Pride Home Inspections Property Inspection For:102 Felicity laneHuntsville, AL
Pride Home Inspections13015 Branscomb Road, Huntsville, AL 35803
Property Inspection Agreement
Client: John Doe Property:102 Felicity lane
E−mail Address: Huntsville, AL
Date of Inspection:12/13/2005 Time: 1:00 PM
I (Client) hereby request a limited visual inspection of the structure at the above address to be conducted by PRIDEHOME INSPECTION for my sole use and benefit. I warrant that I will read the following agreement carefully. Iunderstand that I am bound by all the terms of this contract.
SCOPE OF INSPECTION
The scope of the inspection and report is a limited visual inspection of the general systems and components of thehome to identify any system or component listed in the report that may be in need of immediate major repair. Theinspection will be performed in compliance with generally accepted standards of practice.
OUTSIDE THE SCOPE OF INSPECTION
Any area that is not exposed to view, is concealed, or is inaccessible because of soil, walls, floors, carpets, ceilings,furnishing, or any other thing is not included in this inspection.
The inspection does not include any destructive testing or dismantling. Client agrees to assume all the risk for allconditions that are concealed from view at the time of the inspection.
This is not a home warranty, guarantee, insurance policy or substitute for real estate transfer disclosures which may berequired by law.
Whether or not they are concealed, the following ARE OUTSIDE THE SCOPE OF THIS INSPECTION:
Building code or zoning ordinance violations.• Geological stability or soils condition.• Structural stability or engineering analysis.• Termites, pests or other wood−destroyingorganisms.
•
Asbestos, radon, formaldehyde, lead, water or airquality, electromagnetic radiation or anyenvironmental hazards.
•
Building value appraisal or cost estimates.• Condition of detached buildings.• Pools or spas bodies and underground piping.• Specific components noted as being excluded onthe individual system inspection forms.
•
Private water or private sewage systems.• Saunas, steam baths, or fixtures and equipment.• Radio−controlled devices, automatic gates,elevators, lifts, dumbwaiters and thermostatic ortime clock controls.
•
Water softener/purifier systems or solar heatingsystems.
•
Furnace heat exchangers, freestandingappliances, security alarms or personalproperty.
•
Adequacy of efficiency of any system orcomponent.
•
Prediction of life expectancy of any item.• (Some of the above items may be included in this inspection for additional fees – check with your inspector)
Your inspector is a home inspection generalist and is not acting as a licensed engineer or expert in any craft or trade. If
your inspector recommends consulting other specialized experts, client must do so at client’s expense.
ARBRITATION: Any dispute concerning the interpretation of this agreement or arising from this inspection andreport, except one for inspection fee payment, shall be resolved informally between the parties or by arbitrationconducted in accordance with the rules of the recognized Arbitration Association except that the parties shall select anarbitrator who is familiar with the home inspection industry. The Arbitrator shall conduct summary judgment motionsand enforce full discovery rights as a court would as provided in civil proceeding by legal code.CONFIDENTIAL REPORT: The inspection report to be prepared for Client is solely and exclusively for Client’sown information and may not be relied upon by any other person. Client agrees to maintain the confidentiality of theinspection report and agrees not to disclose any part of it to any other person. Client may distribute copies of theinspection report to the seller and the real estate agents directly involved in this transaction, but said persons are notspecifically intended beneficiaries of this Agreement or the inspection report. Client and Inspector do not in any wayintend to benefit said seller or the real estate agents directly or indirectly through this Agreement or inspection report.Client agrees to indemnify, defend, and hold Inspector harmless from any third party claims arising out of Client’sunauthorized distribution of the inspection report.ATTORNEY’S FEES: The prevailing party in any dispute arising out of this agreement, the inspection, or report(s)shall be awarded all attorney’s fees, arbitrator and other costs.SEVERABILITY: Client and Inspector agree that should a Court of Competent Jurisdiction determine and declarethat any portion of this contract is void, voidable or unenforceable, the remaining provisions and portions shall remainin full force and effect.DISPUTES: Client understands and agrees that any claim for failure to accurately report the visually discernibleconditions at the Subject Property, as limited herein above, shall be made in writing and reported to the Inspectorwithin ten (10) business days of discovery. Client further agrees that, with the exception of emergency conditions,Client or Client’s agents, employees or independent contractors, will make no alterations, modifications or repairs tothe claimed discrepancy prior to a reinspection by the Inspector. Client understands and agrees that any failure tonotify the Inspector as stated above shall constitute a waiver of any and all claims for said failure to accurately reportthe condition in question.
