PN-XOS9500 Operation Manual Pure Water

download PN-XOS9500 Operation Manual Pure Water

of 14

Transcript of PN-XOS9500 Operation Manual Pure Water

  • 7/30/2019 PN-XOS9500 Operation Manual Pure Water

    1/14

    OPERATING MANUALLIGHT COMMERCIAL WATER SOFTENER

    LCTA 150 SERIESWith 9500 Twin Alternating-Top Mount Control Valve

    MODEL NO. Meter

    Products, equipment, service. We are the answer.

    Tenergy Water

  • 7/30/2019 PN-XOS9500 Operation Manual Pure Water

    2/14

    1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . .2

    2 PRINCIPLES OF

    Softening - Ion Exchange . . . . . . . . . . . . . . . . .3Regeneration Steps and Purpose . . . . . . . . . .3

    3 SPECIFICATIONS

    Specification Sheet . . . . . . . . . . . . . . . . . . . . .4

    Softener Specification . . . . . . . . . . . . . . . . . . .5

    Softener Data . . . . . . . . . . . . . . . . . . . . . . . . .5

    Tenergy Brand Resin Data . . . . . . . . . . . . . . . .6

    Exchange Capacity Data . . . . . . . . . . . . . . . . .6

    Eductor & Flow Control Data . . . . . . . . . . . . . .6

    Brine (Salt) Data . . . . . . . . . . . . . . . . . . . . . . .6

    4 INSTALLATION INSTRUCTIONS . . . . . . . . . . . . . .7

    5 START-UP INSTRUCTIONS

    Meter Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

    6 PROGRAM SETTING PROCEDURE

    How to Set the Regeneration Cycle . . . . . . . . .9

    Manual Regeneration . . . . . . . . . . . . . . . . . . .10

    7 MEDIA LOADING . . . . . . . . . . . . . . . . . . . . . . . . .10

    8 PARTS LISTS . . . . . . . . . . . . . . . . . . . . . . . . . . . .11

    1-1/2 Meter Assembly . . . . . . . . . . . . . . . . . . . .

    . . . . . .see Model 9500 Service Manual, pg. 19

    Drive Assembly . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . .see Model 9500 Service Manual, pg. 13

    Timer Assembly . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . .see Model 9500 Service Manual, pg. 21

    Control Valve Assembly . . . . . . . . . . . . . . . . . . .

    . . . . . .see Model 9500 Service Manual, pg. 15

    1700 Brine System Assembly . . . . . . . . . . . . . .

    . . . . . .see Model 9500 Service Manual, pg. 17

    1600 Brine System Assembly . . . . . . . . . . . . . .

    . . . . . .see Model 9500 Service Manual, pg. 16

    9 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . .12-13

    DRAWINGSElectrical Diagram . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . .see Model 9500 Service Manual, pg. 26

    Valve Drawing . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . .see Model 9500 Service Manual, pg. 26

    Typical Piping . . . . . . . . . . . . . . . . . . . . . . .back

    Optional-Duplex Piping Assembly . . . . . . . .back

    Brine Tank Assemblies . . . . . . . . . . . . . . . .back

    Introduction

    Tenergy Water Light Commercial water softeners are assembled

    of the highest quality parts available. The LCTA 150 Series is a

    twin tank, single controller, metered system available with 1-1/2

    connections, with different size units to meet your needs.

    The Mineral Tank is a noncorrosive fiberglass tank with a one-piece

    thermoplastic inner liner in compliance with FDA under 21 CFR -

    Part 177. The tank has a working pressure of 150 PSI, or maximum

    temperature of 120F.

    The exchange media is a polystyrene strong acid cation resin in

    the sodium form. It has a maximum exchange capacity of 30,000

    grains per cubic feet, when regenerated with 15 lbs. salt.

    The valve body is constructed of high quality brass to assure long

    life. The piston is Teflon coated to prevent wear and allow foreign

    particles to pass without damage to the piston.

    The unit is a twin alternating system, where one unit is in service

    and the other unit regenerated and in standby. Regeneration cycle

    is fully adjustable to meet your changing needs.

    Regeneration on the LCTA 150 Series is initiated by the 9500

    Econominder Water Meter. Once a preset number of gallons flow

    through the system, and the meter zeroes out, the unit in service

    starts to regenerate and the unit in standby is put into service.

    Once the unit completes its regeneration cycle, it automatically

    goes into standby.

