PN-XOS9500 Operation Manual Pure Water
Transcript of PN-XOS9500 Operation Manual Pure Water
-
7/30/2019 PN-XOS9500 Operation Manual Pure Water
1/14
OPERATING MANUALLIGHT COMMERCIAL WATER SOFTENER
LCTA 150 SERIESWith 9500 Twin Alternating-Top Mount Control Valve
MODEL NO. Meter
Products, equipment, service. We are the answer.
Tenergy Water
-
7/30/2019 PN-XOS9500 Operation Manual Pure Water
2/14
1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2 PRINCIPLES OF
Softening - Ion Exchange . . . . . . . . . . . . . . . . .3Regeneration Steps and Purpose . . . . . . . . . .3
3 SPECIFICATIONS
Specification Sheet . . . . . . . . . . . . . . . . . . . . .4
Softener Specification . . . . . . . . . . . . . . . . . . .5
Softener Data . . . . . . . . . . . . . . . . . . . . . . . . .5
Tenergy Brand Resin Data . . . . . . . . . . . . . . . .6
Exchange Capacity Data . . . . . . . . . . . . . . . . .6
Eductor & Flow Control Data . . . . . . . . . . . . . .6
Brine (Salt) Data . . . . . . . . . . . . . . . . . . . . . . .6
4 INSTALLATION INSTRUCTIONS . . . . . . . . . . . . . .7
5 START-UP INSTRUCTIONS
Meter Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
6 PROGRAM SETTING PROCEDURE
How to Set the Regeneration Cycle . . . . . . . . .9
Manual Regeneration . . . . . . . . . . . . . . . . . . .10
7 MEDIA LOADING . . . . . . . . . . . . . . . . . . . . . . . . .10
8 PARTS LISTS . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
1-1/2 Meter Assembly . . . . . . . . . . . . . . . . . . . .
. . . . . .see Model 9500 Service Manual, pg. 19
Drive Assembly . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . .see Model 9500 Service Manual, pg. 13
Timer Assembly . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . .see Model 9500 Service Manual, pg. 21
Control Valve Assembly . . . . . . . . . . . . . . . . . . .
. . . . . .see Model 9500 Service Manual, pg. 15
1700 Brine System Assembly . . . . . . . . . . . . . .
. . . . . .see Model 9500 Service Manual, pg. 17
1600 Brine System Assembly . . . . . . . . . . . . . .
. . . . . .see Model 9500 Service Manual, pg. 16
9 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . .12-13
DRAWINGSElectrical Diagram . . . . . . . . . . . . . . . . . . . . . . .
. . . . . .see Model 9500 Service Manual, pg. 26
Valve Drawing . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . .see Model 9500 Service Manual, pg. 26
Typical Piping . . . . . . . . . . . . . . . . . . . . . . .back
Optional-Duplex Piping Assembly . . . . . . . .back
Brine Tank Assemblies . . . . . . . . . . . . . . . .back
Introduction
Tenergy Water Light Commercial water softeners are assembled
of the highest quality parts available. The LCTA 150 Series is a
twin tank, single controller, metered system available with 1-1/2
connections, with different size units to meet your needs.
The Mineral Tank is a noncorrosive fiberglass tank with a one-piece
thermoplastic inner liner in compliance with FDA under 21 CFR -
Part 177. The tank has a working pressure of 150 PSI, or maximum
temperature of 120F.
The exchange media is a polystyrene strong acid cation resin in
the sodium form. It has a maximum exchange capacity of 30,000
grains per cubic feet, when regenerated with 15 lbs. salt.
The valve body is constructed of high quality brass to assure long
life. The piston is Teflon coated to prevent wear and allow foreign
particles to pass without damage to the piston.
The unit is a twin alternating system, where one unit is in service
and the other unit regenerated and in standby. Regeneration cycle
is fully adjustable to meet your changing needs.
Regeneration on the LCTA 150 Series is initiated by the 9500
Econominder Water Meter. Once a preset number of gallons flow
through the system, and the meter zeroes out, the unit in service
starts to regenerate and the unit in standby is put into service.
Once the unit completes its regeneration cycle, it automatically
goes into standby.
10
Section Description Page
LCTA 150 SERIES
TWIN ALTERNATING WATER SOFTENER
CONTENTS SECTION I
TENERGY WATER 2001 2
Copyright 2000 by TENERGY WATER, LLC. All rights reserved. Except as permitted under the United States Copyright Act of 1976, no part of this publication may bereproduced or distributed in any form or by any means, stored in a data base or retrieval system, without the prior written permisssion of TENERGY WATER, LLC.
