Power - System - Einstein Notes
Transcript of Power - System - Einstein Notes
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 1/201
1
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 2/201
Introduction
Structure of Electric Power system
Variable load on power stations
Load curves
Load Characteristics
Load duration curves
Load curves and selection of generating units
2
OUTLINEwww.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 3/201
The power demands of different
consumers vary in accordance with their
activities.
The result of this variation in demand is
that load on a power station is never
constant rather it varies from time to time
3
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 4/201
4
220kV/11kV
Transmission
sub-station
11Kv/400vDistribution
substation
Transmission Line
Individual consumers
Distributor
11kV/220kV
Transformer
Alternators
Power station
STRUCTURE OF ELECTRIC POWER
SYSTEM
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 5/201
Domestic load
Commercial Load
Industrial LoadMunicipal Load
Irrigation load
Traction load
5
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 6/201
Definition:
The Load on a power station varies from time to time
due to uncertain demands of the consumers
Effects of Variable load:
Need of additional equipment
Increase in production cost
6
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 7/2017
Definition:
The curve showing the variation of load
on the power station with respect to time
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 8/201
Daily load curve – Load variations during the whole
day
Monthly load curve – Load curve obtained from the
daily load curve
Yearly load curve - Load curve obtained from the
monthly load curve
8
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 9/201
BASE LOAD:
The unvarying load which occurs almost
the whole day on the stationPEAK LOAD:
The various peak demands of load of the
station
9
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 10/20110
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 11/201
Connected load
Maximum demand
Average load
Load factor Diversity factor
Plant capacity factor
Plant use factor
11
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 12/201
It is the sum of continuous ratings of allthe equipment connected to supply
system
12
MAXIMUM DEMAND
It is the greatest demand of load on the
power station during a given period.
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 13/201
It is the ratio of maximum demand on the
power station to its connected load.
13
load connected
demand imum factor Demand
max
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 14/201
The average of loads occurring on the power station in
a given period (day or month or year)
14
hoursdayain generated KWhunitsof Noload average Daily
24)(.
monthainhoursof Number
monthain generated KWhunitsof Noload average Monthly
)(.
hours
year ain generated KWhunitsof Noload averageYearly
8760
)(.
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 15/201
The ratio of average load to the maximum demand
during a given period .
15
demand Maximum
load Average
factor Load
If the plant is in operation for T hours,
T demand Maximum
T load Average
factor Load
T demand Max
hoursT in generated Units
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 16/201
The ratio of the sum of individual
maximum demands to the maximum
demand on power station .
16
station power ondemand Max
demandsindividual of Sum factor Diversity
.
.max
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 17/201
It is the ratio of actual energy produced tothe maximum possible energy that could
nave been produced during a given period.
17
produced beenhavecould that energy Max
odcued energy Actual
factor capacity Plant .
Pr
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 18/201
It is the ratio of kWh generated to the
product of plant capacity and the number
of hours for which the plant was inoperation
18
useof Hourscapacity Plant kWhinoutput Station factor use Plant
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 19/201
When the elements of a load curve are arranged inthe order of descending magnitudes .
Load curve Load duration curve
19
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 20/201
The load duration curve gives the data in
a more presentable form
The area under the load duration curve is
equal to that of the corresponding load
curve The load duration curve can be extended to include any
period of time
20
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 21/201
The number and size of the units are
selected in such a way that they correctly
fit the station load curve.
21
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 22/201
Major Components
Generators
Transmission Network
Distribution System
Interconnection of the elements
Interconnection of neighboring utilities
22
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 23/201
23
System load varies continuously with time Significant changes from hour to hour, day to day, month
to month and year to year
Typical load curve
Load
Hour
www.Vidyarthiplus.com
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 24/201
Estimating power demand at the various load buses
ahead of time
Required for planning and operational applications.
Make a statistical analysis of previous load data
and set up a suitable model of the demand pattern.
Utilize the identified load model for making a
prediction of the estimated demand for theselected load time.
Forecasting interval – Few seconds to few years.
24
www.Vidyarthiplus.com
www.VIdyarthiplus.com
Vid hi l
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 25/201
25
www.Vidyarthiplus.com
www.VIdyarthiplus.com
Vid thi l
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 26/201
All the load demands are met
Constant frequency
Bus Voltage magnitude within limits
No elements are overloaded
26
www.Vidyarthiplus.com
www.VIdyarthiplus.com
Vid thi l
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 27/201
A.C. motors run at speeds that are directly
related to the frequency.
Generator turbines are designed to operate
at a very precise speed
Better control of overall operation of a
power system
Electrical clocks driven by synchronous
motor
27
www.Vidyarthiplus.com
www.VIdyarthiplus.com
Vid thi l
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 28/201
System Generators meet the load and the real transmission loss.
Energy cannot be stored in electrical form Electrical Energy
production rate must be equal to consumption rate at eachmoment.
Power imbalance would enter into or exit from kinetic energy
storage.
As the K.E depends upon generator speed, power imbalance will
be translated to change in speed ( and frequency).
28
www.Vidyarthiplus.com
www.VIdyarthiplus.com
www Vidyarthiplus com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 29/201
All equipment in a power system is
designed for a certain voltage level.
If the system voltage deviates, the
performance of the device suffers and its
life expectancy drops.
The voltage level of a bus is strongly relatedto the reactive power injection at the bus.
29
www.Vidyarthiplus.com
www.VIdyarthiplus.com
www Vidyarthiplus com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 30/201
Excitation control of generators
Switched Shunt Capacitors and/or reactors
Synchronous Condensers
Tap-Changing of Transformers
30
www.Vidyarthiplus.com
www.VIdyarthiplus.com
www Vidyarthiplus com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 31/201
Change in MW output of a generator does not
result in appreciable change in |V|
Change in Q input at a bus may affect the real
load of the bus in question
31
www.Vidyarthiplus.com
www.VIdyarthiplus.com
www Vidyarthiplus com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 32/201
Cost of real power generation
Allocation of real power at generator buses
Optimum allocation of units – unit
commitment
Optimum allocation of generation to each
station – Economic Dispatch
32
www.Vidyarthiplus.com
www.VIdyarthiplus.com
www Vidyarthiplus com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 33/201
Determine the economic distribution of loadbetween the various units.
