Pressurization Unit
-
Upload
mohammed-hassan-mohiuddin-khan -
Category
Documents
-
view
212 -
download
0
Transcript of Pressurization Unit
-
7/30/2019 Pressurization Unit
1/17
NUMBER OF FLOORS ( N ) = 4 FLOOR
STAIRWELL WALL AREA = 139.4496FT
2PER FLOOR
EXTERIOR BUILDING WALL AREA = 18496.44FT
2PER FLOOR
OUTSIDE DESIGN TEMPERATURE = 115OF 574.67
OR
STAIRWELL DESIGN TEMPERATURE = 85OF 544.67
OR
Exterior building walls Tight N A/Aw 0.00021
Average Y Average
Loose N b
Very lose N
Stairwell walls Tight N A/Aw 0.00011
Average Y AverageLoose N b
STAIRWELL WALL HEIGHT = 12FT
PER FLOOR
THE
FOR
STAIR CASE PRESSURIZATION UNIT SOFTWA
-
7/30/2019 Pressurization Unit
2/17
-
7/30/2019 Pressurization Unit
3/17
-
7/30/2019 Pressurization Unit
4/17
-
7/30/2019 Pressurization Unit
5/17
-
7/30/2019 Pressurization Unit
6/17
-
7/30/2019 Pressurization Unit
7/17
-
7/30/2019 Pressurization Unit
8/17
-
7/30/2019 Pressurization Unit
9/17
-
7/30/2019 Pressurization Unit
10/17
-
7/30/2019 Pressurization Unit
11/17
-
7/30/2019 Pressurization Unit
12/17
-
7/30/2019 Pressurization Unit
13/17
-
7/30/2019 Pressurization Unit
14/17
-
7/30/2019 Pressurization Unit
15/17
-
7/30/2019 Pressurization Unit
16/17
880
CFM
DONE BY:EngineerHasan Kayed
MOUNT OF CFM
EACH FLOOR:
E
-
7/30/2019 Pressurization Unit
17/17
N: Numberof Floors = 4 Floor
As : Stairwell Wall Area = 139.4496FT
2PER FLOOR
Aw: Exterior Building Wall Area = 18496.44FT
2PER FLOOR
To: Outside Design Temperature = 115 OF 574.67 O R
Ts: Stairwell Design Temperature = 85OF 544.67
OR
Y: Stairwell Wall Height = 12FT
PER FLOOR
Max. design pressure differences when all stairwell doors are closed is 0.551 in of Water
The minimum aloowable pressure differences is 0.052 in of Water.
Using the leakage ratio for Table-1: Typical Leakage Areas for Walls and
an exterior building wall of Floors of Commercial Buildings
Average tightness from Wall Area Ratio
the table: Construction Element Tightness A/Aw
Abo = Aw x b Exterior building walls a-Tight 0.70x10-4
= 3.88 FT 2 b-Average 0.21x10-3
c-Loose 0.42x10-3
Using the leakage ratio for d-Very loose 0.13x10-2
stairwell wall of
Average tightness from Stairwell walls a-Tight 0.14x10-4
the table = As x b b-Average 0.11x10-3
= 0.02FT
2c-Loose 0.35x10
-3
The value of flow area between stairwell and building (per floor) equals the lekage area of the stairwell
wall plus the gaps around the closed doors ( 0.26 FT2 ), Asb = 0.02 .+ 0.26
= 0.28FT
2
The temperature factor B = 7.64 x ( 1/Ts - 1/To)= 0.00073 in.of Water
The pressure difference at the stairwell bottom is selected as Psbb = 0.080 in. of Water to
provide an extra degree of protection above the minimum allowable valueof0.052 in. of Water.
The pressure difference from stairwell to building at stairwell top Psbt is calculated by the equation:
Psbt = Psbb + [ ( B x Y x N ) / ( 1 + ( A sb / Abo )2
) ]
= 0.115 in. of Water
Thus, Psbt does not exceed the maximum aloowable pressure
The flow rate Q of pressurization air is calculated from the equation:
Q = 1740 x N x Asb x {[ (Psbt)3/2
- (Psbb)3/2
] / [ (Psbt)- (Psbb)
]
= 896 CFM
224 04.075571 220 230 220
305 05
STAIR CASE PRESSURIZATION UNIT CALCULATIONS