Network-Enabled PowerFlex 525 Commissioning Lab

Transcript of PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with...

Page 1: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

Network-Enabled PowerFlex 525

Commissioning Lab

Page 2: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

`

Network-Enabled PowerFlex 525 Commissioning Lab

Contents

Before you begin ........................................................................................................................................................... 3 About this lab ................................................................................................................................................................ 3 Tools & Prerequisites ..................................................................................................................................................... 3 Network Setup ............................................................................................................................................................... 4 About the Demo Box ..................................................................................................................................................... 5 Exercise 1: Using the HIM Keypad and Display .............................................................................................................. 6 Information .................................................................................................................................................................... 6 Reset Drive to Defaults ................................................................................................................................................ 10 Configuring Drive Parameters ..................................................................................................................................... 11 Exercise 2: Using the USB to access “Mains Free” Drive configuration files in the Control Module …………………..…..12 Exercise 3: Utilizing the file in drive and Connected Component Workbench offline with USB Cable. ................ 15 Connecting to the Drive ............................................................................................................................................... 15 Exercise 4: PowerFlex 525 Start-Up Wizard ................................................................................................................ 23 Exploring Drive Parameters via Parameter Groupings, AppView™, and CustomView™ ............................................. 26 Exercise 5: PowerFlex 525 Drive Add-On Profile with RS Logix 5000 Software. . ....................................................... 42 About Integrated Drive Profiles and Premier Integration ........................................................................................... 42 Using RS Logix 5000 with the PowerFlex 525 Drive Add-On Profile ............................................................................ 43 Exercise 6: Automatic Device Configuration (ADC) with the PowerFlex 525 AC drive ................................................ 60 About Automatic Device Configuration (ADC) ............................................................................................................. 60 Exploring the setup of Automatic Device Configuration (ADC) ............................................................................................ 61

Page 2 of 64

Page 3: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

Before you begin

Please review the following information before starting this lab.

About this lab Learn the basics of drive programming using the new PowerFlex 525 AC drive. Students will configure and commission the 525 drive utilizing a USB cable “Mains Free” with Connected Components Workbench™ and RS Logix 5000 version 20.01. Finally, this lab shows how Premier Integration enhances the use of the Network-Enabled PowerFlex 525 drive with Logix controllers. See how to save time during system development, operation, and maintenance. Also, learn about the new Automatic Device Configuration (ADC) feature for PowerFlex 750-Series and PowerFlex 525 drives in RS 5000.

Tools & Prerequisites

Software programs required • RS Logix 5000™ Logix v20.00.03

• PowerFlex525 AOP for RSLogix5000 v17 to v20+ v1.01.249

• Connected Components Workbench™ v4.00.00

• RS Linx Classic™ v2.59.00

Hardware devices required • 1769-L43 or the 1769-L35e PLC Demos

• PowerFlex 525 v1.003.80

• Ethernet patch cables

• USB A to B Cable

Files required

• L43_PF525_Lab.ACD Depending on which demo you are working with

• L35e_PF525_Lab.ACD Depending on which demo you are working with

Page 3 of 64

Page 4: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

`

Setup Network

Laptop PC

PowerFlex 525 Drive 1769-L35e Demo

1769-L43 Demo

IP Addresses For Demos Laptop PC 100.100.100.100 1769-L35e/L43 100.100.100.35 PF-525 Drive 100.100.100.25 9300-ENA LAN 100.100.100.1

Ethernet Connections

Connect From Connect To 1 Laptop PC Switch on Demo 2 L43/L35e E-net port Switch on Demo 3 PF525 Drive E-net port Switch on Demo

Page 4 of 64

Page 5: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

About the Demo Boxes

1769-L35e Demo

Switch Start Stop

1769-L43 Demo

Stop Start Switch

Page 5 of 64

Page 6: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

`

Exercise 1: Using the HIM Keypad and Display In this section you will perform the following:

• Review key information about the HIM keypad and display of the PowerFlex 525

• Reset the PowerFlex 525 drive to defaults

• Configure several parameters

Information

The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid Crystal Display (LCD) Human Interface Module (HIM). Some of its key features are as follows:

• Improved visibility

• Increased resolution

• Descriptive scrolling text

o Three adjustable speeds

• Full Alphanumeric with 5 Digits and 16 Segments

Page 6 of 64

Page 7: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

Display and Control Keys

• AppView: Dedicated sets of parameters grouped together for the following applications

o Conveyor

o Mixer

o Compressor

o Centrifugal Pump

o Blower

o Extruder

o Positioning

o Textile / Fiber

• CustomView: Parameter Groups can be customized specifically for your application

o Add up to a max of 100 parameters

o Save new “CustomView” for easy copy and paste

Page 7 of 64

Page 8: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

` Control and Navigation Keys

Page 8 of 64

Page 9: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

Viewing and Editing Parameters

The following is an example of basic integral keypad and display functions. This example provides basic navigation instructions and illustrates how to program a parameter. Just read through the following.

Page 9 of 64

Page 10: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

`

Reset Drive to Defaults

1. Press the Esc button until you see on the keypad display.

2. Press the Select button and use the Up or Down arrows or until you see the Basic

Program group on the HIM display.