Fuel Cost is the principal factor in fossil-fuel
plants Express the variable operating costs of the
unit in terms of the power output.
Constraints: i) Real power balance
ii) Generator limits.
hr Rsc P b P a F i gii giii /2
N
iiT F F onCostFuncti 1
33
www.Vidyarthiplus.com
www.VIdyarthiplus.com
www Vidyarthiplus com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 34/201
Lagrange Multiplier method Lamda iteration method
Gradient method
Dynamic programming Evolutionary Computation techniques
34
www.Vidyarthiplus.com
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 35/201
Load varies continuously with time The daily load pattern exhibit large
differences between minimum and maximumdemands.
It is not proper and economical to run all theunits at all the time.
Determine the units of a plant that shouldoperate for a given load- Unit commitment
problem.
35
www.Vidyarthiplus.com
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 36/201
Solution methods:Priority Listing
Dynamic Programming
Lagrange Relaxation method
Genetic Algorithm
36
www.Vidyarthiplus.com
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 37/201
Controls to meet the fundamental requirement of “Normal” state.
37
y p
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 38/201
Controllers on individual system elements
Prime mover controls
Excitation controls
System – generation control
Transmission Controls: Power and voltage
control devices
38
y p
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 39/201
Regulates the MW output and frequency(speed) of the generator.
Primary loop regulates the steam/hydroflow rate via the speed governor and the
control valves to maintain power balance. Secondary ALFC loop works in a slow reset
mode to eliminate the remaining smallfrequency errors.
Secondary loop also controls the powerinterchange between pool members.
39
y p
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 40/201
The primary loop response will be over inseconds, whereas the secondary fineadjustment take about one minute.
In the case of interconnected systems,the
secondary ALFC loop also contain the errorsin the contracted tie-line powers.
40
y p
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 41/201
Maintains reactive power balance of agenerator by maintaining a constant voltagelevel.
Measure the bus voltage, after rectification
and filtering the output is compared with areference. The resulting error voltage after amplification
serve as input to an excitation control
system.
41www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 42/201
Increased Complexity in system control.
Real – time monitoring and control of electricnetwork
42www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 43/201
Obtain the best possible values of the busvoltage magnitudes and angles by processingthe network data.
Modification to account for the presence of
noise. Use the method of least-squared error
estimation.
43www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 44/201
A power system under normal operatingconditions may face a contingencycondition.
Contingencies may result in overloading of some of the power system components andmay result in total or partial blockout.
Analyse the effect of propable
contingencies. Security- Ability of a power system to face
the contingencies without any consequenteffects.
44www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 45/201
Olle L.Elgerd, Electric Energy SystemsTheory, Second Edition, TMH Publications.
B.M.Weedy and B.J.Cory, Electric PowerSystems, Fourth Edition, WSE Publications.
Kundur, Power system stability andcontrol,TMH Publications.
P.S.R.Murthy, Power system operation and
control, Charulatha Publications.
45www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 46/201
46www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 47/201
• Basic Role of AGC: Maintain desired megawatt output of generator.
To assist in frequency control of largeinterconnection.
To keep net interchange of power between poolmembers at pre-determined values
47www.VIdyarthiplus.com
Complete Block Diagramwww.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 48/201
48
Complete Block Diagram
of Single Area System
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 49/201
Generator synchronized to a network of very large size i.e. frequency is independentof power output of individual generator
(individual network).
Direct proportionality between referencesetting and turbine power.
0,0,0 ref T P P f
49www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 50/201
Generator synchronized to a finite sizenetwork. Reference power setting isunchanged.
For a constant speed changer settingsstatic increase in turbine power is
directly proportional to droop in staticfrequency drop.
00,1 f R
P T
50www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 51/201
From the block diagram of the AGC loop,
If ∆Pref = 0;
If there is a step load change of constant magnitude “M”,
The steady state change in frequency due to load change is,
β -Area frequency response characteristics (AFRC).
f G P GG f R
P p DT H ref
1
)(11)0( s P GGG R
G
f DT H P
p
51
s
M s P D )(
M
R D
M s f s f
s
1
)(lim0
0
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 52/201
The dynamic response of the loop will informabout “tracking” ability and stability of theloop.
Assumptions: Action of the speed governor
plus the turbine generator is “instantaneous”compared with the rest of the power system.
52www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 53/201
The Equation of Change in frequency is:
For example let us consider Kp=120Hz/puMW, Tp=20sec, R=2.40 Hz/pu MW, M=0.01pu MW.
The approximate time response is thereforepurely exponential.
53
s
M
sT
K
R
sT
K
s f
p
p
P
p
.
1.
11
1)(
55.2
110235.0)(
s s s f
t et f 55.210235.0)(
t et f 55.210235.0)( www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 54/201
54
Dynamic Response of Single area system
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 55/201
The system can be made still faster byreducing R, that is by increasing the staticloop gain.
Reduction of R also increases the static
frequency error. By considering the time responses causes
larger transient dips.
55www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 56/201
The system could undergo intolerable
dynamic frequency changes with changes inload.
It forces the frequency error to zero by theadjusting the control input.
SPECIFICATIONS:
Loop stability
Isochronous control (i.e.) Δf is 0.
Integral of frequency error should be minimized.
Economical sharing of loads between theindividual generators in the control area.
56www.VIdyarthiplus.com
Secondary ALFC Loopwww.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 57/201
57
Secondary ALFC Loop
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 58/201
In central load frequency control of a given controlarea, the change in frequency is known as AreaControl Error (ACE).In the above scheme AEC being zero under steady stateconditions, a logical design criterion is the minimization of
dt for a step disturbance.
58
s
P
sT
K
s
K
R sT
K
s F D
t
pi p
p
1
11
)(
0)(0
s F state steady f s s
f
www.VIdyarthiplus.com
Dynamic response of the load frequency controllerwith and without integral control action
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 59/201
59
with and without integral control action
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 60/201
Load frequency control with integralcontroller exercises no control over therelative loadings of various generatingstations (i.e., economic dispatch) of thecontrol area.
