Practical PMU Applications for Utilities
University of Washington EE Graduate Seminar
November 1st, 2012
Manu Parashar
Douglas Wilson
![Page 2: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control](https://reader036.fdocuments.us/reader036/viewer/2022081601/60eaa9b4d8c94d22cd210660/html5/thumbnails/2.jpg)
SynchroPhasor Technology
− Next generation measurement technology. (voltages, currents, frequency, frequency
rate-of-change, etc)
− Higher resolution scans (e.g. 30 samples/second). ─ Improved visibility into dynamic
grid conditions.
─ Early warning detection alerts.
− Precise GPS time stamping. ─ Wide-area Situational Awareness. ─ Faster Post-Event Analysis.
PMU ‘Sub-second’
Resolution
SCADA ‘Seconds’
Resolution
Phasor Measurement Units (PMUs)
![Page 3: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control](https://reader036.fdocuments.us/reader036/viewer/2022081601/60eaa9b4d8c94d22cd210660/html5/thumbnails/3.jpg)
PMU Deployment within North America
Currently 200+
PMUs Installed.
Expected to exceed
800+ PMUs by 2013 (under SGIG Investments)
Source: NASPI Website (www.naspi.org)
![Page 4: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control](https://reader036.fdocuments.us/reader036/viewer/2022081601/60eaa9b4d8c94d22cd210660/html5/thumbnails/4.jpg)
SynchroPhasors & Energy Management Systems
Control Center -PDC
PMU MEASUREMENT-BASED Analysis
(PhasorPoint)
Traditional MODEL-BASED Analysis
(EMS)
SCADA & Alarms
WAMS
State Estimator
State Measurement
Other EMS Applications
New Applications
Small Signal Stability
Oscillation Monitoring
Transient & Voltage Stability
Stability Monitoring & Control
Island Management
Island Detection, Resync,& Blackstart
![Page 5: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control](https://reader036.fdocuments.us/reader036/viewer/2022081601/60eaa9b4d8c94d22cd210660/html5/thumbnails/5.jpg)
Look Ahead and Predictive Operations Capability in Control Rooms
• Reduces the impact of variability and uncertainty on real-time decision making in the control room
![Page 6: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control](https://reader036.fdocuments.us/reader036/viewer/2022081601/60eaa9b4d8c94d22cd210660/html5/thumbnails/6.jpg)
SynchroPhasor Benefits
RELIABILITY
• Situational Awareness
• Identifying sources of oscillations
• Vulnerability detection
• Automated wide area protection
• Identifying equivalent dynamic models
• Analysis tools e.g.
• Post Mortem
• Dynamic model validation
• Baselining
CONSTRAINT RELIEF
• Stability (damping) constraints
• Angle constraints
• WAMS + DSA (integration of “measurement-based” and “model-based” security assessment).
• Angle based control
SUSTAINABILITY
• Renewable connections
• Impact of renewables on stability
• Distribution management
![Page 7: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control](https://reader036.fdocuments.us/reader036/viewer/2022081601/60eaa9b4d8c94d22cd210660/html5/thumbnails/7.jpg)
Operational Benefits Improved Reliability
August 10, 1996 Blackout
Monitor wide-area grid stress.
August 14, 2003 Blackout
Early detection of dynamic instability.
Dynamic Instability (Negative Damping)
~ 3% (LOW) Damping (after Keeler Allston line trips)
![Page 8: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control](https://reader036.fdocuments.us/reader036/viewer/2022081601/60eaa9b4d8c94d22cd210660/html5/thumbnails/8.jpg)
Australia Queensland – NSW Interconnector
Great Britain Scotland – England Interconnector
Transmission Corridor Net Transfer Capacity
+300MW
+300MW
Model limit
with margin
Limit with
measured
damping
Thermal limit
AREA 1
AREA 2
Asset Management Congestion Relief
![Page 9: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control](https://reader036.fdocuments.us/reader036/viewer/2022081601/60eaa9b4d8c94d22cd210660/html5/thumbnails/9.jpg)
Planning Benefits Dynamic Model Validation
Western Interconnection August 10th, 1996 Blackout Dynamic models predicted stable system when the system was in fact unstable.
PMU provide necessary dynamic data to calibrate dynamic power system models.
![Page 10: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control](https://reader036.fdocuments.us/reader036/viewer/2022081601/60eaa9b4d8c94d22cd210660/html5/thumbnails/10.jpg)
Timely control actions necessary for them to be effective!
Protection & Control
![Page 11: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control](https://reader036.fdocuments.us/reader036/viewer/2022081601/60eaa9b4d8c94d22cd210660/html5/thumbnails/11.jpg)
PMU Basics: What is a PMU?
