Probe Start Metal Halide Pulse Start Metal Halide High ... BALLASTS Probe Start Metal Halide Pulse...

58
HID BALLASTS Probe Start Metal Halide Pulse Start Metal Halide High Pressure Sodium 13 Columbia Dr. #12 Amherst, NH 03031 www.souheganlighting.com Toll Free: 877-610-4010 Phone: 603-889-8962 Fax: 603-889-0291

Transcript of Probe Start Metal Halide Pulse Start Metal Halide High ... BALLASTS Probe Start Metal Halide Pulse...

HID BALLASTS

Probe Start Metal Halide Pulse Start Metal Halide High Pressure Sodium

13 Columbia Dr. #12 Amherst, NH 03031 www.souheganlighting.com

Toll Free: 877-610-4010 Phone: 603-889-8962 Fax: 603-889-0291

Ballast Specification Page

Probe Start 3

175W Quad MH 4

175W 480V MH 5

250W Quad MH 6

250W Quad 3X4 MH 7

250W 480V MH 8

400W Quad MH 9

400W 480V MH 10

1000W Quad MH 11

1000W Quad 4X4 MH 12

1000W 480V MH 13

1500W Quad MH 14

1500W 480V MH 15

Pulse Start 16

50W Quad PS 17

70W Quad PS 18

100W Quad PS 19

125W Quad PS 20

150W Quad PS 21

175W Quad PS 22

200W Quad PS 23

200W 480V PS 24

250W Quad PS 25

250W 480V PS 26

320W Quad PS 27

320W 480V PS 28

350W Quad PS 29

350W 480V PS 30

Ballast Specification Page

400W Quad PS 31

400W 480V PS 32

450W Quad PS 33

450W 480V PS 34

575W Quad PS 35

575W 480V PS 36

750W Quad PS 37

750W 480V PS 38

875W Quad PS 39

875W 480V PS 40

1000W Quad PS 41

1000W 480V PS 42

High Pressure Sodium 43

35W 120V HPS 44

50W 120V HPS 45

70W 120V HPS 46

70W Quad HPS 47

100W 120V HPS 48

100W Quad HPS 49

150W 120V HPS 50

150W Quad HPS 51

150W 480V HPS 52

250W Quad HPS 53

250W 480V HPS 54

400W Quad HPS 55

400W 480V HPS 56

1000W Quad HPS 57

1000W 480V HPS 58

2

HID BALLASTS

Probe Start Metal Halide

13 Columbia Dr. #12 Amherst, NH 03031 www.souheganlighting.com

Toll Free: 877-610-4010 Phone: 603-889-8962 Fax: 603-889-0291

3

Input Volts 120 208 240 277

Line Current ( Amps ) Operating Open Circuit Starting

1.80 1.20 1.60

1.10 0.65 0.90

0.90 0.60 0.80

0.80 0.50 0.70

Recommended Fuse (Amps) 5 3 3 2 Regulation

Line Volts Lamp Watts

± 10% ± 7%

± 10% ± 7%

± 10% ± 7%

± 10% ± 7%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H) C

80.0

180 (H) D

89.7

180 (H) D

85.8

180 (H) C

84.7

Power Factor (Min) Input Watts Efficiency

90% 210 W

90% 210 W

90% 210 W

90% 210 W

NOM. Open Circuit Voltage 320 320 320 320 Input Voltage At Lamp Dropout 65 115 130 150

Min Ambient Starting Temp -20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

1,650 V 2,000 V

290 – 355

1.55

1.95 1.20

1.80

1,650 V 2,000 V

290 – 355

1.55

1.95 0.65

1.05

1,650 V 2,000 V

290 – 355

1.55

1.95 0.60

0.90

1,650 V 2,000 V

290 – 355

1.55

1.95 0.50

0.80

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

2.22 in 3.60 in 6.8 lbs 12 ‘’

2.22 in 3.60 in 6.8 lbs 12 ‘’

2.22 in 3.60 in 6.8 lbs 12 ‘’

2.22 in 3.60 in 6.8 lbs 12 ‘’

Capacitor Requirement Microfarads Volts (Min)

10.0 uf 400 V

10.0 uf 400 V

10.0 uf 400 V

10.0 uf 400 V

BALLAST SPECIFICATIONS

175W M57 Metal Halide S175M-4 60 Hz CWA

3X4 Core.WMF

Capacitor: CA10400 / CA10400DL Ignitor: None

Microfarads: 10.0 uf 10.0 uf Volts (Max): 400 V 400 V Case Temp (Max): 100° C 100° C Height (Max): 2.75 in 3.68 in Dia (Max): 1.62 in 1.61 in Oval Width (Max): 2.75 in

4

Input Volts 480 Line Current ( Amps )

Operating Open Circuit Starting

0.45 0.35 0.30

Recommended Fuse (Amps) 2 Regulation

Line Volts Lamp Watts

±10% ± 7%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

B 79.2

Power Factor (Min) Input Watts Efficiency

90%

211 W

NOM. Open Circuit Voltage 320 Input Voltage At Lamp Dropout 240

Min Ambient Starting Temp -20°F/ -30° C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,400 V

285 – 355

1.55

1.95 0.25

0.45

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

2.22 in 3.60 in 6.8 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

10.0 uf 400 V

BALLAST SPECIFICATIONS

175W M57 Metal Halide S175M - 48/12 60 Hz CWA

3X4 CORE.WMF

Capacitor: CA10400 /CA10400DL Ignitor: None

Microfarads: 10.0 uf 10.0 uf Volts (Max): 400 V 400 V Case Temp (Max): 100° C 100° C Height (Max): 2.75 in 3.68 in Dia (Max): 1.62 in 1.61 in Oval Width (Max): 2.75 in

5

Input Volts 120 208 240 277

Line Current ( Amps ) Operating Open Circuit Starting

2.50 2.40 1.80

1.45 1.30 0.90

1.25 1.20 0.90

1.10 1.00 0.80

Recommended Fuse (Amps) 8 5 5 3 Regulation

Line Volts Lamp Watts

±10% ±8%

±10% ±8%

±10% ±8%

±10% ±8%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

B 77.8

180 (H)

B 76.8

180 (H)

B 77.1

180 (H)

B 78.7

Power Factor (Min) Input Watts Efficiency

90% 289W

90% 289W

90% 289W

90% 289W

NOM. Open Circuit Voltage 305 305 305 305 Input Voltage At Lamp Dropout 55 90 110 120

Min Ambient Starting Temp -20°C/ -30°F

-20°C/ -30°F

-20°C/ -30°F

-20°C/ -30°F

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

1,650 V 2,000 V 275-335

2.20

2.70 1.40

2.20

1,650 V 2,000 V 275-335

2.20

2.70 0.80

1.30

1,650 V 2,000 V 275-335

2.20

2.70 0.70

1.10

1,650 V 2,000 V 275-335

2.20

2.70 0.60

1.00

CORE and COIL Specifications

Dimension (A) Dimension (B) Weight Lead Lengths

1.65 in 3.25 in 9.3 lbs

12”

1.65 in 3.25 in 9.3 lbs

12”

1.65 in 3.25 in 9.3 lbs

12”

1.65 in 3.25 in 9.3 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

15.0 uf 400 V

15.0 uf 400 V

15.0 uf 400 V

15.0 uf 400 V

BALLAST SPECIFICATIONS

250W M58 Metal Halide S250M-4 60 Hz CWA

4x4 CORE.WMF

Capacitor: CA15400 / CA15400DL Ignitor: None

6

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

2.60 1.90 2.00

1.45 1.00 1.20

1.30 0.95 1.00

1.10 0.80 0.85

Recommended Fuse (Amps) 8 5 5 3 Regulation

Line Volts Lamp Watts

±10% ±7%

±10% ±7%

±10% ±7%

±10% ±7%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

B 76.0

180 (H)

A 74.4

180 (H)

C 82.9

180 (H)

B 79.5

Power Factor (Min) Input Watts Efficiency

90% 291 W

90% 291 W

90% 291 W

90% 291 W

NOM. Open Circuit Voltage 305 305 305 305 Input Voltage At Lamp Dropout 65 115 130 150

Min Ambient Starting Temp -20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

1,600 V 2,000 V

275 – 335

2.20

2.70 1.60

2.50

1,600 V 2,000 V

275 – 335

2.20

2.70 0.90

1.40

1,600 V 2,000 V

275 – 335

2.20

2.70 0.80

1.25

1,600 V 2,000 V

275 – 335

2.20

2.70 0.70

1.10

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

2.80 in 4.20 in 85. lbs

12”

2.80 in 4.20 in 85. lbs

12”

2.80 in 4.20 in 85. lbs

12”

2.80 in 4.20 in 85. lbs

12”

Capacitor Requirement Microfarads Volts (Min)

