pren14339

24
EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM DRAFT prEN 14339 December 2001 ICS English version Underground fire hydrants, surface boxes and covers This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 192. If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom. Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and shall not be referred to as a European Standard. EUROPEAN COMMITTEE FOR STANDARDIZATION COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG Management Centre: rue de Stassart, 36 B-1050 Brussels © 2001 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. prEN 14339:2001 E

Transcript of pren14339

Page 1: pren14339

EUROPEAN STANDARD

NORME EUROPÉENNE

EUROPÄISCHE NORM

DRAFTprEN 14339

December 2001

ICS

English version

Underground fire hydrants, surface boxes and covers

This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 192.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations whichstipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other languagemade by translation under the responsibility of a CEN member into its own language and notified to the Management Centre has the samestatus as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice andshall not be referred to as a European Standard.

EUROPEAN COMMITTEE FOR STANDARDIZATIONC OM ITÉ EUR OP ÉEN DE NOR M ALIS AT IONEUROPÄISCHES KOMITEE FÜR NORMUNG

Management Centre: rue de Stassart, 36 B-1050 Brussels

© 2001 CEN All rights of exploitation in any form and by any means reservedworldwide for CEN national Members.

Ref. No. prEN 14339:2001 E

Page 2: pren14339

prEN 14339:2001 (E)

2

Foreword

This document has been prepared by CEN /TC 192, "Fire service equipment" the secretariat of whichis held by BSI.

This document is currently submitted to the CEN Enquiry.

This is one of a series of standards for fire hydrants.

No International Standard exists for Underground fire hydrants, surface boxes and covers.

This document has been prepared under a mandate given to CEN by the European Commission andthe European Free Trade Association, and supports essential requirements of EU the ConstructionProducts Directive (89/106/EEC).

For relationship with EU Directive(s), see informative annex ZA, which is an integral part of thisdocument.

According to the CEN/CENELEC Internal Regulations, the national standards organizations of thefollowing countries are bound to implement this document: Austria, Belgium, the Czech Republic,Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Netherlands,Norway, Portugal, Spain, Sweden, Switzerland and the United Kingdom.

Page 3: pren14339

prEN 14339:2001 (E)

3

Contents

Foreword ....................................................................................................................... .............................................. 2

Introduction ................................................................................................................... ............................................. 5

1 Scope......................................................................................................................... ..................................... 6

2 Normative references.......................................................................................................... ........................... 6

3 Definitions................................................................................................................... ................................... 6

4 Technical requirements........................................................................................................ ........................ 74.1 Dimensions .................................................................................................................. .................................. 74.2 Material.................................................................................................................... ..................................... 104.3 Obturator................................................................................................................... ................................... 104.4 Valve components............................................................................................................ ........................... 104.5 Spindle seals ............................................................................................................... ................................ 104.6 Potable water ............................................................................................................... ................................ 104.7 Pressures ................................................................................................................... .................................. 104.8 Spindle drive............................................................................................................... ................................. 114.9 Direction of closure........................................................................................................ ............................. 114.10 No of turns ................................................................................................................ ................................... 114.11 Torque ..................................................................................................................... ..................................... 114.12 Start of flow.............................................................................................................. .................................... 114.13 Inlet flanges .............................................................................................................. ................................... 114.14 Outlet connectors.......................................................................................................... .............................. 124.15 Draining................................................................................................................... ..................................... 124.16 Coatings ................................................................................................................... .................................... 124.17 Hydrants for non portable water systems .................................................................................... ............ 12

5 Performance requirements ...................................................................................................... .................. 125.1 Type test requirements...................................................................................................... ......................... 125.2 Production test requirements ................................................................................................ .................... 14

6 Test methods.................................................................................................................. ............................. 146.1 Safety...................................................................................................................... ...................................... 146.2 Flow ........................................................................................................................ ...................................... 146.3 Endurance................................................................................................................... ................................. 156.4 Failure torque .............................................................................................................. ................................ 156.5 Start of flow............................................................................................................... ................................... 156.6 Number of turns ............................................................................................................. ............................. 156.7 Valve seating ............................................................................................................... ................................ 156.8 Complete hydrant............................................................................................................ ............................ 156.9 Outlet connector............................................................................................................ .............................. 16

7 Evaluation of conformity ...................................................................................................... ...................... 167.1 General ..................................................................................................................... .................................... 167.2 Type testing ................................................................................................................ ................................. 167.3 Factory production control (FPC)............................................................................................ .................. 16