    10

    Section Description Page

    LCTA 150 SERIES

    TWIN ALTERNATING WATER SOFTENER

    CONTENTS SECTION I

    TENERGY WATER 2001 2

    Copyright 2000 by TENERGY WATER, LLC. All rights reserved. Except as permitted under the United States Copyright Act of 1976, no part of this publication may bereproduced or distributed in any form or by any means, stored in a data base or retrieval system, without the prior written permisssion of TENERGY WATER, LLC.

  • 7/30/2019 PN-XOS9500 Operation Manual Pure Water

    3/14

    Softening of water by the ion exchange process involves the

    exchange or substitution of the hardness minerals, chiefly calcium

    and magnesium, for sodium minerals. The exchange is made

    possible because the minerals are ionic in nature (often called

    ionized impurities), which means they have an electrical charge.

    The ion exchange process is based on the fact that like charges

    repel one another, and unlike charges attract.

    Calcium and magnesium ions in water are actually dissolved rock.

    They have been dissolved by water, the universal solvent. As the

    water trickles down through strata of rock and soil it dissolves the

    calcium and magnesium deposits. This dissolved rock eventually

    finds its way into an underground aquifer and when water from the

    aquifer is pumped to the surface, it contains the dissolved hardness

    minerals of calcium and magnesium and is said to be hard water.

    An ion exchange softener exchanges the hardness minerals,

    calcium and magnesium, for sodium, from the softener resin.

    Sodium is less objectionable because it does not build up on

    surfaces as scale deposits.

    All three minerals are positively charged ions called cations. The

    exchange takes place by passing water containing hardness

    minerals over a man-made ion exchange resin contained in a suit-

    able tank. The resin, polystyrene divinyl benzene in most modern

    softeners, consists of millions of tiny plastic beads, all of which

    contain many negatively charged exchange sites attracting positivecations. When the resin is in the regenerated state these negatively

    charged exchange sites hold positively charged sodium cations.

    As the calcium and magnesium contact the resin beads in their

    travel through the resin tank, they displace the sodium ions from

    the exchange sites. During the ion exchange process, relatively

    small amounts of other strongly charged cations such as iron and

    manganese are also removed along with the calcium and

    magnesium.

    Ion exchange is possible for two reasons: (1) All cations do not

    have the same strength of positive charge and (2) the resin prefers

    the more strongly charged cations calcium and magnesium than it

    does the weaker sodium cations.

    The exchanged sodium cations pass downward through the resin

    bed and out the softener outlet; thus, the softener delivers soft

    water.

    Eventually, all of the resin exchange sites are occupied by calcium

    and magnesium and no further exchange can take place. The resin

    is said to be exhausted and must be regenerated.

    The softener resin is regenerated with a dilute brine

    solution of sodium chloride (common salt) and water. During

    regeneration the flow of service water from the softener is first

    stopped. Brine is drawn from the brine tank mixing with a separate

    stream of water. The brine solution flows downward through the

    resin, contacting the resin beads loaded with calcium and

    magnesium ions. Even though the calcium and magnesium are

    more strongly charged than the sodium, the concentrated brine

    solution contains literally billions of the more weakly charged

    sodium ions which have the power to displace the smaller

    number of calcium and magnesium ions. When the calcium and

    magnesium ions are displaced, the positive sodium ions are attracted

    to the negative exchange sites. Eventually, all sites are filled by

    sodium ions and the resin is said to be regenerated and ready for

    the next softening cycle.

    REGENERATION STEPS AND PURPOSE

    Tank Switching When unit in service depletes the pre-set volume

    of water and regeneration is initiated, the service flow automatically

    switches from the unit exhausted to the unit that was in standby.

    Backwash Flow through the resin bed is reversed. Water flows

    upward, expanding and agitating the resin bed. This action loosens

    sediment that may have collected on the resin during service andis flushed to drain. Resin fines which developed during service are

    also removed.

    Brine In Brine is educted from the brine tank, passes through the

    resin during service, and is flushed to drain. Resin fines, which

    developed during service, are also removed.

    Slow Rinse After the brine has been introduced, brine air check

    is closed, allowing water to flow through eductor at a slow rate,

    displacing the brine remaining in the resin bed. This insures good

    utilization of the brine.

    Fast Rinse The resin is now flushed downward at a set flow rate.

    This resettles the bed and rinses out any remaining brine left in the

    resin bed.

    Brine Fill Brine tank is refilled with a preset amount of water to

    dissolve salt for the next regeneration.

    After the brine fill step the unit is ready for service, thus

    completing the regeneration cycle. The unit then places itself into

    the standby mode.

