![Page 1: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/1.jpg)
Power System Protection
Dr. Ibrahim El-Amin
![Page 2: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/2.jpg)
Protective Device Coordination
![Page 3: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/3.jpg)
Definition
� Overcurrent Coordination
� A systematic study of current responsive devices
in an electrical power system.
![Page 4: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/4.jpg)
Objective
� To determine the ratings and settings of
fuses, breakers, relay, etc.
� To isolate the fault or overloads.
![Page 5: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/5.jpg)
Criteria
� Economics
� Available Measures of Fault
� Operating Practices
� Previous Experience
![Page 6: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/6.jpg)
Design
� Open only PD upstream of the fault or overload
� Provide satisfactory protection for overloads
� Interrupt SC as rapidly (instantaneously) as
possible
� Comply with all applicable standards and codes
� Plot the Time Current Characteristics of
different PDs
![Page 7: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/7.jpg)
Analysis
When:
� New electrical systems
� Plant electrical system expansion/retrofits
� Coordination failure in an existing plant
![Page 8: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/8.jpg)
Protection vs. Coordination
� Coordination is not an exact science
� Compromise between protection and
coordination
� Reliability
� Speed
� Performance
� Economics
� Simplicity
![Page 9: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/9.jpg)
Protection
� Prevent injury to personnel
� Minimize damage to components
� Quickly isolate the affected portion of the system
� Minimize the magnitude of available short-circuit
![Page 10: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/10.jpg)
Spectrum Of Currents
� Load Current
� Up to 100% of full-load
� 115-125% (mild overload)
� Overcurrent
� Abnormal loading condition (Locked-Rotor)
� Fault Current
� Fault condition
� Ten times the full-load current and higher
![Page 11: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/11.jpg)
Coordination
� Limit the extend and duration of service
interruption
� Selective fault isolation
� Provide alternate circuits
![Page 12: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/12.jpg)
Coordination
t
I
C B A
C
D
D B
A
![Page 13: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/13.jpg)
Equipment
� Motor
� Transformer
� Generator
� Cable
� Busway
![Page 14: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/14.jpg)
Capability / Damage Curves
t
I
I22t
Gen
I2t
MotorXfmr
I2t
Cable
I2t
![Page 15: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/15.jpg)
Transformer CategoryANSI/IEEE C-57.109
Minimum nameplate (kVA)
Category Single-phase Three-phase
I 5-500 15-500
II 501-1667 501-5000
III 1668-10,000 5001-30,000
IV above 1000 above 30,000
![Page 16: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/16.jpg)
Infrequent Fault Incidence Zones for Category II & III Transformers
* Should be selected by reference to the frequent-fault-incidence protection curve or for
transformers serving industrial, commercial and institutional power systems with secondary-side
conductors enclosed in conduit, bus duct, etc., the feeder protective device may be selected by
reference to the infrequent-fault-incidence protection curve.
Source: IEEE C57
Source
Transformer primary-side protective device
(fuses, relayed circuit breakers, etc.) may be
selected by reference to the infrequent-fault-
incidence protection curve
Category II or III Transformer
Fault will be cleared by transformer
primary-side protective device
Optional main secondary –side protective device.
May be selected by reference to the infrequent-fault-
incidence protection curve
Feeder protective device
Fault will be cleared by transformer primary-side
protective device or by optional main secondary-
side protection device
Fault will be cleared by
feeder protective device
Infrequent-Fault
Incidence Zone*
Feeders
Frequent-Fault
Incidence Zone*
![Page 17: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/17.jpg)
Transformer
t
(sec)
I (pu)
Thermal200
2.5
I2t = 1250
2
25Isc
Mechanical
K=(1/Z)2t
(D-D LL) 0.87
(D-R LG) 0.58
Frequent Fault
Infrequent Fault
Inrush
FLA
![Page 18: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/18.jpg)
![Page 19: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/19.jpg)
Transformer Protection
MAXIMUM RATING OR SETTING FOR OVERCURRENT DEVICE
PRIMARY SECONDARY
Over 600 Volts Over 600 Volts 600 Volts or Below
Transformer
Rated
Impedance
Circuit
Breaker
Setting
Fuse
Rating
Circuit
Breaker
Setting
Fuse
Rating
Circuit Breaker
Setting or Fuse
Rating
Not more than
6%
600 %
300 %
300 %
250%
125%
(250% supervised)
More than 6%
and not more
than 10%
400 %
300 %
250%
225%
125%
(250% supervised)
Table 450-3(a) source: NEC
![Page 20: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/20.jpg)
Protective Devices
� Fuse
� Relay (50/51 P, N, G, SG, 51V, 67, 46, 79, 21, ?)