8 Marking....................................................................................................................... .................................. 178.1 Hydrants.................................................................................................................... ................................... 178.2 Outlets ..................................................................................................................... ..................................... 17

9 Surface boxes and covers...................................................................................................... .................... 189.1 Class....................................................................................................................... ...................................... 189.2 Clear area .................................................................................................................. ................................... 189.3 National requirement ........................................................................................................ .......................... 18

Page 4: pren14339

prEN 14339:2001 (E)

4

10 Installation ................................................................................................................. .................................. 18

Annex ZA (informative) Clauses of this European Standard addressing essentialrequirements or other provisions of EU Directives.............................................................................. ... 19

Bibliography ................................................................................................................... .......................................... 24

Page 5: pren14339

prEN 14339:2001 (E)

5

Introduction

The purpose of a Fire Hydrant installation is to provide a connection (i.e. hydrant) to the water main towhich the fire brigade can connect firefighting equipment. Underground hydrants consist of valve/sand connection outlet/s in an underground chamber with a surface manhole cover.

This standard is in conformity with the general requirements established by CEN/TC 164 in the field ofWater Supply. Products in permanent or temporary contact with water intended for humanconsumption should not affect the quality of the water. This Standard therefore does not contravenethe Directives 75/400/EEC and 80/778/EEC.

Page 6: pren14339

prEN 14339:2001 (E)

6

1 Scope

This European Standard specifies the requirements and test methods applicable to undergroundhydrants intended for fire fighting purposes:

� to be installed in a water distribution system;

� in sizes DN 80 and DN 100;

� suitable for an allowable operating pressure, PFA of 1.0 or 1.6 MPa*;

� with or without drain facility;

� having vertical or horizontal, flanged, socket or spigot inlet;

� having outlet to National Requirements;

� of globe (screw down) or gate valve type;

� and for surface boxes and covers.

2 Normative references

This European Standard incorporates by dated or undated reference, provisions from otherpublications. These normative references are cited at the appropriate places in the text and thepublications are listed hereafter. For dated references, subsequent amendments to or revisions of anyof these publications apply to this European Standard only when incorporated in it by amendment orrevision. For undated references, the latest edition of the publication referred to applies.

ISO 6708:1980, Pipe components — Definition of nominal size

ISO 7268:1984, Pipe components — Definition of nominal pressure amendment one

ISO 683-13:1986, Heat-treatable steels, alloy steels and free cutting steels — Part 13: Wrought stainlesssteels

prEN ( ), Leakage classes — in preparation by CEN/TC 69/WG 1

prEN 124, Gully tops and manhole tops for vehicular and pedestrian areas — in preparation byCEN/TC 165

prEN 1074, Endurance Tests for isolating valves — prepared by CEN/TC 69

prEN ( ), Flanges — in preparation by CEN/TC 74

prEN 1267, Valves — Test of flow resistance

3 Definitions

For the purposes of this European Standard the following definitions apply:

Page 7: pren14339

prEN 14339:2001 (E)

7

3.1DN nominal sizenumerical designation of size which is common to all components in a piping system. It is a convenientround number for reference purposes and is only loosely related to manufacturing dimensions

NOTE This definition conforms to prEN 26708.

3.2PN nominal pressurenumerical designation expressed by a number which is used for reference purposes. All components ofthe same nominal size DN designated by the same PN number have compatible mating dimensions

NOTE This definition conforms to prEN 1333.

3.3allowable maximum operating pressure PMAmaximum hydrostatic pressure including surge that a component can withstand from time to time inservice

3.4allowable operating pressure PFAmaximum hydrostatic pressure that a component can withstand continuously in service

3.5allowable test pressure PEAmaximum hydrostatic pressure that a newly installed component can withstand for a relatively shortduration when either fixed above ground level or laid and backfilled underground in order to ensure theintegrity and tightness of the pipeline

3.6clear areaas defined in prEN 124

3.7captive obturatordevice for controlling the flow out of a pipeline and into a pipeline

3.8loose obturatordevice for controlling flow out of a pipeline but which prevents flow into a pipeline

3.9flow coefficient Kvthe rate of flow in cubic metres per hour that will cause a differential pressure of one bar through thehydrant

3.10shellas defined in prEN 736-2

4 Technical requirements

4.1 Dimensions

Hydrants shall comply with the dimensional requirements shown in Figure 1 and Table 1.