3. Press the Enter or Sel button to enter the Basic Program group. The right digit of the last viewed parameter in that group will flash.

4. Use the Up or Down arrows until you see P053. If you wait one (1) second, you will notice that the HIM display scrolls with P053 – Reset to Defaults.

Note: Rather than pressing the Up and Down arrows to scroll through many

parameters in numerical order, you can also press Sel button to move from digit to digit or bit to bit. The digit or bit that you can change will flash.

Page 10 of 64

Page 11: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

5. Once is displayed, Press the Enter button. You will see “0 - Ready/Idle” scroll across the

display. Press the Up or Down arrows until you see “2 – Factory Reset”.

6. Press the Enter button to confirm. The drive will fault with a scrolling message of “F048 – Parameters Defaulted” See picture below.

7. Pres the Stop button to clear the fault from the drive.

Configuring Drive Parameters

8. Take what you have learned about the keypad operation from the Reset Drive to Defaults section to make the following Communication group parameter changes:

• C128 – EN Addr Sel = 1 - “Parameters” • C129 – EN IP Addr Cfg 1 = 100 • C130 – EN IP Addr Cfg 2 = 100 • C131 – EN IP Addr Cfg 3 = 100 • C132 – EN IP Addr Cfg 4 = 25 • C133 – EN Subnet Cfg 1 = 255 • C134 – EN Subnet Cfg 2 = 255 • C135 – EN Subnet Cfg 3 = 255

• C136 – EN Subnet Cfg 4 = 0

9. In order for communication settings to take effect, cycle power to the drive by removing power to the drive. In this lab you would simply un plug the drive from the receptacle until the display shows no sign of power (Green back ground light is extinguished.

Page 11 of 64

Page 12: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

`

Exercise 2: Using the USB to access “Mains Free” Drive configuration files in the Control Module

The purpose of this exercise is to access the drive configuration file (xxxxx.PF5) in the drive so it can be imported into the Connected Components Work Bench or RS Logix 5000 software program where you can make parameter changes. This file can then be exported out to a xxxxx.PF5 file which can then be down loaded back into the drive with the utility using the USB cable.

1. Connect the USB cable from the PC USB Port to the Control Module after you have removed it from the Drive Power

Core.

2. Windows 7 will detect this connection as a removable disk in the “Windows Explorer” Tree and or “AutoPlay” display the following:

3. Click on “Open folder to view files or Select Removable Disk from the Explorer pane: 4. Double click or open the executable file PF52X.exe utility.

Page 12 of 64

Page 13: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

5. Select or click on the “Upload” Button:

6. Click on Next:

7. Click on Browse: then select Libraries\Documents\MyDocuments\Network Expo Labs

8. Give the File your desired name and store it where ever you like. For this Lab please type in the following name:

PF525_Drive.pf5.

. 9. Click on the Save Button.

Page 13 of 64

Page 14: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

` 10. Click on the Upload button.

11. Click on the Close Button and close any other boxes or screens that may be open.

Later we will use this utility to download the completed drive configuration file back into the drive.

This utility is just used to upload and download the drive file and it cannot make any changes to the Parameters. Changes are made using Connected Components Work Bench (CCW) or RS Logix 5000 Version 17 to 20 or Studio Designer 5000 version 21 or newer. NOTE: The utility is a means to transport the Drive configuration back to the drive via USB cable. This utility and or the USB cable is not used when the drive is fully assemble (control Module is mated to the Power module) where normal power is applied to the L1, L2 and or L3 inputs. In this case either CCW or the Logix software via a connection such as DSI or network communications will be used to communicate with the drive.

Page 14 of 64

Page 15: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

Exercise 3: Utilizing the file in drive and Connected Component Workbench offline with USB Cable. The Connected Components Workbench™ programming and configuration software supports the PowerFlex family of drives, the Micro800™ controllers, as well as the PanelView Component graphic terminals.

For this lab, you will be using Connected Components Workbench™, version 4, which supports the PowerFlex 525 drive. In this section you will perform the following: Import the drive xxxxxx.PF5 file from the drive to the Laptop.

Configure the Drive parameters using the Programming Groups. Export the xxxxxx.PF5 file from the Laptop back to the Drive.

Connecting to the Drive 1. Go to the computer’s desktop and double click the Connected Components Workbench shortcut. If the shortcut is not on

the desk top use the “All Programs” in the Start menu then select the Rockwell Automation folder, then the CCW folder and click on the CCW icon.

You will see the following splash screen while the software loads.

Note: May take a couple minutes for the Connected Components Workbench™ software to open.

Page 15 of 64

Page 16: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

`

The main screen for Connected Components Workbench is as follows.

Note: You may want to maximize the Connected Components Workbench software to make viewing easier.

2. Expand the Catalog box and select the “Drives” folder as shown above. Then select ”PF525 Drive” by double mouse clicking it.

3. After a few seconds the PF525 drive icon will appear in the “Project Organizer” Double mouse click on the drive icon and

the drive will appear in the main page as seen below. Click on each of the Push Pins for of the surrounding boxes to maximize the view.

