PNOZ X2.8P
Operating Manual-1004082-EN-20
} Safety relays
PrefaceThis document is the original document.
All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be madefor the user's internal purposes. Suggestions and comments for improving this documenta-tion will be gratefully received.
Source code from third-party manufacturers or open source software has been used forsome components. The relevant licence information is available on the Internet on the Pilzhomepage.
Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®,SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarksof Pilz GmbH & Co. KG in some countries.
SD means Secure Digital
Contents
Operating Manual PNOZ X2.8P1004082-EN-20
| 3
Introduction ............................................................................................................................ 5Validity of documentation.......................................................................................................... 5Using the documentation .......................................................................................................... 5Definition of symbols................................................................................................................. 5
Safety ...................................................................................................................................... 6Intended use ............................................................................................................................. 6Safety regulations ..................................................................................................................... 6Safety assessment ................................................................................................................... 6Use of qualified personnel ........................................................................................................ 7Warranty and liability ................................................................................................................ 7Disposal .................................................................................................................................... 7For your safety.......................................................................................................................... 7
Unit features ........................................................................................................................... 8
Safety features ....................................................................................................................... 8
Block diagram/terminal configuration ................................................................................. 9Type: 24 VAC/DC ..................................................................................................................... 9Type: 24 - 240 V AC/DC ........................................................................................................... 9
Function Description ............................................................................................................. 10Operating modes ...................................................................................................................... 10Timing diagram ......................................................................................................................... 10
Installation .............................................................................................................................. 11
Wiring ...................................................................................................................................... 12
Preparing for operation ......................................................................................................... 13
Operation ................................................................................................................................ 15Status indicators ....................................................................................................................... 16
Faults – Interference .............................................................................................................. 16
Dimensions in mm ................................................................................................................. 16
Technical details .................................................................................................................... 17Safety characteristic data ......................................................................................................... 27
Supplementary data .............................................................................................................. 27Service life graph ...................................................................................................................... 28
Contents
Operating Manual PNOZ X2.8P1004082-EN-20
| 4
Remove plug-in terminals ..................................................................................................... 31
Order reference ...................................................................................................................... 31
EC declaration of conformity ................................................................................................ 31
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 5
Introduction
Validity of documentationThis documentation is valid for the product PNOZ X2.8P. It is valid until new documentationis published.
This operating manual explains the function and operation, describes the installation andprovides guidelines on how to connect the product.
Using the documentationThis document is intended for instruction. Only install and commission the product if youhave read and understood this document. The document should be retained for future ref-erence.
Definition of symbolsInformation that is particularly important is identified as follows:
DANGER!
This warning must be heeded! It warns of a hazardous situation that posesan immediate threat of serious injury and death and indicates preventivemeasures that can be taken.
WARNING!
This warning must be heeded! It warns of a hazardous situation that couldlead to serious injury and death and indicates preventive measures that canbe taken.
CAUTION!
This refers to a hazard that can lead to a less serious or minor injury plusmaterial damage, and also provides information on preventive measuresthat can be taken.
NOTICE
This describes a situation in which the product or devices could be dam-aged and also provides information on preventive measures that can betaken. It also highlights areas within the text that are of particular import-ance.
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 6
INFORMATION
This gives advice on applications and provides information on special fea-tures.
Safety
Intended useThe safety relay PNOZ X2.8P provides a safety-related interruption of a safety circuit.
The safety relay meets the requirements of EN 60947-5-1 and EN 60204-1 and may beused in applications with:} E-STOP pushbuttons} Safety gates} Light grids and safety switches with detection of shorts across contacts
The following is deemed improper use in particular} Any component, technical or electrical modification to the product,} Use of the product outside the areas described in this manual,
} Use of the product outside the technical details (see Technical details [ 17]).
NOTICEEMC-compliant electrical installation
The product is designed for use in an industrial environment. The productmay cause interference if installed in other environments. If installed in otherenvironments, measures should be taken to comply with the applicablestandards and directives for the respective installation site with regard to in-terference.
Safety regulations
Safety assessmentBefore using a device, a safety assessment in accordance with the Machinery Directive isrequired.
The product as an individual component fulfils the functional safety requirements in accord-ance with EN ISO 13849 and EN 62061. However, this does not guarantee the functionalsafety of the overall plant/machine. To achieve the relevant safety level of the overall plant/machine’s required safety functions, each safety function needs to be considered separ-ately.
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 7
Use of qualified personnelThe products may only be assembled, installed, programmed, commissioned, operated,maintained and decommissioned by persons who are competent to do so.
A competent person is a qualified and knowledgeable person who, because of their train-ing, experience and current professional activity, has the specialist knowledge required. Tobe able to inspect, assess and operate devices, systems and machines, the person has tobe informed of the state of the art and the applicable national, European and internationallaws, directives and standards.
