Probe Start Metal Halide Pulse Start Metal Halide High ... BALLASTS Probe Start Metal Halide Pulse...
-
Upload
phungnguyet -
Category
Documents
-
view
249 -
download
0
Transcript of Probe Start Metal Halide Pulse Start Metal Halide High ... BALLASTS Probe Start Metal Halide Pulse...
HID BALLASTS
Probe Start Metal Halide Pulse Start Metal Halide High Pressure Sodium
13 Columbia Dr. #12 Amherst, NH 03031 www.souheganlighting.com
Toll Free: 877-610-4010 Phone: 603-889-8962 Fax: 603-889-0291
Ballast Specification Page
Probe Start 3
175W Quad MH 4
175W 480V MH 5
250W Quad MH 6
250W Quad 3X4 MH 7
250W 480V MH 8
400W Quad MH 9
400W 480V MH 10
1000W Quad MH 11
1000W Quad 4X4 MH 12
1000W 480V MH 13
1500W Quad MH 14
1500W 480V MH 15
Pulse Start 16
50W Quad PS 17
70W Quad PS 18
100W Quad PS 19
125W Quad PS 20
150W Quad PS 21
175W Quad PS 22
200W Quad PS 23
200W 480V PS 24
250W Quad PS 25
250W 480V PS 26
320W Quad PS 27
320W 480V PS 28
350W Quad PS 29
350W 480V PS 30
Ballast Specification Page
400W Quad PS 31
400W 480V PS 32
450W Quad PS 33
450W 480V PS 34
575W Quad PS 35
575W 480V PS 36
750W Quad PS 37
750W 480V PS 38
875W Quad PS 39
875W 480V PS 40
1000W Quad PS 41
1000W 480V PS 42
High Pressure Sodium 43
35W 120V HPS 44
50W 120V HPS 45
70W 120V HPS 46
70W Quad HPS 47
100W 120V HPS 48
100W Quad HPS 49
150W 120V HPS 50
150W Quad HPS 51
150W 480V HPS 52
250W Quad HPS 53
250W 480V HPS 54
400W Quad HPS 55
400W 480V HPS 56
1000W Quad HPS 57
1000W 480V HPS 58
2
HID BALLASTS
Probe Start Metal Halide
13 Columbia Dr. #12 Amherst, NH 03031 www.souheganlighting.com
Toll Free: 877-610-4010 Phone: 603-889-8962 Fax: 603-889-0291
3
Input Volts 120 208 240 277
Line Current ( Amps ) Operating Open Circuit Starting
1.80 1.20 1.60
1.10 0.65 0.90
0.90 0.60 0.80
0.80 0.50 0.70
Recommended Fuse (Amps) 5 3 3 2 Regulation
Line Volts Lamp Watts
± 10% ± 7%
± 10% ± 7%
± 10% ± 7%
± 10% ± 7%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H) C
80.0
180 (H) D
89.7
180 (H) D
85.8
180 (H) C
84.7
Power Factor (Min) Input Watts Efficiency
90% 210 W
90% 210 W
90% 210 W
90% 210 W
NOM. Open Circuit Voltage 320 320 320 320 Input Voltage At Lamp Dropout 65 115 130 150
Min Ambient Starting Temp -20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
1,650 V 2,000 V
290 – 355
1.55
1.95 1.20
1.80
1,650 V 2,000 V
290 – 355
1.55
1.95 0.65
1.05
1,650 V 2,000 V
290 – 355
1.55
1.95 0.60
0.90
1,650 V 2,000 V
290 – 355
1.55
1.95 0.50
0.80
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
2.22 in 3.60 in 6.8 lbs 12 ‘’
2.22 in 3.60 in 6.8 lbs 12 ‘’
2.22 in 3.60 in 6.8 lbs 12 ‘’
2.22 in 3.60 in 6.8 lbs 12 ‘’
Capacitor Requirement Microfarads Volts (Min)
10.0 uf 400 V
10.0 uf 400 V
10.0 uf 400 V
10.0 uf 400 V
BALLAST SPECIFICATIONS
175W M57 Metal Halide S175M-4 60 Hz CWA
3X4 Core.WMF
Capacitor: CA10400 / CA10400DL Ignitor: None
Microfarads: 10.0 uf 10.0 uf Volts (Max): 400 V 400 V Case Temp (Max): 100° C 100° C Height (Max): 2.75 in 3.68 in Dia (Max): 1.62 in 1.61 in Oval Width (Max): 2.75 in
4
Input Volts 480 Line Current ( Amps )
Operating Open Circuit Starting
0.45 0.35 0.30
Recommended Fuse (Amps) 2 Regulation
Line Volts Lamp Watts
±10% ± 7%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
B 79.2
Power Factor (Min) Input Watts Efficiency
90%
211 W
NOM. Open Circuit Voltage 320 Input Voltage At Lamp Dropout 240
Min Ambient Starting Temp -20°F/ -30° C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,400 V
285 – 355
1.55
1.95 0.25
0.45
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
2.22 in 3.60 in 6.8 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
10.0 uf 400 V
BALLAST SPECIFICATIONS
175W M57 Metal Halide S175M - 48/12 60 Hz CWA
3X4 CORE.WMF
Capacitor: CA10400 /CA10400DL Ignitor: None
Microfarads: 10.0 uf 10.0 uf Volts (Max): 400 V 400 V Case Temp (Max): 100° C 100° C Height (Max): 2.75 in 3.68 in Dia (Max): 1.62 in 1.61 in Oval Width (Max): 2.75 in
5
Input Volts 120 208 240 277
Line Current ( Amps ) Operating Open Circuit Starting
2.50 2.40 1.80
1.45 1.30 0.90
1.25 1.20 0.90
1.10 1.00 0.80
Recommended Fuse (Amps) 8 5 5 3 Regulation
Line Volts Lamp Watts
±10% ±8%
±10% ±8%
±10% ±8%
±10% ±8%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
B 77.8
180 (H)
B 76.8
180 (H)
B 77.1
180 (H)
B 78.7
Power Factor (Min) Input Watts Efficiency
90% 289W
90% 289W
90% 289W
90% 289W
NOM. Open Circuit Voltage 305 305 305 305 Input Voltage At Lamp Dropout 55 90 110 120
Min Ambient Starting Temp -20°C/ -30°F
-20°C/ -30°F
-20°C/ -30°F
-20°C/ -30°F
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
1,650 V 2,000 V 275-335
2.20
2.70 1.40
2.20
1,650 V 2,000 V 275-335
2.20
2.70 0.80
1.30
1,650 V 2,000 V 275-335
2.20
2.70 0.70
1.10
1,650 V 2,000 V 275-335
2.20
2.70 0.60
1.00
CORE and COIL Specifications
Dimension (A) Dimension (B) Weight Lead Lengths
1.65 in 3.25 in 9.3 lbs
12”
1.65 in 3.25 in 9.3 lbs
12”
1.65 in 3.25 in 9.3 lbs
12”
1.65 in 3.25 in 9.3 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
15.0 uf 400 V
15.0 uf 400 V
15.0 uf 400 V
15.0 uf 400 V
BALLAST SPECIFICATIONS
250W M58 Metal Halide S250M-4 60 Hz CWA
4x4 CORE.WMF
Capacitor: CA15400 / CA15400DL Ignitor: None
6
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
2.60 1.90 2.00
1.45 1.00 1.20
1.30 0.95 1.00
1.10 0.80 0.85
Recommended Fuse (Amps) 8 5 5 3 Regulation
Line Volts Lamp Watts
±10% ±7%
±10% ±7%
±10% ±7%
±10% ±7%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
B 76.0
180 (H)
A 74.4
180 (H)
C 82.9
180 (H)
B 79.5
Power Factor (Min) Input Watts Efficiency
90% 291 W
90% 291 W
90% 291 W
90% 291 W
NOM. Open Circuit Voltage 305 305 305 305 Input Voltage At Lamp Dropout 65 115 130 150
Min Ambient Starting Temp -20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
1,600 V 2,000 V
275 – 335
2.20
2.70 1.60
2.50
1,600 V 2,000 V
275 – 335
2.20
2.70 0.90
1.40
1,600 V 2,000 V
275 – 335
2.20
2.70 0.80
1.25
1,600 V 2,000 V
275 – 335
2.20
2.70 0.70
1.10
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
2.80 in 4.20 in 85. lbs
12”
2.80 in 4.20 in 85. lbs
12”
2.80 in 4.20 in 85. lbs
12”
2.80 in 4.20 in 85. lbs
12”
Capacitor Requirement Microfarads Volts (Min)
15.0 uf 360 V
15.0 uf 360 V
15.0 uf 360 V
15.0 uf 360 V
BALLAST SPECIFICATIONS
250W M58 Metal Halide S250M-4/3X4 60 Hz CWA
3X4 CORE.WMF
Capacitor: CA15400 / CA15400DL Ignitor: None
7
Input Volts 480
Line Current ( Amps ) Operating Open Circuit Starting
.63
0.55 0.50
Recommended Fuse (Amps) 2 Regulation
Line Volts Lamp Watts
±10% ±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
B
Power Factor (Min) Input Watts Efficiency
90% 295W
NOM. Open Circuit Voltage 305 Input Voltage At Lamp Dropout 210
Min Ambient Starting Temp -20°C/ -30°F
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,400 V
275 – 335
2.20
2.70 0.35
0.55
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
1.55 in 3.35 in 8.8 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
