PowerPoint Presentation...29. Assertion (A): A synchronous motor is not inherently self starting....
Transcript of PowerPoint Presentation...29. Assertion (A): A synchronous motor is not inherently self starting....
ashishsoniwifistudy
1. If the speed of rotation of a dynamo is doubled, then
the induced emf will: [LMRC 2015]
a) become half
b) become double
c) become four times
d) remain unchanged
2. An exciter for a turbo generator is a: [LMRC 2015]
a) separately excited generator
b) shunt generator
c) series generator
d) compound generator
3. On which of the following parameters does the
power factor of an alternator depend? [UPRVUNL 2014]
a) Load
b) Speed or rotor
c) Core losses
d) Armature losses
4. Consider the following figure for a 4-pole, 3-phase,
24-slots double layer winding. Find the pole pitch and
the slot pitch angle. [UPRVUNL 2014]
a) 4 and 40 electrical degrees
b) 5 and 50 electrical degrees
c) 6 and 30 electrical degrees
d) 6 and 60 electrical degrees
5. If the excitation of an alternator operating in parallel
with other alternator is increased above the normal
value of excitation, its [SSCJE 2014]
a) Power factor becomes more lagging
b) Power factor becomes more leading
c) Output current decreases
d) output k W decreases
6. In an alternator, the effect of armature reaction is
minimum at power factor of [SSCJE 2014]
a) 0.5 lagging
b) 0.866 lagging
c) 0.866 leading
d) unity
7. Direction of the alternating e.m.f. produced in the
stator conductors of an alternator is given by [BSNL TTA
2016]
a) Lenzβs law
b) Flemings left hand rule
c) Flemingβs right hand rule
d) Kirchhoffβs Law
8. In a synchronous machine when the rotor speed
becomes more than the synchronous speed during
hunting, the damping bars develop [BSNL TTA 2016]
a) Synchronous motor torque
b) D.C. motor torque
c) Induction motor torque
d) Induction generator torque
9. The disadvantages of hunting in synchronous
machines is [ESE 2019]
a) fault occurs in the supply system.
b) causes sudden change in inertia.
c) causes large mechanical stresses and fatigue in the
rotor shaft.
d) causes harmonics.
10. A synchronous motor has 12-poles and operates
from 440V, 50Hz supply. If it takes a line current of 100A
at 0.8 power factor leading, its speed and torque are
nearly [ESE 2019]
a) 500 rpm and 1165N-m
b) 1000 rpm and 2330 N-m
c) 500 rpm and 2330 N-m
d) 1000 rpm and 1165 N-m
11. Which of the following is NOT an application of
synchronous motors? [ESIC 2019]
a) Reciprocating compressor drivers
b) Variable speed applications
c) Voltage regulation
d) Power factor correction
12. Identify the INCORRECT statement from below with
regard to synchronous motors [ESIC 2019]
a) Synchronous motors are inherently not self-starting
b) for a given frequency a synchronous motor will run
at constant average speed regardless of load
c) DC excitation is not required by synchronous motors
but required by induction motors
d) Synchronous motors can be operated over wide
range of power factors (both lagging and leading)
13. The maximum torque which the motor can develop
without pulling out of step or synchronism is called:
[ESIC 2019]
a) Starting torque
b) Pull out torque
c) Running torque
d) Pull in torque
14. Which of the following statements is true? [ESIC
2019]
a) The motoring machine draw a lagging power factor
current when over-excited
b) The generating machine supplies a lagging power
factor current when over-excited.
c) The generating machine supplies a lagging power
factor current when under-excited.
d) The motoring machine draws a leading power
factor current when under-excited.
15. Apart from the ability to operate under both
leading and lagging power factors, which among the
following is an advantage of a Synchronous motor?