It is the company’s responsibility only to employ personnel who} Are familiar with the basic regulations concerning health and safety / accident prevention,} Have read and understood the information provided in the section entitled Safety} Have a good knowledge of the generic and specialist standards applicable to the specific
application.
Warranty and liabilityAll claims to warranty and liability will be rendered invalid if} The product was used contrary to the purpose for which it is intended,} Damage can be attributed to not having followed the guidelines in the manual,} Operating personnel are not suitably qualified,} Any type of modification has been made (e.g. exchanging components on the PCB
boards, soldering work etc.).
Disposal} In safety-related applications, please comply with the mission time TM in the safety-related
characteristic data.} When decommissioning, please comply with local regulations regarding the disposal of
electronic devices (e.g. Electrical and Electronic Equipment Act).
For your safetyThe unit meets all the necessary conditions for safe operation. However, please note thefollowing:} Note for overvoltage category III: If voltages higher than low voltage (>50 VAC or >120
VDC) are present on the unit, connected control elements and sensors must have a ratedinsulation voltage of at least 250 V.
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 8
Unit features} Positive-guided relay outputs:
– 3 safety contacts (N/O), instantaneous
– 1 auxiliary contact (N/C), instantaneous} Connection options for:
– E-STOP pushbuttons
– Safety gate limit switches
– Start button
– Light guards and safety switches} LED display for:
– Supply voltage
– Switch status of the safety contacts} Plug-in connection terminals (either spring-loaded terminal or screw terminal)} See order reference for unit types
Safety featuresThe safety relay meets the following safety requirements:} The circuit is redundant with built-in self-monitoring.} The safety function remains effective in the case of a component failure.} The correct opening and closing of the safety function relays is tested automatically in
each on-off cycle.
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 9
Block diagram/terminal configuration
Type: 24 VAC/DC} UB: 24 VAC/DC; Order no. 777301, 787301
S11 S52 S21 S22 S12 S34
PNOZ X2.8P
*Insulation between the non-marked area and the relay contacts: Basic insulation (over-voltage category III), Protective separation (overvoltage category II)
Type: 24 - 240 V AC/DC} UB: 24 – 240 VAC/DC; Order no. 777302, 787302
S11 S52 S21 S22 S12 S34
PNOZ X2.8P
*Insulation between the non-marked area and the relay contacts: Basic insulation (over-voltage category III), Protective separation (overvoltage category II)
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 10
Function DescriptionThe safety relay PPNOZ X2.8P provides a safety-oriented interruption of a safety circuit.When supply voltage is supplied the "POWER" LED is lit. The unit is ready for operationwhen the start circuit S12-S34 is closed.} Input circuit is closed (e.g. E-STOP pushbutton not operated):
– LEDs "CH1" and "CH2" will light.
– Safety contacts 13-14, 23-24 and 33-34 are closed, auxiliary contact 41-42 is open.The unit is active.
} Input circuit is opened (e.g. E-STOP pushbutton operated):
– The LEDs "CH1" and "CH2" go out.
– Safety contacts 13-14, 23-24 and 33-34 are opened redundantly, auxiliary contact41-42 is closed.
Operating modes} Single-channel operation: No redundancy in the input circuit, earth faults in the start and
input circuit are detected.} Dual-channel operation without detection of shorts across contacts: Redundant input cir-
cuit, detects PNOZ X2.8P
– earth faults in the start and input circuit,
– short circuits in the input circuit.} Dual-channel operation with detection of shorts across contacts: Redundant input circuit,
PNOZ X2.8P detects
– earth faults in the start and input circuit,
– short circuits in the input circuit,
– shorts across contacts in the input circuit.} Automatic start: Unit is active once the input circuit has been closed.} Manual start: Unit is active once the input circuit and the start circuit are closed.} Increase in the number of available contacts by connecting contact expandsion modules
or external contactors/relays.
Timing diagram
[1][1] [2][2]
3 3
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 11
Legend} Power: Supply voltage} Start: Start circuit} Input: Input circuit} Output safe: Safety contacts} Output aux: Auxiliary contact} [1]: Automatic start} [2]: Manual start} a: Input circuit closes before start circuit} b: Start circuit closes before input circuit} t1: Switch-on delay} t2: Delay-on de-energisation} t3: Recovery time
Installation} The unit should be installed in a control cabinet with a protection type of at least IP54.} Use the notch on the rear of the unit to attach it to a DIN rail (35 mm).} When installed vertically: Secure the unit by using a fixing element (e.g. retaining bracket
or end angle).