    SECTION 2

    TENERGY WATER 2001 3

    Principles of Softening Ion Exchange

  • 7/30/2019 PN-XOS9500 Operation Manual Pure Water

    4/14

    Specifications

    SPECIFICATIONS SHEET (to be filled out by installer)

    Job No.

    Model No.

    Water Test

    Capacity Per Unit

    Gallons Per Regeneration Reserve Gallons

    Mineral Tank Size: Diameter Height

    Brine Tank Size & Salt Setting Per Regeneration

    Control Valve Specifications

    1. Type of Timer

    Meter Initiated

    2. Timer Program Settings

    a) Backwash min.

    b) Brine & Slow Rinse min.

    c) Rapid Rinse min.

    d) Brine Tank Refill min.

    3. Drain Line Flow Controller gpm

    4. Brine Line Flow Controller gpm

    5. Injector Size #

    SECTION 3

    TENERGY WATER 2001 4

  • 7/30/2019 PN-XOS9500 Operation Manual Pure Water

    5/14

    MODEL # SIZE SIZE CU. FT. 1/4x1/8 #20 SIZE FILL MAX MAX MIN GPM PSI GPM FLOOR HEIGHT

    TT60F 1-1/2 12x52 2 30 24x41 600 60K 40K 30 12 25/33 15/25 5 24x42 63

    TT90F 1-1/2 14x65 3 60 24x41 600 90K 60K 45 18 26/37 15/25 7 24x44 76TT120F 1-1/2 16x65 4 80 24x41 600 120K 80K 60 24 29/40 15/25 9 24X46 76

    TT150F 1-1/2 20X62 5 100 24X50 800 150K 100K 75 30 37/48 15/25 12 24x50 73

    TT180F 1-1/2 21x62 6 100 24x50 800 180K 120K 90 36 35/47 15/25 12 24x52 65

    TT210F 1-1/2 21x62 7 100 24x50 800 210K 140K 105 42 34/46 15/25 15 24x52 71

    TT240F 1-1/2 24x72 8 100 100 30x48 1200 240K 160K 120 48 37/49 15/25 15 30x69 83

    TT300F 1-1/2 24x72 10 100 100 39x48 2000 300K 200K 150 60 35/47 15/25 15 39x69 83

    SERV DROP BKW

    BRINE TANKMINERAL TANK

    TANK

    PIPE

    PART # DESCRIPTION SIZE WEIGHT

    9500 Twin/Alt 1-1/2 MeterM2218 TT60F95 Twin Alt Softener 1-1/2 370

    M2220 TT90F95 Twin Alt Softener 1-1/2 550

    M2222 TT120F95 Twin Alt Softener 1-1/2 720

    M2224 TT150F95 Twin Alt Softener 1-1/2 900

    M2226 TT180F95 Twin Alt Softener 1-1/2 1115

    M2228 TT210F95 Twin Alt Softener 1-1/2 1215

    M2230 TT240F95 Twin Alt Softener 1-1/2 1535

    M2235 TT300F95 Twin Alt Softener 1-1/2 1750

    SOFTENER DATA - Commercial

    SOFTENER SPECIFICATIONS

    TENERGY WATER 2001 5

    PIPE RESIN SALT

    SOFTENINGCAPACITY1

    LBS. SALT PERREGENERATION2

    FLOW RATE & PRESSURE SPACEREQUIRED

    MIN3

    KEY TO THE NOTATIONS ABOVE:

    1. 2. All units from Tenergy Water are set at minimum salt settings.

    3. Use the minimum capacity when sizing units.

    4. Duplex systems require approximately twice the floor length space.

    RANGES:1-1/2 Meter: Standard Range = 10,625 Gallons1-1/2 Meter: Extended Range = 53,125 Gallons

    Above information subject to change or correction as required by the manufacturer.

    Capacities are based on resin manufacturers data and are dependentupon influent water TDS, temperature, bed depth, pressure, and flowrates. The raw water is to be free of oil, color, and turbidity.

    4 4 4

    4UNDERBED

  • 7/30/2019 PN-XOS9500 Operation Manual Pure Water

    6/14

    TANK TANK BRINE PER SALT PER INCHDIA. AREA INCH OF HEIGHT SATURATED BRINE(IN.) (SQ. FT.) (GALLONS)* SOLUTION (LBS)

    18 1.76 1.10 2.8620 2.16 1.33 3.4824 3.14 1.95 5.0730 4.90 3.04 7.9036 7.06 4.40 11.442 9.62 5.97 15.548 12.57 7.8 20.2

    54 15.90 9.9 25.260 19.63 12.2 31.866 23.76 14.7 38.272 28.27 17.5 45.5

    *without salt in tank - brine only

    It is recommended that a good grade of solar or pellet salt be used. One gallon warm water (80F) will dissolve a maximum of 2.6 lbs. of salt. One gallon colder water will dissolve a maximum of 2.4 lbs. of salt One gallon of saturated brine weighs 10.74 lbs.