� Thermal Magnetic
� Low Voltage Solid State Trip
� Electro-Mechanical
� MCP
� Overload Heater
![Page 21: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/21.jpg)
Fuse
� Non Adjustable Device
� Continuous and Interrupting Rating
� Voltage Levels
� Characteristic Curves
� Min. Melting
� Total Clearing
� Application
![Page 22: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/22.jpg)
Minimum Melting
Time Curve
Total Clearing
Time Curve
![Page 23: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/23.jpg)
Current Limiting Fuse(CLF)
� Limits the peak current of short-circuit
� Reduces magnetic stresses (mechanical
damage)
� Reduces thermal energy
![Page 24: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/24.jpg)
![Page 25: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/25.jpg)
Symmetrical RMS Amperes
Peak L
et-
Th
rou
gh
Am
pere
s
100 A
60 A
15% PF (X/R = 6.6)
12,500
5,200
230,000
300 A
100,000
Let-Through Chart
![Page 26: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/26.jpg)
Fuse
Generally:
� CLF is a better short-circuit protection
� Non-CLF (expulsion fuse) is a better Overload
protection
![Page 27: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/27.jpg)
Selectivity Criteria
Typically:
� Non-CLF: 140% of full load
� CLF: 150% of full load
![Page 28: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/28.jpg)
Molder Case CB
� Thermal-Magnetic
� Magnetic Only
� Integrally Fused
� Current Limiting
� High Interrupting
Capacity
Types
� Frame Size
� Trip Rating
� Interrupting Capability
� Voltage
![Page 29: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/29.jpg)
Thermal Minimum
Thermal Maximum
Magnetic
(instantaneous)
![Page 30: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/30.jpg)
LVPCB
� Voltage and Frequency Ratings
� Continuous Current / Frame Size
� Override (12 times cont. current)
� Interrupting Rating
� Short-Time Rating (30 cycle)
� Fairly Simple to Coordinate
![Page 31: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/31.jpg)
480 kV
CB 2
CB 1
CB 2CB 1
IT
ST PU
ST Band
LT PU
LT Band
If=30 kA
![Page 32: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/32.jpg)
Motor Protection
� Motor Starting Curve
� Thermal Protection
� Locked Rotor Protection
� Fault Protection
![Page 33: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/33.jpg)
Motor Overload Protection (NEC Art 430-32)
� Thermal O/L (Device 49)
� Motors with SF not less than 1.15
� 125% of FLA
� Motors with temp. rise not over 40
� 125% of FLA
� All other motors
� 115% of FLA
![Page 34: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/34.jpg)
Locked Rotor Protection
� Thermal Locked Rotor (Device 51)
� Starting Time (TS < TLR)
� LRA
� LRA sym
� LRA asym (1.5-1.6 x LRA sym) + 10% margin
![Page 35: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/35.jpg)
Fault Protection (NEC Art 430-52)
� Non-Time Delay Fuses� 300% of FLA
� Dual Element (Time-Delay Fuses)� 175% of FLA
� Instantaneous Trip Breaker� 800% of FLA*
� Inverse Time Breakers� 250% of FLA
*MCPs can be set higher
![Page 36: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/36.jpg)
200 HP
MCP
O/L
Starting Curve
I2T
(49)
MCP (50)
(51)ts
tLR
LRAs LRAasym
![Page 37: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/37.jpg)
Overcurrent Relay
� Time-Delay (51 – I>)
� Short-Time Instantaneous ( I>>)
� Instantaneous (50 – I>>>)
� Electromagnetic (induction Disc)
� Solid State (Multi Function / Multi Level)
� Application
![Page 38: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/38.jpg)
![Page 39: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/39.jpg)
Time-Overcurrent Unit
� Ampere Tap Calculation
� Ampere Pickup (P.U.) = CT Ratio x A.T. Setting
� Relay Current (IR) = Actual Line Current (IL) / CT
Ratio
� Multiples of A.T. = IR/A.T. Setting
= IL/(CT Ratio x A.T. Setting)IL
IR
CT
51
![Page 40: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/40.jpg)
Instantaneous Unit
� Instantaneous Calculation
