Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... ·...

28
Practical Transformer on Load We now consider the deviations from the last two ideality conditions : 1. The resistance of its windings is zero. 2. There is no leakage flux. The effects of these deviations become more prominent when a practical transformer is put on load. Monday, August 01, 2011 Transformers 1 Next

Transcript of Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... ·...

Page 1: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Practical Transformer on Load We now consider the deviations from the last two

ideality conditions :

1. The resistance of its windings is zero.

2. There is no leakage flux.

The effects of these deviations become more prominent when a practical transformer is put on load.

Monday, August 01, 2011 Transformers 1Next

Page 2: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

(1) Effect of Winding Resistance Current flow through the windings causes a power loss

called I2R loss or copper loss.

This effect is accounted for by including a resistance R1

in the primary and resistance R2 in the secondary

Monday, August 01, 2011 Transformers 2Next

Page 3: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

(2) Effect of Flux Leakage The difference between the total flux linking with the

primary and the useful mutual flux Φu linking with both the windings is called the primary leakage flux, ΦL1.

Similarly, ΦL2 represents the secondary leakage flux.

Flux leakage results in energy being alternately stored in and discharged from the magnetic fields with each cycle of the power supply.

It is not directly a power loss, but causes the secondary voltage to fail to be directly proportional to the primary voltage, particularly under heavy loads.

Monday, August 01, 2011 Transformers 3Next

Page 4: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Leakage flux in a transformer

Monday, August 01, 2011 Transformers 4

(a) Its definition. (b) Its effect accounted for.

• The useful mutual flux Φu is responsible for the transformer action.• The leakage flux ΦL1 induces an emf EL1 in the primary winding.

Next

Page 5: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Similarly, flux ΦL2 induces an emf EL2 in the secondary.

Hence, we include reactances X1 and X2 in the primary and secondary windings, in the equivalent circuit.

The paths of leakage fluxes ΦL1 and ΦL2 are almost entirely due to the long air paths and are therefore practically constant.

The reluctance of the paths being very high, X1 and X2

are relatively small even on full load.

However, the useful flux Φu remains almost independent of the load.

Monday, August 01, 2011 Transformers 5Next

Page 6: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Monday, August 01, 2011 Transformers 6Next

Page 7: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Equivalent Circuit of a Transformer

Monday, August 01, 2011 Transformers 7

It is merely a representation of the following KVL equations :

1 1 1 1 1 1 1 1 1 1( )I R jI X I R jX V E E

2 2 2 2 2 2 2 2 2 2( )I R jI X I R jX E V V

Next

Page 8: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Points to Draw Phasor Diagram

1. Resistive voltage drop in phase with current phasor.

2. Inductive voltage drop in quadrature with current.

3. To get V1, add I1Z1 to –E1.

4. Add V2 and I2Z2 , to get E2.

5. Current I1 is vector sum of I0 and I2’.

6. Angle between V1 and I1 gives the power factor angle of the transformer.

Monday, August 01, 2011 Transformers 8

Page 9: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Monday, August 01, 2011 Transformers 9

m

E2

E1

-E1

I1R1

I1X1V1

I1

I0

I1'

I2

V2

I2R2

I2X2

0

1

Ph

aso

r D

iag

ram

fo

r

Pra

ctic

al T

ran

sfo

rmer

on

R

esi

stiv

e L

oa

d

1 1 1 1 1

2 2 2 2

( )

( )

I R jX

V I R jX

2

V E

E

O

I1Z1

I2Z2

Next

Page 10: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Monday, August 01, 2011 Transformers 10

Pra

ctic

al T

ran

sfo

rmer

on

In

du

ctiv

e L

oa

d

Next

Page 11: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Monday, August 01, 2011 Transformers 11

Pra

ctic

al T

ran

sfo

rmer

on

C

ap

aci

tive

Lo

ad

Next

Page 12: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Simplified Equivalent Circuit The no-load current I0 is only about 3-5 % percent of the

full-load current.

The exciting circuit R0-X0 in is shifted to the left of impedance R1-X1.

Monday, August 01, 2011 Transformers 12

Transforming the impedances from the secondary to the primary side.

Next

Page 13: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Monday, August 01, 2011 Transformers 13

Equivalent resistance and reactance referred to the primary side

2 2

e1 1 2 e1 1 2( / ) and ( / )R R R K X X X K

Next

Page 14: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Approximate Equivalent Circuit

Monday, August 01, 2011 Transformers 14Next

Page 15: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Example 5 A single-phase, 50-kVA, 4400-V/220-V, 50-Hz transformer

has R1 = 3.45 Ω, R2 = 0.009 Ω, X1 = 5.2 Ω and X2 = 0.015 Ω. Calculate

(a) the Re as referred to the primary,

(b) the Re as referred to the secondary,

(c) the Xe as referred to the primary,

(d) the Xe as referred to the secondary,

(e) the Ze as referred to the primary,

(f) the Ze as referred to the secondary, and

(g) the total copper loss.