Page 16 of 64

Page 17: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

4. Your view will look like this:

5. Click on the “Properties” button

6. Then select the “USB Import Export Tab”.

Page 17 of 64

Page 18: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

` 7. Click on the “Import” button

8. Select the PF525_Drive.PF5 file from the Network Expo Labs folder:

9. Click on “Import Entire Device”

10. Close the Properties Box

Page 18 of 64

Page 19: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

11. Click on the “Parameters” Button.

12. Click on the “All Parameters” button and Select “Baic Program”.

13. The Basic parameters are where the majority of the drive settings will be made.

Page 19 of 64

Page 20: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

` 14. Populate your page with the drive settings as listed below:

Note: if you want to view and or configure more drive parameters you can select the various programming groups.

15. Close the Parameters page 16. Click on the “Properties” button. You will now export the drive setting back to the PF525_Drive.PF5 file located in the

Network Expo Folder.

y

Page 20 of 64

Page 21: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

17. Then select the “USB Import/ Export Tab”.

18. Click on the “Export” button

19. Select the PF525_Drive.PF5 file from the Network Expo Labs folder then click on the “Save” button:

20. Confirm save by clicking on the “Yes” button

21. Close any remaining boxes then until you are left with this view then minimize but do not close the CCW sessesion we

have started. We will come back to CCW and go online with the drive later. If you did close it down make sure you save the file in a place you can find it again.

Page 21 of 64

Page 22: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

` 22. Open the Explorer Folder window and click on the “Removable Drive”. Then double mouse click on the PF52xUSB.exe file.

23. Take what you have learned earlier from the uploading procedure and by selecting “Download” move the PF525_Drive.PF5

back to the drive.

Note: Refer back to Execise 2. This will verify that you have understood the purpose of the PF525_Drive.PF5 file which is just a container used to get the drive information in and out of the drive when Main power is not applied to the drive. Remember you do not need to use this file if you plan to connect to the drive when it has power applied to it.

In the next exercise we will validate the drive parameters by connecting or going on line with the drive using the CCW Software.

24. Disconnect the USB cable from the drive.

25. Reconnect Control Module with the Power Module. Do Not Force the connection between the surfaces are properly mated they push together fairly easily. Please ask for assistance if you are having any trouble (that is our nice way of saying please don’t break drive) with the assembly.

26. With the drive properly assembled apply power to the drive.

27. Connect the Ethernet (E-Net) Patch cord to the Switch located on the PLC demo.

28. Verify the Laptop PC has its E-net Patch cord connected to the Switch on the PLC demo

29. Verify the PLC E-net Port is connected to the Switch on the PLC Demo.

Page 22 of 64

Page 23: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

Exercise 4: Utilizing an E-net connection and Connected Component Workbench online with the drive.

Connect to the PowerFlex 525 through the embedded Ethernet/IP via Connected Components Workbench

Explore the Startup wizard.

There are many features to Connected Components Workbench. You can set up a driver in RS Linx so that a 1203_USB cable can be used to connect to a PowerFlex drive or the LInx driver can be Ethernet I/P… If you can see the drive in RS Linx you connect to it with CCW. CCW and the PF525 Drive Add On Profile (AOP) in RS-Logix look and feel nearly the same. We will use the CCW software to go online with the PowerFlex 525. In the next exercise we will use the RS Logix software to finish commissioning.

1. The Connected Components Workbench was minimized in the last exercise and now it is time to bring it back into focus.

2. Click on the Task Bar to restore the view of CCW. If CCW has been accidentally shut down start it back up again. Then

proceed to Step 7. Do this only if you lost the Drive that was in your “Program Organizer” as seen below.

3. Double mouse click on the PF525 drive icon in the “Program Organizer” if the drive is not in the middle of the screen (see

Screen shot in step 4).

Page 23 of 64

Page 24: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

` 4. Select the Connect button and using the RS LInx Ethernet/IP driver that appears and find the PF525 Drive, Select it and

acknowledge the connection. ( See step 5)

5. The lab’s preconfigured RSLinx driver will appear. Click on the [+] to expand AB_ETHIP-1, Ethernet, click/highlight the

100.100.100.25, PowerFlex 525 1P 110V .50HP device.

6. Jump to Step 10) … Step 7 through 10 show how to do a direct connect to the drive when a parameter file has not yet been

created.

7. Click the [+] next to the Discover within the Device Toolbox.

8. Click the Browse Connections button to launch the RSWho connection browser.

Page 24 of 64

Page 25: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

9. The lab’s preconfigured RSLinx driver will appear. Click on the [+] to expand AB_ETHIP-1, Ethernet, click/highlight the 100.100.100.25, PowerFlex 525 1P 110V .50HP device.

10. Press the OK button to initiate the connection process. For a quick moment, you might see a connection status window.

Otherwise, once the connection process is complete, you will see the following main screen with a green highlighted “Connected” for the PowerFlex 525 within the Connected Components Workbench™ software.