    MODEL # INJECTOR RATE B.L.F.C.1 D.L.F.C.2

    TENERGY WATER 2001 6

    GENERAL DESCRIPTION

    Ionic form, as delivered Na+

    Functional Group Sulfonic Acid

    Matrix Polystyrene - DVB

    Structure Gel

    Appearance Dark

    PHYSICAL AND CHEMICAL PROPERTIES

    Bead Size (U.S. Standard Mesh) min. 90% 16-50Bead Size Range mm 0.41-0.51

    Uniformity coefficient Maximum 1.7

    Bead Integrity min. % Whole Beads 95

    Bulk Density ( 5%) lbs/ft3 53

    True Density approx. g/ml 1.29

    Water Retention % wt. 42-46

    Total Capacity min. eq/l 2.0

    Volume Change Na max. % 5-10

    TYPICAL OPERATING PARAMETERS

    Operating Temperature max. F 248

    Operating pH Range 0-14

    Bed Depth min. inches 24

    Pressure drop (59F) per gpm/ft2 Approx. psi/ft 0.16Flow Velocity service up to gpm/ft2 16

    Flow Velocity backwash (68F) gpm/ft2 6-7

    Flow Velocity type NaCl

    Regenerant level approx. lbs/ft3 6-15

    Regenerant concentration % 10

    Flow Velocity regeneration gpm/ft3 0.50-1

    Flow Velocity rinsing approx. gpm/ft3 1-5

    Rinse Water Requirement approx. gal/ft3 resin 20-40

    Bed Expansion approx. % per gpm/ft3 (68F) 10

    Freeboard (as % of resin volume) 50-100

    TENERGY BRAND SOFTENER RESIN DATA

    EDUCTOR AND FLOW CONTROL DATA BRINE (SALT) DATA

    TT 60F95 #3 Yellow 1.10 gpm 1.0 gpm 5.0 gpm

    TT 90F95 #3 Yellow 1.10 gpm 1.0 gpm 5.0 gpm

    TT120F95 #3 Yellow 1.10 gpm 1.0 gpm 7.0 gpm

    TT 150F95 #3C Yellow 1.30 gpm 2.0 gpm 12.0 gpm

    TT 180F95 #3C Yellow 1.30 gpm 2.0 gpm 12.0 gpm

    TT 210F95 #4C Green 1.79 gpm 2.0 gpm 12.0 gpm

    TT 240F95 #4C Green 1.79 gpm 2.0 gpm 15.0 gpm

    TT 300F95 #4C Green 1.79 gpm 2.0 gpm 15.0 gpm

    SLOW RINSE

    KEY TO THE NOTATIONS ABOVE:

    1. Brine Line Flow Control (Refill Brine Tank)2. Drain Line Flow Control (Backwash and Rapid Rinse Flow Rate)

    Due to varying water conditions, tank sizes, and water pressures, the above settings shouldbe used only as a guideline.

    EXCHANGECAPACITY DATA

    20,000 grain approx. per cu. ft.6 lbs. salt-sodium chloride

    25,000 grain approx. per cu. ft.8 lbs. salt-sodium chloride

    27,000 grain approx. per cu. ft.10 lbs. salt-sodium chloride

    30,000 grain approx. per cu. ft.15 lbs. salt-sodium chloride

    Note: To convert parts permillion (ppm) or milligramsper liter (mpl) to grains divideby 17.1.

    Example:

    Water Hardness of250 ppm

    (250 ppm 17.1 ppm/gr)= 14.6 gr.

  • 7/30/2019 PN-XOS9500 Operation Manual Pure Water

    7/14

    Connect raw water supply line to the inlet valve connection.

    Connect treated water outlet to service line. It is suggested

    that pipe sizes be equal to or one size larger than the valve

    connection.

    Warning: When piping with copper, solder all piping as sub-

    assemblies before installing. Internal valve damage can result from

    the high heat of the torch.