Page 8: pren14339

prEN 14339:2001 (E)

8

H

C

R1R2

B

D

A

H

34

1

2

5

6

NOTE The actual size and shape of the surface box and cover is not specified provided that the minimumclear area shown is provided.

Key1 Vertical Inlet DN 4 Outlet Connector2 Horizontal Inlet DN 5 Maximum size of hydrant (A max, B max)3 Drive 6 Minimum clear area of Surface box and

Covers (D, R1min, R2min)Figure 1 — Typical fire hydrant

Page 9: pren14339

prE

N 1

4339

:200

1 (E

) 9

Tab

le 1

— D

imen

sion

s an

d h

ydra

nt t

ypes

DN

Cle

ar o

peni

ng fo

r ope

ratio

nIn

let

Hyd

rant

Dim

ensi

ons

of h

ydra

ntD

esig

nate

dT

ype

A M

AX

B M

AX

C M

INC

MA

XH

± 5

0D

R1

MIN

R2

MIN

mm

mm

mm

mm

mm

mm

mm

mm

210

380

160

170

375

170

105

105

80V

1

80V

ertic

al22

535

014

0 5

00, 7

5013

080

80V

222

032

015

015

050

0, 7

50, 1

000,

125

015

083

8380

V3

255

390

125

125

250

to 1

250

125

5080

80V

421

529

013

017

053

5, 6

35, 7

35, 8

35, 9

3517

011

080

100V

110

35, 1

135,

123

510

0

355

490

175

175

250

to 1

250

175

5012

010

0V2

360

430

117

117

750,

100

0, 1

250

117

148

148

100V

380

255

390

225

290

250

to 1

250

290

105

8580

H1

220

320

150

150

655,

905

, 115

5, 1

405

150

8383

80H

221

046

025

025

039

025

013

080

80H

3H

oriz

onta

l21

529

013

017

057

5, 6

75, 7

75, 8

75, 9

75,

170

110

8010

0H1

100

1075

, 117

5, 1

275

200

330

170

170

530

to 4

000

170

6010

010

0H2

355

490

175

175

250

to 1

250

175

5012

010

0H3

Page 10: pren14339

prEN 14339:2001 (E)

10

4.2 Material

Material for the shell of hydrants shall be chosen from those given in Table 2.

Table 2 — Material requirements

Material Specification

Flake graphite cast iron Grade 200 MPa min

Spheroidal graphite cast iron Minimum values shall be:

Tensile strength 370 MPa

Elongation after fracture 3 %

Stainless steel ISO 683/13-1986 tensile strength 500 MPa min

NOTE 1 ISO 683/13-1986 will be replaced by CEN when available.

NOTE 2 The above materials are those currently in use in Europe. Other materials may be included in arevision of this standard if their safety and durability is shown to be acceptable.

4.3 Obturator

The hydrant obturator shall be either captive or loose type, as specified by the purchaser.

NOTE Wherever practicable, the design of the fire hydrant should be such that the obturator may bereplaced in situ. This replacement should only be carried out when the fire hydrant is not under pressure.

4.4 Valve components

Valve components shall comply with the requirements of ENs currently being produced by CEN/TC 69'Industrial Valves'.

4.5 Spindle seals

Spindle seals of globe (screw down) hydrants shall be capable of being replaced with the valve underthe operating pressure.

4.6 Potable water

Materials which may come into contact with potable water shall be checked for conformity with EN XXXX(TC 164/WG 3) or in the absence of this, in accordance with national regulations in operation at the placeof use.

4.7 Pressures

The hydrant shall be suitable for the relevant pressures shown in Table 3.

Page 11: pren14339

prEN 14339:2001 (E)

11

Table 3 — Pressures

PFA PMA PEA

MPa (bar) MPa (bar) MPa (bar)

1.0 (10) 1.5 (15) 1.5 (15)

1.6 (16) 2.1 (21) 2.4 (24)

4.8 Spindle drive

Spindle drive shall comply with national requirements. Where fitted, the spindle cap shall be securelyfixed in position during normal use. The means of fixing shall be such as to permit removal of the capby authorised users but also to prevent unauthorised removal. The design of the spindle cap recessshall suit the spindle end of the valve.

4.9 Direction of closure

Valves shall be closed by turning the spindle in a clockwise direction when viewed from above.

