MITSUBISHI ELECTRONIC MULTI-MEASURING INSTRUMENT
ME96NSRMODEL
-
8/13/2019 Power Meter ME96NSR Catalog
2/32
MITSUBISHI Electronic Multi-Measuring Instrument NS Series features high performanceand crystal clear display.
With simple operating functions, NS Series is the best support your measuring and moni-toring systems.
16
23262829
Upper/lower limit monitoring up to 4 itemsHarmonics monitoringMeasures import/export active energy
4 items displayableBacklight automatic off function
ModBus communicationCC-Link communication
Simple settingsSimple operations
Output functions for 7 itemsPulse width settablePulse output at 2 points
Analog output range settable
DIN Size 9696mm3P4W/3P3W Common Use
Add-on Type Output OptionsCE MarkingConforms to EU RoHS Directive( 2002/95/EC )
FeaturesFunctions
Dimensions / Mounting / WiringSpecificationsRelated ProductsSafety Precaution
-
8/13/2019 Power Meter ME96NSR Catalog
3/32
F eature sModBus Transmission System (ME96NSR-MB, Optional Plug-in Module ME-0052-NS96)
CC-Link Transmission System (ME96NSR, Optional Plug-in Module ME-0040C-NS96)
Analog Pulse Transimission System (ME96NSR, Optional Plug-in Module ME-4201-NS96)
RS485/RS232Converter
Central Monitor
RS485 (ModBus)
RS232
ModBus communication system to monitor computers. By adding the optional plug-in module ME-0052-NS96, monitoring of contact input
signal and ON/OFF of contact output signal can be controlled remotely. Digital input signal can be latched for over 30ms, and there is no need for external latch
circuits.Optional Plug-in ModuleME-0052-NS96
SHT (OFF)CC (ON)ALPALTALACB Status
Max. Baud Rate 38.4kbp Max. Connection Distance 1000m Max. Connection Units 31
Digital Input 5 points (24VDC) Digital Output 2 points (35VDC)
Optimum transmission system for remote monitoring using MITSUBISHI PLC.
Remote monitoring of contact signal leading to less wiring, less spacing. Digital input signal can be latched for over 30ms, and there is no need for external latch
circuits.
Abnormal Signal (Facility)
Abnormal Signal (Earth Leakage)
Abnormal Signal (Temperature)
Circuit Breaker Status Signal etc
Max. Baud Rate 10Mbps Max. Connection Distance 100m (10Mbps)
to 1000m (156kbps) Max. Connection Units 42 Digital Input 4 points (24VDC)
CC-Link
NETWORK
MELSEC Series
NETWORK
Can remotely monitor A, DA, V, W, var, VA, PF, Hz, Harmonics Current RMS Value,and Harmonics Voltage RMS Value at 4 to 20mA output. (Max. of 4 outputs)
Active energy and reactive energy can be remotely monitored by pulse output.(Max. of 2 pulses)
Can remotely monitor upper/lower limit alarm by contact output. (Max. 1 point)
4 to 20mA 4 outputs Maximum 600 No-voltage a contact
35VDC 0.1A Pulse width 0.125, 0.5, 1s is selectable No-voltage a contact 35VDC 0.2A
Analog OutputPulse OutputAlarm Output
Basic Device
Model NameME96NSR
ME96NSR-MB
Transmission
ModBus Communication Optional Plug-in Modules
Model NameME-4201-NS96ME-0040C-NS96ME-0052-NS96
Analog Output4
Pulse Output2
Contact Input45
Contact Output (Note)
12
Transmission Function
CC-Link
Used withME96NSR
ME96NSR-MB(Note): Contact Output for ME-4201-NS96 closes at the time of high and low alarm occurrence. Contact Output for ME-0052-NS96 switches according to 16 bit set of ModBus communication.
1
-
8/13/2019 Power Meter ME96NSR Catalog
4/32
(1) All Phase Simultaneous Display
Displays measuring value for each phase digitally, and shows average value or total value by bar graph.
(2) Four Measuring Items Simultaneous Display
Four measuring items can be displayed simultaneously by tri-level digital display and bar graph.
(3) Special Display by Display Pattern P00
Display can be selected as desired in Display Pattern P00.
Average Current Average Voltage Total Electricity
Note: Average value or total value can be displayed by numbers by pressing the PHASE button.
< Functions Available >
Keep the display unchanged. Keep the display unchanged even when DISPLAY button is pressed.
Use ME96NSR instead of electric energy meter by displaying electric power.
Set onlyone display
Note: Digital display of each phase is possible by pressing the PHASE button.
DISPLAY DISPLAY DISPLAY
DISPLAY DISPLAY DISPLAY
Upper : Select from A, DA, V, W, var, VA, PF, Hz
Middle : Select from A, DA, V, W, var, VA, PF, Hz
Under : Select from A, DA, V, W, var, VA, PF, Hz, Wh, varh
Maximum of four displays can be set.
Desired Display can be ChosenDesired display can be chosen by selecting from existing patterns or selecting displays. (For the details of display patterns, please refer toDisplay Pattern Contents on page 22.)
F eature sVariety of Display Functions
2
-
8/13/2019 Power Meter ME96NSR Catalog
5/32
Note: Alarm Indicator blinks when it is set on alarm mode.
(1) Bar Graph Fixed Display
Measuring items displayed by bar graph can be fixed. shows that display is fixed.Also, display can be changed between average voltage, average current, total power, total reactive power, total power ratio, frequency bypressing , button.
(2) Digital Value Display by Bar Graph
Values shown on the tri-level digital display can be displayed by bar graph. (Except when the tri-level display is measuring the same items)Bar graph shows the digital value of .
Bar GraphEach measuring items can be displayed by a bar graph. With bar graph display, one can grasp the rated value and percentage against the alarmvalue instantly.
Maximum/Minimum Value DisplayThe maximum and minimum value of each measuring items can be displayed. Both the maximum and minimum value show the current status,so monitoring by the maximum and minimum value is possible. Also, range of minimum value to maximum value is shown by bar graph.
Cyclic DisplayIn cyclic display, the display changes automatically every five seconds. Even when this device is used in a very high place or inside of a panel,measuring items and measuring value of each phase can be checked without pushing DISPLAY , PHASE buttons.
Alarm Indicator
+
+
+
+ + +
Value shown by bar graph
Alarm Indicator
Operation Behavior
Press DISPLAY for 2 seconds Measuring items change automatically every 5 seconds
Press PHASE for 2 seconds Phase display changes automatically every 5 seconds
DISPLAY DISPLAY DISPLAY
< Features of Cyclic Display >
Cyclic display can display current status, maximum/minimum value Cyclic display continues even after power failures (No need for cyclic display operation)
+
3
-
8/13/2019 Power Meter ME96NSR Catalog
6/32
Measuring Functions
Harmonics MeasurementMeasuring of harmonics current, harmonics voltage is possible. This device can also be used for harmonics monitoring.
Harmonics Current
(other than phase N) Harmonics VoltageMeasuring
Items
Degree RMS Value Distortion Ratio
Harmonics Current(phase N)
RMS Value Distortion RatioRMS Value Distortion RatioSynthesis
1st3rd5th7th9th
11th13th
Note: When the 1st RMS value is 0 (zero), the distortion ratio shows 0% .
Measurement of Active Energy/Reactive EnergyThis device can be used to measure active power/reactive energy for particular type of power distribution facility, such as private powergenerating facility or condenser panel.
There are two ways of counting quadrant in measurement of reactive energy.
Wh varhEnergy Measurement
Setting (Sett ing 4.1) Imported Exported Imported Lag Imported Lead Exported Lag Exported LeadRemark
1
2Measurement of reactiveenergy is by 2 quadrants
3
4Measurement of reactiveenergy is by 4 quadrants
Measurement of 2 Quadrants/4 Quadrants by Reactive Energy
Pressing the , button at the same time for 2 seconds displays lower 3 digits. Small amount of value change of measuring value can bechecked.
Lower Digit Expanded Display
-varh(Imported lead + Exported lag)
+varh(Imported lag + Exported lead)
Press for 2 sec.
Decimal points shifts
Counts imported lag andexported lead as 1 segment,and imported lead andexported lag as 1 segment.Dead region occurs only inaround var=0 (Power ratio: 1).Since dead region does notoccur around Power ratio=0,
this is suited for facility withoutprivate power generator ormeasurement of reactivepower with condenser load ofPower ratio=0.
Counts each import lag, importlead, export lag, and exportlead as one segment.It is generally felt that a deadregion occurs in the border ofeach segment.This is suited for measurementof facilities with private power
generators.
F eatures
Accurate Measurement by Our Own ASICOur own ASIC allows for accurate measurements. (For details on measurement accuracy, please refer to Specifications on page 26.)
+var
-var
+W-W
Exportedlag
Exportedlead
Importedlead
Importedlag
+var
-var
+W-W
Exportedlag
Exportedlead
Importedlead
Importedlag
Lower digit expanded display is displayed onlywhen active/reactive energy is shown on the display.When the expanded display is operated duringactive energy screen, reactive energys lowerdigit is not expanded. For displaying lower digitsreactive energy, please operate by displayingreactive energy screen.
Note:
+
+ ,
4
-
8/13/2019 Power Meter ME96NSR Catalog
7/32
No lower limit alarm on 0A, 0V.
Monitoring of Upper/Lower Limit
Even during a setup of a facility, where no current/voltage input is found, analog output, pulse output, contact output, and communication data isreplied. This allows for checkup of wiring and monitoring program system.
Current
Time
Upper LimitValue
Lower LimitValue
MotorStrikingCurrent
Alarm DelayTime
Alarm DelayTime
Maximum Value Update
Minimum Value Update
AlarmGeneration
Monitoring of Upper/Lower Limit (Max. 4 points)There is an output of upper/lower limit alarm when plug-in optional module ME-4201-NS96 is mounted.(Since contact output is 1 point, it becomes OR output set in upper/lower limit alarm item)
Test Function
Setting of Alarm Output DelayTime of alarm output after the maximum value and minimum value is reached can be set.With this function, alarm output caused by frequency change at start-up current of a motor and start-up of private power generating facility can beavoided.Furthermore, maximum value and minimum value do not update during alarm delay.