Page 25 of 64

Page 26: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

`

Exploring Drive Parameters via Parameter Groupings, AppView™, and CustomView™

1. There are many features supported by Connected Components Workbench™ for the PowerFlex 525 as shown below.

Take some time to explore them.

2. Click on the Parameters icon to view the PowerFlex 525 drive parameters as seen below.

The PowerFlex 525 Drive Add-On Profile has a nice new feature from Connected Components Workbench™ software that will show the non-default parameters. This makes it easy for users to find out in a simple view what parameters were changed from their default setting. This button only updates the set of parameters shown based on the upload. If parameter “x” changes from defaults after clicking the button, it won't be added to the display until the view is refreshed.

3. Make sure All Parameters is selected within the Group dropdown selection box and then click the Show Non-Defaults button as shown below.

Page 26 of 64

Page 27: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

4. An upload progress window will pop up.

5. Once the upload has completed you will see the parameters window update to just show only the non-default parameters.

Take a look, you will notice that the parameters you changed in Lab 1 appear in this list. Example shown below.

6. Click the Show All button to return to viewing all of the PowerFlex 525 drive parameters.

7. To make viewing and editing parameters even simpler, you can enter a word or abbreviation into the filter value entry box. For example, type Motor into the Filter Value entry box. Notice that it filters and only shows the parameters that have the word motor in their parameter names.

Page 27 of 64

Page 28: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

` 8. Try some other examples such as Dig , Speed, 10 and see the results.

Note: Remember to clear/delete the entry field when finished.

9. Under the Group: dropdown selection box, you can scroll through the different drive parameter groups, AppView™ and the CustomView™.

10. Clear any values you may have in the Filter value Box and then Click on Basic Program and explore the parameters shown

below.

Page 28 of 64

Page 29: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

These are the most simplistic parameters that are needed to start up/commission a PowerFlex 525 drive. Take some time to explore some of the other parameter groupings such as Terminals, Communications and Advanced Program for more startup/commission parameters.

11. The PowerFlex 525 drive has several AppView™ groupings that are tailored for a specific application to make the respective drive startup/commission simpler. No more guessing what parameters you need to change, drive parameters for that application are all in one convenient location. For example, within the Group dropdown selection box, click on the Conveyor AppView™. Scroll through these application specific parameters, some are shown below.

12. The PowerFlex 525 drive has a CustomView™ which is an application set that can be customized specifically for your

application. You can add up to a max of 100 additional parameters and save the new “CustomView”. Select Custom Group from the Parameter Group dropdown selection box and click on the Edit Group button.

13. The Edit Custom Group window will appear. Here you will be able to select and add parameters into a nameable custom

group. In this example, type in ABC’s Group in the Group Name box highlighted by #4.

Page 29 of 64

Page 30: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

`

Note: You can also select/highlight multiple parameters then click the Add - > button. This makes adding parameters go a lot faster.

14. Add the following parameters:

Parameter 30 - Language

Parameter 43 - Minimum Freq Parameter 31 - Motor NP Volts

Parameter 44 - Maximum Freq

Parameter 32 - Motor NP Hertz

Parameter 45 - Stop Mode Parameter 33 - Motor OL Current

Parameter 46 - Start Source 1

Parameter 34 - Motor NP FLA

Parameter 47 - Speed Reference1 Parameter 35 - Motor NP Poles

Parameter 62 - DigIn TermBlk 02

Parameter 36 - Motor NP RPM

Parameter 63 - DigIn TermBlk 03 Parameter 37 - Motor NP Power

Parameter 64 - 2-Wire Mode

Parameter 39 - Torque Perf Mode

Parameter 65 - DigIn TermBlk 05 Parameter 40 - Autotune

Parameter 76 - Relay Out1 Sel

Parameter 41 - Accel Time 1

Parameter 81 - Relay Out2 Sel Parameter 42 - Decel Time 1

Once the parameters have been added Click OK to download this custom group to the drive.

Page 30 of 64

Page 31: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

15. Notice how the parameters entries from above are all now in the ABC’s Group CustomView for easy parameter viewing and editing.

Click [X] in the upper right hand corner to Close the Parameters – PowerFlex 525_1* window.

Page 31 of 64

Page 32: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

`

Exercise 4: PowerFlex 525 Start-Up Wizard

1. Click on the Wizards button and Select the PowerFlex 525 Startup Wizard and Click the Select button to launch the PowerFlex 525 Startup wizard.

2. Below is the Welcome screen for the PowerFlex 525 Startup Wizard. Click the Next > button to proceed with exploring the startup wizard.

Page 32 of 64

Page 33: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

3. Below is the Reset Parameters page. Here you have a couple different options.

• Reset all settings to factory defaults but retain the custom parameter group. • Reset all settings to factory defaults (including the custom parameter group). • Reset only the “Power Parameters”.

Click the Reset button for the first option, “Reset all settings to factory defaults but retain the custom parameter group”

Click Yes and once you see, , Click the Next > button to proceed to the next page.

4. Make sure English is selected in the Language dropdown selection box.

Click the Next > button to proceed to the next page.