-
7/30/2019 PN-XOS9500 Operation Manual Pure Water
3/14
Softening of water by the ion exchange process involves the
exchange or substitution of the hardness minerals, chiefly calcium
and magnesium, for sodium minerals. The exchange is made
possible because the minerals are ionic in nature (often called
ionized impurities), which means they have an electrical charge.
The ion exchange process is based on the fact that like charges
repel one another, and unlike charges attract.
Calcium and magnesium ions in water are actually dissolved rock.
They have been dissolved by water, the universal solvent. As the
water trickles down through strata of rock and soil it dissolves the
calcium and magnesium deposits. This dissolved rock eventually
finds its way into an underground aquifer and when water from the
aquifer is pumped to the surface, it contains the dissolved hardness
minerals of calcium and magnesium and is said to be hard water.
An ion exchange softener exchanges the hardness minerals,
calcium and magnesium, for sodium, from the softener resin.
Sodium is less objectionable because it does not build up on
surfaces as scale deposits.
All three minerals are positively charged ions called cations. The
exchange takes place by passing water containing hardness
minerals over a man-made ion exchange resin contained in a suit-
able tank. The resin, polystyrene divinyl benzene in most modern
softeners, consists of millions of tiny plastic beads, all of which
contain many negatively charged exchange sites attracting positivecations. When the resin is in the regenerated state these negatively
charged exchange sites hold positively charged sodium cations.
As the calcium and magnesium contact the resin beads in their
travel through the resin tank, they displace the sodium ions from
the exchange sites. During the ion exchange process, relatively
small amounts of other strongly charged cations such as iron and
manganese are also removed along with the calcium and
magnesium.
Ion exchange is possible for two reasons: (1) All cations do not
have the same strength of positive charge and (2) the resin prefers
the more strongly charged cations calcium and magnesium than it
does the weaker sodium cations.
The exchanged sodium cations pass downward through the resin
bed and out the softener outlet; thus, the softener delivers soft
water.
Eventually, all of the resin exchange sites are occupied by calcium
and magnesium and no further exchange can take place. The resin
is said to be exhausted and must be regenerated.
The softener resin is regenerated with a dilute brine
solution of sodium chloride (common salt) and water. During
regeneration the flow of service water from the softener is first
stopped. Brine is drawn from the brine tank mixing with a separate
stream of water. The brine solution flows downward through the
resin, contacting the resin beads loaded with calcium and
magnesium ions. Even though the calcium and magnesium are
more strongly charged than the sodium, the concentrated brine
solution contains literally billions of the more weakly charged
sodium ions which have the power to displace the smaller
number of calcium and magnesium ions. When the calcium and
magnesium ions are displaced, the positive sodium ions are attracted
to the negative exchange sites. Eventually, all sites are filled by
sodium ions and the resin is said to be regenerated and ready for
the next softening cycle.
REGENERATION STEPS AND PURPOSE
Tank Switching When unit in service depletes the pre-set volume
of water and regeneration is initiated, the service flow automatically
switches from the unit exhausted to the unit that was in standby.
Backwash Flow through the resin bed is reversed. Water flows
upward, expanding and agitating the resin bed. This action loosens
sediment that may have collected on the resin during service andis flushed to drain. Resin fines which developed during service are
also removed.
Brine In Brine is educted from the brine tank, passes through the
resin during service, and is flushed to drain. Resin fines, which
developed during service, are also removed.
Slow Rinse After the brine has been introduced, brine air check
is closed, allowing water to flow through eductor at a slow rate,
displacing the brine remaining in the resin bed. This insures good
utilization of the brine.
Fast Rinse The resin is now flushed downward at a set flow rate.
This resettles the bed and rinses out any remaining brine left in the
resin bed.
Brine Fill Brine tank is refilled with a preset amount of water to
dissolve salt for the next regeneration.
After the brine fill step the unit is ready for service, thus
completing the regeneration cycle. The unit then places itself into
the standby mode.
SECTION 2
TENERGY WATER 2001 3
Principles of Softening Ion Exchange
-
7/30/2019 PN-XOS9500 Operation Manual Pure Water
4/14
Specifications
SPECIFICATIONS SHEET (to be filled out by installer)
Job No.
Model No.
Water Test
Capacity Per Unit
Gallons Per Regeneration Reserve Gallons
Mineral Tank Size: Diameter Height
Brine Tank Size & Salt Setting Per Regeneration
Control Valve Specifications
1. Type of Timer
Meter Initiated
2. Timer Program Settings
a) Backwash min.
b) Brine & Slow Rinse min.
c) Rapid Rinse min.
d) Brine Tank Refill min.