Alarm occurrence status can be checked by current status display and maximum/minimum value display. Upper/Lower Limit Alarm Display by LCD
No alarm output andmaximum/minimumvalue update duringalarm delay time.
5
-
8/13/2019 Power Meter ME96NSR Catalog
8/32
Functions of Buttons
Settings
LEAD statusLAG statusScale of the bar graphOutside rangeAlarm indicatorBar graph status
Phase statusUnitMetering statusHarmonicsCommunication statusAlarm statusTest statusSetup statusDigital
They show direction of Power Factor or Reactive Power on bar graph.They show the type of counting of Reactive Energy on Reactive Energy Display.They show the scales of the bar graph.Measurement value is outside range of scale of the bar graph.It shows the setting value of the upper limit or lower limit.They show the item expressed with the bar graph.
They show the phase for each of the digital displays.They show the unit for each of the digital displays.When it is blinking, the instrument is counting active energy.It means that the digital displays are harmonics values.It shows that the instrument is equipped with a communication function.They show that the upper limit value or lower limit value was exceeded.It shows that the output of the option module is tested.It appears at Set-up mode.The measured value is displayed in a digital number.
123456
789
101112131415
snoitcnuFButtonssnoitcnuF OperationsSpecial functionsBasic functions
Buttons
SET
orMAX/MINPHASE
DISPLAY
Set up setting items such as primary voltage or primary
current, and choose and indicate setting items.Change settings and bar graph display.Change display from Max/Min to instantaneous value.Change phases.Change display.
Press for 2 sec.
Press for 2 sec.Press for 2 sec.Press for 2 sec.Press for 1 sec.
DISPLAY
PHASE&
& RESETor
Manual display change Cyclic display change
Manual phase change Cyclic phase changeZoom display of Wh, varh values (last 3 digits)Reset all the Max/Min values.Fast forward or fast return values when setting.Reset Wh, varh values to zero by holding down the buttons for 2 sec.SET & RESET & PHASE
For correct measurement, it is necessary to set the primary voltage and the primary current, etc. in the Set-up mode. It can set necessary items,after it shifts from the Operation mode to Set-up mode. Items not set are on the initial setting. In case of regular use, it can be used by setting onlythe Set-up menu 1(basic set-up).In case of using the communication function, set Set-up menu 2. Refer to the next page or later for the set-up items.
Note: The above display is an example for explanation.
Set-up Diagram
Press SET and RESET simultaneously for 2 seconds to get in theSet-up mode.
Select a Set-up menu number by or . Change the contents in each Set-up menu. (Refer to pages 7-14.)
After completion of set-up, select End in the Set-up menu and press.
When the End display appears, press once again.+ SET
SET
Shift from the operation mode tothe set-up mode.
Press them simultaneouslyfor 2 seconds.
Press themsimultaneously for 1second.Press themsimultaneously for 1second.
Shift from the operation mode tothe set value confirmation mode.Select the menu number to set orEnd.Get into each setting screen. Shiftto the next setting item.Go back to the previous settingitem.
Memorize the setting contents, andgo back to the operation mode.
Skip remaining setting itemsduring setting.Shift from the set-up mode tosimplified set-up menu.
Change the page of the simplifiedset-up menu.
Phasewire
Displaypattern
Using VT/ direct input
Direct
voltage
Secondaryvoltage
Primaryvoltage
Secondarycurrent
Primarycurrent
Time constantfor currentdemand
Phasewire
Displaypattern
Using VT/ direct input
Direct
voltage
Secondaryvoltage
Primaryvoltage
Primarycurrent
Time constantfor currentdemand
CC-Link stationnumber
Communicationmethod
ModBusaddress
ModBusbaud rates
ModBusparity
ModBusstop bit
CC-Link baud rates
Communicationmodule reset
Expandedcounting
Harmonics
Digitalinput/output
Back light
ON/OFF
Currentdisplay
digit
Voltagedisplay
digit
Activepower
display digit
Reactivepower
display digit
Apparentpower
display digit
Communicationmethod
ModBusaddress
ModBusbaud rates
ModBus
parity
ModBusstop bit
CC-Link baud rates
Communicationmodule reset
Digital inputreset
Currentmaximum
scale
Active powermaximum
scale
Reactive powermaximum
scale
Power
factor scale
Analogoutput 1
Analogoutput 2
Analogoutput 3
Analogoutput 4
Analogoutput limit
Alarmitem
Alarmvalue
Alarmdelay time
Operation mode
Measurement display
Action
Select a set value.
Shift to the End screen.
Select CANCEL.
Cancel the setting.
Display the type of option unit.
Initializing of instrument
Key operation
Press it for 2 seconds.
Press it several times.
Press it.
Press it.
Press it several times.
Press it.
Press it.
Press it.
Press it.
Press it for 1 second.
Press it.
or
or
or
Omittedin figure
Arrow infigure
+
+
+
Set-up mode or set value confirmation mode
Set-up menu End
End displayType of optiondisplay
P-1
P-2
CANCEL display
Example ofset-up mode
Set-up menu 1 Set-up menu 2 Set-up menu 3 Set-up menu 4
Analogoutput 1 Adj.
Analogoutput 2 Adj.
Analogoutput 3 Adj.
Analog
output 4 Adj.
Pulseoutput 1
Pulsewidth
Set-up menu 5 Set-up menu 6 Set-up menu 8Set-up menu 7
S i m p
l i f i e d s e
t - u p m e n u
blink extinction
Pulseoutput 2
CC-Link stationnumber
Alarmcancelmethod
+
+
SET
SET
SET
SET
SET
SET
SET
RESET
PHASE DISPLAY
DISPLAY
PHASE
PHASE
MAX/MIN
+
InitializingprocessShift
automatically
(Example)
Example of set valueconfirmation mode
14
1 2
13 12 11 10
9
8
54
3
4
6
7
15
This figure writes all set menus.There is a menu not displayedby the presence of the settingcondition and the option.
CAUTION
1. Make sure to set for Directvoltage, Secondary voltage,Primary voltage, Secondarycurrent, Primary current.
(Or check the set-up contents.)A correct measurement cannotbe done if the set-up contentsare wrong.
2. Set for the other set-up contentswhen it is necessary.When it is not done, it operateswith the initial contents.
Functions of LCD
F unction s
How to access Set-up
6
-
8/13/2019 Power Meter ME96NSR Catalog
9/32
SET RESET
Settings (Continued)
Setting ProcedureDisplay the setting screen with , and setup the items with / .Settings can be registered for each setup menu number. Display the [End] screen and register with .
+ SETSET
Set-up menu
Phase wire
Display pattern
Using VT/direct input
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
SET
DISPLAY SET
DISPLAY SET
Set the set-up menu number to 1.
Set the phase wire system.
Three phase 3-wire (2CT)Three phase 3-wire (3CT)Three phase 4-wire
3P3.2Ct3P3.3Ct3P4
:::
Set the display pattern. (Initial content: P13)
Choose VT or direct input (without VT).
P01P02P03P04P05P06P07P08P09P10P11P12P13P00
A DA V W PF var Hz varhVA Wh HI HV DI DO
Direct voltage
Set-up the rated voltage for scaling of the bar graph. If you set YES on set up No. , this display does not appear.
110V/63.5V173V/100V190V/110V380V/220V
415V/240V440V/254V480V/277V
110V 220V
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
VT secondary voltage
CT secondary current
Set the secondary voltage values of VT.If you set no on set up No. , this display does not appear.
63.5V100V110V115V120V
100V110V220V
+ ,
+ ,
VT primary voltage
CT primary current
Set the secondary current value of CT.
SET DISPLAY
+ ,SET DISPLAY
Time constant forcurrent demand
Set the primary current value of CT. (The initial value is 5A.)DISPLAY SET
5A 1A
Set-up menu
According to the set-up diagram (page 6), save the changedcontents, or continue to the other set-up menu.
Set up the time constant for calculating current demand.
In this set-up menu 1, set-up the basic contents as following for correct measurement .
In the operation mode, press and simultaneously for 2 seconds or more, and the following operation becomes available.The underline shows the initial value.
Set-up Menu 1 (Basic Set-up)
Note: As for detailed display patterns, refer to page 22.: Displayed in display setting: Set by the set-up menu 4 (page 9): Select P00, and set display sequence and display
position (Please refer to the users manual)
DA : current demand, HI: harmonic current, HV: harmonic voltageDI : digital input, DO: digital output (DI/DO: only when option module is installed) VA : Three phase 4-wire only
Displaypattern
WhExportedactive
energy
varhSpecial
YESno
: using VT: direct input
Initial setting Three phase 3-wire : using VT Three phase 4-wire : direct input Three phase 4-wire
(phase to phase(L-L)/phase to neutral(L-N))Three phase 3-wire(phase to phase(L-L))
Three phase 4-wire Three phase 3-wire Set the primary voltage value of VT in the case of using VT.
If you select no on set up No. , this display does not appear.Initial setting Three phase 3-wire : 10000V Three phase 4-wire : 200V
From top digit, select the value of the flickering digit by
The setting digit can be moved to right by SET .The setting digit can be moved to left by D ISPLAY .The number of settable digits are upper 3 digits. Setting isavailable in the range from 60V to 750kV (750000V).
If it is set on range other than 60V to 750kV, error display(E05) appears. At the moment of the error display, pressSET and review the set value, and set it once again.
When SET is pressed at the lowest digit, the setting itemgoes to the next one.
and .+
+
From top digit, select the value of the flickering digit by
The setting digit can be moved to right by SET .The setting digit can be moved to left by D ISPLAY .The number of settable digits are upper 2 digits. Setting isavailable in the range from 5A to 30kA (30000A).
If it is set on range other than 5A to 30kA, error display (E05)appears. At the moment of the errorand review the set value, and set it once again.
display, press SET
When SET is pressed at the lowest digit, the setting itemgoes to the next one.
and .
