ABB Control Inc. 2.1AC 1700 – 5/00
PowerLineCompact, heavy dutyFusible disconnect switches30A – 800A, 600V
ABB PowerLine includes seven different amperage sizesfrom 30A to 800A. All PowerLine fusible switches aredesigned to meet customer requirements in terms of highinterrupting capacity and long electrical life while occupyinglittle more panel space than the appropriate fuses. Thebasic construction provides flexibility and high performancein an extremely compact size. ABB PowerLine switches area perfect choice to withstand the heat and humidity of thetropics, the extreme cold of the arctic and any ruggedindustrial environment you may have.
ION
OOFF
Fu
sible
2.2 ABB Control Inc.AC 1700 – 5/00
Overviewfor Fusible disconnect switchesOS30ACC12 – OES800L3
Catalog number 3 pole OS30ACC12 OS30AJ12 OS60J12 OS100J03 OES200J3 OES400J3 OES600J3 OES800L3
UL listed, CSA approved, IEC rated, CE markedS = Standard• = Available— = Not available
FOverview
General purposeamp rating A 30 30 60 100 200 400 600 800Catalog reference Page # 2.11 2.11 2.17 2.17 2.23 2.23 2.23 2.23
Approvals1
2 pole N/A N/A N/A UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC3 pole UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC4 pole UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC
Technical ratings(UL,CSA)
Max operating voltage V 600 600 600 600 600 600 600 600
Max horsepower ratingThree phase
200 – 208V HP 5/7.5 5/7.5 15 25 50 100/125 150 200240V HP 7.5 7.5 15 30 60 125 200 250480V HP 15 15 30 60 125 250 400 500600V HP 20 20 50 75 150 350 500 600
Single phase120V HP 2 2 — — — — — —240V HP 3 3 — — — — — —
UL fuse class CC J J J J,T J,T J,T L
Technical ratings(IEC)
Rated insulation and operationalvoltage. AC20 and DC20 1000 1000 1000 1000 1000 1000 1000 1000
Rated thermal current, IthAC 20/DC 20 open A 32 32 63 160 200 400 630 800AC 20/DC 20 enclosed A 32 32 63 160 200 400 600 720
AC 21A 500V A 32 32 63 160 200 400 630 800690V A 32 32 63 160 200 400 630 800
Rated operational power AC23400/415V kW 14/15 14/15 30 80/90 100/110 210/230 315/340 350/380690V kW 25 25 60 132 180 330 540 600
Physical characteristics
Weight 3 pole switch lb 1.54 1.54 2.86 3.30 15.20 17.18 37.44 37.444 pole lb 1.98 1.98 3.52 3.96 17.4 19.38 46.26 46.26
Dimension 3 pole H in 3.66 3.60 3.94 5.67 7.87 8.90 10.10 10.10W in 4.15 4.15 5.63 7.07 10.32 11.26 14.80 14.80D in 4.10 4.10 5.04 5.10 7.80 8.07 9.17 9.17
Accessories
Double break contacts S S S S S S S S
Fuse cover S S S S S S S S
Terminal lug kit Integral Integral Integral OZXA-24 OZXA-25 OZXA-26 OZXA-27 OZXA-27
Terminal shroud Not required Not required Not required • • • • •Auxiliary contact • • • • • • • •Handle UL/NEMA type
Type 1, 3R, 12 • • • • • • • •Type 1, 3R, 4, 4X, 12 • • • • • • • •
Conversion kit6 pole • • • • • • • •Transfer • • • • • • • •Bypass — — — — • • • •Mechanical interlock • • • • • • • •
Electrical interlock — — — — • • • •
OS30A_12 OS60J12 OS100J03 OES200J3 OES400J3 OES600J3 OES800L3
1 UL listed switches are also CSA approved.
ION
OOFF
Fu
sib
le
ABB Control Inc. 2.3AC 1700 – 5/00
General informationfor Fusible disconnect switches
VersatilityABB PowerLine fusible disconnect switches are designed to offer maximum versatility inmany ways.
Broad rangePowerLine is seven amperage sizes from 30A – 800A. All sizes are compact, heavy duty,600V disconnect switches. Many sizes are available in 2, 3, 4, 6, and 8 poleconfigurations.
Compact sizeThe PowerLine’s unique compact dimensions allow panel size reduction in newapplications or easily retrofits into space-sensitive existing applications. The entire switchoccupies little more panel space than the appropriate fuses.
International acceptancePowerLine fusible switches are available with a wide range of fuse clip options:
UL USA CSA CanadaDIN Europe BS United KingdomNFC France Ultra-rapid
As well as the corresponding approvals: UL listed, CSA approved, IEC rated, CE marked, andmost other international standards.UL98 (CSA 22.2 No.4) — UL File # E101914, CSA File #LR58077For 30A – 800A switches, OH__ pistol grip handlesSuitable for use as motor disconnects or industrial control panel disconnects on service entranceequipment, panelboards, switchboards, industrial control equipment, motor control centers, etc.and are horsepower rated and ampere rated.IECTested in accordance to IEC 947-1 and 3, IEC 664, IEC 269, and IEC 204CECompliance with the European Machine Directive IEC 204 (EN 60204)
Installation optionsRotary through the door: available in all sizes, 30A – 800AFlange: versions available in 30A, 60A & 100A sizesA rotary disconnect switch may be installed nearly anywhere in a control panel — mountingis not limited to the upper right hand corner of the panel.Mount the switch where it conveniently fits in your panel and simply install the handle on thedoor, in line with the switch. The switch and handle are mechanically linked through aneasily adjusted shaft. This allows fast and easy installation into panels of different depthsand layouts.
FGeneral
Information
Tota
l ins
talle
d co
sts
Traditionalswitches
ABBswitches
Cost reductionSwitches
Accessories
Installation
Space
Rotary through the door installation Easily adjusted shaft
OOFF
ION
NOI
OO
FF
ION
OOFF
Fu
sible
2.4 ABB Control Inc.AC 1700 – 5/00
General informationfor Fusible disconnect switches
Broad range of accessories• Handles — UL/NEMA type 1, 3R, 4, 4X, 12
IP 54, 65, 66• Auxiliary contacts available for every switch size• Additional terminal poles (neutrals & grounds)• Terminal shrouds• 6 & 8 pole mechanisms• Transfer mechanisms• Bypass mechanisms• Mechanical interlock mechanisms• Electro-mechanical interlock mechanisms• Motor operators
MountingPowerLine disconnect switch mounting possibilities:
• DIN rail mounting — OS30, OS60 & OS100• Base mounting with screws
DIN rail mounting
Base mounting with screws
FGeneral
Information
Incoming power feedsAll PowerLine disconnectswitches can beused equally wellwith either top orbottom incomingpower feeds.
Terminal connectionsVersatile connecting possibilities, 100A – 800A:
• Ring tongue crimp on lugs• Direct bus• Terminal lugs
Top feed
Bottom feed
I
O
NOI
OO
FF
ION
OOFF
Fu
sib
le
ABB Control Inc. 2.5AC 1700 – 5/00
General informationfor Fusible disconnect switches
1 Please consult ABB sales office for additional information
High performanceThe mechanism is quick-make/quick-break, meaning thecontacts operate independently of the speed and force atwhich the handle is operated. This, in combination with unique,patented self-cleaning contacts, provides a long, reliable,electrical life.
FGeneral
Information
Modular construction1
Modular switch construction allows the operating mechanism tobe placed at either end of the switch or anywhere in-between,100A – 800A.
Mounting positionsPowerLine disconnect switches may be mountedin any position:
Vertical Horizontal Ceiling Floor
Unique terminal locations1
• Side connections• Rear connections• Bus stabs
34 42
54 64
I
O
I
O
ION
OOFF
ION
OOFF
Fu
sible
2.6 ABB Control Inc.AC 1700 – 5/00
Superior short circuit protectionFuses efficiently limit the peak let-through current, i2t,during a fault better than any other product, contributing tosafety and reliability. Selectivity and coordination are easilyaccomplished with fused protection. PowerLine fusibledisconnect switches accept a wide range of North Americanfuses:
Class CC 30AClass J 30A – 600AClass L 800AClass T 200A – 800A
Finger proofDead-front construction plus terminal shrouds reduce the risk oftouching live parts, improving the safety and reliability of theinstallation.
Fuse isolationPowerLine switches contain contacts on both sides of the fuse. Thefuses are totally isolated in the “OFF” position, reducing the risk of shockto authorized personnel — even if the switch has been back fed.
General informationfor Fusible disconnect switches
Positive opening operationAll switches operate according to the “positive opening operation” principle.This means the contacts are opened and closed by a driven mechanism, asolid moving bridge, not merely springs. This provides reliable positionindication to the user; if the switch is in the “OFF” position, the contacts areopen.
Positive opening operation
NOIO
OFF
FGeneral
Information
Superior short circuit protection
Fuse isolation
Fuse Circuit breaker
ION
OOFF
Fu
sib
le
ABB Control Inc. 2.7AC 1700 – 5/00
Welded contact protectionPositive opening operation safeguards users in case of welded contacts due to anoverload or short circuit.The switch can not reach the “OFF” position unless the contacts are truly open. If anyor all of the contacts are welded shut, the switch mechanism will only allow the handleto operate a maximum of 45o. This safeguards personnel by:
• alerting them a problem has occurred• maintaining the door interlock and• not allowing a padlock to be inserted.
General informationfor Fusible disconnect switches
Clear position indicationAll switches and handles have clear “ON” and “OFF” designations. Whetherthe door is open or closed, it is possible to simply look at the switch anddetermine if the switch is “ON” or “OFF”.
Door interlockThe handle and shaft provide door interlock, the door can not beopened when the switch is in the “ON” position. NOTE: Somehandles provide a method for qualified personnel to circumvent thedoor interlock. This is commonly referred to as a “defeater”mechanism.
PadlockableHandles can be padlocked in the “OFF” position with up to threepadlocks; additionally, the switch mechanism can be directlypadlocked in the “OFF” position when the door is open. NOTE:Some handles can be ordered with the ability to padlock in both the“ON” & “OFF” positions. Please consult your ABB sales office forordering information.
Door interlock
FGeneral
Information
Handle and mechanism padlocked OFF
Track resistant materialExcellent track resistant material, CTI > 600V, IEC112, reduces the risk of flashover between phasesin even the most severe circumstances.
Window forviewing blades
Visible bladesVisible blades offer an additional safety featurefrom 200A – 800A.
ON
OFF
45°Max
NOI
OO
FF
NOI
OO
FF
NOI
OO
FF
MAIN SWITCH
ION
OOFF
Fu
sible
2.8 ABB Control Inc.AC 1700 – 5/00
Environmentally friendlyABB products are designed and manufactured using environmentally-friendly practices,according to ISO 14001:
• Heavy metals are avoided — cadmium is not used in contacts• Plastic used in switches is recyclable• Product packaging is constructed using recycled/recyclable materials• Electroplating is centralized in one location
SFS has granted ABBControl a certificate asproof the environmentalmanagement systemcomplies with therequirements ofSFS-EN ISO 14001.
General informationfor Fusible disconnect switches
FGeneral
Information
ABB Control Inc. 2.9AC 1700 – 5/00
ION
OOFF
Fu
sib
le
IndexKits .............................................................................................................2.10Kit components ........................................................................................... 2.10
Kitsfor Fusible disconnect switches30A – 800A, 600VUL fuse Class J, CC, T, L
2.10 ABB Control Inc.AC 1700 – 5/00
ION
OOFF
Fu
sible
Kits with selector handles
Each kit includes:
1 three pole switch
1 handle
1 shaft
1 terminal lug kit
If other handles or shafts are desired, please order from the individual component pages 2.11 – 2.28.
FKits
30A – 800A
30 J 5 7.5 7.5 15 20 OSJ30B2A1-180 $ 31430 CC 5 7.5 7.5 15 20 OSC30B2A1-180 314
UL ULgeneral Fuse
Maximum horsepower rating Kit
purpose type Three phase catalog List
amp rating 600V 200V 208V 240V 480V 600V number price
Kits with pistol handles
Components for kits with selector handles
Kitcatalog Catalog NEMA De- Handle Mounting Length Shaft
number number type Marking feat- catalog depth5(inches/mm) catalog Wire Wire Catalog
able number (inches) number size type number
OSJ30B2A1-180 OS30AJ12 1, 3R, 12 I/O & Off/On — OHB2AJ1 6.3 - 9.5 7.1/180 OXS5X180 #18 – 8 Cu IntegralOSC30B2A1-180 OS30ACC12 1, 3R, 12 I/O & Off/On — OHB2AJ1 6.3 - 9.5 7.1/180 OXS5X180 #18 – 8 Cu Integral
Kitcatalog Catalog NEMA De- Handle Mounting Length Shaft
number number type Marking feat- catalog depth5(inches/mm) catalog Wire Wire Catalog
able number (inches) number size type number
OSJ30B6-150 OS30AJ12 1, 3R, 12 I/O & Off/On Yes OHB65J5 5.3 - 8.3 5.9/150 OXP5X150 #18 – 8 Cu IntegralOSC30B6-150 OS30ACC12 1, 3R, 12 I/O & Off/On Yes OHB65J5 5.3 - 8.3 5.9/150 OXP5X150 #18 – 8 Cu Integral
OSJ60B6-150 OS60J12 1, 3R, 12 I/O & Off/On Yes OHB65J6 5.5 - 8.5 5.9/150 OXP6X150 #14 – 4 Cu IntegralOSJ100B6-150 OS100J03 1, 3R, 12 I/O & Off/On Yes OHB80J6 5.5 - 8.5 5.9/150 OXP6X150 #14 – 2/0 Cu/Al OZXA-24
OSJ200B4-280 OES200J3 1, 3R, 12 I/O & Off/On Yes OHB145J12 7.9 - 12.2 8.7/220 OXP12X280 #6 – 300kcmil Cu/Al OZXA-25OSJ400B4-280 OES400J3 1, 3R, 12 I/O & Off/On Yes OHB145J12 7.9 - 12.2 8.7/220 OXP12X280 #2 – 600kcmil Cu/Al OZXA-26OSJ600B4-280 OES600J3 1, 3R, 12 I/O & Off/On Yes OHB145J12 11.2 - 14.0 11.0/280 OXP12X280 (2) #2 – 600kcmil Cu/Al OZXA-27OSL800B4-280 OES800J3 1, 3R, 12 I/O & Off/On Yes OHB145J12 11.2 - 14.0 11.0/280 OXP12X280 (2) #2 – 600kcmil Cu/Al OZXA-27
Kit
Components for kits with pistol handles
handle
shaft
switch
terminal lug kit2
1 Other pole configurations available. Please see the individual component pages.2 30A and 60-A fusible switches include standard integral terminal lugs.3 J type fuse clips are standard. If 600V Type "T" fuse clips are desired, please select a fuse adapter kit from the individual component pages.4 All handles are black and accept three padlocks. For others, please see the individual component pages.5 Mounting depth is the distance from the outside of the door to the disconnect switch mounting plate. Shaft can be cut to desired length.