Page 33 of 64

Page 34: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

` 5. Go through, verify and if needed, modify the parameters according to the following screenshots.

Remember to Click the Next > button to proceed to the next page.

6. If Connected to the drive, and the PLC is not in controll you may execute the Direction Test and if not, you can skip this by

Clicking the Next > button. If you realize you want to do this test just hit the back button.

Page 34 of 64

Page 35: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

Press Stop button to Clear Faults if the drive is faulted. PRESS and HOLD the Jog button to run the Direction Test.

If the following window pops-up, Click “Yes”.

If the direction is correct, Click on the Yes radio button and Click the Next > button.

Page 35 of 64

Page 36: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

`

7. If desired, you may skip the AutoTune Test by Clicking the Next > button.

8. Click on the StaticTune button to initiate the AutoTune Test. (see next page)

Note: This may take up to a minute to complete. Once finished, you will see the Test Completed: Yes result.

Note: This may take up to a minute to complete.

Click the Next > button.

9. Go through, verify and if needed, modify the parameters according to the following screenshots.

Remember to Click the Next > button to proceed to the next page

Page 36 of 64

Page 37: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

Page 37 of 64

Page 38: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

`

This can be any IP Adress of course…

Select how you want the Terminal Block inputs to behave.

Notice how The GUI shows you which terminals are configurable.

Page 38 of 64

Page 39: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

10. Once changes have been made, Go to the Pending Changes page for a summary of the planned programming changes

you have made to the PowerFlex 525 drive.

Page 39 of 64

Page 40: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

`

Make sure all the Pages have the black check to the left of the page name / icon.

Click the Finish >> button to accept pending changes.

11. The main PowerFlex 525 window will be present. Click the Reset button for the Ethernet communication settings to take affect.

Click OK. You will hear the PowerFlex 525 cycle power and the HIM Keypad display turn off and on and start scrolling the drive power ratings

12. This is a pretty quick process. You will see the following screen.

Click OK.

13. You will see the main PowerFlex 525 screen go from this…

to this once…the Connected Components Workbench™ software has re-established it’s connection with the drive.

14. Exit Connected Components Workbench software; we will not save any of the configuration files so the answer is no to

save. If you were working on your project of course you would say yes to save... “Just in case”

Page 40 of 64

Page 41: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

When prompted, Click No.

When prompted, Click No.

Page 41 of 64

Page 42: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

`

Exercise 5: PowerFlex 525 Drive Add-On Profile with RS Logix 5000 Software. This section will provide a preview of the PowerFlex 525 Drive Add-On Profile as well as the PowerFlex 525 Drives and Motion Accelerator Toolkit Add-On Instructions and Faceplates for the PowerFlex 525. About Integrated Drive Profiles and Premier Integration Integrated Drive Profiles were designed to save system development time and to make systems easier to maintain.

Integrated Drive Profiles in RSLogix 5000 / Studio 5000 Logix Designer can reduce drive system development time by as much as 70% (figure obtained from timed side-by-side drive configuration comparison testing) by:

• Providing one software tool to configure the entire Logix / drive system.

• Configuring both controller and drive network connections from a single location - eliminating I/O mismatch errors.

• Allowing the dynamic selection of drive parameters transmitted as network I/O – communicating only what is needed for the application.

• Auto-generating descriptive tag names - eliminating the need to enter individual tag descriptions.

• Auto-generating respective tag data types - eliminating the need to convert from one data type to another.

• Saving all drive configurations in the project file and in the Logix controller – providing a single source of drive configuration data.

• Providing Copy & Paste capability when creating additional duplicate drives – also duplicates the drive configuration settings so all the new drive needs is a different node address.

• Allowing use of the same easy-to-use drive configuration Wizards used in Connected Components Workbench™, DriveTools SP, and DriveExplorer.

Systems using the Integrated Drive Profiles in RSLogix 5000 / Studio 5000 Logix Designer are also easier to maintain:

• Drive diagnostic; fault, alarm and event information is integral to RSLogix 5000 / Studio 5000 Logix Designer.

• Drive Tech Support Wizard can be run from RSLogix 5000 / Studio 5000 Logix Designer to collect all pertinent information about a drive, its peripherals, various software components, and PC operating system.

• Drives can be flash updated from RSLogix 5000 / Studio 5000 Logix Designer.

Having a single repository of drive configuration data (in project file) speeds drive replacement.

Integrated Drive Profiles are "Add-On" Profiles, meaning new profiles can be introduced at any time (not tied to a specific RSLogix 5000 / Studio 5000 Logix Designer release) and are utilized by the software.

Page 42 of 64

Page 43: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

Using RS Logix 5000 Version 20.01 with the PowerFlex 525 Drive Add-On Profile

1. Start the program. Double-click the Studio 5000 icon on the desktop, or from the Start menu, select All Programs > Rockwell Software > RSLogix 5000 Enterprise Series> RSLogix 5000. After the splash Screen you will see something like this:

2. A pre-configured RS Logix 5000 program has already been created for your convenience. Depending on which Demo you have in front of you select one of the following: Select the either the L35ePF525_Lab.ACD or L43PF525_Lab.ACD file and Click Open.