    It is recommended that manual isolation valves be installed on the

    inlet and outlet piping along with a system bypass valve. This will

    isolate the unit when service is required. (See Section 10 Typical

    Piping Arrangement Drawing)

    Connect Drain to a sump, drain trench or other open drain. Open

    drains are required for taking samples and allowing a visual check.Avoid overhead pipe runs to drain facility, as undue back pressure

    will affect the operation of injectors.

    NOTE:All piping is to meet your state and local code.

    Position brine tank approximately 6 from the softener tank on a

    level smooth surface.

    Connect the brine air check assembly in the salt/brine tank to the

    brine suction (eductor) connection. If brine tank is located more

    than six feet from softener tank, use one size larger tubing.

    Tubing 5/8 may be installed from the brine tank overflow to drain.

    This is a gravity drain designed to divert brine overflow to the drain

    in the event of a malfunction which could cause overflow of the

    brine tank.

    Be sure inlet/outlet isolation valves are closed and by-pass valve

    is open.

    Conduct a visual check of all equipment for any damage that may

    have occurred during shipping.

    NOTE: If there is obvious damage to any equipment, it must benoted on the carriers Bill of Lading. Open and inspect the contents

    of all closed crates, cartons, etc. and inspect for concealed damage.

    The manufacturer is not liable for any damage during transit.

    Position the equipment in its proper location, setting on a flat

    surface. Level equipment as required; both tanks must be at the

    same weight. Equipment out of plumb can exhibit poor flow

    characteristics which will affect the performance and regeneration

    of the system.

    Load media if required. (See Section 7 Media Loading)

    NOTE: Units 12 and smaller are shipped with media (resin and

    gravel), distribution tube, and control valve installed.

    Warning: If new distribution tube is to be installed, it must be cut

    1/16 below top of tank (valve) mounting.

    Unit should be positioned with the valve control facing forward.

    Install 1-1/2 copper interconnecting pipe.

    Check the main line war pressure. The softener is designed for a

    minimum of 30 psi and a maximum of 120 psi working pressure. If

    the line pressure exceeds this limit, a pressure-reducing valve

    should be installed.

    NOTE: Injector flow rates are based on approximately 40 to 60 psi

    working pressure.

    Maximum allowable water temperature of 120F. A 120 Vac, 60-

    cycle electrical source must be available for operation of the

    control timer.

    SECTION 4

    TENERGY WATER 2001 7

    Installation Instructions

    CLOSE-UP VIEW OF PROGRAM WHEEL (see Section 6 for its location and use)

    BACKWASH60 MINUTE

    (2 MIN. PER

    PROGRAM WHEELFOR CONTROL OF

    REGENERATION CYCLE

    BRINE TANK REFILLFIELD ADJUSTED(16 MIN. SHOWN)

    (2 MIN. PER HOLE)

    FAST RINSE10 MINUTE

    (2 MIN. PER PIN)

    BRINE & RINSE60 MINUTE

    (2 MIN. PER HOLE)

  • 7/30/2019 PN-XOS9500 Operation Manual Pure Water

    8/14

    SECTION 5

    TENERGY WATER 2001 8

    Start-Up Instructions

    The start-up of this system is relatively simple and should be easily

    accomplished. It is suggested that the start-up procedure be reviewed

    thoroughly until each step is fully understood.

    Tank #1 will have control valve.

    Tank #2 will have tank adapter.

    Remove Control Box Cover. Notice the indicator located on right side

    of housing with two arrows that tell you the control valve position

    during regeneration and which tank is in service. Do not plug unit into

    electrical outlet yet.

    On units without bypass lever, close

    inlet/outlet isolation valves and open

    bypass valve and flush piping. Once

    piping has been flushed, open inlet/

    outlet isolation valves and close by-

    pass valve. Let water flow into the

    mineral tank. When water flow stops,

    open cold water tap nearby and let

    run until system is relieved of air

    pressure.

    Next, plug unit into electrical outlet.

    DO NOT INSERT METER CABLE YET.

    Turn manual regeneration knob so that indicator mentioned above

    shows valve is in backwash position (See Section 6 Manual

    Regeneration) to relieve any air from the vessel.

    With a water hose, fill the brine tank with approximately 6 of water.

    Let cycle timer automatically switch to second position brine

    in/slow rinse. Observe brine (water) draw from brine tank. Once

    water drops to a certain level a ball check in the brine well closes,

    thus not allowing air in the system.

    Move manual regeneration knob to the next position fast rinse.

    Allow water to go to drain. Water color should be clear at the end

    of step 10 minutes.