Switch Handle4 Shaft Terminal lugs
Switch Handle4 Shaft Terminal lugs
UL ULgeneral Fuse
Maximum horsepower ratingKit
purpose typeThree phase catalog List
amp rating 600V 200V 208V 240V 480V 600V number price
30 J 5 7.5 7.5 15 20 OSJ30B6-150 $ 37430 CC 5 7.5 7.5 15 20 OSC30B6-150 374
60 J 15 15 15 30 50 OSJ60B6-150 472100 J3 25 25 30 60 75 OSJ100B8-150 646
200 J3 50 50 60 125 150 OSJ200B4-280 1586400 J3 100 125 125 250 350 OSJ400B4-280 2176600 J3 150 150 200 400 500 OSJ600B4-280 3406800 L 200 200 250 500 600 OSL800B4-280 5266
Discount schedule H4: F, 30A – 100ADiscount schedule H5: F, 200A – 800A
Kits for Fusible disconnect switches30A – 800A, 600V, 3 pole1
UL fuse class J, CC, T, L
ABB Control Inc. 2.11AC 1700 – 5/00
ION
OOFF
Fu
sib
le
IndexSwitches, 30A ............................................................................................... 2.12Handles
Selector ..................................................................................................... 2.12Pistol .......................................................................................................... 2.13
Shaftsfor selector handles ................................................................................... 2.12for pistol handles ....................................................................................... 2.13
AccessoriesAuxiliary contacts ...................................................................................... 2.14DIN rail ...................................................................................................... 2.14Direct mount handle .................................................................................. 2.13Fuse carriers ............................................................................................. 2.14Mounting base (for auxiliaries) .................................................................. 2.14Terminal cover........................................................................................... 2.14Terminal pole............................................................................................. 2.14
Conversion mechanisms .............................................................................. 2.15 6 or 8 pole Transfer Mechanical interlock
Fuse monitor ................................................................................................ 2.38
30AFusible disconnect switchesBase & DIN rail mountedUL fuse Class J, CC
➱NEW!!
2.12 ABB Control Inc.AC 1700 – 5/00
ION
OOFF
Fu
sible
30A Fusible disconnect switchesBase & DIN rail mountedUL fuse Class J,CC
For a complete assembly,please select one of each:
1 switch1 handle1 shaft
30 Amp switches, 600V
1 Rejection style fuses only.
UL UL Maximum horsepower rating Terminal lugs
general Fuse Three phasepurpose type Wire Wire Catalog List
amp rating 600V 200V 208V 240V 480V 600V size type number price
Selector handles — for use with shafts .20 x .20" ( 5 x 5 mm)
UL/NEMA IEC Color Defeat- Padlock- Weight Catalog Listtype type able able (lbs.) number price
3.3/85 5.5 – 5.7 0.04 OXS5X85 $ 44.1/105 5.5 – 6.5 0.04 OXS5X105 44.7/120 5.5 – 7.1 0.05 OXS5X120 45.1/130 5.5 – 7.5 0.05 OXS5X130 67.1/180 6.3 – 9.4 0.08 OXS5X180 69.8/250 9.1 – 12.2 0.10 OXS5X250 1213.0/330 12.2 – 15.4 0.14 OXS5X330 20
Shaft length Mounting depth1 Weight Catalog List(inches/mm) (in inches) (lbs.) number price
Shafts — for use with OH_2_ selector handles .20 x .20" ( 5 x 5 mm)
OS30A__12
OHY2__
OXS5X__
All marked both O/I & Off/On
1,3R,12 IP65 Black — Yes 0.16 OHB2AJ1 $ 281,3R,12 IP65 Red/Yel — Yes 0.16 OHY2AJ1 28
1,3R,12 IP65 Blk Yes Yes 0.16 OHB2AJ 301,3R,12 IP65 Red/Yel Yes Yes 0.16 OHY2AJ 30
OS30AJ12 + OXS5X180 + OHB2AJ1
OHB2__
3 pole 3 pole
30 J 5 7.5 7.5 15 20 #18 – 8 Cu OS30AJ12 $ 280301 CC 5 7.5 7.5 15 20 #18 – 8 Cu OS30ACC12
4 pole 4 Pole
30 J 5 7.5 7.5 15 20 #18 – 8 Cu OS30AJ22F 350301 CC 5 7.5 7.5 15 20 #18 – 8 Cu OS30ACC22F
F30A
Discount schedule H4: F, 30A – 100ADiscount schedule H6: Handles, shafts, accessories
ABB Control Inc. 2.13AC 1700 – 5/00
ION
OOFF
Fu
sib
le
Handles & shaftsfor 30A fusible disconnect switches
For a complete assembly,please select one of each:
1 switch1 handle1 shaft
OHB5
OHB5 Mounted
OHB5 Mounted depth
5.20"132mm
Pistol handles — for use with shafts .20 x .20" ( 5 x 5 mm)
UL/NEMA IEC Color Marking Length Defeat- Padlock- Weight Catalog Listtype type inches/mm able able (lbs.) number price
Shafts — for use with pistol handles .20 x .20" ( 5 x 5 mm)
Direct mount handle — mounts directly to switch, no shaft necessaryUL/NEMA Color Marking Length Padlockable Weight Catalog List
type mm (lbs.) number price
1 Blk O/I/Test 50 Yes 0.10 OHB5 $ 60
OS30AJ12 + OXP5X170 + OHB65J5
OHB_J5
1,3R,12 IP65 Black O/I & Off/On 1.8/45 Yes Yes 0.28 OHB45J5 $ 701,3R,12 IP65 R/Y O/I & Off/On 1.8/45 Yes Yes 0.28 OHY45J5 701,3R,12 IP65 Black O/I & Off/On 2.6/65 Yes Yes 0.29 OHB65J5 801,3R,12 IP65 R/Y O/I & Off/On 2.6/65 Yes Yes 0.29 OHY65J5 80
1,3R,4,4X,12 IP65 Black O/I & Off/On 2.6/65 Yes Yes 0.29 OHB65L5 1201,3R,4,4X,12 IP65 R/Y O/I & Off/On 2.6/65 Yes Yes 0.29 OHY65L5 120
1,3R,12 IP65 Black Off/On/Test 2.6/65 Yes Yes 0.29 OHB65J5T 1001,3R,12 IP65 R/Y Off/On/Test 2.6/65 Yes Yes 0.29 OHY65J5T 100
Discount schedule H6: Handles, shafts, accessories
OXP5X__
OHY_J5
F30A
5.9/150 4.9 – 8.9 0.07 OXP5X150 $ 146.7/170 5.9 – 9.7 0.08 OXP5X170 1610.4/265 9.5 – 13.4 0.12 OXP5X265 1815.8/400 15.0 – 18.7 0.18 OXP5X400 3019.7/500 20.5 – 22.6 0.23 OXP5X500 42
Shaft length Mounting depth Weight Catalog List(inches/mm) (in inches) (lbs.) number price
2.14 ABB Control Inc.AC 1700 – 5/00
ION
OOFF
Fu
sible
Accessoriesfor 30A fusible disconnect switches
1 UL File # E835102 Solid link installed in carrier.
Auxiliary contacts1
Description For use on: Weight AC thermal AC rated Catalog List(lbs) amp rating voltage number price
Mounting baseDescription For use with: Weight Catalog List
(lbs) number price
Description For use on: Weight AC thermal AC rated Catalog List(lbs) amp rating voltage number price
Terminal pole
Description For use on: Weight Length Catalog List(lbs.) inches/mm number price
35mm DIN Rail OS30_ 2.96 39.4/1000 DIN RAIL $ 52
Fuse carriers (replacement part)
Description For use on: Catalog Listnumber price
Terminal cover (replacement part)
Description For use on: Catalog Listnumber price
Covers terminal OS30_ CXBY67121 $ 10below fuse carrier
Mounting base OA1G10, OA3G01 0.08 OSZ4 $ 20
Detachable neutral mounts OS30_ 0.45 30 600 OESA-ZX171 $ 40 on side of switch or DIN rail
CC fuse carrier OS30CC_ OESAZD48J fuse carrier OS30AJ_ OESAZD28 $ 50
Solid link carrier2 OS30_ OESAZD55
DIN rail
F30A
Form C 1 N.O. & 1 N.C. OS30_for direct mounting 0.04 6 250 OA4B1C $ 40
(2 maximum) to switch
1 N.O. OS30_ OA1G10 201 N.C. OSZ4 mounting 0.03 NEMA A600,P600 OA3G01(6 maximum) base required
Discount schedule H6: Handles, shafts, accessories
OA4B1C
OSZ4
OA1G10/OA3G01
OS30AJ12 with auxiliaries
CXBY67121
DIN rail
OESA-ZX171
OESAZD28 OESAZD55OESAZD48
ABB Control Inc. 2.15AC 1700 – 5/00
ION
OOFF
Fu
sib
le
Accessoriesfor 30A fusible disconnect switches
Conversion mechanisms• Switches are not included
Transfer — OWC5DSH1, OWC5DSH2, OWC5DSH1X, OWC5DSH2XTransfer mechanism manually transfers betweentwo power sources using two switches and acenter OFF position. A 3 position handle isincluded. OHB65J6E011 (UL Type 1,3R,12) or OHB65L6E011 (UL Type 1,3R,4,4X,12)Equipment required for a complete installation:• One conversion mechanism• Two disconnect switches (from pg. 2.12)• One 5 mm shaft (from pg. 2.13)
6 or 8 pole — OWP5DS1,OWP5DS26 (8) pole mechanism allows two switches,controlled by one handle, to open or closesimultaneously.Equipment required for a completeinstallation:• One conversion mechanism• Two disconnect switches (from pg. 2.12)• One handle (from pg. 2.13)• One 5 mm shaft (from pg. 2.13)
POS. O POS. I
SW. A O X
SW. B O X
X = ClosedO = Open
POS. I POS. O POS. II
SW. A X O O
SW. B O O X
X = ClosedO = Open
Mechanical interlock — OWM5DS1,OWM5DS2Mechanical interlock mechanism preventsboth switches from being in the "ON" positionat the same time.Equipment required for a completeinstallation:• One conversion mechanism• Two disconnect switches (from pg. 2.12)• Two handles (from pgs. 2.12 – 2.13)• Two 5 mm shafts (from pgs. 2.12 – 2.13)
SW. A SW. BPOS. I POS. I
SW. A X O
SW. B O X
X = ClosedO = Open
Description For use on: Weight UL/NEMA Catalog List(lbs) type number price
I O II
LOAD LOAD LOAD
SW. A SW. B SW. A SW. B SW. A SW. B
6 pole OS30A_12 1.74 — OWP5DS1 $ 220
8 pole OS30A_22 1.90 — OWP5DS2 240
Transfer3 pole OS30A_12 2.11 1,3R,12 OWC5DSH1 3003 pole OS30A_12 2.11 1,3R,4,4X,12 OWC5DSH1X 3404 pole OS30A_12 2.30 1,3R,12 OWC5DSH2 3004 pole OS30A_22 2.30 1,3R,4,4X,12 OWC5DSH2X 340
Mechanical interlock3 pole OS30A_12 1.74 — OWM5DS1 1904 pole OS30A_22 1.90 — OWM5DS2 190
Discount schedule H6: Handles, shafts, accessories
1 = Three poles
1
1
1
Drawing and mounting information found on pg 2.53
F30A
OWC5DSH1OWC5DSH2
OWM5DS1OWM5DS2OWP5DS1OWP5DS2
2.16 ABB Control Inc.AC 1700 – 5/00
ION
OOFF
Fu
sible
NotesF
30A
ABB Control Inc. 2.17AC 1700 – 5/00
ION
OOFF
Fu
sib
le
IndexSwitches, 60A – 100A ................................................................................. 2.18Pistol handles ............................................................................................. 2.18Shafts .......................................................................................................... 2.18Twisted shafts ............................................................................................. 2.19Terminal lug kits .......................................................................................... 2.19Accessories
Auxiliary contacts ..................................................................................... 2.19DIN rail ..................................................................................................... 2.19Direct mount handle................................................................................. 2.18Replacement fuse clips ........................................................................... 2.19Fuse covers ............................................................................................. 2.20Locking accessories ................................................................................ 2.20Shaft adapter ........................................................................................... 2.20Shaft extension coupler ........................................................................... 2.20Shorting bars ........................................................................................... 2.20“T” Type fuse adapter kit ......................................................................... 2.19Terminal poles ......................................................................................... 2.19Terminal shroud ....................................................................................... 2.19
Conversion mechanisms ............................................................................ 2.216 or 8 poleTransferMechanical interlock
Fuse monitor ...............................................................................................2.38
60A – 100AFusible disconnect switchesUL fuse Class J
➱NEW!!