15.0 uf 400 V
BALLAST SPECIFICATIONS
250W M58 Metal Halide S250M-48/12 60 Hz CWA
4X4 CORE.WMF
Capacitor: CA15400 / CA15400DL Ignitor: None
8
Input Volts 120 208 240 277
Line Current ( Amps ) Operating Open Circuit Starting
4.00 3.50 2.80
2.30 2.00 1.60
2.00 1.75 1.40
1.75 1.50 1.20
Recommended Fuse (Amps) 10 6 5 5 Regulation
Line Volts Lamp Watts
±10% ±9%
±10% ±9%
±10% ±9%
±10% ±9%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
D 88.6
180 (H)
D 89.9
180 (H)
E 90.8
180 (H)
E 92.5
Power Factor (Min) Input Watts Efficiency
90% 458W 87%
90% 458W 87%
90% 458W 87%
90% 458W 87%
NOM. Open Circuit Voltage 300 300 300 300 Input Voltage At Lamp Dropout 52 90 105 120
Min Ambient Starting Temp -20°C/ -30°F
-20°C/ -30°F
-20°C/ -30°F
-20°C/ -30°F
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
1,600 V 1,900 V 270-330
3.45
4.25 2.20
3.40
1,600 V 1,900 V 270-330
3.45
4.25 1.25
2.00
1,600 V 1,900 V 270-330
3.45
4.25 1.10
1.70
1,600 V 1,900 V 270-330
3.45
4.25 0.95
1.45
CORE and COIL Specifications
Dimension (A) Dimension (B) Weight Lead Lengths
2.00 in 3.90 in 10.7 lbs
12”
2.00 in 3.90 in 10.7 lbs
12”
2.00 in 3.90 in 10.7 lbs
12”
2.00 in 3.90 in 10.7 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
24.0 uf 360 V
24.0 uf 360 V
24.0 uf 360 V
24.0 uf 360 V
BALLAST SPECIFICATIONS
400W M59 Metal Halide S400M-4 60 Hz CWA
4X4 CORE.WMF
Capacitor: CA24400 / CA24400DL Ignitor: None
9
Input Volts 480
Line Current ( Amps ) Operating Open Circuit Starting
1.00 0.90 0.70
Recommended Fuse (Amps) 3 Regulation
Line Volts Lamp Watts
±10% ±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
E 90.1
Power Factor (Min) Input Watts Efficiency
90% 457W
NOM. Open Circuit Voltage 300 Input Voltage At Lamp Dropout 220
Min Ambient Starting Temp -40°F/ -40°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,400 V 270-330
3.40
4.20 0.45
0.70
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
2.15 in 4.10 in 11.5 lbs
Capacitor Requirement Microfarads Volts (Min)
24.0 uf 360 V
BALLAST SPECIFICATIONS
400W M59 Metal Halide S400M-48/12 60 Hz CWA
4X4 CORE.WMF
Capacitor: CA24400 / CA24400DL Ignitor: None
10
Input Volts 120 208 240 277
Line Current ( Amps ) Operating Open Circuit Starting
9.00 5.35 6.30
5.55 3.95 3.50
4.60 2.95 3.25
4.00 2.50 2.85
Recommended Fuse (Amps) 22 15 12 10 Regulation
Line Volts Lamp Watts
±10% ±10%
±10% ±10%
±10% ±10%
±10% ±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
D 89.4
180 (H)
D 89.9
180 (H)
C 82.4
180 (H)
C 84.9
Power Factor (Min) Input Watts Efficiency
90% 1085W
90% 1085W
90% 1085W
90% 1085W
NOM. Open Circuit Voltage 420 420 420 420 Input Voltage At Lamp Dropout 75 120 140 160
Min Ambient Starting Temp -20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,500 V 375-460
4.80
5.90 5.05
7.60
2,000 V 2,500 V 375-460
4.80
5.90 2.80
4.20
2,000 V 2,500 V 375-460
4.80
5.90 2.60
3.90
2,000 V 2,500 V 375-460
4.80
5.90 2.25
3.40
CORE and COIL Specifications
Dimension (A) Dimension (B) Weight Lead Lengths
2.80 in 4.95 in 18.5 lbs
12”
2.80 in 4.95 in 18.5 lbs
12”
2.80 in 4.95 in 18.5 lbs
12”
2.80 in 4.95 in 18.5 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
24.0 uf 480 V
24.0 uf 480 V
24.0 uf 480 V
24.0 uf 480 V
BALLAST SPECIFICATIONS
1000W M47 / H36 Metal Halide S1000M-4 60 Hz CWA
4X8 CORE.WMF
Capacitor: CA24480 Ignitor: None
11
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
8.80 6.70 5.50
5.00 3.60 3.20
4.60 3.70 2.80
3.90 3.10 2.40
Recommended Fuse (Amps) 22 13 12 10 Regulation
Line Volts Lamp Watts
±10% ±10%
±10% ±10%
±10% ±10%
±10% ±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
D 89.4
180 (H)
A 74.0
180 (H)
B 79.9
180 (H)
C 82.0
Power Factor (Min) Input Watts Efficiency
90% 1085 W
90% 1085 W
90% 1085 W
90% 1085 W
NOM. Open Circuit Voltage 420 420 420 420 Input Voltage At Lamp Dropout 60 110 130 140
Min Ambient Starting Temp -20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
1,650 V 2,000 V
375 – 465
4.65
5.70 4.15
6.25
1,650 V 2,000 V
375 – 465
4.65
5.70 2.50
3.85
1,650 V 2,000 V
375 – 465
4.65
5.70 2.10
3.25
1,650 V 2,000 V
375 – 465
4.65
5.70 1.85
2.85
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
3.25 in 5.45 in 18.5 lbs
12”
3.25 in 5.45 in 18.5 lbs
12”
3.25 in 5.45 in 18.5 lbs
12”
3.25 in 5.45 in 18.5 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
24.0 uf 450 V
24.0 uf 450 V
24.0 uf 450 V
24.0 uf 450 V
BALLAST SPECIFICATIONS
1000W M47 / H36 Metal Halide S1000M-4/4X4 60 Hz CWA
4X4 CORE.WMF
Capacitor: CA24480 Ignitor: None
12
Input Volts 480
Line Current ( Amps ) Operating Open Circuit Starting
2.30 1.55 1.55
Recommended Fuse (Amps) 6 Regulation
Line Volts Lamp Watts
±10% ±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H) D
88.7
Power Factor (Min) Input Watts Efficiency
90% 1085W
NOM. Open Circuit Voltage 420 Input Voltage At Lamp Dropout 260
Min Ambient Starting Temp -20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,400 V
375 – 460
4.30
6.40 1.25
1.85
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
2.80 in 4.90 in 18.5 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
24.0 uf 480 V
BALLAST SPECIFICATIONS
1000W M47 Metal Halide S1000M-48/12 60 Hz CWA
4X6 CORE.WMF
Capacitor: CA24480 Ignitor: None
13
Input Volts 120 208 240 277
Line Current ( Amps ) Operating Open Circuit Starting
13.40 6.30
11.30
7.75 3.65 6.50
6.70 3.15 5.65
5.80 2.75 4.90
Recommended Fuse (Amps) 34 19 17 15 Regulation
Line Volts Lamp Watts
±10% ±12%
±10% ±12%
±10% ±12%
±10% ±12%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
G 101.6
180 (H)
E 90.4
180 (H)
E 92.4
180 (H) E
93.4 Power Factor (Min) Input Watts Efficiency
90% 1605W
90% 1605W
90% 1605W
90% 1605W
NOM. Open Circuit Voltage 440 440 440 440 Input Voltage At Lamp Dropout 80 140 160 185
Min Ambient Starting Temp -20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,500 V
385 – 475
7.30
9.00 9.90
12.10
2,000 V 2,500 V
385 – 475
7.30
9.00 5.70
7.05
2,000 V 2,500 V
385 – 475
7.30
9.00 4.95
6.05
2,000 V 2,500 V
385 – 475
7.30
9.00 4.30
5.30
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
4.10 in 6.10 in 31.0 lbs
12”
4.10 in 6.10 in 31.0 lbs
12”
4.10 in 6.10 in 31.0 lbs
12”
4.10 in 6.10 in 31.0 lbs
12” Capacitor Requirement
Microfarads Volts (Min)
32.0 uf 525 V
32.0 uf 525 V
32.0 uf 525 V
32.0 uf 525 V
BALLAST SPECIFICATIONS
1500W M48 Metal Halide S1500M-4 60 Hz CWA
4X8 CORE.WMF
Capacitor: CA32525 Ignitor: None
14
Input Volts 480 Line Current ( Amps )
Operating Open Circuit Starting
3.40 1.65 3.00
Recommended Fuse (Amps) 10 Regulation
Line Volts Lamp Watts
±10% ±12%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
E 92.5
Power Factor (Min) Input Watts Efficiency
90% 1625 W
NOM. Open Circuit Voltage 450 Input Voltage At Lamp Dropout 265
Min Ambient Starting Temp -20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000V 2,400V
405 – 495
7.20
8.80 2.40
3.60
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