0 second10 seconds20 seconds30 seconds
40 seconds50 seconds
1 minute2 minutes
3 minutes4 minutes5 minutes6 minutes
7 minutes8 minutes9 minutes10 minutes
15 minutes20 minutes25 minutes30 minutes
Note: Even when the display pattern do not display the current demand, thisscreen appears. If the current demand is not necessary, press SET .
NoteIf the contents in the Set-up Menu 1 are changed, maximum value, minimum value, and demand value of related measurement items will be reset.(However, all of the counting values are not reset.)
7
-
8/13/2019 Power Meter ME96NSR Catalog
10/32
Set-up Menu 2 (Set-up of Communication, Contact Input Reset Procedure)
Note
00.5
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
In the operation mode, press SET and RESET simultaneously for 2 seconds or more, and the following operation becomes available.
Set-up Menu 3 (Bar Graph Set-up)
In the operation mode, press SET and RESET simultaneously for 2 seconds or more, and the following operation becomes available.
1. Accuracy is defined to rated current. Although the maximum scale may display 120% or more of rated current and rated voltage in order to makethe scale easy to read, current input is within 100% of rated current.
2. When the display pattern that does not display power, reactive power, active energy, and reactive energy is selected, the setting item related tothem is skipped.
Set-up menu
Communication method
ModBus address
ModBus baud rates
ModBus parity
ModBus stop bit
Set-up menu
Set-up menu
Current maximum scale
Active power maximum scale
Active power scale
Reactive power maximum scale
Power factor scale
CC-Link station number
Set the set-up menu number to 2.
CC485
::
2400 bps4800 bps9600 bps19.2 kbps38.4 kbps
+ ,
+ ,
+ ,
Settable parity : nonoddEVEn
+ ,
+ ,
+ , CC-LinkModBus
CC-Link baud rates
Communication module reset
Digital input reset
Set-up menu
onoFF
0 : 156k1 : 625k2 : 2.5M3 : 5M4 : 10M
+ ,
+ ,
+ ,
+ ,
+ ,
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
SET
DISPLAY SET
DISPLAY SET
SET
DISPLAY SET
DISPLAY SET
Settings (Continued)
F unction s
Set the CC-Link or ModBus as thecommunication method.This display appears only if the type ME96NSR-MBhas the type ME-0040C-NS96 option module.
Set the ModBus address number.
Set the set-up menu number to 3.
Set the current maximum scale.The maximum scale is set in the range of about 40%to about 120% of the rated current.
Set the single / double deflection of active power.
Set the power factor scale.
Set the maximum scale of active power.The maximum scale is set in the range of about 40%to about 120% of the rated full load power.
Set the reactive power maximum scale.
According to the set-up diagram (page 6), save thechanged contents or continue to the other set-up menu.
In case of CC-Link, this display does not appear.
Settable addresses: 1 to 255 Set the ModBus baud rate.In case of CC-Link, this display does not appear.
Settable baud rate:
Set the ModBus parity.
In case of CC-Link, this display does not appear.
Set the ModBus stop bit.In case of CC-Link, this display does not appear.
Stop bit : 1Stop bit : 2
Set the CC-Link station number.
In case of ModBus, this display does not apper.
Settable addresses: 1 to 64 Set the CC-Link baud rates.
In case of ModBus, this display does not apper.
Settable baud rates:
Reset of communication module.In case of ModBus, this display does not apper.
Set it ON.
Note: When it is not set on ON, changed stationnumber and baud rate do not become valid. Set the digital input(DI) reset method.
Without digital input, this display does not apper.
HoLd: Manual methodAuto: Automatic method
Note: When selected the manual method(HoLd), input state is kept until thecancel operation is done manually. For the method of the cancel operation,refer to page 21.
Note: This insturuments rating is 100% value.
For the maximum scale value, please refer tothe users manual.
Note: This insturuments rating is 100% value. For the maximum scale value, please refer to
the users manual.
According to the set-up diagram (page 6), save thechanged contents or continue to the other set-up menu.
When + and are pressed, the scale value ofbar graph flickers at single / double deflection.
The setting method is same as that of maximum scale value of activepower.
8
-
8/13/2019 Power Meter ME96NSR Catalog
11/32
-
8/13/2019 Power Meter ME96NSR Catalog
12/32
F unction s
Set the alarm item to be allowed to measurement items.
+ ,
+ ,
+ ,
DISPLAY SET
DISPLAY SET
DISPLAY SET
SET
DISPLAY SET
DISPLAY SET
+ ,
+ ,
+ ,Set-up menu
Alarm cancelmethod
Set the alarm cancel method at generation of alarm. (screen, relay)
Set the alarm delay time.
Set the upper and lower limit alarm item 2 to 4 (AL2, AL3, AL4) in the same method.+ ,
Set-up menu
Alarm item 1
Alarm value 1
Alarm item 2 to 4
Alarm delay time, delay time of max/min value
Set the set-up menu number to 5.
Alarm itemA, DA, AN, DAN upper limit
A,DA lower limit
V upper limit
V lower limit
W, var upper limit
W, var lower limit
PF upper limit
PF lower limit
Hz upper limit
Hz lower limit
Set-up range5 to 100 to 120%
3 to 10 to 95%
25 to 110 to 135%
20 to 70 to 95%
95 to 100 to 120%
120 to 3 to 95%
0.05 to 1 to 0.05
0.05 to 0.5 to 0.05
45 to 65Hz
45 to 65Hz
5 to 35 to 120%
0.5 to 3.5 to 20%
Step1%
1%
1%
1%
1%
1%
0.05
0.05
1Hz
1Hz
1%
0.5%
Harmonic current total RMS value upper limit
Harmonic voltage total distortion ratio upper limit
Set the alarm value of alarm item 1.The set-up range is shown below.
Example display when Aupper limit is set to 100%
Note 1: The upper and lower limit alarm mark by the bar graph is displayed in the step of about 5%though the digital value can be set in the above-mentioned step on A, DA, V, W and var.However, the alarm is generated with the accuracy of the digital value. DA: current demand
Note 2: V alarm value is set according to the value of primary voltage (direct voltage).A, DA, W, and var is set for value of rated scale.
Note 1: A measurement item that is not selected in the display pattern can be selected.Note 2: The alarm of W, var, and PF is judged from the total RMS value.
The upper alarm of A and DA is judged from the phase of 1, 2, 3 and N.The lower alarm of A and DA is judged from the phase of 1, 2 and 3. (N is excluded.)
Note 3: The alarm of the total distortion ratio is judged from the phase of 1, 2 and 3.(N is excluded.)
nonA upper limitA lower limit
Demand A upper limitDemand A lower limit
V(L-L) upper limitV(L-L) lower limit
W upper limitW lower limit
var upper limitvar lower limitPF upper limitPF lower limitHz upper limitHz lower limit
Harmonic current totalRMS value
Harmonic voltage totaldistortion ratio
nonA upper limitA lower limit
AN upper limitDemand A upper limitDemand A lower limit
Demand A N upper limitV(L-N) upper limitV(L-N) lower limitV(L-L) upper limitV(L-L) lower limit
W upper limitW lower limit
var upper limitvar lower limit
PF upper limitPF lower limitHz upper limitHz lower limit
Harmonic current total RMS valueHarmonic current phase N RMS valueHarmonic voltage total distortion ratio
Three phase 3-wire Three phase 4-wire
Display of non upperand lower limit alarm
Display when A upper limit is setto upper and lower limit alarm
If the condition of limit exceeding continues f or more than the delay time,the alarm generates.And if it does not continue during this time, the maximum/minimum valueis not updated.
0 seconds5 seconds
10 seconds20 seconds
30 seconds40 seconds50 seconds
1 minute
2 minutes3 minutes4 minutes5 minutes
Display of automaticreset method
Display of manual reset
method
Method
Automatic(Auto)
Manual(HoLd)
Cancel method
When there is no alarm generating condition,
alarm is automatically reset.
Please refer to page 19 for details.
Alarm is reset by pressing RESET .Alarm continues until RESET is pressed.
According to the set-up diagram (page 6), save the changed contents or continue to the other set-up menu.
Set-up Menu 5 (Alarm Set-up)
SET RESET
This sets the upper and lower limit alarm. The upper and lower limit set value mark (blinking) is displayed on the bar graph. From the display items,four items can be set.In the operation mode, press and simultaneously for 2 seconds or more, and the following operation becomes available.
Settings (Continued)
to
Refer to page 19 for details.
10
-
8/13/2019 Power Meter ME96NSR Catalog
13/32
-
8/13/2019 Power Meter ME96NSR Catalog
14/32
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
No.
Content No. Content
Simplified setting page: P-1
No. Content No. Content
Simplified setting page: P-2
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
SET
DISPLAY SET
DISPLAY SET
SET
DISPLAY SET
F unction s Set-up Menu 7 (Pulse Output Set-up)
SET RESETIn the operation mode, press and simultaneously for 2 seconds or more, and the following operation becomes available.When the ME-4201-NS96 optional plug-in module is not installed, this menu cannot be set.
Set-up Menu 8 (Analog Output Adjustment)
Set-up menu
Set-up menu
Pulse width
Pulse output item 1 pulse value
Pulse output item 2
Pulse output item 1
Pulse output item 2 pulse value
Set the set-up menu number to 7.
According to the set-up diagram (page 6), save thechanged contents or continue to the other set-up menu.
At initial setting, imported active energy is set to pulseoutput 1, press SET to go to the next setting.
Set the output element to pulse output 1.
Settable elementsExample of pulse output 1
Example of pulse output 2
Example of pulse output 1
Total load [kW] =1000
(Primary voltage) (Primary current)
Set the pulse value of pulse output 1.Pulse value is selected from the table below, according to total load [kW].
= 3 (Three-phase 4-wire)= 3 (Three-phase 3-wire)
In case of reactive energy, kW in the above tableis exchanged into kvar and kWh into kvarh.
Primary voltage value is calculated by phase t o newtral.