2.18 ABB Control Inc.AC 1700 – 5/00
ION
OOFF
Fu
sible
60A – 100A Fusible disconnect switchesUL fuse class J, T
OS60J12 + OXP6X210 + OHB65J6
For a complete assembly,please select one of each:
1 switch1 handle1 shaft1 terminal lug kit
60 – 100 Amp switches, 600V
F60A – 100A
OXP6X__
OXP6X__-45
UL/NEMA IEC Color Length Marking De- Pad- Weight Catalog Listtype type in/mm featable lockable (lbs.) number price
Shafts — .24 x .24" ( 6 x 6mm)
5.9/150 5.5 – 8.5 0.09 OXP6X150 $ 128.3/210 8.0 – 11.0 0.13 OXP6X210 16
11.4/290 11.0 – 14.0 0.18 OXP6X290 2014.2/360 13.8 – 16.8 0.23 OXP6X360 2416.9/430 16.5 – 19.7 0.27 OXP6X430 28
Shaft length Mounting depth Weight Catalog List(inches/mm) (inches) (lbs.) number price
5.1/130 4.8 – 7.8 0.08 OXP6X130-45 $ 128.3/210 8.0 – 11.0 0.13 OXP6X210-45 16
11.4/290 11.0 – 14.0 0.18 OXP6X290-45 2014.2/360 13.8 – 16.8 0.23 OXP6X360-45 24
OS60J12
OHB__J6
Pistol handles — .24 x .24" ( 6 x 6mm)
Shaft length Mounting depth Weight Catalog List(inches/mm) (inches) (lbs.) number price
Twisted shafts — Rotates handle 45° .24 x .24" ( 6 x 6mm)
OHY__J6
3 pole 3 pole
60 J 15 15 15 30 50 OS60J12 $ 380100 J 25 25 30 60 75 OS100J03 520
4 pole 4 pole
60 J 15 15 15 30 50 OS60J22 490100 J 25 25 30 60 75 OS100J04 660
1,3R,12 IP65 Black 2.6/65 O/I & Off/On Yes Yes 0.29 OHB65J6 $ 801,3R,12 IP65 Red/Yel 2.6/65 O/I & Off/On Yes Yes 0.29 OHY65J6 801,3R,12 IP65 Black 3.1/80 O/I & Off/On Yes Yes 0.30 OHB80J6 901,3R,12 IP65 Red/Yel 3.1/80 O/I & Off/On Yes Yes 0.30 OHY80J6 90
1,3R,4,4X,12 IP65 Black 3.1/80 O/I & Off/On Yes Yes 0.30 OHB80L6 1301,3R,4,4X,12 IP65 Red/Yel 3.1/80 O/I & Off/On Yes Yes 0.30 OHY80L6 130
UL UL Maximum horsepower ratinggeneral Fuse Three phasepurpose type Catalog List
amp rating 600V 200V 208V 240V 480V 600V number price
Direct mount handle — mounts directly to switch, no shaft necessary
UL/NEMA Color Marking Length Padlockable Weight Catalog Listtype mm (lbs.) number price
1 Black O/I/Test 50 Yes 0.10 OHB4 $ 60
Discount schedule H4: F, 30A – 100ADiscount schedule H6: Handles, shafts, accessories
OS100J03
ABB Control Inc. 2.19AC 1700 – 5/00
ION
OOFF
Fu
sib
le
Accessoriesfor 60A – 100A fusible disconnect switches
Discount schedule H6: Handles, shafts, accessories
F60A – 100A
OZXA-24
Terminal lug kitKit
For use on: Wire weight Wire Terminal Catalog Listsize (lbs) type lugs per kit number price
Auxiliary contacts
Description For use on: Weight AC thermal AC rated Catalog List(lbs) amp rating voltage number price
OS60J_ #14 – 4 — Cu — Integral —
OS100J_ #14 – 2/0 0.43 Cu/Al 6 OZXA-24 $ 24
DIN rail
Replacement fuse clip
Description For use on: Catalog Listnumber price
Terminal shroudDescription For use on: Weight Catalog List
(lbs) number price
Terminal polesDescription For use on: Weight AC thermal AC rated Catalog List
(lbs) amp rating voltage number price
DIN railDescription For use on: Weight Length Catalog List
(lbs.) inches/mm number price
Includes three single poleterminal shrouds OS100, 3-Pole 0.04 OSS160T3 $ 60
for line or load side
Detachable neutral OS60 0.13 63 600 OSZ1 $ 50mounts on side
of switch or DIN rail OS100 0.31 125 600 OSZ2 50
35mm DIN Rail OS60 2.36 39.4/1000 DIN RAIL $ 52
Removable fuse carrier OS60 OSC60J1 $ 20
Replacement fuse covers
Description For use on: Catalog Listnumber price
Transparent fuse cover OS100 CXBY68362 $ 20
1 N.O. 0.07 10 600 OA1G10 $ 201 N.C. OS60 – OS100 0.07 10 600 OA3G01 20
“T” type fuse adapter kitDescription For use on: Catalog List
number price
100A, 600V, 3 pole OS100 OESA-ZX1-J1T6 $ 60
OA1G10, OA3G01
OSC60J1 CXBY68362
OSS160T3
OSZ1
OESA-ZX1-J1T6
2.20 ABB Control Inc.AC 1700 – 5/00
ION
OOFF
Fu
sible
Accessoriesfor 60A – 100A fusible disconnect switches
Shorting bars
Description For use on: AC thermal AC rated Catalog Listamp rating voltage number price
OETL-ZK19(X=6MM)
OESA-ZX167OETL-ZX95
OESA-ZS36
OETL-ZW16
F60A – 100A
12x
x-1
Locking accessories
Description For use on: Weight Catalog List(lbs) number price
Shaft extension coupler
Description For use on: Weight Catalog List(lbs) number price
Shaft adapter
Description For use on: Weight Catalog List(lbs) number price
Discount schedule H6: Handles, shafts, accessories
Dummy fuse OS60 60 600 OESA-ZD54 $ 50
Solid links: Metal strap OS100 100 600 OESA-ZS36 24
Adapts one end of a 6mm shaft to 12mm. Use with 6mm shafts 0.20 OETL-ZK19 $ 40
shaft extension coupler
Joins two shafts togetherfor applications where 6mm shafts 0.26 OESA-ZX167 $ 56
extended length is required 12mm shafts 0.26 OETL-ZX95 100
Cam attachment for Kirk Key,Castell, Lowe & Fletcher and
Ronis interlock. Cam attachment OS60 –for adapting to the OS100 0.25 OETL-ZW16 $ 190
interlock system. Theinterlock is not included.
ABB Control Inc. 2.21AC 1700 – 5/00
ION
OOFF
Fu
sib
le
Accessoriesfor 60A – 100A fusible disconnect switches
Transfer — OESA-ZW1, OESA-ZW1XTransfer mechanism manually transfersbetween two power sources using twoswitches and a center OFF position. A 3position handle is included. OHB80J6E011 (UL Type 1,3R,12) or OHB80L6E011 (UL Type 1,3R4,4X,12)Shafts included .Equipment required for a completeinstallation:• One conversion mechanism• Two disconnect switches (from pg. 2.18)
6 or 8 pole — OESA-ZW26 (8) pole mechanism allows two switchescontrolled by one handle, to open or closesimultaneously. Shafts included.Equipment required for a completeinstallation:• One conversion mechanism• Two disconnect switches (from pg. 2.18)• One handle (from pg. 2.24)
POS. O POS. I
SW. A O X
SW. B O X
X = ClosedO = Open
POS. I POS. O POS. II
SW. A X O O
SW. B O O X
X = ClosedO = Open
I O II
LOAD LOAD LOAD
SW. A SW. B SW. A SW. B SW. A SW. B
OESA-ZW2
OESA-ZW1
F60A – 100A
Conversion mechanisms• Switches are not included
Description For use on: Weight UL/NEMA Catalog List(lbs) type number price
6 and 8 pole OS60 – OS100 1.52 — OESA-ZW2 $ 220
Transfer OS60 – OS100 2.20 1,3R,12 OESA-ZW1 300
Transfer OS60 – OS100 2.20 1,3R,4,4X,12 OESA-ZW1X 340
Mechanical interlock OS60 – OS100 0.55 — OTZW10 100
Discount schedule H6: Handles, shafts, accessories
1 = Three poles
1
1
Drawing and mounting information found on pg 2.54
SW. A SW. BPOS. I POS. I
SW. A X O
SW. B O X
Mechanical interlock — OTZW10Mechanical interlock mechanism preventsboth switches from being in the "ON"position at the same time.Equipment required for a completeinstallation:• One conversion mechanism• Two disconnect switches (from pg. 2.18)• Two handles (from page 2.18)• Two shafts (from pg. 2.18)
X = ClosedO = Open
OTZW10
1
I ON
2.22 ABB Control Inc.AC 1700 – 5/00
ION
OOFF
Fu
sible
NotesF
60A – 100A
ABB Control Inc. 2.23AC 1700 – 5/00
ION
OOFF
Fu
sib
le
IndexSwitches, 200A – 800A ...............................................................................2.24Handles .......................................................................................................2.24Shafts ..........................................................................................................2.25Twisted shafts .............................................................................................2.25Terminal lug kits ..........................................................................................2.25Accessories
90° angle kit ..............................................................................................2.27Auxiliary contacts ......................................................................................2.26Fuse cover interlock .................................................................................2.26Fuse covers ..............................................................................................2.26Locking accessories .................................................................................2.27Shaft extension coupler ............................................................................2.27Shorting bars ............................................................................................2.27"T" type fuse adapter kit ...........................................................................2.25Terminal pole ............................................................................................2.26Terminal shroud ........................................................................................2.26
Conversion mechanisms .............................................................................2.286 or 8 poleTransferBypassMechanical interlock
Fuse monitor ...............................................................................................2.38
200A – 800AFusible disconnect switchesUL fuse Class J, T, L
➱NEW!!
2.24 ABB Control Inc.AC 1700 – 5/00
ION
OOFF
Fu
sible
200 – 800 Amp switches, 600V
200A – 800A Fusible disconnect switchesUL fuse class J, T, L
For a complete assembly,please select one of each:
1 switch1 handle1 shaft1 terminal lug kit
F200A – 800A
OHY__J12
OES600J3OES800L3
OES400J3
OES200J3 + OXP12X280 + OHB145J12 + OZXA-25
OHB__J12
2 pole 2 pole200 J — — — — — OES200J2 $ 1240400 J — — — — — OES400J2 1680600 J — — — — — OES600J2 2600800 L — — — — — OES800L2 4280
3 pole 3 pole
200 J 50 50 60 125 150 OES200J3 1380400 J 100 125 125 250 350 OES400J3 1860600 J 150 150 200 400 500 OES600J3 2900800 L 200 200 250 500 600 OES800L3 4760
4 pole 4 pole
200 J 50 50 60 125 150 OES200J4 1720400 J 100 125 125 250 350 OES400J4 2320600 J 150 150 200 400 500 OES600J4 3620800 L 200 200 250 500 600 OES800L4 5950
UL UL Maximum horsepower ratinggeneral Fuse Three phasepurpose type Catalog List
amp rating 600V 200V 208V 240V 480V 600V number price
Pistol handles — .47 x .47" ( 12 x 12mm)
UL/NEMA IEC Color Length Marking Defeat- Padlock- Weight Catalog Listtype type inches/mm able able (lbs) number price
1,3R,12 IP65 Black 4.9/125 O/I & Off/On Yes Yes 0.39 OHB125J12 $ 901,3R,12 IP65 Red/Yel 4.9/125 O/I & Off/On Yes Yes 0.39 OHY125J12 901,3R,12 IP65 Black 5.7/145 O/I & Off/On Yes Yes 0.39 OHB145J12 901,3R,12 IP65 Red/Yel 5.7/145 O/I & Off/On Yes Yes 0.39 OHY145J12 901,3R,12 IP65 Black 6.9/175 O/I & Off/On Yes Yes 0.41 OHB175J12 1001,3R,12 IP65 Red/Yel 6.9/175 O/I & Off/On Yes Yes 0.41 OHY175J12 100
1,3R,4,4X,12 IP65 Black 5.7/145 O/I & Off/On Yes Yes 0.39 OHB145L12 1301,3R,4,4X,12 IP65 Red/Yel 5.7/145 O/I & Off/On Yes Yes 0.39 OHY145L12 1301,3R,4,4X,12 IP65 Black 6.9/175 O/I & Off/On Yes Yes 0.41 OHB175L12 1401,3R,4,4X,12 IP65 Red/Yel 6.9/175 O/I & Off/On Yes Yes 0.41 OHY175L12 140
1,3R,4,4X,12 IP65 Metal 8.7/220 Off/On — Yes 1.50 YASDA-8 190
Discount schedule H5: F, 200A – 800ADiscount schedule H6: Handles, shafts, accessories
ABB Control Inc. 2.25AC 1700 – 5/00
ION
OOFF
Fu
sib
le
Accessoriesfor 200A – 800A fusible disconnect switches
F200A – 800A
OXP12X__-45
OESA-ZX1-J_1 Mounting depth is the distance from the outside of the door to the disconnect switch mounting plate. Shaft can be cut to desired length.