4.10 No of turns

The number of turns "N" required to fully open the valve shall be between 5 and 14 for DN 80 andbetween 7 and 15 for DN 100.

4.11 Torque

The maximum operating torque required to open or close a valve, as delivered and under a pressureof PFA, shall not exceed that given in Table 4. The purchaser shall specify the class to be supplied.The minimum torque required to cause failure of the valve shall be that given in Table 4.

Table 4 — Torques

DN Maximum operating torque Minimum failure torque

Class A Class B Class A Class B

Nm Nm Nm Nm

80 125 130 250 260

100 125 150 250 300

4.12 Start of flow

The maximum number of turns to commence flow shall be 2 for N <10 and 3 for N >10.

4.13 Inlet flanges

Inlet flanges shall conform to National Standards. Where the inlet is socket or spigot, the dimensionsshall be agreed between the purchaser and the supplier.

Page 12: pren14339

prEN 14339:2001 (E)

12

4.14 Outlet connectors

Outlet connectors shall conform to National Requirements.

4.15 Draining

Each hydrant shall be provided with a drain boss on the outlet side, located at the lowest practicablepoint, such that, if fitted with a drainage device, with the hydrant valve closed and the drain valve fullyopen, the volume of water retained shall not exceed 80 ml for DN 80 and 100 ml for DN 100. Thedrain boss shall permit the fitting of a blank plug, drilled drip plug or self operating frost valve.

Where a drilled drip plug or a self operating frost valve is fitted, it shall be capable of draining thehydrant to the minimum retained volume within 15 minutes.

4.16 Coatings

All cast iron components shall be coated to provide protection against corrosion. The coating shallcomply with 4.6, where applicable.

4.17 Hydrants for non portable water systems

NOTE The user should consult the hydrant manufacturer concerning compatibility with the fluid to beconveyed.

5 Performance requirements

5.1 Type test requirements

A single set of tests only is required to ascertain that the hydrant design meets the statedrequirements of this clause.

NOTE Requirements for testing individual production units are given in 5.2.

5.1.1 Number of turns

When tested in accordance with 6.6, the number of turns 'N' shall meet the requirements of 4.10.

5.1.2 Maximum operating torque

When tested in accordance with 6.7, the torque required to seal shall meet the requirements of 4.11.

5.1.3 Minimum failure strength torque

When tested in accordance with 6.4, the valve shall meet the requirements of 4.11.

After test the hydrant shall meet the requirements of 5.17.

5.1.4 Start of flow

When tested in accordance with 6.5, flow shall occur.

Page 13: pren14339

prEN 14339:2001 (E)

13

5.1.5 Flow

When tested in accordance with 6.2, the hydrant shall have a Kv not less than that specified inTable 5 or Table 6.

Table 5 — Minimum Kv (m 3/h) for globe (screw down) hydrants

Inlet Internal diameter of outlet mm

DN <65 65 >65 <100 100 >100

80 60 70 110 - - -

100 - - - 75 160 260

Table 6 — Minimum Kv (m 3/h) for gate valve hydrants

Inlet Internal diameter of outlet mm

DN 54 65

80 69 -

100 - 210

5.1.6 Leak tightness

5.1.6.1 Hydrant valve seating

When tested in accordance with 6.7.1 there shall be no visible sign of leakage past the valve.

NOTE This is equivalent to rate 'A' as defined in prEN 1074-1.

5.1.6.2 Complete hydrant

When tested in accordance with 6.8 there shall be no visible sign of leakage from the hydrant.

NOTE This is equivalent to rate 'A' as defined in prEN 1074-1.

When type tested in accordance with 6.7.2 the vacuum pressure shall not change by more than80 millibar.

5.1.6.3 Outlet connector

When outlet connectors are supplied separately they shall be tested in accordance with 6.9. Thereshall be no visible sign of leakage from the outlet connector.

NOTE This is equivalent to rate 'A' as defined in prEN 1074-1.

Where plastics material outlet connectors are permitted by National Requirements they shall be testedin accordance with those requirements.

Page 14: pren14339

prEN 14339:2001 (E)

14

5.1.7 Endurance

5.1.7.1 Torque

When tested in accordance with 6.3 the torque to fully open and close the valve shall not exceed 1.2times that specified in 4.11.

5.1.7.2 Sealing

When tested in accordance with 6.3 there shall be no visible sign of leakage past the valve or fromthe hydrant when the valve is closed with a torque not exceeding 1.2 times that specified in 4.11.