� Ampere Pickup (P.U.) = CT Ratio x IT Setting
� Relay Current (IR) = Actual Line Current (IL) / CT
Ratio
� Multiples of IT= IR/IT Setting
= IL/(CT Ratio x IT Setting)IL
IR
CT
50
![Page 41: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/41.jpg)
41
Relay Coordination
� Time margins should be maintained between T/C curves
� Adjustment should be made for CB opening time
� Shorter time intervals may be used for solid state relays
� Upstream relay should have the same inverse T/C characteristic as the downstream relay (CO-8 to CO-8) or be less inverse (CO-8 upstream to CO-6 downstream)
� Extremely inverse relays coordinates very well with CLFs
![Page 42: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/42.jpg)
Fixed Points
� Motor starting curves
� Transformer damage curves & inrush
points
� Cable damage curves
� SC maximum fault points
� Cable ampacities
Points or curves which do not change
regardless of protective device settings:
![Page 43: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/43.jpg)
Situation
Calculate Relay Setting (Tap, Inst. Tap & Time Dial)
For This System
4.16 kV
DS 5 MVA
Cable
1-3/C 500 kcmilCU - EPR
CB
Isc = 30,000 A
6 %
50/51 Relay: IFC 53CT 800:5
![Page 44: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/44.jpg)
Solution
AInrsuh
328,869412I =×=
A338.4800
5II LR =×=
Transformer: AkV
kVA
L694
16.43
000,5I =
×
=
IL
CTR
IR
Set Relay:
A 55 1.52800
5328,8)50(
1
)38.1(6/4.338 0.6
4.5338.4%125
=>=×=
=
=
=×
=
AInst
TD
ATAP
A
![Page 45: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/45.jpg)
Question
What is ANSI Shift Curve?
![Page 46: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/46.jpg)
Answer
� For delta-delta connected transformers, with
line-to-line faults on the secondary side, the
curve must be reduced to 87% (shift to the left
by a factor of 0.87)
� For delta-wye connection, with single line-to-
ground faults on the secondary side, the curve
values must be reduced to 58% (shift to the left
by a factor of 0.58)
![Page 47: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/47.jpg)
Question
What is meant by Frequent and
Infrequent for transformers?
![Page 48: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/48.jpg)
AnswerInfrequent Fault Incidence Zones for Category II & III Transformers
Source
Transformer primary-side protective device
(fuses, relayed circuit breakers, etc.) May be selected by reference to the infrequent-fault-
incidence protection curve
Category II or III Transformer
Fault will be cleared by transformer
primary-side protective device
Optional main secondary –side protective device.
May be selected by reference to the infrequent-fault-
incidence protection curve
Feeder protective device
Fault will be cleared by transformer primary-side
protective device or by optional main secondary-
side protection device
Fault will be cleared by
feeder protective device
Infrequent-Fault
Incidence Zone*
Feeders
Frequent-Fault
Incidence Zone*
![Page 49: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/49.jpg)
Question
What T/C Coordination interval should be
maintained between relays?
![Page 50: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/50.jpg)
Answer
At
I
B
CB Opening Time
+
Induction Disc Overtravel (0.1 sec)
+
Safety margin (0.2 sec w/o Inst. & 0.1 sec w/ Inst.)
![Page 51: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/51.jpg)
Question
What is Class 10 and Class 20
Thermal OLR curves?
![Page 52: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/52.jpg)
Answer
� Class 10 for fast trip, 10 seconds or less
� Class 20 for, 20 seconds or less
� There is also a Class 30 for long trip time
![Page 53: Power System Protection - libvolume3.xyzlibvolume3.xyz/electrical/btech/semester6/switchgearprotection/... · Power System Protection Dr. Ibrahim El-Amin. Protective Device Coordination.](https://reader030.fdocuments.us/reader030/viewer/2022040116/5ec6773fe690c36f2e144a11/html5/thumbnails/53.jpg)
Answer