3. Drain Line Flow Controller gpm
4. Brine Line Flow Controller gpm
5. Injector Size #
SECTION 3
TENERGY WATER 2001 4
-
7/30/2019 PN-XOS9500 Operation Manual Pure Water
5/14
MODEL # SIZE SIZE CU. FT. 1/4x1/8 #20 SIZE FILL MAX MAX MIN GPM PSI GPM FLOOR HEIGHT
TT60F 1-1/2 12x52 2 30 24x41 600 60K 40K 30 12 25/33 15/25 5 24x42 63
TT90F 1-1/2 14x65 3 60 24x41 600 90K 60K 45 18 26/37 15/25 7 24x44 76TT120F 1-1/2 16x65 4 80 24x41 600 120K 80K 60 24 29/40 15/25 9 24X46 76
TT150F 1-1/2 20X62 5 100 24X50 800 150K 100K 75 30 37/48 15/25 12 24x50 73
TT180F 1-1/2 21x62 6 100 24x50 800 180K 120K 90 36 35/47 15/25 12 24x52 65
TT210F 1-1/2 21x62 7 100 24x50 800 210K 140K 105 42 34/46 15/25 15 24x52 71
TT240F 1-1/2 24x72 8 100 100 30x48 1200 240K 160K 120 48 37/49 15/25 15 30x69 83
TT300F 1-1/2 24x72 10 100 100 39x48 2000 300K 200K 150 60 35/47 15/25 15 39x69 83
SERV DROP BKW
BRINE TANKMINERAL TANK
TANK
PIPE
PART # DESCRIPTION SIZE WEIGHT
9500 Twin/Alt 1-1/2 MeterM2218 TT60F95 Twin Alt Softener 1-1/2 370
M2220 TT90F95 Twin Alt Softener 1-1/2 550
M2222 TT120F95 Twin Alt Softener 1-1/2 720
M2224 TT150F95 Twin Alt Softener 1-1/2 900
M2226 TT180F95 Twin Alt Softener 1-1/2 1115
M2228 TT210F95 Twin Alt Softener 1-1/2 1215
M2230 TT240F95 Twin Alt Softener 1-1/2 1535
M2235 TT300F95 Twin Alt Softener 1-1/2 1750
SOFTENER DATA - Commercial
SOFTENER SPECIFICATIONS
TENERGY WATER 2001 5
PIPE RESIN SALT
SOFTENINGCAPACITY1
LBS. SALT PERREGENERATION2
FLOW RATE & PRESSURE SPACEREQUIRED
MIN3
KEY TO THE NOTATIONS ABOVE:
1. 2. All units from Tenergy Water are set at minimum salt settings.
3. Use the minimum capacity when sizing units.
4. Duplex systems require approximately twice the floor length space.
RANGES:1-1/2 Meter: Standard Range = 10,625 Gallons1-1/2 Meter: Extended Range = 53,125 Gallons
Above information subject to change or correction as required by the manufacturer.
Capacities are based on resin manufacturers data and are dependentupon influent water TDS, temperature, bed depth, pressure, and flowrates. The raw water is to be free of oil, color, and turbidity.
4 4 4
4UNDERBED
-
7/30/2019 PN-XOS9500 Operation Manual Pure Water
6/14
TANK TANK BRINE PER SALT PER INCHDIA. AREA INCH OF HEIGHT SATURATED BRINE(IN.) (SQ. FT.) (GALLONS)* SOLUTION (LBS)
18 1.76 1.10 2.8620 2.16 1.33 3.4824 3.14 1.95 5.0730 4.90 3.04 7.9036 7.06 4.40 11.442 9.62 5.97 15.548 12.57 7.8 20.2
54 15.90 9.9 25.260 19.63 12.2 31.866 23.76 14.7 38.272 28.27 17.5 45.5
*without salt in tank - brine only
It is recommended that a good grade of solar or pellet salt be used. One gallon warm water (80F) will dissolve a maximum of 2.6 lbs. of salt. One gallon colder water will dissolve a maximum of 2.4 lbs. of salt One gallon of saturated brine weighs 10.74 lbs.
