Product Information Air Conditioning Wall Mounted System ... Info Sheet.pdf · Heat Pump Wall...
Transcript of Product Information Air Conditioning Wall Mounted System ... Info Sheet.pdf · Heat Pump Wall...
PKA-RP Power InverterHeat PumpWall Mounted System
Our wide range of power invertersoffer customers high seasonal efficiency,advanced control options and quiet operation, whilst providing greaterflexibility and ease of installation.
Product Information
Air Conditioning PKA-RP Power Inverter Heat PumpWall Mounted System
Key FeaturesSwing Vane Mode with Auto Vane Shutter
Infra-red remote controller
Auto-Restart
Quiet operation
Auto-Changeover
Hot Start - draught prevention
Factory charged refrigerant up to 30m
Standard filter
Quick clean design
Replace Technology available
Refrigerant volume check function
Duty Standby Operation
Demand Control
Noise Reduction
Optional Heating Only
UNITED KINGDOM Mitsubishi Electric Europe Living Environmental Systems DivisionTravellers Lane, Hatfield, Hertfordshire, AL10 8XB, England General Enquiries Telephone: 01707 282880 Fax: 01707 278881IRELAND Mitsubishi Electric Europe Westgate Business Park, Ballymount, Dublin 24, IrelandTelephone: Dublin (01) 419 8800 Fax: Dublin (01) 419 8890 International code: (003531)
Telephone: 01707 282880email: [email protected] web: www.airconditioning.mitsubishielectric.co.uk
Country of origin: United Kingdom – Japan – Thailand – Malaysia. ©Mitsubishi Electric Europe 2013. Mitsubishi and Mitsubishi Electric are trademarks of Mitsubishi Electric Europe B.V. The company reserves theright to make any variation in technical specification to the equipment described, or to withdraw or replace products without prior notification or public announcement. Mitsubishi Electric is constantly developingand improving its products. All descriptions, illustrations, drawings and specifications in this publication present only general particulars and shall not form part of any contract. All goods are supplied subject tothe Company’s General Conditions of Sale, a copy of which is available on request. Third-party product and brand names may be trademarks or registered trademarks of their respective owners.
Product Information
Air Conditioning PKA-RP Power Inverter Heat PumpWall Mounted System
CAPACITY (kW) Heating (nominal) Cooling (nominal) Heating (UK) Cooling (UK)SHF (nominal & UK)COP / EER (nominal)SCOP / SEER (BS EN14825)ErP ENERGY EFFICIENCY CLASS Heating/CoolingAIRFLOW (m3/min) Lo-Mi-HiPIPE SIZE mm (in) Gas LiquidSOUND PRESSURE LEVEL (dBA)SOUND POWER LEVEL (dBA) DIMENSIONS (mm) Width x Depth x HeightWEIGHT (kg)ELECTRICAL SUPPLYFUSE RATING (BS88) - HRC (A)INTERCONNECTING CABLE No. Cores
PKA-RP - INDOOR UNITS4.1 (1.6-5.2)3.6 (1.6-4.5)3.5 (1.35-4.4)3.3 (1.45-4.15)
0.813.83 / 3.833.9 / 5.7A / A+9-10.5-1212.7 (1/2”)6.35 (1/4”)36-40-4360
898 x 249 x 29513
Fed by Outdoor Unit64
5.0 (2.5-7.3)4.6 (2.3-5.6)4.25 (2.15-6.2)4.23 (2.1-5.15)
0.723.33 / 3.264.0 / 5.3A+ / A9-10.5-1212.7 (1/2”)6.35 (1/4”)36-40-4360
898 x 249 x 29513
Fed by Outdoor Unit64
7.0 (2.8-8.2)6.1 (2.7-6.7)5.95 (2.4-6.95)5.5 (2.5-6.15)
0.863.57 / 3.814.2 / 6.3A+ / A++18-20-2215.88 (5/8”)9.52 (3/8”)39-42-4564
1170 x 295 x 36521
Fed by Outdoor Unit64
8.0 (3.5-10.2)7.1 (3.3-8.1)6.8 (3.0-8.65)6.55 (3.05-7.45)
0.783.65 / 3.944.3 / 6.5A+ / A++18-20-2215.88 (5/8”)9.52 (3/8”)39-42-4564
1170 x 295 x 36521
Fed by Outdoor Unit64
11.2 (4.5-14.0)10.0 (4.9-11.4)9.5 (3.85-11.9)9.2 (4.5-10.5)
0.733.68 / 3.774.0 / 6.1A+ / A++20-23-2615.88 (5/8”)9.52 (3/8”)41-45-4965
1170 x 295 x 36521
Fed by Outdoor Unit64
INDOOR PRICE
PKA-RP35HAL PKA-RP50HAL PKA-RP60KAL PKA-RP71KAL PKA-RP100KAL
PUHZ-ZRP - OUTDOOR UNITSSOUND PRESSURE LEVEL (dBA) Heating/CoolingSOUND POWER LEVEL (dBA) CoolingWEIGHT (kg)DIMENSIONS (mm) Width x Depth x HeightELECTRICAL SUPPLYPHASE Heating/Cooling (nominal) Heating/Cooling (UK)STARTING CURRENT (A)SYSTEM RUNNING CURRENT (A) Heating/Cooling [MAX] FUSE RATING (BS88) - HRC (A)MAINS CABLE No. CoresMAX PIPE LENGTH (m)MAX HEIGHT DIFFERENCE (m)CHARGE R410A (kg) - 30m
46 / 446543
809 x 300 x 630220-240v, 50Hz
Single1.07 / 0.940.84 / 0.914.0
4.22 / 3.94 [13.4]16350302.2
46 / 446546
809 x 300 x 630220-240v, 50Hz
Single1.50 / 1.411.25 / 1.285.0
7.16 / 6.59 [13.4]16350302.4
48 / 476767
950 x 330 + 30 x 943220-240v, 50Hz
Single1.96 / 1.601.42 / 1.675.0
9.23 / 8.11 [19.4]25350303.5
48 / 476767
950 x 330 + 30 x 943220-240v, 50Hz
Single2.19 / 1.801.60 / 1.866.0
8.75 / 7.79 [19.4]25350303.5
51 / 4969116
1050 x 330 + 30 x 1338220-240v, 50Hz
Single3.04 / 2.652.36 / 2.5812.0
11.46 / 11.44 [ 27.1]32375305.0
PUHZ-ZRP35VKA PUHZ-ZRP50VKA PUHZ-ZRP60VHA PUHZ-ZRP71VHA PUHZ-ZRP100VKA
11.2 (4.5-14.0)10.0 (4.9-11.4)9.5 (3.85-11.9)9.2 (4.5-10.5)
0.733.68 / 3.774.0 / 6.0A+ / A+20-23-2615.88 (5/8”)9.52 (3/8”)41-45-4965
1170 x 295 x 36521
Fed by Outdoor Unit64
PKA-RP100KAL
51 / 4969124
1050 x 330 + 30 x 1338380-415v, 50Hz
Three3.04 / 2.652.36 / 2.584.0
4.82 / 4.41 [8.616575305.0
PUHZ-ZRP100YKAThree Phase
SYSTEM POWERINPUT (kW)
3
Three Phase3
Effective as of February 2013