NOTE This is equivalent to rate 'A' as defined in prEN 1074-1.

5.2 Production test requirements

5.2.1 Hydrant valve seating

Each hydrant shall be tested in accordance with 6.7.1 and there shall be no visible sign of leakagepast the valve.

NOTE This is equivalent to rate 'A' as defined in prEN 1074-1.

5.2.2 Complete hydrant

Each hydrant shall be tested in accordance with 6.8. and there shall be no visible sign of leakage fromthe hydrant.

NOTE This is equivalent to rate 'A' as defined in prEN 1074-1.

5.2.3 Outlet connector

Each outlet connector supplied separately shall be tested in accordance with 6.9 and there shall beno visible sign of leakage from the connector.

NOTE This is equivalent to rate 'A' as defined in prEN 1074-1.

6 Test methods

6.1 Safety

Before applying any hydrostatic pressure, release all air from within the component under test.

6.2 Flow

6.2.1 Method

Determine the hydrant Kv in accordance with prEN 1267.

6.2.2 Test medium

The test medium shall be water.

Page 15: pren14339

prEN 14339:2001 (E)

15

6.2.3 Connecting pipes

The internal diameter of the pipes connected to the inlet and the outlet of the hydrant shall be thesame as the internal diameter of the inlet to the hydrant within the tolerances specified. Any change indiameter between the hydrant outlet and the outlet pipe shall be by a step change in internaldiameter, ie no transition taper shall be incorporated.

6.2.4 Test duration

Measure Kv in accordance with prEN 1267 and then maintain the flow induced by the differentialpressure of 100 kN ± 10 kN (1 bar ± 0.1 bar) for 15 minutes.

6.3 Endurance

This test shall be carried out on a valve that has previously been subjected to the flow test (6.2). Thetest shall be carried out in accordance with prEN 1074 except that the number of cycles shall be 500and the hydrant shall be connected to a water supply pressurized to 600 kN (6 bar) when the valve isclosed. The flow through the hydrant when the valve is fully open shall be not less than 30 m3/h for aDN 80 hydrant and not less than 60 m3/h for a DN 100 hydrant.

6.4 Failure torque

Apply a torque equal to that given in Table 4 to the closed valve. Open the valve and apply a torqueequal to that given in Table 4 to the fully open valve.

6.5 Start of flow

Connect the hydrant to a water supply and close the valve with a torque sufficient to seal the hydrant.Open the valve by the number of turns specified in 5.1.5. Determine if flow has started.

6.6 Number of turns

Close the valve with a torque sufficient to seal the hydrant. Fully open the valve and determine thenumber of turns necessary.

6.7 Valve seating

6.7.1 Positive pressure

Connect the inlet of the hydrant to a water supply and close the hydrant valve with a torque notexceeding that specified in 4.11. Raise the pressure in the inlet side of the closed valve to 1.1 PFA fora period of not less than 30 sec, and examine for leaks.

6.7.2 Negative pressure test

Connect the inlet of the hydrant to a vacuum pump and close the valve with a torque not exceedingthat specified in 4.11. Evacuate the hydrant to a pressure of 80 KPa (800 millibar) below atmospheric(approximately 20 KPa or 200 millibar absolute). Isolate the vacuum pump from the hydrant andmonitor the vacuum pressure for a period of one hour.

6.8 Complete hydrant

Connect the inlet of the hydrant to a water supply and blank off the outlet, including the outletconnector if supplied fitted. With the valve open, raise the pressure to 1.5 x PFA for a period of notless than 1 minute and examine for leaks.

Page 16: pren14339

prEN 14339:2001 (E)

16

6.9 Outlet connector

When outlet connectors are supplied separately, blank off the outlet of the connector with a suitablecap and connect the other end to a pressurised water supply. Raise the pressure to 1.5 � PFA for aperiod of not less than 1 minute and examine for leaks.

7 Evaluation of conformity

7.1 General

The compliance of an underground hydrant with the requirements of this standard and with the statedvalues shall be demonstrated by:

� initial type testing,

� factory production control by the manufacturer, including product assessment.

For the purposes of testing, hydrants may be grouped into families where it is considered that theselected property is common to all hydrants within that family.