Economic dispatch control can be viewed asan additional tertiary control loop. The function of the Economic Dispatch
Control (EDC) Program is to calculate theeconomic loading point for the various
generating units. Economic dispatch controller is a slow
acting control, which adjusts the speedchanger setting every minute in accordance
with a command signal generated by thecentral economic dis atch controller 60www.VIdyarthiplus.com
Control Area Load Frequency Control and Economic Dispatch
C t l
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 61/201
61
Control
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 62/201
If there are several generators in an area,the lumped behavior of the generators canbe got if: Controls of the generators are in unison. This
can be justified if individual control loops havesame parameters of regulation (R).
Turbine response characteristics are identical.
62www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 63/201
63
AREA - 1AREA - 2
Pnet int
Pnet int = total actual net interchange (+ : power leaving;
- : power entering)
ΔPnet int
( = ΔP12
) = Pnet int
- Pnet int schd
Pnet int schd = scheduled or desired value of interchange;
ΔPL1 = Load change in area 1; ΔPL2 = Load change in area 2;
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 64/201
64
Δf ΔPnet intLOAD
CHANGE
CONTROL
ACTION
_ _ ΔPL1 > 0
ΔPL2 = 0Increase Pgen1.
+ + ΔPL1 < 0
ΔPL2 = 0Decrease Pgen1
_ + ΔPL1 = 0
ΔPL2 > 0
Increase Pgen2
+ _ ΔPL1 = 0
ΔPL2 < 0Decrease Pgen2
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 65/201
65www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 66/201
Basic Operating Principles:1. Each pool member or control area shouldstrive to carry its own load.
2. Each control area must agree upon
adopting regulating and control strategiesand equipment that are mutually beneficialunder both normal and abnormal situations.
66www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 67/201
In normal operation the power on the tie-lineis given by,
Where synchronizing co-efficient is:
67
2
0
1
02
01
0
12
0
sin X
V V
P
MW X
V V P 212
01
02
01
0
12 cos
rad MW X
V V T /cos 2
01
02
01
0
0
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 68/201
The tie-line power deviation then takes of thefollowing form
The frequency deviation is related to thereference angle by the formula,
Tie-line power deviations is:
68
MW T P 21
0
12
Hz dt
d
dt
d f
2
1
2
1 0
t
rad dt f 2
MW f dt f T P
t t
dt
21
0
12 2
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 69/201
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 70/201
70www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 71/201
TIE-LINE BIAS CONTROL: The control error for each area is a linear combination of
(biased/weighted) frequency error and the net interchangeerror,
ACE1 = ∆Pnet int1 + B1 ∆f 1ACE2 = ∆Pnet int2 + B2 ∆f 2
If KI1 and KI2 are integrator gains, speed-changer commandsare given by,
Negative sign indicates the increase in generation for adecrease in ∆f or ∆Pnet,int.
Our aim is to drive ∆f and ∆Pnet,int 0. when steady state isreached, speed changer settings would have to be zero. Hence,
∆P12,0 + B1 ∆f 0 = 0 ; ∆P,21,0 + B2 ∆f 0 = 0
dt f B P K P
dt f B P K P
net I ref
net I ref
222int,22,
111int,11,
71www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 72/201
The response of the two-area system withfixed speed changer positions is:
The incremental increase in turbine dynamics
in this static case is determined by the staticloop gains.
72
02,1,
ref ref P P
0
1
0,1
1 f
R P T
0
2
0,2
1 f
R P T
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 73/201
73
0,10110
1
1tie P f D M f
R
0,10220
2
1tie P f D M f
R
Hz M M f 21
210
puMW M M
P P tietie
21
1221
0,20,1
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 74/201
Equation of changes in frequency and tie-linepower is:
74
Hz M M
f 2
210
MW pu M M
P P tietie
2
12
0,20,1
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 75/201
Assumptions: Consider the case of two equal areas.
Consider the turbine controller fast relativeto the inertia part of the systems, i.e., we
set GH=GT=1. Neglect the system damping. This means
that we assume the load not to vary withfrequency; i.e., we set D1=D2=0.
75www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 76/201
76
H T f s RH f s
s P s P
H
T f s P D D
tie/22/
0002
12
00
1
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 77/201
77www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 78/201
An excitation system is the source of fieldcurrent for the excitation of a principleelectric machine, including means for its
control.
78www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 79/201
To provide direct current to the synchronousmachine field winding.
To perform control and protective functionsessential to the satisfactory performance of
the power system by controlling the fieldvoltage and thereby the field current.
79www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 80/201
To meet specified response criteria. To provide limiting and protective functions.
To meet specified requirements for operatingflexibility.
To meet the desired reliability andavailability.
80www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 81/201
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 82/201
82
Limiters andProtective ckts
Terminal voltagetransducer & load
compensator
Generator
Power System
Stabilizer
ExciterRegulator
ToPS
Ref
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 83/201
ExciterProvide dc power to the synchronous
machine field winding.
RegulatorProcess and amplifies input control
signals to a level and form appropriate forcontrol of the exciter.
83www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 84/201
Terminal voltage transducer and loadcompensator
Senses generator terminal voltage,
rectifies and filters it to dc quantity andcompares it with a reference whichrepresents desired terminal voltage.
Power system stabilizerProvides additional input signal to the
regulator to damp power systemoscillations.
Limiters & protective circuitsInclude a wide array of control and
protective functions which ensure that thecapability limits of the exciter andsynchronous generator are not exceeded.
84www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 85/201
Essential for the assessment of desiredperformance requirements.
For the design and co-ordination of supplementary control and protective circuits.
For system stability related to the planningand operation of power systems.
85www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 86/201
For an isolated generator feeding a load,AVR is used to maintain the bus bar voltageconstant.
To keep the system voltage constant so thatthe connected equipment operatessatisfactorily.
To obtain a suitable distribution of reactive
load between machines working in parallel. To improve stability.