Page 43 of 64

Page 44: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

`

*NOTE* Lab files are located within Libraries>Network Expo>L35ePF525_Lab or Libraries>Network Expo>L35ePF525_Lab folders depending on which demo you are using.

Note: May take a minute or two for the RS Logix 5000™ software to open.

3. Open the PowerFlex 525-EENET module properties by double-click on the PowerFlex 525-EENET node in the I/O Configuration folder to display the Module Properties screen.

Click on the Drive tab.

4. View the PowerFlex 525-EENET Drive tab.

For the PowerFlex 525 Add-On Profile, the Drive tab utilizes Connected Components Workbench™, so when compared to previous Drive Add-On profiles, the PowerFlex 525 has a new look and feel. However, the basic functionality is still the same when it comes to having the ability to upload, download, view and compare drive parameters as well as access the drive’s wizards. You can also setup Automatic Device Configuration (ADC) your respective PF525 drive.

Page 44 of 64

Page 45: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

5. Click on the Properties button. This opens the properties window and the Setup tab, which shows some basic drive information, such as configuration, revision, device language and electronic keying.

= Creates device database from online drive to add new revisions and configurations

= Reset device data to factory defaults

= Print

Page 45 of 64

Page 46: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

` 6. Click on the Communications tab to view the settings; you can manually configure the PowerFlex 525 drive Ethernet

network settings or obtain via BOOTP or DHCP.

7. The details page.

8. There is also Import / Export for the PF525 USB connection file format, .pf5. It can be used for saving/restoring

configurations. IT DOES NOT import *.dno / *.csf files from DriveExecutive / DriveExplorer.

9. Click on the [X] in the upper right hand corner to close the Properties window.

Page 46 of 64

Page 47: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

10. The Parameters icon launches the Parameters window. This is the same as what you performed in the previous section with using the Connected Components Workbench™ software to go online with the drive, view and modify parameters with the Parameter, AppView™ and CustomView™ groups

11. Click on the [X] in the upper right hand corner to close the Parameters window

12. Going back to the PowerFlex 525-EENET Module Properties screen, Click on the General tab.

The General tab is used to set the following drive’s name, ethernet address and module definition.

13. Click the Change… button to open the Module Definiton window. Within the Module Definition window, you can perform the following actions:

Page 47 of 64

Page 48: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

` a. Select the drive rating b. Set the firmware revision c. Set the Electronic Keying d. Configure the Input and Output Datalinks e. Create Database from the online drive or download from the web.

The PowerFlex 525 Add-On Profile provides the ability to configure Up to 4 words of Input Data and 4 words of Output Data can be defined for the embedded Ethernet connection. By default, drive status and control information will be communicated. The PowerFlex 525 allows datalinks to be configured to drive parameters. Status Information The “DriveStatus” word contains the drive status bit information, such as Ready, Fault, and At Reference.

The “OutputFreq” word contains the speed feedback information, which shows the actual operating frequency (Hz) of the drive. Control Information The “LogicCommand” word contains the drive command bit information, such as Stop, Start, Forward, Reverse, and Clear Faults.

The “FreqCommand” word contains the commanded reference value for the drive to run.

Datalinks Datalinks are pointers to drive and/or other port parameters. Instead of offering fixed I/O assemblies where what-you-see-is-what-you-get, our drive I/O assembly is dynamic and gives the programmer the ability to pick & choose the desired parameters to communicate as network I/O.

14. To configure the Input and Output datalinks, click the button to open the respective parameter selection list. Take some time to scroll through the available Input and Output Datalink parameter selections.

Page 48 of 64

Page 49: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

Click on the [X] in the upper right hand corner to Close the Module Definition window and then the Module Properties window.

15. If your application required multiple duplicate drives, you could right-click on the PowerFlex 525-EENET to copy it and then right-click on the Ethernet network and paste it as many times as needed. All node information is copied, including the drive parameter settings. All the user has to do is change the IP address, and give the drive a new name. Integrated Drive Profiles are not only easy-to-use; they also allow larger systems to be designed faster.

Page 49 of 64

Page 50: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

`

Where do you think the drive configuration data gets stored? The drive configuration data for each node is actually stored in your Studio 5000 project (the .ACD file)! It also resides in the ControlLogix when the .ACD is downloaded to the controller. This provides a convenient local resource for a node’s configuration settings should the node need replacing. Just connect to the controller, open the drive’s AOP and download the configuration!

16. Delete the copy of the drive profile. The drive you will delete on the E-Net tree is: PowerFlex 525-EENETPF525_Drive1

17. View the input tags on the drive that remains. Double-click on the Controller Tags under the Controller folder and expand the PF525_Drive:I inputs.

It may be necessary to drag the “Name” column right margin in the header to view the full input tag names.

Descriptive tag names have been created for the configured I/O. The Drive Status bits (BOOLs) are clearly defined as well as the Feedback and Input Datalink Output Current. Note that the proper data types are used for every tag.

Page 50 of 64

Page 51: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

18. View the output tags.

Now expand the PF525_Drive:O output to view the output tag names.

