GDS Pole Mounted Disconnectors Up to 52kV

Transcript of Pole Mounted Disconnectors Up to 52kV -...

Page 1: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

GDSPole Mounted Disconnectors

Up to 52kV

Page 2: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

2

General Information

The switch for every application

The GDS range is a modern switch system with components for different isolation and switching applications in overheadlines and substations. The system is characterised by a high degree of flexibility in order to meet different national standards as well as to meet various customer specifications.

The base in the switch system is the phase element. To this component can different accessories be added for having the requested disconnector or switch specification.

The switch can be installed in all different pole types, wood, concrete, steel poles or substation structures.

Different insulator alternatives

The GDS can be supplied with a wide range of different insulators in order to meet different isolation philosofies, enviromental conditions and different standards.

The components of the switch system allow for different insulators to be used due to the design with parallel insulators without affecting the base and contact components.

As standard can porcelain, outdoor epoxy resin and silicon rubber insulators be offerd. Beside the standard material can also insulators according to customer specifications be used.

Page 3: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

3

Charctersistic ValueApplicable standards IEC 62271-102, IEC 60265

Rated voltage 24kV 36kV

Impulse withstand voltage Phase-Earth 125kV 170kV

Impulse withstand voltage over isolating distance 145kV 195kV

Power frequency voltage 1 min wet, Phase-Earth 50kV 70kV

Power frequency voltage 1 min wet, over isolating distance

60kV 80kV

Rated frequency 50-60Hz 50-60Hz

Rated current *) 630A 630A

Short time current 25kA 25kA

Duration of short time current 3 sec. 3 sec

Peak withstand current 62,5kA 62,5kA

Making capacity 5kA 3kA

Interupting capacity with the loadbreak heads of mainlyactive load at rated voltage and cosφ=0,7

630A 400A

Interupting capacity with the loadbreak heads of mainlyactive load at rated voltage and cosφ=0,15 capacitive

25A 16A

Interupting capacity with the loadbreak heads of mainlyactive load at rated voltage and cosφ=0,15 reactive

16A 4A

Ringinterupting capacity with the loadbreak heads of mainly active load at rated voltage and cosφ=0,3 reactive

400A 400A

Interupting capacity with breaking whip of mainly activeload at rated voltage and cosφ=0,7

25A 16A

Interupting capacity with breaking whip of cable and linechanging currents at rated voltage

15A 10A

Permissible ice load Up to 20mm

Mechanical endurance >2000 operations

Temperature range -50oC to +50oC

Insulator material Porcelain,Silicon rubber, Outddoor epoxy resin

Insulator creepage distance Various for different insulators

Technical characteristics

*) 630A is standard value. Alternative current ratings are 800A, 1250A and 2000A.

Page 4: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

4

Phase elements

Article No.** Type Insulator material Rated

voltage Rated current’ Weight, kg

2862003 GP2G Outdoor epoxy resin 24kV 630A 30

A6737 GP2P Porcelain 24kV 630A 33

A7513 GP2G4 Outdoor epoxy resin 36kV 630A 33

A7332 GP2S Silicon rubber 36kV 630A 36

A7598 GDS36/52-6600 Porcelain 52kV 630A 60

A8268 GDSS26/52-6600 Silicon rubber 52kV 630A 54

*) 630A is the standard current rating. Other rated currents available on request