15.0 uf 360 V

15.0 uf 360 V

15.0 uf 360 V

15.0 uf 360 V

BALLAST SPECIFICATIONS

250W M58 Metal Halide S250M-4/3X4 60 Hz CWA

3X4 CORE.WMF

Capacitor: CA15400 / CA15400DL Ignitor: None

7

Input Volts 480

Line Current ( Amps ) Operating Open Circuit Starting

.63

0.55 0.50

Recommended Fuse (Amps) 2 Regulation

Line Volts Lamp Watts

±10% ±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

B

Power Factor (Min) Input Watts Efficiency

90% 295W

NOM. Open Circuit Voltage 305 Input Voltage At Lamp Dropout 210

Min Ambient Starting Temp -20°C/ -30°F

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,400 V

275 – 335

2.20

2.70 0.35

0.55

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

1.55 in 3.35 in 8.8 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

15.0 uf 400 V

BALLAST SPECIFICATIONS

250W M58 Metal Halide S250M-48/12 60 Hz CWA

4X4 CORE.WMF

Capacitor: CA15400 / CA15400DL Ignitor: None

8

Input Volts 120 208 240 277

Line Current ( Amps ) Operating Open Circuit Starting

4.00 3.50 2.80

2.30 2.00 1.60

2.00 1.75 1.40

1.75 1.50 1.20

Recommended Fuse (Amps) 10 6 5 5 Regulation

Line Volts Lamp Watts

±10% ±9%

±10% ±9%

±10% ±9%

±10% ±9%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

D 88.6

180 (H)

D 89.9

180 (H)

E 90.8

180 (H)

E 92.5

Power Factor (Min) Input Watts Efficiency

90% 458W 87%

90% 458W 87%

90% 458W 87%

90% 458W 87%

NOM. Open Circuit Voltage 300 300 300 300 Input Voltage At Lamp Dropout 52 90 105 120

Min Ambient Starting Temp -20°C/ -30°F

-20°C/ -30°F

-20°C/ -30°F

-20°C/ -30°F

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

1,600 V 1,900 V 270-330

3.45

4.25 2.20

3.40

1,600 V 1,900 V 270-330

3.45

4.25 1.25

2.00

1,600 V 1,900 V 270-330

3.45

4.25 1.10

1.70

1,600 V 1,900 V 270-330

3.45

4.25 0.95

1.45

CORE and COIL Specifications

Dimension (A) Dimension (B) Weight Lead Lengths

2.00 in 3.90 in 10.7 lbs

12”

2.00 in 3.90 in 10.7 lbs

12”

2.00 in 3.90 in 10.7 lbs

12”

2.00 in 3.90 in 10.7 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

24.0 uf 360 V

24.0 uf 360 V

24.0 uf 360 V

24.0 uf 360 V

BALLAST SPECIFICATIONS

400W M59 Metal Halide S400M-4 60 Hz CWA

4X4 CORE.WMF

Capacitor: CA24400 / CA24400DL Ignitor: None

9

Input Volts 480

Line Current ( Amps ) Operating Open Circuit Starting

1.00 0.90 0.70

Recommended Fuse (Amps) 3 Regulation

Line Volts Lamp Watts

±10% ±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

E 90.1

Power Factor (Min) Input Watts Efficiency

90% 457W

NOM. Open Circuit Voltage 300 Input Voltage At Lamp Dropout 220

Min Ambient Starting Temp -40°F/ -40°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,400 V 270-330

3.40

4.20 0.45

0.70

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

2.15 in 4.10 in 11.5 lbs

Capacitor Requirement Microfarads Volts (Min)

24.0 uf 360 V

BALLAST SPECIFICATIONS

400W M59 Metal Halide S400M-48/12 60 Hz CWA

4X4 CORE.WMF

Capacitor: CA24400 / CA24400DL Ignitor: None

10

Input Volts 120 208 240 277

Line Current ( Amps ) Operating Open Circuit Starting

9.00 5.35 6.30

5.55 3.95 3.50

4.60 2.95 3.25

4.00 2.50 2.85

Recommended Fuse (Amps) 22 15 12 10 Regulation

Line Volts Lamp Watts

±10% ±10%

±10% ±10%

±10% ±10%

±10% ±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

D 89.4

180 (H)

D 89.9

180 (H)

C 82.4

180 (H)

C 84.9

Power Factor (Min) Input Watts Efficiency

90% 1085W

90% 1085W

90% 1085W

90% 1085W

NOM. Open Circuit Voltage 420 420 420 420 Input Voltage At Lamp Dropout 75 120 140 160

Min Ambient Starting Temp -20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,500 V 375-460

4.80

5.90 5.05

7.60

2,000 V 2,500 V 375-460

4.80

5.90 2.80

4.20

2,000 V 2,500 V 375-460

4.80

5.90 2.60

3.90

2,000 V 2,500 V 375-460

4.80

5.90 2.25

3.40

CORE and COIL Specifications

Dimension (A) Dimension (B) Weight Lead Lengths

2.80 in 4.95 in 18.5 lbs

12”

2.80 in 4.95 in 18.5 lbs

12”

2.80 in 4.95 in 18.5 lbs

12”

2.80 in 4.95 in 18.5 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

24.0 uf 480 V

24.0 uf 480 V

24.0 uf 480 V

24.0 uf 480 V

BALLAST SPECIFICATIONS

1000W M47 / H36 Metal Halide S1000M-4 60 Hz CWA

4X8 CORE.WMF

Capacitor: CA24480 Ignitor: None

11

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

8.80 6.70 5.50

5.00 3.60 3.20

4.60 3.70 2.80

3.90 3.10 2.40

Recommended Fuse (Amps) 22 13 12 10 Regulation

Line Volts Lamp Watts

±10% ±10%

±10% ±10%

±10% ±10%

±10% ±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

D 89.4

180 (H)

A 74.0

180 (H)

B 79.9

180 (H)

C 82.0

Power Factor (Min) Input Watts Efficiency

90% 1085 W

90% 1085 W

90% 1085 W

90% 1085 W

NOM. Open Circuit Voltage 420 420 420 420 Input Voltage At Lamp Dropout 60 110 130 140

Min Ambient Starting Temp -20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

1,650 V 2,000 V

375 – 465

4.65

5.70 4.15

6.25

1,650 V 2,000 V

375 – 465

4.65

5.70 2.50

3.85

1,650 V 2,000 V

375 – 465

4.65

5.70 2.10

3.25

1,650 V 2,000 V

375 – 465

4.65

5.70 1.85

2.85

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

3.25 in 5.45 in 18.5 lbs

12”

3.25 in 5.45 in 18.5 lbs

12”

3.25 in 5.45 in 18.5 lbs

12”

3.25 in 5.45 in 18.5 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

24.0 uf 450 V

24.0 uf 450 V

24.0 uf 450 V

24.0 uf 450 V

BALLAST SPECIFICATIONS

1000W M47 / H36 Metal Halide S1000M-4/4X4 60 Hz CWA

4X4 CORE.WMF

Capacitor: CA24480 Ignitor: None

12

Input Volts 480

Line Current ( Amps ) Operating Open Circuit Starting

2.30 1.55 1.55

Recommended Fuse (Amps) 6 Regulation

Line Volts Lamp Watts

±10% ±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H) D

88.7

Power Factor (Min) Input Watts Efficiency

90% 1085W

NOM. Open Circuit Voltage 420 Input Voltage At Lamp Dropout 260

Min Ambient Starting Temp -20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,400 V

375 – 460

4.30

6.40 1.25

1.85

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

2.80 in 4.90 in 18.5 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

24.0 uf 480 V

BALLAST SPECIFICATIONS

1000W M47 Metal Halide S1000M-48/12 60 Hz CWA

4X6 CORE.WMF

Capacitor: CA24480 Ignitor: None

13

Input Volts 120 208 240 277

Line Current ( Amps ) Operating Open Circuit Starting

13.40 6.30

11.30

7.75 3.65 6.50

6.70 3.15 5.65

5.80 2.75 4.90

Recommended Fuse (Amps) 34 19 17 15 Regulation

Line Volts Lamp Watts

±10% ±12%

±10% ±12%

±10% ±12%

±10% ±12%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

G 101.6

180 (H)

E 90.4

180 (H)

E 92.4

180 (H) E

93.4 Power Factor (Min) Input Watts Efficiency

90% 1605W

90% 1605W

90% 1605W

90% 1605W

NOM. Open Circuit Voltage 440 440 440 440 Input Voltage At Lamp Dropout 80 140 160 185

Min Ambient Starting Temp -20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,500 V

385 – 475

7.30

9.00 9.90

12.10

2,000 V 2,500 V

385 – 475

7.30

9.00 5.70

7.05

2,000 V 2,500 V

385 – 475

7.30

9.00 4.95

6.05

2,000 V 2,500 V

385 – 475

7.30

9.00 4.30

5.30

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

4.10 in 6.10 in 31.0 lbs

12”

4.10 in 6.10 in 31.0 lbs

12”

4.10 in 6.10 in 31.0 lbs

12”

4.10 in 6.10 in 31.0 lbs

12” Capacitor Requirement

Microfarads Volts (Min)