86www.VIdyarthiplus.com
FUNCTIONAL BLOCK DIAGRAM OF AVR LOOPwww.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 87/201
87
Gs
Gf
Comparator Amplifier Exciter Rectifier
Synchronousgenerator
a
b
c
PT
Rectifier and FilterStability
compensators
+
-
| V| ref e
- +
+
-
Rotating components
+-
| V|
VR
+
-
Vf
ieif
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 88/201
88
KA /(1+ sTA) K e / (1+sTe )
ΔIvIref Δe ΔvR
Δvf
ΔIvI
Comparator Amplifier Exciter
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 89/201
89
0,0,0,0 .100 ref ref V
pV V e
0,0,00,0)0(1
)0(ref ref ref
V G
GV V V e
0,0, 1
1
)0(1
1ref ref
V K
V G
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 90/201
From the theory of linear control systems it isknown that the time response Δ|V| (t) of theloop equals
∆│V│ (t) = £-1{∆ Vref(s) (G(s) / G(s) +1)}
Mathematically, the response depends uponthe eigen values or closed-loop poles, whichare obtained from the characteristic equation
G(s) +1 = 0
90www.VIdyarthiplus.com
Closing the AVR loop; (a) individual blockrepresentation; (b) condensed model; (c) closed
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 91/201
91
representation; (b) condensed model; (c) closed
loop model.
Comparator Amplifier Exciter field Generator field
G(s)
(G(s) / G(s) +1)
(a)
(b)
(c)
Δ│ V│ref Δ │ V│
Δ │ V│Δ│ V│ref
-
+ Δe
k A / (1 + sT A ) K e / (1+sTe) K F / (1+sT’ do)
Δ vR Δ vf Δ │ V│
Δ│ V│ref Δe
Δ │ V│
+
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 92/201
High loop gain is needed for static accuracybut this causes undesirable dynamic
response, possibly instability. By adding series and / or feedback stability
compensation to the AVR loop, thisconflicting situation can be resolved.
Consider for example the addition of aseries phase lead compensator, having thetransfer function
Gs = 1 + sTc92www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 93/201
The open-loop transfer function will nowcontain a zero
G (s) = k (1 + sTc) / (1 + sTA) (1 + sTe) (1
+ Tdo)
The added network will not affect the staticloop gain K, and thus the static accuracy.
The dynamic response characteristics willchange to the better.
93www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 94/201
Excitation system
Generation & absorption of reactive power
Relation b/w V, P,& Q at a node
Methods of voltage control
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 95/201
1. Shunt capacitors2. Series capacitors
3. Synchronous capacitors
4. SVC
5. Tap changing transformers
6. Booster transformers.
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 96/201
By adjusting the excitation of the generator at the sendingend.
The larger the reactive power required by the load themore is the excitation to be provided at the sending end.
Limitation:
Worked well in small isolated system where there wasno local load at the sending end.
Excitation below a certain limit may result in instabilityand excitation above certain level will result inoverheating of the rotor.
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 97/201
Used across an inductive load so as to supply part of the reactive vars required by the load so that thereactive vars transmitted over the line are reduced,thereby the voltage across the load is maintained withincertain desirable limits.
The shunt reactors are used across capacitive loads orlightly loaded lines to absorb some of the leading varsagain to control the voltage across the load to withincertain desirable limits.
Capacitors are connected either directly to a bus bar or
through a tertiary winding of the main transformer andare disposed along the route to minimize the voltagedrop and the losses.
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 98/201
It reduces the inductive reactance between the load andthe supply point, thereby reducing the voltage dropproduced by an inductive load.
It improves the voltage stable state and supplies reactivepower to the receiving end such that voltage profile is
maintained. Improves the steady state stability.
Increases the power flow transfer in lines.
For long transmission lines where the total reactance ishigh, series capacitors are effective for improvement of
system stability.
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 99/201
It is basically a synchronous motor running at noload.
Depending on the value of excitation, it canabsorb or generate reactive power.
Its use in high voltage transmission lines helps in
either absorption of reactive power or supply of reactive power under light load or heavy loadconditions respectively.
Improves system stability.
Supply heavy amount of reactive power duringshort period.
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 100/201
Compensation
Type
Drawbacks
Static SwitchedShuntCapacitor
On light loads when the corrective varsrequired are relatively less, thecapacitor output is large and vice versa.
Synchronouscondensors
Only continuous control is possible.
High cost of installment & need highmaintenance.
SeriesCapacitor
Severe over voltage during line fault.Problem of Ferro resonance & Subsynchronous resonance
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 101/201
A parallel combination of controlled reactor and fixed staticcapacitor.
Working Principle: By varying the thyristor firing angle, thereactor current is varied thereby controlling the reactivepower absorption by inductor. Capacitor in parallel supplies
reactive power to the system. The net reactive power injection to bus becomes Q =
Q c – Q l. Q l is varied and thus Q is controllable. The bus voltage is thus
controllable by SVC.
During light load Ql > Qc, while during heavy load Qc < Ql. Improves system stability, voltage stability and reduces power
oscillations.
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 102/201
Almost the power transformers on transmission lines areprovided with taps for ration control i.e. control of secondary voltage. There are two types of tap changingtransformers:
(i) Off-load tap changing transformers.
(ii) On-load (under-load) tap changing transformers.
The tap changing transformers do not control the voltageby regulating the flow of reactive vars but by changing thetransformation ratio, the voltage in the secondary circuit isvaried and voltage control is obtained. This method is themost popular as it can be used for controlling voltages at
all levels.
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 103/201
Requires the disconnection of the transformer when thetap setting is to be changed.
S2S1
Q1Q2
Neutral
Line
Winding
Winding
V
Fig. 4.5.5 Off-load tap changing
transformer
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 104/201
In the position shown the voltage is amaximum and since the currents divide equallyand flow in opposition through the coilbetween Q1 and Q2, the resultant flux is zeroand hence minimum impedance.
To reduce the voltage, the following operationsare required in sequence: (i) open Q1; (ii) moveselector switch S1 to the next contact; (iii) closeQ1; (iv) open Q2; (v) move selector switch S2 to
the next contact; and (vi) close Q2.