LIMITATION ON LIABILITY
INSPECTOR’S LIABILITY FOR MISTAKES OR OMISSIONS IN THIS INSPECTION REPORT IS LIMITEDTO A REFUND OF THE FEE PAID FOR THIS INSPECTION AND REPORT. THE LIABILITY OFINSPECTOR’S PRINCIPALS, AGENTS, AND EMPLOYEES IS ALSO LIMITED TO THE FEE PAID. THISLIMITATION APPLIES TO ANYONE WHO IS DAMAGED OR HAS TO PAY EXPENSES OF ANY KINDBECAUSE OF MISTAKES OR OMISSIONS IN THIS INSPECTION AND REPORT. THIS LIABILITYLIMITATION IS BINDING ON CLIENT AND CLIENT’S SPOUSES, HEIRS, PRINCIPALS, ASSIGNS ANDANYONE ELSE WHO MAY OTHERWISE CLAIM THROUGH CLIENT. CLIENT ASSUMES THE RISK OFALL LOSSES GREATER THAN THE FEE PAID FOR THE INSPECTION. CLIENT AGREES TOIMMEDIATELY ACCEPT A REFUND OF THE FEE AS FULL SETTLEMENT OF ANY AND ALL CLAIMSWHICH MAY EVER ARISE FROM THIS INSPECTION.Client understands that if Client wants an inspection WITHOUT A LIMIT ON LIABILITY TO A REFUND OF THEFEE PAID for the inspection, Client may pay an additional fee to receive a report without the limitation.I have read and agree to the above Scope of Inspection.
Client or representative Pride Home Inspector
Date: 12/13/2005 Date: 12/13/2005Please make checks payable to Pride Home Inspections. Received: Check
PROPERTY ANALYSIS REPORTPride Home Inspections13015 Branscomb RoadHuntsville, AL 35803
Present at inspection: Owner Buyer's Agent Buyer Seller's Agent
Tenant Builder Representative
Weather Conditions: Sunny (80°) Vacant Occupied New Construction
SUMMARY OF INSPECTION
The inspection resulted in the following summarized items (the locations are listed as viewed from the street facingthe property):
It is important to read this report in its entirety to fully understand all information obtained.• A home inspection is not a warranty. Appliances ,Heating and cooling systems, and other mechanicalsystems do fail suddenly and without notice. Purchasing a home warranty can be a good investment.
•
Items noted in the summary are not of equal importance. Safety issues, structural items and the functioning ofa home's major mechanical systems are more important. Some items may be less significant.
•
Personal possessions limited visual inspection.•
EXTERIOR• Rotten trim boards noted on one window sil. Recommend repair to prevent water infiltration. (See Figure 4.0in the Appendix)
•
Failed window seal noted at rear door. Condensation noted between the window panes. (See Figure 5.0 in theAppendix)
•
Damaged/ rotten siding noted at north side of home. Recommend repair as needed. (See Figure 3.0 in theAppendix)
•
The safety reverse for the garage door does not reverse on contact. Recommend repairs for safety.• Broken springs noted on hinges for one piece garage door. Recommend repairs. (See Figure 6.0 in theAppendix)
•
ROOF• Noted cracking and general deterioration of rubber gaskets around plumbing vents. Recommend replacinggaskets in order to prevent water entry. (See Figure 1.0 in the Appendix)
•
Noted hole in shingle on front side of roof above garage door. Recommend sealing hole to prevent waterinfiltration. (See Figure 2.0 in the Appendix)
•
Debris noted in gutters. Recommend cleaning for proper operation.•
ELECTRICAL• Cable clamps missing at electrical box under deck. Cable clamps protect the cable connection from beingpulled apart , help protect the insulation from nicks and seal the box's hole. (See Figure 14.0 in the Appendix)
•
Nicked wires noted at circuit breaker at main panel. Also noted overheat/singe marks on adjacent wiring .Recommend further evaluation and repair by licensed electrician prior to close. (See Figure 13.0 in theAppendix)
•
Circuit breakers are not labled inside main panel/sub panel box.• Open splices noted at attic. All electrical splices should be contained inside an electrical box for safety. (SeeFigure 12.0 in the Appendix)
•
Loose junction box noted at attic fan. Also noted splices not contained inside this box. Recommend licensedelectrician repair as needed for safety. (See Figure 15.0 in the Appendix)
•
No ground fault circuit protection noted at Kitchen. Not required at time of construction. Recommend addingfor safety upgrade.