32.0 uf 525 V

32.0 uf 525 V

32.0 uf 525 V

32.0 uf 525 V

BALLAST SPECIFICATIONS

1500W M48 Metal Halide S1500M-4 60 Hz CWA

4X8 CORE.WMF

Capacitor: CA32525 Ignitor: None

14

Input Volts 480 Line Current ( Amps )

Operating Open Circuit Starting

3.40 1.65 3.00

Recommended Fuse (Amps) 10 Regulation

Line Volts Lamp Watts

±10% ±12%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

E 92.5

Power Factor (Min) Input Watts Efficiency

90% 1625 W

NOM. Open Circuit Voltage 450 Input Voltage At Lamp Dropout 265

Min Ambient Starting Temp -20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000V 2,400V

405 – 495

7.20

8.80 2.40

3.60

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

4.20 in 6.20 in 31.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

32.0 uf 525 V

BALLAST SPECIFICATIONS

1500W M48 Metal Halide S1500M-48/12 60 Hz CWA

4X6 CORE.WMF

Capacitor: CA325525 Ignitor: None

15

HID BALLASTS

Pulse Start Metal Halide

13 Columbia Dr. #12 Amherst, NH 03031 www.souheganlighting.com Toll Free: 877-610-4010 Phone: 603-889-8962 Fax: 603-889-0291

16

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

0.60 1.20 0.60

0.35 0.65 0.35

0.30 0.60 0.30

0.25 0.50 0.25

Recommended Fuse (Amps) 3 2 2 2 Regulation

Line Volts Lamp Watts

±5%

±10%

±5%

±10%

±5%

±10%

±5%

±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

A 66.6

180 (H)

A 64.7

180 (H)

A 64.3

180 (H)

A 70.7

Power Factor (Min) Input Watts Efficiency

90% 68 W

90% 68 W

90% 68 W

90% 68 W

NOM. Open Circuit Voltage 265 265 265 265 Input Voltage At Lamp Dropout 85 150 170 195

Min Ambient Starting Temp -20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,500 V

235 – 295

0.65

0.85 0.40

0.75

2,000 V 2,500 V

235 – 295

0.65

0.85 0.20

0.40

2,000 V 2,500 V

235 – 295

0.65

0.85 0.15

0.35

2,000 V 2,500 V

235 – 295

0.65

0.85 0.15

0.35

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

1.05 in 2.45 in 3.5 lbs

12”

1.05 in 2.45 in 3.5 lbs

12”

1.05 in 2.45 in 3.5 lbs

12”

1.05 in 2.45 in 3.5 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

6.0 uf 280 V

6.0 uf 280 V

6.0 uf 280 V

6.0 uf 280 V

BALLAST SPECIFICATIONS

50W M110 Pulse Start Metal Halide S50M-4 60 Hz HX-HPF

3X4 CORE.WMF

Capacitor: CA6280DL Ignitor: SMH-2

17

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

0.80 1.65 0.75

0.45 0.95 0.55

0.40 0.80 0.50

0.35 0.70 0.35

Recommended Fuse (Amps) 4 3 2 2 Regulation

Line Volts Lamp Watts

±5% ±8%

±5% ±8%

±5% ±8%

±5% ±8%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

A 60.9

180 (H)

A 63.0

180 (H)

A 62.4

180 (H)

A 64.1

Power Factor (Min) Input Watts Efficiency

90% 92 W 76%

90% 92 W 76%

90% 92 W 76%

90% 92 W 76%

NOM. Open Circuit Voltage 250 250 250 250 Input Voltage At Lamp Dropout 85 140 165 185

Min Ambient Starting Temp -20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

1,600 V 1,900 V

225 – 275

0.95

1.20 0.45

0.85

1,600 V 1,900 V

225 – 275

0.95

1.20 0.25

0.50

1,600 V 1,900 V

225 – 275

0.95

1.20 0.25

0.45

1,600 V 1,900 V

225 – 275

0.95

1.20 0.20

0.40

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

1.45 in 2.85 in 4.6 lbs

12”

1.45 in 2.85 in 4.6 lbs

12”

1.45 in 2.85 in 4.6 lbs

12”

1.45 in 2.85 in 4.6 lbs

12” Capacitor Requirement

Microfarads Volts (Min)

8.0 uf 280 V

8.0 uf 280 V

8.0 uf 280 V

8.0 uf 280 V

BALLAST SPECIFICATIONS

70 W M98 Pulse Start Metal Halide S70M-4 60 Hz HX-HPF

3X4 CORE.WMF

Capacitor: CA8300DL Ignitor: SMH-2

18

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

1.10 2.60 1.00

0.65 1.50 0.60

0.55 1.30 0.50

0.50 1.15 0.45

Recommended Fuse (Amps) 7 4 4 3 Regulation

Line Volts Lamp Watts

±5%

±10%

±5%

±10%

±5%

±10%

±5%

±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

A 70.1

180 (H)

A 69.8

180 (H)

A 65.9

180 (H)

A 71.8

Power Factor (Min) Input Watts Efficiency

90%

125W

90%

125W

90%

125W

90%

125W

NOM. Open Circuit Voltage 270 270 270 270 Input Voltage At Lamp Dropout 80 140 160 185

Min Ambient Starting Temp -20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

1,600V 1,900V

240 – 300

1.20

1.50 0.40

0.75

1,600V 1,900V

240 – 300

1.20

1.50 0.25

0.45

1,600V 1,900V

240 – 300

1.20

1.50 0.20

0.40

1,600V 1,900V

240 – 300

1.20

1.50 0.15

0.35

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

1.70 in 3.10 in 5.2 lbs

12”

1.70 in 3.10 in 5.2 lbs

12”

1.70 in 3.10 in 5.2 lbs

12”

1.70 in 3.10 in 5.2 lbs

12” Capacitor Requirement

Microfarads Volts (Min)

12.0 uf 280V

12.0 uf 280V

12.0 uf 280V

12.0 uf 280V

BALLAST SPECIFICATIONS

100W M90 Pulse Start Metal Halide S100M-4 60 Hz HX-HPF

3X4 CORE.WMF

Capacitor: CA10280DL Ignitor: SMH-2

19

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

1.25 0.80 0.80

0.75 0.45 0.45

0.65 0.40 0.40

0.55 0.35 0.35

Regulation Line Volts Lamp Watts

±10% ±10%

±10% ±10%

±10% ±10%

±10% ±10%

UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

H A

66.5

H A

65.0

H A

62.7

H A

61.9

Input Watts 150W 150W 150W 150W NOM. Open Circuit Voltage 225 225 225 225 Power Factor 90% 90% 90% 90% Current Crest Factor 1.60 1.60 1.60 1.60 Input Voltage At Lamp Dropout 80 140 160 185

MIN. Ambient Starting Temp. -20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

1,600 V 2,000 V

200 – 250

1.45

1.80 0.50

0.85

1,600 V 2,000 V

200 – 250

1.45

1.80 0.30

0.50

1,600 V 2,000 V

200 – 250

1.45

1.80 0.25

0.45

1,600 V 2,000 V

200 – 250

1.45

1.80 0.20

0.35

Recommended Fuse (Amps) 4 3 2 2 CORE and COIL Specifications

Dimension (A) Dimension (B) Weight Lead Lengths

1.70 in 3.15 in 5.4 lbs

12”

1.70 in 3.15 in 5.4 lbs

12”

1.70 in 3.15 in 5.4 lbs

12”

1.70 in 3.15 in 5.4 lbs

12” Capacitor Requirement

Microfarads Volts (Min)

12.0 uf 280 V

12.0 uf 280 V

12.0 uf 280 V

12.0 uf 280 V

BALLAST SPECIFICATIONS

125W M150 Pulse Start Metal Halide S125M-4/PS 60 Hz CWA

3X4 CORE – HX, CWA & CWI UNITS

Capacitor: CA12280DL Ignitor: SMH-2

20

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

1.60 3.50 1.30

1.00 2.15 0.95

0.80 1.75 0.65

0.70 1.55 0.55

Recommended Fuse (Amps) 9 6 5 4 Regulation

Line Volts Lamp Watts

±5%

±10%

±5%

±10%

±5%

±10%

±5%

±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

B 78.0

180 (H)

D 87.6

180 (H)

C 80.9

180 (H)

C 80.5

Power Factor (Min) Input Watts Efficiency

90% 185 W 81%

90% 185 W 81%

90% 185 W 81%

90% 185 W 81%

NOM. Open Circuit Voltage 265 265 265 265 Input Voltage At Lamp Dropout 75 120 150 170

Min Ambient Starting Temp -20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

1,600 V 1,900 V

235 – 295

1.95

2.45 0.90

1.70

1,600 V 1,900 V

235 – 295

1.95

2.45 0.55

1.10

1,600 V 1,900 V

235 – 295

1.95

2.45 0.45

0.85

1,600 V 1,900 V

235 – 295

1.95

2.45 0.40

0.75

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

2.25 in 3.90 in 7.1 lbs

12”

2.25 in 3.90 in 7.1 lbs

12”

2.25 in 3.90 in 7.1 lbs

12”

