Powerware 9125 9910 - P30
Transcript of Powerware 9125 9910 - P30
1p30.ppt rev 4.16.04
Powerware 9Powerware 91251259910 - P309910 - P30
High Performance
High Reliability & Availability
Flexible & Configurable
Advanced Communications
2
• Fourth-Generation Online™topology
• Advanced Battery ManagementPlus (ABM Plus™)
• Extended Battery Modules(EBMs)
• Load Segments• Two-in-One form factor• 2U rack-mount height• Hot-swappable batteries• X-Slot™• Power management software
bundle
Product SnapshotPower Rating: 3000VA/2100W Voltage: 120/208-240 VacFrequency: 50/60 Hz (auto-sensing)Configuration: use as rackmount or tower unit
P30 Features
3
P30 Applications
The P64 was specifically designed, engineered andapproved for IBM rack applications• iSeries and AS/400• pSeries and RS/6000• xSeries and other eServers• Storage and networking devices
9910 UPSs are ideal power protection foriSeries family of serversIBM x200IBM p660IBM p640
in rackIBM x220
4
Series 9 Power ProtectionThe P30 provides double-conversion online powerprotection from all 9 of the most common power problemsthat threaten your equipment and data
Power failures High voltage spikes
Power sags Frequency variations
Power surges Switching transients
Brownouts Harmonic distortion
Line noise
5
Utility Load
Internal Automatic Bypass
Battery
AC to DCRectifier
DC to ACInverter
Bi-DirectionalPower Converter
Filtering
• Wide input voltage range– Reduces battery usage– Reserves batteries for power failures--when you
need maximum runtime– Extends UPS service life– Reduces battery replacement costs
• EnergyShare– Under extremely poor utility conditions, P30 takes
power from both the utility and battery– Reduces battery usage– Extends runtime and service life of the battery
P30 Fourth-Generation OnlineTopologyTM
6
Energy Share
EnergyShare range: 120-160V(combined battery and utility)
Battery Power: <120V
Battery Power: >288V
Online voltage regulation: 160-288V
(no battery power needed)
Input Voltage RangeDuring extreme brownouts,the P30 provides an extralevel of protection; the UPS“shares” battery andincoming voltage to continueto provide ±3% of nominalvoltage
7
B CABM® Technology
• Doubles batteryservice life by chargingonly when needed
• Optimizes rechargetime
• Does not trickle chargeand starve the electrolyte
• Intelligent microprocessor controlled -Only true & automatic battery check (periodic, controlleddischarge) for most accurate advanced failure protection
• Sleep Feature - no unnecessary battery “drain”
8
Compact Design
By minimizing the size of the P30, you save rackspace for other equipment such as servers,storage, I/O and networking.
2U
Model shown in white for illustration only.
9
Informative User Interface
On Button(Start-On-Battery)
Overtemperature
Overload
Load Level/Battery LevelBypass Mode
Alarm Silence/Test Button Off Button
Battery Mode
Normal Mode(UPS On)
Site Wiring Fault
Self-Test
ReplaceBattery (ABM)
Note: rotate 90° for cabinet configuration
10
Load Segments
Individual control of two
Load Segments
• Power down sequencing of Load Segments– Extends runtime for critical devices
• Power up sequencing of Load Segments– Orderly power up of connected devices
• Scheduled on/off times– Turn off equipment for security and power conservation
12
2U
One EBM Two EBMs
Add EBMs to extend backup timeIn rack-mount configurations, each EBMoccupies only 2U (3.5 inches) of rack space
Extended Battery Modules
Models shown in white for illustration only.
14
P30 Battery RuntimesBattery Runtime (in minutes)*
Standard (Std)Watts Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
875 16 57 90 150 2001050 13 55 72 120 1601750 7 28 48 68 882100 5 25 38 54 70Rack Height 2U 4U 6U 8U 10U
* Up to 4 EBMs can be connected to the P30. EBM runtimes include P30 internal batteries. Runtime chart provides typicalinformation. Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.