MODEL # INJECTOR RATE B.L.F.C.1 D.L.F.C.2
TENERGY WATER 2001 6
GENERAL DESCRIPTION
Ionic form, as delivered Na+
Functional Group Sulfonic Acid
Matrix Polystyrene - DVB
Structure Gel
Appearance Dark
PHYSICAL AND CHEMICAL PROPERTIES
Bead Size (U.S. Standard Mesh) min. 90% 16-50Bead Size Range mm 0.41-0.51
Uniformity coefficient Maximum 1.7
Bead Integrity min. % Whole Beads 95
Bulk Density ( 5%) lbs/ft3 53
True Density approx. g/ml 1.29
Water Retention % wt. 42-46
Total Capacity min. eq/l 2.0
Volume Change Na max. % 5-10
TYPICAL OPERATING PARAMETERS
Operating Temperature max. F 248
Operating pH Range 0-14
Bed Depth min. inches 24
Pressure drop (59F) per gpm/ft2 Approx. psi/ft 0.16Flow Velocity service up to gpm/ft2 16
Flow Velocity backwash (68F) gpm/ft2 6-7
Flow Velocity type NaCl
Regenerant level approx. lbs/ft3 6-15
Regenerant concentration % 10
Flow Velocity regeneration gpm/ft3 0.50-1
Flow Velocity rinsing approx. gpm/ft3 1-5
Rinse Water Requirement approx. gal/ft3 resin 20-40
Bed Expansion approx. % per gpm/ft3 (68F) 10
Freeboard (as % of resin volume) 50-100
TENERGY BRAND SOFTENER RESIN DATA
EDUCTOR AND FLOW CONTROL DATA BRINE (SALT) DATA
TT 60F95 #3 Yellow 1.10 gpm 1.0 gpm 5.0 gpm
TT 90F95 #3 Yellow 1.10 gpm 1.0 gpm 5.0 gpm
TT120F95 #3 Yellow 1.10 gpm 1.0 gpm 7.0 gpm
TT 150F95 #3C Yellow 1.30 gpm 2.0 gpm 12.0 gpm
TT 180F95 #3C Yellow 1.30 gpm 2.0 gpm 12.0 gpm
TT 210F95 #4C Green 1.79 gpm 2.0 gpm 12.0 gpm
TT 240F95 #4C Green 1.79 gpm 2.0 gpm 15.0 gpm
TT 300F95 #4C Green 1.79 gpm 2.0 gpm 15.0 gpm
SLOW RINSE
KEY TO THE NOTATIONS ABOVE:
1. Brine Line Flow Control (Refill Brine Tank)2. Drain Line Flow Control (Backwash and Rapid Rinse Flow Rate)
Due to varying water conditions, tank sizes, and water pressures, the above settings shouldbe used only as a guideline.
EXCHANGECAPACITY DATA
20,000 grain approx. per cu. ft.6 lbs. salt-sodium chloride
25,000 grain approx. per cu. ft.8 lbs. salt-sodium chloride
27,000 grain approx. per cu. ft.10 lbs. salt-sodium chloride
30,000 grain approx. per cu. ft.15 lbs. salt-sodium chloride
Note: To convert parts permillion (ppm) or milligramsper liter (mpl) to grains divideby 17.1.
Example:
Water Hardness of250 ppm
(250 ppm 17.1 ppm/gr)= 14.6 gr.
-
7/30/2019 PN-XOS9500 Operation Manual Pure Water
7/14
Connect raw water supply line to the inlet valve connection.
Connect treated water outlet to service line. It is suggested
that pipe sizes be equal to or one size larger than the valve
connection.
Warning: When piping with copper, solder all piping as sub-
assemblies before installing. Internal valve damage can result from
the high heat of the torch.
It is recommended that manual isolation valves be installed on the
inlet and outlet piping along with a system bypass valve. This will
isolate the unit when service is required. (See Section 10 Typical
Piping Arrangement Drawing)
Connect Drain to a sump, drain trench or other open drain. Open
drains are required for taking samples and allowing a visual check.Avoid overhead pipe runs to drain facility, as undue back pressure
will affect the operation of injectors.
NOTE:All piping is to meet your state and local code.
Position brine tank approximately 6 from the softener tank on a
level smooth surface.
Connect the brine air check assembly in the salt/brine tank to the
brine suction (eductor) connection. If brine tank is located more
than six feet from softener tank, use one size larger tubing.
Tubing 5/8 may be installed from the brine tank overflow to drain.
This is a gravity drain designed to divert brine overflow to the drain
in the event of a malfunction which could cause overflow of the
brine tank.
Be sure inlet/outlet isolation valves are closed and by-pass valve
is open.
Conduct a visual check of all equipment for any damage that may
have occurred during shipping.
NOTE: If there is obvious damage to any equipment, it must benoted on the carriers Bill of Lading. Open and inspect the contents
of all closed crates, cartons, etc. and inspect for concealed damage.
The manufacturer is not liable for any damage during transit.