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 12
WiringPlease note:
} Information given in the "Technical details [ 17]" must be followed.} Outputs 13-14, 23-24, 33-34 are safety contacts; output 41-42 is an auxiliary contact (e.g.
for display).} Auxiliary contact 41-42 should not be used for safety circuits!} To prevent contact welding, a fuse should be connected before the output contacts (see
Technical details [ 17]).} Calculation of the max. cable length lmax in the input circuit:
Rlmax
Rl / km
Imax
=
Rlmax = max. overall cable resistance (see Technical details [ 17])Rl / km = cable resistance/km
} Use copper wiring with a temperature stability of 60/75 °C.} To prevent EMC interferences (particularly common-mode interferences) the measures
described in EN 60204-1 must be executed. This includes the separate routing of cablesof the control circuits (input, start and feedback loop) from other cables for energy trans-mission or the shielding of cables, for example.
} Adequate protection must be provided on all output contacts with capacitive and inductiveloads.
} Do not switch low currents using contacts that have been used previously with high cur-rents.
} When connecting magnetically operated, reed proximity switches, ensure that the max.peak inrush current (on the input circuit) does not overload the proximity switch.
} With 24 V AC/DC units:The power supply must meet the regulations for extra low voltages with protective elec-trical separation (SELV, PELV).
Important for detection of shorts across contacts:
As this function for detecting shorts across contacts is not failsafe, it is tested by Pilz duringthe final control check. If there is a danger of exceeding the cable runs, we recommend thefollowing test after the installation of the device:
1. Unit ready for operation (output contacts closed)
2. Short circuit the test terminals S12, S22 for detecting shorts across the inputs.
3. The unit's fuse must be triggered and the output contacts must open. Cable lengths inthe scale of the maximum length can delay the fuse triggering for up to 2 minutes.
4. Reset the fuse: remove the short circuit and switch off the supply voltage for approx. 1minute.
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 13
Preparing for operation
Supply voltage AC DC
UB = 24 VAC/DC; Order no. 777301, 787301
A1
A2
L1
N
A1
A2
L+
L-
UB = 24 - 240 VAC/DC; Order no. 777302, 787302
A1
A2
L1
N
S21
A1
A2
L+
L-
S21
Input circuit Single-channel Dual-channel
E-STOPwithout detection of shortsacross contacts
S1
S22
S21
S11
S52
S12
S1
S11
S12
S52
S22
S21
E-STOPwith detection of shorts acrosscontacts
S1
S22
S21
S12
S11
S52
S11
Safety gatewithout detection of shortsacross contacts S1
S22
S21
S11
S52
S12 S1S2
S22
S21
S11
S12
S52
Safety gatewith detection of shorts acrosscontacts
Light guards or safety switch, de-tection of shorts across contactsvia ESPE(only when UB = 24 VDC); Order no. 777301, 787301)
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 14
NOTICE
With single-channel wiring the safety level of your machine/plant may belower than the safety level of the unit (see Safety characteristicdata [ 27]).
NOTICEOperation with a light guard or safety switch
It must not be possible to switch off the supply voltage for the PNOZ X2.8Pseparately from the supply voltage for the light guard or safety switch.
Start circuit E-STOP wiring, safety gate(single-channel)
E-STOP wiring, safety gate (dual-channel)
Automatic start
Manual start
NOTICEIn the event of an automatic start or manual start with bridged startcontact (fault):
The unit starts up automatically when the safeguard is reset, e.g. when theE-STOP pushbutton is released. Use external circuit measures to preventan unexpected restart.
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 15
Feedback loop Automatic start Manual start
Contacts from external contactorsK5 K6
K5L1
N
K6
S12
13 (23,33)
S34
14 (24,34)
K5 K6
K5L1
K6
S12
S34
S3
N
13 (23, 33)
14 (24 ,34)
Legend} S1/S2: E-STOP/safety gate switch} S3: Reset button
} : Switch operated
} : Gate open
} : Gate closed
OperationWhen the relay outputs are switched on, the mechanical contact on the relay cannot betested automatically. Depending on the operational environment, measures to detect thenon-opening of switching elements may be required under some circumstances.
When the product is used in accordance with the European Machinery Directive, a checkmust be carried out to ensure that the safety contacts on the relay outputs open correctly.Open the safety contacts (switch off output) and start the device again, so that the internaldiagnostics can check that the safety contacts open correctly} for SIL CL 3/PL e at least 1x per month} for SIL CL 2/PL d at least 1x per year
NOTICE
The safety function should be checked after initial commissioning and eachtime the plant/machine is changed. The safety functions may only bechecked by qualified personnel.
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 16
Status indicatorsLEDs indicate the status and errors during operation:
LED on
POWERSupply voltage is present.
CH.1 Safety contacts of channel 1 are closed.
CH.2 Safety contacts of channel 2 are closed.
Faults – Interference} Earth fault: The supply voltage fails and the safety contacts open. Once the cause of the
respective fault has been rectified and the supply voltage is switched off for approx.1 minute, the unit is ready for operation again.
} Contact malfunctions: If the contacts have welded, reactivation will not be possible afterthe input circuit has opened.
} LED "POWER" does not light: Short circuit or no supply voltage.