Monday, August 01, 2011 Transformers 15Next

Page 16: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Monday, August 01, 2011 Transformers 16

Solution : Full-load primary current,

1

1

kVA 5000011.36 A

4400I

V

Full-load secondary current, 2

2

kVA 50000227.27 A

220I

V

2

1

220 10.05

4400 20

VK

V

(a) 2 2

e1 1 2( / ) 3.45 [0.009/(0.05) ]R R R K 7.05 Ω

(b)

(c)

2 2

e2 1 2 (0.05) 3.45 0.009R K R R 0.0176 Ω

2 2

e1 1 2( / ) 5.2 [0.015/(0.05) ]X X X K 11.2 Ω

(d) 2 2

e2 1 2 (0.05) 5.2 0.015X K X X 0.028 Ω

Next

Click

Click

Click

Click

Click

Click

Page 17: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Monday, August 01, 2011 Transformers 17

(e) 2 2 2 2

e1 e1 e1 (7.05) (11.2)Z R X 13.23 Ω

(f)

(g) Total copper loss

2 2 2 2

e2 e2 e2 (0.0176) (0.028)Z R X 0.0331 Ω

2 2 2 2

1 1 2 2 (11.36) 3.45 (227) 0.009I R I R 909 W

Alternatively, by considering equivalent resistances, total copper loss

2 2

1 e1 (11.36) 7.05I R 909.8 W

2 2

2 e2 (227.27) 0.0176I R 909 W

Next

Click

Click

Click

Page 18: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Voltage Regulation

Monday, August 01, 2011 Transformers 18

V2(0) = secondary terminal voltage at no load,

and V2 = secondary terminal voltage at full load.

The voltage regulation of a transformer is defined as the change in its secondary terminal voltage from no load to full load, the primary voltage being assumed constant.

The voltage drop V2(0) - V2 is called the inherent regulation.

2(0) 2

2(0)

( ) Per unit V V

iV

regulation down

2(0) 2

2(0)

% 100V V

V

regulation down

Next

Page 19: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Monday, August 01, 2011 Transformers 19

2(0) 2

2

( ) Per unit V V

iiV

regulation up

2(0) 2

2

% 100V V

V

regulation up

Normally, when nothing is specified, ‘regulation’ means ‘regulation down’.

Next

Page 20: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Monday, August 01, 2011 Transformers 20

Exact voltage drop =

2(0) 2 OC OA OG OA AG AF+FGV V

Next

Approximate Voltage Drop

The secondary terminal voltage at no load,2(0) 2 1 1V E KE KV

Page 21: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Monday, August 01, 2011 Transformers 21

In case of leading power factor,

2 e2 2 e2

Approximate voltage drop, AF AE EF AE BD

cos sinI R I X

2 e2 2 e2

Approximate voltage drop, AF AE EF AE BD

cos sinI R I X

In general,

2 e2 2 e2Approximate voltage drop cos sinI R I X

Next

Page 22: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Monday, August 01, 2011 Transformers 22

2 2 2 2

2(0)

cos sin% Regulation 100

cos sin

e e

r x

I R I X

V

V V

Condition for Zero Regulation :Possible only if the load has leading power factor.

2 2 2 2cos sin 0e eI R I X 2

2

tan e

e

R

X

Use + sign for lagging power factor and – sign for leading power factor.

Next

Page 23: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Condition for Maximum Regulation

Monday, August 01, 2011 Transformers 23

2 2 2 2( cos sin ) 0e e

dI R I X

d

2 2 2 2( sin cos ) 0e eI R I X

2

2

tan e

e

X

R

Maximum regulation can occur only for inductive load. The voltage drop is maximum when

Next

Page 24: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Monday, August 01, 2011 Transformers 24

Example 6

Solution :

Click

Next

Page 25: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Monday, August 01, 2011 Transformers 25

Example 7

Solution :

2the load voltage, 240 6V 234V

Click

Next

Page 26: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Example 8 A single-phase, 40-kVA, 6600-V/250-V,

transformer has primary and secondary resistances R1 = 10 Ω and R2 = 0.02 Ω, respectively. The equivalent leakage reactance as referred to the primary is 35 Ω. Find the full-load regulation for the load power factor of

(a) unity,

(b) 0.8 lagging, and

(c) 0.8 leading.

Monday, August 01, 2011 Transformers 26Next

Page 27: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Monday, August 01, 2011 Transformers 27

2 2

e2 1 2 (0.0379) 10 0.02 0.0343R K R R

2 2

e2 e1and (0.0379) 35 0.0502X K X

(a) For power factor, cos = 1; sin = 0. Hence,

2 2 2 2

2(0)

cos sin% Regulation 100

160 0.0343 1 0100

250

e eI R I X

V

2.195 %

Solution : Given : R1 = 10 Ω; R2 = 0.02 Ω; Xe1 = 35 Ω

2

250 the turns-ratio, 0.0379

6600

40000the full-load current, 160 A

250

K

I

Next

Click

Click

Click

Page 28: Practical Transformer on Load - HA.incmyjiit.weebly.com/uploads/8/0/3/2/8032658/transformer... · 2018-10-04 · Practical Transformer on Load We now consider the deviations from

Monday, August 01, 2011 Transformers 28

(b) For power factor, cos = 0.8 (lagging, positive);

(c) For power factor, cos = 0.8 (leading, negative);

sin 0.6

2 e2 2 e2

2(0)

cos sin% Regulation 100

160 0.0343 0.8 160 0.0502 0.6100

250

I R I X

V

0.172 %

2sin 1 cos 0.6

2 e2 2 e2

2(0)

cos sin% Regulation 100

160 0.0343 0.8 160 0.0502 0.6100

250

I R I X

V

3.68 %

Next

Click

Click