Position the equipment in its proper location, setting on a flat
surface. Level equipment as required; both tanks must be at the
same weight. Equipment out of plumb can exhibit poor flow
characteristics which will affect the performance and regeneration
of the system.
Load media if required. (See Section 7 Media Loading)
NOTE: Units 12 and smaller are shipped with media (resin and
gravel), distribution tube, and control valve installed.
Warning: If new distribution tube is to be installed, it must be cut
1/16 below top of tank (valve) mounting.
Unit should be positioned with the valve control facing forward.
Install 1-1/2 copper interconnecting pipe.
Check the main line war pressure. The softener is designed for a
minimum of 30 psi and a maximum of 120 psi working pressure. If
the line pressure exceeds this limit, a pressure-reducing valve
should be installed.
NOTE: Injector flow rates are based on approximately 40 to 60 psi
working pressure.
Maximum allowable water temperature of 120F. A 120 Vac, 60-
cycle electrical source must be available for operation of the
control timer.
SECTION 4
TENERGY WATER 2001 7
Installation Instructions
CLOSE-UP VIEW OF PROGRAM WHEEL (see Section 6 for its location and use)
BACKWASH60 MINUTE
(2 MIN. PER
PROGRAM WHEELFOR CONTROL OF
REGENERATION CYCLE
BRINE TANK REFILLFIELD ADJUSTED(16 MIN. SHOWN)
(2 MIN. PER HOLE)
FAST RINSE10 MINUTE
(2 MIN. PER PIN)
BRINE & RINSE60 MINUTE
(2 MIN. PER HOLE)
-
7/30/2019 PN-XOS9500 Operation Manual Pure Water
8/14
SECTION 5
TENERGY WATER 2001 8
Start-Up Instructions
The start-up of this system is relatively simple and should be easily
accomplished. It is suggested that the start-up procedure be reviewed
thoroughly until each step is fully understood.
Tank #1 will have control valve.
Tank #2 will have tank adapter.
Remove Control Box Cover. Notice the indicator located on right side
of housing with two arrows that tell you the control valve position
during regeneration and which tank is in service. Do not plug unit into
electrical outlet yet.
On units without bypass lever, close
inlet/outlet isolation valves and open
bypass valve and flush piping. Once
piping has been flushed, open inlet/
outlet isolation valves and close by-
pass valve. Let water flow into the
mineral tank. When water flow stops,
open cold water tap nearby and let
run until system is relieved of air
pressure.
Next, plug unit into electrical outlet.
DO NOT INSERT METER CABLE YET.
Turn manual regeneration knob so that indicator mentioned above
shows valve is in backwash position (See Section 6 Manual
Regeneration) to relieve any air from the vessel.
With a water hose, fill the brine tank with approximately 6 of water.
Let cycle timer automatically switch to second position brine
in/slow rinse. Observe brine (water) draw from brine tank. Once
water drops to a certain level a ball check in the brine well closes,
thus not allowing air in the system.
Move manual regeneration knob to the next position fast rinse.
Allow water to go to drain. Water color should be clear at the end
of step 10 minutes.
Timer will automatically move to next position brine refill. Once
brine refill step is complete, check water in brine tank. Water level
should be approximately 1 above grid plate. If not, adjust brine
refill time accordingly. (See Section 6 How to Change
Regeneration Cycle Times)
Allow timer to return to home (Service) position automatically.
Once back in the service position, cycle the control valve again intothe backwash position. The tanks will switch and relieve any air
from the other vessel. Slowly cycle the control valve back to the
service position. (See Section 6 Manual Regeneration)
Unplug unit from electrical outlet when setting the gallon wheel.
Knowing the amount of resin per each tank and the salt setting per
regeneration, calculate the gallons available. (See Section 3
Exchange Capacity Data)
The 9500 valve regenerates with soft water from the other tank.
Water used for regeneration must be subtracted from total gallons
available. (See Section 3 Eductor and Flow Control Data)
Example: 20 Diameter Tank
A. Backwash . . . . . . . . . . . . . . . .(10 min) (12 gpm) = 120.0 gal.
B. Brine In/Slow Rinse . . . . . . . . (42 min) (1.95 gpm) = 81.9 gal.
C. Rapid Rinse . . . . . . . . . . . . . .(10 min) (12 gpm) = 120.0 gal.
D. Brine Fill . . . . . . . . . . . . . . . . . (10 min) (2.0 gpm) = 20.0 gal.
Regeneration Water Used 341.9 gal.
Subtract 342 from total gallons available.