Dimensions in mm* with spring-loaded terminals
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 17
Technical details
Order no. 777301 – 777302See below for more order numbers
General 777301 777302
CertificationsCCC, CE, EAC (Eurasian),KOSHA, TÜV, cULus Listed
CCC, CE, EAC (Eurasian),KOSHA, TÜV, cULus Listed
Electrical data 777301 777302Supply voltage
Voltage 24 V 24 - 240 VKind AC/DC AC/DCVoltage tolerance -15 %/+10 % -15 %/+10 %Output of external power supply(AC) 5,5 VA 4,5 VAOutput of external power supply(DC) 2,5 W 2 WFrequency range AC 50 - 60 Hz 50 - 60 HzResidual ripple DC 160 % 160 %
Duty cycle 100 % 100 %Max. inrush current impulse
Current pulse, A1 1,7 A –Pulse duration, A1 3,3 ms –
Inputs 777301 777302Number 2 2Voltage at
Input circuit DC 24 V 24 VStart circuit DC 24 V 24 VFeedback loop DC 24 V 24 V
Current atInput circuit DC 30 mA 25 mAStart circuit DC 40 mA 50 mAFeedback loop DC 40 mA 50 mA
Min. input resistance at power-on 88 Ohm 209 Ohm
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 18
Inputs 777301 777302Max. overall cable resistance Rl-max
Single-channel at UB DC 30 Ohm 45 OhmSingle-channel at UB AC 100 Ohm 45 OhmDual-channel without detectionof shorts across contacts at UBDC 50 Ohm 80 OhmDual-channel without detectionof shorts across contacts at UBAC 100 Ohm 80 OhmDual-channel with detection ofshorts across contacts at UB DC 15 Ohm 15 OhmDual-channel with detection ofshorts across contacts at UB AC 15 Ohm 15 Ohm
Relay outputs 777301 777302Number of output contacts
Safety contacts (N/O), instant-aneous 3 3Auxiliary contacts (N/C) 1 1
Max. short circuit current IK 1 kA 1 kAUtilisation category
In accordance with the standard EN 60947-4-1 EN 60947-4-1Utilisation category of safety con-tacts
AC1 at 240 V 240 VMin. current 0,01 A 0,01 AMax. current 6 A 6 AMax. power 1500 VA 1500 VADC1 at 24 V 24 VMin. current 0,01 A 0,01 AMax. current 6 A 6 AMax. power 150 W 150 W
Utilisation category of auxiliary con-tacts
AC1 at 240 V 240 VMin. current 0,01 A 0,01 AMax. current 6 A 6 AMax. power 1500 VA 1500 VADC1 at 24 V 24 VMin. current 0,01 A 0,01 AMax. current 6 A 6 AMax. power 150 W 150 W
Utilisation categoryIn accordance with the standard EN 60947-5-1 EN 60947-5-1
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 19
Relay outputs 777301 777302Utilisation category of safety con-tacts
AC15 at 230 V 230 VMax. current 5 A 3 ADC13 (6 cycles/min) at 24 V 24 VMax. current 5 A 4 A
Utilisation category of auxiliary con-tacts
AC15 at 230 V 230 VMax. current 5 A 3 ADC13 (6 cycles/min) at 24 V 24 VMax. current 5 A 4 A
Utilisation category in accordancewith UL
Voltage 240 V AC G.U. (same polarity) 250 V AC G.U. (same polarity)With current 6 A 6 AVoltage 24 V DC G. P. 24 V DC G. P.With current 6 A 6 APilot Duty R300 B300, R300
External contact fuse protection,safety contacts
In accordance with the standard EN 60947-5-1 EN 60947-5-1Max. melting integral 260 A²s 66 A²sBlow-out fuse, quick 10 A 6 ABlow-out fuse, slow 6 A 4 ABlow-out fuse, gG 6 A 6 ACircuit breaker 24V AC/DC,characteristic B/C 6 A 4 A
External contact fuse protection,auxiliary contacts
Max. melting integral 160 A²s 66 A²sBlow-out fuse, quick 10 A 6 ABlow-out fuse, slow 6 A 4 ABlow-out fuse, gG 6 A 6 ACircuit breaker 24 V AC/DC,characteristic B/C 6 A 4 A