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 105/201
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 106/201
In large interconnected system, some times with the tap-setting adjustments of the tap-changing transformersindirectly in the system, the reactive power requirement may
be altered.
X/t2
V1 /t
t:1
Q
(a)
t:1
Q
V2V1
X V2V1
~~
~ ~
(b)
Fig. 4.6.2 (a) Systems interconnected through tap-changing transformer (b) its equivalent circuit
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 107/201
Reactive power requirement
◦ By changing the off-normal setting t, it is possible tochange the var requirement Q of the line due to thereactance X.
◦ When t is less than unity, Q is positive and there isthus a flow of lagging VAR to bus 2.
◦
When t is greater than unity, Q is negative and there isthus a flow of leading VAR to bus 2.
X
t t V Q
)1(2
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 108/201
10
8www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 109/201
Refers to the most economic loading of thegenerators which are connected to the systemand running.
Fuel cost is the principal factor in fossil fuelplants and is given as a function of generation.
ED problem is to define the production levelof each plant so that the total generation andtransmission cost is minimum for a
prescribed schedule of loads.
10
9www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 110/201
Lagrange Multiplier method Lambda Iteration method
Gradient method
Dynamic programming
Evolutionary Computation Techniques
11
0www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 111/201
Used to describe the efficiency of the plants. Graphical Representation of input in Rs/hr
versus power output in megawatts is calledinput-output curve.
11
1www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 112/201
A plot of the input in kilocalories per hourversus power output in megawatts is calledinput-output curve.
The ordinates of the curve may beconverted to Rs/hr by multiplying the fuel
in Rs/kilocalories. The empirical equation of the this curve is
given by
Where a, b and c are constants dependingupon a particular plant.
11
2
cbP aP C iii 2
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 113/201
Incremental fuel cost
The incremental cost is equal to the slope of the cost curve. A plot of incremental costversus power output is called the incrementalcost curve. It is shown in Fig.3. Equation (2) isof the form
The incremental cost is equal to the slope of the cost curve.
11
3
i
i
idP
dC IC )(
=
baP i 2;
Rs/ MWh
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 114/201
The input-output curve for a typical hydro unitis shown in Fig. 4. This is obtained by plottingthe water input or discharge in cubic metersper second as a function of the power output in
megawatts. The incremental cost curve forhydro unit is shown in Fig. 5. This is obtainedby plotting the incremental cost in rupees perMW – second (Rs/MW - s)
as a function of power output in megawatts(MW).
11
4www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 115/201
11
5www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 116/201
It consists of N generating units connected toa single bus bar serving a receiving electricalload
11
6www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 117/201
let
11
7
N T F F F F F ...321
N
i
ii P F 1
N
iiload P P 10
subject to (1) energy balance equation and (11)
inequality constraints
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 118/201
This is a constrained optimization problemthat may be attacked formally usingadvanced calculus methods that involve theLagrange function.
In order to establish the necessaryconditions for an extreme value of theobjective function, add the constraintfunction to the objective function after the
constraint function has been multiplied byan undetermined multiplier. This is knownas the Lagrange function.
11
8www.VIdyarthiplus.com
Lagrange function with respect to the power
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 119/201
Lagrange function with respect to the poweroutput values one at a time give the set of
equations shown
Where is the Lagrangian multiplier.
The necessary condition for this
optimization problem is taking the firstderivative of the Lagrange unction withrespect to the each of the independentvariables and set the derivatives equal tozero i.e
11
9
L = FT +
0
i
ii
i P
P F
P
L
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 120/201
i
i
P
F 0
i
i
P
F 0
12
0
This is called as coordination equation. i.e. the
necessary condition for the existence of a minimum
operating cost is that the incremental cost rates of all
the units be equal to the some in determined value .
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 121/201
This is the necessary condition for the existence of aminimum cost operating condition for the thermal power system is that the incremental cost rates of allthe units be equal to some undetermined value, . Of course, to this necessary condition we must add theconstraint equation that the sum of the power outputs
must be equal to the power demanded by the load. Inaddition, there are two inequalities that must besatisfied for each of the units. That is, the power output of each unit must be greater than or equal tothe minimum power permitted and must also be less
than or equal to the maximum power permitted onthat particular unit.
12
1www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 122/201
These conditions and inequalities may besummarized as shown in the set of equationsN equations
12
2
i
i
P
F
max,min, iiiP P P
N
i
Loa d i P P 1
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 123/201
12
3www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 124/201
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 125/201
Objective Fn
FT=F1+F2+………+FN
Subjected to
12
5
N
i
i Loss Load P P P
1
0
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 126/201
Using Lagrangian FunctionL = FT +
Where „‟ is the lagrangian multiplier i.e.,add the constrained function „ „ to the
objective function after the constrainedfunction is multiplied by an undeterminedmultiplier
12
6www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 127/201
Taking the derivative of lagrangian functionwith respect to any one of the N values of Pi isshown as:
12
7
01
i
loss
i
i
i P
P
P
F
P
L
i
loss
i
i
P
P
P
F
01
N
i
ilossload P P P
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 128/201
Step1: Development of mathematical modelfor the losses in the network as the functionof the power output of each units (LossFormula Method).
Step2: To incorporate the power flowequations
as essential constraints. (Optimal PowerFlow)
12
8www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 129/201
One of the method to solve the economicdispatch problem by neglecting the losses.
Eg.
consider three units system, to find the
optimal economic operating point withoutlosses
- assume an incremental cost rate andfind the power outputs of these three units.
12
9www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 130/201
Is an iterative type of computation andstopping rules are used,
(1) stopping rules based on finding theproper operating point with in a specified
tolerance.(2) stopping rules based on maximum
number of iteration
13
0www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 131/201
EDP is solved repeatedly by moving the generators fromone economically optimum schedule to another as theload changes by a reasonably small amount.
Next, the scheduler assumes a load change andinvestigates how much each generating unit needs to bemoved ie, participate in the load change in order that
the new load be served at the most economic operatingpoint.
Assume that both the first and second derivatives in thecost versus power output function are available (ie, bothand ). As the unit load is changed by an amount , the
system incremental cost moves from to . For a smallchange in power output on this single unit.