**) Numbers are for sets of three units

GP2G GP2PGP2G4

GP2SGDS36/52-6600 GDSS36/52-6600

Page 5: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

5

Loadbreaking accessories

Article No.* Type Rated voltage For Phase element type Weight, kg

2862006 GBGK1 12-36kV GP2G,GP2P,GP2S,GP2G4 2,5

Breaking whip

Loadbreak head

*) Set of three

GBGK1

Article No.* Type Rated voltage For Phase element type Weight, kg

A6733 GLBD1 12-24kV GP2G,GP2P,GP2S,GP2G4 12

A6733-2 GLBD2 36kV GP2S, GP2G4, GDS36/52-6600, GDSS36/52-6600 12

GLBD

Page 6: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

6

Connecting accessories

Article No.** Type Insulator material Rated

voltageRated

current

For Phase element

type

Weight, kg

2862011 GF2G Outdoor epoxy resin 24kV 630A GP2G 18

A6729-2 GF2P Porcelain 24kV 630A GP2P 20

A6729-5 GF2G4 Outdoor epoxy resin 36kV 630A GP2G4 20

2862009 GF2S Silicon rubber 36kV 630A GP2S 19

Extension part

Article No.** Type Height of surge

arresterRated current

For Phase element type Weight, kg

2862123 GF2PI* 630AGP2G,GP2P,

GP2S15

5821934 GF2PI1* 630AGP2G,GP2P,

GP2S15

Extension Part for integrated surge arrester

**) Surge arrester is not included in articel number

GF2G

GF2PI

Page 7: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

7

Connecting accessories

Article No.** Type Insulator material Rated

voltageRated current

For Phase element type Weight, kg

2862016 GK2G Outddor epoxy resin 24kV 630A GP2G 22

A6732-2 GK2P Porcelain 24kV 630A GP2P 23

A6732-5 GK2G4 Outdoor epoxy resin 36kV 630A GP2G4 23

2862014 GK2S Silicon rubber 36kV 630A GP2S 23

Cable connection Part

Article No.** Type Height of surge

arresterRated current

For Phase element type Weight, kg

2862124 GK2PI* 630AGP2G,GP2P,

GP2S14

Cable connection Part for integrated surge arrester

**) Surge arrester is not included in articel number

GK2G

GK2PI

Page 8: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

8

Fuse combinations

Article No.** Type Insulator material Rated

voltageRated current

For Phase element type Weight, kg

2862037 GS3G Outddor epoxy resin 24kV 80A GP2G 21

A6741-2 GS3P Porcelain 24kV 80A GP2P 22

2862035 GS3S Silicon rubber 24kV 80A GP2S 22

For RP33 type fuse tubes

For fuses with dimensions according to DIN 43625

GS3G assembled on GP2G

Article No.** Type Insulator material Rated

voltageRated current

For Phase element type Weight, kg

2862071 GS5RG Outddor epoxy resin 24kV 20A GP2G 23

2862069 GS5RS Silicon rubber 24kV 20A GP2S 24

GS5Rs assembled on GP2S

Page 9: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

9

Connecting accessories

Article No. Type Weight, kg

A6530* GPK 3

A7997 CPAU 0,2

A7335 CSP 0,4

Hinge terminal bar and connection bars

Article No. Type Weight, kg

A6847* GCCB 2,4

Cable connection bar

*) Article number is for set of three

GPK

CPAU CSP

GCCB

Article No.* Type Conductor

crossectionWeight, kg

2862056 GKG16 Al 16-120mm2 0,8

2862057 GKG43 Al 50-240mm2 1

2862058 GKG44Al 16-120mm2

Cu 10-95mm20,8

A3037 EKN1 Cu 10-120mm2 0,4

Connecting clamps

GKG

EKN1

Page 10: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

10

Overvoltage protection accessories

Article No.** Type Placement For Phase

element type Weight, kg

5221927 GHG Horizontal over support insulator GP2G, GP2P 0,5

A6951 GSG1 Horizontal with crossarm bracket

GP2G,GP2P,GP2S,GP2G4

10,5

Spark gaps

GHG

GSG1

Page 11: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

11

Overvoltage protection accessories

Article No.* Type Placement Weight, kg

2862121 GSAB Attached to base of phaseelement or accessorie 4

2862120 GVP Together with crossarm clamp GRF 3

Surge arrester brackets

*) Article number is for set of three

GSAB

GSAB on cable connection part

GSAB on phase element

GVP on crossarm clamp GRF

GVP

Page 12: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

12

Earthing accessories

Article No.** Type Placement For Phase element

type Weight, kg

A7681 EB2 Fixed contact side of phase element GP2G, GP2P 15

A7998 EB3 Fixed contact side of phase element GP2S,GP2G4 16

A8062 EB4 Rocking contact side of phase element GP2G, GP2P 15

A8034-1 GIL6 Mechanical interlock when earth blades installed on both sides of phase element - 2

A3500*) JOPO Earth bolt for connection of portable earthing tool All types 1

A6906 GJPEarth contact for rocking insulator. When

disconnector opens, rocking insulator gets earth connected automatically

GP2P,GP2G,GP2S 7

EB4

*) Article number is for set of 6 pcs

**) Article numbers include three earth blades with mechanical interlock. Associated equipment such as phase coupling tubes, operating rods, operating handles must be ordered separately.