    Timer will automatically move to next position brine refill. Once

    brine refill step is complete, check water in brine tank. Water level

    should be approximately 1 above grid plate. If not, adjust brine

    refill time accordingly. (See Section 6 How to Change

    Regeneration Cycle Times)

    Allow timer to return to home (Service) position automatically.

    Once back in the service position, cycle the control valve again intothe backwash position. The tanks will switch and relieve any air

    from the other vessel. Slowly cycle the control valve back to the

    service position. (See Section 6 Manual Regeneration)

    Unplug unit from electrical outlet when setting the gallon wheel.

    Knowing the amount of resin per each tank and the salt setting per

    regeneration, calculate the gallons available. (See Section 3

    Exchange Capacity Data)

    The 9500 valve regenerates with soft water from the other tank.

    Water used for regeneration must be subtracted from total gallons

    available. (See Section 3 Eductor and Flow Control Data)

    Example: 20 Diameter Tank

    A. Backwash . . . . . . . . . . . . . . . .(10 min) (12 gpm) = 120.0 gal.

    B. Brine In/Slow Rinse . . . . . . . . (42 min) (1.95 gpm) = 81.9 gal.

    C. Rapid Rinse . . . . . . . . . . . . . .(10 min) (12 gpm) = 120.0 gal.

    D. Brine Fill . . . . . . . . . . . . . . . . . (10 min) (2.0 gpm) = 20.0 gal.

    Regeneration Water Used 341.9 gal.

    Subtract 342 from total gallons available.

    INDICATOR

    TIMER FACE ILLUSTRATIONLOWER WHEEL HAS/IS REGENERATION KNOB

  • 7/30/2019 PN-XOS9500 Operation Manual Pure Water

    9/14

    SECTION 6

    Program Setting

    Procedure

    TENERGY WATER 2001 9

    SET GALLONS CALCULATED

    Lift (pull hub toward you) the gallon label wheel (the inner dial of

    the meter program wheel) so you can rotate meter program wheel

    freely.

    Position the white dot on the meter program wheel opposite the

    approximate number of gallons calculated.

    NOTE: There is a slight delay time from the time the meter zeros

    out and when the cycle starts. Units using the 1/15 rpm motor,

    82 minute regeneration time available (tanks 6 thru 12) have a

    9 minute delay. Units using the 1/30 rpm motor, 180 minute regen-

    eration time available (tanks 13 and larger) have an 18 minute

    delay. Typically on residential equipment this delay period is

    not critical. On commercial applications, this must be taken into

    consideration and continuous flows for 9 minutes or 18 minutes

    should be subtracted from water available.

    NOTE: If during the setting of your meter wheel, or your water

    usage is such that the capacity of the in-service unit is exhausted

    before the timer is back into service; the trip arm will advance past

    the position shown and the Meter Reset Stop will stall in the

    12:00 position. No regenerations will be initiated. To get unit back

    to proper position: 1st turn manual regeneration knob into

    backwash, and 2nd lift the reset plate up and allow the meter

    program wheel to reset itself.

    Insert meter cable into meter and controller.

    Check that both inlet/outlet isolation valves are open and the

    bypass valve is closed.

    Check that system bypass valve is in the service position. Plug unit

    in electrical outlet.

    Unit is ready for service.

    HOW TO SET THE

    REGENERATION CYCLE PROGRAM

    The regeneration cycle program on your water conditioner has

    been factory preset; however, portions of the cycle or program may

    be lengthened or shortened in time to suit local conditions.

    The timer face plate is hinged. To expose cycle program wheel,

    grasp timer in lower right-hand corner and pull, releasing snapretainer and swinging timer to the left.

    To change the regeneration cycle program, the program wheel

    must be removed. Grasp program wheel and squeeze protruding

    lugs towards center; lift program wheel off timer. (Switch arms may

    require movement to facilitate removal).

    Return timer to closed position engaging snap retainer in back

    plate. Make certain all electrical wires locate above snap retainer post.

    How to Change the Length of the Backwash Time:

    The program wheel as shown in the drawing is in the service

    position. As you look at the numbered side of the program wheel,

    the group of pins starting at zero determines the length of time your

    unit will backwash.

    FOR EXAMPLE: If there are six pins in this section, the time of

    backwash will be 12 min. (2 min. per pin). To change the length of

    backwash time, add or remove pins as required. The number of

    pins times two equals the backwash time in minutes.