Contact material AgCuNi + 0,2 µm Au AgCuNi + 0,2 µm AuConventional thermal currentwhile loading several contacts
777301 777302
Ith per contact at UB AC;AC1: 240 V, DC1: 24 V
Conv. therm. current with 1 con-tact 6 A 6 AConv. therm. current with 2 con-tacts 4 A 6 AConv. therm. current with 3 con-tacts 3,5 A 4,5 A
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 20
Conventional thermal currentwhile loading several contacts
777301 777302
Ith per contact at UB DC;AC1: 240 V, DC1: 24 V
Conv. therm. current with 1 con-tact 6 A 6 AConv. therm. current with 2 con-tacts 6 A 6 AConv. therm. current with 3 con-tacts 5 A 4,5 A
Times 777301 777302Switch-on delay
With automatic start typ. 250 ms 340 msWith automatic start max. 450 ms 400 msWith automatic start after poweron typ. 250 ms 600 msWith automatic start after poweron max. 450 ms 800 msWith manual start typ. 125 ms 180 msWith manual start max. 450 ms 400 ms
Delay-on de-energisationWith E-STOP typ. 15 ms 10 msWith E-STOP max. 30 ms 20 msWith power failure typ. 60 ms –With power failure max. 100 ms –With power failure typ. UB 240 V – 1100 msWith power failure max. UB 240V – 1500 msWith power failure typ. UB 24 V – 180 msWith power failure max. UB 24 V – 230 ms
Recovery time at max. switchingfrequency 1/s
After E-STOP 50 ms 50 msAfter power failure 200 ms 1500 ms
Supply interruption before de-ener-gisation 20 ms 20 msSimultaneity, channel 1 and 2 max. ∞ ∞Environmental data 777301 777302Climatic suitability EN 60068-2-78 EN 60068-2-78Ambient temperature
Temperature range -35 - 55 °C -10 - 55 °CStorage temperature
Temperature range -40 - 85 °C -40 - 85 °CClimatic suitability
Humidity 93 % r. h. at 40 °C 93 % r. h. at 40 °CCondensation during operation Not permitted Not permittedEMC EN 60947-5-1, EN 61000-6-2, EN
61000-6-4, EN 61326-3-1EN 60947-5-1, EN 61000-6-2, EN61000-6-4, EN 61326-3-1
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 21
Environmental data 777301 777302Vibration
In accordance with the standard EN 60068-2-6 EN 60068-2-6Frequency 10 - 55 Hz 10 - 55 HzAmplitude 0,35 mm 0,35 mm
Airgap creepageIn accordance with the standard EN 60947-1 EN 60947-1Overvoltage category III / II III / IIPollution degree 2 2
Rated insulation voltage 250 V 250 VRated impulse withstand voltage 4 kV 4 kVProtection type
Housing IP40 IP40Terminals IP20 IP20Mounting area (e.g. control cab-inet) IP54 IP54
Mechanical data 777301 777302Mounting position Any AnyMechanical life 10,000,000 cycles 10,000,000 cyclesMaterial
Bottom PPO UL 94 V0 PPO UL 94 V0Front ABS UL 94 V0 ABS UL 94 V0Top PPO UL 94 V0 PPO UL 94 V0
Connection type Screw terminal Screw terminalMounting type plug-in plug-inConductor cross section with screwterminals
1 core flexible 0,25 - 2,5 mm², 24 - 12 AWG 0,25 - 2,5 mm², 24 - 12 AWG2 core with the same cross sec-tion, flexible with crimp connect-ors, no plastic sleeve 0,25 - 1 mm², 24 - 16 AWG 0,25 - 1 mm², 24 - 16 AWG2 core with the same cross sec-tion, flexible without crimp con-nectors or with TWIN crimp con-nectors 0,2 - 1,5 mm², 24 - 16 AWG 0,2 - 1,5 mm², 24 - 16 AWG
Torque setting with screw terminals 0,5 Nm 0,5 NmStripping length with screw termin-als 8 mm 8 mmDimensions
Height 94 mm 94 mmWidth 22,5 mm 22,5 mmDepth 121 mm 121 mm
Weight 185 g 210 g
Where standards are undated, the 2020-07 latest editions shall apply.