EB2

JOPO

GJK

Page 13: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

13

Handoperating Mechanisms

Article No. Type Indication label Weight

A6731 GHM I-0 4

A6941 GHM2 ON-OFF 4

A6941-J GHM2-J* Earth On-Earth Off 4

A6941/AU GHM/AU** ON-OFF 4

A8215 GHMEI*** I-0 10

*) The GHM2-J are assembled for reversed operation direction

**) The A6941/AU has flexible copper leads between the pole bracket and handle

***) Handoperating mechanism with electrical interlock. When ordering indicate voltage for the locking magnet

Article No. Type Comment Weight

A7460 GHMSK 1NO+1NC contact 0,4

A8216 GHMDI 1NO+1NC x2 1

A7459 GHMIV* Interlocking wheel with one slot 0,2

A7459-1 GHMIV-1* Interlocking wheel with double slots 0,2

GHMSK Installed on GHM

GHMDI

Installed on GHM

Operating handles

Auxillary contacts and accessories

GHMEI

GHM

GHMIV

Installed on GHM

*) Castell interlocks are not included with the interlocking wheel, but can be supplied on request

Page 14: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

14

Handoperating Mechanisms

Article No. Type Weight

A7380 GHS1 8

The GHS1 has a automatic resetting of the latchpin when operated.

Article No. Type Comment Weight

A8327 GHSSLStickoperated

safety lock attachment

0,5

Hookstick operating mechanism

Accessories

GHS1

Page 15: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

15

Operating rods with accessories

Operating rod accessories

Operating rods

Article No. Description Type Length,mm

2862032 Complete rod set with upper and lower rod.Telescopically adjustable length GMR1 5800-7600

A7435 Complete rod set with upper and lower rod.Telescopically adjustable GMR2 7300-9100

A7352-1 Upper operating rod with fork for connection to the operating lever GMR3 3250

A7352-2 Intermediate operating rod GMR4 3250

A7352-3 Lower operating rod with telescopically length adjustable section GMR5 2000-3800

A7373 Telescopical rod set with forks in both ends for connection to hookstick operating mechanism GMR6 2000-3800

2862034 Extension rod with coupling socket for operating rods. Including one extra rod guide GFR2 2000

A8174 Complete operating rod for substation disconnectors GMR17 3500-5300

Article No. Type Suitable for crossarm Weight

A6734 GMK Operating lever 1

A7635 GMK5 Operating lever for earth blades 1

A6742 GSI Rod insulator up to 24kV 0,5

A7550 GSI2 Rod insulator up to 52kV 1,3

A7354 GRC Rod coupling socket 0,3

A6743 GSS Rod guide 0,7

A7944 GSS2 Rod guide 2,5

GMR6

GMKGMK5

GSIGRC GSS GSS2

Page 16: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

16

Pole assembling crossarms

Article No. Type Dimensions Weight

5821911 GFLR1 80x80x2000 19kg

5821912 GFLR2 100x100x2000 25kg

A6611-21 GFLR21 100x100x2500 31kg

A8000 GFLR24 80x80x2400 22kg

Crossarm assembling parts

Crossarms

Article No. Type Suitable for crossarm Weight

5821919 GFLRME GFLR1&GFLR2 4

A8139-1 GFLRME-1 GFLR21 4

For single-pole installation

For H-pole installation

Article No. Type Suitable for crossarm Weight

5821920 GFLRMPGFLR1,GFLR2,

GFLR212

Article No. Type Suitable for crossarm Weight

A7962 PBRCGFLR1,GFLR2,

GFLR21, GFLR247

Note: The PBRC pole bracket should not be used when conductors are terminated to the crossarm.