•
Reverse polarity noted on the electrical outlet in cabinet under kitchen stove. Recommend repairs for safety.(See Figure 11.0 in the Appendix)
•
Wire clamp missing on garbage disposal. Recommend repair for safety. (See Figure 10.0 in the Appendix)• No cover plate noted on electrical outlet at garage.• Doorbell is inoperative.•
PLUMBING• Excessive water pressure noted. Water pressure was 100, PSI when tested at the outside hose bib. Maximumpressure should be 80 PSI. Recommend installing a pressure−reducing valve to reduce the water pressurebelow 80 PSI.
•
Temperature pressure relief line for the hot water heater incorrectly terminates in the crawl space.Recommend extending the termination point to the exterior. (See Figure 22.0 in the Appendix)
•
Drain line under the master bathtub was not connected to the main drain line. Recommend licensed plumberrepair as needed. (See Figure 7.0 in the Appendix)
•
Trap leak noted under hall bath sink. Repair as needed. (See Figure 8.0 in the Appendix)•
HEATING SYSTEM• Gas vent pipe in attic was joined incorrectly at the bend near roof line. Duct tape is not an appropriatesubstitute for type b vent pipe. Recommend licensed HVAC technician make repairs as needed for safety.(See Figure 17.0 in the Appendix)
•
Branch duct has fallen off main trunk line in crawl space. Recommend Repair for improved energyefficiency. (See Figure 23.0 in the Appendix)
•
Recommend replacing air filters for energy efficiency.•
COOLING SYSTEM• The ground mounted air conditioning unit does not cool properly. A 10−12 degree temperature drop wasnoted. Recommend heating/air−conditioning contractor evaluate issues noted.
•
Missing/damaged insulation noted on large refrigerant line for ground mounted air conditioning unit.Recommend repairs for energy efficiency. (See Figure 24.0 in the Appendix)
•
BATHROOM REMARKS• Loose toilet noted in hall bath. Loose at floor. Recommend repairs to ensure water tightness.• Toilet lid loose in master bath.•
INTERIOR• Water stain noted on ceiling in guest bedroom. This stain is directly below the damaged plumbing vent on theroof. (See Figure 9.0 in the Appendix)
•
Recommend minor adjustment to Master bedroom and front office doors. Doors rub on top/side/bottom.• Recommend strike plate adjustment to kitchen door for proper operation• Windows do not open at several locations. Recommend repairs for safety and egress.•
ATTIC• Large squirrel nest in attic. Recommend removal of nest and repair of any holes to prevent any further entry.(See Figure 18.0 in the Appendix)
•
Insulation in attic minimal. Heavy squirrel traffic has compressed fiberglass insulation. Suggest addinginsulation to approximately R−30 to improve energy efficiency. (See Figure 19.0 in the Appendix)
•
Out of place insulation noted inside attic. Recommend repairs for energy efficiency. (See Figure 16.0 in theAppendix)
•
CRAWL SPACE• Dryer vent incorrectly terminated in the crawl space. Recommend re−routing to an exterior location. (SeeFigure 21.0 in the Appendix)
•
Fungal growth noted on subfloor under the front door area. Water appears to be penetrating wall aboveduring heavy rains. Critical to keep the gutters clean. Recommend further evaluation by a mold remediationexpert prior to close.