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 22
Order no. 787301 – 787302
General 787301 787302
CertificationsCCC, CE, EAC (Eurasian),KOSHA, TÜV, cULus Listed
CCC, CE, EAC (Eurasian),KOSHA, TÜV, cULus Listed
Electrical data 787301 787302Supply voltage
Voltage 24 V 24 - 240 VKind AC/DC AC/DCVoltage tolerance -15 %/+10 % -15 %/+10 %Output of external power supply(AC) 5,5 VA 4,5 VAOutput of external power supply(DC) 2,5 W 2 WFrequency range AC 50 - 60 Hz 50 - 60 HzResidual ripple DC 160 % 160 %
Duty cycle 100 % 100 %Max. inrush current impulse
Current pulse, A1 1,7 A –Pulse duration, A1 3,3 ms –
Inputs 787301 787302Number 2 2Voltage at
Input circuit DC 24 V 24 VStart circuit DC 24 V 24 VFeedback loop DC 24 V 24 V
Current atInput circuit DC 30 mA 25 mAStart circuit DC 40 mA 50 mAFeedback loop DC 40 mA 50 mA
Min. input resistance at power-on 88 Ohm 209 OhmMax. overall cable resistance Rl-max
Single-channel at UB DC 30 Ohm 45 OhmSingle-channel at UB AC 100 Ohm 45 OhmDual-channel without detectionof shorts across contacts at UBDC 50 Ohm 80 OhmDual-channel without detectionof shorts across contacts at UBAC 100 Ohm 80 OhmDual-channel with detection ofshorts across contacts at UB DC 15 Ohm 15 OhmDual-channel with detection ofshorts across contacts at UB AC 15 Ohm 15 Ohm
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 23
Relay outputs 787301 787302Number of output contacts
Safety contacts (N/O), instant-aneous 3 3Auxiliary contacts (N/C) 1 1
Max. short circuit current IK 1 kA 1 kAUtilisation category
In accordance with the standard EN 60947-4-1 EN 60947-4-1Utilisation category of safety con-tacts
AC1 at 240 V 240 VMin. current 0,01 A 0,01 AMax. current 6 A 6 AMax. power 1500 VA 1500 VADC1 at 24 V 24 VMin. current 0,01 A 0,01 AMax. current 6 A 6 AMax. power 150 W 150 W
Utilisation category of auxiliary con-tacts
AC1 at 240 V 240 VMin. current 0,01 A 0,01 AMax. current 6 A 6 AMax. power 1500 VA 1500 VADC1 at 24 V 24 VMin. current 0,01 A 0,01 AMax. current 6 A 6 AMax. power 150 W 150 W
Utilisation categoryIn accordance with the standard EN 60947-5-1 EN 60947-5-1
Utilisation category of safety con-tacts
AC15 at 230 V 230 VMax. current 5 A 3 ADC13 (6 cycles/min) at 24 V 24 VMax. current 5 A 4 A
Utilisation category of auxiliary con-tacts
AC15 at 230 V 230 VMax. current 5 A 3 ADC13 (6 cycles/min) at 24 V 24 VMax. current 5 A 4 A
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 24
Relay outputs 787301 787302Utilisation category in accordancewith UL
Voltage 240 V AC G.U. (same polarity) 250 V AC G.U. (same polarity)With current 6 A 6 AVoltage 24 V DC G. P. 24 V DC G. P.With current 6 A 6 APilot Duty R300 B300, R300
External contact fuse protection,safety contacts
In accordance with the standard EN 60947-5-1 EN 60947-5-1Max. melting integral 260 A²s 66 A²sBlow-out fuse, quick 10 A 6 ABlow-out fuse, slow 6 A 4 ABlow-out fuse, gG 6 A 6 ACircuit breaker 24V AC/DC,characteristic B/C 6 A 4 A
External contact fuse protection,auxiliary contacts
Max. melting integral 160 A²s 66 A²sBlow-out fuse, quick 10 A 6 ABlow-out fuse, slow 6 A 4 ABlow-out fuse, gG 6 A 6 ACircuit breaker 24 V AC/DC,characteristic B/C 6 A 4 A
Contact material AgCuNi + 0,2 µm Au AgCuNi + 0,2 µm AuConventional thermal currentwhile loading several contacts
787301 787302
Ith per contact at UB AC;AC1: 240 V, DC1: 24 V
Conv. therm. current with 1 con-tact 6 A 6 AConv. therm. current with 2 con-tacts 4 A 6 AConv. therm. current with 3 con-tacts 3,5 A 4,5 A
Ith per contact at UB DC;AC1: 240 V, DC1: 24 V
Conv. therm. current with 1 con-tact 6 A 6 AConv. therm. current with 2 con-tacts 6 A 6 AConv. therm. current with 3 con-tacts 5 A 4,5 A
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 25
Times 787301 787302Switch-on delay
With automatic start typ. 250 ms 340 msWith automatic start max. 450 ms 400 msWith automatic start after poweron typ. 250 ms 600 msWith automatic start after poweron max. 450 ms 800 msWith manual start typ. 125 ms 180 msWith manual start max. 450 ms 400 ms
Delay-on de-energisationWith E-STOP typ. 15 ms 10 msWith E-STOP max. 30 ms 20 msWith power failure typ. 60 ms –With power failure max. 100 ms –With power failure typ. UB 240 V – 1100 msWith power failure max. UB 240V – 1500 msWith power failure typ. UB 24 V – 180 msWith power failure max. UB 24 V – 230 ms
Recovery time at max. switchingfrequency 1/s
After E-STOP 50 ms 50 msAfter power failure 200 ms 1500 ms
Supply interruption before de-ener-gisation 20 ms 20 msSimultaneity, channel 1 and 2 max. ∞ ∞Environmental data 787301 787302Climatic suitability EN 60068-2-78 EN 60068-2-78Ambient temperature
Temperature range -35 - 55 °C -10 - 55 °CStorage temperature
Temperature range -40 - 85 °C -40 - 85 °CClimatic suitability
Humidity 93 % r. h. at 40 °C 93 % r. h. at 40 °CCondensation during operation Not permitted Not permittedEMC EN 60947-5-1, EN 61000-6-2, EN
