Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection
-
Upload
general-air-products-inc-fire-protection-division -
Category
Business
-
view
456 -
download
0
description
Transcript of Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection
![Page 1: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/1.jpg)
The Leading Manufacturer of Air Compressors The Leading Manufacturer of Air Compressors Designed for All Types of Dry Pipe Sprinkler SystemsDesigned for All Types of Dry Pipe Sprinkler Systems
Quality& ServiceSince 1936
![Page 2: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/2.jpg)
The Leading Manufacturer of Air Compressors The Leading Manufacturer of Air Compressors Designed for All Types of Dry Pipe Sprinkler SystemsDesigned for All Types of Dry Pipe Sprinkler Systems
Proud Member of
![Page 3: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/3.jpg)
Dry Air Pac For Critical Applications
•Basics of Compressed Air
•Ice Plugs
•Primary Components
•A Closer Look At The Integrated Control Panel
•Inside the Control Panel
•Troubleshooting
![Page 4: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/4.jpg)
Dry Air Pac For Critical Applications
Basics of Compressed Air
![Page 5: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/5.jpg)
Basics of Compressed Air
Air Compressors
Compressed Air: Atmospheric air compressed by a mechanical device to increase its pressure.
• Compressed air is an energy source – often considered the 4th utility.
Moisture
Dewpoint: Temperature at which moisture will occur.
• Example: 75ºF, 75 RH, 25 CFM = 4.5 gallons of water per day
Air Dryers
• Refrigerated, 30ºF – 39ºF dewpoint
• Chemical, down to -100ºF dewpoint
![Page 6: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/6.jpg)
Basics of Compressed Air
Compression Ratio
It takes 7.8 Ft3 of atmospheric air (14.69 PSIA) to make one actual cubic foot of air at 100 psig. (psia / atmosphere)
![Page 7: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/7.jpg)
Basics of Compressed Air
Compression Ratio
![Page 8: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/8.jpg)
Dry Air Pac For Critical Applications
Ice Plugs
![Page 9: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/9.jpg)
The Problem - Ice Plugs
• Ice Plug formation causes partial and eventually complete blockage of the dry-pipe system.
•Factory Mutual, after several years of study, found that 50% to 70% of the dry pipe systems inspected were plagued with Ice Plug problems.
![Page 10: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/10.jpg)
The Cause - Ice Plugs
• Evaporating Priming Water
• Water left in the lines after annual trip test.
• The Major Culprit, moisture laden compressed air meeting freezing temperatures in the Dry Pipe System.
(Contrary to popular belief, using air from the freezer room for the dry pipe systemWill not solve the ice plug problem)
![Page 11: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/11.jpg)
Dry Air Pac For Critical Applications
The Solution …
• Freezer Rooms
• Cold Storage
• Parking Garages
• Potential MIC Effected Areas
• Anywhere Dry Air is Essential
![Page 12: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/12.jpg)
Dry Air Pac For Critical Applications
Primary Components
![Page 13: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/13.jpg)
FM Approval eliminates requirement to connect air intake to freezer room.
![Page 14: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/14.jpg)
Industrial Duty Compressor Pump
![Page 15: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/15.jpg)
Removable Intake Filter with Weatherhood
![Page 16: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/16.jpg)
Compact Air Cooled Aftercooler
![Page 17: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/17.jpg)
Pressure Switch
![Page 18: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/18.jpg)
Check Valve
![Page 19: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/19.jpg)
ASME / NB Tank (30 Gallons)
![Page 20: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/20.jpg)
Integrated Electronic Drain
![Page 21: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/21.jpg)
Vibration Isolation Pads
![Page 22: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/22.jpg)
Prefilter with Differential Pressure Gauge
![Page 23: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/23.jpg)
SAEJ10 Towers
![Page 24: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/24.jpg)
Purge Pressure Gauge
![Page 25: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/25.jpg)
Oversized Mufflers for quiet discharges and low backpressure
![Page 26: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/26.jpg)
UL Listed / FM Approved Air Maintenance Device
![Page 27: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/27.jpg)
Combination Afterfilter & Regulator
![Page 28: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/28.jpg)
Dry Air Outlet
![Page 29: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/29.jpg)
Dewpoint Test Port
![Page 30: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/30.jpg)
Dry Air Pac Test Kit
gives visual indication if moisture is present (Available as option).