FIBRE OPTIC
1 pps
IRIG-B
un-modulated
ANALOG
Electrical
Signal
A/D DIGITISED
SAMPLE PROTECTION
and MEASUREMENT
PROCESSORS
Microprocessors
Areva P847 PMU
P594 GPS
RECEIVER
IEEE C37.118 DATA
Data frame
over Serial or Ethernet
(TCP/UDP)
ETHERNET
PROCESSOR
![Page 12: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control](https://reader036.fdocuments.us/reader036/viewer/2022081601/60eaa9b4d8c94d22cd210660/html5/thumbnails/12.jpg)
Fundamental WAMS Components
Analog Channels
− Va, Vb ,Vc,V1, V2,V0 − I1 , I2 , I0, Ia , Ib ,Ic − Frequency & Rate of Change of Frequency
Digital Channels
− Any 8 status signals available
Phasor Measurement Unit (PMU) (MiCOM P847 Series)
Phasor Data Concentrator (PDC) (PhasorPoint PDC, OpenPDC)
Time align measurements received from
multiple PMU/PDC streams.
Perform data validation.
Provide time-aligned data at desired periodicity
and formats to downstream applications.
![Page 13: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control](https://reader036.fdocuments.us/reader036/viewer/2022081601/60eaa9b4d8c94d22cd210660/html5/thumbnails/13.jpg)
Typical WAMS Architecture
Source: NASPI Website (www.naspi.org)
![Page 14: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control](https://reader036.fdocuments.us/reader036/viewer/2022081601/60eaa9b4d8c94d22cd210660/html5/thumbnails/14.jpg)
IMPROVED RELIABILITY: OSCILLATORY STABILITY MANAGEMENT
1/F MODE FREQUENCY
MODE AMPLITUDE
A
MODE DECAY TIME
EXP(-t/ )
MODE PHASE
Mode Frequency
Mode Amplitude
Mode decay time
Mode Phase
Exp(-t/ )
Measured P / f /
Simultaneous multi-oscillation detection and characterisation direct from
measurements
For each oscillation detected, alarm on:
• mode damping and/or
• mode amplitude for
Operations
Planning & Analysis, Plant Performance
Unlimited oscillation frequency sub-bands
Individual alarm profiles for each sub-band
In operational use since 1995 Does not use system model
Post-event analysis
Dynamic model validation
Damping controller performance assessment
Dynamic performance baselining
Early warning of poor damping (two level alarms)
Fast Modal Analysis: Alarms
Trend Modal Analysis: Analysis
Wide area mode alarms Mode locus plot with alarm thresholds
Oscillatory Stability Management
![Page 15: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control](https://reader036.fdocuments.us/reader036/viewer/2022081601/60eaa9b4d8c94d22cd210660/html5/thumbnails/15.jpg)
Oscillatory Modes Observed in Colombia (2009)
Ecuador Mode 0.49Hz
Governor Mode 0.06Hz
Inter-area mode at 0.49Hz (Colombia-
Ecuador). Opposing phase in South
Governor common-mode: whole
system oscillates in coherent phase
![Page 16: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control](https://reader036.fdocuments.us/reader036/viewer/2022081601/60eaa9b4d8c94d22cd210660/html5/thumbnails/16.jpg)
Islanding, Resynchronization and Blackstart
System split
Colour: Frequency
Vectors: Voltage Phasors
Identify islanding quickly
Alarm raised
Islands clearly visualized
Reduce time to resynchronize
Improve system visibility in
blackstart
Ice slide destroys 2 transmission
towers, IRB used to monitor system to
maintain synchronisation for 2 weeks
![Page 17: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control](https://reader036.fdocuments.us/reader036/viewer/2022081601/60eaa9b4d8c94d22cd210660/html5/thumbnails/17.jpg)
PSS Tuning & Generator Commissioning – Iceland (2006)
Mod
e A
mpl
itud
e (M
W)
Mode Decay Time Constant (sec)
1.2Hz Mode
Before PSS tuning After PSS tuning
PhasorPoint Oscillatory Stability Management:
• Wide area real-time damping visualization and alarms
• Dynamics baselining & trending
• Wide area event analysis
![Page 18: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control](https://reader036.fdocuments.us/reader036/viewer/2022081601/60eaa9b4d8c94d22cd210660/html5/thumbnails/18.jpg)
In distribution network, increase connection capacity by constraining by angle
Marginal reduction of
capacity factor
More capacity
More energy
Renewables Integration – Scotland (2012)
![Page 19: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control](https://reader036.fdocuments.us/reader036/viewer/2022081601/60eaa9b4d8c94d22cd210660/html5/thumbnails/19.jpg)
Wide Area Protection Scheme – Iceland (2012)
SW FREQ
E FREQ
Smelter load
132kV ring power
Main generation area
Loss of Large Smelter in SW
Frequency rises rapidly
Nearby generators change speed/angle quickly
Frequency rises more slowly
Trip Gen proportionally in correct zone
Angle difference increase
![Page 20: Practical PMU Applications for Utilities Presentation - Parashar.pdfPMU ‘Sub-second’ Resolution SCADA ‘Seconds ... data to calibrate dynamic power system models. Timely control](https://reader036.fdocuments.us/reader036/viewer/2022081601/60eaa9b4d8c94d22cd210660/html5/thumbnails/20.jpg)