INDICATOR
TIMER FACE ILLUSTRATIONLOWER WHEEL HAS/IS REGENERATION KNOB
-
7/30/2019 PN-XOS9500 Operation Manual Pure Water
9/14
SECTION 6
Program Setting
Procedure
TENERGY WATER 2001 9
SET GALLONS CALCULATED
Lift (pull hub toward you) the gallon label wheel (the inner dial of
the meter program wheel) so you can rotate meter program wheel
freely.
Position the white dot on the meter program wheel opposite the
approximate number of gallons calculated.
NOTE: There is a slight delay time from the time the meter zeros
out and when the cycle starts. Units using the 1/15 rpm motor,
82 minute regeneration time available (tanks 6 thru 12) have a
9 minute delay. Units using the 1/30 rpm motor, 180 minute regen-
eration time available (tanks 13 and larger) have an 18 minute
delay. Typically on residential equipment this delay period is
not critical. On commercial applications, this must be taken into
consideration and continuous flows for 9 minutes or 18 minutes
should be subtracted from water available.
NOTE: If during the setting of your meter wheel, or your water
usage is such that the capacity of the in-service unit is exhausted
before the timer is back into service; the trip arm will advance past
the position shown and the Meter Reset Stop will stall in the
12:00 position. No regenerations will be initiated. To get unit back
to proper position: 1st turn manual regeneration knob into
backwash, and 2nd lift the reset plate up and allow the meter
program wheel to reset itself.
Insert meter cable into meter and controller.
Check that both inlet/outlet isolation valves are open and the
bypass valve is closed.
Check that system bypass valve is in the service position. Plug unit
in electrical outlet.
Unit is ready for service.
HOW TO SET THE
REGENERATION CYCLE PROGRAM
The regeneration cycle program on your water conditioner has
been factory preset; however, portions of the cycle or program may
be lengthened or shortened in time to suit local conditions.
The timer face plate is hinged. To expose cycle program wheel,
grasp timer in lower right-hand corner and pull, releasing snapretainer and swinging timer to the left.
To change the regeneration cycle program, the program wheel
must be removed. Grasp program wheel and squeeze protruding
lugs towards center; lift program wheel off timer. (Switch arms may
require movement to facilitate removal).
Return timer to closed position engaging snap retainer in back
plate. Make certain all electrical wires locate above snap retainer post.
How to Change the Length of the Backwash Time:
The program wheel as shown in the drawing is in the service
position. As you look at the numbered side of the program wheel,
the group of pins starting at zero determines the length of time your
unit will backwash.
FOR EXAMPLE: If there are six pins in this section, the time of
backwash will be 12 min. (2 min. per pin). To change the length of
backwash time, add or remove pins as required. The number of
pins times two equals the backwash time in minutes.
-
7/30/2019 PN-XOS9500 Operation Manual Pure Water
10/14
SECTION 7
How to Change the Length of Brine and Rinse Time:
The group of holes between the last pin in the backwash sectionand the second group of pins determines the length of time that
your unit will brine and rinse (2 min. per hole).
To change the length of brine and rinse time, move the rapid rinse
group of pins to give more or fewer holes in the brine and rinsesection. Number of holes times two equals brine and rinse time in
minutes.
How to Change the Length of Rapid Rinse:
The second group of pins on the program wheel determines thelength of time that your water conditioner will rapid rinse (2 min.
per pin).
To change the length to rapid rinse time, add or remove pins at the
higher numbered end of this section as required. The number ofpins times two equals the rapid rinse time in minutes.
How to Change the Length of Brine Tank Refill Time:
The second group of holes on the program wheel determines the
length of time that your water conditioner will refill the brine tank (2
min. per hole).To change the length of refill time, move the two pins at the end ofthe second group of holes as required.
The regeneration cycle is complete when the outer micro-switch istripped by the two pin set at end of the brine tank refill section. The
program wheel, however, will continue to rotate until the innermicro-switch drops into the notch on the program wheel.
MANUAL REGENERATION
Turn the manual regeneration knob clockwise until the service
position indicator is in the 3:00 position. This slight movement ofthe Manual Regeneration Knob engages the program wheel andstarts the reset motor.
The black center knob will make one revolution.
Warning: When you manually move cycle timer to different
regeneration steps you must wait until positioning of upper andlower piston has stopped before advancing to next step. Ifadvanced too fast the control will not advance to the service
position or to any other position. To correct this, rotate the manualknob back to service and start again.
When manual regeneration is engaged, position of regeneration
cycle is shown by the arrow on the position indicator.