![Page 31: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/31.jpg)
Fully Integrated Control Panel ensures package performs to specification.
![Page 32: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/32.jpg)
A Closer Look at the Fully Integrated Control
Panel
![Page 33: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/33.jpg)
Fully Integrated Control Panel – Performance Lights
![Page 34: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/34.jpg)
Fully Integrated Control Panel –
•Reset Button
•Control Panel Power
•Incorporated Automatic Drain Controls
![Page 35: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/35.jpg)
Fully Integrated Control Panel – Hour Meter
![Page 36: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/36.jpg)
Fully Integrated Control Panel – Receiver Pressure Gauge
![Page 37: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/37.jpg)
Fully Integrated Control Panel – Left Tower Pressure Gauge
![Page 38: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/38.jpg)
Fully Integrated Control Panel – Right Tower Pressure Gauge
![Page 39: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/39.jpg)
Fully Integrated Control Panel – Outlet Pressure Gauge
![Page 40: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/40.jpg)
Inside the Control Panel
![Page 41: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/41.jpg)
Inside the Control Panel – Magnetic Line Starter (NEMA Rated)
![Page 42: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/42.jpg)
Inside the Control Panel – Control Circuit Transformer (with primary and secondary fusing)
![Page 43: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/43.jpg)
Inside the Control Panel – Cam Timer
![Page 44: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/44.jpg)
Inside the Control Panel – Solenoid Valves
![Page 45: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/45.jpg)
Dry Air Pac For Critical Applications
Troubleshooting
![Page 46: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/46.jpg)
Troubleshooting the Dry Air Pac
Problem
Poor Dewpoint Performance
Probable Cause
Low pressure on desiccant dryer
Excessive water or oil in dryer
Low purge flow
Desiccant contamination
High inlet temp. to dryer
Solution
Reset Pressure Switch .
Check coalescing filter & automatic drain operation
Check purge pressure setting
Check the date of the last desiccant change. Recommended change every 1 to 2 years
Clean aftercooler
![Page 47: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/47.jpg)
Troubleshooting the Dry Air Pac
Problem
Excessive Pressure Drop
Probable Cause
Switching valve failure . .
Desiccant breakdown
Clogged filters
Solution
Check tower-operating sequence to verify and identify which valves are operating.
Change desiccant
Change filter elements
![Page 48: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/48.jpg)
Troubleshooting the Dry Air Pac
Problem
Switchover Failure
Probable Cause
Electric power loss . .
Solenoid valve failure
Solution
Turn dryer off; check connections to cam timer and inlet to unit.
Check valve operative sequence. Replace valve.
![Page 49: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/49.jpg)
Troubleshooting the Dry Air Pac
Problem
Repressurization Failure or Purge Failure
Probable Cause
Purge flow control valve orifice clogged.
Failed check valve.
Purge exhaust solenoid valve failure.
Purge exhaust muffler clogged.
Solution
Clean or replace. .
Replace.
Turn dryer off, check connections to cam timer, inspect valve and solenoid, replace if necessary. .
Clean or replace.
![Page 50: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection](https://reader033.fdocuments.us/reader033/viewer/2022052909/559912bd1a28ab93798b4574/html5/thumbnails/50.jpg)
The Leading Manufacturer of Air Compressors The Leading Manufacturer of Air Compressors Designed for All Types of Dry Pipe Sprinkler SystemsDesigned for All Types of Dry Pipe Sprinkler Systems