Shafts — .47 x .47" ( 12 x 12mm)
Twisted shafts — Rotates handle 45° .47 x .47" ( 12 x 12mm)
Discount schedule H6: Handles, shafts, accessories
OZXA-27
OZXA-25 OZXA-26
OXP12X__
Shaft length Mounting depth1 in inches Weight Catalog Listinches/mm (lbs) number price
For use on OES200 – OES400
8.7/220 7.9 – 12.2 0.61 OXP12X220 $ 289.8/250 9.1 – 13.4 0.70 OXP12X250 3211.0/280 10.2 – 14.5 0.77 OXP12X280 3612.8/325 12.0 – 16.3 0.90 OXP12X325 4015.6/395 14.8 – 19.1 1.10 OXP12X395 4418.3/465 17.5 – 21.9 1.32 OXP12X465 4821.1/535 20.3 – 24.6 1.54 OXP12X535 52
For use on OES600 – OES800
9.8/250 10.0 – 12.8 0.70 OXP12X250 3211.0/280 11.2 – 14.0 0.77 OXP12X280 3612.8/325 13.0 – 15.8 0.90 OXP12X325 4015.6/395 15.8 – 18.6 1.10 OXP12X395 4418.3/465 18.5 – 21.3 1.32 OXP12X465 4821.1/535 21.1 – 24.1 1.54 OXP12X535 52
Shaft length Mounting depth Weight Catalog List(inches/mm) (inches) (lbs.) number price
For use on OES200 – OES400
11.0/280 10.2 – 14.5 0.77 OXP12X280-45 $ 3612.8/325 12.0 – 16.3 0.90 OXP12X325-45 4018.3/465 17.5 – 21.9 1.32 OXP12X465-45 48
For use on OES600 – OES800
11.0/280 11.2 – 14.0 0.77 OXP12X280-45 3612.8/325 13.0 – 15.8 0.90 OXP12X325-45 4018.3/465 18.5 – 21.3 1.32 OXP12X465-45 48
Terminal lug kit
OES200 #6 – 300 kcmil 0.93 Cu/Al 6 OZXA-25 $ 80OES200 (6) #14 – 6 kcmil 0.55 Cu/Al 3 OZXA-175 180OES400 #2 – 600 kcmil 3.50 Cu/Al 6 OZXA-26 190OES400 #2 – 600 kcmil 1.75 Cu/Al 3 OZXA-26/3P 95OES400 (2) #2 – 500 kcmil — Cu/Al 6 OZXA-33 375
OES600 – OES800 (12)#14 – 6 kcmil 1.10 Cu/Al 3 OZXA-175/400 270OES600 – OES800 (2) #2 – 600 kcmil 4.62 Cu/Al 6 OZXA-27 380OES600 – OES800 (2) #2 – 600 kcmil 2.31 Cu/Al 3 OZXA-27/3P 190
“T” type fuse adapter kit
For use on: AC thermal AC rated Poles Catalog Listamp rating voltage number price
OES200 200 600 3 OESA-ZX1-J2T6 $ 100OES400 400 600 3 OESA-ZX1-J4T6 140OES600 600 600 3 OESA-ZX1-J6T6 240
KitFor use on: Wire weight Wire Terminal Catalog List
size (lbs) type lugs per kit number price
OZXA-175/400
OZXA-175
2.26 ABB Control Inc.AC 1700 – 5/00
ION
OOFF
Fu
sible
Accessoriesfor 200A – 800A fusible disconnect switches
F200A – 800A
OESA-ZX85OESA-ZX88
OESA-ZX213OESA-ZX271OESA-ZX216
OESA-ZX190OESA-ZX272OESA-ZX196
OESA-ZX204
OESA-ZX191OESA-ZX273OESA-ZX197
1 UL file #E57057
Fuse covers (replacement part)
OZXK-_200A & 400A 600A & 800A
Switches Switches
Discount schedule H6: Handles, shafts, accessories
Auxiliary contacts1
Description For use on: Weight AC thermal AC rated Catalog List(lbs) amp rating voltage number price
1 N.O. + 1 N.C. 0.20 10 600 OZXK-1 $ 1002 N.O. + 2 N.C. 0.26 10 600 OZXK-2 1704 N.O. + 4 N.C. OES200 – 0.40 10 600 OZXK-3 340
2 N.O. OES800 0.18 10 600 OZXK-4 1004 N.O. 0.25 10 600 OZXK-5 1708 N.O. 0.40 10 600 OZXK-6 340
Description For use on: Weight Catalog List(lbs) number price
2 pole 0.30 OESA-ZX213 $ 1203 pole OES200 0.40 OESA-ZX190 1604 pole 0.53 OESA-ZX191 220
2 pole 0.30 OESA-ZX271 1403 pole OES400 0.40 OESA-ZX272 2004 pole 0.53 OESA-ZX273 270
2 pole 0.40 OESA-ZX216 1803 pole OES600 – 0.50 OESA-ZX196 2604 pole OES800 0.67 OESA-ZX197 350
Fuse cover interlockDescription For use on: Catalog List
number price
Terminal shroudDescription For use on: Weight Catalog List
(lbs) number price
Terminal poleDescription For use on: Weight AC thermal AC rated Catalog List
(lbs) amp rating voltage number price
OES200 – 1.04 400 600 OESA-ZX85 $ 150Detachable neutral mounts on OES400
side of switch or DIN rail OES600 – 1.19 800 600 OESA-ZX88 160OES800
OESA-ZX70OESA-ZX123OESA-ZX125
Prevents the fuse cover from OES200 –being opened when the switch OESA-ZX204 $ 90
is in the ON position OES800
Includes one OES200 0.13 OESA-ZX70 $ 100
terminal shroud for OES400 0.13 OESA-ZX123 110line or load side OES600 – OES800 0.11 OESA-ZX125 160
ABB Control Inc. 2.27AC 1700 – 5/00
ION
OOFF
Fu
sib
le
Accessoriesfor 200A – 800A fusible disconnect switches
OETL-ZT80
OETL-ZX108
OESA-ZK98OESA-ZL79
OETL-ZX95
F200A – 800A
OETL-ZW5
Discount schedule H6: Handles, shafts, accessories
Locking accessories
Description For use on: Weight Catalog List(lbs) number price
Shaft extension couplerDescription For use on: Weight Catalog List
(lbs) number price
Joins two shafts togetherfor applications where 12mm shafts 0.26 OETL-ZX95 $ 100
extended length is required
Shorting barsDescription For use on: AC thermal AC rated Catalog List
amp rating voltage number price
OES200 – 400 600 OESA-ZK98 $ 23Solid links OES400(1 per kit) OES600 – 800 600 OESA-ZL79 79
OES800
Description For use on: Weight Catalog List(lbs) number price
90° angle kit
Converts switch mechanism from OES200 – 4.63 OETL-ZX108 $ 794front operation to side operation OES800
★ - Coil voltage
Cam attachment for Kirk Key,Castell, Lowe & Fletcher and OES200 –Ronis interlock. For adapting 0.29 OETL-ZW5 $ 190to the interlock system. OES800
The interlock is not included.
Electrical interlock Closedcircuit principle for interlockingthe switch movement. When thecoil circuit is dead, A-types cannot OES600 –be operated to ON-position and 2.42 OETL-ZT80A/★ 1280L-types cannot be operated to OES800
ON- or OFF-position. OETL-ZT80L/★ 1220
Coil voltages 110VAC, 220VAC,24VDC, 48VDC, 60 VDC
110VDC, 220VDC, P = 15W
2.28 ABB Control Inc.AC 1700 – 5/00
ION
OOFF
Fu
sible
Accessoriesfor 200A – 800A fusible disconnect switches
Conversion mechanisms• Switches are not included
Transfer — OETL-ZW12Transfer mechanism manually transfersbetween two power sources using twoswitches and a center OFF position. A 3position handle is included. YASDA-21(UL Type 1, 3R, 4, 4X & 12).Equipment required for a completeinstallation:• One conversion mechanism• Two disconnect switches (from pg. 2.24)• Two OETL-ZX95 shaft extension couplers
(from pg. 2.27)• Two shafts (from pg. 2.25)
6 or 8 pole — OETL-ZW96 (8) pole mechanism allows two switchescontrolled by one handle, to open or closesimultaneously.Equipment required for a completeinstallation:• One conversion mechanism• Two disconnect switches (from pg. 2.24)• One handle (from pg. 2.24)• One additional shaft (from pg. 2.25)(Only one shaft is included with mechanism)
POS. O POS. I
SW. A O X
SW. B O X
X = ClosedO = Open
POS. I POS. O POS. II
SW. A X O O
SW. B O O X
X = ClosedO = Open
6 or 8 pole 2.42 — OETL-ZW9 $ 260Transfer OES200 – OES800 10.1 1,3R,4,4X,12 OETL-ZW12 560Bypass 8.81 1,3R,4,4X,12 OETL-ZW13 560
1.26 — OETL-ZW3 140Mechanical interlock OES200 – OES800 1.15 — OETL-ZW14 140
2.64 — OETL-ZW15 160
Bypass — OETL-ZW13Bypass mechanism operates three switches:Two switches in series and one changeoverswitch to allow power bypass. A 3 positionhandle is included. YASDA-6(UL Type 1, 3R, 4, 4X & 12).Equipment required for a completeinstallation:• One conversion mechanism• Three disconnect switches (from pg. 2.24)• Three OETL-ZX95 shaft extension couplers
(from pg. 2.27)• Three shafts (from pg. 2.25)
POS. I POS. O POS. II
SW. A O O X
SW. B O O X
SW. C X O O
X = ClosedO = Open
SW. A SW. BPOS. I POS. I
SW. A X O
SW. B O X
Mechanical interlock — OETL-ZW3,OETL-ZW14, OETL-ZW15Mechanical interlock mechanism preventsboth switches from being in the "ON"position at the same time.Equipment required for a completeinstallation:• One conversion mechanism• Two disconnect switches (from pg. 2.24)• Two handles (from page 2.25)• Two shafts (from pg. 2.24)
X = ClosedO = Open
F200A – 800A
Description For use on: Weight UL/NEMA Catalog List(lbs) type number price
OETL-ZW9
OETL-ZW12
OETL-ZW13
OETL-ZW3OETL-ZW14OETL-ZW15
Discount schedule H6: Handles, shafts, accessories
1 = Three poles
1
1
1
1
Drawing and mounting information found on pg 2.55 & 2.56
I O II
LOAD LOAD LOAD
SW. A SW. B SW. A SW. B SW. A SW. B
ION
OOFF
Fu
sib
le
ABB Control Inc. 2.29AC 1700 – 5/00
IndexSide operated switches ............................................................................... 2.30Flange operated switches ........................................................................... 2.31Global concept switches ............................................................................. 2.32High speed fuse switches, special types .................................................... 2.33High speed fuse switches, standard types ................................................. 2.34BS fuse pattern switches ............................................................................ 2.35DIN fuse pattern switches ........................................................................... 2.36NFC fuse pattern switches ......................................................................... 2.37Fuse monitor ...............................................................................................2.38Motor operators .......................................................................................... 2.39
Other configurationsFusible disconnect switches
➱NEW!!
ION
OOFF
Fu
sible
2.30 ABB Control Inc.AC 1700 – 5/00
FSide
operated
Side operated fusible disconnect switches 130A – 400AUL fuse class J,CC,T
For a complete assembly,please select one of each:
1 switch1 handle1 shaft1 terminal lug
OS30A_S_ + OXP5X170 + OHY65J5TE00S
Side operated switches — 3 pole
1 J type fuse clips are standard. If 600V Type "T" fuse clips are desired, please order the "T" type fuse adapter kit.
KitFor use on: Wire weight Wire Lugs Catalog List
size (lbs) type per kit number price
For use with: Length Description Weight Catalog List(inches/mm) (lbs.) number price
OS30AJS30 & OS30ACCS30 6.7/170 0.20 x 0.20" (5 x 5mm) 0.08 OXS5X170 $ 16
OS60JS30 & OS100JS30 6.7/170 0.24 x 0.24" (6 x 6mm) 0.08 OXP6X170 —
OES200J3-S & OES400J3-S 12.8/325 0.47 x 0.47" (12 x 12mm) 0.90 OXP12X325 40
OS30AJS30 & OS30ACCS30 #18 – 8 — Cu — Integral —OS60JS30 #14 – 4 — Cu — Integral —
OS100JS30 #14 – 2/0 0.43 Cu/Al 6 OZXA-24 $ 24
OES200J3-S #6 – 300 kcmil 0.93 Cu/AI 6 OZXA-25 80
OES400J3-S #2 – 600 kcmil 3.50 Cu/AI 6 OZXA-26 190
UL ULgeneral fuse
Maximum horsepower rating
purpose type Three phase Weight Catalog List
amp rating 600V 200V 208V 240V 480V 600V (lbs) number price
UL/NEMA type IEC type Color Length Marking Defeat- Padlock- Weight Catalog Listinches/mm able able number price
For use with OS30AJ12-S & OS30ACC12-S
1, 3R, 12 IP65 Black 2.6/65 OFF/ON/TEST Yes Yes 0.29 OHB65J5TE00S $ 80
1, 3R, 12 IP65 Red/Yel 2.6/65 OFF/ON/TEST Yes Yes 0.29 OHY65J5TE00S 80
For use with OS60J12-S & OS100J03-S
1, 3R, 12 IP65 Black 3.1/80 OFF/ON/TEST Yes Yes 0.30 OHB80J8TE00S 80
1, 3R, 12 IP65 Red/Yel 3.1/80 OFF/ON/TEST Yes Yes 0.30 OHY80J8TE00S 80
For use with OES200J3-S & OES400J3-S
1, 3R, 12 IP65 Black 4.9/145 OFF/ON/TEST Yes Yes 0.39 OHB145J12TE002S 80
1, 3R, 12 IP65 Red/Yel 4.9/145 OFF/ON/TEST Yes Yes 0.39 OHY145J12TE002S 80
1, 3R, 12 IP65 Metal 4.9/145 OFF/ON/TEST — Yes 1.50 OETL-ZX74 190
OS100JS30
OS60JS30
OZXA-25
OXP12X325
OETL-ZX74
— = No
Handles
Shafts
Terminal lug kit
30 J 5 7.5 7.5 15 20 1.54 OS30AJS30 $ 36030 CC 5 7.5 7.5 15 20 1.54 OS30ACCS30 36060 J 15 15 15 30 50 3.52 OS60JS30 540
100 J1 25 25 30 60 75 3.97 OS100JS30 640200 J1 50 50 60 125 150 15.21 OES200J3-S 1800400 J1 100 125 125 250 350 17.20 OES400J3-S 2600
Discount schedule H4: F, 30A – 100ADiscount schedule H5: F, 200A – 600ADiscount schedule H6: Handles, shafts, accessories
ION
OOFF
Fu
sib
le
ABB Control Inc. 2.31AC 1700 – 5/00
Flange operated fusible disconnect switches30A – 100AUL fuse class J,CC,T
1 J type fuse clips are standard. If 600V Type "T" fuse clips are desired, please order the "T" type fuse adapter kit.2 200A available by using a non-fusible 200A switch and a trailing fuse block. Please consult factory.3 Discount schedule SA
FFlange
For a complete assembly,please select one of each:
1 switch1 handle1 shaft1 terminal lug
OS30AJ30-F + DSFHS-12 + DSFHN-HS12
Flange operated switches — 3 poleUL UL
general fuseMaximum horsepower rating
purpose type Three phase Weight Catalog List
amp rating 600V 200V 208V 240V 480V 600V (lbs) number price
HandlesUL/NEMA Color Length Marking Defeat- Padlock- Weight Catalog List
type inches/mm able able (lbs) number price
1, 3R, 12 Metal 6.9/175 O/I & OFF/ON Yes Yes 3.52 DSFHN-HS12 $ 1564, 4X Metal 6.9/175 O/I & OFF/ON Yes Yes 3.52 DSFHN-HS4 240
ShaftsShaft length Weight Catalog List
inches (lbs) number price
Door hardware — NEMA 12
Item Weight Catalog List(lbs) number price
Terminal lug kit
OS30_ #18 – #8 — Cu — Standard —OS60_ #14 – #4 — Cu — Standard —
OS100_ #14 – 2/0 0.43 Cu/Al 6 OZXA-24 $ 24
KitFor use on: Wire weight Wire Lugs Catalog List
size (lbs) type per kit number price
12 0.39 DSFHS-12 $ 2817 0.55 DSFHS-17 40
22.5 0.73 DSFHS-22 52
Safety door latch, 1.92 FH-DHK3 $ 1502 point with 6" handle
Roller for 3 point latch, 0.39 FH-3RL3 30add to FH-DHK
OZXA-24
DSFHN-HS__
DSFHS-__
30 J 5 7.5 7.5 15 20 2.20 OS30AJF30 $ 50030 CC 5 7.5 7.5 15 20 2.50 OS30ACCF30 50060 J 15 15 15 30 50 3.52 OS60JF30 590100 J1 25 25 30 60 75 3.97 OS100JF30 690
200 2
Discount schedule H4: F, 30A – 100ADiscount schedule H6: Handles, shafts, accessoriesDiscount schedule SA: FH-DHK, FH-3RL
UL Listed
CSA Approved
IEC Rated
CE Marked
ION
OOFF
Fu
sible
2.32 ABB Control Inc.AC 1700 – 5/00
FGlobal
concept
Global concept disconnect switches30A – 60A
For a complete assembly,please select one of each:
1 fusible disconnect body1 set of fuse carriers1 shaft1 handle
OS63X12 + OSC__ + OX_ + OH_
About the global concept …Customers in Boston and Berlin?Do your customers in Boston prefer UL Class J fuses andyour customers in Berlin specify DIN standard fuses? Noproblem!