Pulse output 2 is set in the same method as pulse output item 1 set-up. (At initial setting, imported lag reactive energy is set to pulse output 2.)
Set the output element to pulse output 2.
Pulse output 2 is set in the same method as pulse output item 1 set-up.
Set the pulse value of pulse output 2.
0.125s 0.500s 1.000s
Note: When the pulse width is set to 0.500s, 1.000s, and pulse unitis set to lowest settable unit, pulse output cannot follow, and thecounting pulse may decrease when load is large.
Set the pulse width of output pulse.
When the ME-4201-NS96 optional plug-in module is installed, zero adjustment and span adjustment of analog output is possible.(Only for circuits set on analog output)Please adjust it only when the matches with the receiving instrument or the output have changed.In the operation mode, press and simultaneously for 2 seconds or more, and the following operation becomes available.SET RESET
Phase wire
Display pattern
Using VT/direct input
Direct voltage
VT secondary voltage
VT primary voltage
CT primary current
Time constant for current demand
Communication method
ModBus address
ModBus baud rates
ModBus parity
ModBus stop bit
CC-Link station number
CC-Link baud rates
Communication module reset
Set-up menu
Set-up menu
Span Adj. for CH1
Zero Adj. for CH1
CH2, CH3 and CH4can be adjusted thesame as above.
Simplified Set-upThe setting contents of the main 16 items can be set by using two displays. It can be set by the method of substituting numerical value.For the setting contents, refer to the following table.
20mA
4
Zero adjustment
mA
INPUT INPUT INPUT
20mA
4
Span adjustment
mASingle deflection
0
mADouble deflection
0
Set the set-up menu number to 8.
50 steps can be set. (about 0.3mA )
Set the zero adjustment for CH1.
50 steps can be set. (about 0.3mA )
Set the span adjustment for CH1.
According to the set-up diagram (page 6), save thechanged contents, or continue to the other set-up menu.
Settings (Continued)
Pulse output elementImported active energy (Pulse output 1)Exported active energyImported lag reactive energy (Pulse output 2)Imported lead reactive energyExported lag reactive energyExported lead reactive energyNo output
Display Wh
Wh varh (LAG) varh (LEAD)
varh (LAG) varh (LEAD) non
Digital display Settable pulse value [kW/pulse]18888.88
88888.88888888888.8888888.8888888
10100
110
100
0.11
100.11
10
0.010.11
0.010.11
0.0010.010.1
0.0010.010.1
kWh/PulsekWh/PulsekWh/PulseMWh/PulseMWh/PulseMWh/Pulse
Total load [kW]1 or higher and below 10
10 or higher and below 100100 or higher and below 1000
1000 or higher and below 1000010000 or higher and below 100000
100000 or higher
12
-
8/13/2019 Power Meter ME96NSR Catalog
15/32
4:115V5:120V
1:100V2:110V3:220V
VT primary current
[Exponent value]
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
DISPLAY
DISPLAYDISPLAY
PHASE
SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
Phase wire1:3P3W (2CT)2:3P3W (3CT)3:3P4W
Display pattern Using VT Direct voltage00:P00 11:P1101:P01 12:P1202:P02 13:P1303:P0304:P0405:P0506:P0607:P0708:P0809:P0910:P10
Simplified Set-up Contents List
/direct input0:direct input1:using VT
[3P4W]1:110V/63.5V2:173V/100V3:190V/110V4:380V/220V5:415V/240V6:440V/254V7:480V/277V[3P3W]1:110V2:220V
[3P4W]1:63.5V2:100V3:110V
[3P3W]
VT secondary voltage
Phase wire
Display pattern
Direct voltage
Using VT /direct input
Set-up menu
VT secondary voltage
VT primary voltage
For 1 secend or more+
Set the set-up menu number to End.Press PHASE and DISPLAY simultaneously for 1 secondor more.
Set the phase wire.
1 : 3P3W 2CT 2 : 3P3W 3CT
3 : 3P4W
00 : P00 to
13 : P13
Set the display pattern.
0 : direct input.1 : using VT
Set using VT or direct input (without VT).
[3P3W]1 : 110V2 : 220V
[3P4W]
Set the rated voltage scaling for the bar graph.If you set 1: using VT on set up No. , this contentcannot be set.
Set the secondary voltage values of VT.
cannot be set.If you set 0: direct input on set up No. , this content
[3P3W]1 : 100V2 : 110V3 : 220V
[3P4W]1 : 63.5V2 : 100V3 : 110V
4 : 115V5 : 120V Set the primary voltage values of VT.
If you set 0: direct input on set up No. , this contentcannot be setIt is set by the top 3 digits voltage values and the exponentvalues (10 to the n-th power).The set-up order is the exponent values and the voltage values.
Exponent values: 0 (10 0 = 1 time)1 (10 1 = 10 times)2 (10 2 = 100 times)3 (10 3 = 1000 times)
Voltage values: the top 3 digits (0 to 9)Example: Set-up to 10000V
Exponent values: 2Voltage values: 100
Simplified Set-upSET RESET
PHASEIn the operation mode, press and simultaneously for 2 seconds or more, and the following operation becomes available.By pressing in the simplified set-up mode, the simplified setting page is changed.
Time constantfor currentdemand
00:0s 10:5min01:10s 11:6min02:20s 12:7min03:30s 13:8min04:40s 14:9min05:50s 15:10min06:1min 16:15min07:2min 17:20min08:3min 18:25min09:4min 19:30min
CT primary current
[Exponent value]0:5.0 to 9.9A1:10 to 99A2:100 to 990A3:1000 to 9900A4:10000 to 30000A
[Current value](10 digits) (1 digit) 0 to 9 0 to 9
Communicationmethod
1:CC-Link 2:ModBus
ModBusbaud rates
1:2400bps2:4800bps3:9600bps4:19.2kbps5:38.4kbps
ModBusaddress
001 to 255
ModBus parity0:non1:odd2:EVEn
ModBusstop bit
1:12:2
CC-Link station number
01 to 64
Communicationmodule reset
0:OFF1:ON
CC-Link Baud rates
1:156kbps2:625kbps3:2.5Mbps4:5Mbps5:10Mbps
0:60 to 999V1:1000 to 9990V2:10000 to 99900V3:100000 to 750000V
[Voltage value](100 digits) (10 digits) (1 digit) 0 to 9 0 to 9 0 to 9
1 : 100/63.5V2 : 173/100V3 : 190/110V4 : 380/220V
5 : 415/240V6 : 440/254V7 : 480/277V
13
-
8/13/2019 Power Meter ME96NSR Catalog
16/32
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,00: 0s01: 10s02: 20s03: 30s04: 40s
05: 50s06: 1min07: 2min08: 3min09: 4min
10: 5min11: 6min12: 7min13: 8min14: 9min
15: 10min16: 15min17: 20min18: 25min19: 30min
(Page change ofset-up display)
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
PHASE
MAX/MIN
SET
F unction s
Time constant forcurrent demand
CT primary current
Set the primary current values of CT.It is set by the top 2 digits current values and the exponentvalues (10 to the (n-1)th power).The set-up order is the exponent values and the current values.
Exponent values : 0 (10 -1 = 0.1 time)1 (10 0 = 1 time)2 (10 1 = 10 times)
3 (102
= 100 times)4 (10 3 = 1000 times)
Current values:the top 2 digits(0 to 9)
Example: Set-up to 50A
Exponent values: 1 Current values: 50 Set the time constant for calculating current demand.
Communicationmethod
ModBus address
ModBus parity
ModBus stop bit
CC-Linkstation number
CC-Link baud lates
ModBus baud rates
Set-up menu
Communicationmodule reset
0: OFF1: ON
Set the communication module reset.In case of ModBus, this content cannot be set.
Set it ON.
According to the set-up diagram (page 6), save the changed contents,or continue to the other set-up menu.
Set the CC-Link baud rate.In case of ModBus, this content cannot be set.
1: 156kbps2: 625kbps3: 2.5Mbps
4: 5Mbps5: 10Mbps
Set the ModBus stop bit.In case of CC-Link, this content cannot be set.
1: 12: 2
Set the ModBus baud rate.In case of CC-Link, this content cannot be set.
1: 2400bps2: 4800bps3: 9600bps
4: 19.2kbps5: 38.4kbps
Set the communication method.This is set only if the type of ME96NSR-MB has theCC-Link optional plug-in module. In case of theother combination, this content cannot be set.1: CC-Link2: ModBus Set the ModBus address number.
In case of CC-Link, this content cannot be set.
Address: 001 to 255
Set the ModBus parity.In case of CC-Link, this content cannot be set.
0: non1: odd2: even
Set the CC-Link station number.In case of ModBus, this content cannot be set.
Address: 01 to 64
It is possible to display the type of the optional plug-in module when the optional plug-in module is mounted.In the operation mode, after pressing and simultaneously for 2 seconds or more, the following operation becomes available.
Display of the Type of Optional Plug-in Module
SET RESET
Set-up menu
Set-up menu
1 secend or more+
Display the type of theoptional plug-in module
Set the set-up menu number to End.
According to the set-up diagram (page 6), end the display of the type ofoptional plug-in module or continue to the other set-up menu.
Displays the type of the optional plug-in module.
non : No optional plug-in module4201 : ME-4201-NS960052 : ME-0052-NS960040C: ME-0040C-NS96
Settings (Continued)
Note Even in the set value confirmation mode, the type of the optional plug-in module can be displayed. The procedure is the same as the above-mentioned.
14
-
8/13/2019 Power Meter ME96NSR Catalog
17/32
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
SET
SET
SET
SET
SET
SET
SET
Set the test menu number to 1.
Test the alarm output.When , is pressed, the display and the contact output are changed as follows.+
When , is pressed, the display and the analog output CH1 are changed as follows.+
oFF(Opened)
on(Closed)
To test the other outputs, continue the test according to the procedures in page 15 to page 16.When the test is finished, turn off the power supply.
When the ME-4201-NS96 optional plug-in module is installed, simulated signal output to test the alarm output circuit can be put out. Alarm Output Test
The following operation becomes possible when you turn on the power supply while pressing at the state of power failure.It is not possible to test without the optional plug-in module.