MediaLoadingMedia loading or replacement is sometimes required for units in thefield. Replacement of media is relatively simple, if the following pro-
cedure is followed:
Replacement of Media
Close inlet/outlet isolation valve of unit to be rebedded.
Manually turn timer dial to backwash position (See Section 6
Manual Regeneration) to relieve vessel pressure.
Unplug electrical connection of unit.
Disconnect inlet, outlet, drain, and brine lines. Unscrew valve headfrom tank.
Remove distribution tube from tank and visually inspect for any
damage or wear replace if necessary.
Warning: If new distribution tube is to be installed, it must be cut1/16 below top of tank (valve) mounting connection.
Empty tank into resin trap/strainer, holding the resin/gravel andallowing water to flow to drain. Dispose of used media. Relocatetank in original location.
NOTE: Disposal of resin must meet local and state regulations.
Loading of Media
Install distribution tube in mineral tank. Place a cap or tape over the
open end of distributor to prevent any media from entering. Fill tankwith approximately one-third water to act as a buffer.
Slowly pour the required amount of media in each vessel: Gravel to be loaded first
Resin to be loaded second
Multiple tank system, divide the gravel and resin quantitiesequally per number of vessels.
Clean top of tank and tank threads of any resin or gravel. Removecap or tape from distribution tube and clean.
Visually check and clean valve and distribution O Ring of any
foreign matter and lubricate with silicone or soap.
NOTE: Do not use Vaseline or grease.
Locate control valve on tank making certain riser tube is locatedproperly. Tighten valve to tank.
Reposition and level tank if necessary to assure proper alignment.
Connect inlet, outlet, drain, and brine connections.
The unit is ready for start-up. (See Section 5)
TENERGY WATER 2001 10
-
7/30/2019 PN-XOS9500 Operation Manual Pure Water
11/14
SECTION 8
TENERGY WATER 2001 11
UNIT ASSEMBLY
ITEM NO. PARTNO. REQD NO. DESCRIPTION
1 1 K4028 9500 Control Valve w/1-1/2 Meter
2 Specify A4000 C1 Dark softener Resin
3 Specify A7005 #20 Flint Gravel4 Specify A7006 1/4 x 1/8 Gravel
5 2 C2020-4 12 x 52 - 4 PI Blue Tank w/RB
2 C2023 14 x 42 - 4 PI Blue Tank w/RB
2 C2025 16 x 65 - 4 PI Blue Tank w/RB
2 C2026 20 x 62 - 4 PI Blue tank w/RB
2 C2028 22 x 54 - 4 PI Natural Tank w/Base
2 C2029 22 x 60 - 4 Pl Natural Tank w/Base
2 C1031 24 x 72 - 4
6 2 D5007 1-1/2 - 72 w/R2A-2 Screen (cut to fit)
7 1 G2002 18 x 40 Blue Tank
1 G2003 24 x 41 Black Tank
1 G2004 24 x 50 Black Tank
1 G2007 30 x 48 Black Tank
8 1 H1072 TP500 Grid Plate1 H1075 24 Grid Plate
9 1 H1040-36 3-1/2 Brine Well x 36
1 H1071 6 Well x 48 H.
10 1 H1015 3-1/2 Brine Well Cap
1 H1024 6 Brine Well Cap
11 1 H1018 Overflow Set
12 1 Brine Assembly
13 1 K4560366 1 F x 3/4 F Brass Flow Control
1 V2003-A 1 PVC Flow Control
BRINE PICKUP SYSTEM
ASSEMBLY
1 1 H7076-28 Brine Assembly 33 Tank
H7076-36 Br ine Assembly 40 Tank
1A 3/8 X 28 Rigid PVC
(for 28 brine wells)
3/8 x 30 Rigid PVC
(for 30 brine wells)
3/8 x 36 Rigid PVC
(for 36 brine wells)
1B Body, Drilled Less Ball
1C Quad Ring
1D Float Rod - 14 Float Rod - 241E Float Grommet (2 required)
1F Bell Type Float
1G Guide, Lock, Adaptor
1H Washer
1J Crown Nut
1K Ball Cage
1L Air Check Ball
1M Quad Cup Seat
1N Stem
1P Spool Seat
2 1 I4366J 3/8 x 3/8 Union Elbow
NOTE: Brine System Sold as Assemblies Only.
ITEM NO. PARTNO. REQD NO. DESCRIPTION
-
7/30/2019 PN-XOS9500 Operation Manual Pure Water
12/14
PROBLEM CAUSE CORRECTION
1. LOSS OF RESIN A. Broken distribution tube A. Replace distribution tube.
B. Inlet/outlet connection reversed B. Reconnect inlet/outlet connection properly.
2. SOFTENER FAILS TO A. Electrical service to unit A. Assure permanent electrical serviceREGENERATE interrupted. (check fuse, plug, pull chain, or switch).