Descriptive tag names have been created for the configured I/O. The Logic Command bits (BOOLs) are clearly defined as well as the Reference. Note that the proper data types are used for every tag.

Close the Controller Tags window by clicking the lower [X] button in the upper-right corner of the screen.

19. Select the either the L35ePF525_Lab.ACD or L43PF525_Lab.ACD file and Click Open. You must open the folder which represents the demo in front of you to access the correct file. Ask for help if you need assistance.

*NOTE* Lab files are located within Libraries>Network Expo>L35ePF525_Lab or Libraries>Network Expo>L43ePF525_Lab folders depending on which demo you are using.

Page 51 of 64

Page 52: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

` 20. Open the PowerFlex 525-EENET module properties by Double-click on the PowerFlex 525-EENET node in the I/O

Configuration folder to display the Module Properties screen.

Your view will have the correct Processor indicated. Click on the Drive tab.

21. View the PowerFlex 525-EENET Drive tab.

22. Click the Download button and Expand the AB_ETHIP-1, Ethernet drive and Select the 100.100.100.25, PowerFlex 525 drive. (See next page)

Click OK.

23. Download the entire device

Page 52 of 64

Page 53: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

24. For a brief moment, you will see a downloading progress bar while the parameter settings are being sent to the drive. Your

IP address will be 100.100.100.25

25. Click back to the Connections Tab and Select the Inhibit Box by giving it a Check mark.

Note: By inhibiting the drive The PLC is prevented from having full ownership of the drive which will let us finish the commissioning process.

26. Click Apply and OK to close the Module Properties window.

27. Download the PF525_Lab project to the controller by clicking on Communications then Who Active.

Make sure the path to the CompactLogix controller at 100.100.100.35 via the AB_ETHIP-1 ethernet driver is selected and click Download.

28. Click Download again

Page 53 of 64

Page 54: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

`

v 29. Put the controller in Run mode.

If prompted to confirm Remote Run, click “Yes” 30. Click on the mode drop-down arrow and select Run Mode.

.

31. Open the PowerFlex 525-EENET module properties by Double-click on the PowerFlex 525-EENET node in the I/O Configuration folder to display the Module Properties screen.

Page 54 of 64

Page 55: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

Click on the Drive tab.

32. View the PowerFlex 525-EENET Drive tab. With the PLC on line you are now allowed to go on line with the drive and while the connection is being made you should see something like this.

33. If you see this Screen Shot below then select download Button.

Page 55 of 64

Page 56: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

`

Start the PowerFlex 525 Start-Up Wizard Again so we can use it to Bump the motor and Auto Tune.

34. Click on the Wizards button and Select the PowerFlex 525 Startup Wizard and Click the Select button to launch the PowerFlex 525 Startup wizard.

35. Below is the Welcome screen for the PowerFlex 525 Startup Wizard. Click the” Direction Test” button to proceed with

exploring the startup wizard

.

36. Enter a Safe Speed in Hertz for the Reference and the click on the Green Push Button

37.

Press Stop button to stop finish the Direction Test. If the rotation direction is not correct the drive can be powered down and any 2 motor leads can be swapped either at the drive or the motor.

Page 56 of 64

Page 57: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

Note: The direction of the rotor can be predicted in advance so long as the installer is aware of the lead terminations. The motor as you face the shaft will rotate clockwise (CW) when T1, T2, T3 on the drive is connected with Motor leads T1, T2, and T3. This is because the drive will produce a phase rotation of A,B,C. Again as you face the Motor Drive shaft it will spin CW when wired T1,T2, and T3… both on the drive and the Motor.

38. If the direction is correct, Click on the Yes radio button and Click the Next > button.

If the following window pops-up, Click “Yes” Button.

39. If desired, you may skip the AutoTune Test by Clicking the Next > button.

40. Click on the StaticTune button to initiate the AutoTune Test. (see next page)

Note: This may take up to a minute to complete. Once finished, you will see the Test Completed: Yes result.

41. Select Finish >> which will and accept any prompts to Close the Start up Wizard. Then select Apply button.

Page 57 of 64

Page 58: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

` 42. Click on the connection Tab and remove the inhibit or uncheck the box. Click on the Apply button.

43. Then Click on the OK Button. Verify you are still on line with the processor and that you are in Run.

44. Use the PF525 routine to test the drive performance. The external I/O Push Buttons are wired to the PLC so they will respond to Start > Stop Commands

45. Change the speed reference which may appear with a value of 0 or something like12.45 hertz in this screen shot.

See rung 0

Page 58 of 64

Page 59: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

46. Have some fun while monitoring the drive status.

47. You have now completed the PF525 Commisioning lab.

Exta Credit:: If you have time and want to learn about ADC or Automatic Device Configuration. See next Section

Page 59 of 64

Page 60: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

`

Exercise 6: Automatic Device Configuration (ADC) with the PowerFlex 525 AC drive About Automatic Device Configuration (ADC) Automatic Device Configuration (ADC) is an RSLogix 5000 (version 20) and Logix Designer (version 21 or greater) feature that supports the automatic download of configuration data upon the Logix controller establishing an EtherNet/IP network connection to a PowerFlex 525 drive and its associated peripherals.