•
EXTERIOR
Exterior Doors Satisfactory See Remarks
Windows andSkylights Satisfactory See Remarks
Exterior WallCovering
Location* Materials
Front: Fibrous siding Satisfactory
Left: Fibrous siding Satisfactory
Right: Fibrous siding Satisfactory
Rear: Fibrous siding Satisfactory
No cracks found Common cracks Major cracks
*Location of exterior walls as viewed from street toward property
Exterior Trim Wood Metal Stucco Other Satisfactory
Chimney Brick Metal Block Fibrous siding Satisfactory
Spark Screen: Present Not Present N/A
Garage/Carport Garage Carport Attached Detached N/A Satisfactory
Fire rated sheet rock was removed from garage/ceiling for attic access
Door operator Operating Not operating Safety Reverse N/A
Fire rated entrance door from garage should be self closing and self latching for safety
Pet door installed in fire rated door between living area and garage compromising its fireprotection
RemarksChimney flu not inspected. Unable to view interior .• Eaves soffits and fascia are constructed of %. Condition is satisfactory.• See Summary Remarks•
ROOFING
Roof CoveringType
Concrete tile Clay tile Asphalt composition Rolled asphalt Satisfactory
Wood Shingles Built up Other
How Observed: Walked on roof
Unable to fully view entire roof due to unsafe access or possible damage to the roofing
Roof Leaks Some signs Extensive None observed
Cracked/Broken/Missing Tiles Some signs Extensive None observed N/A
Worn/MissingShingles Some signs Extensive None observed N/A
Flashing Aluminum Galvanized Vinyl Satisfactory
N/A
Gutters andDownspouts
Aluminum Galvanized Vinyl Satisfactory
Plastic N/A
RemarksSee Summary Remarks•
GROUNDS (Page 1)
Grading General Grading Satisfactory
Sidewalk andWalkway Concrete Brick Common cracks Other Satisfactory
Driveway Concrete Asphalt Common cracks Other Satisfactory
N/A
Window Wells Metal Brick Concrete Other Satisfactory
N/A
Retaining Wall Block Brick Stone Concrete Other Satisfactory
Mortared joints Dry Weep holes N/A
Sprinkler System Operating Not operating Random Testing Satisfactory
Type: Manual Automatic
Location: Front Rear Other
N/A
Trees and Shrubs Monitor tree limbs/vines near roof edge to extend roof life Satisfactory
Vegetation close to exterior surface blocking full view N/A
Remarks n/a
GROUNDS (Page 2)
Fencing Block Wood Metal Other Satisfactory
Stucco facing Concrete Interlock N/A
Front Porch Floor: Concrete Wood Other Satisfactory
N/A
Patio #1 Floor: Concrete Wood Brick
Stone Other Satisfactory
Cover: Open Design Enclosed Covered roof N/A
Patio #2 Floor: Concrete Wood Brick
Stone Other Satisfactory
Cover: Open Design Enclosed Covered roof N/A
Deck / Balcony Floor: Wood Metal Other Satisfactory
Cover: Open Design Covered roof Enclosed N/A
Inspection of the sprinkler system is limited to examination of readily accessible valves and thevisual inspection of coverage. Sprinklers are tested in manual mode only. Automatic timers arebeyond the scope of this inspection.
Adjust or modify sprinklers to avoid wetting the houseLocation:
Wood to earth contact noted Location:
Remarks n/a
ELECTRICAL
ServiceEntrance
Cable
Capacity: 200 Amps 120−240 Volts Satisfactory
Service line entrance: Overhead Underground
Conductor material: Aluminum Copper Not Visible
Main PanelBox
Location: Garage Grounded Satisfactory
Fuses Circuit breakers
Subpanel Location: n/a
Capacity of main current disconnect: 200 Amps
Termination of ground is not traceable.