2.25 in 3.90 in 7.1 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

16.0 uf 280 V

16.0 uf 280 V

16.0 uf 280 V

16.0 uf 280 V

BALLAST SPECIFICATIONS

150W M102 Pulse Start Metal Halide S150M-4 60 Hz HX-HPF

3X4 CORE.WMF

Capacitor: CA16330DL Ignitor: SMH-2

21

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

1.90 1.00 1.00

1.05 0.60 0.60

0.95 0.50 0.50

0.80 0.45 0.45

Recommended Fuse (Amps) 5 3 3 2 Regulation

Line Volts Lamp Watts

±10% ±10%

±10% ±10%

±10% ±10%

±10% ±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

B 77.7

180 (H)

C 80.6

180 (H)

A 74.5

180 (H)

A 73.2

Power Factor (Min) Input Watts Efficiency

90% 208 W 84%

90% 208 W 84%

90% 208 W 84%

90% 208 W 84%

NOM. Open Circuit Voltage 265 265 265 265 Input Voltage At Lamp Dropout 70 120 140 160

Min Ambient Starting Temp -20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

1,600 V 1,900 V

240 – 290

1.85

2.25 0.70

1.10

1,600 V 1,900 V

240 – 290

1.85

2.25 0.40

0.65

1,600 V 1,900 V

240 – 290

1.85

2.25 0.35

0.55

1,600 V 1,900 V

240 – 290

1.85

2.25 0.30

0.50

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

2.63 in 3.75 in 8.0 lbs

12”

2.63 in 3.75 in 8.0 lbs

12”

2.63 in 3.75 in 8.0 lbs

12”

2.63 in 3.75 in 8.0 lbs

12” Capacitor Requirement

Microfarads Volts (Min)

12.5 uf 330 V

12.5 uf 330 V

12.5 uf 330 V

12.5 uf 330 V

BALLAST SPECIFICATIONS

175W M137 / M152 Pulse Start Metal Halide S175M-4/PS 60 Hz CWA

3X4 CORE.WMF

Capacitor: CA12.5330DL Ignitor: SMH-2

22

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

2.00 3.30 2.10

1.25 2.05 1.15

1.00 1.65 1.10

0.85 1.45 0.75

Regulation Line Volts Lamp Watts

±5%

±10%

±5%

±10%

±5%

±10%

±5%

±10%

UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

H A

72.0

H A

70.0

H A

73.0

H A

67.0

Input Watts 225W 225W 225W 225W NOM. Open Circuit Voltage 285 285 285 285 Power Factor 90% 90% 90% 90% Current Crest Factor 1.50 1.50 1.50 1.50 Input Voltage At Lamp Dropout 90 140 150 190

MIN. Ambient Starting Temp. -40°F/ -40°C

-40°F / -40°C

-40°F/ -40°C

-40°F/ -40°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,500 V

255 – 315

1.90

2.35 1.60

1.90

2,000 V 2,500 V

255 – 315

1.90

2.35 1.05

1.30

2,000 V 2,500 V

255 – 315

1.90

2.35 0.80

1.00

2,000 V 2,500 V

255 – 315

1.90

2.35 0.70

0.80

Recommended Fuse (Amps) 9 6 5 4 CORE and COIL Specifications

Dimension (A) Dimension (B) Weight Lead Lengths

2.25 in 3.90 in 7.0 lbs

12”

2.25 in 3.90 in 7.0 lbs

12”

2.25 in 3.90 in 7.0 lbs

12”

2.25 in 3.90 in 7.0 lbs

12” Capacitor Requirement

Microfarads Volts (Min)

16.0 uf 290 V

16.0 uf 290 V

16.0 uf 290 V

16.0 uf 290 V

BALLAST SPECIFICATIONS

200W M136 Pulse Start Metal Halide S200M-4/PS 60 Hz HX – HPF

3X4 CORE – HX, CWA & CWI UNITS

Capacitor: CA16330DL Ignitor: SMH-2

23

Input Volts 480 Line Current ( Amps )

Operating Open Circuit Starting

0.50 0.80 0.50

Recommended Fuse (Amps) 2 Regulation

Line Volts Lamp Watts

±5%

±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

D 86.5

Power Factor (Min) Input Watts Efficiency

90% 237 W 84%

NOM. Open Circuit Voltage 285 Input Voltage At Lamp Dropout 320

Min Ambient Starting Temp -20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000V 2,500 V

255 – 315

1.85

2.25 0.45

0.50

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

2.45 in 3.90 in 8.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

16.0 uf 280 V

BALLAST SPECIFICATIONS

200W M136 Pulse Start Metal Halide S200M-48/12/PS 60 Hz HX-HPF

3X4 CORE – HX, CWA & CWI UNITS

Capacitor: CA16330DL Ignitor: SMH-2

24

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

2.50 1.80 1.40

1.45 1.10 0.80

1.25 0.90 0.70

1.10 0.80 0.60

Recommended Fuse (Amps) 7 4 4 3 Regulation

Line Volts Lamp Watts

±10% ±10%

±10% ±10%

±10% ±10%

±10% ±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H) B

75.4

180 (H) B

76.9

180 (H) A

74.1

180 (H) A

74.2

Power Factor (Min) Input Watts Efficiency

90% 288 W 87%

90% 288 W 87%

90% 288 W 87%

90% 288 W 87%

NOM. Open Circuit Voltage 270 270 270 270 Input Voltage At Lamp Dropout 60 104 120 138

Min Ambient Starting Temp -20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

1,600 V 1,900 V

240 – 290

2.25

2.75 1.10

1.70

1,600 V 1,900 V

240 – 290

2.25

2.75 0.65

0.95

1,600 V 1,900 V

240 – 290

2.25

2.75 0.55

0.85

1,600 V 1,900 V

240 – 290

2.25

2.75 0.45

0.75

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

1.55 in 3.50 in 10.0 lbs

12”

1.55 in 3.50 in 10.0 lbs

12”

1.55 in 3.50 in 10.0 lbs

12”

1.55 in 3.50 in 10.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

15.0 uf 400 V

15.0 uf 400 V

15.0 uf 400 V

15.0 uf 400 V

BALLAST SPECIFICATIONS

250W M138 / M153 Pulse Start Metal Halide S250M-4/PS 60 Hz CWA

4X4 CORE.WMF

Capacitor: CA15400 / CA15400DL Ignitor: SMH-2

25

Input Volts 480 Line Current ( Amps )

Operating Open Circuit Starting

0.60 0.45 0.45

Recommended Fuse (Amps) 2 Regulation

Line Volts Lamp Watts

±10% ±9%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

A 59.0

Power Factor (Min) Input Watts Efficiency

90% 285 W 88%

NOM. Open Circuit Voltage 275 Input Voltage At Lamp Dropout 270

Min Ambient Starting Temp -20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,400 V

245 – 300

2.35

2.90 0.35

0.50

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

2.00 in 4.10 in 11.5 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

16.0 uf 370 V

BALLAST SPECIFICATIONS

250W M138 / M153 Pulse Start Metal Halide S250M-48/12/PS 60 Hz CWA

4X4 CORE.WMF

Capacitor: CA15400 / CA15400DL Ignitor: SMH-2

26

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

3.20 1.20 2.60

1.80 0.70 1.50

1.60 0.60 1.30

1.40 0.50 1.15

Recommended Fuse (Amps) 8 5 4 4 Regulation

Line Volts Lamp Watts

±10% ±10%

±10% ±10%

±10% ±10%

±10% ±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

B 75.7

180 (H)

B 76.2

180 (H)

B 78.0

180 (H)

B 78.3

Power Factor (Min) Input Watts Efficiency

90% 368 W 87%

90% 368 W 87%

90% 368 W 87%

90% 368 W 87%

NOM. Open Circuit Voltage 265 265 265 265 Input Voltage At Lamp Dropout 80 140 160 200

Min Ambient Starting Temp -20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

1,600 V 1,900 V

235 – 295

3.10

3.80 2.15

3.25

1,600 V 1,900 V

235 – 295

3.10

3.80 1.20

1.85

1,600 V 1,900 V

235 – 295

3.10

3.80 1.05

1.65

1,600 V 1,900 V

235 – 295

3.10

3.80 0.90

1.40

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

1.85 in 3.65 in 10.0 lbs

12”

1.85 in 3.65 in 10.0 lbs

12”

1.85 in 3.65 in 10.0 lbs

12”

1.85 in 3.65 in 10.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

22.0 uf 330 V

22.0 uf 330 V

22.0 uf 330 V

22.0 uf 330 V

BALLAST SPECIFICATIONS

320W M132 / M154 Pulse Start Metal Halide S320M-4 60 Hz CWA

4X4 CORE – HX, CWA & CWI UNITS

Capacitor: CA22330DL Ignitor: SMH-2

27

Input Volts 480 Line Current ( Amps )

Operating Open Circuit Starting

0.80 0.40 0.60

Recommended Fuse (Amps) 3 Regulation

Line Volts Lamp Watts

±10% ±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

D 85.9

Power Factor (Min) Input Watts Efficiency

90% 368 W 87%

NOM. Open Circuit Voltage 265 Input Voltage At Lamp Dropout 320

Min Ambient Starting Temp -20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,400 V