4.20 in 6.20 in 31.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
32.0 uf 525 V
BALLAST SPECIFICATIONS
1500W M48 Metal Halide S1500M-48/12 60 Hz CWA
4X6 CORE.WMF
Capacitor: CA325525 Ignitor: None
15
HID BALLASTS
Pulse Start Metal Halide
13 Columbia Dr. #12 Amherst, NH 03031 www.souheganlighting.com Toll Free: 877-610-4010 Phone: 603-889-8962 Fax: 603-889-0291
16
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
0.60 1.20 0.60
0.35 0.65 0.35
0.30 0.60 0.30
0.25 0.50 0.25
Recommended Fuse (Amps) 3 2 2 2 Regulation
Line Volts Lamp Watts
±5%
±10%
±5%
±10%
±5%
±10%
±5%
±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
A 66.6
180 (H)
A 64.7
180 (H)
A 64.3
180 (H)
A 70.7
Power Factor (Min) Input Watts Efficiency
90% 68 W
90% 68 W
90% 68 W
90% 68 W
NOM. Open Circuit Voltage 265 265 265 265 Input Voltage At Lamp Dropout 85 150 170 195
Min Ambient Starting Temp -20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,500 V
235 – 295
0.65
0.85 0.40
0.75
2,000 V 2,500 V
235 – 295
0.65
0.85 0.20
0.40
2,000 V 2,500 V
235 – 295
0.65
0.85 0.15
0.35
2,000 V 2,500 V
235 – 295
0.65
0.85 0.15
0.35
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
1.05 in 2.45 in 3.5 lbs
12”
1.05 in 2.45 in 3.5 lbs
12”
1.05 in 2.45 in 3.5 lbs
12”
1.05 in 2.45 in 3.5 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
6.0 uf 280 V
6.0 uf 280 V
6.0 uf 280 V
6.0 uf 280 V
BALLAST SPECIFICATIONS
50W M110 Pulse Start Metal Halide S50M-4 60 Hz HX-HPF
3X4 CORE.WMF
Capacitor: CA6280DL Ignitor: SMH-2
17
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
0.80 1.65 0.75
0.45 0.95 0.55
0.40 0.80 0.50
0.35 0.70 0.35
Recommended Fuse (Amps) 4 3 2 2 Regulation
Line Volts Lamp Watts
±5% ±8%
±5% ±8%
±5% ±8%
±5% ±8%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
A 60.9
180 (H)
A 63.0
180 (H)
A 62.4
180 (H)
A 64.1
Power Factor (Min) Input Watts Efficiency
90% 92 W 76%
90% 92 W 76%
90% 92 W 76%
90% 92 W 76%
NOM. Open Circuit Voltage 250 250 250 250 Input Voltage At Lamp Dropout 85 140 165 185
Min Ambient Starting Temp -20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
1,600 V 1,900 V
225 – 275
0.95
1.20 0.45
0.85
1,600 V 1,900 V
225 – 275
0.95
1.20 0.25
0.50
1,600 V 1,900 V
225 – 275
0.95
1.20 0.25
0.45
1,600 V 1,900 V
225 – 275
0.95
1.20 0.20
0.40
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
1.45 in 2.85 in 4.6 lbs
12”
1.45 in 2.85 in 4.6 lbs
12”
1.45 in 2.85 in 4.6 lbs
12”
1.45 in 2.85 in 4.6 lbs
12” Capacitor Requirement
Microfarads Volts (Min)
8.0 uf 280 V
8.0 uf 280 V
8.0 uf 280 V
8.0 uf 280 V
BALLAST SPECIFICATIONS
70 W M98 Pulse Start Metal Halide S70M-4 60 Hz HX-HPF
3X4 CORE.WMF
Capacitor: CA8300DL Ignitor: SMH-2
18
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
1.10 2.60 1.00
0.65 1.50 0.60
0.55 1.30 0.50
0.50 1.15 0.45
Recommended Fuse (Amps) 7 4 4 3 Regulation
Line Volts Lamp Watts
±5%
±10%
±5%
±10%
±5%
±10%
±5%
±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
A 70.1
180 (H)
A 69.8
180 (H)
A 65.9
180 (H)
A 71.8
Power Factor (Min) Input Watts Efficiency
90%
125W
90%
125W
90%
125W
90%
125W
NOM. Open Circuit Voltage 270 270 270 270 Input Voltage At Lamp Dropout 80 140 160 185
Min Ambient Starting Temp -20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
1,600V 1,900V
240 – 300
1.20
1.50 0.40
0.75
1,600V 1,900V
240 – 300
1.20
1.50 0.25
0.45
1,600V 1,900V
240 – 300
1.20
1.50 0.20
0.40
1,600V 1,900V
240 – 300
1.20
1.50 0.15
0.35
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
1.70 in 3.10 in 5.2 lbs
12”
1.70 in 3.10 in 5.2 lbs
12”
1.70 in 3.10 in 5.2 lbs
12”
1.70 in 3.10 in 5.2 lbs
12” Capacitor Requirement
Microfarads Volts (Min)
12.0 uf 280V
12.0 uf 280V
12.0 uf 280V
12.0 uf 280V
BALLAST SPECIFICATIONS
100W M90 Pulse Start Metal Halide S100M-4 60 Hz HX-HPF
3X4 CORE.WMF
Capacitor: CA10280DL Ignitor: SMH-2
19
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
1.25 0.80 0.80
0.75 0.45 0.45
0.65 0.40 0.40
0.55 0.35 0.35
Regulation Line Volts Lamp Watts
±10% ±10%
±10% ±10%
±10% ±10%
±10% ±10%
UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
H A
66.5
H A
65.0
H A
62.7
H A
61.9
Input Watts 150W 150W 150W 150W NOM. Open Circuit Voltage 225 225 225 225 Power Factor 90% 90% 90% 90% Current Crest Factor 1.60 1.60 1.60 1.60 Input Voltage At Lamp Dropout 80 140 160 185
MIN. Ambient Starting Temp. -20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
1,600 V 2,000 V
200 – 250
1.45
1.80 0.50
0.85
1,600 V 2,000 V
200 – 250
1.45
1.80 0.30
0.50
1,600 V 2,000 V
200 – 250
1.45
1.80 0.25
0.45
1,600 V 2,000 V
200 – 250
1.45
1.80 0.20
0.35
Recommended Fuse (Amps) 4 3 2 2 CORE and COIL Specifications
Dimension (A) Dimension (B) Weight Lead Lengths
1.70 in 3.15 in 5.4 lbs
12”
1.70 in 3.15 in 5.4 lbs
12”
1.70 in 3.15 in 5.4 lbs
12”
1.70 in 3.15 in 5.4 lbs
12” Capacitor Requirement
Microfarads Volts (Min)
12.0 uf 280 V
12.0 uf 280 V
12.0 uf 280 V
12.0 uf 280 V
BALLAST SPECIFICATIONS
125W M150 Pulse Start Metal Halide S125M-4/PS 60 Hz CWA
3X4 CORE – HX, CWA & CWI UNITS
Capacitor: CA12280DL Ignitor: SMH-2
20
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
1.60 3.50 1.30
1.00 2.15 0.95
0.80 1.75 0.65
0.70 1.55 0.55
Recommended Fuse (Amps) 9 6 5 4 Regulation
Line Volts Lamp Watts
±5%
±10%
±5%
±10%
±5%
±10%
±5%
±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
B 78.0
180 (H)
D 87.6
180 (H)
C 80.9
180 (H)
C 80.5
Power Factor (Min) Input Watts Efficiency
90% 185 W 81%
90% 185 W 81%
90% 185 W 81%
90% 185 W 81%
NOM. Open Circuit Voltage 265 265 265 265 Input Voltage At Lamp Dropout 75 120 150 170
Min Ambient Starting Temp -20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
1,600 V 1,900 V
235 – 295
1.95
2.45 0.90
1.70
1,600 V 1,900 V
235 – 295
1.95
2.45 0.55
1.10
1,600 V 1,900 V
235 – 295
1.95
2.45 0.45
0.85
1,600 V 1,900 V
235 – 295
1.95
2.45 0.40
0.75
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
2.25 in 3.90 in 7.1 lbs
12”
2.25 in 3.90 in 7.1 lbs
12”
2.25 in 3.90 in 7.1 lbs
12”
2.25 in 3.90 in 7.1 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
16.0 uf 280 V
16.0 uf 280 V
16.0 uf 280 V
16.0 uf 280 V
BALLAST SPECIFICATIONS
150W M102 Pulse Start Metal Halide S150M-4 60 Hz HX-HPF
3X4 CORE.WMF
Capacitor: CA16330DL Ignitor: SMH-2
21
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
1.90 1.00 1.00
1.05 0.60 0.60
0.95 0.50 0.50
0.80 0.45 0.45
Recommended Fuse (Amps) 5 3 3 2 Regulation
Line Volts Lamp Watts
±10% ±10%
±10% ±10%
±10% ±10%
±10% ±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
B 77.7
180 (H)
C 80.6
180 (H)
A 74.5
180 (H)
A 73.2
Power Factor (Min) Input Watts Efficiency
90% 208 W 84%
90% 208 W 84%
90% 208 W 84%
90% 208 W 84%
NOM. Open Circuit Voltage 265 265 265 265 Input Voltage At Lamp Dropout 70 120 140 160
Min Ambient Starting Temp -20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
1,600 V 1,900 V
240 – 290
1.85
2.25 0.70
1.10
1,600 V 1,900 V