Circuitsand
Conductors
Wiring: Copper Aluminum Satisfactory
GFCI: Exterior Garage Kitchen Bathroom(s) Basement N/A
Arc: Operating Breaker does not trip when tested N/A
Outlets,Fixtures
And Switches
Random Testing Reverse polarity Open ground Satisfactory
Personal belongings prevent testing of all outlets and switches
See maintenance remarks on GFCI for increased safety enhancements
SmokeDetectors Operating Not Operating Inaccessible N/A
RemarksOverhead electrical service is satisfactory.• Wire type used in home is romex.• See Summary Remarks•
PLUMBING
Water Service Public Private Satisfactory
Entrance Pipe Copper Galvanized Brass Plastic PVC Unknown
Pipes Copper Galvanized Plastic Other Satisfactory
Water Pressure: 100 psiTested atInterior
Tested atExterior Satisfactory
Leaks:Noneobserved
Hose Bibs: Operating Not Operating Not Tested
Drain / Waste /Vent / Pipes
Plastic Copper Galvanized Lead Cast Iron Other
Slow drain Leaks None observed
Waste Disposal: Public Private Septic System
Water Heater 1 − Capacity:50 Gallon Satisfactory
Age: 4 N/A
Make: Rheem
Gas Electric
Relief Valve Extension
2 − Capacity: Satisfactory
Age: N/A
Make:
Gas Electric
Relief Valve Extension
Water Conditioning Water conditioning equipment was present. We cannot determine the effectiveness orproper operability of this equipment within the time and testing parameters of a homeinspection.
RemarksWater meter shut off is located in the front yard near street.• See Summary Remarks•
HEATING
Heating System Forced air furnace Heat pump Satisfactory
Baseboard Other N/A
No. 1 Capacity:Data tag not legible No. 4 Capacity:n/a
Make:American Standard Make:
No. 2 Capacity:n/a No. 5 Capacity:n/a
Make: Make:
No. 3 Capacity:n/a No. 6 Capacity:n/a
Make: Make:
When turned on by thermostat Fired Did not fire
Fuel Supply Gas Electric Propane Other
Heat Exchanger Partially observed Not visible; enclosed combustion N/A
Distribution Ductwork Heat source in each room: Yes No
Filter Washable Disposable Electronic Electrostatic N/A
SupplementaryHeating Location: Type:
Comprehensive evaluation of the combustion compartment and heat exchanger is specificallyexcluded from the inspection due to visibility and design limitations of the furnace.Comprehensive evaluation can only be obtained by dismantling or specialized testing. Yearlyinspection and maintenance by a heating contractor is recommended.
RemarksGas lines are steel pipe.• Gas shutoff is located at north side of home.• See Summary Remarks•
Air Conditioning (Cooling)
Cooling Central air Room units Heat pump Evaporative cooler Satisfactory
Electric compressor Ductwork N/A
No. 1 Capacity:3 ton No. 4 Capacity:n/a
Make:American Standard Make:
No. 2 Capacity:n/a No. 5 Capacity:n/a
Make: Make:
No. 3 Capacity:n/a No. 6 Capacity:n/a
Make: Make:
Tested Not tested
Yearly inspection and maintenance by an air conditioning contractor is recommended.
Install condensation drain hose over roof edge to extend roof life
Temperature drops:
No 1: 10−11 No 2: n/a No 3: n/a
(Normal temperature drop ranges from 18−22 F degrees)
RemarksSee Summary Remarks•
BATH
Bathroom #1 Location: Master Bath
Built in Tub Tub/Shower Stall Spa Tub Bidet Steam Unit
Toilet Sink Vanity Window Fan Spa Tub/Shower
Wall covering: Drywall
Floor covering: Sheetgoods
Separations noted in grout seams in the bathroom tub/shower. Recommend maintenance toensure water tightness.
Leaks: Some signs None observed
Bathroom #2 Location: Hall Bath
Built in Tub Tub/Shower Stall Spa Tub Bidet Steam Unit
Toilet Sink Vanity Window Fan Spa Tub/Shower
Wall covering: Drywall
Floor covering: Sheetgoods
Separations noted in grout seams in the bathroom tub/shower. Recommend maintenance toensure water tightness.