235 – 295

3.00

3.60 0.45

0.75

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

1.90 in 3.75 in 10.5 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

22.0 uf 330 V

BALLAST SPECIFICATIONS

320W M132 / M154 Pulse Start Metal Halide S320M-48/12 60 Hz CWA

4X4 CORE – HX, CWA & CWI UNITS

Capacitor: CA2233DL Ignitor: SMH-2

28

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

3.60 1.30 3.30

2.10 0.75 1.90

1.80 0.65 1.65

1.55 0.55 1.40

Recommended Fuse (Amps) 9 6 5 4 Regulation

Line Volts Lamp Watts

±10% ±10%

±10% ±10%

±10% ±10%

±10% ±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

B 75.9

180 (H)

C 80.2

180 (H)

C 80.6

180 (H)

C 82.2

Power Factor (Min) Input Watts Efficiency

90% 398 W 88%

90% 398 W 88%

90% 398 W 88%

90% 398 W 88%

NOM. Open Circuit Voltage 245 245 245 245 Input Voltage At Lamp Dropout 85 155 170 190

Min Ambient Starting Temp -20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

1,600 V 1,900 V

215 – 275

3.25

3.95 2.50

3.80

1,600 V 1,900 V

215 – 275

3.25

3.95 1.45

2.15

1,600 V 1,900 V

215 – 275

3.25

3.95 1.25

1.90

1,600 V 1,900 V

215 – 275

3.25

3.95 1.10

1.70

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

1.92 in 3.80 in 10.5 lbs

12”

1.92 in 3.80 in 10.5 lbs

12”

1.92 in 3.80 in 10.5 lbs

12”

1.92 in 3.80 in 10.5 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

24.0 uf 330 V

24.0 uf 330 V

24.0 uf 330 V

24.0 uf 330 V

BALLAST SPECIFICATIONS

350W M131 Pulse Start Metal Halide S350M-4 60 Hz CWA

4X4 CORE – HX, CWA & CWI UNITS

Capacitor: CA24400DL Ignitor: SMH-2

29

Input Volts 480 Line Current ( Amps )

Operating Open Circuit Starting

0.85 0.55 0.65

Recommended Fuse (Amps) 3 Regulation

Line Volts Lamp Watts

±10% ±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

C 80.9

Power Factor (Min) Input Watts Efficiency

90% 398 W 88%

NOM. Open Circuit Voltage 250 Input Voltage At Lamp Dropout 300

Min Ambient Starting Temp -20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,400 V

225 – 275

3.15

3.85 0.50

0.75

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

2.00 in 4.10 in 10.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

24.0 uf 330 V

BALLAST SPECIFICATIONS

350W M131 Pulse Start Metal Halide S350M-48/12 60 Hz CWA

4X4 CORE – HX, CWA & CWI UNITS

Capacitor: CA24400DL Ignitor: SMH-2

30

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

4.00 2.00 3.50

2.30 1.15 2.00

2.00 1.00 1.75

1.75 0.85 1.50

Recommended Fuse (Amps) 10 6 5 5 Regulation

Line Volts Lamp Watts

±10% ±10%

±10% ±10%

±10% ±10%

±10% ±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

C 84.3

180 (H)

C 84.8

180 (H)

C 84.8

180 (H)

C 84.9

Power Factor (Min) Input Watts Efficiency

90% 453 W 88%

90% 453 W 88%

90% 453 W 88%

90% 453 W 88%

NOM. Open Circuit Voltage 280 280 280 280 Input Voltage At Lamp Dropout 60 104 120 138

Min Ambient Starting Temp -20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,500 V

250 – 310

3.50

4.30 2.80

4.20

2,000 V 2,500 V

250 – 310

3.50

4.30 1.60

2.40

2,000 V 2,500 V

250 – 310

3.50

4.30 1.40

2.10

2,000 V 2,500 V

250 – 310

3.50

4.30 1.20

1.80

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

2.00 in 3.90 in 10.7 lbs

12”

2.00 in 3.90 in 10.7 lbs

12”

2.00 in 3.90 in 10.7 lbs

12”

2.00 in 3.90 in 10.7 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

26.0 uf 330 V

26.0 uf 330 V

26.0 uf 330 V

26.0 uf 330 V

BALLAST SPECIFICATIONS

400W M135 / M155 Pulse Start Metal Halide S400M-4/PS 60 Hz CWA

4X4 CORE.WMF

Capacitor: CA26400DL Ignitor: SMH-2

31

Input Volts 480 Line Current ( Amps )

Operating Open Circuit Starting

1.00 0.50 0.90

Recommended Fuse (Amps) 3 Regulation

Line Volts Lamp Watts

±10% ±9%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

D 88.9

Power Factor (Min) Input Watts Efficiency

90% 452 W 89%

NOM. Open Circuit Voltage 280 Input Voltage At Lamp Dropout 240

Min Ambient Starting Temp -20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,500 V

250 – 310

3.55

4.35 0.60

0.90

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

2.20 in 4.10 in 12.0 lbs

12’

Capacitor Requirement Microfarads Volts (Min)

26.0 uf 330 V

BALLAST SPECIFICATIONS

400W M135 / M155 Pulse Start Metal Halide S400M-48/12/PS 60 Hz CWA

4X4 CORE – HX, CWA & CWI UNITS

Capacitor: CA26400DL Ignitor: SMH-2

32

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

4.40 1.50 4.00

2.50 0.85 2.30

2.20 0.75 2.00

1.90 0.65 1.70

Recommended Fuse (Amps) 11 7 6 5 Regulation

Line Volts Lamp Watts

±10% ±10%

±10% ±10%

±10% ±10%

±10% ±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

C 83.7

180 (H)

D 85.2

180 (H)

D 85.4

180 (H)

D 88.1

Power Factor (Min) Input Watts Efficiency

90% 507 W 89%

90% 507 W 89%

90% 507 W 89%

90% 507 W 89%

NOM. Open Circuit Voltage 260 260 260 260 Input Voltage At Lamp Dropout 70 120 140 160

Min Ambient Starting Temp -20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,500 V

235 – 285

4.20

5.15 3.20

4.80

2,000 V 2,500 V

235 – 285

4.20

5.15 1.85

2.75

2,000 V 2,500 V

235 – 285

4.20

5.15 1.60

2.40

2,000 V 2,500 V

235 – 285

4.20

5.15 1.40

2.10

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

2.30 4.20

12.4 lbs 12”

2.30 4.20

12.4 lbs 12”

2.30 4.20

12.4 lbs 12”

2.30 4.20

12.4 lbs 12”

Capacitor Requirement Microfarads Volts (Min)

32.0 uf 300 V

32.0 uf 300 V

32.0 uf 300 V

32.0 uf 300 V

BALLAST SPECIFICATIONS

450W M144 Pulse Start Metal Halide S450M-4/PS 60 Hz CWA

4X4 CORE – HX, CWA & CWI UNITS

Capacitor: CA32330DL Ignitor: SMH-2

33

Input Volts 480 Line Current ( Amps )

Operating Open Circuit Starting

1.10 0.55 0.85

Recommended Fuse (Amps) 3 Regulation

Line Volts Lamp Watts

±10% ±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

C 84.3

Power Factor (Min) Input Watts Efficiency

90% 509 W 88%

NOM. Open Circuit Voltage 255 Input Voltage At Lamp Dropout 250

Min Ambient Starting Temp -20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,400 V

230 – 280

4.15

5.05 0.65

1.95

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

2.30 in 4.40 in 14.5 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

32.0 uf 300 V

BALLAST SPECIFICATIONS

450W M144 Pulse Start Metal Halide S450M-48/12/PS 60 Hz CWA

4X4 CORE.WMF

Capacitor: CA32330DL Ignitor: SMH-2

34

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

5.70 8.75 7.80

3.05 4.70 4.20

2.95 4.45 4.05

2.50 3.80 3.20

Regulation Line Volts Lamp Watts

±5%

±10%

±5%

±10%

±5%

±10%

±5%

±10%

UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

H B

79.3

H B

73.9

H B

81.6

H B

81.3

Input Watts 635 W 635 W 635 W 635 W NOM. Open Circuit Voltage 300 300 300 300 Power Factor 90% 90% 90% 90% Current Crest Factor 1.50 1.50 1.50 1.50 Input Voltage At Lamp Dropout 90 160 180 210

MIN. Ambient Starting Temp. -40°F/ -40°C

-40°F/ -40°C

-40°F/ -40°C

-40°F/ -40°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,500 V

270 – 330

5.65

6.95 6.05

9.15

2,000 V 2,500 V

270 – 330

5.65

6.95 3.10

4.70

2,000 V 2,500 V

270 – 330

5.65

6.95 3.15

4.75

2,000 V 2,500 V

270 – 330

5.65

6.95 2.65

4.05

Recommended Fuse (Amps) 15 8 8 7 CORE and COIL Specifications

Dimension (A) Dimension (B) Weight Lead Lengths

3.25 in 4.90 in 18.0 lbs

12”