7.2 Type testing

7.2.1 Initial type testing

Initial type testing shall be performed on first application of this standard. Tests previously performedin accordance with the provisions of this standard (same product, same characteristic(s), test method,sampling procedure, system of attestation of conformity, etc.) may be taken into account. In addition,initial type testing shall be performed at the beginning of the production of a new hydrant type (unlessa member of the same family) or at the beginning of a new method of production (where this mayaffect the stated properties).

Where characteristics are determined on the basis of conformity with other product standards(e.g. valves and surface boxes and covers), these characteristics need not be reassessed providedthat the hydrant manufacturer ensures the validity of the results. Products CE marked in accordancewith appropriate harmonised European specifications may be presumed to have the performancesstated of them, although this does not replace the responsibility of the hydrant manufacturer to ensurethat the hydrant as a whole is correctly designed and its component products have the necessaryperformance values.

All characteristics in clauses 4, 5.1 and 9 shall be subject to initial type testing. The results of all typetests shall be recorded and held by the manufacturer for at least 5 years.

7.3 Factory production control (FPC)

7.3.1 General

The manufacturer shall establish, document and maintain an FPC system to ensure that the productsplaced on the market conform with the stated performance characteristics. The FPC system shallconsist of procedures, regular inspections and tests and/or assessments and the use of the results tocontrol raw and other incoming materials or components, equipment, the production process and theproduct.

An FPC system conforming with the requirements of EN ISO 9001 and made specific to therequirements of this standard, is considered to satisfy the above requirements.

Page 17: pren14339

prEN 14339:2001 (E)

17

The results of inspections, tests or assessments requiring action shall be recorded, as shall any actiontaken. The action to be taken when control values or criteria are not met shall be recorded.

7.3.2 Equipment

All weighing, measuring and testing equipment shall be calibrated and regularly inspected accordingto documented procedures, frequencies and criteria.

7.3.3 Raw materials and components

The specifications of all incoming raw materials and components shall be documented, as shall theinspection scheme for ensuring their conformity.

8 Marking

NOTE Where annex Z.A3 covers the same information as this clause, the requirements of this clause 8 aremet.

8.1 Hydrants

All hydrants shall be durably marked on the upper part with the following:

� Direction of opening

� No. of turns to open

In addition all hydrants shall be durably marked, either directly or with an attached label, with thefollowing:

� DN

� PFA

� Type (from Table 1)

� Class (from Table 4)

� Loose obturator (if applicable)

� Manufacturer's mark

� Date of manufacture

� Third Party certification (if applicable)

8.2 Outlets

Outlets shall be durably marked in accordance with National Requirements.

Page 18: pren14339

prEN 14339:2001 (E)

18

9 Surface boxes and covers

9.1 Class

The class of surface boxes and covers shall comply with the requirements of EN 124. Class of boxand cover shall be specified by the purchaser.

9.2 Clear area

The minimum clear area shall be that specified in Table 1, dimension D, R1 min and R2 min. andillustrated in Figure 1.

9.3 National requirement

All other features including design, method of lifting, marking etc shall conform to NationalRequirements.

10 Installation

Hydrants, surface boxes and covers shall be installed in accordance with National Regulations.

Page 19: pren14339

prEN 14339:2001 (E)

19

Annex ZA(informative)

Clauses of this European Standard addressing essentialrequirements or other provisions of EU Directives

ZA.0 Scope of this annex

The scope as given in clause 1 is applicable.

ZA.1 Relationship between EU Directive and this European Standard

This European standard has been prepared under a Mandate given to CEN by the EuropeanCommission and the European Free Trade Association.

The clauses of this European standard shown in this annex meet the requirements of the Mandategiven under the EU Construction Products Directive (89/106).

Compliance with these clauses confers a presumption of fitness of the construction products coveredby this European standard for their intended use.

WARNING Other requirements and other EU Directives, not affecting the fitness for intended use may beapplicable to a product falling within the scope of this European Standard.

NOTE In addition to any specific clauses relating to dangerous substances contained in thisStandard, there may be other requirements applicable to the products falling within its scope (e.g.transposed European legislation and national laws, regulations and administrative provisions). Inorder to meet the provisions of the EU Construction Products Directive, these requirements need alsoto be complied with, when and where they apply. An informative database of European and nationalprovisions on dangerous substances is available at the Construction web site on EUROPA (CREATE,accessed through http://europa.eu.int).

Construction product: Underground fire hydrants.

Intended use(s): For use in fire fighting.