ABB Global concept fusible disconnect switches offer theflexibility to design a panel using a common disconnect
Fusible disconnect bodies — 30A & 60AUL IEC
general purpose AC21 Description Technical Weight Catalog List
amp rating amp rating ratings (lbs) number price
3 pole 1.40 OS32M12 $ 1304 pole 1.70 OS32M22F 150
30 32 3 pole + neutral See pages 1.70 OS32M22N11 2003 pole, side operation 2.40 – 2.42 1.40 OS32MS30 2104 pole, side operation 1.70 OS32MS40F 270
3 pole + neutral, side operation 1.70 OS32MS40N11 3203 pole 2.40 OS63X12 $ 2304 pole 2.80 OS63X22F 290
60 63 3 pole + neutral See pages 2.80 OS63X22N11 3403 pole, side operation 2.40 – 2.42 2.40 OS63XS30 3904 pole, side operation 2.80 OS63XS40F 450
3 pole + neutral, side operation 2.80 OS63XS40N11 500
Fuse carriers for 3 pole units and units with neutral2For use on: Fuse type Technical Weight Catalog List
ratings (lbs) number price
UL J 30A OSC30AJ3UL CC 30A OSC30ACC3
DIN Neozed D01 OSC16D301DIN Neozed D02 OSC35D302
OS32M_ NFC 10x38 See pages 0.48 OSC25F310NFC 14x51 2.40 – 2.42 OSC32F314
BS88 A1 OSC32B3A1BS88 A2 OSC32B3A2 $ 150BS88 E1 OSC32B3E1BS88 F1 OSC32B3F1
UL J 60A OSC60J3NFC 14x51 See pages OSC50F3
OS63X_ NFC 22x58 2.40 – 2.42 0.60 OSC63F3BS88 A2, A3 CSA C30, C60 OSC63B3
DIN 000, 00 OSC63D3
body. When the panel destination is known, simply insertthe appropriate fuse carrier.
Global concept = common disconnect body + anassortment of fuse carriers.
High volumes with various fuse types — Global concept.
Fuse carriers for 4 pole units3
For use on: Fuse type Technical Weight Catalog Listratings (lbs) number price
UL J 30A OSC30AJ4UL CC 30A OSC30ACC4
DIN Neozed D01 OSC16D401DIN Neozed D02 OSC35D402
OS32M_ NFC 10x38 See pages 0.64 OSC25F410NFC 14x51 2.40 – 2.42 OSC32F414
BS88 A1 OSC32B4A1BS88 A2 OSC32B4A2 $ 200BS88 E1 OSC32B4E1BS88 F1 OSC32B4F1
UL J 60A OSC60J4NFC 14x51 See pages OSC50F4
OS63X_ NFC 22x58 2.40 – 2.42 0.80 OSC63F4BS88 A2, A3 CSA C30, C60 OSC63B4
DIN 000, 00 OSC63D4
1 N1-versions will be delivered with neutral carrier.2 Part number includes 3 pieces of fuse carriers.3 Part number includes 4 pieces of fuse carriers.
NOTE: Handles and shafts — please see pages 2.12 – 2.13 for OS32_ and pages 2.18 – 2.19 for OS63_.
DIN Neozed 0_
NFC Style
BS88
Discount schedule H4: F, 30A – 100ADiscount schedule H5: F, 200A – 600ADiscount schedule H6: Handles, shafts, accessories
ION
OOFF
Fu
sib
le
ABB Control Inc. 2.33AC 1700 – 5/00
Switch bodies — 200A through 800A
3 pole200 50 60 125 150 15.21 OESA250R3 $ 1220400 125 125 250 350 17.20 OESA400R3 1740600 150 200 400 500 37.48 OESA630R3 2640800 200 250 500 600 37.48 OESA800R3 4590
4 pole200 50 60 125 150 17.4 OESA250R4 1510400 125 125 250 350 19.4 OESA400R4 2140600 150 200 400 500 46.3 OESA630R4 3270800 200 250 500 600 46.3 OESA800R4 5710
UL Maximum horsepower rating
general purpose Three phase Weight Catalog Listamp rating 208V 240V 480V 600V (lbs) number price
Adapter kits — for switches OESA250 – OESA400
For 3 pole switch For 4 pole switch
OESA250 – OESA400 Catalog List Catalog Listnumber price number price
American standard OESAZX1-S4 OESAZX1-S4/4OESAZX1-S5 OESAZX1-S5/4
DIN80 (DIN43653) OESAZX1-S7 OESAZX1-S7/4DIN80 sizes 00 and 000 (DIN 43653) OESAZX1-S9 OESAZX1-S9/4
DIN110 (DIN43653) OESAZX1-S2 $ 220 OESAZX1-S2/4 $ 290DIN140 (DIN43653) OESAZX1-S6 OESAZX1-S6/4
Flush-end, 70mm body OESAZX1-S8 OESAZX1-S8/4Flush-end, 50mm body OESAZX1-S3 OESAZX1-S3/4
French OESAZX1-S10 OESAZX1-S10/4French with micro switches OESAZX1-S11 OESAZX1-S11/4
Adapter kits — for switches OESA630 – OESA800For 3 pole switch For 4 pole switch
OESA630 – OESA800 Catalog List Catalog Listnumber price number price
American standard OESAZX2-S4 OESAZX2-S4/4
DIN80, DIN 110, DIN 140 (DIN43653) OESAZX2-S2 OESAZX2-S2/4
Flush-end, 50mm and 70mm body OESAZX2-S3 $ 400 OESAZX2-S3/4 $ 530
French OESAZX2-S5 OESAZX2-S5/4French with micro switches OESAZX2-S6 OESAZX2-S6/4
Handles and shafts — please see pages 2.24 – 2.25.
Selecting the right fusible disconnect for HSF fuses may be confusing. Due to UL restrictions it is not possible to give ageneral fuse selection table for your use. Therefore we ask you to contact ABB Control Inc., Wichita Falls, inapplication issues.
Selecting switch bodies and adapter kitsPlease select switch body and adapter kit according to your fuses. Switch body alone can not be used —an adapter kit is always needed.
For a complete assembly,please select one of each:
1 switch body1 adapter kit1 shaft1 handle OESA_R_ + OESAZX_ + OXP_ + OH_
High speed fuse pattern fusible switchesSpecial type fuses
FHigh speed
DIN 43653
Flush end
French style
American standard
Discount schedule H4: F, 30A – 100ADiscount schedule H5: F, 200A – 600ADiscount schedule H6: Handles, shafts, accessories
ION
OOFF
Fu
sible
2.34 ABB Control Inc.AC 1700 – 5/00
High speed fuse pattern fusible switchesStandard switches
FHigh speed
DIN-style fusible disconnects — 32A through 800A1
Selecting switch bodiesThere are some HSF fuses that fit in standard pattern fusible disconnects, no adapter kits needed.
For a complete assembly,please select one switchcatalog number whichincludes:
Switch body + shaft + handle
ULgeneral purpose AC23A rated operational power in kW Fuse Weight Catalog List
amp rating 230V 400V 500V 690V type (lbs.) number price
Selecting the right fusible disconnect for HSF fuses may be confusing. Due to UL restrictions it is not possible to give ageneral fuse selection table for your use. Therefore we ask you to contact ABB Control Inc., Wichita Falls, regardingapplication issues.
NFC-style fusible disconnects — 25A through 125A2
3 pole30 6 11 14 22 NFC 10x38 1.54 OS25RF1210 $ 40030 8 14 18 25 NFC 14x51 1.54 OS32RF1214 40060 18.5 30 37 60 NFC 14x51 2.90 OS63RF1214 500
100 37 60 80 110 NFC 22x58 3.30 OS125RF0322 700100 45 80 110 132 NFC 27x60 3.30 OS160RF0327 700
4 pole30 6 11 14 22 NFC 10x38 2.00 OS25RF2210 53030 8 14 18 25 NFC 14x51 2.00 OS32RF2214 53060 18.5 30 37 60 NFC 14x51 3.50 OS63RF2214 660
100 37 60 80 110 NFC 22x58 4.00 OS125RF0422 930100 45 80 110 132 NFC 27x60 4.00 OS160RF0427 930
ULgeneral purpose AC23A rated operational power in kW Fuse Weight Catalog List
amp rating 230V 400V 500V 690V type (lbs.) number price
3 pole30 9 15 22 30 DIN 000, 00 2.9 OS32RD12 $ 50060 18.5 30 37 60 DIN 000, 00 2.9 OS63RD12 500
100 45 80 110 132 DIN 000, 00 3.3 OS160RD03 700100 45 80 110 132 DIN 43653: 000/80 3.3 OS160RD0380 700200 70 132 170 230 DIN 0, 1 16.1 OESA250RD3 1380400 110 210 280 330 DIN 0, 1, 2 18.3 OESA400RD3 1860600 180 315 400 540 DIN 3 35.2 OESA630RD3 2900800 200 350 470 600 DIN 3 39.6 OESA800RD3 4760
4 pole30 9 15 22 30 DIN 000, 00 3.5 OS32RD22 66060 18.5 30 37 60 DIN 000, 00 3.5 OS63RD22 660
100 45 80 110 132 DIN 000, 00 4.0 OS160RD04 930100 45 80 110 132 DIN 43653: 000/80 4.0 OS160RD0480 930200 70 132 170 230 DIN 0, 1 18.1 OESA250RD4 1840400 110 210 280 330 DIN 0, 1, 2 20.7 OESA400RD4 2480600 180 315 400 540 DIN 3 46.3 OESA630RD4 3860800 200 350 470 600 DIN 3 52.9 OESA800RD4 6340
1 OS32 – OS160 include handle OHB65J6 and shaft OXP6X161.OESA250 – OESA400 include handle OHB125J12 and shaft OXP12X250.OESA630 – OESA800 include handle OHB145J12 and shaft OXP12X250.
2 OS25 – OS32 include handle OHB65J5 and shaft OXP5X150.OS50 – OS125 include handle OHB65J6 and shaft OXP6X161.
DIN 43620
Discount schedule H4: F, 30A – 100ADiscount schedule H5: F, 200A – 600ADiscount schedule H6: Handles, shafts, accessories
NFC Style
ION
OOFF
Fu
sib
le
ABB Control Inc. 2.35AC 1700 – 5/00
BS fuse pattern switches (20A – 32A)Handle and shaft included
Catalog Number Rated op. current/ Fuse Fusenumber of poles Rated op. power type and standard
415V 690V size
BS fuse pattern fusible disconnect switches1
20A – 800A
1 Please consult factory for additional information.2 The fourth pole is provided with a solid link which can be replaced with a fuse.
BS pattern switches (32A – 800A)Handle and shaft includedFuse covers included for 200A – 800A
FBritish
Standard
Rated Rated operational current/ Weight
Number opera- Ith Rated operational power in withCatalog
of poles tional (open) category AC23A, IEC947 [A/kW] pack-number voltage age
AC23/[V] [A] 230V 400V 415V 500V 690V [kg]
OS20B12A1 3 20 A 20A A1OS20B22A1N1 3 + non-fused neutral 10 kW 15 kW 20 AOS20B22A1F 4
OS32B12A1 3 32 A 32A A1 BS 88-2OS32B22A1N1 3 + non-fused neutral 15 kW 25 kW 32 A IEC 269-2-1OS32B22A1F 4
OS32B12A2 3 32 A 32A A2OS32B22A2N1 3 + non-fused neutral 15 kW 25 kW 32 A
OS32B12F1 3 32 A 32A F1 BS 88-6OS32B22F1N1 3 + non-fused neutral 15 kW 25 kW 32 A