15
P30 Rear Panel
X-Slot Communication Port
Network Transient Protector
Battery Connector
REPO port
(4) IEC-320-C13
IEC-320-C19
IEC-320-C20
16
Network Transient Protector provides protectionfrom “back door” disturbances that travel throughphone/network lines
REPO/Network TransientProtector
Shut down UPS remotely with REPO port;ideal for rack applications
17
• Replace or upgrade the UPS without powering downthe equipment
• Surge Protection in the Absence of UPS electronicsmodule during maintenance
• Individual load segment switched maximize back uptime for critical devices
• Designed to line-up and match the P30
PowerPass
Model shown in white for illustration only.
18
Powerware ExtensionsSoftware for IBM Director
• Seamless UPS and softwareintegration into IBM DirectorNetwork Management System(NMS)
• Real time monitoring,management and alarmnotification of all UPSs in thenetwork: e.g. battery status,battery replacement, load leveland metering information
• Automatically launches LanSafeand ConnectUPS Web/SNMPCard applications from withinDirector
• Available on Powerware web• FREE-OF-CHARGE
19
Powerware Software SuiteThe industry’s most comprehensive software bundle, The PowerwareSoftware Suite, is free and included with every P30.
Software Wizard guides you through softwareselection and installation. In addition to multimediademonstrations, product data sheets, and video clips,the Software Suite contains the following powermanagement software:• LanSafe™ Network UPS shutdown and monitoring
software• PowerVision® (30-day trial version) UPS performance
analysis and monitoring software• Foreseer® (demonstration) facility and data center
management software
Power Management Software
20
Software Application
Powerware Extensions for
Application LanSafe NetWatch IBM Director
Single pSeries (serial/TTY) non-LPAR !
Single pSeries (network) non-LPAR !* !*
Single pSeries (LPAR) !*
Multiple pSeries (non-LPAR) ! !*
Multiple pSeries (LPAR) !*
IBM Director Network Device !*
* Co-requisite FC 2934 ConnectUPS Web/SNMP network card.
Note: UPS for iSeries applications utilize OS/400 UPS monitoring functions.
21
Software Comparison
AmbientEmail/ SSL/SSH1 Temperature
Application Monitoring Shutdown GUI SMTP Security Humidity
LanSafe Yes Yes Yes Yes / Yes No/No No/No
NetWatch - Yes - No/No No/No No/No
ConnectUPS Web/ Yes2 Yes3 Yes Yes / Yes Yes / Yes Yes / Yes4
SNMP Card(FC 2934)1SSL = Secure Sockets Layer. SSH = Secure Shell. 2Via Web Browser, LanSafe or Network Management System (e.g.IBM Director, Tivoli). 3In conjunction with NetWatch software. 4With optional FC 2938 EMP (Environmental MonitoringProbe) device attached.
22
ConnectivityWhat you need by application
Software Solution zSeries iSeries pSeries xSeries Storage Networking
LanSafe ! !
LanSafe and ConnectUPS ! !MultiServer card (IBM FC 2933)
NetWatch and ConnectUPS ! !! ! ! !Web/SNMP card (IBM FC 2934) LPARs
Powerware Extensions for ! ! ! IBM Director
NetWatch ! ! ! ! !
ConnectUPS Relay card andAS/400 cable (IBM FC 2936) !!Use ConnectUPS Web/SNMP/xHub card, IBM FC 2934 to support LPAR (POWER 4 Chip Set) servers. For pSeriesconfigurations, each LPAR needs a network connection and will install Powerware provided NetWatch or LanSafesoftware.
23
P30 Collateral
• Additional information available atwww.oem.powerware.com/ibm-ups– Select your region. Click “Products”, click “9910
Solutions” then click “Powerware pSeries” or“Powerware iSeries”
• Materials available– Data sheet– Application overview chart– Product presentation– Documents (manuals)