Page 20: pren14339

prEN 14339:2001 (E)

20

Table ZA.1 — Relevant clauses

Essential characteristics Requirementclauses in thisstandard

Mandatedlevels orclasses

Notes

Operational reliability 4.2, 4.4, 4.7, 4.8,4.9, 4.10, 4.11,4.12, 5.1.6, 9.1*

* Whererelevant

Connection dimensioning 4.13, 4.14

Durability of operational reliability against corrosion 4.16

Durability of operational reliability; endurance 5.1.7

ZA.2 Procedure for the attestation of conformity of underground fire hydrants

ZA.2.1 System of attestation of conformity

Underground fire hydrants for the intended use listed shall follow the system of attestation ofconformity shown in Table ZA.2.

Table ZA.2 — Attestation of conformity system

Product Intended use Level(s) orclass(es)

Attestation of conformitysystem

Underground fire hydrants Fire safety 1

System 1: See CPD annex III.2.(I) without audit testing of samples.

The product certification body will certify the initial type testing of all characteristics given inTable ZA.1, in accordance with the provisions of 7.2, and for the initial inspection of the factory and ofthe factory production control, and for the continuous surveillance, assessment and approval of thefactory production control, all characteristics shall be of interest to the approved body.

The manufacturer shall operate a factory production control system in accordance with the provisionsof 7.3 and, for further testing of samples taken at the factory, shall perform production tests accordingto 5.2.

ZA.3 CE marking

The CE marking symbol in the format specified in the EU Directive 93/68/EC shall be shown on thehydrant together with the marking as specified in clause 8. In addition, the CE marking shall appearon the packaging and/or on the accompanying commercial documents, together with the followinginformation:

� the identification number of the certification body, and

� the name or identifying mark of the producer/supplier; and

Page 21: pren14339

prEN 14339:2001 (E)

21

� the last two digits of the year in which the marking was affixed; and

� the appropriate number of the EC-certificate of conformity; and

� the number of this standard (EN xxx); and

� the product type (i.e. underground fire hydrant, DN (80 or 100), flow coefficient Kv, inlet andoutlet flange sizes); and

� information on the essential characteristics in Figure ZA.1:

� operating pressure PFA (MPa);

� torque class;

� coating type and thickness (if relevant);

� class of surface box and cover (if relevant);

� minimum clear area (if relevant).

In addition to any specific information relating to dangerous substances shown above, the productshould also be accompanied, when and where required and in the appropriate form, bydocumentation listing any other legislation on dangerous substances for which compliance is claimed,together with any information required by that legislation.

NOTE European legislation without national derogations need not be mentioned.

Figure ZA.1 gives an example of the information to be given on the commercial documents.

Page 22: pren14339

prEN 14339:2001 (E)

22

0123

AnyCo Ltd , P.O. Box 21, B - 1050

01

0123-CPD-001

EN WI 00192015

Underground fire hydrant,

DN, 80

Kv, 70

inlet flange, xx mm

outlet flange xx mm

Operating pressure PFA 1,0 MPa

Torque class A

Surface box and cover classes C 250

Minimum clear area a, b, c

Figure ZA.1 — Example CE marking information

ZA.4 EC certificate and declaration of conformity

The manufacturer, or his agent established in the EEA, shall prepare and retain a declaration ofconformity, which authorises the affixing of the CE marking. This declaration shall include:

� name and address of the manufacturer, or his authorized representative established in the EEA,and the place of production

� description of the product (type, identification, use), and a copy of the information accompanyingthe CE marking

� provisions to which the product conforms (e.g. Annex ZA of this EN)

� particular conditions applicable to the use of the product [if necessary]

� the name and address (or identification number) of the Notified Product Certification Body

� name of and position held by the person empowered to sign the declaration on behalf of themanufacturer or of his authorized representative.

The declaration shall contain a certificate of conformity with, in addition to the information above, thefollowing information:

� the name and address of the certification body,

Page 23: pren14339

prEN 14339:2001 (E)

23

� the certificate number,

� conditions and period of validity of the certificate, where applicable,

� name of, and position held by, the person empowered to sign the certificate.

Duplication of information between the declaration and certificate shall be avoided. The declarationand certificate shall be presented in the official language(s) of the Member State of the use of theproduct.

Page 24: pren14339

prEN 14339:2001 (E)

24

Bibliography

[1] EN ISO 9001, Quality management systems — Requirements