Note: The GFLR24 Crossarm have no holes drilled

Page 17: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

17

Crossarm assembling accessories

Article No. Type Suitable for crossarms Weight

2862091 GRF1 Box tubes and C-channels with max dimensions100x130mm (WxH) 0,6 kg

2862092 GRF2 Box tubes and C-channels with max dimensions130x180mm (WxH) 0,7 kg

A6915 GRF3 Angle channels with max dimensions 130x180 (WxH) 0,7 kg

Crossarm clamps

Page 18: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

18

Mast Head Loadbreaklswitch 24kV,630AHandle operation, epoxy resin insulators

Component Type Qty Remark

Phase element GP2G 1

Hinge Terminal bar GPK 1

Loadbreak head GLBD1 1

Phase coupling tube GMA16 1

Crossarm clamps GRF1 3

Operating lever GMK 1

Operating tube GMR2 1

Assembling crossarm GFLR1 1

Operating handle GHM 1

Rod guide GSS 2

Rod insulator GSI 1

Ordering number for the complete unit A7535

Component Type Qty Remark

Single pole assembling parts GFLRME 1 Article number 5821919

H-pole assembling parts GFLRMP 1 Article number 5821920 (pole distance 2000mm c/c)

Crossarm assembling parts (to be ordered separately)

Page 19: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

19

Mast Head installed disconnector 24kV,630AWith Hookstick operation, epoxy resin insulators

Component Type Qty Remark

Phase element GP2G 1

Hinge Terminal bar GPK 1

Breaking whip GBGK1 1

Phase coupling tube GMA20 1

Crossarm clamps GRF6 3

Operating lever GMK 1

Pole bracket PBRC 1 Bolts for pole not included

Operating tube GMR16 1

Assembling crossarm GMA24 1

Telescopical oåperating rod GMR17 1

Hookstick operating mechanism GHS1 1

Resin operating tube - 1 Not supplied by Gevea

Ordering number for the complete unit A8176Ordering number for the complete unit, but with assembled loadbreakhaeds A8176/GLBD1

Page 20: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

20

Vertical disconnector 24kV,630AWith earth blades, epoxy resin insulators

Component Type Qty Remark

Phase element GP2G 1

Earth blade set EB4 1 Include mechanical interlock

Breaking whip GBGK1 1

Phase coupling tube GMA16 2

Crossarm clamps GRF1 3

Operating lever GMK 1

Operating lever GMK5 1

Operating tube GMR2 2

Rod coupling socket GRC 2

Rod guide GSS 4

Operating handle for disconnector GHM 1

Operating handle for earth blade GHM2-J 1

Ordering number for the complete unit excluding assembling crossarm A8336-1

Ordering number for the complete unit including assembling crossarm and pole attacment accessories A8336

Page 21: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

21

Masthead installed disconnector 24kV,630Aassembled on square concrete pole 200x200mm

Ordering No. Description

A8099Complete unit including crossarm and operating mechanism. With assembled

breaking whips

A8099/LBComplete unit including crossarm and operating mechanism. With assembled

loadbreak head

Page 22: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

22

Masthead installed disconnector 24kV,630Aassembled in steel pole

Ordering No. Description

A8184/GBGK1Complete unit including crossarm and operating mechanism. With assembled

breaking whips

A8184Complete unit including crossarm and operating mechanism. With assembled

loadbreak head

Page 23: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

23

Substation installed loadbreakswitch 36kV,630AWith earthblades, epoxy resin insulators

Component Type Qty Remark

Phase element GP2G4 1

Extension part GF2G4 1

Loadbreak head GLBD1 1

Phase coupling tube GMA25 2

Crossarm clamps GRF1 6

Operating lever GMK 1 For disconnector blade

Operating lever GMK5 1 For eathblade

Operating tube GMR17 2

Operating handle GHM2 1 For disconnector blade

Operating handle GHM2-J 1 For earthblade

Earth blade EB4 1 Includes mechanical interlock

Connection palm CPAU 6

Ordering number for the complete unit A8137

Page 24: Pole Mounted Disconnectors Up to 52kV - GEVEAgevea.se/wp-content/uploads/2016/10/gds_english_brochure...Pole Mounted Disconnectors Up to 52kV 2 General Information The switch for every

24

AB GEVEA Box 12043 Tlf. +46 11 184800

S-600 12 Norrköping Fax. +46 11 182350

Sweden E -mail. [email protected]

www.gevea.se

Version 2010-02-10 Eng