Test menu
Test menu
Alarm output test
at the state of power failure.
When the ME-4201-NS96 optional plug-in module is installed, simulated signal output to test the analog output circuit can be put out. Analog Output Test
The following operation becomes possible when you turn on the power supply while pressingIt is not possible to test without the optional plug-in module.
Test menu
Test menu
Analog outputCH1 test
Analog outputCH2 test
Analog outputCH3 test
Analog outputCH4 test
Set the test menu number to 2.
Test the analog output CH1.
50% output 100% output0% output
Test the analog output CH2.When , is pressed, the display and the analog output CH2 are changed as follows.+
50% output 100% output0% output
Test the analog output CH3.When , is pressed, the display and the analog output CH3 are changed as follows.+
50% output 100% output0% output
Test the analog output CH4.When , is pressed, the display and the analog output CH4 are changed as follows.+
50% output 100% output0% output
To test the other outputs, continue the test according to the procedures in page 15 to page 16.
When the test is finished, turn off the power supply.
Test Function
DISPLAY
DISPLAY
15
-
8/13/2019 Power Meter ME96NSR Catalog
18/32
F un ctions
Test menu
Test menu
Pulse outputCH1 test
Pulse outputCH2 test
Test menu
Test menu
Digital outputCH1 test
Digital outputCH2 test
Set the test menu number to 3.
Set the test menu number to 4.
When , is pressed, the display and the pulse output are changed as follows.
To test the other outputs, continue the test according to the procedures in page 15 to page 16.When the test is finished, turn off the power supply.
To test the other outputs, continue the test according to the procedures in page 15 to page 16.When the test is finished, turn off the power supply.
The initial value of each CH of this test mode is Open.If CH is changed or this test mode ends, the output becomes Open.
+
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
+ ,
When the ME-4201-NS96 optional plug-in module is installed, simulated signal output to test the pulse output circuit can be put out.
The following operation becomes possible when you turn on the power supply while pressing at the state of power failure.It is not possible to test without the optional plug-in module.
Pulse Output Test
SET
SET
SET
SET
SET
SET
Digital Output Test
Note
DISPLAY
When the ME-0052-NS96 optional plug-in module is installed, simulated signal output to test the digital output circuit can be put out.
The following operation becomes possible when you turn on the power supply while pressing at the state of power failure.It is not possible to test without the optional plug-in module.
DISPLAY
oFF(Opened)
on(Closed)
When , is pressed, the display and the pulse output are changed as follows.+
oFF(Opened)
on(Closed)
When , is pressed, the display and the contact output are changed as follows.+
oFF(Opened)
on(Closed)
When , is pressed, the display and the contact output are changed as follows.+
oFF(Opened)
on(Closed)
Test the digital output CH1.
Test the digital output CH1.
Test the pulse output CH1.
Test the pulse output CH2.
Test Function (Continued)
16
-
8/13/2019 Power Meter ME96NSR Catalog
19/32
DISPLAY DISPLAY DISPLAY DISPLAY
First display
Current average valuePower (total)Voltage average value
Example of display of upperstage element on bar graph
Example of display ofpower factor on bar graph
Current phase 1Power (total)Voltage phase 1-2
Current phase 2Power (total)Voltage phase 2-3
Current phase 3Power (total)Voltage phase 3-1
Second display Third display Fourth display Display number
This shows that second display ofthe four displays is being displayed.
Note 2: Even in the maximum and minimum value display, when the DISPLAY is pressed, the display will switch over.
Note 1: When the display is changed by pressing DISPLAY ,the following display is displayed just for a few seconds.
Note: When PHASE is pressed, the phase will switch over, even in the maximum and minimum value display.
PHASEPHASEPHASEPHASE
PF var WAAVGV(L-L) AVG Hz
PF var WAAVGV(L-L) AVGV(L-N) AVG Hz
PF var WAAVGV(L-L) AVG Hz
PF var WAAVGV(L-L) AVGV(L-N) AVG Hz
By pressing DISPLAY , the measurement display switches over.
By pressing PHASE , the current phase and the voltage phase switches over.
Measurement item to be displayed on bar graph can be selected. By displaying one item by a bar graph and other three items by digital numbers,four elements can be displayed at once.
In the bar graph, measurement elements shown by or are displayed. As for voltage, current, active power, reactive power, power factor, andfrequency, they can be displayed on the bar graph even if they are not set on display pattern.
Press or to select measurement elements to be displayed on the bar graph.
AVG (or ) of display measuring items
AVG (or ) of displaymeasuring items
Upper Lower Middle
Lower MiddleUpper
Display change example (Display pattern: P01, Phase wire: Three phase 4 wire)
Display Change
+
Operation
Phase Change
Bar Graph Display
Display change example (Phase wire: Three phase 3 wire)
The display element in the bar graph changes as follows by the display pattern that has been selected.(i) When digital tri-level display are the same items
[Three-phase 3 wire ]
[Three-phase 4 wire ]
(ii) When the measuring items are all different[Three-phase 3 wire ]
[Three-phase 4 wire ]
Explanation of Bar Graph
Selection of Bar Graph
Reference Display items and sequences vary with display patterns (P01 to P13) and additional display. For detailed display pattern, refer to page 22.
17
-
8/13/2019 Power Meter ME96NSR Catalog
20/32
F un ctions
Display change example (Display pattern : P01)
Update of Delay Time
Cyclic Display
Phase Cyclic Display
When MAX/MIN is pressed, the display changes into maximum value and minimum value display. And when MAX/MIN is pressed, the displaychanges back to the present value display.
When RESET is pressed for 2 seconds or more, the displayed maximum value and minimum value can be reset.(The maximum/minimum value and the present value become the same.)
Reset of Maximum Value and Minimum Value
When RESET and are pressed simultaneously for 2 seconds or more, all the maximum values and minimum values are reset.
If maximum/minimum values do not continue for a long time since delay time, it is not updated. (Delay time is set by set-up menu 5.)Please set the delay time when you do not want to make the maximum value updated in the condition of excessive value in short time such asstarting currents of the motor.
In cyclic display, display and phases automatically change every 5 seconds.
When DISPLAY is pressed for 2 seconds, the cyclic display screen appears.Cyclic display is possible even on the maximum value and minimum value display.
When PHASE is pressed for 2 seconds, the phase cyclic display screen appears.Phase cyclic display is possible even on the maximum value and minimum value display.
Note 1: Before shifting to the cyclic display screen, the display blinks 3times.Note 2: By pressing any key other than the SET , it goes back to manual
display change.Note 3: In the cyclic display, display number is not displayed.
Note 1: Before shifting t o the cyclic display screen, the display blinks 3times.
Note 2: By pressing any key other than the SET , it goes back to manualdisplay change.
Display of maximum value and minimum value
Note 1: In the maximum value and minimum value display, bar graph is lit only between the maximum value and the minimum value.Note 2: When the screen shifts to the maximum value and minimum value display, the following are displayed in the order below. A AN DA DAN V W var VA PF Hz HI HI N HV However, item that are not set for display are not displayed.Note 3: For harmonics, only the following maximum values are displayed. Harmonic current total effective value, 1st, 3rd, 5th, 7th, 9th, 11th, 13th current effective values Harmonic voltage total distortion ratio, 1st voltage effective value, 3rd, 5th, 7th, 9th, 11th, 13th containing ratio
Note 1: The maximum values and minimum values n ot displayed are not reset.Note 2: All degrees are reset for harmonics.
Note 1: When delay time is set, the value whose value of middle stage is larger than the maximum value might be displayed until delay time passes.Note 2: The demand current, harmonics current, and harmonics voltage are not delayed, so the current and voltage may display larger value than the present value.
Cyclic Display
The maximum values and the minimum values can be displayed. Maximum Value and Minimum Value Display
+
MAX/MIN MAX/MIN
RESET
Press for 2 seconds.
DISPLAY
Display for 5 seconds Display for 5 seconds Display for 5 seconds Display for 5 seconds
Press for 2 seconds.
PHASE
Maximum value andminimum value display
Present value display
Operation (Continued)
Display for 5 seconds Display for 5 seconds Display for 5 seconds Display for 5 seconds
18
-
8/13/2019 Power Meter ME96NSR Catalog
21/32
Note 1: In alarm condition, the digital value, the unit (A, V, W, var, VA, PF, Hz), and the phase (1, 2, 3, N, AVG, , DM) of the measurement items blink. There is no blinking when the item is not on the display.Note 2: In alarm hold condition, the unit (A, V, W, var, VA, PF, Hz) and the phase (1, 2, 3, N, AVG, , DM) of the measurement items blink. There is no blinking when the element is not on the display.Note 3: Only the present value (middle digital display) blinks on maximum and minimum value screen.
Note 4: In harmonics, only total distortion ratio and RMS value blink. The display of degree does not blink.
Note: In contact input screen, alarm reset (including all items batch reset) cannot be operated.
Set-up
If the item that had alarm set-up is displayed on the bar graph, the alarm indicator appears.By blinking of , upper or lower limit is shown.
Alarm Indicator
Refer to set-up menu 5. (see page 10)
Behavior During Alarm GenerationAlarm condition: When measurement value exceeds alarm value, display blinks and alarm contact closes.Alarm cancel: When alarm is canceled, display blinks normally and alarm contact opens.
Alarm Cancel MethodTiming of alarm cancel differs by alarm cancel method.
When alarm delay time is set, alarm is not generated until status of measurement value exceeding upper/lower setting value continues for delay time.
Alarm Delay
Generation and Cancel of Upper/Lower Limit Alarm
Phase that judge upper/lower limit alarm differs by measuring items. Please refer to the following table.
When the value exceeds the upper or lower limit setting value set in advance, the display blinks and alarm can be output.(No alarm output when all of the input voltage/input current is zero)
After the measurement value falls below the upper value or exceeds the lower setting value, alarm is maintained. When the item thatgenerates the alarm is displayed, and button is pressed, the alarm resets.When button is pressed for two seconds or more, all items of alarm are reset.