240 – 290
1.85
2.25 0.40
0.65
1,600 V 1,900 V
240 – 290
1.85
2.25 0.35
0.55
1,600 V 1,900 V
240 – 290
1.85
2.25 0.30
0.50
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
2.63 in 3.75 in 8.0 lbs
12”
2.63 in 3.75 in 8.0 lbs
12”
2.63 in 3.75 in 8.0 lbs
12”
2.63 in 3.75 in 8.0 lbs
12” Capacitor Requirement
Microfarads Volts (Min)
12.5 uf 330 V
12.5 uf 330 V
12.5 uf 330 V
12.5 uf 330 V
BALLAST SPECIFICATIONS
175W M137 / M152 Pulse Start Metal Halide S175M-4/PS 60 Hz CWA
3X4 CORE.WMF
Capacitor: CA12.5330DL Ignitor: SMH-2
22
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
2.00 3.30 2.10
1.25 2.05 1.15
1.00 1.65 1.10
0.85 1.45 0.75
Regulation Line Volts Lamp Watts
±5%
±10%
±5%
±10%
±5%
±10%
±5%
±10%
UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
H A
72.0
H A
70.0
H A
73.0
H A
67.0
Input Watts 225W 225W 225W 225W NOM. Open Circuit Voltage 285 285 285 285 Power Factor 90% 90% 90% 90% Current Crest Factor 1.50 1.50 1.50 1.50 Input Voltage At Lamp Dropout 90 140 150 190
MIN. Ambient Starting Temp. -40°F/ -40°C
-40°F / -40°C
-40°F/ -40°C
-40°F/ -40°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,500 V
255 – 315
1.90
2.35 1.60
1.90
2,000 V 2,500 V
255 – 315
1.90
2.35 1.05
1.30
2,000 V 2,500 V
255 – 315
1.90
2.35 0.80
1.00
2,000 V 2,500 V
255 – 315
1.90
2.35 0.70
0.80
Recommended Fuse (Amps) 9 6 5 4 CORE and COIL Specifications
Dimension (A) Dimension (B) Weight Lead Lengths
2.25 in 3.90 in 7.0 lbs
12”
2.25 in 3.90 in 7.0 lbs
12”
2.25 in 3.90 in 7.0 lbs
12”
2.25 in 3.90 in 7.0 lbs
12” Capacitor Requirement
Microfarads Volts (Min)
16.0 uf 290 V
16.0 uf 290 V
16.0 uf 290 V
16.0 uf 290 V
BALLAST SPECIFICATIONS
200W M136 Pulse Start Metal Halide S200M-4/PS 60 Hz HX – HPF
3X4 CORE – HX, CWA & CWI UNITS
Capacitor: CA16330DL Ignitor: SMH-2
23
Input Volts 480 Line Current ( Amps )
Operating Open Circuit Starting
0.50 0.80 0.50
Recommended Fuse (Amps) 2 Regulation
Line Volts Lamp Watts
±5%
±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
D 86.5
Power Factor (Min) Input Watts Efficiency
90% 237 W 84%
NOM. Open Circuit Voltage 285 Input Voltage At Lamp Dropout 320
Min Ambient Starting Temp -20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000V 2,500 V
255 – 315
1.85
2.25 0.45
0.50
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
2.45 in 3.90 in 8.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
16.0 uf 280 V
BALLAST SPECIFICATIONS
200W M136 Pulse Start Metal Halide S200M-48/12/PS 60 Hz HX-HPF
3X4 CORE – HX, CWA & CWI UNITS
Capacitor: CA16330DL Ignitor: SMH-2
24
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
2.50 1.80 1.40
1.45 1.10 0.80
1.25 0.90 0.70
1.10 0.80 0.60
Recommended Fuse (Amps) 7 4 4 3 Regulation
Line Volts Lamp Watts
±10% ±10%
±10% ±10%
±10% ±10%
±10% ±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H) B
75.4
180 (H) B
76.9
180 (H) A
74.1
180 (H) A
74.2
Power Factor (Min) Input Watts Efficiency
90% 288 W 87%
90% 288 W 87%
90% 288 W 87%
90% 288 W 87%
NOM. Open Circuit Voltage 270 270 270 270 Input Voltage At Lamp Dropout 60 104 120 138
Min Ambient Starting Temp -20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
1,600 V 1,900 V
240 – 290
2.25
2.75 1.10
1.70
1,600 V 1,900 V
240 – 290
2.25
2.75 0.65
0.95
1,600 V 1,900 V
240 – 290
2.25
2.75 0.55
0.85
1,600 V 1,900 V
240 – 290
2.25
2.75 0.45
0.75
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
1.55 in 3.50 in 10.0 lbs
12”
1.55 in 3.50 in 10.0 lbs
12”
1.55 in 3.50 in 10.0 lbs
12”
1.55 in 3.50 in 10.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
15.0 uf 400 V
15.0 uf 400 V
15.0 uf 400 V
15.0 uf 400 V
BALLAST SPECIFICATIONS
250W M138 / M153 Pulse Start Metal Halide S250M-4/PS 60 Hz CWA
4X4 CORE.WMF
Capacitor: CA15400 / CA15400DL Ignitor: SMH-2
25
Input Volts 480 Line Current ( Amps )
Operating Open Circuit Starting
0.60 0.45 0.45
Recommended Fuse (Amps) 2 Regulation
Line Volts Lamp Watts
±10% ±9%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
A 59.0
Power Factor (Min) Input Watts Efficiency
90% 285 W 88%
NOM. Open Circuit Voltage 275 Input Voltage At Lamp Dropout 270
Min Ambient Starting Temp -20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,400 V
245 – 300
2.35
2.90 0.35
0.50
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
2.00 in 4.10 in 11.5 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
16.0 uf 370 V
BALLAST SPECIFICATIONS
250W M138 / M153 Pulse Start Metal Halide S250M-48/12/PS 60 Hz CWA
4X4 CORE.WMF
Capacitor: CA15400 / CA15400DL Ignitor: SMH-2
26
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
3.20 1.20 2.60
1.80 0.70 1.50
1.60 0.60 1.30
1.40 0.50 1.15
Recommended Fuse (Amps) 8 5 4 4 Regulation
Line Volts Lamp Watts
±10% ±10%
±10% ±10%
±10% ±10%
±10% ±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
B 75.7
180 (H)
B 76.2
180 (H)
B 78.0
180 (H)
B 78.3
Power Factor (Min) Input Watts Efficiency
90% 368 W 87%
90% 368 W 87%
90% 368 W 87%
90% 368 W 87%
NOM. Open Circuit Voltage 265 265 265 265 Input Voltage At Lamp Dropout 80 140 160 200
Min Ambient Starting Temp -20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
1,600 V 1,900 V
235 – 295
3.10
3.80 2.15
3.25
1,600 V 1,900 V
235 – 295
3.10
3.80 1.20
1.85
1,600 V 1,900 V
235 – 295
3.10
3.80 1.05
1.65
1,600 V 1,900 V
235 – 295
3.10
3.80 0.90
1.40
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
1.85 in 3.65 in 10.0 lbs
12”
1.85 in 3.65 in 10.0 lbs
12”
1.85 in 3.65 in 10.0 lbs
12”
1.85 in 3.65 in 10.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
22.0 uf 330 V
22.0 uf 330 V
22.0 uf 330 V
22.0 uf 330 V
BALLAST SPECIFICATIONS
320W M132 / M154 Pulse Start Metal Halide S320M-4 60 Hz CWA
4X4 CORE – HX, CWA & CWI UNITS
Capacitor: CA22330DL Ignitor: SMH-2
27
Input Volts 480 Line Current ( Amps )
Operating Open Circuit Starting
0.80 0.40 0.60
Recommended Fuse (Amps) 3 Regulation
Line Volts Lamp Watts
±10% ±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
D 85.9
Power Factor (Min) Input Watts Efficiency
90% 368 W 87%
NOM. Open Circuit Voltage 265 Input Voltage At Lamp Dropout 320
Min Ambient Starting Temp -20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,400 V
235 – 295
3.00
3.60 0.45
0.75
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
1.90 in 3.75 in 10.5 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
22.0 uf 330 V
BALLAST SPECIFICATIONS
320W M132 / M154 Pulse Start Metal Halide S320M-48/12 60 Hz CWA
4X4 CORE – HX, CWA & CWI UNITS
Capacitor: CA2233DL Ignitor: SMH-2
28
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
3.60 1.30 3.30
2.10 0.75 1.90
1.80 0.65 1.65
1.55 0.55 1.40
Recommended Fuse (Amps) 9 6 5 4 Regulation
Line Volts Lamp Watts
±10% ±10%
±10% ±10%
±10% ±10%
±10% ±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
B 75.9
180 (H)
C 80.2
180 (H)
C 80.6
180 (H)
C 82.2
Power Factor (Min) Input Watts Efficiency
90% 398 W 88%
90% 398 W 88%
90% 398 W 88%
90% 398 W 88%