13
1www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 132/201
13
2www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 133/201
Refers to the most economic loading of thegenerators which are connected to the systemand running.
Fuel cost is the principal factor in fossil fuelplants and is given as a function of
generation. ED problem is to define the production level
of each plant so that the total generation andtransmission cost is minimum for a
prescribed schedule of loads.
13
3www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 134/201
Lagrange Multiplier method Lambda Iteration method
Gradient method
Dynamic programming
Evolutionary Computation Techniques
13
4www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 135/201
Used to describe the efficiency of the plants. Graphical Representation of input in Rs/hr
versus power output in megawatts is calledinput-output curve.
13
5www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 136/201
A plot of the input in kilocalories per hourversus power output in megawatts is calledinput-output curve.
The ordinates of the curve may beconverted to Rs/hr by multiplying the fuel
in Rs/kilocalories. The empirical equation of the this curve is
given by
Where a, b and c are constants dependingupon a particular plant.
13
6
cbP aP C iii 2
www.VIdyarthiplus.com
I t l f l t
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 137/201
Incremental fuel cost
The incremental cost is equal to the slope of the cost curve. A plot of incremental costversus power output is called the incrementalcost curve. It is shown in Fig.3. Equation (2) isof the form
The incremental cost is equal to the slope of the cost curve.
13
7
i
i
idP
dC IC )(
=
baP i 2;
Rs/ MWh
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 138/201
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 139/201
13
9www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 140/201
It consists of N generating units connected toa single bus bar serving a receiving electricalload
14
0
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 141/201
let
14
1
N T F F F F F ...321
N
i
ii P F 1
N
iiload
P P 1
0
subject to (1) energy balance equation and (11)
inequality constraints
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 142/201
This is a constrained optimization problemthat may be attacked formally usingadvanced calculus methods that involve theLagrange function.
In order to establish the necessaryconditions for an extreme value of theobjective function, add the constraintfunction to the objective function after the
constraint function has been multiplied byan undetermined multiplier. This is knownas the Lagrange function.
14
2
www.VIdyarthiplus.com
Lagrange function with respect to the powerl i i h f
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 143/201
output values one at a time give the set of
equations shown
Where is the Lagrangian multiplier.
The necessary condition for this
optimization problem is taking the firstderivative of the Lagrange unction withrespect to the each of the independentvariables and set the derivatives equal tozero i.e
14
3
L = FT +
0
i
ii
i P
P F
P
L
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 144/201
i
i
P
F 0
i
i
P
F 0
14
4
This is called as coordination equation. i.e. the
necessary condition for the existence of a minimum
operating cost is that the incremental cost rates of all
the units be equal to the some in determined value .
www.VIdyarthiplus.com
This is the necessary condition for the existence of a
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 145/201
This is the necessary condition for the existence of aminimum cost operating condition for the thermal
power system is that the incremental cost rates of allthe units be equal to some undetermined value, . Of course, to this necessary condition we must add theconstraint equation that the sum of the power outputsmust be equal to the power demanded by the load. Inaddition, there are two inequalities that must besatisfied for each of the units. That is, the power output of each unit must be greater than or equal tothe minimum power permitted and must also be less
than or equal to the maximum power permitted onthat particular unit.
14
5
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 146/201
These conditions and inequalities may besummarized as shown in the set of equationsN equations
14
6
i
i
P
F
max,min, iiiP P P
N
i
Loa d i P P 1
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 147/201
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 148/201
The unit commitment economically schedulesgenerating units over a short-term planninghorizon subject to the satisfaction of demandand other system operating constraints.
It involves determining start-up and shut-down schedule of units to be used to meet theforecasted demand , over a future short termperiod.
belongs to the class of complex combinatorialoptimization problems..
14
8
www.VIdyarthiplus.com
Consider 3 units shown below:
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 149/201
Consider 3 units shown below:Unit 1: Min = 150MW, Max=600MW.Unit 2: Min = 100MW, Max=400MW.Unit 3: Min= 50 MW, Max = 200 MW.Load is 550 MW.
What is the combination of units tosupply the load most economically?
14
9
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 150/201
Unit 1 Unit 2 Unit 3 PG Total generationcost
ON ON ON P1= 267
P2=233
P3=50
5617
ON ON OFF P1= 295
P2=255
5471
ON OFF OFF P1= 550 5389
OFF ON ON P2= 400
P3=150
5418
150www.VIdyarthiplus.com
A E l f P k ll l d tt
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 151/201
An Example of Peak-valley load pattern
15
1
1200 MW
500 MW
Time
Total Load
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 152/201
15
2
600 MW
Time
Total Load
1200 MW
UNIT 1
UNIT 2UNIT 2
UNIT 1 UNIT 1
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 153/201
Spinning Reserve:Describes the total amount of generation
schedule available from all unitssynchronized on the system minus presentload and losses being supplied.
Loss of one or more units should not causea too far drop in frequency.
Reserve must be capable of making up theloss of most heavily loaded unit in a givenperiod of time.
15
3
www.VIdyarthiplus.com
Units
1,2 and 3Units 4
and 5550
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 154/201
15
4
MW
Unit Unitcapacity
Unitoutput
SpinningReserve
12
3
1000800
800
900420
420
100380
380
4
5
1200
600
1040
310
160
290
1900 MW1190 MW
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 155/201
Thermal Constraints:Thermal units undergo only gradual
temperature changes.
Minimum Up time: Once the unit is running,it should not be turned off immediately
Minimum Down time: Once the unit isdecommited, there is a minimum time beforeit can be recommitted.
Crew Constraints: No enough crew membersto attend two or more units while starting up.
155
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 156/201
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 157/201
157
f
t
c c F c
)1(
cc
F
f c
t
where
= cold-start cost (MBtu)
= Fuel cost
=Fixed cost
= Thermal time constant for the Unit
= time (h) the unit was cooled
www.VIdyarthiplus.com
Start-up cost when banking
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 158/201
158
f t c F t c
t c = cost (MBtu/h) of maintaining unit
at operating temperature
where
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 159/201
159
Banking
CoolingStart upcost
Time
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 160/201
Must run constraint: Some units are given amust run status during all the times.