Alarm Cancel MethodMeasurement value > Upper limit value(or Measurement value < Lower limit value)
Measurement value < Upper limit value(or Measurement value > Lower limit value)
Normal display
Normal display
ClosedAlarm contact
Alarm contact
Display
Display
Automatic(Auto)
Manual(HoLd)
Closed Closed
(Alarm retention)
Opened
Opened
ALARM , HI or LO : blink
ALARM , HI or LO : blink ALARM , HI or LO : appear
Automatic(Auto)
Manual(HoLd)
When the measurement value falls below the upper setting value or exceeds the lower setting value, alarm automatically resets.
A upper limitA lower limit
AN upper limit (*2)Demand A upper limitDemand A lower limit
Demand A N upper limit (*2)V(L-N) upper limitV(L-N) lower limitV(L-L) upper limitV(L-L) lower limit
W upper limitW lower limit
var upper limitvar lower limitPF upper limitPF lower limitHz upper limit
Hz lower limitHarmonic currenttotal RMS value
Harmonic currentphase N RMS value (*2)
Harmonic voltagetotal distortion ratio
Alarm item (*1)3P3W/3P4W3P3W/3P4W
3P4W3P3W/3P4W3P3W/3P4W
3P4W3P4W3P4W
3P3W/3P4W3P3W/3P4W3P3W/3P4W3P3W/3P4W3P3W/3P4W3P3W/3P4W3P3W/3P4W3P3W/3P4W3P3W/3P4W
3P3W/3P4W3P3W3P4W
3P4W
3P3W3P4W
PhasesPhase 2 Phase 3 Phase N Phase 1-2 Phase 2-3 Phase 3-1 AVG/
*1: The apparent power is not included in the alarm element.*2: Phase N is a alarm element to be independent.
Phase wire Phase 1
RESETRESET
RESET
19
-
8/13/2019 Power Meter ME96NSR Catalog
22/32
When and are pressed, harmonic degree changes. When PHASE is pressed, harmonic phase changes.
Measuring Items
Degree Change Method
Harmonic Display Examples
RMSvalue
Distortionratio
Note: When a fundamental harmonic is 0, the distortion ratio display 0%.
Harmonics DisplayHarmonic RMS value, distortion ratio, and content rate can be displayed.
F un ctions
Note: Harmonic total is shown by ALL.
* When used as 3P3W, transition is only for 1-2 phase, 2-3 phase.
Operation (Continued)
+
Example of harmoniccurrent total display
Example of harmonicvoltage 5th display( ) ( )
DegreeCurrent ( other than phase N)
Harmonic total1st3rd5th7th9th
11th13th
RMSvalue
Distortionratio
Current (phase N)RMSvalue
Distortionratio
VoltageRMSvalue
Distortionratio
Harmonic current(phase N)
+ ,
+ ,
+ ,
DISPLAY
+ ,
+ ,
DISPLAY
PHASEPHASE
PHASE
PHASEPHASE
PHASE
+ ,
PHASEPHASE
PHASE
PHASE PHASE
PHASE
DISPLAY
+ ,
+ ,
PHASEPHASE
PHASE
PHASEPHASE
PHASE
+ ,
PHASEPHASE
PHASE
PHASEPHASE
PHASE
DISPLAY
Current total phase 3 Distortion ratio/RMS
Current 1st phase 3 RMS
Current totalphase N RMS
Current 1stphase N RMS
Current 3rdphase N RMS
Current 13thphase N RMS
Current 13th phase 3 Distortion ratio/RMS
Current 3rd phase 3 Distortion ratio/RMS
Voltage total phase 3-N Distortion ratio/RMS
Voltage 1st phase 3-N RMS
Voltage 3rd phase 3-N Distortion ratio/RMS
Voltage 13th phase 3-N Distortion ratio/RMS
Harmonic current
Harmonic voltage
Previousdisplay
Nextdisplay
Current total phase 2 Distortion ratio/RMS
Current total phase 1 Distortion ratio/RMS
Current 1st phase 2 RMS
Current 1st phase 1 RMS
Current 3rd phase 2 Distortion ratio/RMS
Current 3rd phase 1 Distortion ratio/RMS
Current 13th phase 2 Distortion ratio/RMS
Current 13th phase 1 Distortion ratio/RMS
Voltage total phase 2-N Distortion ratio/RMS
Voltage total phase 1-N Distortion ratio/RMS
Voltage 1st phase 2-N RMS
Voltage 1st phase 1-N RMS
Voltage 3rd phase 2-N Distortion ratio/RMS
Voltage 3rd phase 1-N Distortion ratio/RMS
Voltage 13th phase 2-N Distortion ratio/RMS
Voltage 13th phase 1-N Distortion ratio/RMS
20
-
8/13/2019 Power Meter ME96NSR Catalog
23/32
There are Auto reset method and Latch method for digital input reset method.When set on the latch method, the input status is continued until the latch canceling operation.For example, when the alarm contact is input and the alarm is stopped, you cannot miss the alarm because the alarm generated status is continued inthe basic device.
When SET , RESET , and PHASE are pressed simultaneously for 2 seconds, the measured values of active energy (Wh) and reactive energy(varh) are reset. (This is effective only in the present value display.)
As same as in the set-up diagram (page 6), select the set-up menu number to confirm,and press SET .The way to get back into the operation mode is same as in the set-up diagram.However, the simplified set-up menu canot be confirmed in the setting value confirmationmode.
In the operation mode, press SET for 2 seconds.
1 In the operation mode, press DISPLAY and digital input (d.in) screen is displayed.2 In the digital input screen, the latch is canceled by pressing RESET for 2 seconds.
Reset Method of Digital Input
Canceling of the Latch
Going into Setting Value Confirmation Mode
Setting Value Confirmation
Note: All of active energy (Wh) and reactive energy (varh) not displayed are also reset.
8888. 88
88888. 8888888
8888. 8888888. 8888888
k
M
1000 = 3 Three-phase 4-wire type
(Primary voltage value: phase to neutral)
(Primary voltage value: phase to phase)3 Three-phase 3-wire type
Enlarged 3 Digital FiguresWhen and are pressed simultaneously for 2 seconds, values of active energy and reactive energy are enlarged by 3 figures.
Active energy and reactive energy are displayed on the lower stage.Display type is shown in the right table according to total load power.
Expanded Counting DisplayMeasured value display and enlarged 3 digital figures display of active energy and reactive energy can be displayed. Display of Active Energy and Reactive Energy Display
Wh and varh Reset
Example of Display
Display of Digital Input and Digital OutputDisplays the digital input and digital output state.When the type ME-0052-NS96 or ME-0040C-NS96 optional plug-in module is not installed, this operation cannot be done. Display of Digital Input and Digital Output
Note: To display digital input screen, it is needed to set display of the digital input/output on on. The initial setting is set on on.
When confirming the setting value, use the setting value confirmation mode.In this mode, the contents of the set-up items cannot be set, which prevents changing other set values by mistake during operation.
Setting Value Confirmation Mode
Total load [kW] =
In the case of reactive power, kW in the right table is exchanged intokvar, and kWh into kvarh.
(Primary voltage value) (Primary current value)
Note: This function is made only on active energy and reactive energy display.Example: When 3 digital figures are enlarged on active energy screen, reactive energy is not enlarged.
In order to enlarge digital figures of reactive energy, display reactive energy on the screen andoperate the same way.
Exported active energy
(Example of d ig ital input disp lay) (Example of d ig ital output disp lay)
Imported lead reactive energy Exported lag reactive energy Exported lead reactive energy
Total load [kW]1 or higher and below 10
10 or higher and below 100100 or higher and below 1000
1000 or higher and below 1000010000 or higher and below 100000
100000 or higher
Digital display Unit (k/M)
,Pressing
simultaneouslyfor 2 seconds
(Set-up mode) (Set value confirmation mode)
+
blink extinction
ItemsQuadrant
Unsigned
Unsigned
LAG Display*Unsigned
A, DA, V, VAHz, HI, HV
W
var, PF
Unsigned
Unsigned
LEAD Display* sign
Unsigned
sign
LAG Display*Unsigned
1 2 3 4
Unsigned
sign
LEAD Display* sign
* When displaying var or PF by bar graph, LEAD/LAG display is lit.
-var
+var
- W +W
Quadrant 2Quadrant 3
Quadrant 1Quadrant 4
The polar display of each measuringitems are as follows.
Polar Display of Each Measuring Items
+
21
-
8/13/2019 Power Meter ME96NSR Catalog
24/32
Display Patten Contents
Operation (Continued)
F un ctionsWhen the display elements are set in the set-up menu 1 and the set-up menu 4, by pressing DISPLAY , the display transits from No.1 in the order shown in the following table.Three phase 4-wire
P01
P02
P03
P04
P05
P06
P07
P08
P09
P10
P11
P12
P13
P00
UpperMiddleLowerUpperMiddleLowerUpperMiddleLowerUpperMiddleLowerUpperMiddleLowerUpperMiddleLowerUpperMiddleLower
UpperMiddleLowerUpperMiddleLowerUpperMiddleLowerUpperMiddleLowerUpperMiddleLowerUpperMiddleLowerUpperMiddleLower
AWVAV
WhA
PFVAV
WhPFWvarA1A2A3AVW
AV
WhA
DAVA
DAVA
DAWh
ADAWh
AWPFAW
WhA
PFWAW
WhHzW
var
AW
Wh
ADAWAV
WhAW
Wh
APFVA
PFWhA
PFvarA
varvarhVAWvarA
V
AV
Wh
A
A
APFVAA
VAWh
A ANA
AN
DAV
Wh
APFHzA
PFWh
A ANA
AN
A ANWV
Wh
A ANA
HzWh
DA
DA NA
ANDA
DA NA
AN
A AN
DA
DA N
DA
DA NV
HzWh
VHz
varh
A AN
NO.1 NO.2 NO.3 NO.4 NO.5NO.6NO.7NO.8 NO.9 Exportedactive energy
Exportedactive energy
Exportedactive energy
Importedlead reactive energy
Exportedlag reactive energy
Exportedlead reactive energy
Exportedactive energy
Importedlead reactive energy
Exportedlag reactive energy
Exportedlead reactive energy
Exportedactive energy
Exportedactive energy
Exportedactive energy
Exportedactive energy
Exportedactive energy
Exportedactive energy
Exportedactive energy
Exportedactive energy
Exported
active energy
Importedlead reactive energy
Exportedlag reactive energy
Exportedlead reactive energy
Exportedactive energy
Importedlead reactive energy
Exportedlag reactive energy
Exportedlead reactive energy
Importedlead reactive energy
Exportedlag reactive energy
Exportedlead reactive energy
Exportedactive energy
Importedlead reactive energy
Exportedlag reactive energy
Exportedlead reactive energy
Imported
lead reactive energy
Exported
lag reactive energy
Exported
lead reactive energy
Exportedactive energy
Importedlead reactive energy
Exportedlag reactive energy
Exportedlead reactive energy
Harmonic phase N current
Degree
RMS value
DegreeRatio
RMS value
diDI No.State
doDO No.