B. Timer defective B. Replace timer.
C. Power failure C. Reset time of day.
3. HARD WATER A. Bypass valve open A. Close bypass valve.
B. No salt in brine tank B. Add salt to brine tank and maintain salt levelabove water level.
C. Injector screen plugged C. Clean injector screen.
D. Insufficient water flowing D. Check brine tank fill time and clean brine lineinto brine tank flow control if plugged.
E. Hot water tank hardness E. Repeated flushing of the hot water tank is
required.
F. Leak at distributor tube F. Make sure distributor tube is not cracked.Check O Ring and tube pilot.
G. Internal valve leaking G. Replace seals and spacers and/or piston.
4. UNIT USED TOO MUCH SALT A. Improper salt setting A. Check salt usage and salt setting.
B. Excessive water in brine tank B. See Problem No. 8.
5. LOSS OF WATER PRESSURE A. Iron buildup in line to A. Clean line to water conditioner.water conditioner
B. Iron buildup in water conditioner B. Clean control and add mineral cleaner tomineral bed.
Increase frequency of regeneration.
C. Inlet of control plugged due to C. Remove piston and clean control.foreign material broken loose from
pipes by recent work done onplumbing system
6. LOSS OF MINERAL A. Air in water system A. Assure that well system has proper
THROUGH DRAIN LINE air eliminator control.
Check for dry well condition.
7. IRON IN CONDITIONED WATER A. Fouled mineral bed A. Check backwash, brine draw, and brine tank fill.
Increase frequency of regeneration.
Increase backwash time.
8. EXCESSIVE WATER A. Plugged drain line flow control A. Clean flow control.
B. Plugged injector system B. Clean injector and screen.
C. Injector screen plugged C. Replace timer.
D. Foreign material in brine valve D. Replace brine valve seat and clean valve.
E. Foreign material in E. Clean brine line flow control.
brine line flow control
TENERGY WATER 2001 12
SECTION 9
Troubleshooting
IN BRINE TANK
-
7/30/2019 PN-XOS9500 Operation Manual Pure Water
13/14
13. SOFTENER DELIVERS A. Reserve capacity exceeded A. Check salt dosage requirements and resetHARD WATER program wheel to provide additional reserve.
B. Program wheel not rotating B. Pull cable out of meter cover and rotate
with meter output manually. Program wheel must move withoutbinding and clutch must give positive clicks
when program wheel strikes regenerationstop. If it does not, replace timer.
C. Meter not measuring flow C. Check flow output by observing rotation of small gear on front of timer. Each tooth totooth is approximately 30 gallons; if not,
replace meter.
NOTE: Program wheel must not be against
regeneration stop for this check.
PROBLEM CAUSE CORRECTION
SOFTENER FAILS TO DRAW BRINE A. Drain line flow control plugged A. Clean drain l ine flow control.
B. Injector plugged B. Clean injector.
C. Injector screen plugged C. Clean screen.
D.L ine pressure too low D. Increase line pressure to 20 P.S.I.
E. Internal control leak E. Change seals, spacers, and piston assembly.
10. CONTROL CYCLES A. Broken or shorted switch A. Determine if switch or timer is faulty andCONTINUOUSLY replace it, or replace complete power head.
11. DRAIN FLOWS CONTINUOUSLY A. Valve not programming A. Check timer program and positioning of correctly control.
Replace power head assembly if notpositioning properly.
B. Foreign matter in control B. Remove power head assembly and inspect
bore.Remove foreign material and check control in
various regeneration positions.
C. I nternal control leak C. Replace seals and piston assembly.
12. BRINE TANK FILLS DURING A. Clogged drain A. Replace drain line.
B. Internal piston seal leaks B. Replace seals in piston assembly.
OPTIONAL WATER METER
TENERGY WATER 2001 13
9.
BRINE DRAW STEP
Troubleshooting continued
-
7/30/2019 PN-XOS9500 Operation Manual Pure Water
14/14
Manufactured by: Tenergy Water, LLC, New Britain, Connecticut
DISTRIBUTED BY:
INSTALLATIONTYPICAL PIPING
OPTIONAL
DUPLEX INSTALLATIONTYPICAL PIPING
TYPICAL INSTALLATIONBRINE TANK ASSEMBLY
(18 Diameter)
TYPICAL INSTALLATIONBRINE TANK ASSEMBLY(24 Diameter and Larger)
SECTION 10