3.25 in 4.90 in 18.0 lbs

12”

3.25 in 4.90 in 18.0 lbs

12”

3.25 in 4.90 in 18.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

38.0 uf 330 V

38.0 uf 330 V

38.0 uf 330 V

38.0 uf 330 V

BALLAST SPECIFICATIONS

575W Pulse Start Metal Halide S575M-4/PS 60 Hz HX – HPF

4X4 CORE – HX, CWA & CWI UNITS

Capacitor: CA38330DL Ignitor: BVS-045

35

Input Volts 480 Line Current ( Amps )

Operating Open Circuit Starting

1.45 2.30 2.20

Regulation Line Volts Lamp Watts

±5%

±10%

UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

H D

89.0

Input Watts 645 W NOM. Open Circuit Voltage 325 Power Factor 90% Current Crest Factor 1.50 Input Voltage At Lamp Dropout 300

MIN. Ambient Starting Temp. -40°F/ -40°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,500 V

295 – 355 5.70 6.30 1.40 2.10

Recommended Fuse (Amps) 4 CORE and COIL Specifications

Dimension (A) Dimension (B) Weight Lead Lengths

3.25 in 4.90 in 18.5 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

38.0 uf 330 V

BALLAST SPECIFICATIONS

575W Pulse Start Metal Halide S575M-48/PS 60 Hz HX – HPF

4X4 CORE – HX, CWA & CWI UNITS

Capacitor: CA38330DL Ignitor: BVS-045

36

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

6.80 4.60 4.80

4.00 2.60 2.80

3.40 2.30 2.40

3.00 2.00 2.10

Recommended Fuse (Amps) 17 10 9 8 Regulation

Line Volts Lamp Watts

±10% ±10%

±10% ±10%

±10% ±10%

±10% ±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

B 75.9

180 (H)

C 81.6

180 (H)

B 75.9

180 (H)

B 78.2

Power Factor (Min) Input Watts Efficiency

90% 815 W

90% 815 W

90% 815 W

90% 815 W

NOM. Open Circuit Voltage 370 370 370 370 Input Voltage At Lamp Dropout 60 105 120 140

Min Ambient Starting Temp -20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,500 V

335 – 405

4.30

5.30 3.60

5.50

2,000 V 2,500 V

335 – 405

4.30

5.30 2.00

3.10

2,000 V 2,500 V

335 – 405

4.30

5.30 1.85

2.75

2,000 V 2,500 V

335 – 405

4.30

5.30 1.60

2.40

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

2.30 in 4.30 in 18.0 lbs

12”

2.30 in 4.30 in 18.0 lbs

12”

2.30 in 4.30 in 18.0 lbs

12”

2.30 in 4.30 in 18.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

24.0 uf 480 V

24.0 uf 480 V

24.0 uf 480 V

24.0 uf 480 V

BALLAST SPECIFICATIONS

750W M149 Pulse Start Metal Halide S750M-4/PS 60 Hz CWA

4X6 CORE.WMF

Capacitor: CA24480 Ignitor: BVS-042

37

Input Volts 480 Line Current ( Amps )

Operating Open Circuit Starting

1.70 1.35 1.10

Recommended Fuse (Amps) 4 Regulation

Line Volts Lamp Watts

±10% ±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

D 85.2

Power Factor (Min) Input Watts Efficiency

90% 820 W

NOM. Open Circuit Voltage 370 Input Voltage At Lamp Dropout 220

Min Ambient Starting Temp -20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,500 V

335 – 405

4.30

5.30 0.80

1.20

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

2.40 in 4.40 in 19.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

24.0 uf 480 V

BALLAST SPECIFICATIONS

750W M149 Pulse Start Metal Halide S750M-48/12/PS 60 Hz CWA

4X6 CORE.WMF

Capacitor: CA24480 Ignitor: BVS-042

38

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

8.00 5.50 5.50

4.50 3.20 3.20

4.00 2.75 2.75

3.45 2.40 2.40

Recommended Fuse (Amps) 20 12 10 9 Regulation

Line Volts Lamp Watts

±10% ±10%

±10% ±10%

±10% ±10%

±10% ±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

B 78.6

180 (H)

A 63.1

180 (H)

A 67.7

180 (H)

A 67.2

Power Factor (Min) Input Watts Efficiency

90% 950W 92%

90% 950W 92%

90% 950W 92%

90% 950W 92%

NOM. Open Circuit Voltage 420 420 420 420 Input Voltage At Lamp Dropout 65 110 130 150

Min Ambient Starting Temp -20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

1,650 V 2,500 V

380 – 470

4.30

5.30 4.30

6.60

1,650 V 2,500 V

380 – 470

4.30

5.30 2.50

3.80

1,650 V 2,500 V

380 – 470

4.30

5.30 2.15

3.30

1,650 V 2,500 V

380 – 470

4.30

5.30 1.85

2.85

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

2.80 in 4.80 in 21.0 lbs

12”

2.80 in 4.80 in 21.0 lbs

12”

2.80 in 4.80 in 21.0 lbs

12”

2.80 in 4.80 in 21.0 lbs

12” Capacitor Requirement

Microfarads Volts (Min)

22.0 uf 460 V

22.0 uf 460 V

22.0 uf 460 V

22.0 uf 460 V

BALLAST SPECIFICATIONS

875W M166 Pulse Start Metal Halide S875M-4 60 Hz CWA

4X6 CORE.WMF

Capacitor: CA22525 Ignitor: BVS-020

39

Input Volts 480 Line Current ( Amps )

Operating Open Circuit Starting

2.00 1.60 1.30

Recommended Fuse (Amps) 5 Regulation

Line Volts Lamp Watts

±10% ±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

C 81.5

Power Factor (Min) Input Watts Efficiency

90% 950 W 92%

NOM. Open Circuit Voltage 420 Input Voltage At Lamp Dropout 250

Min Ambient Starting Temp -20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,400 V

380 – 460

4.30

5.30 1.00

1.50

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

2.82 in 4.85 in 21.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

22.0 uf 460 V

BALLAST SPECIFICATIONS

875W M166 Pulse Start Metal Halide S875M-48 60 Hz CWA

4X6 CORE.WMF

Capacitor: CA22525 Ignitor: BVS-020

40

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

9.00 6.00 6.00

5.20 3.50 3.50

4.50 3.00 3.00

3.90 2.60 2.60

Recommended Fuse (Amps) 25 15 12 10 Regulation

Line Volts Lamp Watts

±10% ±10%

±10% ±10%

±10% ±10%

±10% ±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

D 88.2

180 (H)

A 73.5

180 (H)

B 78.4

180 (H)

B 78.2

Power Factor (Min) Input Watts Efficiency

90% 1082 W

92%

90% 1082 W

92%

90% 1082 W

92%

90% 1082 W

92%

NOM. Open Circuit Voltage 420 420 420 420 Input Voltage At Lamp Dropout 70 125 140 160

Min Ambient Starting Temp -20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

1,850 V 2,200 V

380 – 460

4.75

5.85 4.80

7.20

1,850 V 2,200 V

380 – 460

4.75

5.85 2.80

4.20

1,850 V 2,200 V

380 – 460

4.75

5.85 2.40

3.60

1,850 V 2,200 V

380 – 460

4.75

5.85 2.10

3.15

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

2.80 in 4.80 in 21.0 lbs

12”

2.80 in 4.80 in 21.0 lbs

12”

2.80 in 4.80 in 21.0 lbs

12”

2.80 in 4.80 in 21.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

24.0 uf 480 V

24.0 uf 480 V

24.0 uf 480 V

24.0 uf 480 V

BALLAST SPECIFICATIONS

1000W M141 Pulse Start Metal Halide S1000M-4/PS 60 Hz CWA

4X6 CORE.WMF

Capacitor: CA24480 Ignitor: BVS-020

41

Input Volts 480 Line Current ( Amps )

Operating Open Circuit Starting

2.25 1.60 1.50

Recommended Fuse (Amps) 6 Regulation

Line Volts Lamp Watts

±10% ±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

D 85.0

Power Factor (Min) Input Watts Efficiency

90% 1082 W

92%

NOM. Open Circuit Voltage 420 Input Voltage At Lamp Dropout 300

Min Ambient Starting Temp -20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,400 V

375 – 460

4.75

5.85 1.10

1.80

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

2.82 in 4.85 in 21.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

24.0 uf 480 V

BALLAST SPECIFICATIONS

1000W M141 Pulse Start Metal Halide S1000M-48/12/PS 60 Hz CWA

4X6 CORE.WMF

Capacitor: CA24480 Ignitor: BVS-020

42

HID BALLASTS

High Pressure Sodium

13 Columbia Dr. #12 Amherst, NH 03031 www.souheganlighting.com

Toll Free: 877-610-4010 Phone: 603-889-8962 Fax: 603-889-0291

43

Input Volts 120 Line Current ( Amps )