61000-6-4, EN 61326-3-1EN 60947-5-1, EN 61000-6-2, EN61000-6-4, EN 61326-3-1
VibrationIn accordance with the standard EN 60068-2-6 EN 60068-2-6Frequency 10 - 55 Hz 10 - 55 HzAmplitude 0,35 mm 0,35 mm
Airgap creepageIn accordance with the standard EN 60947-1 EN 60947-1Overvoltage category III / II III / IIPollution degree 2 2
Rated insulation voltage 250 V 250 V
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 26
Environmental data 787301 787302Rated impulse withstand voltage 4 kV 4 kVProtection type
Housing IP40 IP40Terminals IP20 IP20Mounting area (e.g. control cab-inet) IP54 IP54
Mechanical data 787301 787302Mounting position Any AnyMechanical life 10,000,000 cycles 10,000,000 cyclesMaterial
Bottom PPO UL 94 V0 PPO UL 94 V0Front ABS UL 94 V0 ABS UL 94 V0Top PPO UL 94 V0 PPO UL 94 V0
Connection type Spring-loaded terminal Spring-loaded terminalMounting type plug-in plug-inConductor cross section withspring-loaded terminals: Flexiblewith/without crimp connector 0,2 - 1,5 mm², 24 - 16 AWG 0,2 - 1,5 mm², 24 - 16 AWGSpring-loaded terminals: Terminalpoints per connection 2 2Stripping length with spring-loadedterminals 8 mm 8 mmDimensions
Height 101 mm 101 mmWidth 22,5 mm 22,5 mmDepth 121 mm 121 mm
Weight 180 g 210 g
Where standards are undated, the 2020-07 latest editions shall apply.
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 27
Safety characteristic data
NOTICE
You must comply with the safety characteristic data in order to achieve therequired safety level for your plant/machine.
Operatingmode
EN ISO13849-1:2015
PL
EN ISO13849-1:2015
Category
EN 62061
SIL CL
EN 62061
PFHD [1/h]
IEC 61511
SIL
IEC 61511
PFD
EN ISO13849-1:2015
TM [year]– PL e Cat. 4 SIL CL 3 2,31E-09 SIL 3 2,03E-06 20
Explanatory notes for the safety-related characteristic data:} The SIL CL value in accordance with EN 62061 corresponds to the SIL value in accord-
ance with EN 61508.} TM is the maximum mission time in accordance with EN ISO 13849-1. The value also ap-
plies as the retest interval in accordance with EN 61508-6 and IEC 61511 and as theproof test interval and mission time in accordance with EN 62061.
All the units used within a safety function must be considered when calculating the safetycharacteristic data.
INFORMATION
A safety function's SIL/PL values are not identical to the SIL/PL values ofthe units that are used and may be different. We recommend that you usethe PAScal software tool to calculate the safety function's SIL/PL values.
Supplementary data
CAUTION!
It is essential to consider the relay's service life graphs. The relay outputs'safety-related characteristic data is only valid if the values in the service lifegraphs are met.
The PFH value depends on the switch frequency and the load of the relay output.If the service life graphs are not accessible, the stated PFH value can be used irrespectiveof the switch frequency and the load, as the PFH value already considers the relay's B10dvalue as well as the failure rates of the other components.
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 28
Service life graphThe service life graphs indicate the number of cycles from which failures due to wear mustbe expected. The wear is mainly caused by the electrical load; the mechanical load is negli-gible.
Unit types with UB 24 VAC/DC} UB: 24 VAC/DC; Order no. 777301, 787301
Cyc
les
x 10
00
Switching current (A)
Fig.: Service life graphs at 24 V DC and 230 V AC
Cyc
les
x 10
00
Switching current (A)
Fig.: Service life graphs at 110 V DC
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 29
Example} Inductive load: 0.2 A} Utilisation category: AC15} Contact service life: 2 000 000 cycles
Provided the application to be implemented requires fewer than 2 000 000 cycles, the PFHvalue (see Technical details [ 17]) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all outputcontacts. With capacitive loads, any power surges that occur must be noted. With DC con-tactors, use flywheel diodes for spark suppression.
Unit types with UB 24-240 VAC/DC} UB: 24 – 240 VAC/DC; Order no. 777302, 787302
10000
1000
5000
100
500
10
50
0,1 0,5 1 2 3 4 5 6 8 10
DC-1: 24VDC-1: 24V
AC-1: 230VAC-1: 230V
AC-15: 230VAC-15: 230V
DC-13: 24VDC-13: 24V
Num
ber o
f ope
ratin
g cy
cles
x 1
000
Switching current (A)
Fig.: Service life graphs at 24 V DC and 230 V AC
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 30
Num
ber o
f cyc
les
x 10
00
Switching current (A)
Fig.: Service life graphs at 110 V DC
Example} Inductive load: 0.2 A} Utilisation category: AC15} Contact service life: 1 000 000 cycles
Provided the application to be implemented requires fewer than 1 000 000 cycles, the PFHvalue (see Technical details [ 17]) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all relay con-tacts. With capacitive loads, any power surges that occur must be noted. With DC contact-ors, use flywheel diodes for spark suppression.