Leaks: Some signs None observed
Bathroom #3 Location: n/a
Built in Tub Tub/Shower Stall Spa Tub Bidet Steam Unit
Toilet Sink Vanity Window Fan Spa Tub/Shower
Wall covering:
Floor covering:
Separations noted in grout seams in the bathroom tub/shower. Recommend maintenance toensure water tightness.
Leaks: Some signs None observed
Bathroom #4 Location: n/a
Built in Tub Tub/Shower Stall Spa Tub Bidet Steam Unit
Toilet Sink Vanity Window Fan Spa Tub/Shower
Wall covering:
Floor covering:
Separations noted in grout seams in the bathroom tub/shower. Recommend maintenance toensure water tightness.
Leaks: Some signs None observed
RemarksSee Summary Remarks•
KITCHEN
Cabinets andCountertops Satisfactory
Sink Plumbing leaks: Some signs None observed Satisfactory
Dishwasher Operating Not operating Satisfactory
Airgap device No Airgap method provided N/A
Rusted racks noted inside dishwasher
Range/Oven Operating Not operating Gas Electric Satisfactory
N/A
Note: Testing the oven in self−cleaning mode is beyond the scope of this inspection.
Exhaust /Recirculation Fan
Operating Not operating Satisfactory
N/A
OtherAppliances
Disposal: N/A Operating Not operating Satisfactory
Microwave: N/A Operating Not operating Satisfactory
Compactor: N/A Operating Not operating Satisfactory
Free standing appliances such as washers, dryers, and refrigerators are not part of thisinspection.
Floor Sheetgoods Tile Wood Other Satisfactory
Remarks n/a
INTERIOR
FloorCoverings
Tile Sheetgoods Wood Satisfactory
Wall to wall carpet Not fully visible Other
Walls Plaster Drywall Masonry Common Cracks Other Satisfactory
Ceilings Plaster Drywall Wood Common Cracks Other Satisfactory
Stairs/Railings N/A
Satisfactory
Fireplace Wood burning Gas Enclosed gas appliance Satisfactory
Free−standing Other N/A
Flue liner Damper: Operating Not operating
Recommend a damper stop on fireplace damper for safety
Location:
Interior Doors Hollow core Raised panel Solid core Satisfactory
Windows Sliding Single hung Casement Fixed
Metal Wood Double hung Other
Dual paned Vinyl Single pane
Security Bars: Present Not present Safety releases
Become familiar with operation of safety releases on security bars.
RemarksSee Summary Remarks•
ATTIC
Access How observed: Walked Not observed Satisfactory
Scuttlehole Pulldown Door No access N/A
Inspection limited to view from access. Not all areas were completely visible.
MoistureStaining
Some signs Extensive None observed
Condensation
Storage Heavy Light Floored Not floored
Insulation None Batts Fill Avg. Inches: 2−3 Satisfactory
Installed in: Rafters Floor Approx. R Rating: 5−8 N/A
Ventilation Window(s) Attic fan Whole house fan Satisfactory
Ridge vent Soffit vent Turbine N/A
Gable end louvers Roof vents
Framing Cracked/broken/sagging rafters Satisfactory
Bracing Cracked/broken/sagging bracing Satisfactory
RemarksCeiling structure is 2x6 16 on center• Atttic insulation is blown fiberglass.• See Summary Remarks•
STRUCTURAL
Type ofbuilding
Single Family Duplex/Patio home Townhouse Condominium Other
Wood Frame Masonry Frame Metal Frame Other
Gable Roof Mansard Roof Hip Roof Flat Roof Other
Structure Foundation: Poured concrete slab Sub floor Other
Post Columns: Steel Masonry Wood Concrete
None Not visible
Floor Structure: 2 x 10 floor joist &masonry footing
Wall Structure: Wood frame
Roof Structure: 2x6
Prefabricated trusses
Minor cracking in concrete flooring is common and is not considered to be structurally significant. Slabwas partially visible at exterior perimeter
Remarks n/a
BASEMENT (or lower level)
Basement Full Partial None Slab on grade N/A
Walls: Finished Partitioned Ceiling:
Limited visibility due to extensive basement storage
Floor Concrete Carpeting Sheetgoods Other Satisfactory
Floor Drain Tested Not tested Satisfactory
N/A
Crawl Space Wood to earth contact How observed: Physically entered N/A
Floor: Concrete Dirt Other
Dampness: Some signs Extensive None observed
Vapor barrier Insulation Ventilation
RemarksSee Summary Remarks•
Appendix:
Figure 1.0:Plumbing vent
Noted cracking and general deterioration of rubbergaskets around plumbing vents. Recommend replacinggaskets in order to prevent water entry.