NOM. Open Circuit Voltage 245 245 245 245 Input Voltage At Lamp Dropout 85 155 170 190
Min Ambient Starting Temp -20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
1,600 V 1,900 V
215 – 275
3.25
3.95 2.50
3.80
1,600 V 1,900 V
215 – 275
3.25
3.95 1.45
2.15
1,600 V 1,900 V
215 – 275
3.25
3.95 1.25
1.90
1,600 V 1,900 V
215 – 275
3.25
3.95 1.10
1.70
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
1.92 in 3.80 in 10.5 lbs
12”
1.92 in 3.80 in 10.5 lbs
12”
1.92 in 3.80 in 10.5 lbs
12”
1.92 in 3.80 in 10.5 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
24.0 uf 330 V
24.0 uf 330 V
24.0 uf 330 V
24.0 uf 330 V
BALLAST SPECIFICATIONS
350W M131 Pulse Start Metal Halide S350M-4 60 Hz CWA
4X4 CORE – HX, CWA & CWI UNITS
Capacitor: CA24400DL Ignitor: SMH-2
29
Input Volts 480 Line Current ( Amps )
Operating Open Circuit Starting
0.85 0.55 0.65
Recommended Fuse (Amps) 3 Regulation
Line Volts Lamp Watts
±10% ±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
C 80.9
Power Factor (Min) Input Watts Efficiency
90% 398 W 88%
NOM. Open Circuit Voltage 250 Input Voltage At Lamp Dropout 300
Min Ambient Starting Temp -20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,400 V
225 – 275
3.15
3.85 0.50
0.75
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
2.00 in 4.10 in 10.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
24.0 uf 330 V
BALLAST SPECIFICATIONS
350W M131 Pulse Start Metal Halide S350M-48/12 60 Hz CWA
4X4 CORE – HX, CWA & CWI UNITS
Capacitor: CA24400DL Ignitor: SMH-2
30
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
4.00 2.00 3.50
2.30 1.15 2.00
2.00 1.00 1.75
1.75 0.85 1.50
Recommended Fuse (Amps) 10 6 5 5 Regulation
Line Volts Lamp Watts
±10% ±10%
±10% ±10%
±10% ±10%
±10% ±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
C 84.3
180 (H)
C 84.8
180 (H)
C 84.8
180 (H)
C 84.9
Power Factor (Min) Input Watts Efficiency
90% 453 W 88%
90% 453 W 88%
90% 453 W 88%
90% 453 W 88%
NOM. Open Circuit Voltage 280 280 280 280 Input Voltage At Lamp Dropout 60 104 120 138
Min Ambient Starting Temp -20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,500 V
250 – 310
3.50
4.30 2.80
4.20
2,000 V 2,500 V
250 – 310
3.50
4.30 1.60
2.40
2,000 V 2,500 V
250 – 310
3.50
4.30 1.40
2.10
2,000 V 2,500 V
250 – 310
3.50
4.30 1.20
1.80
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
2.00 in 3.90 in 10.7 lbs
12”
2.00 in 3.90 in 10.7 lbs
12”
2.00 in 3.90 in 10.7 lbs
12”
2.00 in 3.90 in 10.7 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
26.0 uf 330 V
26.0 uf 330 V
26.0 uf 330 V
26.0 uf 330 V
BALLAST SPECIFICATIONS
400W M135 / M155 Pulse Start Metal Halide S400M-4/PS 60 Hz CWA
4X4 CORE.WMF
Capacitor: CA26400DL Ignitor: SMH-2
31
Input Volts 480 Line Current ( Amps )
Operating Open Circuit Starting
1.00 0.50 0.90
Recommended Fuse (Amps) 3 Regulation
Line Volts Lamp Watts
±10% ±9%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
D 88.9
Power Factor (Min) Input Watts Efficiency
90% 452 W 89%
NOM. Open Circuit Voltage 280 Input Voltage At Lamp Dropout 240
Min Ambient Starting Temp -20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,500 V
250 – 310
3.55
4.35 0.60
0.90
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
2.20 in 4.10 in 12.0 lbs
12’
Capacitor Requirement Microfarads Volts (Min)
26.0 uf 330 V
BALLAST SPECIFICATIONS
400W M135 / M155 Pulse Start Metal Halide S400M-48/12/PS 60 Hz CWA
4X4 CORE – HX, CWA & CWI UNITS
Capacitor: CA26400DL Ignitor: SMH-2
32
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
4.40 1.50 4.00
2.50 0.85 2.30
2.20 0.75 2.00
1.90 0.65 1.70
Recommended Fuse (Amps) 11 7 6 5 Regulation
Line Volts Lamp Watts
±10% ±10%
±10% ±10%
±10% ±10%
±10% ±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
C 83.7
180 (H)
D 85.2
180 (H)
D 85.4
180 (H)
D 88.1
Power Factor (Min) Input Watts Efficiency
90% 507 W 89%
90% 507 W 89%
90% 507 W 89%
90% 507 W 89%
NOM. Open Circuit Voltage 260 260 260 260 Input Voltage At Lamp Dropout 70 120 140 160
Min Ambient Starting Temp -20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,500 V
235 – 285
4.20
5.15 3.20
4.80
2,000 V 2,500 V
235 – 285
4.20
5.15 1.85
2.75
2,000 V 2,500 V
235 – 285
4.20
5.15 1.60
2.40
2,000 V 2,500 V
235 – 285
4.20
5.15 1.40
2.10
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
2.30 4.20
12.4 lbs 12”
2.30 4.20
12.4 lbs 12”
2.30 4.20
12.4 lbs 12”
2.30 4.20
12.4 lbs 12”
Capacitor Requirement Microfarads Volts (Min)
32.0 uf 300 V
32.0 uf 300 V
32.0 uf 300 V
32.0 uf 300 V
BALLAST SPECIFICATIONS
450W M144 Pulse Start Metal Halide S450M-4/PS 60 Hz CWA
4X4 CORE – HX, CWA & CWI UNITS
Capacitor: CA32330DL Ignitor: SMH-2
33
Input Volts 480 Line Current ( Amps )
Operating Open Circuit Starting
1.10 0.55 0.85
Recommended Fuse (Amps) 3 Regulation
Line Volts Lamp Watts
±10% ±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
C 84.3
Power Factor (Min) Input Watts Efficiency
90% 509 W 88%
NOM. Open Circuit Voltage 255 Input Voltage At Lamp Dropout 250
Min Ambient Starting Temp -20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,400 V
230 – 280
4.15
5.05 0.65
1.95
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
2.30 in 4.40 in 14.5 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
32.0 uf 300 V
BALLAST SPECIFICATIONS
450W M144 Pulse Start Metal Halide S450M-48/12/PS 60 Hz CWA
4X4 CORE.WMF
Capacitor: CA32330DL Ignitor: SMH-2
34
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
5.70 8.75 7.80
3.05 4.70 4.20
2.95 4.45 4.05
2.50 3.80 3.20
Regulation Line Volts Lamp Watts
±5%
±10%
±5%
±10%
±5%
±10%
±5%
±10%
UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
H B
79.3
H B
73.9
H B
81.6
H B
81.3
Input Watts 635 W 635 W 635 W 635 W NOM. Open Circuit Voltage 300 300 300 300 Power Factor 90% 90% 90% 90% Current Crest Factor 1.50 1.50 1.50 1.50 Input Voltage At Lamp Dropout 90 160 180 210
MIN. Ambient Starting Temp. -40°F/ -40°C
-40°F/ -40°C
-40°F/ -40°C
-40°F/ -40°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,500 V
270 – 330
5.65
6.95 6.05
9.15
2,000 V 2,500 V
270 – 330
5.65
6.95 3.10
4.70
2,000 V 2,500 V
270 – 330
5.65
6.95 3.15
4.75
2,000 V 2,500 V
270 – 330
5.65
6.95 2.65
4.05
Recommended Fuse (Amps) 15 8 8 7 CORE and COIL Specifications
Dimension (A) Dimension (B) Weight Lead Lengths
3.25 in 4.90 in 18.0 lbs
12”
3.25 in 4.90 in 18.0 lbs
12”
3.25 in 4.90 in 18.0 lbs
12”
3.25 in 4.90 in 18.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
38.0 uf 330 V
38.0 uf 330 V
38.0 uf 330 V
38.0 uf 330 V
BALLAST SPECIFICATIONS
575W Pulse Start Metal Halide S575M-4/PS 60 Hz HX – HPF
4X4 CORE – HX, CWA & CWI UNITS
Capacitor: CA38330DL Ignitor: BVS-045
35
Input Volts 480 Line Current ( Amps )
Operating Open Circuit Starting
1.45 2.30 2.20
Regulation Line Volts Lamp Watts
±5%
±10%
UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
H D
89.0
Input Watts 645 W NOM. Open Circuit Voltage 325 Power Factor 90% Current Crest Factor 1.50 Input Voltage At Lamp Dropout 300