Fuel Constraints: Some units have limited fuelor have constraints that require them to burn
a specified amount of fuel.
160
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 161/201
Let there be M periods and N units.
The total number of combinations at eachhour is:
The maximum number of possiblecombinations is (2N-1)M
j j
j j N
N
j N C
........21!
!)!(
!
),(
161
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 162/201
Priority list schemes
Dynamic Programming
Lagrange Relaxation
162
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 163/201
It consists of priority list of units to becommitted.
Full load average production cost of each unitis calculated.
Then in the order of ascending costs, theunits are arranged for commitment.
163
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 164/201
Consider 3 units shown below:
Unit 1: Min = 150MW, Max=600MW.H1=510+7.2P1+0.00142P1
2
Unit 2: Min = 100MW, Max=400MW.
H2= 310+7.85P2+0.00194P22.
Unit 3: Min= 50 MW, Max = 200 MW.H3 = 78+7.97P3+0.00482P3
2. Load is 550 MW.
Fuel cost1=1.1 R/MBtu
Fuel cost2=1.0 R/MBtu
Fuel cost3=1.2 R/MBtuWhat is the combination of units to
supply the load most economically?
164
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 165/201
165
Unit Full loadaverage
productioncost(R/MWh)
Min MW Max MW
1 9.79 100 400
2 9.48 150 600
3 11.188 50 200
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 166/201
166
Combination Min MW Max MW
2+1+3 300 1200
2+1 250 1000
2 100 400
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 167/201
No load costs are zero.
Unit input-output characteristics are linearbetween zero output and full load.
There are no other restrictions.
Start up costs are a fixed amount.
167
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 168/201
A state consists of an array of units
with specified units operating and therest off-line.
The start up cost of a unit isindependent of the time it has been
off-lined (i.e., it is a fixed amount). There are no costs for shutting down a
unit. There is a strict priority order, and in
each interval a specified minimumamount of capacity must be operating.
168
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 169/201
),(),1(cos),:,1(cos
),(cos),(cos
),(cos),(cos
)],1(cos),:,1(cos),(cos[min),(cos
I K to L K state fromt transition I K L K t S
I K state for t production I K t P
I K stateat arrivetot total least I K t F
where
L K t F I K L K t S I K t P L
I K t F
169
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 170/201
170
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 171/201
REC-EEE DEPT171
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 172/201
REC-EEE DEPT172
What is SCADA◦ SCADA – Supervisory Control and Data Acquisition
◦ SCADA system includes a computer system with an application
program running that acquires the real-time data from the data
acquisition units located in the field at a remote location in order
the monitor the devices remotely and control them. SCADA equipment are located in:
1. Master control center (national grid control centre)
2. Zonal (regional) control centers
3. District control centre (state electricity board)
4. Control rooms of generating stations and large sub-station.
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 173/201
REC-EEE DEPT173
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 174/201
1. Monitoring
2. Alarm
3. Control and indication of production automatic generationcontrol (AGC)
4. Data logging
5. Data acquisition
6. Control ON/OFF, RAISE/LOWER7. Display
Additional functions are provided with SCADA systems for national loadcontrol centres:
1. Interactive studies
2. Security assessment calculations contingency
3. Training simulator 4. Network modeling and Energy management systems(EMS)
REC-EEE DEPT174
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 175/201
Point to Point Connection Multiple point to point connection
Star connection
REC-EEE DEPT175
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 176/201
SCADA system is for local and remote control
applications suitable for electrical and non-electrical
distribution areas.
SCADA-based electrical application areas are:◦ Power transmission and distribution
The SCADA-based non- electrical application areas are:◦ District heating
◦ Water purification and distribution
◦ Waste water treatment
◦
Oil and gas distribution etc.
REC-EEE DEPT176
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 177/201
Substation Automation means that the substation has
equipment, which enables communication with theprimary equipment and use of process data for supervision, control and communication.
The functions may include:◦
viewing status of breakers and disconnectors◦ controlling the breakers and disconnectors◦ dynamic coloring of the busbars◦ viewing and setting of protection parameters◦ viewing condition of auxiliary equipment e.g. batteries◦ collection of metering data◦
transferring data to network control center
REC-EEE DEPT177
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 178/201
REC-EEE DEPT178
www.VIdyarthiplus.com
f
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 179/201
The integration of control, protection and monitoring in
one common system is achieved using SCADA systemin a substation.
Control functions Control and monitoring of switching devices, tapped transformers,
auxiliary devices, etc. Bay- and a station-wide interlocking Dynamic Busbar coloring according to their actual operational
status. Automatic switching sequences Automatic functions such as load shedding, power restoration, and
high speed bus bar transfer (HBT) Time synchronization by radio and satellite clock signal
REC-EEE DEPT179
www.VIdyarthiplus.com
M it i f ti
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 180/201
Monitoring functions:
Measurement and displaying of current, voltage, frequency, activeand reactive power, energy, temperature, etc. Alarm functions. Storage and evaluation of time stamped events Trends and archiving of measurements Collection and evaluation of maintenance data Disturbance recording and evaluation
Protection functions: Substation protection functions includes the monitoring of eventslike start, trip indication and relay operating time and setting andreading of relay parameters.
Protection of bus bars. Line feeders, transformers, generators Protection monitoring (status, events, measurements, parameters,
recorders) Adaptive protection by switch-over of the active parameter set Optional: all information regarding protection on a separate
workplace.
REC-EEE DEPT180
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 181/201
Strategic Benefits:
Improved quality of service
Improvedreliability
Maintenance/expansion of customer base
High value service provider Added value services
Improved customer access to information
Enterprise information accessibility
Flexible billing options
REC-EEE DEPT181
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 182/201
Tangible Benefits: Reduced manpower requirements
Reduced system implementation costs
Reduced operating costs
Reduced maintenance costs Ability to defer capacity addition projects
Improved information for engineering decisions
Improved information for planning decisions
Reduced customer outage minutes
REC-EEE DEPT182
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 183/201
REC-EEE DEPT183
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 184/201
REC-EEE DEPT184
www.VIdyarthiplus.com
P t ti f ti
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 185/201
Protective functions:
Under frequency protection Earth fault protection Condition Fail protection feeder protection & auto reelecting Breather failure protection Busbar protection Back up protection
Benefits of distribution automation:
Improved reliability Economic benefits Early warning feature
REC-EEE DEPT185
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 186/201
REC-EEE DEPT186
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 187/201
REC-EEE DEPT187
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 188/201
REC-EEE DEPT188
www.VIdyarthiplus.com
S f
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 189/201
Soft sensor:
It allows for proper closure of the control loop on product
quality, leading to superior performance in quality
control, while also meeting production targets on
throughput and energy consumption.