Figure 2.0:Hole in shingle
Noted hole in shingle on front side of roof abovegarage door. Recommend sealing hole to prevent waterinfiltration.
Figure 3.0:Rotten siding
Damaged/ rotten siding noted at north side of home.Recommend repair as needed.
Figure 4.0:Sil rotten
Rotten trim boards noted on one window sil.Recommend repair to prevent water infiltration.
Appendix:
Figure 5.0:Seal broken
Failed window seal noted at rear door. Condensationnoted between the window panes.
Figure 6.0:Garage door spring
Broken springs noted on hinges for one piece garagedoor. Recommend repairs.
Figure 7.0:Bath drain
Drain line under the master bathtub was not connectedto the main drain line. Recommend licensed plumberrepair as needed.
Figure 8.0:Trap leak
Trap leak noted under hall bath sink. Repair as needed.
Appendix:
Figure 9.0:Water stain
Water stain noted on ceiling in guest bedroom. Thisstain is directly below the damaged plumbing vent onthe roof.
Figure 10.0:Garbage disposal
Wire clamp missing on garbage disposal. Recommendrepair for safety.
Figure 11.0:Hot neutral reverse
Reverse polarity noted on the electrical outlet incabinet under kitchen stove. Recommend repairs forsafety.
Figure 12.0:Splice in attic
Open splices noted at attic. All electrical splices shouldbe contained inside an electrical box for safety.
Appendix:
Figure 13.0:Nicked wire
Nicked wires noted at circuit breaker at main panel.Also noted overheat/singe marks on adjacent wiring .Recommend further evaluation and repair by licensedelectrician prior to close.
Figure 14.0:Box under deck
Cable clamps missing at electrical box under deck.Cable clamps protect the cable connection from beingpulled apart , help protect the insulation from nicks andseal the box's hole.
Figure 15.0:Attic fan
Loose junction box noted at attic fan. Also notedsplices not contained inside this box. Recommendlicensed electrician repair as needed for safety.
Figure 16.0:Attic insulation
Out of place insulation noted inside attic. Recommendrepairs for energy efficiency.
Appendix:
Figure 17.0:Gas vent
Gas vent pipe in attic was joined incorrectly at the bendnear roof line. Duct tape is not an appropriate substitutefor type b vent pipe. Recommend licensed HVACtechnician make repairs as needed for safety.
Figure 18.0:Squirrel nest
Large squirrel nest in attic. Recommend removal ofnest and repair of any holes to prevent any furtherentry.
Figure 19.0:Insulation compressed
Insulation in attic minimal. Heavy squirrel traffic hascompressed fiberglass insulation. Suggest addinginsulation to approximately R−30 to improve energyefficiency.
Figure 20.0:Fungus
Fungal growth noted on subfloor under the front doorarea. Water appears to be penetrating wall above duringheavy rains. Critical to keep the gutters clean.Recommend further evaluation by a mold remediationexpert prior to close.
Appendix:
Figure 21.0:Dryer vent
Dryer vent incorrectly terminated in the crawl space.Recommend re−routing to an exterior location.
Figure 22.0:TPR line
Temperature pressure relief line for the hot waterheater incorrectly terminates in the crawl space.Recommend extending the termination point to theexterior.
Figure 23.0:Duct
Branch duct has fallen off main trunk line in crawlspace. Recommend Repair for improved energyefficiency.
Figure 24.0:Suction line
Missing/damaged insulation noted on large refrigerantline for ground mounted air conditioning unit.Recommend repairs for energy efficiency.