I
O
NOI
OO
FF
OS32B12A1
OESA200B3PL1
OS32B12 3 1.3OS32B22N1 42 500 32 32/7.5 32/11 32/15 32/15 — 1.6
OS63B12 3 1.3OS63B22N1 42 690 63 63/15 63/30 63/30 63/30 401/30 1.6
OS100B12 3 1.5OS100B13 42
690 125 100/30 100/55 100/55 100/70 501/45 1.8OS100B01 1 0.9OS100B11 2 1.9
OS160B12 3 1.5OS160B13 4 690 160 100/30 100/55 100/55 100/70 501/45 1.8OS160B01 1 0.9OS160B11 2 1.2
OESA200B3PL1 3 7.1OESA200B4PL1 42
690 200 200/57 200/100 200/110 200/140 200/180 8.2OESA200B1PL1 1 5.1OESA200B2PL1 2 6.1
OESA250B3PL1 3 690 250 250/70 250/132 250/140 250/170 250/230 7.1OESA250B4PL1 42 8.2
OESA315B3PL1 3 7.9OESA315B4PL1 42
690 315 315/90 315/100 315/100 315/220 315/290 8.9OESA315B1PL1 1 5.9OESA315B2PL1 2 6.9
OESA400B3PL1 3 8.3OESA400B4PL1 42
690 400 400/110 400/210 400/230 400/280 400/330 9.4OESA400B1PL1 1 6.3OESA400B2PL1 2 7.3
OESA630B3PL1 3 16.0OESA630B4PL1 42
690 630 630/180 630/315 630/340 630/400 630/540 21.0OESA630B1PL1 1 6.5OESA630B2PL1 2 11.0
OESA800B3PL1 3 18.0OESA800B4PL1 42
690 800 800/200 800/350 800/380 720/470 720/600 24.0OESA800B1PL1 1 6.7OESA800B2PL1 2 12.3
Discount schedule H4: F, 30A –100ADiscount schedule H5: F, 200A – 800A
OS63B12
OS160
ION
OOFF
Fu
sible
2.36 ABB Control Inc.AC 1700 – 5/00
DIN fuse pattern fusible disconnect switches1
32A – 800A
1 Please consult factory for additional information.
FDIN
DIN pattern switches (32A – 800A)Handle and shaft included
Rated Rated operational current/ Weight
Catalog Number opera- Ith Rated operational power in with
number of poles tional (open) category AC23A, IEC947 [A/kW] pack-voltage age
AC23/[V] [A] 230V 400V 415V 550V 690V [kg]
OS32D12 3 1.3OS32D22N1 3 + non-fused neutral 690 32 32/7.5 32/11 32/15 32/15 — 1.6OS32D22F 4 1.6
OS63D12 3 1.3OS63D22N1 3 + non-fused neutral 690 63 63/15 63/30 63/30 63/30 40/30 1.6OS63D22F 4 1.6
OS125D12 3 1.5OS125D22N1 3 + non-fused neutral 1.8OS125D22F 4 690 125 100/30 100/55 100/55 100/70 50/45 1.8OS125D01 1 0.9OS125D11 2 1.2
OS160D12 3 1.5OS160D22N1 3 + non-fused neutral 1.8OS160D22F 4 690 160 100/30 100/55 100/55 100/70 50/45 1.8OS160D01 1 0.9OS160D11 2 1.2
OESA250D3PL 3 7.3OESA250D4PL 3 + non-fused neutral 8.2OESA250DF4PL 4 690 250 250/70 250/132 250/140 250/170 250/230 8.2OESA250D1PL 1 5.5OESA250D2PL 2 6.4
OESA400D3PL 3 8.3OESA400D4PL 3 + non-fused neutral 9.4OESA400DF4PL 4 690 400 400/110 400/210 400/230 400/280 400/330 9.4OESA400D1PL 1 6.3OESA400D2PL 2 7.3
OESA630D3PL 3 16.0OESA630D4PL 3 + non-fused neutral 21.0OESA630DF4PL 4 690 630 630/180 630/315 630/340 630/400 630/540 21.0OESA630D1PL 1 6.5OESA630D2PL 2 11.0
OESA800D3PL 3 18.0OESA800D4PL 3 + non-fused neutral 24.0OESA800DF4PL 4 690 800 800/200 800/350 800/380 720/470 720/600 24.0OESA800D1PL 1 8.5OESA800D2PL 2 13.0
OESA250P3PL
NOI
OO
FF
Discount schedule H4: F, 30A – 100ADiscount schedule H5: F, 200A – 800A
OS63D12
OS160
ION
OOFF
Fu
sib
le
ABB Control Inc. 2.37AC 1700 – 5/00
NFC fuse pattern fusible disconnect switches63A – 125A14x51 & 22x58
NFC fuse pattern (cylinder fuse links), (14x51 & 22x58)Handle and shaft included
Rated Weight
Number opera- Ith Rated operational power in withCatalog
of poles tional (open) category AC23A, IEC947 [A/kW] pack-number voltage age
AC23/[V] [A] 230V 400V 415V 550V 690V [kg]
1 Please consult factory for additional information.
FNFC
Discount schedule H4: F, 30A – 100A
OS50F12 3 690 50 50/15 50/25 50/25 50/33 50/45 1.3OS50F22F 4 690 50 50/15 50/25 50/25 50/33 50/45 1.6OS63F12 3 690 63 63/18.5 63/30 63/30 63/37 63/60 1.3OS63F22F 4 690 63 63/18.5 63/30 63/30 63/37 63/60 1.6
OS100F03 3 2.2OS100F04F 4 690 125 100/30 100/45 100/55 100/60 100/90 2.8OS100F04N1 3 + non-fuse N 2.8
OS125F03 3 690 1.3OS125F04F 4 690 125 125/37 125/60 125/60 125/80 125/110 1.6OS125F04N1 3 + non-fuse N 690 1.6
NFC fuse pattern switches (cylinder) (10x38) (14x51)Handle and shaft included
Catalog Number Rated op. current/ Fuse Fusenumber of poles Rated op. power type and standard
415V 690V size
OS25F1210 3 25 A 25A 10 x 38OS25F2210N1 3 + non-fused neutral 12 kW 22 kW 25 A IEC 269-2-1OS25F2210F 4
OS32F1214 3 32 A 32A 14 x 51OS32F2214N1 3 + non-fused neutral 15 kW 25 kW 32 A IEC 269-2-1OS32F2214F 4
OS32F1214
OS63F12
OS125F03
ION
OOFF
Fu
sible
2.38 ABB Control Inc.AC 1700 – 5/00
FFuse
monitor
Fuse monitors
Rated Weight Catalog Listvoltage (lbs.) number price
100 - 240 0.31 OFM240 $ 290380 - 600 0.31 OFM600
Suitable for 3 phase circuits. Includes 1 N.O. & 1 N.C. auxiliary contacts.
Fuse monitors
For switch Crimp terminal Catalog Listsize size (mm) number price
OS30 - 100 2.8 - 0.8 OFMZX211111OES200 - 800 6.3 - 0.8 OFMXZ4
Includes 6 crimp terminals. Type OFMZX4 includes.
Mounting accessories
Description• Indicates single phasing• Operates with all fuse types• No need for external supply voltage• Wide voltage range, 100-240VAC and 380-600VAC• UL Listed, EMC tested• Fuse monitor is automatically reset after the blown fuses have been replaced• One trip contact, one alarm contact and two LEDs (red and green)• Phase imbalance immune• Compact size• Snap-on and screw-on mounting for OS disconnects• Suitable to be used as a standalone device
1 Please contact ABB Control for more information.
OFM_
ION
OOFF
Fu
sib
le
ABB Control Inc. 2.39AC 1700 – 5/00
Motor operators1
for 200A – 800A Fusible disconnect switches
Motor operators1 — function I/O (On/Off)
For use on: Voltage Weight Catalog List(lbs.) number price
For use on: Voltage Weight Catalog List(lbs.) number price
For use on: Package Catalog List(pcs.) number price
OEMO 202_ – 303_ motor operators require a transfer mechanism.
Discount schedule H6: Handles, shafts and accessories
FMotor
operators
24 VDC/AC OEMO002/24VDCAC48 VDC/AC OEMO002/48VDCAC
110 VAC OEMO002/110VACOES200 – OES400 220 VAC 14.0 OEMO002/220VAC $ 6514
220 VDC OEMO002/220VDC230 VAC OEMO002/230VAC240 VAC OEMO002/240VAC
24 VDC/AC OEMO003/24VDCAC48 VDC/AC OEMO003/48VDCAC
110 VAC OEMO003/110VACOES600 – OES800 110 VDC 14.0 OEMO003/110VDC 7644
220 VAC OEMO003/220VAC220 VDC OEMO003/220VDC230 VAC OEMO003/230VAC240 VAC OEMO003/240VAC
24 VDC/AC OEMO202/24VDCAC48 VDC/AC OEMO202/48VDCAC
110 VAC 14.0 OEMO202/110VAC $ 7644OES200 – OES400 220 VAC OEMO202/220VAC
220 VDC OEMO202/220VDC240 VAC OEMO202/240VAC
24 VDC/AC OEMO303/24VDCAC48 VDC/AC OEMO303/48VDCAC
OES600 – OES800 110 VAC 14.0 OEMO303/110VAC 9490220 VAC OEMO303/220VAC240 VAC OEMO303/240VAC
OES200 – OES400 1 OEMOZX1 $ 400OES600 – OES800 1 OEMOZX2 400
Mounting kit for OEMO motor operator
OEMO__
Motor operators1 — function I-O-II
OEMO__
1 Not UL listed
Mounting options
On the door Behind the door
Behind the switch Flush mountings
ION
OOFF
Fu
sible
2.40 ABB Control Inc.AC 1700 – 5/00
Notes
ION
OOFF
Fu
sib
le
ABB Control Inc. 2.41AC 1700 – 5/00
IndexTechnical data
UL & CSA Technical data .......................................................................... 2.40IEC Technical ratings ................................................................................ 2.41Selecting switches per NEC ...................................................................... 2.43Selecting switches per IEC ........................................................................ 2.43Definitions .................................................................................................. 2.44Auxiliary contact timing diagrams .............................................................. 2.45
Approximate dimensionsDisconnect switches ...................................................................... 2.47 – 2.49Terminal lugs ............................................................................................. 2.50Conversion mechanisms ............................................................... 2.51 – 2.55Flange operated switches .......................................................................... 2.56Pre-charge switches .................................................................................. 2.57Fuses ......................................................................................................... 2.58Handles .......................................................................................... 2.59 – 2.60
Technical dataApproximate dimensions
ION
OOFF
Fu
sible
2.42 ABB Control Inc.AC 1700 – 5/00
Catalog number 3 pole OS30A_12 OS60J12 OS100J03 OES200J3 OES400J3 OES600J3 OES800L3
UL & CSA Technical datafor Fusible disconnect switchesOS30A_12 – OES800L3
UL & CSA
FTechnical
ratings
1 The following UL Listed switches are also CSA approved.
Approvals1 2 pole N/A N/A IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC3 pole UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC4 pole UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC UL98 & IEC
Technical ratings -40° to 40°C
General purpose amp rating A 30 60 100 200 400 600 800pf = 0.7 – 0.8
Max operating voltage V 600 600 600 600 600 600 600
Max horsepower rating/Max motor FLA current
pf = 0.4 – 0.5Three phase
200 – 208V HP/A 5/16.8 – 7.5/24.2 15/46.2 25/75.0 50/143.0 100/273 – 125/344 150/396 200/528
240V HP/A 7.5/22.0 15/42.0 30/80.0 60/145.0 125/312.0 200/480.0 250/602.0
480V HP/A 15/21.0 30/40.0 60/77.0 125/156.0 250/302.0 400/477.0 500/590.0
600V HP/A 20/22.0 50/52.0 75/77.0 150/144.0 350/336.0 500/472.0 600/ —
Single phase120V HP/A 2/24.0 — — — — — —
240V HP/A 3/17.0 — — — — — —
Short circuit rating with fuse kA 200 200 200 200 200 200 200
UL Fuse size A 30 60 100 200 400 600 800
UL Fuse type J/CC J J/T J/T J/T J/T L
EndurancesMin. Electrical endurance,
pf = 0.75 – 0.80 operation cycles 6000 6000 6000 6000 1000 1000 500
Mechanical enduranceoperation 20,000 20,000 20,000 16,000 12,000 10,000 7000
Physical characteristics
Weight 3 pole lb 1.54 2.86 3.30 15.20 17.18 37.44 37.44
4 pole lb 1.98 3.52 3.96 17.4 19.38 46.26 46.26
Dimension 3 pole H in 3.66 3.94 5.67 7.87 8.90 10.10 10.10
W in 4.15 5.63 7.07 10.32 11.26 14.80 14.80
D in 4.10 5.04 5.10 7.80 8.07 9.17 9.17
Shaft size square in .20 x 2.0 .24 x .24 .24 x .24 .47 x .47 .47 x .47 .47 x .47 .47 x .47
mm 5 x 5 6 x 6 6 x 6 12 x 12 12 x 12 12 x 12 12 x 12
Switch operating torque lb. in. 26.6 35.5 70.9 195 195 248 248for rotary 3 pole switches
Terminal lug kits Integral Integral OZXA-24 OZXA-25 OZXA-26 OZXA-27 OZXA-27
Wire range AWG #18 – 8 #14 – 4 #14 – 2/0 #6 – 300kcmil #2 – 600kcmil (2) #2 – 600 kcmil (2) #2 – 600 kcmil
Torque:
Wire tightening lb. in. 17 30 120 375 500 500 500
Lug mounting lb. in. N/A N/A 50 230 480 480 480
Auxiliary contacts OA4G_ OA1/3G_ OA_G_ OA_G_ OZXK-__ OZXK-__ OZXK-__ OZXK-__
NEMA ratings, AC — A600 A600 A600 A600 A600 A600 A600
AC rated voltage VAC 250 600 600 600 600 600 600 600
AC thermal rated current A 6 10 10 10 10 10 10 10
AC maximum volt ampere making VA — 7200 7200 7200 7200 7200 7200 7200
AC maximum volt ampere breaking VA — 720 720 720 720 720 720 720
NEMA ratings, DC — P300 R300 R300 P600 P600 P600 P600
DC rated voltage VDC — 300 300 300 600 600 600 600
DC thermal rated current A — 1 1 1 5 5 5 5
DC maximum make break current A — 28 28 28 138 138 138 138
Torque:
Wire tightening lb. in. 7 7 7 7 7 7 7
Wire range AWG #22 – 14/#18 – 14 #18 – 14 #22 – 14 #22 – 14 #22 – 14 #22 – 14 #22 – 14
ION
OOFF
Fu
sib
le
ABB Control Inc. 2.43AC 1700 – 5/00
IEC Technical datafor Fusible disconnect switchesOS30A_12 – OES800L3
1 Ambient temperature 60°C: derating 20 percent. Mounting on ceiling: derating 10 percent. Mounting on wall, horizontal fuses: derating 8 percent.2 The ambient air temperature does not exceed +40°C and its average over a period of 24h does not exceed +35°C according to IEC 947.3 For 30A switches, use 2 + 2 parallel contacts in series.4 Available on request.5 IEC 947-3, utilization category B, infrequent operation.6 Pollution degree 3: Conductive pollution occurs, or dry, non-conductive pollution occurs, which becomes conductive due to condensation.
Catalog number 3 pole OS30A_12 OS60J12 OS100J03 OES200J3 OES400J3 OES600J3 OES800L3
IEC
FTechnicalRatings
Technical ratings -40° to 40°C
Rated insulation voltagePollution degree 36 V 1000 1000 1000 1000 1000 1000 1000
Dielectric strength 50Hz/60Hz, 1 min kV 10 10 10 10 10 10 10
Rated impulse withstand voltage kV 12 12 12 12 12 12 12
Rated thermal current, Ith/max. fuse power dissipation1
AC 20/DC 20 open2 A/W 32/3.5 63/7.5 160/12 200/22 400/45 630/60 800/65
40°C enclosed A/W 32/3.5 63/7.5 160/10, 135/12 200/22 400/34, 360/37 600/45, 570/50 720/55
Enclosed with solid links A/W 32 85 175 280 450 700 900
with minimum cable cross section Cu mm2
6 16 70 95 240 2 x 185 2 x 240
Rated operational voltageAC 20 and DC 20V 1000 1000 1000 1000 1000 1000 1000
AC Rated operational currents
AC 21A 500V A 32 63 160 200 400 630 800
690V A 32 63 160 200 400 630 800
AC 22A 500V A 32 63 160 200 400 630 800
690V A 32 63 160 200 400 630 800
AC 23A 500V A 32 635 1605 200 400 630 720
690V A 32 635 1605 200 400 630 720
DC Rated operational currents/poles in series
DC21A 48V A 32/23 4 4 200/2 400/2 630/2 800/2
110V A 32/2 4 4 200/2 400/2 630/2 800/2
220V A 32/2 4 4 200/2 400/2 630/2 800/2
440V A 32/4 4 4 200/2 400/2 630/2 800/2
750V A — 4 4 200/3 400/3 630/3 800/3
1000V A — 4 4 200/4 400/4 630/4 800/4
DC22A 48V A 32/23 4 4 200/2 400/2 630/2 800/2
110V A 32/2 4 4 200/2 400/2 630/2 800/2
220V A 32/2 4 4 200/2 400/2 630/2 800/2
440V A 32/4 4 4 200/2 400/2 630/2 800/2
750V A — 4 4 200/3 400/3 630/3 800/3
1000V A — 4 4 200/4 400/4 630/4 800/4
DC23A 48V A 32/23 4 4 200/2 400/2 630/2 800/2
110V A 32/2 4 4 200/2 400/2 630/2 800/2
220V A 32/2 4 4 200/2 400/2 630/2 800/2
440V A 32/4 4 4 200/2 400/2 630/2 800/2
750V A — 4 4 200/3 400/3 630/3 800/3
1000V A — 4 4 — — 630/4 800/4
Rated operational power AC23A
230V kW 8 18.5 45 57 110 180 200
400V kW 14 30 80 100 210 315 350
415V kW 15 30 90 110 230 340 380
500V kW 18 37 110 140 280 400 470
690V kW 25 60 132 180 330 540 600
2 polesin series
Load
3 polesin series
4 polesin series
Load Load Load
2 + 2 parallel contacts in series
ION
OOFF
Fu
sible
2.44 ABB Control Inc.AC 1700 – 5/00
IEC Technical datafor Fusible disconnect switchesOS30A_12 – OES800L3
Catalog number 3 pole OS30A_12 OS60J12 OS100J03 OES200J3 OES400J3 OES600J3 OES800L3
IEC
1 AC15 / DC12, according to IEC 947-5-12 AC15, according to IEC 947-5-13 Values shown are corresponding max. allowed cut-off current, peak-values per single phase fuse tests.