  • 7/30/2019 PN-XOS9500 Operation Manual Pure Water

    10/14

    SECTION 7

    How to Change the Length of Brine and Rinse Time:

    The group of holes between the last pin in the backwash sectionand the second group of pins determines the length of time that

    your unit will brine and rinse (2 min. per hole).

    To change the length of brine and rinse time, move the rapid rinse

    group of pins to give more or fewer holes in the brine and rinsesection. Number of holes times two equals brine and rinse time in

    minutes.

    How to Change the Length of Rapid Rinse:

    The second group of pins on the program wheel determines thelength of time that your water conditioner will rapid rinse (2 min.

    per pin).

    To change the length to rapid rinse time, add or remove pins at the

    higher numbered end of this section as required. The number ofpins times two equals the rapid rinse time in minutes.

    How to Change the Length of Brine Tank Refill Time:

    The second group of holes on the program wheel determines the

    length of time that your water conditioner will refill the brine tank (2

    min. per hole).To change the length of refill time, move the two pins at the end ofthe second group of holes as required.

    The regeneration cycle is complete when the outer micro-switch istripped by the two pin set at end of the brine tank refill section. The

    program wheel, however, will continue to rotate until the innermicro-switch drops into the notch on the program wheel.

    MANUAL REGENERATION

    Turn the manual regeneration knob clockwise until the service

    position indicator is in the 3:00 position. This slight movement ofthe Manual Regeneration Knob engages the program wheel andstarts the reset motor.

    The black center knob will make one revolution.

    Warning: When you manually move cycle timer to different

    regeneration steps you must wait until positioning of upper andlower piston has stopped before advancing to next step. Ifadvanced too fast the control will not advance to the service

    position or to any other position. To correct this, rotate the manualknob back to service and start again.

    When manual regeneration is engaged, position of regeneration

    cycle is shown by the arrow on the position indicator.

    MediaLoadingMedia loading or replacement is sometimes required for units in thefield. Replacement of media is relatively simple, if the following pro-

    cedure is followed:

    Replacement of Media

    Close inlet/outlet isolation valve of unit to be rebedded.

    Manually turn timer dial to backwash position (See Section 6

    Manual Regeneration) to relieve vessel pressure.

    Unplug electrical connection of unit.

    Disconnect inlet, outlet, drain, and brine lines. Unscrew valve headfrom tank.

    Remove distribution tube from tank and visually inspect for any

    damage or wear replace if necessary.

    Warning: If new distribution tube is to be installed, it must be cut1/16 below top of tank (valve) mounting connection.

    Empty tank into resin trap/strainer, holding the resin/gravel andallowing water to flow to drain. Dispose of used media. Relocatetank in original location.

    NOTE: Disposal of resin must meet local and state regulations.

    Loading of Media

    Install distribution tube in mineral tank. Place a cap or tape over the

    open end of distributor to prevent any media from entering. Fill tankwith approximately one-third water to act as a buffer.

    Slowly pour the required amount of media in each vessel: Gravel to be loaded first

    Resin to be loaded second

    Multiple tank system, divide the gravel and resin quantitiesequally per number of vessels.

    Clean top of tank and tank threads of any resin or gravel. Removecap or tape from distribution tube and clean.

    Visually check and clean valve and distribution O Ring of any

    foreign matter and lubricate with silicone or soap.

    NOTE: Do not use Vaseline or grease.

    Locate control valve on tank making certain riser tube is locatedproperly. Tighten valve to tank.

    Reposition and level tank if necessary to assure proper alignment.

    Connect inlet, outlet, drain, and brine connections.

    The unit is ready for start-up. (See Section 5)

    TENERGY WATER 2001 10

  • 7/30/2019 PN-XOS9500 Operation Manual Pure Water

    11/14

    SECTION 8

    TENERGY WATER 2001 11

    UNIT ASSEMBLY

    ITEM NO. PARTNO. REQD NO. DESCRIPTION

    1 1 K4028 9500 Control Valve w/1-1/2 Meter

    2 Specify A4000 C1 Dark softener Resin

    3 Specify A7005 #20 Flint Gravel4 Specify A7006 1/4 x 1/8 Gravel

    5 2 C2020-4 12 x 52 - 4 PI Blue Tank w/RB

    2 C2023 14 x 42 - 4 PI Blue Tank w/RB

    2 C2025 16 x 65 - 4 PI Blue Tank w/RB

    2 C2026 20 x 62 - 4 PI Blue tank w/RB

    2 C2028 22 x 54 - 4 PI Natural Tank w/Base

    2 C2029 22 x 60 - 4 Pl Natural Tank w/Base

    2 C1031 24 x 72 - 4

    6 2 D5007 1-1/2 - 72 w/R2A-2 Screen (cut to fit)

