    Power system Protection

    Visited Grid stations1) 500 KV Sheik Muhammadi Grid Station.2) 220 KV Grid Station near khazana Sugar Mill .

    Group members

    Zahid ur RehmanShaiq Ali.Najib Ullah Afridi.Shabir Asghar.

    Dept: of Electrical Power Engineering UET Peshawar.

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    2/23

    23/05/2012. power system protection 2

    Why protection system is Necessary .

    Impossible and uneconomical to build faultfree Power system.

    Small disturbances handled by controlsystem.Severe disturbance can jeopardize P.S

    Needs a separate protection for handlingthese faults.

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    3/23

    23/05/2012. power system protection 3

    Protection system basic

    goal.Detection & disconnection of faulty section.

    Reasons:-Unnecessary interruption to consumers.

    Prevention of Spreading of fault. Assures System stability .

    Consumer devices are not made to carry faultcurrent for longer period of time.

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    4/23

    23/05/2012. power system protection 4

    Schemes of Protection.1) Generators.2) Low tension Switch gear.3) Transformer.4) High tension Switch gear.5) Transmission lines.

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    5/23

    23/05/2012. power system protection 5

    General Introduction.500kv S/C 4 bundled conductor Line fromtarbela.

    Two auto transformer 500/220kv each rated450MVA .220KV line from Ghazi Brotha.

    220kv/132kv khazana grid.

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    6/23

    23/05/2012. power system protection 6

    Essential Elements.Power Line Carrier Traps.Mainly used for telecomm: , teleprotection & telemonitoring.Frequency Range: 272kHz-700kHz.

    CCVT:Step down the EHV signals for measurmentand protection.

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    7/23

    23/05/2012. power system protection 7

    Continue

    Surge arresters:To protect against the lightning andswitching strokes.

    Always on the live wireBased on metal oxide varistor.Eearthing of switchyard.Increased safety.

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    8/23

    23/05/2012. power system protection 8

    Continue

    Isolating switches:Used for de-energizing of the lines formaintenance.Earth switches.Circuit Breakers:

    Used for the disconnection of the faultyelement from the PS.SF6 is used as a quenching media.

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    9/23

    23/05/2012. power system protection 9

    Continue.

    INSULATORS:Porcelain and glass insulators are used.The dielectric strength is as follow;Porcelain:11.5kv/disc.Glass:110kv/disc.

    One and half breaker scheme .To increase reliability.

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    10/23

    23/05/2012. power system protection 10

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    11/23

    23/05/2012. power system protection 11

    Components of Protection.

    Fuses.C.Ts & P.Ts

    Circuit breaker.Relays.

    Auto reclosers.

    Spark gap and surge arrester.Isolaters and earth switches.FACTS , SVC, TPSC,SCCL..

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    12/23

    23/05/2012. power system protection 12

    Transmission lines ProtectionDistance Protection.Total length 117 km.Primary protection ( static distancerelays).L-G, L-L , L-L-L-G faults .

    Back up protection (Electromechanicaldistance relays).Grid faults or system fault indications.

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    13/23

    23/05/2012. power system protection 13

    Transmission lines ProtectionCarrier current protection.Carrier added protection.Pilot protection.Optical fibre / shielding line protection.

    O.C relay coupled with distance relay .

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    14/23

    23/05/2012. power system protection 14

    Transmission line zonesZone 1: 85% of total length.Zone 2: 50 % of total length.Zone 3: 25 % of total length.Zone 4: 15 % of total length.

    No pet rule for zoning .Zoning based on importance of TX-line.

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    15/23

    23/05/2012. power system protection 15

    Bus Bar protection.High impedance differential relay.

    Voltage based protection.No C.T on busbars.Dangreous protection scheme.

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    16/23

    23/05/2012. power system protection 16

    Transformer Protection.

    Over current protection.Differential Relay.Earth fault relay.Restricted Earth fault.

    Tertiary O.C protection.Over flux protection.

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    17/23

    23/05/2012. power system protection 17

    Transformer Protection.

    Bucholz protection.Current inrush protection.T/F fire protection.Nitrogen used mostly.

    Thermal protection.Temp > 95C initiates alarm signal.Temp> 110C trips.

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    18/23

    23/05/2012. power system protection 18

    Transformer Testing

    Megger Testing.DGA of T/F oil.

    Vacum dehydration.TTR Testing.

    Capacitance & dissipation factor testing.

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    19/23

    23/05/2012. power system protection 19

    Transformer Testing

    Bushing tests.DC- winding resistance test.Polarity tests.Earth resistance test.

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    20/23

    23/05/2012. power system protection 20

    Miscellaneous protection.

    Frequency metering & Triping.

    Frequency less than 48.80HZ.132kv line is tripped.

    Frequency less than 48.60HZ.220kv lines may b tripped.

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    21/23

    23/05/2012. power system protection 21

    Miscellaneous protection.

    Check synchronizing relay.Maximum voltage difference on L.T side of transfomer may be 20kv.Phase difference is 30.Ensure above feature before closing of

    breaker.

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    22/23

    23/05/2012. power system protection 22

    Miscellaneous protection.

    Over voltage .Under voltage.Power swing blocking relay.Over load protection.

    Interface relay for PLC.

  • 7/31/2019 Power System Protection Basics..a Visit to Sheik Muhammadi Grid Peshawar.

    23/23

    23/05/2012. power system protection 23

    End..