FTechnical
ratings
Rated breaking capacity
in category AC-23A 500V A 256 504 1280 2000 3200 5760 5760
690V A 256 504 1280 2000 3200 5760 5760
Rated breaking capacity/poles in series
in category DC-23 <220V A 128/2 — — 1000/2 1600/2 3200/2 3200/2
440V A 128/4 — — 1000/2 1600/2 3200/2 3200/2
500 – 750V A — — — 1000/3 1600/3 3200/3 3200/3
1000V A — — — — — 3200/4 3200/4
Rated conditional short-circuit current r.m.s.3
80 kA, 415V kA 9 17 22 40 40 75 75
100 kA, 500 V kA 7.5 17 22 40 40 75 75
50 kA, 690 V kA 6 13 15 35 35 60 60
Rated short time withstand current, 1s. kA 1 2.5 5 8 10 16 16
Rated capacitor power
– The capacitor rating of the fusible
disconnect switch is limited by the fuse link
400 V kVar 15 30 — 90 180 250 310
415V kVar 15 32 — 100 200 270 340
690V kVar 25 50 — 160 325 450 550
Power loss/pole
with rated current, without fuse W 2 4 9 5 30 55 77
Mechanical endurance operations 20,000 20,000 20,000 16,000 16,000 10,000 10,000
Fuse types, IEC 269-2 DIN 43620 — 000, 00 000, 00 0 – 1 0 – 2 3 3
NFC 10 x 38, 14 x 51 14 x 51, 22 x 58 22 x 58 0 – 1 0 – 2 3 —
BS 88 A1, A2, F1 A2 – A3 A2 – A4 B1 – B3 B1 – B4 C1 – C2 C1 – C3
size/distance of link bolts M4/44.5(A1) M5/73 M5/73 M8/111 M8/111 M10/133, 184 M10/133, 184M5/73(A2) M8/94
Physical characteristics
Weight 3 pole kg 0.7 1.3 1.5 6.9 7.8 17.0 17.0
4 pole kg 0.9 1.6 1.8 7.9 8.8 21.0 21.0
Dimension 3 pole H mm 93 100 144 200 226 282 282
W mm 106 143 179 262 286 376 376
D mm 104 120 129 198 205 233 233
Shaft size square mm 5 x 5 6 x 6 6 x 6 12 x 12 12 x 12 12 x 12 12 x 12
Terminals
Built-in terminal size mm2
0.5 – 10 2.5 – 25 — — — — —
Terminal bolt size, metric thread
diameter x length mm — — — M6 x 20 M10 x 40 M10 x 40 M12 x 40 M12 x 40
Terminal bolt tightening torque Nm 2 3.5 6 – 9 30 – 44 30 – 44 50 – 75 50 – 75
Fuse-links bolts tightening torque Nm 2 3.5 3.5 – 5 15 15 40 40
Operating torque Nm 3 4 8 22 22 28 28
Auxiliary contacts OA4G_ OA1/3G OA_G_ OA_G_ OZXK-_ OZXK-_ OZXK-_ OZXK-_1 2 2 2
Ratings according to IEC 947-5-1Rated voltage, Ui VAC 690 690 690 690 690 690 690 690Thermal current, Ith A 10 16 16 16 10 10 10 10AC12 / DC12, Ie Ue= 24V A — / 6 — — — — — — —
120V A — / 6 — — — 8 / — 8 / — 8 / — 8 / —125V A — — — — — / 1.1 — / 1.1 — / 1.1 — / 1.1230V A — 6 / — 6 / — 6 / — 6 / — 6 / — 6 / — 6 / —250V A 3 / 0.1 — — — — / 0.55 — / 0.55 — / 0.55 — / 0.55400V A — 4 / — 4 / — 4 / — 4 / — 4 / — 4 / — 4 / —415V A — — — — 4 / — 4 / — 4 / — 4 / —440V A 2 / — — — — — / 0.31 — / 0.31 — / 0.31 — / 0.31480V A — — — — 3 / — 3 / — 3 / — 3 / —500V A — — — — 3 / 0.27 3 / 0.27 3 / 0.27 3 / 0.27600V A — — — — — / 0.2 — / 0.2 — / 0.2 — / 0.2690V A — 2 / — 2 / — 2 / — 2 / — 2 / — 2 / — 2 / —
ION
OOFF
Fu
sib
le
ABB Control Inc. 2.45AC 1700 – 5/00
Selecting switchesper NEC & IEC
FTechnical
information
Selecting switches per IECUtilization categories
Nature of currentUtilization category
Typical applicationsFrequent operation Infrequent operation
• Category AC-23 includes occasional switching of individual motors. The switching of capacitors of tungsten filament lamps shall be subject to agreement betweenmanufacturer and user.
AC-20A AC-20B • Connecting and disconnecting under no-loadconditions
AC-21A AC-21B • Switching of resistive loads including moderateoverloads
Alternating current AC-22A AC-22B • Switching of mixed resistive and inductiveloads, including moderate overloads
AC-23A AC-23B • Switching of motor loads or other highlyinductive loads
DC-20A DC-20B • Connecting and disconnecting under no-loadconditions
DC-21A DC-21B • Switching of resistive loads including moderateoverloads
Direct current DC-22A DC-22B • Switching of mixed resistive and inductiveloads, including moderate overloads (e.g.,shunt motors)
DC-23A DC-23B • Switching of highly inductive loads (e.g., seriesmotors)
Mechanical endurance Number of operations Number of operations
100A 10,000 2000315A 8000 1600
>315A 2000 400
Article 430 of the US National Electric Code includes two methods for properly sizing disconnect switches:
Selecting switches per NEC
1. Single motor applicationA properly sized disconnect switch for a single motor will:a) have an ampere rating greater than or equal to 115 percent
of the rated motor full load current; or,b) have a HP rating greater than or equal to the rated motor
HP (at applied voltage) if the disconnect switch underconsideration is HP rated.
2. Combination load applicationA properly sized disconnect switch for a combination load willbe selected by adding all the simultaneous individual loads inthe circuit under consideration.Using motor nameplate information, load information, andtables from section 430 of the NEC, determine one equivalentfull load current and one equivalent locked rotor current. Theequivalent locked rotor current can be used with table 430-151to determine an equivalent HP rating. Select a disconnectswitch:a) greater than or equal to 115 percent of the equivalent full
load current; and,b) greater than or equal to the equivalent HP rating.
ION
OOFF
Fu
sible
2.46 ABB Control Inc.AC 1700 – 5/00
DefinitionsF
Definitions
AC – Alternating current — Current that reverses its directionof flow twice per cycle.
Ambient temperature — Temperature of the air surroundingthe unit.
Amp rating — The basic unit of measurement for electriccurrent (columbs / seconds).
Conventional thermal current Ith — Value of the current thedisconnect switch can withstand with poles in closed position,in free air for an eight hour duty, without the temperature rise ofits various parts exceeding the limits specified by thestandards.
Cycle duration — Total time of the on-load + off-load period.
DC – Direct current — Current that flows in only one direction.
Electrical endurance — Number of on-load operating cycles.
IEC environmental protection type — see page 1.59.
Full load amp current FLA — The current required by a motorto produce full-load torque at the motor's rated speed.
Inductive load — An electrical load characterized by havingsignificant inrush (5 to 6 times FLA for typical design-B ACinduction motors).
kW — Kilowatts (1000 watts)
Lockout/Tagout — Means of removing power from electricalequipment during inspection, service or repair.
Make / Break — ON / OFF
Mechanical endurance — Number of off-load operatingcycles.
Poles in series — Means of connection poles using wires orbus bars to increase breaking capacity of load.
Power factor — The relationship between working power andtotal power consumed. Power factor measures how effectivelyelectrical power is being used.
Rated insulation Ui — Voltage value which designates theunit and to which dielectric tests, clearance and creepagedistances are referred.
Rated operating current Ie — Current value stated by themanufacturer and taking into account the rated operatingvoltage Ue, the rated frequency, the rated duty, the utilizationcategory, the electrical contact life and the type of protectiveenclosure.
Rated operating voltage Ue — Voltage value to whichutilization characteristics of the disconnect switch are referred,i.e. phase-to-phase voltage in 3 phase circuits.
Rated short circuit making capacity Icm — The rated short-circuit making capacity of a disconnect switch, a disconnectoror a switch-disconnector is the value assigned to equipment atthe rated operational voltage, frequency (if any) and specifiedpower-factor for AC or time constant for DC. It is expressed asthe maximum prospective peak current under prescribedconditions.
Rated short time withstand current Icw — The rated short-time withstand current of a disconnect switch, a disconnectoror a switch-disconnector is the value that the equipment cancarry without damage, under the test conditions specified in therelevant product standard. The value of the rated short-timewithstand current shall be not less than twelve times themaximum rated operational current unless otherwise stated bymanufacturer and the duration of the current shall be 1 s.
Resistive load — An electrical load characterized by nothaving any significant inrush current.
Short circuit protection co-ordination — Co-ordination types"1" and "2" are defined in IEC 947-4-1.
Type 1 co-ordination — There has to be no discharge ofparts beyond the enclosure. Damage to the contactor andthe overload is acceptable.Type 2 co-ordination — No damage to the overload relay orother parts has occured, except that welding of contactor orstarter contacts is permitted, if they are easily separated.
Time constant — Ratio of inductance to the resistance: L/R =mH/Ohm = ms.
Torque — The force that produces rotation. It is commonlymeasured in pound-feet (lb-ft). Torque applies to such thingsas motor operations, handle rotations, wire tightening.
UL environmental protection type — see page 1.58.
Volt — The unit of electrical potential difference andelectromotive force.
ION
OOFF
Fu
sib
le
ABB Control Inc. 2.47AC 1700 – 5/00
Auxiliary contact timing diagramsfor Fusible disconnect switchesOS30_ – OS100
Contacts closing Contacts opening1 Main contacts close 4 Main contacts open2 N.O. auxiliary contacts close 5 N.O. auxiliary contacts open3 N.C. auxiliary contacts open 6 N.C. auxiliary contacts close
OS30_
OS60
FTiming
Diagrams
Catalog number Auxiliary contact Contact configuration
OS30_ OA4B1C 1 N.O. & 1 N.C.OA1G10 1 N.O.OA3G01 1 N.C.
Catalog number Auxiliary contact Contact configuration
O O
FF
I ON
ON
OFF➠
➠00
II
OFF 0
ON I
1
2
3
4
5
6
= Contacts in closed position= Contacts in closed position
Main contacts
N.O. auxiliary contact
N.C. auxiliary contact
0¡ 30¡ 60¡ 90¡ αLegend
OS60 OA1G10 1 N.O.OA3G01 1 N.C.
OA4B1C
OA4B1C
OA1G10
Test
OA3G01
Main contacts
N.O. auxiliary contact
N.C. auxiliary contact
N.O. auxiliary contact
N.C. auxiliary contact
-45¡ 0¡ 30¡ 60¡ 90¡ α
OA1G10
OA3G01
OA3G01
Test
OA1G10
Installed in mechansim
Installed on side of switch
Main contacts
N.O. auxiliary contact
N.C. auxiliary contact
N.O. auxiliary contact
N.C. auxiliary contact
-45¡ 0¡ 30¡ 60¡ 90¡ α
OS100
Catalog number Auxiliary contact Contact configuration
OS100 OA1G10 1 N.O.OA3G01 1 N.C.
OA3G01
OA3G01
OA1G10
Installed in mechanism
Installed on side of switch
OA3G01
Test
OA1G10Test location
Main contacts
N.O. auxiliary contact
N.C. auxiliary contact
N.O. auxiliary contact
N.C. auxiliary contact
N.O. auxiliary contact
N.C. auxiliary contact
-45¡ 0¡ 30¡ 60¡ 90¡ α
ION
OOFF
Fu
sible
2.48 ABB Control Inc.AC 1700 – 5/00
Auxiliary contact timing diagramsfor Fusible disconnect switchesOES200 – OES800
FTiming
Diagrams
OZXK-1 1 N.O. & 1 N.C.OZXK-2 2 N.O. & 2 N.C.
OES600 – OZXK-3 4 N.O. & 4 N.C.OES800 OZXK-4 2 N.O.
OZXK-5 4 N.O.OZXK-6 8 N.O.
OZXK-1 1 N.O. & 1 N.C.OZXK-2 2 N.O. & 2 N.C.
OES200 – OZXK-3 4 N.O. & 4 N.C.0ES400 OZXK-4 2 N.O.
OZXK-5 4 N.O.OZXK-6 8 N.O.