Statedi
DI No.State
doDO No.
Statedi
DI No.State
doDO No.
Statedi
DI No.State
doDO No.
State
diDI No.State
doDO No.
Statedi
DI No.State
doDO No.
State
diDI No.State
doDO No.
Statedi
DI No.State
doDO No.
Statedi
DI No.State
doDO No.
State
diDI No.State
doDO No.
Statedi
DI No.State
doDO No.
Statedi
DI No.State
doDO No.
Statedi
DI No.State
doDO No.
Statedi
DI No.State
doDO No.
State
DegreeRatio
RMS valueDegree
RMS value
DegreeRatio
RMS value
DegreeRatio
RMS valueDegree
RMS value
DegreeRatio
RMS value
DegreeRatio
RMS value
Degree
RMS value
DegreeRatio
RMS value
DegreeRatio
RMS valueDegree
RMS value
DegreeRatio
RMS value
DegreeRatio
RMS valueDegree
RMS value
DegreeRatio
RMS value
DegreeRatio
RMS value
Degree
RMS value
DegreeRatio
RMS value
DegreeRatio
RMS valueDegree
RMS value
DegreeRatio
RMS value
DegreeRatio
RMS valueDegree
RMS value
DegreeRatio
RMS value
DegreeRatio
RMS valueDegree
RMS value
DegreeRatio
RMS value
DegreeRatio
RMS valueDegree
RMS value
DegreeRatio
RMS value
DegreeRatio
RMS value
Degree
RMS value
DegreeRatio
RMS value
DegreeRatio
RMS value
Degree
RMS value
DegreeRatio
RMS value
DegreeRatio
RMS valueDegree
RMS value
DegreeRatio
RMS value
DegreeRatio
RMS value
Harmonic current
Additional screen (displays when Set-up Menu 4 i s set)NO.10 NO.11 NO.12 NO.13 NO.14 NO.15
Harmonic voltageNO.16
Digital input stateNO.17
Digital output stateNO.18
Screen set on display pattern
P01
P02
P03
P04
P05
P06
P07
P08
P09
P10
P11
P12
P13
P00
UpperMiddleLowerUpperMiddleLowerUpperMiddleLowerUpperMiddleLower
UpperMiddleLowerUpperMiddleLowerUpperMiddleLowerUpperMiddleLowerUpperMiddleLowerUpperMiddleLowerUpperMiddleLower
UpperMiddleLowerUpperMiddleLowerUpperMiddleLower
A W
VAV
WhA
VAV
Wh
W
AVWAV
WhA
DAVA
DAVA
DAWh
ADAWh
A W
A WWh
A
WA
WWh
Hz W
A WWh
ADA W
AV
Wh
A WWh
A PF
VA
WhA
A
varh
A V
AV
Wh W
A
HzA
Wh
DAV
WhV
HzWh
AHzWh
WV
WhV
Hzvarh
NO.1 NO.2 NO.3 NO.4 NO.5 NO.6Harmonic voltage
DegreeRatio
RMS valueDegreeRatio
RMS valueDegreeRatio
RMS valueDegreeRatio
RMS value
DegreeRatioRMS value
DegreeRatio
RMS valueDegreeRatio
RMS valueDegreeRatio
RMS valueDegreeRatio
RMS valueDegreeRatio
RMS valueDegreeRatio
RMS value
DegreeRatio
RMS valueDegreeRatio
RMS valueDegreeRatio
RMS value
diDI No.State
doDO No.
Statedi
DI No.State
doDO No.
Statedi
DI No.State
doDO No.
Statedi
DI No.State
doDO No.
State
diDI No.State
doDO No.
Statedi
DI No.State
doDO No.
State
diDI No.State
doDO No.State
diDI No.State
doDO No.
Statedi
DI No.State
doDO No.
Statedi
DI No.State
doDO No.
Statedi
DI No.State
doDO No.
Statedi
DI No.State
doDO No.
Statedi
DI No.State
doDO No.
State
diDI No.State
doDO No.
State
Harmonic current
Additional screen (displays when Set-up Menu 4 i s set)NO.7
Digital input stateNO.13
Digital output stateNO.14
Screen set on display pattern
Three phase 3-wire
V3NV2NV1N
V3NV2NV1NA1
A2A3
A1A2A3 V 3N
V2NV1N
A1A2A3
A1A2A3
V3NV2NV1N
V3NV2NV1N
V3NV2NV1N
DA 1DA 2DA 3
DA 1DA 2DA 3
DA 1DA 2DA 3
V3NV2NV1NA1
A2A3
VA 1VA 2VA 3
PF 1PF 2PF 3
W 1W 2W 3
var 1var 2var 2
PF PF PF PF
PF
PF
PF
PF
AN
AN
var
var
var var
varV23V31
V12A1A2A3
V23V31
V12
DA 1DA 2DA 3
DA 1DA 2DA 3
DA 1DA 2DA 3
V12V23V31
V12V23V31
A1A2A3
A1A2A3
V12V23V31
A1A2A3
V12V23V31
V12V23V31
A1A2A3
A1A2A3
PF
NO.8 NO.9 NO.10 NO.11 NO.12
DegreeRatio
RMS valueDegreeRatio
RMS valueDegreeRatio
RMS valueDegreeRatio
RMS value
DegreeRatioRMS value
DegreeRatio
RMS valueDegreeRatio
RMS valueDegreeRatio
RMS valueDegreeRatio
RMS valueDegreeRatio
RMS valueDegreeRatio
RMS value
DegreeRatio
RMS valueDegreeRatio
RMS valueDegreeRatio
RMS value
Displaypattern
Displaypattern
Digitaldisplay
Digitaldisplay
Wh: Imported active energy, varh: Imported reactive energyNote: When an additional screen is added, a screen number is added.
W: Total active power, var: Total active power, PF: Total power factor
Arbitrarymeasuring item
For details, refer tothe users manual
Arbitrary measuring item For details, refer tothe users manual
22
-
8/13/2019 Power Meter ME96NSR Catalog
25/32
Dimensions
Dimensions / Mounting / Wiring,RSN69EM BM-RSN69EM
Option cover
(With the optional plug-in module)
( 1 0 6
. 9 )
8 6
. 2
2 0
. 7
Optional Plug-in Module
7 5
. 8 6 1
. 3
46.8
81.2 25.2
17.1
88.8
Mounting1 Dimensions of Panel
92 + 0.50
9 2 +
0 . 5
0
2 View Angle
3 Attachment
Protective sheet
Attachment position
In the case to attaching to the end of the panel, check the wiring work space and decide the attachment position.
Optional Plug-in module
4 Installing the Optional Plug-in Module
Please do not tighten too stronglyto prevent panel and screw frombreaking.Tightening torque for this product:0.3Nm to 0.5Nm(Half the torque applied normallyfor this type of screw)Also, please tighten the upper andlower screws at the same time.
A protective sheet is attached to the display for protection against scratch during the attachment to panel. Before using, remove the protective sheet.When you remove it, the display may light up due to generation of static electricity, but it is not an error. It goes off by natural discharge after a while.
The contrast of the display changes at view angles.Mount it at the position that is easy to see.
The panel hole dimensions are shown below.It can be attached to a panel with thickness of 1.6 to 4.0mm.
For attachment of the basic device into the panel hole, attach according to the following procedure.
Install the optional plug-in module after the power is turned off.The option is not recognized when installed while power is on.In this case, the option is recognized by power suspension/power resumption or restarting the basic device.
Combine the slot of the basic device and theconvex part of the optional plug-in module.
9 1
. 6 ( P A
N E L C U T )
9 5
. 8 ( C O V E R )
95.8 (COVER)
91.6 (PANEL CUT)
Note
Note
The attachment lug is installed in two holesof the top and bottom of the basic device.
Tighten the screws of the lug, and fix onto the panel.
When installing the optional plug-in module onto the basic device, install according to the following procedure.The option cover is removed. The optional plug-in module is installed.
View angle
6 0
10
60
6 0 Viewed from
the topViewed from
the side
23
-
8/13/2019 Power Meter ME96NSR Catalog
26/32
Wiring
Wiring Diagram
1 Applicable Cable Size
The table on the right describes the applicablewire size. Applicable wire size
Tightening torqueStrip Gauge
Input and output terminals of the basic deviceAWG24 to 14
0.4Nm10mm
Terminals of the optional plug-in module
10mm
2 Wiring Input and Output Terminals of the Basic DeviceStrip top of the cable or crimp the ferrule.Slacken screws of the terminal block, and insert the cables into
terminal hole.Tighten the terminal screws according to the tightening torque
mentioned above.
Terminals of the Optional Plug-in ModuleStrip top of the cable or
crimp the ferrule.
Insert the cables bypushing the lever, andconnect by releasingthe lever.
Insert hole Lever
3 Confirmations
After wiring, make sure the following:M The wires are connected correctly.M There is no mistake in wiring.