PNOZ X2.8P
Operating Manual PNOZ X2.8P1004082-EN-20
| 31
Remove plug-in terminalsProcedure: Insert the screwdriver into the housing recess behind the terminal and lever theterminal out.
Do not remove the terminals by pulling the cables!
Order reference
Product type Features Connection type Order no.
PNOZ X2.8P 24 VAC/DC Screw terminals 777301
PNOZ X2.8P C 24 VAC/DC Spring-loaded terminals 787301
PNOZ X2.8P 24 - 240 VAC/DC Screw terminals 777302
PNOZ X2.8P C 24 - 240 VAC/DC Spring-loaded terminals 787302
EC declaration of conformityThis product/these products meet the requirements of the directive 2006/42/EC for ma-chinery of the European Parliament and of the Council. The complete EC Declaration ofConformity is available on the Internet at www.pilz.com/support/downloads.Representative: Norbert Fröhlich, Pilz GmbH & Co. KG, Felix-Wankel-Str. 2, 73760 Ost-fildern, Germany
The Best of German Engineering
Partner of:
SupportTechnical support is available from Pilz round the clock.
Americas
Brazil
+55 11 97569-2804
Canada
+1 888 315 7459
Mexico
+52 55 5572 1300
USA (toll-free)
+1 877-PILZUSA (745-9872)
Asia
China
+86 21 60880878-216
Japan
+81 45 471-2281
South Korea
+82 31 778 3300
Australia
+61 3 95600621
Europe
Austria
+43 1 7986263-0
Belgium, Luxembourg
+32 9 3217570
France
+33 3 88104003
Germany
+49 711 3409-444
Ireland
+353 21 4804983
Italy, Malta
+39 0362 1826711
Scandinavia
+45 74436332
Spain
+34 938497433
Switzerland
+41 62 88979-32
The Netherlands
+31 347 320477
Turkey
+90 216 5775552
United Kingdom
+44 1536 462203
You can reach our
international hotline on:
+49 711 3409-444
Pilz develops environmentally-friendly products using
ecological materials and energy-saving technologies.
Offices and production facilities are ecologically designed,
environmentally-aware and energy-saving. So Pilz offers
sustainability, plus the security of using energy-efficient
products and environmentally-friendly solutions.
We are represented internationally. Please refer to our homepage www.pilz.com for further details or contact our headquarters.
Headquarters: Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, GermanyTelephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected], Internet: www.pilz.com
CEC
E®, C
HR
E®, C
MS
E®, I
ndur
aNET
p®, L
eans
afe®
, Mas
ter
of S
afet
y®, M
aste
r of
Sec
urity
®, P
AS
4000
®, P
AS
cal®
, PA
Sco
nfig®
, Pilz
®, P
IT®, P
LID
®, P
MC
prim
o®, P
MC
prot
ego®
, PM
Cte
ndo®
, P
MD
®, P
MI®
, PN
OZ®
, PR
BT®
, PR
CM
®, P
rimo®
, PR
TM®, P
SEN
®, P
SS
®, P
VIS
®, S
afet
yBU
S p
®, S
afet
yEY
E®, S
afet
yNET
p®, T
HE
SP
IRIT
OF
SA
FETY
® a
re re
gist
ered
and
pro
tect
ed tr
adem
arks
of
Pilz
Gm
bH &
Co.
KG
in s
ome
coun
trie
s. W
e w
ould
poi
nt o
ut th
at p
rodu
ct fe
atur
es m
ay v
ary
from
the
deta
ils s
tate
d in
this
doc
umen
t, de
pend
ing
on th
e st
atus
at t
he ti
me
of p
ublic
atio
n
and
the
scop
e of
the
equi
pmen
t. W
e ac
cept
no
resp
onsi
bilit
y fo
r th
e va
lidity
, acc
urac
y an
d en
tiret
y of
the
text
and
gra
phic
s pr
esen
ted
in th
is in
form
atio
n. P
leas
e co
ntac
t our
Tec
hnic
al S
uppo
rt
if yo
u ha
ve a
ny q
uest
ions
.
1800
XXXX
-en-
0X, 2
019-
05 P
rinte
d in
Ger
man
y©
Pilz
Gm
bH &
Co.
KG
, 201
9
Back cover
1004
082-
EN-2
0, 2
020-
10 P
rinte
d in
Ger
man
y©
Pilz
Gm
bH &
Co.
KG
, 201
9