SCADA system allows optimal use of the plant and
generates sustainable improvements in product quality
and consistency.
REC-EEE DEPT189
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 190/201
REC-EEE DEPT190
STATION CHECK TRIP-CLOSE
LOWER-RAISE CLOSE-OPENSTOP-START
ANALOG DATA COUNTED
DATA BINARY DATA
ALARMS & STATUS
INDICATION
ALARM ANNUNCITOR
A/D
CONVERTER
DATA
DISPLAYS
CONTROL
CONTORL &
INDICATION
ANALOG
DATA
MASTER
STATION
M
O
D
E
M
M
O
D
E
M
REMOTE
STATION
INDICATION
BINARY
DATA
PULSE
COUNTER
INDICATION
SPECIAL FUNCTIONS
www.VIdyarthiplus.com
P Li C i
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 191/201
Power Line Carrier: Power line carrier communication (PLCC) was quite popular in the
past, mainly for signaling.
Power line carrier systems use electric transmission and distribution
lines to carry digital data and voice.
Wire lines: Many SCADA systems employ wireline links (private networks) to
communicate between the SCADA Master Control Center (MCC)and substation RTUs.
The commonly used wireline and telephone networks allow veryreliable point-to-point or point-to-multi-point (multi-drop)communication.
REC-EEE DEPT191
www.VIdyarthiplus.com
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 192/201
192
NATIONAL CONTROL CENTRE
REGION COMPUTER
SYSTEM
REGION COMPUTER
SYSTEM
REGION COMPUTER
SYSTEM
BOARD COMPUTERSYSTEM
BOARD COMPUTERSYSTEM
BOARD COMPUTERSYSTEM
Ist LEVEL
IInd LEVEL
IIIrd LEVEL
www.VIdyarthiplus.com
Regional load control centre:
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 193/201
Regional load control centre:
It decides generation allocation to various generating stations withinthe region on the basics of equal incremental operating cost
considering line losses are equal and Frequency control in the
region.
Plant load control room
It decides the allocation of generation of various units in the plant onthe basis of:
1. Equal incremented operating cost of various units
2. Minimize the reactive power flow through line so as to minimize
line loss and maintain voltage levels and Frequency control in the
plant.
REC-EEE DEPT193
www.VIdyarthiplus.com
It minimizes
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 194/201
REC-EEE DEPT194
It minimizes
1. Reactive power flow through the transmission lines bycompensation.
2. Maintain voltage levels by minimize the line
3. The Synchronizing and system restoration are also done by the
Sub-station control room.
The primary objectives of the various levels are:•load frequency control
•voltage control
•economic load dispatch
www.VIdyarthiplus.com
1 Electrical and mechanical variables on/off states
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 195/201
1.Electrical and mechanical variables on/off states
2. Analogue quantities
3. Digital quantities
4. Change of state sequence of event
5. Time of occurrence and several other data which the
control room operator would like to know.
Data transmission:
Data is transmitted from the process location to thecontrol room and the control room to the control center.
REC-EEE DEPT195
www.VIdyarthiplus.com
The large number of electrical/ mechanical/other data
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 196/201
The large number of electrical/ mechanical/other data
are scanned at required interval, recorded and displayedas per the requirements. Some of the data is converted
from analogue to digital form by A/D converters. The
data loggers perform the following function:◦
Input scanning◦ A/D conversion
◦ Display
◦ Signal amplification
◦ Recording
◦ Programming
REC-EEE DEPT196
www.VIdyarthiplus.com
1 The data is acquired by means of a CTs VTs
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 197/201
1. The data is acquired by means of a CTs VTs,
transducers and other forms of collecting informations.
2. The transducers convert very large number of electrical,mechanical and other datas (informations) into electricalform to enable easy measurement and transmission.
3. Data may be collected at low level (5 mA) or high level(5 v). The data amplified in signal amplifier andconditioned in data signal conditioner.
REC-EEE DEPT197
www.VIdyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 198/201
◦ Acquisition of information (measured values signals alarms
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 199/201
◦ Acquisition of information (measured values, signals, alarms,
meter readings), including features such as plausibility checksand filtering.
◦ Output of commands / instructions (binary pulse type or
continuous commands, set points, control variables) . Including
their monitoring ( as a function of time, lout of n)
◦ Recognition of changes in signal input states, pulse time dataallocation for sequential recording of events by the master control
stations.
◦ Processing of information transmitted to and from the
telecommunication equipment ( Data compression, Coding and
protection)◦ Communication with master control stations.
REC-EEE DEPT199
www.VIdyarthiplus.com
Transmission Substation RTUs:
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 200/201
Transmission Substation RTUs:
Main substation RTU can connect to many other RTUs
in the substation, each with a specific function or
functions, including closed loop control and
computation.
Many RTUs have the ability to interface with other
substation devices generally referred to as IEDs
(Intelligent Electronic Devices)
REC-EEE DEPT200
www.VIdyarthiplus.com
Distribution Automation RTUs:
www.Vidyarthiplus.com
7/27/2019 Power - System - Einstein Notes
http://slidepdf.com/reader/full/power-system-einstein-notes 201/201
Distribution Automation RTUs:
“DA” RTUs are having all inputs, outputs and the RTUmicroprocessor on just one printed circuit board.
If the RTU is expandable, additional input and output
cards are connected by flat ribbon cables rather than
plug-in cards, making the system more rugged andcompact.
These RTUs usually contain an integral lead acid gel
cell battery backup system and integral