Operating Open Circuit Starting

0.85

0.75

Recommended Fuse (Amps) 3 Regulation

Line Volts Lamp Watts

±5%

±12%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

A

Power Factor (Min) Input Watts Efficiency

40% 45 W

NOM. Open Circuit Voltage 120 Input Voltage At Lamp Dropout

Min Ambient Starting Temp -40°F / -40°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,500 V 110 – 35

.00

.00

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

.90 in 2.15 in 2.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

BALLAST SPECIFICATIONS

35W S76 High Pressure Sodium S35S-12 60 Hz Reactor-NPF

0.75EI CORE.wmf

Capacitor: NONE Ignitor: S55V

44

Input Volts 120 Line Current ( Amps )

Operating Open Circuit Starting

1.20

1.10

Recommended Fuse (Amps) 2 Regulation

Line Volts Lamp Watts

±5%

±12%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

A

Power Factor (Min) Input Watts Efficiency

40% 65W

NOM. Open Circuit Voltage 120 Input Voltage At Lamp Dropout 95

Min Ambient Starting Temp -40°F / -40°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,500 V

110 – 135

1.35

1.65 0.55

0.95

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

1.15 in 2.35 in 2.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

BALLAST SPECIFICATIONS

50 W S68 High Pressure Sodium S50S-12 60 Hz Reactor-NPF

0.75EI CORE.wmf

Capacitor: NONE Ignitor: S55V

45

Input Volts 120 Line Current ( Amps )

Operating Open Circuit Starting

1.70

1.25

Recommended Fuse (Amps) 5 Regulation

Line Volts Lamp Watts

±5% ±9%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

B

Power Factor (Min) Input Watts Efficiency

40% 85 W

NOM. Open Circuit Voltage 120 Input Voltage At Lamp Dropout

Min Ambient Starting Temp -40°F / -40°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,500 V

110 – 135

.00

.00

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

1.29 in 2.55 in 3.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

BALLAST SPECIFICATIONS

70W S62 High Pressure Sodium S70S-12 60 Hz Reactor-NPF

78EI CORE.wmf

Capacitor: NONE Ignitor: S55V

46

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

0.80 1.50 0.60

0.45 0.85 0.35

0.40 0.75 0.30

0.35 0.65 0.25

Regulation Line Volts Lamp Watts

±5%

±10%

±5%

±10%

±5%

±10%

±5%

±10%

UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

H A

51.2

H A

49.0

H A

51.0

H A

48.3 Input Watts 90 W 90 W 90 W 90 W NOM. Open Circuit Voltage 120 120 120 120 Power Factor 90% 90% 90% 90% Current Crest Factor 1.50 1.50 1.50 1.50 Input Voltage At Lamp Dropout 90 160 180 205

MIN. Ambient Starting Temp. -40°F / -40°C

-40°F / -40°C

-40°F / -40°C

-40°F / -40°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,500 V

105 – 135

1.80

2.20 0.40

0.70

2,000 V 2,500 V

105 – 135

1.80

2.20 0.25

0.40

2,000 V 2,500 V

105 – 135

1.80

2.20 0.20

0.35

2,000 V 2,500 V

105 – 135

1.80

2.20 0.15

0.30

Recommended Fuse (Amps) 4 3 2 2 CORE and COIL Specifications

Dimension (A) Dimension (B) Weight Lead Lengths

1.50 in 2.95 in 4.6 lbs

12”

1.50 in 2.95 in 4.6 lbs

12”

1.50 in 2.95 in 4.6 lbs

12”

1.50 in 2.95 in 4.6 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

7.0 uf 280 V

7.0 uf 280 V

7.0 uf 280 V

7.0 uf 280 V

BALLAST SPECIFICATIONS

70W S62 High Pressure Sodium S70S-4 60 Hz Reactor-NPF

3X4 CORE – HX, CWA & CWI UNITS

Capacitor: CA300DL Ignitor: S55V

47

Input Volts 120 Line Current ( Amps )

Operating Open Circuit Starting

2.15

1.80

Recommended Fuse (Amps) 6 Regulation

Line Volts Lamp Watts

±5% ±8%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

E

Power Factor (Min) Input Watts Efficiency

40% 118 W

NOM. Open Circuit Voltage 120 Input Voltage At Lamp Dropout

Min Ambient Starting Temp -40°F/ -40°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,500 V

110 – 135

.00

.00

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

1.48 in 2.75 in 3.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

BALLAST SPECIFICATIONS

100W S54 High Pressure Sodium S100S-12 60 Hz Reactor-NPF

78EI CORE.wmf

Capacitor: NONE Ignitor: S55V

48

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

1.10 2.10 0.90

0.60 1.20 0.55

0.55 1.05 0.45

0.45 0.90 0.40

Regulation Line Volts Lamp Watts

±5%

±10%

±5%

±10%

±5%

±10%

±5%

±10%

UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

H A

H A

H A

H A

Input Watts 126 W 126 W 126 W 126 W NOM. Open Circuit Voltage 130 130 130 130 Power Factor 90% 90% 90% 90% Current Crest Factor 1.50 1.50 1.50 1.50 Input Voltage At Lamp Dropout 90 160 180 210

MIN. Ambient Starting Temp. -20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

-20°F/ -30°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,500 V

115 – 145

2.50

2.80 0.70

1.00

2,000 V 2,500 V

115 – 145

2.50

2.80 0.40

0.60

2,000 V 2,500 V

115 – 145

2.50

2.80 0.35

0.50

2,000 V 2,500 V

115 – 145

2.50

2.80 0.30

0.45

Recommended Fuse (Amps) 6 3 3 3 CORE and COIL Specifications

Dimension (A) Dimension (B) Weight Lead Lengths

2.00 in 3.45 in 5.9 lbs

12”

2.00 in 3.45 in 5.9 lbs

12”

2.00 in 3.45 in 5.9 lbs

12”

2.00 in 3.45 in 5.9 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

10.0 uf 280 V

10.0 uf 280 V

10.0 uf 280 V

10.0 uf 280 V

BALLAST SPECIFICATIONS

100W S54 High Pressure Sodium S100S-4 60 Hz HX-HPF

3X4 CORE – HX, CWA & CWI UNITS

Capacitor: CA10280DL Ignitor: S55V

49

Input Volts 120 Line Current ( Amps )

Operating Open Circuit Starting

1.50 2.45 2.00

Recommended Fuse (Amps) 4 Regulation

Line Volts Lamp Watts

±5%

±10%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H) E

Power Factor (Min) Input Watts Efficiency

90% 166W

NOM. Open Circuit Voltage 120 Input Voltage At Lamp Dropout 95

Min Ambient Starting Temp -40°F/ -40°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,500 V

110 – 135

3.80

4.70 1.50

2.50

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

2.00 in 3.05 in 4.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

52.0 uf 120 V

BALLAST SPECIFICATIONS

150W S55 High Pressure Sodium S150S-12 60 Hz Reactor–HPF

78EI CORE.wmf

Capacitor: NONE Ignitor: S55V

50

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

1.60 2.80 1.60

0.85 1.60 0.85

0.80 1.40 0.80

0.70 1.25 0.70

Regulation Line Volts Lamp Watts

±5%

±10%

±5%

±10%

±5%

±10%

±5%

±10%

UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

H D

86.3

H B

79.6

H C

83.9

H C

83.5

Input Watts 188 W 188 W 188 W 188 W NOM. Open Circuit Voltage 120 120 120 120 Power Factor 90% 90% 90% 90% Current Crest Factor 1.50 1.50 1.50 1.50 Input Voltage At Lamp Dropout 95 180 190 225

MIN. Ambient Starting Temp. -40°F/ -40°C

-40°F/ -40°C

-40°F/ -40°C

-40°F/ -40°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,500 V

105 – 135

3.80

4.70 1.20

1.85

2,000 V 2,500 V

105 – 135

3.80

4.70 0.65

1.00

2,000 V 2,500 V

105 – 135

3.80

4.70 0.60

0.95

2,000 V 2,500 V

105 – 135

3.80

4.70 0.50

0.80

Recommended Fuse (Amps) 7 4 4 4 CORE and COIL Specifications

Dimension (A) Dimension (B) Weight Lead Lengths

2.50 in 3.80 in 7.4 lbs

12”

2.50 in 3.80 in 7.4 lbs

12”

2.50 in 3.80 in 7.4 lbs

12”

2.50 in 3.80 in 7.4 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

14.0 uf 280 V

14.0 uf 280 V

14.0 uf 280 V

14.0 uf 280 V

BALLAST SPECIFICATIONS

150W S55 High Pressure Sodium S150S-4 60 Hz HX-HPF

3X4 CORE – HX, CWA & CWI UNITS

Capacitor: CA14300DL Ignitor: S55V

51

Input Volts 480 Line Current ( Amps )

Operating Open Circuit Starting

0.40 0.20 0.25

Recommended Fuse (Amps) 1 Regulation

Line Volts Lamp Watts

±10% ±6%

Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

180 (H)

D 85.0

Power Factor (Min) Input Watts Efficiency

90% 186 W

NOM. Open Circuit Voltage 120 Input Voltage At Lamp Dropout 250

Min Ambient Starting Temp -40°F/ -40°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,500 V