[BSPHCL JE 2019]
a) Lower cost
b) Constant speed
c) Self-starting
d) Can be used for high speed drives
16. A salient pole synchronous motor is running at no
load. Its excitation is reduced to zero? [SAIL (RSP) OCTT
2019]
a) It will stop
b) It will remain running at synchronous speed
c) It will loose synchronism
d) It is uncertain
17. The mechanical power developed by synchronous
motor is independent of? [HPCL A.M.T. 2019]
a) speed
b) field excitation
c) applied stator voltage
d) torque angle
18. In which of the following conditions will a 3-phase
synchronous machine works as a capacitor? [UPPCL
J.E. 2018, SSC-JE 2018, DMRC, 2018, DMRC JE Electrical
2017, UPURVUNL 2014, MP JE 2016, SSC JE 2014, MPJE
2016]
a) None of these
b) Critically Excited
c) Under Excited
d) Over Excited
19. In a three phase synchronous motor, if one of the
winding is short circuited then the motor will [SSC-JE
2018, IOF 2014, SSC JE Electrical 2017]
a) run at ΒΌ of synchronous speed
b) not start
c) run with excessive vibrations
d) rotate at less than the rated load
20. Synchronous motor will stop when [SSC-JE 2018]
a) load in motor varies
b) supply voltage fluctuates
c) excitation winding gets disconnected
d) supply voltage frequency changes
21. While starting a synchronous motor as induction
motor, field winding is [SSC-JE 2018]
a) kept open-circuited
b) short-circuited by low resistance
c) connected to D.C. supply
d) None of these
22. In a synchronous motor, the negative phase
sequence exists when the motor is [SSC-JE 2018, SSCJE
2009]
a) under-loaded
b) supplied with unbalanced voltage
c) over-loaded
d) None of these
23. If the synchronous motor, properly synchronized to
the supply is running on no load and is having
negligible loss then [SSC-JE 2018]
a) the stator current will be very small
b) the stator current will be zero
c) the stator current will be very high
d) the back e.m.f. will be more than the supply voltage
24. A synchronous motor operates at rated voltage
and frequency and has a load torque angle of 30Β°. If
both the terminal voltage and frequency are reduce
by 10%, then [ESE 2015]
a) the load torque angle remains the same
b) the load torque angle increases
c) the load torque angle decreases
d) nothing can be said about the torque angle
25. The synchronous reactance of a 500 V, 50 kVA
alternator having an effective resistance of 0.2 Ξ©, if an
excitation current of 10 A produces 200 A armature
current on short circuit and an emf of 450 volts on
open circuit, is [ESE 2014]
a) 2.6 Ξ©
b) 5.2 Ξ©
c) 2.24 Ξ©
d) 4.5 Ξ©
26. A 3-phase synchronous motor with constant
excitation is driving a certain load drawing electric
power from infinite bus at leading power factor. If the
shaft load decreases [ESE 2012]
a) the power angle decreases while power factor
increases.
b) the power angle increases while power factor
decreases.
c) both power angle and power factor increase.
d) both power angle and power factor decrease.
27. A synchronous generator connected to an infinite
bus is supplying electrical power at unity power factor
to the bus. If the field current is increased [ESE 2012]
a) both the active and reactive power output of the
machine will remain unchanged.
b) the active power of the machine will remain
unchanged but the machine will also supply lagging
reactive power.
c) the active power output of the machine will
increase and the machine will draw leading reactive
power from the bus.
d) the active power output of the machine will remain
unchanged but the machine will also supply leading
reactive power.
28. Assertion (A): In a certain case of load change, an
alternator became unstable and pulled-out. [ESE 2011]
Reason (R): In an alternator, damper winding is
present.
a) Both A and R are true and R is the correct
explanation of A
b) Both A and R are true but R is NOT the correct
explanation of A
c) A is true but R is false
d) A is false but R is true
29. Assertion (A): A synchronous motor is not inherently
self starting. [ESE 2010]
Reason (R): At standstill the rotor of a synchronous
motor is subjected to alternate forces of repulsion and
attraction.