AWG 24 to 14 When using a stranded wire, use a ferrule. (AWG 16)
Dimensions / Mounting / Wiring
Three phase 4-wire type : Example of ME96NSR (with VT) Three phase 4-wire type : Example of ME96NSR-MB (for direct input)
+C1
PN
P3
P2
P1
C3
+C3
C2
+C2
C1
T+
MA
NC
MB
NC
SLD
SLD
Ter
T
ProtectiveEarthing
Load
(+)()
RS485(ModBus)
RS485(ModBus)
kKL
1 2 3 0
KL
l k
lKL
k
l
RS485(ModBus)
+C1
PN
P3
P2
P1
C3
+C3
C2
+C2
C1
NC
MA
NC
MB
NC
NC
NC
NC
NC
u
vu
vuv
UVU
VUV
kKL
1 2 3 0
Load
KL
l k
lKL
k
l
ProtectiveEarthing
(+)()
ProtectiveEarthing
Load
(+)()Load
ProtectiveEarthing
(+)()
Three phase 3-wire type : Example of ME96NSR-MB (with VT, wiring 2CT)
Three phase 3-wire type : Example of ME96NSR (for direct input, wiring 3CT)
UV
u
vu
v
UV
kKL
l
KL
k
l
+C1
P2
P3
NC
P1
C3
+C3
C2
+C2
C1
T+
MA
NC
MB
NC
SLD
SLD
Ter
T
kKL
l
kKL
1 2 31 2 3
l
KL
k
l
+C1
P2
P3
NC
P1
C3
+C3
C2
+C2
C1
NC
MA
NC
MB
NC
NC
NC
NC
NC
Auxiliary power supply100 to 240VAC 100 to 240VDC
1 For a low voltage circuit,grounding of the secondarysides of VT and CT in notnecessary.
2 Do not connect to NC terminal.
Auxiliary power supply100 to 240VAC 100 to 240VDC
1 For a low voltage circuit,grounding of the secondary
sides of VT and CT in notnecessary.2 Do not connect to NC terminal.
1. If the polarity of VT and CT is not correct, it cannot be measured correctly.2. In case of DC auxiliary power, it should be wired correctly because it has polarity. In case of AC auxiliary power, it does not have polarity.3. For a low voltage circuit, grounding of the secondary sides of VT and CT is not necessary.4. Always earth the terminal to the protective earth conductor. Earth the terminal with under 100 ohm of earth resistance. Otherwise, there will be a
false operation.
1. Use the shielded twisted pair cable.2. To the units of both the end of ModBus link, the 120 ohm resistance has to be attached.
This instrument can perform 120 ohm termination by short-circuiting the terminal of T-and Ter.3. The earth has to be connected to earth by a thick wire of low impedance.4. Keep the distance between ModBus link to power line.5. When the setting is 2CT, the use by 3CT wiring cannot correctly measure for phase 2.
Note
Note
24
-
8/13/2019 Power Meter ME96NSR Catalog
27/32
Optional Plug-in Module : ME-4201-NS96 Optional Plug-in Module : ME-0052-NS96
Note
Note
Conditions DistanceBelow 600V power lines
Other power lines
30cm or more
60cm or more
ME-4201-NS96ME96NSRCH1+CH1CH2+CH2CH3+CH3CH4+CH4C1AC1BC2AC2BA
COM
Analog output CH1
Analog output CH2
Analog output CH3Analog output CH4
Pulse output1
Pulse output2
{ {
{ { { { {Alarm output
DI1,DI2,DI3,DI4,DI5are connected inside.
ME-0052-NS96ME96NSR-MBDI1+DI1DI2+DI2DI3+
DI3DI4+DI4DI5+DI5DO1+DO1DO2+DO2
24VDC
DO1
DO2
{ {
C RR
DI1+
DI1
DI5+DI5
Optional Plug-in Module : ME-0040C-NS96
ME-0040C-NS96ME96NSR
C RR
24VDC
DI1
DI4COM
C RR
DI2
DA
DB
DG
SLD
FG
SLD
DG
DB
DA
DI1
DI2
DI3DI4
COM
ProtectiveEarthing
CC-LinkCommunication
CC-LinkCommunication
+C1
PN
P3
P2
P1
C3
+C3
C2
+C2
C1
NC
MA
NC
MB
NC
NC
NC
NC
NC
1. Do not bunch the digital input/output signal cables with the main circuit or power cables, or install them close to each other. Keep the distance betweenthe digital input/output signal cables, the main circuit or power cables, and high voltage lines shown below, when they run parallel to each other.
1. As for CC-Link cable, use the designated cable. Each of Ver.1.10 compatible CC-Link cables, CC-Link specified cables, and CC-Link specifiedhigh-performance cables cannot be used together with other cable types. If used together, correct data transmission will not be guaranteed.The terminating resistor is different depending on the applied cable.
2. Connect the shielded wire of the CC-Link specified cable to SLD of each module, and earth the both ends of the shielded wire FG. The SLD and FGare connected into the module.
3. Keep the distance between CC-Link cables to power lines (At least 10cm). When connecting long distance in parallel, please set apart more than 30cm.4. Fill the requirements of total wire distance, station distance, and terminal resistance value according to baud rate and type of cable. (As for detail of the
requirements, refer to the operation manual for CC-Link master unit.)5. To the units of both the end of CC-Link line, the terminal resistors should be attached. And the terminal resistors should be attached in between DA andDB.
2. Analog output signal cables should keep the distance from the other power cables and input signal (VT, CT and auxiliary power) cables, and should not
be bunched. And use the shielded cables or twisted pair cables so that it is not affected noise, serge, and induction.Also, the wiring cables should be as short as possible.
3. In case of ME96NSR-MB with ME-4201-NS96, the ModBus interface and the analog outputs do not have the insulation between them.
Wiring Diagram (Continued)
25
-
8/13/2019 Power Meter ME96NSR Catalog
28/32
-
8/13/2019 Power Meter ME96NSR Catalog
29/32
Transmission
Twist Pair Cable SpecificationsPart of recommended cables of twist pair cables to be used in CC-Link are introduced below.As for details, refer to Mitsubishi Electric Open Field Network CC-Link.CC-Link performance is not guaranteed with other than the recommended cables.
ModBus Specifications
SpecificationsItemRS485, 2 wires half duplexModBus RTU
2400, 4800, 9600, 19200, 38400bps1000m1 to 255 (FFh)31120 1/2WShielded twisted pair, AWG26 (or wider) gauge
InterfaceProtocol
SpeedDistanceAddressStation NumberTerminal ResistanceRecommended Cables
CC-Link Specifications
SpecificationsItem
1 StationRemote device station (I/O data and word data can be transmitted)
CC-Link Ver 1.1010Mbps/5Mbps/2.5Mbps/625kbps/156kbps
Numbers of Occupied Stations
CC-Link VersionBaud Rate
1 to 64Remote Station Number (Station Number)
The following conditions should be satisfied.If the system is configured by only this instrument, up to 42 units can be connected.Condition 1 : {(1 a) + (2 b) + (3 c) + (4 d)} 64
a: number of units occupied by 1 station, b: number of units occupied by 2 stationsc: number of units occupied by 3 stations, d: number of units occupied by 4 stations
Condition 2 : {(16 A) + (54 B) + (88 C)} 2304A: number of remote I/O stations, B: number of remote device stations, C: number of local stations
Maximum Number of Connected Units
Name CC-Link Exclusive Cable
FANC-SB
FA-CBL200SB, etc.
CC-Link Exclusive High Performance Cable
FANC-SBH
FA-CBL200SBH
Contact
Type
CC-Link Exclusive New Cable (CC-Link Ver.1.10)FANC-SB110H
ContactNameType
Mitsubishi Electric System & Service Co., Ltd.Kuramo Electric Co., Ltd.MITSUBISHI ELECTRIC ENGINEERING, CO., LTD.
Kuramo Electric Co., Ltd.
Notes: 1. As for terminal resistance, be sure to use 110 (1/2W) when using CC-Link exclusive cable, and 130 (1/2W) when using CC-Link exclusive highperformance cable.If other combination than the above is used, normal data transmission is not guaranteed.
2. CC-Link exclusive cable and CC-Link exclusive high performance cable cannot be used in mixture.3. System construction is eas ier by using CC-Link exclusive cable in 10Mbps and CC-Link exclusive high performance cable under 5Mbps.4. The CC-Link Exclusive New Cable is more suited for system constructed with CC-Link Ver.1.10 products.
As for details of twist pair cable, refer to CC-Link catalog CC-Link Cable Wiring Manual and MELFANS Web.
MELFANS Web : http://wwwf2.mitsubishielectric.co.jp/melfansweb/english/index.html
About ProgrammingNecessary information for operating this device by MELSEC-A/Q series sequencer loading CC-Link interface unit are as follows.In addition to this operation manual, read the following documents also. PLC I/F unit users manual Electronic Multi-Measuring Instrument programming manual (CC-Link) .................................................................................................................... LAN040503
Data Collection for ModBus Electronic Multi-Measuring Instrument ModBus I/F specification ................................................................................................................................. LSPM0075
Output Specification
Output SpecificationOutputLoad Resistance
4 to 20mADC600 max
No-voltage a contactContact Capacity: 35VDC, 0.1ARated 24VDC (19 to 30VDC), under 4mASignal Width over 30ms (with DI latch HoLd, over 30ms of pulse can be latched)
ME-0052-NS96ME-0040C-NS96
No-voltage a contactContact Capacity: 35VDC, 0.2A
ME-4201-NS96ME-0052-NS96
Optional Plug-in Module Type
Analog Output
Digital Output
Digital Input
Pulse Output
ME-4201-NS96
ME-4201-NS96
27
-
8/13/2019 Power Meter ME96NSR Catalog
30/32
R ela ted Produ cts
Unit : mm
VAR-6A
Lineup of 6-Circuit and 12-Circuit Control Types Only one device is needed where many condensers are needed in 12-circuit control such as large facility orlow-voltage control.
Better Accuracy for Power Factor Measurement Accurac