MIN. Ambient Starting Temp. -40°F/ -40°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,500 V
295 – 355 5.70 6.30 1.40 2.10
Recommended Fuse (Amps) 4 CORE and COIL Specifications
Dimension (A) Dimension (B) Weight Lead Lengths
3.25 in 4.90 in 18.5 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
38.0 uf 330 V
BALLAST SPECIFICATIONS
575W Pulse Start Metal Halide S575M-48/PS 60 Hz HX – HPF
4X4 CORE – HX, CWA & CWI UNITS
Capacitor: CA38330DL Ignitor: BVS-045
36
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
6.80 4.60 4.80
4.00 2.60 2.80
3.40 2.30 2.40
3.00 2.00 2.10
Recommended Fuse (Amps) 17 10 9 8 Regulation
Line Volts Lamp Watts
±10% ±10%
±10% ±10%
±10% ±10%
±10% ±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
B 75.9
180 (H)
C 81.6
180 (H)
B 75.9
180 (H)
B 78.2
Power Factor (Min) Input Watts Efficiency
90% 815 W
90% 815 W
90% 815 W
90% 815 W
NOM. Open Circuit Voltage 370 370 370 370 Input Voltage At Lamp Dropout 60 105 120 140
Min Ambient Starting Temp -20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,500 V
335 – 405
4.30
5.30 3.60
5.50
2,000 V 2,500 V
335 – 405
4.30
5.30 2.00
3.10
2,000 V 2,500 V
335 – 405
4.30
5.30 1.85
2.75
2,000 V 2,500 V
335 – 405
4.30
5.30 1.60
2.40
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
2.30 in 4.30 in 18.0 lbs
12”
2.30 in 4.30 in 18.0 lbs
12”
2.30 in 4.30 in 18.0 lbs
12”
2.30 in 4.30 in 18.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
24.0 uf 480 V
24.0 uf 480 V
24.0 uf 480 V
24.0 uf 480 V
BALLAST SPECIFICATIONS
750W M149 Pulse Start Metal Halide S750M-4/PS 60 Hz CWA
4X6 CORE.WMF
Capacitor: CA24480 Ignitor: BVS-042
37
Input Volts 480 Line Current ( Amps )
Operating Open Circuit Starting
1.70 1.35 1.10
Recommended Fuse (Amps) 4 Regulation
Line Volts Lamp Watts
±10% ±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
D 85.2
Power Factor (Min) Input Watts Efficiency
90% 820 W
NOM. Open Circuit Voltage 370 Input Voltage At Lamp Dropout 220
Min Ambient Starting Temp -20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,500 V
335 – 405
4.30
5.30 0.80
1.20
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
2.40 in 4.40 in 19.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
24.0 uf 480 V
BALLAST SPECIFICATIONS
750W M149 Pulse Start Metal Halide S750M-48/12/PS 60 Hz CWA
4X6 CORE.WMF
Capacitor: CA24480 Ignitor: BVS-042
38
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
8.00 5.50 5.50
4.50 3.20 3.20
4.00 2.75 2.75
3.45 2.40 2.40
Recommended Fuse (Amps) 20 12 10 9 Regulation
Line Volts Lamp Watts
±10% ±10%
±10% ±10%
±10% ±10%
±10% ±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
B 78.6
180 (H)
A 63.1
180 (H)
A 67.7
180 (H)
A 67.2
Power Factor (Min) Input Watts Efficiency
90% 950W 92%
90% 950W 92%
90% 950W 92%
90% 950W 92%
NOM. Open Circuit Voltage 420 420 420 420 Input Voltage At Lamp Dropout 65 110 130 150
Min Ambient Starting Temp -20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
1,650 V 2,500 V
380 – 470
4.30
5.30 4.30
6.60
1,650 V 2,500 V
380 – 470
4.30
5.30 2.50
3.80
1,650 V 2,500 V
380 – 470
4.30
5.30 2.15
3.30
1,650 V 2,500 V
380 – 470
4.30
5.30 1.85
2.85
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
2.80 in 4.80 in 21.0 lbs
12”
2.80 in 4.80 in 21.0 lbs
12”
2.80 in 4.80 in 21.0 lbs
12”
2.80 in 4.80 in 21.0 lbs
12” Capacitor Requirement
Microfarads Volts (Min)
22.0 uf 460 V
22.0 uf 460 V
22.0 uf 460 V
22.0 uf 460 V
BALLAST SPECIFICATIONS
875W M166 Pulse Start Metal Halide S875M-4 60 Hz CWA
4X6 CORE.WMF
Capacitor: CA22525 Ignitor: BVS-020
39
Input Volts 480 Line Current ( Amps )
Operating Open Circuit Starting
2.00 1.60 1.30
Recommended Fuse (Amps) 5 Regulation
Line Volts Lamp Watts
±10% ±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
C 81.5
Power Factor (Min) Input Watts Efficiency
90% 950 W 92%
NOM. Open Circuit Voltage 420 Input Voltage At Lamp Dropout 250
Min Ambient Starting Temp -20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,400 V
380 – 460
4.30
5.30 1.00
1.50
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
2.82 in 4.85 in 21.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
22.0 uf 460 V
BALLAST SPECIFICATIONS
875W M166 Pulse Start Metal Halide S875M-48 60 Hz CWA
4X6 CORE.WMF
Capacitor: CA22525 Ignitor: BVS-020
40
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
9.00 6.00 6.00
5.20 3.50 3.50
4.50 3.00 3.00
3.90 2.60 2.60
Recommended Fuse (Amps) 25 15 12 10 Regulation
Line Volts Lamp Watts
±10% ±10%
±10% ±10%
±10% ±10%
±10% ±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
D 88.2
180 (H)
A 73.5
180 (H)
B 78.4
180 (H)
B 78.2
Power Factor (Min) Input Watts Efficiency
90% 1082 W
92%
90% 1082 W
92%
90% 1082 W
92%
90% 1082 W
92%
NOM. Open Circuit Voltage 420 420 420 420 Input Voltage At Lamp Dropout 70 125 140 160
Min Ambient Starting Temp -20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
1,850 V 2,200 V
380 – 460
4.75
5.85 4.80
7.20
1,850 V 2,200 V
380 – 460
4.75
5.85 2.80
4.20
1,850 V 2,200 V
380 – 460
4.75
5.85 2.40
3.60
1,850 V 2,200 V
380 – 460
4.75
5.85 2.10
3.15
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
2.80 in 4.80 in 21.0 lbs
12”
2.80 in 4.80 in 21.0 lbs
12”
2.80 in 4.80 in 21.0 lbs
12”
2.80 in 4.80 in 21.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
24.0 uf 480 V
24.0 uf 480 V
24.0 uf 480 V
24.0 uf 480 V
BALLAST SPECIFICATIONS
1000W M141 Pulse Start Metal Halide S1000M-4/PS 60 Hz CWA
4X6 CORE.WMF
Capacitor: CA24480 Ignitor: BVS-020
41
Input Volts 480 Line Current ( Amps )
Operating Open Circuit Starting
2.25 1.60 1.50
Recommended Fuse (Amps) 6 Regulation
Line Volts Lamp Watts
±10% ±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
D 85.0
Power Factor (Min) Input Watts Efficiency
90% 1082 W
92%
NOM. Open Circuit Voltage 420 Input Voltage At Lamp Dropout 300
Min Ambient Starting Temp -20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,400 V
375 – 460
4.75
5.85 1.10
1.80
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
2.82 in 4.85 in 21.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
24.0 uf 480 V
BALLAST SPECIFICATIONS
1000W M141 Pulse Start Metal Halide S1000M-48/12/PS 60 Hz CWA
4X6 CORE.WMF
Capacitor: CA24480 Ignitor: BVS-020
42
HID BALLASTS
High Pressure Sodium
13 Columbia Dr. #12 Amherst, NH 03031 www.souheganlighting.com
Toll Free: 877-610-4010 Phone: 603-889-8962 Fax: 603-889-0291
43
Input Volts 120 Line Current ( Amps )
Operating Open Circuit Starting
0.85
0.75
Recommended Fuse (Amps) 3 Regulation
Line Volts Lamp Watts
±5%
±12%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
A
Power Factor (Min) Input Watts Efficiency
40% 45 W
NOM. Open Circuit Voltage 120 Input Voltage At Lamp Dropout
Min Ambient Starting Temp -40°F / -40°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,500 V 110 – 35
.00
.00
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