105 – 130

3.90

4.80 0.20

0.30

CORE and COIL Specifications Dimension (A) Dimension (B) Weight Lead Lengths

3.15 in 4.55 in 11.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

51.0 uf 180 V

BALLAST SPECIFICATIONS

150W S55 High Pressure Sodium S150S-48 60 Hz CWI

3X4 CORE.WMF

Capacitor: CA14300DL Ignitor: S55V

52

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

2.50 1.90 1.80

1.45 1.10 1.00

1.25 0.95 0.90

1.10 0.85 0.75

Regulation Line Volts Lamp Watts

±10% ±13%

±10% ±13%

±10% ±13%

±10% ±13%

UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

H B

77.4

H B

79.3

H B

79.1

H B

77.9 Input Watts 295 W 295 W 295 W 295 W NOM. Open Circuit Voltage 195 195 195 195 Power Factor 90% 90% 90% 90% Current Crest Factor 1.65 1.65 1.65 1.65 Input Voltage At Lamp Dropout 85 145 170 195

MIN. Ambient Starting Temp. -40°F / -40°C

-40°F / -40°C

-40°F / -40°C

-40°F / -40°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

1,600 V 2,000 V

175 – 215

3.80

4.70 1.25

1.90

1,600 V 2,000 V

175 – 215

3.80

4.70 0.70

1.10

1,600 V 2,000 V

175 – 215

3.80

4.70 0.60

0.95

1,600 V 2,000 V

175 – 215

3.80

4.70 0.50

0.85

Recommended Fuse (Amps) 7 4 4 3 CORE and COIL Specifications

Dimension (A) Dimension (B) Weight Lead Lengths

1.80 in 3.60 in 11.0 lbs

12”

1.80 in 3.60 in 11.0 lbs

12”

1.80 in 3.60 in 11.0 lbs

12”

1.80 in 3.60 in 11.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

35.0 uf 240 V

35.0 uf 240 V

35.0 uf 240 V

35.0 uf 240 V

BALLAST SPECIFICATIONS

250W S50 High Pressure Sodium S250S-4 60 Hz CWA

4X4 CORE – HX, CWA & CWI UNITS

Capacitor: CA35280DL Ignitor: S100V

53

Input Volts 480 Line Current ( Amps )

Operating Open Circuit Starting

0.65 0.40 0.47

Regulation Line Volts Lamp Watts

±10% ±12%

UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

H B

Input Watts 305 W NOM. Open Circuit Voltage 200 Power Factor 90% Current Crest Factor 1.65 Input Voltage At Lamp Dropout 320

MIN. Ambient Starting Temp. -40°F / -40°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,400 V

180 – 220

3.80

4.70 0.30

0.60

Recommended Fuse (Amps) 2 CORE and COIL Specifications

Dimension (A) Dimension (B) Weight Lead Lengths

1.80 in 3.60 in 11.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

35.0 uf 240 V

BALLAST SPECIFICATIONS

250W S50 High Pressure Sodium S250S-48/12 60 Hz CWA

4X4 CORE – HX, CWA & CWI UNITS

Capacitor: CA35280DL Ignitor: S100V

54

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

3.80 1.50 3.70

2.20 0.85 2.15

1.90 0.75 1.85

1.70 0.65 1.60

Regulation Line Volts Lamp Watts

±10% ±13%

±10% ±13%

±10% ±13%

±10% ±13%

UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

H C

83.8

H C

84.2

H C

85.9

H C

82.3 Input Watts 460 W 460 W 460 W 460 W NOM. Open Circuit Voltage 195 195 195 195 Power Factor 90% 90% 90% 90% Current Crest Factor 1.60 1.60 1.60 1.60 Input Voltage At Lamp Dropout 90 155 180 205

MIN. Ambient Starting Temp. -40°F / -40°C

-40°F / -40°C

-40°F / -40°C

-40°F / -40°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

1,600 V 2,000 V

175 - 215

6.25

7.65 3.00

4.50

1,600 V 2,000 V

175 - 215

6.25

7.65 1.70

2.60

1,600 V 2,000 V

175 - 215

6.25

7.65 1.50

2.25

1,600 V 2,000 V

175 - 215

6.25

7.65 1.30

1.95

Recommended Fuse (Amps) 10 7 6 5 CORE and COIL Specifications

Dimension (A) Dimension (B) Weight Lead Lengths

2.30 in 4.20 in 14.0 lbs

12”

2.30 in 4.20 in 14.0 lbs

12”

2.30 in 4.20 in 14.0 lbs

12”

2.30 in 4.20 in 14.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

55.0 uf 240 V

55.0 uf 240 V

55.0 uf 240 V

55.0 uf 240 V

BALLAST SPECIFICATIONS

400W S51 High Pressure Sodium S400S-4 60 Hz CWA

4X4 CORE – HX, CWA & CWI Units

Capacitor: CA55240DL Ignitor: S100V

55

Input Volts 480 Line Current ( Amps )

Operating Open Circuit Starting

1.00 0.40 0.80

Regulation Line Volts Lamp Watts

±10% ±13%

UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

H C

81.9

Input Watts 464 W NOM. Open Circuit Voltage 195 Power Factor 90% Current Crest Factor 1.63 Input Voltage At Lamp Dropout 370

MIN. Ambient Starting Temp. -40°F / -40°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,400 V

175 – 215

6.35

7.75 0.55

0.90

Recommended Fuse (Amps) 3 CORE and COIL Specifications

Dimension (A) Dimension (B) Weight Lead Lengths

2.60 in 4.45 in 15.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

55.0 uf 240 V

BALLAST SPECIFICATIONS

400W S51 High Pressure Sodium S400S-48/12 60 Hz CWA

4X4 CORE – HX, CWA & CWI Units

Capacitor: CA55240DL Ignitor: S100V

56

Input Volts 120 208 240 277 Line Current ( Amps )

Operating Open Circuit Starting

9.50 4.80 7.20

5.50 2.75 4.15

4.75 2.40 3.60

4.20 2.05 3.10

Regulation Line Volts Lamp Watts

±10% ±13%

±10% ±13%

±10% ±13%

±10% ±13%

UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

H C

83.8

H B

77.8

H C

81.8

H C

80.5 Input Watts 1100 W 1100 W 1100 W 1100 W NOM. Open Circuit Voltage 425 425 425 425 Power Factor 90% 90% 90% 90% Current Crest Factor 1.65 1.65 1.65 1.65 Input Voltage At Lamp Dropout 95 170 190 220

MIN. Ambient Starting Temp. -40°F / -40°C

-40°F / -40°C

-40°F / -40°C

-40°F / -40°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,400 V

380 – 470

6.20

7.60 5.20

8.20

2,000 V 2,400 V

380 – 470

6.20

7.60 3.15

4.80

2,000 V 2,400 V

380 – 470

6.20

7.60 2.60

4.10

2,000 V 2,400 V

380 – 470

6.20

7.60 2.35

3.55

Recommended Fuse (Amps) 25 15 12 10 CORE and COIL Specifications

Dimension (A) Dimension (B) Weight Lead Lengths

3.75 in 5.90 in 27.0 lbs

12”

3.75 in 5.90 in 27.0 lbs

12”

3.75 in 5.90 in 27.0 lbs

12”

3.75 in 5.90 in 27.0 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

26.0 uf 525 V

26.0 uf 525 V

26.0 uf 525 V

26.0 uf 525 V

BALLAST SPECIFICATIONS

1000W S52 High Pressure Sodium S1000S-4 60 Hz CWA

4X4 CORE – HX, CWA & CWI UNITS

Capacitor: CA26525 Ignitor: S250V

57

Input Volts 480 Line Current ( Amps )

Operating Open Circuit Starting

2.30 0.80 2.30

Regulation Line Volts Lamp Watts

±10% ±14%

UL Temperature Ratings Insulation Class Coil Temperature Code Benchtop Coil Rise

H C

82.9

Input Watts 1100 W NOM. Open Circuit Voltage 430 Power Factor 90% Current Crest Factor 1.65 Input Voltage At Lamp Dropout 385

MIN. Ambient Starting Temp. -40°F / -40°C

60 Hz TEST PROCEDURES High Potential Test (Volts)

1 Minute 1 Second

Open Circuit Voltage Test (V) Short Circuit Current Test (A)

Min Secondary Current

Max Min

Input Current Max

2,000 V 2,400 V

385 – 475

6.35

7.80 1.80

2.80

Recommended Fuse (Amps) 6 CORE and COIL Specifications

Dimension (A) Dimension (B) Weight Lead Lengths

3.90 in 5.90 in 28.8 lbs

12”

Capacitor Requirement Microfarads Volts (Min)

26.0 uf 525 V

BALLAST SPECIFICATIONS

1000W S52 High Pressure Sodium S1000S-48/12 60 Hz CWA

4X6 CORE – HX, CWA & CWI UNITS

Capacitor: CA26525 Ignitor: S250V

58