The Hartford Steam Boiler Inspection and Insurance CompanyThe Hartford Steam Boiler Inspection and Insurance Company
Preventing Equipment
Failures
BoilersElectrical Distribution Systems
Air Conditioning Equipment
![Page 2: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/2.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Any Questions?
Then let’s get started!
![Page 3: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/3.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Preventing Equipment Failures
![Page 4: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/4.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Boiler Maintenance
![Page 5: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/5.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
What is a boiler?
A closed vessel in which water is heated, steam is generated, or steam is superheated for use external to itself by the application of heat.
![Page 6: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/6.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Boiler Categories
Power BoilerHigh Temperature Hot
Water BoilerHeating Boiler
![Page 7: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/7.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Watertube BoilersComponents: Steam drum Water (mud)
drum Tubes
![Page 8: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/8.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Watertube Boilers
![Page 9: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/9.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Firetube Boilers
![Page 10: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/10.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Firetube Boilers
Components: Shell (Drum) Tube Sheets,
Front & Rear Tubes (Flues) Furnace Stays (Stay
Bolts)
![Page 11: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/11.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Firetube Scotch Marine
![Page 12: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/12.jpg)
The Hartford Steam Boiler Inspection and Insurance CompanyThe Hartford Steam Boiler Inspection and Insurance Company
What could possibly go wrong with my
boiler?
Let’s take a look at some typical boiler
failures!
![Page 13: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/13.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Major Causes of Boiler Failures
Low WaterPoor MaintenanceFailure of Controls and
Safety Devices
![Page 14: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/14.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Low Water
Results in over temperature condition
Can cause extensive damage to boiler
Or
Catastrophic failure of the boiler
![Page 15: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/15.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 16: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/16.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 17: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/17.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 18: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/18.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Poor Maintenance
![Page 19: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/19.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 20: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/20.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 21: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/21.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 22: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/22.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Failure of Controls and Safety Devices
![Page 23: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/23.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 24: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/24.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 25: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/25.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 26: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/26.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 27: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/27.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 28: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/28.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 29: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/29.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 30: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/30.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Preventing Boiler Failures
Proper OperationProper Maintenance It’s all up to you!
![Page 31: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/31.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Boiler Operation
Prepare the boiler for operation
Starting the boilerRegular operationControls and safety valvesFeedwater treatment
![Page 32: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/32.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Boiler Logs
Why use themWhat to includeHow to use them
![Page 33: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/33.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Boiler Codes
ASME Boiler & Pressure Vessel Code
ASME Controls and Safety Devices
National Board Inspection Code
Jurisdictional Rules
![Page 34: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/34.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Jurisdictional Rules
Inspection Frequencies Inspection types Installation requirementsRules for repair
![Page 35: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/35.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
HousekeepingSafetyFire PreventionCombustibles
•paint, oil, gas and cleaning productsFlammables
•wood, paper and cardboard •keep at least 8 to 10 feet from the
boilerEmergency Access
![Page 36: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/36.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Controls & Safety Devices
Maintain control over boiler operation
Monitor operating conditionsProtect boiler from failure
![Page 37: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/37.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Controls and Safety Devices
Controls and safety devices are installed on boilers to monitor, indicate, regulate, or control:
• Pressure• Temperature• Water Level• Combustion• Auxiliary Equipment
![Page 38: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/38.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Pressure GagesVisual display of
operating pressures.Most accurate in
their mid-range.Dial range:
•Power Boilers: 1.5 – 2 times lowest safety valve setting
![Page 39: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/39.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Control Water Seals Most controls are
designed to be subjected to water pressure.
A “loop” or trap is installed to protect controls from direct contact with steam.
Condensate fills the lines during normal operation.
![Page 40: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/40.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Siphon Loops
![Page 41: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/41.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Safety Valve Body Seat Disc Stem Spring Blow-Down Ring Huddling
Chamber
![Page 42: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/42.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Low Water Fuel Cutoffs
![Page 43: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/43.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Low Water Fuel Cutoffs
![Page 44: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/44.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Low Water Fuel Cutoffs
![Page 45: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/45.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Low Water Fuel Cutoffs
![Page 46: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/46.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Conclusion
Follow proper operating procedures
Regular maintenanceBe preparedAbove all …Work Safely!
![Page 47: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/47.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Electrical Maintenance
![Page 48: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/48.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Electrical Distribution System
![Page 49: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/49.jpg)
Common Electrical Failures
“Figure illustrates specific causes of electrical failures and the individual contribution of each cause. This list is based upon twenty years of HSB claims data.”
![Page 50: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/50.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Preventing Electrical Failures
CleanCool
DryTight
![Page 51: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/51.jpg)
Yes
No
Yes
No
Did you observe any combustible material in the electrical room?
![Page 52: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/52.jpg)
![Page 53: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/53.jpg)
Yes
No
Changes to electrical system
Such as loads added or relocated or equipment upgraded or replaced.
Yes
No
Changes to electrical system
Such as loads added or relocated or equipment upgraded or replaced.
Have there been any changes to the electrical system in the last three (3) years?
![Page 54: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/54.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 55: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/55.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 56: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/56.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 57: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/57.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 58: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/58.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 59: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/59.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 60: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/60.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 61: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/61.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 62: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/62.jpg)
![Page 63: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/63.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 64: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/64.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
![Page 65: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/65.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Everything “Looks Okay”
![Page 66: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/66.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
…However!
![Page 67: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/67.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Infrared Thermographic
Imaging Detects Hot
Spots Dirty, Loose,
Oxidized, or Corroded Connections.
Finds Phase Imbalance Problems.
Finds Undersized Wiring Problems.
![Page 68: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/68.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Surge ProtectionSurge Protection Device (SPD)Transient Voltage Surge
Suppressor (TVSS)Diverts surge currents to
groundLimits the voltage across the
terminals of the equipment being protected
![Page 69: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/69.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
SPD - Zones of Protection
Zone 1: Service Entrance EquipmentIntercept surges before they enter the building
Zone 2: Distribution PanelSecond line of defense for each panel supplying critical or sensitive electronic equipment Protects against internally generated surges
Zone 3: Locally at Each Piece of EquipmentThird line of defenseProtects against internally generated surges
Grounding System is key to protection
![Page 70: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/70.jpg)
The Hartford Steam Boiler Inspection and Insurance CompanyThe Hartford Steam Boiler Inspection and Insurance Company
Above all else…..
SAFETY FIRST!
![Page 71: Preventing Equipment Failures](https://reader037.fdocuments.us/reader037/viewer/2022103100/56813217550346895d987387/html5/thumbnails/71.jpg)
The Hartford Steam Boiler Inspection and Insurance Company
Have a Safe Trip Home!