.90 in 2.15 in 2.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
BALLAST SPECIFICATIONS
35W S76 High Pressure Sodium S35S-12 60 Hz Reactor-NPF
0.75EI CORE.wmf
Capacitor: NONE Ignitor: S55V
44
Input Volts 120 Line Current ( Amps )
Operating Open Circuit Starting
1.20
1.10
Recommended Fuse (Amps) 2 Regulation
Line Volts Lamp Watts
±5%
±12%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
A
Power Factor (Min) Input Watts Efficiency
40% 65W
NOM. Open Circuit Voltage 120 Input Voltage At Lamp Dropout 95
Min Ambient Starting Temp -40°F / -40°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,500 V
110 – 135
1.35
1.65 0.55
0.95
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
1.15 in 2.35 in 2.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
BALLAST SPECIFICATIONS
50 W S68 High Pressure Sodium S50S-12 60 Hz Reactor-NPF
0.75EI CORE.wmf
Capacitor: NONE Ignitor: S55V
45
Input Volts 120 Line Current ( Amps )
Operating Open Circuit Starting
1.70
1.25
Recommended Fuse (Amps) 5 Regulation
Line Volts Lamp Watts
±5% ±9%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
B
Power Factor (Min) Input Watts Efficiency
40% 85 W
NOM. Open Circuit Voltage 120 Input Voltage At Lamp Dropout
Min Ambient Starting Temp -40°F / -40°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,500 V
110 – 135
.00
.00
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
1.29 in 2.55 in 3.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
BALLAST SPECIFICATIONS
70W S62 High Pressure Sodium S70S-12 60 Hz Reactor-NPF
78EI CORE.wmf
Capacitor: NONE Ignitor: S55V
46
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
0.80 1.50 0.60
0.45 0.85 0.35
0.40 0.75 0.30
0.35 0.65 0.25
Regulation Line Volts Lamp Watts
±5%
±10%
±5%
±10%
±5%
±10%
±5%
±10%
UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
H A
51.2
H A
49.0
H A
51.0
H A
48.3 Input Watts 90 W 90 W 90 W 90 W NOM. Open Circuit Voltage 120 120 120 120 Power Factor 90% 90% 90% 90% Current Crest Factor 1.50 1.50 1.50 1.50 Input Voltage At Lamp Dropout 90 160 180 205
MIN. Ambient Starting Temp. -40°F / -40°C
-40°F / -40°C
-40°F / -40°C
-40°F / -40°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,500 V
105 – 135
1.80
2.20 0.40
0.70
2,000 V 2,500 V
105 – 135
1.80
2.20 0.25
0.40
2,000 V 2,500 V
105 – 135
1.80
2.20 0.20
0.35
2,000 V 2,500 V
105 – 135
1.80
2.20 0.15
0.30
Recommended Fuse (Amps) 4 3 2 2 CORE and COIL Specifications
Dimension (A) Dimension (B) Weight Lead Lengths
1.50 in 2.95 in 4.6 lbs
12”
1.50 in 2.95 in 4.6 lbs
12”
1.50 in 2.95 in 4.6 lbs
12”
1.50 in 2.95 in 4.6 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
7.0 uf 280 V
7.0 uf 280 V
7.0 uf 280 V
7.0 uf 280 V
BALLAST SPECIFICATIONS
70W S62 High Pressure Sodium S70S-4 60 Hz Reactor-NPF
3X4 CORE – HX, CWA & CWI UNITS
Capacitor: CA300DL Ignitor: S55V
47
Input Volts 120 Line Current ( Amps )
Operating Open Circuit Starting
2.15
1.80
Recommended Fuse (Amps) 6 Regulation
Line Volts Lamp Watts
±5% ±8%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
E
Power Factor (Min) Input Watts Efficiency
40% 118 W
NOM. Open Circuit Voltage 120 Input Voltage At Lamp Dropout
Min Ambient Starting Temp -40°F/ -40°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,500 V
110 – 135
.00
.00
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
1.48 in 2.75 in 3.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
BALLAST SPECIFICATIONS
100W S54 High Pressure Sodium S100S-12 60 Hz Reactor-NPF
78EI CORE.wmf
Capacitor: NONE Ignitor: S55V
48
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
1.10 2.10 0.90
0.60 1.20 0.55
0.55 1.05 0.45
0.45 0.90 0.40
Regulation Line Volts Lamp Watts
±5%
±10%
±5%
±10%
±5%
±10%
±5%
±10%
UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
H A
H A
H A
H A
Input Watts 126 W 126 W 126 W 126 W NOM. Open Circuit Voltage 130 130 130 130 Power Factor 90% 90% 90% 90% Current Crest Factor 1.50 1.50 1.50 1.50 Input Voltage At Lamp Dropout 90 160 180 210
MIN. Ambient Starting Temp. -20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
-20°F/ -30°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,500 V
115 – 145
2.50
2.80 0.70
1.00
2,000 V 2,500 V
115 – 145
2.50
2.80 0.40
0.60
2,000 V 2,500 V
115 – 145
2.50
2.80 0.35
0.50
2,000 V 2,500 V
115 – 145
2.50
2.80 0.30
0.45
Recommended Fuse (Amps) 6 3 3 3 CORE and COIL Specifications
Dimension (A) Dimension (B) Weight Lead Lengths
2.00 in 3.45 in 5.9 lbs
12”
2.00 in 3.45 in 5.9 lbs
12”
2.00 in 3.45 in 5.9 lbs
12”
2.00 in 3.45 in 5.9 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
10.0 uf 280 V
10.0 uf 280 V
10.0 uf 280 V
10.0 uf 280 V
BALLAST SPECIFICATIONS
100W S54 High Pressure Sodium S100S-4 60 Hz HX-HPF
3X4 CORE – HX, CWA & CWI UNITS
Capacitor: CA10280DL Ignitor: S55V
49
Input Volts 120 Line Current ( Amps )
Operating Open Circuit Starting
1.50 2.45 2.00
Recommended Fuse (Amps) 4 Regulation
Line Volts Lamp Watts
±5%
±10%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H) E
Power Factor (Min) Input Watts Efficiency
90% 166W
NOM. Open Circuit Voltage 120 Input Voltage At Lamp Dropout 95
Min Ambient Starting Temp -40°F/ -40°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,500 V
110 – 135
3.80
4.70 1.50
2.50
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
2.00 in 3.05 in 4.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
52.0 uf 120 V
BALLAST SPECIFICATIONS
150W S55 High Pressure Sodium S150S-12 60 Hz Reactor–HPF
78EI CORE.wmf
Capacitor: NONE Ignitor: S55V
50
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
1.60 2.80 1.60
0.85 1.60 0.85
0.80 1.40 0.80
0.70 1.25 0.70
Regulation Line Volts Lamp Watts
±5%
±10%
±5%
±10%
±5%
±10%
±5%
±10%
UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
H D
86.3
H B
79.6
H C
83.9
H C
83.5
Input Watts 188 W 188 W 188 W 188 W NOM. Open Circuit Voltage 120 120 120 120 Power Factor 90% 90% 90% 90% Current Crest Factor 1.50 1.50 1.50 1.50 Input Voltage At Lamp Dropout 95 180 190 225
MIN. Ambient Starting Temp. -40°F/ -40°C
-40°F/ -40°C
-40°F/ -40°C
-40°F/ -40°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,500 V
105 – 135
3.80
4.70 1.20
1.85
2,000 V 2,500 V
105 – 135
3.80
4.70 0.65
1.00
2,000 V 2,500 V
105 – 135
3.80
4.70 0.60
0.95
2,000 V 2,500 V
105 – 135
3.80
4.70 0.50
0.80
Recommended Fuse (Amps) 7 4 4 4 CORE and COIL Specifications
Dimension (A) Dimension (B) Weight Lead Lengths
2.50 in 3.80 in 7.4 lbs
12”
2.50 in 3.80 in 7.4 lbs
12”
2.50 in 3.80 in 7.4 lbs
12”
2.50 in 3.80 in 7.4 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
14.0 uf 280 V
14.0 uf 280 V
14.0 uf 280 V
14.0 uf 280 V
BALLAST SPECIFICATIONS
150W S55 High Pressure Sodium S150S-4 60 Hz HX-HPF
3X4 CORE – HX, CWA & CWI UNITS
Capacitor: CA14300DL Ignitor: S55V
51
Input Volts 480 Line Current ( Amps )
Operating Open Circuit Starting
0.40 0.20 0.25
Recommended Fuse (Amps) 1 Regulation
Line Volts Lamp Watts
±10% ±6%
Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
180 (H)
D 85.0
Power Factor (Min) Input Watts Efficiency
90% 186 W
NOM. Open Circuit Voltage 120 Input Voltage At Lamp Dropout 250
Min Ambient Starting Temp -40°F/ -40°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,500 V
105 – 130
3.90
4.80 0.20
0.30
CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths
3.15 in 4.55 in 11.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
51.0 uf 180 V
BALLAST SPECIFICATIONS
150W S55 High Pressure Sodium S150S-48 60 Hz CWI
3X4 CORE.WMF
Capacitor: CA14300DL Ignitor: S55V
52
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
2.50 1.90 1.80
1.45 1.10 1.00
1.25 0.95 0.90
1.10 0.85 0.75
Regulation Line Volts Lamp Watts
±10% ±13%
±10% ±13%
±10% ±13%
±10% ±13%
UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
H B
77.4
H B
79.3
H B
79.1
H B
77.9 Input Watts 295 W 295 W 295 W 295 W NOM. Open Circuit Voltage 195 195 195 195 Power Factor 90% 90% 90% 90% Current Crest Factor 1.65 1.65 1.65 1.65 Input Voltage At Lamp Dropout 85 145 170 195
MIN. Ambient Starting Temp. -40°F / -40°C
-40°F / -40°C
-40°F / -40°C
-40°F / -40°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
1,600 V 2,000 V
175 – 215
3.80
4.70 1.25
1.90
1,600 V 2,000 V
175 – 215
3.80
4.70 0.70
1.10
1,600 V 2,000 V
175 – 215
3.80
4.70 0.60
0.95
1,600 V 2,000 V
175 – 215
3.80
4.70 0.50
0.85
Recommended Fuse (Amps) 7 4 4 3 CORE and COIL Specifications
Dimension (A) Dimension (B) Weight Lead Lengths
1.80 in 3.60 in 11.0 lbs
12”
1.80 in 3.60 in 11.0 lbs
12”
1.80 in 3.60 in 11.0 lbs
12”
1.80 in 3.60 in 11.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
35.0 uf 240 V
35.0 uf 240 V
35.0 uf 240 V
35.0 uf 240 V
BALLAST SPECIFICATIONS
250W S50 High Pressure Sodium S250S-4 60 Hz CWA
4X4 CORE – HX, CWA & CWI UNITS
Capacitor: CA35280DL Ignitor: S100V
53
Input Volts 480 Line Current ( Amps )
Operating Open Circuit Starting
0.65 0.40 0.47
Regulation Line Volts Lamp Watts
±10% ±12%
UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
H B
Input Watts 305 W NOM. Open Circuit Voltage 200 Power Factor 90% Current Crest Factor 1.65 Input Voltage At Lamp Dropout 320
MIN. Ambient Starting Temp. -40°F / -40°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,400 V
180 – 220
3.80
4.70 0.30
0.60
Recommended Fuse (Amps) 2 CORE and COIL Specifications
Dimension (A) Dimension (B) Weight Lead Lengths
1.80 in 3.60 in 11.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
35.0 uf 240 V
BALLAST SPECIFICATIONS
250W S50 High Pressure Sodium S250S-48/12 60 Hz CWA
4X4 CORE – HX, CWA & CWI UNITS
Capacitor: CA35280DL Ignitor: S100V
54
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
3.80 1.50 3.70
2.20 0.85 2.15
1.90 0.75 1.85
1.70 0.65 1.60
Regulation Line Volts Lamp Watts
±10% ±13%
±10% ±13%
±10% ±13%
±10% ±13%
UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
H C
83.8
H C
84.2
H C
85.9
H C
82.3 Input Watts 460 W 460 W 460 W 460 W NOM. Open Circuit Voltage 195 195 195 195 Power Factor 90% 90% 90% 90% Current Crest Factor 1.60 1.60 1.60 1.60 Input Voltage At Lamp Dropout 90 155 180 205
MIN. Ambient Starting Temp. -40°F / -40°C
-40°F / -40°C
-40°F / -40°C
-40°F / -40°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
1,600 V 2,000 V
175 - 215
6.25
7.65 3.00
4.50
1,600 V 2,000 V
175 - 215
6.25
7.65 1.70
2.60
1,600 V 2,000 V
175 - 215
6.25
7.65 1.50
2.25
1,600 V 2,000 V
175 - 215
6.25
7.65 1.30
1.95
Recommended Fuse (Amps) 10 7 6 5 CORE and COIL Specifications
Dimension (A) Dimension (B) Weight Lead Lengths
2.30 in 4.20 in 14.0 lbs
12”
2.30 in 4.20 in 14.0 lbs
12”
2.30 in 4.20 in 14.0 lbs
12”
2.30 in 4.20 in 14.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
55.0 uf 240 V
55.0 uf 240 V
55.0 uf 240 V
55.0 uf 240 V
BALLAST SPECIFICATIONS
400W S51 High Pressure Sodium S400S-4 60 Hz CWA
4X4 CORE – HX, CWA & CWI Units
Capacitor: CA55240DL Ignitor: S100V
55
Input Volts 480 Line Current ( Amps )
Operating Open Circuit Starting
1.00 0.40 0.80
Regulation Line Volts Lamp Watts
±10% ±13%
UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
H C
81.9
Input Watts 464 W NOM. Open Circuit Voltage 195 Power Factor 90% Current Crest Factor 1.63 Input Voltage At Lamp Dropout 370
MIN. Ambient Starting Temp. -40°F / -40°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,400 V
175 – 215
6.35
7.75 0.55
0.90
Recommended Fuse (Amps) 3 CORE and COIL Specifications
Dimension (A) Dimension (B) Weight Lead Lengths
2.60 in 4.45 in 15.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
55.0 uf 240 V
BALLAST SPECIFICATIONS
400W S51 High Pressure Sodium S400S-48/12 60 Hz CWA
4X4 CORE – HX, CWA & CWI Units
Capacitor: CA55240DL Ignitor: S100V
56
Input Volts 120 208 240 277 Line Current ( Amps )
Operating Open Circuit Starting
9.50 4.80 7.20
5.50 2.75 4.15
4.75 2.40 3.60
4.20 2.05 3.10
Regulation Line Volts Lamp Watts
±10% ±13%
±10% ±13%
±10% ±13%
±10% ±13%
UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
H C
83.8
H B
77.8
H C
81.8
H C
80.5 Input Watts 1100 W 1100 W 1100 W 1100 W NOM. Open Circuit Voltage 425 425 425 425 Power Factor 90% 90% 90% 90% Current Crest Factor 1.65 1.65 1.65 1.65 Input Voltage At Lamp Dropout 95 170 190 220
MIN. Ambient Starting Temp. -40°F / -40°C
-40°F / -40°C
-40°F / -40°C
-40°F / -40°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,400 V
380 – 470
6.20
7.60 5.20
8.20
2,000 V 2,400 V
380 – 470
6.20
7.60 3.15
4.80
2,000 V 2,400 V
380 – 470
6.20
7.60 2.60
4.10
2,000 V 2,400 V
380 – 470
6.20
7.60 2.35
3.55
Recommended Fuse (Amps) 25 15 12 10 CORE and COIL Specifications
Dimension (A) Dimension (B) Weight Lead Lengths
3.75 in 5.90 in 27.0 lbs
12”
3.75 in 5.90 in 27.0 lbs
12”
3.75 in 5.90 in 27.0 lbs
12”
3.75 in 5.90 in 27.0 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
26.0 uf 525 V
26.0 uf 525 V
26.0 uf 525 V
26.0 uf 525 V
BALLAST SPECIFICATIONS
1000W S52 High Pressure Sodium S1000S-4 60 Hz CWA
4X4 CORE – HX, CWA & CWI UNITS
Capacitor: CA26525 Ignitor: S250V
57
Input Volts 480 Line Current ( Amps )
Operating Open Circuit Starting
2.30 0.80 2.30
Regulation Line Volts Lamp Watts
±10% ±14%
UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise
H C
82.9
Input Watts 1100 W NOM. Open Circuit Voltage 430 Power Factor 90% Current Crest Factor 1.65 Input Voltage At Lamp Dropout 385
MIN. Ambient Starting Temp. -40°F / -40°C
60 Hz TEST PROCEDURES High Potential Test (Volts)
1 Minute 1 Second
Open Circuit Voltage Test (V) Short Circuit Current Test (A)
Min Secondary Current
Max Min
Input Current Max
2,000 V 2,400 V
385 – 475
6.35
7.80 1.80
2.80
Recommended Fuse (Amps) 6 CORE and COIL Specifications
Dimension (A) Dimension (B) Weight Lead Lengths
3.90 in 5.90 in 28.8 lbs
12”
Capacitor Requirement Microfarads Volts (Min)
26.0 uf 525 V
BALLAST SPECIFICATIONS
1000W S52 High Pressure Sodium S1000S-48/12 60 Hz CWA
4X6 CORE – HX, CWA & CWI UNITS
Capacitor: CA26525 Ignitor: S250V
58