820-9696mail: [email protected]

www.abb.com