a) Both A and R are true and R is the correct
explanation of A
b) Both A and R are true but R is NOT the correct
explanation of A
c) A is true but R is false
d) A is false but R is true
30. Consider the following: [ESE 2010]
1. EMF
2. Reversal
3. MMF
4. Direct
Which methods among these are for the determination
of voltage regulation of an alternator?
a) 1, 2, 3 and 4
b) 1 and 2 only
c) 2 and 3 only
d) 1 and 3 only
1. Power factor of an alternator driven by constant
prime mover input can be changed by changing its
[ESE 2010]
a) Speed
b) Load
c) Field excitation
d) Phase sequence
2. What is the effect of the field failure of salient pole
synchronous motor connected with infinite bus? [ESE
2009]
a) Reduces motor torque and speed
b) Not change motor torque and speed
c) Stop the motor
d) Reduces motor torque but motor will continue to run
at synchronous speed
3. Consider the following:
1. L.P.F. method
2. E.M.F. method
3. Z.P.F. method
4. M.M.F. method
Which of the above methods are correct for
determination of voltage regulation of an alternator?
[ESE 2009]
a) 1, 2 and 3
b) 2, 3 and 4
c) 2 and 3 only
d) 3 and 4 only
4. Which of the following conditions are to be satisfied
for proper synchronization of alternators? [ESE 2008]
1. Equal terminal voltage
2. Same frequency
3. Same phase sequence
4. Same kVA rating
5. Same phase displacement
Select the correct answer using the code given below:
a) 1, 3 and 4
b) 1, 2, 4 and 5
c) 2, 3, 4 and 5
d) 1, 2, 3 and 5
5. If the excitation of a 3-phase alternator operating on
infinite bus bars is changed, which one of the following
shall alter? [ESE 2008]
a) Active power of machine
b) Reactive power of machine
c) Terminal voltage of machine
d) Frequency of machine
6. The stator of a 3-phase, 6-pole a.c. machine has 45
slots. The stator winding has 45 coils with a coil span of
6 slots. What type of winding will be selected for this
machine? [ESE 2008]
a) Double-layer, fractional slot, short-pitched winding
b) Single-layer, fractional slot, short-pitched winding
c) Single-layer, integral slot, full-pitch winding
d) Double-layer, fractional slot, full-pitch winding
7. A three phase 50 Hz, 11 kV and 37.5 MW at 0.9 p.f.
capacity synchronous generator has its stator core
diameter of 765 cm and an axial core length of 80 cm.
For which power plant this generator is suitable? [ESE
2009]
a) Thermal coal fired plant
b) Hydroelectric power plant
c) Nuclear power plant
d) Pumped storage power plant
8. Assertion (A): AC armature windings are short
chorded by selecting value of coil span more than the
pole pitch.
Reason (R): Short chording is done to eliminate
harmonics in the induced e.m.f. [ESE ]
a) Both A and R are true and R is the correct
explanation of A
b) Both A and R are true but R is NOT the correct
explanation of A
c) A is true but R is false
d) A is false but R is true
9. Assertion (A): For a 3-phase alternator operating on
leading p.f. at full load, the terminal voltage may be
more than the no-load induced e.m.f.
Reason (R): At leading power factor, the effect of
armature reaction is demagnetizing. [ESE 2008]
a) Both A and R are true and R is the correct
explanation of A
b) Both A and R are true but R is NOT the correct
explanation of A
c) A is true but R is false
d) A is false but R is true
10. Match List-I (Machine characteristic) with List-II
(Quantity) and select the correct answer using the
code given below the lists: [ESE 2008]
List-I List-IIA. Open-circuit characteristic 1. π. π. π―π¬. ππB. V-curve 2. ππ π―π¬. ππC. Internal characteristic 3. ππ π―π¬. ππD. Inverted V-curve 4. ππ π―π¬. ππCodes:
A B C D
a) 3 1 2 4
b) 2 4 3 1
c) 3 4 2 1
d) 2 1 3 4
11. A 10 pole, 25 Hg alternator is directly couple to and
is driven by 60 Hz synchronous motor. What is the
number of poles for the synchronous motor? [ESE 2007]
a) 48
b) 12
c) 24
d) 16
12. Consider the following statements:
Assertion (A): Large synchronous machines are
constructed with armature winding on stator.