Catalog number Auxiliary contact Contact configuration
OES200 & OES400
OES600 & OES800Catalog number Auxiliary contact Contact configuration
0 30 60 90 αo o o o
Main contacts
No auxiliary contact
Nc auxiliary contact
OZXK-1OZXK-2OZXK-3OZXK-4OZXK-5OZXK-6
0 30 60 90 αo o o o
Main contacts
N.O. auxiliary contact
N.C. auxiliary contact
OZXK-1OZXK-2OZXK-3OZXK-4OZXK-5OZXK-6
00.0000.00
InchesMillimeters
ION
OOFF
Fu
sib
le
ABB Control Inc. 2.49AC 1700 – 5/00
Approximate dimensionsfor Fusible disconnect switchesOS30A_12 – OS60J12
OS30AJ12 & OS30ACC12
FDimensions
30A – 60A
OS60J12
4.10104
3.6693
3.8497.5
2.7570
0.184.5
0.9323.5
1.8346.5
1.5238.5
4.15105.5
2.95...3.1575...80
3.6693
2.5564.7
1.0627
0.184.5
3.94100
1.9750
3.6292
5.04128
0.246
4.72120
2.2356.6
1.5940.5
0.5514
5.63143
00.0000.00
InchesMillimeters
ION
OOFF
Fu
sible
2.50 ABB Control Inc.AC 1700 – 5/00
Approximate dimensionsfor Fusible disconnect switchesOS100J03 – OES200J3
1.7745
0.205
5.12130
7.80198
7.87200
6.77172
0.4712
2.4462
0.4912.5
5.91150
0.287
4.06103
0.98250.28
7DIA.
0.4311
DIA.
9.88251
12.76324
(4 pole)
10.32262
(3 pole)
7.87200
(2 pole)
5.43138
(2 pole)
7.87200
(3 pole)
10.32262
(4 pole)
0.7920
OES200J3
FDimensions100A – 200A
OS100J03
1.0226.0
0.082.0
4.72120
0.245
2.6467
4.35110.5
4.80122
6.67169.5
1.3835
1.1228.5
1.6040.5
1.6141.0
1.3835
1.4236.0
5.67144
8.35212
Terminal detail(enlarged)
6.6 X 10.6mmOB round hole
0.7920
0.5915
0.4712
0.4712
0.6115.5
0.6917.5
5.10129.5
5.69144.5
(2 pole)
7.07179.5
(3 pole)
8.44214.5
(4 pole)
00.0000.00
InchesMillimeters
ION
OOFF
Fu
sib
le
ABB Control Inc. 2.51AC 1700 – 5/00
Approximate dimensionsfor Fusible disconnect switchesOES400J3 – OES800J3
OES600J3 & OES800L3
OES400J3
2.7670
0.6115.5
5.91150
1.3835
0.5113
DIA.
0.287 DIA.
0.287
4.06103
1.7745
0.205
5.12130
8.07205
6.77172
0.4712
12.20310
8.90226
14.02356
(4 Pole)
11.26286
(3 Pole)
8.50216
(2 Pole)
0.9123
6.02153
(2 Pole)
8.78223
(3 Pole)
11.54223
(4 Pole)
0.359
DIA.
3.5490
0.9624.5
3.7495
0.6316
1.5840
0.4311 DIA.
7.48190
14.49368
8.27210
10.10282
0.4712
4.41112
9.17233
0.246
1.5840
1.4236
18.35466
(4 pole)
14.80376
(3 pole)
11.26286
(2 pole)
15.67398
(4 Pole)
12.13308
(3 Pole)
8.58218
(2 Pole)
FDimensions400A – 800A
00.0000.00
InchesMillimeters
ION
OOFF
Fu
sible
2.52 ABB Control Inc.AC 1700 – 5/00
Approximate dimensionsfor Terminal lugs
OZXA-25 — for use with 200A switches
OZXA-26 — for use with 400A switches
OZXA-27 — for use with 600A switches
OZXA-24 — for use with 100A switches
0.63 16
0.45 11.5
0.41 10.5
1.46 37
C.L.
0.18 4.5
0.10 2.5
0.79 20
0.26 6.5
0.41 10.5
0.45 11.51.91
48.5
1.00 25.5
C.L.
0.26 6.5
0.125 3.1
1.12 28.5
0.43 11
1.56 39.5
0.43 11
0.13 3.3
1.50 38
0.87 22
0.63 16
3.19 81
C.L.0.53 13.5
2.40 61
2.00 51
1.56 39.5
0.43 11
0.13 3.3
0.87 22
0.63 16
3.19 81
C.L.0.53 13.5
FDimensions
Lugs
OZXA-175 — power distribution lug, for 200A switch
OZXA-33 — for use with 400A switches
OZXA-175/400 — for use with 600-800A switches
0.41 10.5
0.45 11.5
1.91 48.5
1.00 25.5
C.L.
0.26 6.5
0.125 3.1
1.12 28.5
0.43 11
0.31 8
3.25 82.5
C.L. 0.42 9.5
1.18 30
2.75 70
0.06 1.5
0.44 11
1.91 48.5
2.00 51.0
1.12 28.5
0.65 16.5
C.L.0.53 13.5 0.19
4.8
00.0000.00
InchesMillimeters
ION
OOFF
Fu
sib
le
ABB Control Inc. 2.53AC 1700 – 5/00
Approximate dimensionsfor 30A Conversion mechanisms
6 pole — OWP5DS1
3 pole transfer switch — OWC5DSH1, OWC5DSH1X
9.49241
8.74222
4.61117
4.13105
4.65118
0.5514
9.49241
8.74222
4.61117
4.13105
4.65118
2.9074
0.5514
FDimensions
Conversionmechanisms
Mechanical interlock — OWM5DS1
9.49241
8.74222
4.61117
4.13105
4.65118
0.5514
OWP5DS1_ Minimum Maximum1
in combination with: inches/mm inches/mm
OS30_ 5.51 / 140 n/a
OWC5DSH1_ Minimum Maximum1
in combination with: inches/mm inches/mm
OS30_ 5.51 / 140 n/a
OWM5DS1 Minimum Maximum1
in combination with: inches/mm inches/mm
OS30_ 5.51 / 140 n/a
00.0000.00
InchesMillimeters
ION
OOFF
Fu
sible
2.54 ABB Control Inc.AC 1700 – 5/00
Approximate dimensionsfor 60A – 100A conversion mechanisms
6 or 8 pole — OESA-ZW2
Transfer switch — OESA-ZW1 & OESA-ZW1XOESA-ZW1 Minimum Maximum1
in combination with: inches/mm inches/mm
OS60 7.87/200 13.23/336
OS100 8.27/210 13.23/336
For installation of 6 or 8 pole and transfer mechanisms, the following minimumand maximum mounting dimensions are given below.
Note: Deeper enclosures will require a longer shaft, please select a 6mm shaftfrom page 2.19.
OESA-ZW2 Minimum Maximum1
in combination with: inches/mm inches/mm
OS60 6.89/175 10.83/275
OS100 6.89/175 10.83/275
Note: Deeper enclosures will require a longer shaft, please select a 12mm shaftfrom page 2.25, and an OETL-ZX95 shaft extension coupler from page 2.21.
1.77...9.4945...240
(15mm Steps)
0.5915
0.246
0.246
0.4712
4.72120
7.72196
1.5740
2.8372
10.71272
0.5915
2.1755
4.57116
1.5439 0.24
6
0.246
0.246
1.5439
3.54...9.4590...240
15mm STEPS
FDimensions
Conversionmechanisms
7.48190
0.245
Mechanical interlock — OTZW10OTZW10 Minimum Maximum1
in combination with: inches/mm inches/mm
OS60 - OS 100 6.3 / 160 —
Note: Deeper enclosures will require a longer shaft, please select a 6mm shaftfrom page 2.19.
00.0000.00
InchesMillimeters
ION
OOFF
Fu
sib
le
ABB Control Inc. 2.55AC 1700 – 5/00
Approximate dimensionsfor 200A – 800A conversion mechanisms
6 or 8 pole — OETL-ZW9
Transfer switch — OETL-ZW12
For installation of 6 or 8 pole and transfer mechanisms, the following minimumand maximum mounting dimensions are given below.
OETL-ZW9 Minimum Maximum1
in combination with: inches/mm inches/mm
OES200 9.84/250 N/A
OES400 9.84/250 N/A
OES600 11.02/280 N/A
OES800 11.02/280 N/A
OETL-ZW12 Minimum Maximum1
in combination with: inches/mm inches/mm
OES200 10.43/265 N/A
OES400 10.82/275 N/A
OES600 11.81/300 N/A
OES800 11.81/300 N/A
2.36...17.3260...240
20mm Steps0.7920
0.4712
1.4637
4.53115
1.8948
1.5740
3.3184
0.4712
3.5490
0.7920
8.27...24.02210...610
20mm steps
0.4712
0.4712
26.06662
FDimensions
Conversionmechanisms
00.0000.00
InchesMillimeters
ION
OOFF
Fu
sible
2.56 ABB Control Inc.AC 1700 – 5/00
Bypass switch — OETL-ZW13
Mechanical interlock — OETL-ZW3, OETL-ZW14 & OETL-ZW15
Approximate dimensionsfor 200A – 800A conversion mechanisms
For installation of bypass and mechanical interlock mechanisms, the followingminimum and maximum mounting dimensions are given below.
OETL-ZW13 Minimum Maximum1
in combination with: inches/mm inches/mm
OES200 11.42/290 N/A
OES400 11.61/295 N/A
OES600 12.80/325 N/A
OES800 12.80/325 N/A
OETL-ZW3, 14, 15 Minimum Maximum1
in combination with: inches/mm inches/mm
OES200 9.06/230 N/A
OES400 9.45/240 N/A
OES600 10.43/265 N/A
OES800 10.43/265 N/A
3.5490
26.06662
0.7920
4.53115
2.0752.5 1.32
33.5
3.3184
8.27...22.44210...570
0.4712
9.84...24.02250...610
0.4712
0.4712
0.4712
Dimensions in Inches & mm
OETL-ZW3 11.81 0.47 300.0 12.0OETL-ZW14 9.84 0.47 250.0 12.0OETL-ZW15 19.69 0.47 500.0 12.0
BA
A
B
FDimensions
Conversionmechanisms
00.0000.00
InchesMillimeters
ION
OOFF
Fu
sib
le
ABB Control Inc. 2.57AC 1700 – 5/00
Class J (600V)
Class T (300V)
Class CC (600V) — Rejection type
Class L (600V)
Class T (600V)
Ampere rating A B C D E F G H
1 – 30 .88 .41 — — — — —31 – 60 .88 .56 — — — — —
61 – 100 2.16 .81 .12 .75 1 3.62 .38101 - 200 2.45 1.06 .19 1.12 1.38 4.38 .38201 - 400 2.75 1.33 .25 1.62 1.88 5.25 .53401 - 600 3.06 1.62 .31 2.00 2.12 6.00 .69601 - 800 3.38 2.08 .38 1.75 2.22 .55 .88
Ampere rating A B C D F G J
Ampere rating A B C D E F G H
Dimension A B C D
1 – 30 2.25 .81 — — — — — —31 – 60 2.38 1.06 — — — — — —
61 – 100 4.62 1.12 .12 .75 1 3.62 .38 .28101 - 200 5.75 1.62 .19 1.12 1.38 4.38 .38 .28201 - 400 7.12 2.12 .25 1.62 1.88 5.25 .53 .41401 600 8.00 2.5 .38 2.00 2.12 6.00 .69 .53
Ampere rating A B C D F G J
1.500 (38.1) 0.406 (10.31) 0.250 (6.35) 0.125 (3.18)
200 - 600 8.62 2.00 .31 1.62 2.41 6.25 1.12 .62601 - 800 8.62 2.50 .38 2.00 2.41 6.25 1.12 .62
1 – 30 1.50 .56 — — — — —35 – 60 1.56 .81 — — — — —
70 – 100 2.95 — .12 .75 2.36 .28 1.64110 - 200 3.25 — .19 .88 2.50 .34 1.66225 - 400 3.62 — .25 1.00 2.69 .41 1.64450 - 600 3.98 — .31 1.25 2.95 .48 1.78601 - 800 4.37 — .38 1.75 3.17 .55 1.88
Approximate dimensionsfor Fuses
EG
C
B
F
A
H D
A B
C
D
F
J G
0.133.18
1.5038.10
0.4110.31
0.256.35
EG
C
B
F
A
H D
A B
C
D
F
J G
FDimensions
Fuses
00.0000.00
InchesMillimeters
ION
OOFF
Fu
sible
2.58 ABB Control Inc.AC 1700 – 5/00
Approximate dimensionsHandles
Pistol handles
2.6667.5
2.0953
45º
MOUNTING HOLEDETAIL
1.2231 D
0.205 D
L
1.7745
B
L
1.5740
2.2056
45º1.77
45 D
0.287 D
MOUNTING HOLEDETAIL
3.94100 2.76
70.0
B
FDimensions
Handles
OH_45J5 1.8/45 0.20/5 1, 3R, 12OH_65J5 2.6/65 0.20/5 1, 3R, 12
OH_45J6 1.8/45 0.24/6 1, 3R, 12OH_65J6 2.6/65 0.24/6 1, 3R, 12OH_80J6 3.1/80 0.24/6 1, 3R, 12
OH_65J8 2.6/65 0.31/8 1, 3R, 12OH_80J8 3.1/80 0.31/8 1, 3R, 12
OH_125J12 4.9/125 0.47/12 1, 3R, 12OH_145J12 5.7/145 0.47/12 1, 3R, 12OH_175J12 6.9/175 0.47/12 1, 3R, 12
OH_65L5 2.6/65 0.20/5 1, 3R, 4, 4X, 12
OH_80L6 3.1/80 0.24/6 1, 3R, 4, 4X, 12
OH_80L8 3.1/80 0.31/8 1, 3R, 4, 4X, 12
OH_145L12 5.7/145 0.47/12 1, 3R, 4, 4X, 12OH_175L12 6.9/175 0.47/12 1, 3R, 4, 4X, 12
__ = Handle color, B (Black) or Y (Red/Yellow)
BL Shaft size UL / NEMA TypeCatalog number Inches/ mm Inches/ mm
YASDA-7 8.66/220 0.47/12 1, 3R, 4, 4X, 12
YASDA-8 8.66/220 0.47/12 1, 3R, 4, 4X, 12
YASDA-21 8.66/220 0.47/12 1, 3R, 4, 4X, 12
YASDA-6 12.60/320 0.47/12 1, 3R, 4, 4X, 12
BL Shaft size UL / NEMA TypeCatalog number Inches/ mm Inches/ mm
OH_2A_
0.1253.2
0.8822.5
0.9624.5
MOUNTING HOLEDETAIL
2.5665
1.3033
0.3910
0.5514
B
OHB2AJ1 No 0.20/5 1, 3R, 12
OHY2AJ1 No 0.20/5 1, 3R, 12
OHB2AJ Yes 0.20/5 1, 3R, 12
OHY2AJ Yes 0.20/5 1, 3R, 12
B
Catalog number Defeatable Shaft size UL / NEMA TypeInches/ mm