IMPORTANT: ADC is NOT available for DSI peripherals.

ADC is NOT available in Multi-drive mode.

ADC is only available when the drive is connected using the embedded EtherNet/IP adapter or future EtherNet/IP DLR adapter to a compatible controller.

An RSLogix 5000 (version 20) or Logix Designer (version 21 or greater) project (.ACD file) contains the configuration settings for any PowerFlex drives in the project. When the project is downloaded to the Logix controller, these settings are also transferred and reside in the controller’s memory. Prior to ADC in RSLogix 5000 (version 20) or Logix Designer (version 21 or greater), downloading PowerFlex 525 configuration data was a manual process where the user would open the Drive tab in the respective drive Add-On Profile (AOP) in the application and click on the Download icon. ADC now automates the process and saves the user time. It is particularly beneficial in a drive replacement situation when a production line is down.

NOTE: At this point in time, Automatic Device Configuration (ADC) is only available for the following PowerFlex drives:

PowerFlex 525 via Embedded Ethernet (EENET) and Dual Port Ethernet (E2P)

PowerFlex 755 (Version 4.001) via Embedded Ethernet (EENET) and Dual Port Ethernet (ENETR)

PowerFlex 753 (version 7.001) via Dual Port Ethernet (ENETR)

ADC can also work in tandem with Firmware Supervisor. If Firmware Supervisor is set up and enabled for a drive (“Exact Match” keying must be used), and if the respective ControlFLASH firmware kit is installed on the computer, the drive/peripheral will be automatically flashed (if necessary) prior to any ADC operation.

IMPORTANT: Logix owns the configuration of the drive. ADC will be triggered any time the Logix controller detects a configuration signature mismatch when establishing an EtherNet/IP network I/O connection.

The use of other configuration tools, such as a HIM or Connected Components Workbench software should be minimized and restricted to monitor-only operation. Any configuration changes made by these tools will cause a configuration signature mismatch the next time the Logix controller connects to the device and ADC will write over any changes made by the other tool(s). Any drive configuration changes should be made with the drive Add-On Profile.

For more information in regards to the PowerFlex 525 and Automatic Device Configuration (ADC), refer to the PowerFlex 525 Embedded EtherNet/IP Adapter User Manual.

Page 60 of 64

Page 61: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

Exploring the setup of Automatic Device Configuration (ADC) 1. Open the PowerFlex 525-EENET module properties by Double-click on the PowerFlex 525-EENET node in the I/O

Configuration folder to display the Module Properties screen.

2. Click on the Drive tab.

The drive AOP requires user action to enable ADC. This helps ensure that the user understands ADC operation prior to turning it on. The drive AOPs also have an ADC icon on the Drive tab that shows if ADC is enabled (green arrow) or disabled (gray arrow) for the respective drive.

3. Click on the ADC button.

This will open the Automatic Device Configuration setup window.

4. The picture below shows how you would enable or disable Automatic Device Configuration (ADC) for the PowerFlex 525 drive and it’s peripherals (if applicable). Click

IMPORTANT: In order for setting changes to take effect, you must Click Apply and then the [X] to close.

Page 61 of 64

Page 62: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

`

5. Click the OK button to Close the PowerFlex 525 Module Properties. 6. Download the PF525_Lab project to the controller by clicking on Communications then Who Active.

Make sure the path to the CompactLogix controller at 100.100.100.35 via the AB_ETHIP-1 ethernet driver is selected and click Download.

7. Click Download again

8. Put the controller in Run mode.

9. Click on the mode drop-down arrow and select Run Mode. This is done with a Click on the mode drop-down arrow and select Run Mode.

10. If prompted to confirm Remote Run, Click Yes.

Page 62 of 64

Page 63: PowerFlex 525 Commissioning Lab - Kendall Electric...The PowerFlex 525 is easy to configure with flexibility in programming options to meet your application. One of which is the Liquid

11. Automatic Device Configuration (ADC) will cause the transition to run to be longer. Click the OK button to confirm / acknowledge the following window.

NOTE: ADC will cause the tranistion to run to be longer

12. Notice that the PowerFlex 525 drive will get a F048 – Parameters Defaulted fault on the LCD Keypad display. This is normal and the first step of the Automatic Device Configuration process. The drive is now being configured.

13. Go back to the I/O Configuration tree; you will notice a Yellow triangle next to the PowerFlex 525 drive (PF525_Drive).

Click once on the drive to highlight/select it. You will notice that the drive’s connection status is in a “Configuring” state.

NOTE: It will take about one (1) minute for the PowerFlex 525 drive to be configured.

14. Once the ADC process has completed, the drive’s connection status will go from “Configuring” to “Running”

ADC will automatically reset (power cycle) the drive as part of the configuration process. This is done because some parameters require a reset before they take effect. If a drive is being replaced with an out-of-the-box drive, you will typically see one or more resets during the ADC process.

You have completed the Drive Programming with the PowerFlex® 525 AC Drives Lab.

Page 63 of 64