Reason (R): Stationary armature winding would have
reduced armature reactance.
Of these statements [ESE 2007]
a) Both A and R are true and R is the correct
explanation of A
b) Both A and R are true but R is not the correct
explanation of A
c) A is true but R is false
d) A is false but R is true
13. The resultant flux density in the air gap of a
synchronous generator is the lowest during [ESE 2006]
a) Open circuit
b) Solid short circuit
c) Full load
d) Half load
14. A loss-less cylindrical rotor synchronous generator
is floating on the system bus-bar after being properly
synchronised and is running at no-load. Now, if the
prime mover is acting as a mechanical load on the
machine, then [ESE 2006]
a) the torque developed by the machine will act in the
same direction as the prime-mover torque.
b) the torque developed by the machine will act in the
opposite direction to that of the prime-mover torque.
c) the machine rotor would fall-back and the induced
emf would lag behind the terminal voltage.
d) the machine rotor would overspeed and the
induced emf would lead the terminal voltage
15. Which one of the following statement is not correct
in respect of synchronous machines? [ESE 2006]
a) In salient pole machines, the direct-axis
synchronous reactance is greater than the quadrature
axis synchronous reactance.
b) The damper bars help the motor to self-start.
c) Short circuit ratio is the ratio of field current required
to produce the rated voltage on open circuit to the
rated armature current.
d) The V-curve of a synchronous motor represents the
variation in the armature current with field excitation at
a given output power.
16. What is the value of the load angle when the power
output of a salient pole synchronous generator is
maximum? [ESE 2006]
a) 0Β°
b) 45Β°
c) 90Β°
d) None of these
17. In the measurement of ππ, ππͺ (in ohms), following
data are obtained by the slip test on a salient pole
machine: [ESE 2005]
ππmax = 10 A ππ min = 6.5 A
ππ max = 30 V ππ min = 25 V
Which one of the following is correct?a) ππ = π, ππͺ = π. ππ
b) ππ = π. πππ, ππͺ = π. π
c) ππ = π, ππͺ = π. π
d) ππ = π. ππ, ππͺ = π. ππ
18. A synchronous motor is operated from a bus
voltage of 1.0 p.u. and is drawing 1.0 p.u. zero power
factor leading current. Its synchronous reactance is 0.5
p.u. What is the excitation emf of the motor? [ESE 2005]
a) 2.0
b) 1.5
c) 1.0
d) 0.5
19. Assertion (A): If the load requirement of a
synchronous motor exceeds the pull-out torque, the
synchronous motor action is lost.
Reason (R): Rotor and stator fields are no longer
stationary with respect to each other. [ESE 2004]
a) Both A and R are true and R is the correct
explanation of A
b) Both A and R are true but R is NOT the correct
explanation of A
c) A is true but R is false
d) A is false but R is true
20. Assertion: A synchronous motor operating from
constant voltage and constant frequency source has a
substantially constant resultant air-gap flux.
Reason (R): If the d.c. field current in this motor can set
up the required resultant air-gap flux, the lagging
reactive volt-amperes drawn from a.c. source is zero.
[ESE 2004]
a) Both A and R are true and R is the correct
explanation of A
b) Both A and R are true but R is NOT the correct
explanation of A
c) A is true but R is false
d) A is false but R is true
SSC JE-2019
Benefits
Personalized Learning: -
Regular PDF update
(28) In a steam power plantβ¦β¦β¦β¦heats the feed water on its way to the boiler by
delivering heat from the flue gases: -
(A) Superheater (B) Economizer
(B) Preheater (D) Turbine
(29) Power generation of thermal power plants is based on: -
(A) Rankine cycle
(B) Otto cycle
(C) Diesel cycle
(D) Carnot cycle