    7 1 G2002 18 x 40 Blue Tank

    1 G2003 24 x 41 Black Tank

    1 G2004 24 x 50 Black Tank

    1 G2007 30 x 48 Black Tank

    8 1 H1072 TP500 Grid Plate1 H1075 24 Grid Plate

    9 1 H1040-36 3-1/2 Brine Well x 36

    1 H1071 6 Well x 48 H.

    10 1 H1015 3-1/2 Brine Well Cap

    1 H1024 6 Brine Well Cap

    11 1 H1018 Overflow Set

    12 1 Brine Assembly

    13 1 K4560366 1 F x 3/4 F Brass Flow Control

    1 V2003-A 1 PVC Flow Control

    BRINE PICKUP SYSTEM

    ASSEMBLY

    1 1 H7076-28 Brine Assembly 33 Tank

    H7076-36 Br ine Assembly 40 Tank

    1A 3/8 X 28 Rigid PVC

    (for 28 brine wells)

    3/8 x 30 Rigid PVC

    (for 30 brine wells)

    3/8 x 36 Rigid PVC

    (for 36 brine wells)

    1B Body, Drilled Less Ball

    1C Quad Ring

    1D Float Rod - 14 Float Rod - 241E Float Grommet (2 required)

    1F Bell Type Float

    1G Guide, Lock, Adaptor

    1H Washer

    1J Crown Nut

    1K Ball Cage

    1L Air Check Ball

    1M Quad Cup Seat

    1N Stem

    1P Spool Seat

    2 1 I4366J 3/8 x 3/8 Union Elbow

    NOTE: Brine System Sold as Assemblies Only.

    ITEM NO. PARTNO. REQD NO. DESCRIPTION

  • 7/30/2019 PN-XOS9500 Operation Manual Pure Water

    12/14

    PROBLEM CAUSE CORRECTION

    1. LOSS OF RESIN A. Broken distribution tube A. Replace distribution tube.

    B. Inlet/outlet connection reversed B. Reconnect inlet/outlet connection properly.

    2. SOFTENER FAILS TO A. Electrical service to unit A. Assure permanent electrical serviceREGENERATE interrupted. (check fuse, plug, pull chain, or switch).

    B. Timer defective B. Replace timer.

    C. Power failure C. Reset time of day.

    3. HARD WATER A. Bypass valve open A. Close bypass valve.

    B. No salt in brine tank B. Add salt to brine tank and maintain salt levelabove water level.

    C. Injector screen plugged C. Clean injector screen.

    D. Insufficient water flowing D. Check brine tank fill time and clean brine lineinto brine tank flow control if plugged.

    E. Hot water tank hardness E. Repeated flushing of the hot water tank is

    required.

    F. Leak at distributor tube F. Make sure distributor tube is not cracked.Check O Ring and tube pilot.

    G. Internal valve leaking G. Replace seals and spacers and/or piston.

    4. UNIT USED TOO MUCH SALT A. Improper salt setting A. Check salt usage and salt setting.

    B. Excessive water in brine tank B. See Problem No. 8.

    5. LOSS OF WATER PRESSURE A. Iron buildup in line to A. Clean line to water conditioner.water conditioner

    B. Iron buildup in water conditioner B. Clean control and add mineral cleaner tomineral bed.

    Increase frequency of regeneration.

    C. Inlet of control plugged due to C. Remove piston and clean control.foreign material broken loose from

    pipes by recent work done onplumbing system

    6. LOSS OF MINERAL A. Air in water system A. Assure that well system has proper

    THROUGH DRAIN LINE air eliminator control.

    Check for dry well condition.

    7. IRON IN CONDITIONED WATER A. Fouled mineral bed A. Check backwash, brine draw, and brine tank fill.

    Increase frequency of regeneration.

    Increase backwash time.

    8. EXCESSIVE WATER A. Plugged drain line flow control A. Clean flow control.

    B. Plugged injector system B. Clean injector and screen.

    C. Injector screen plugged C. Replace timer.

    D. Foreign material in brine valve D. Replace brine valve seat and clean valve.

    E. Foreign material in E. Clean brine line flow control.

    brine line flow control

    TENERGY WATER 2001 12

    SECTION 9

    Troubleshooting

    IN BRINE TANK

  • 7/30/2019 PN-XOS9500 Operation Manual Pure Water

    13/14

    13. SOFTENER DELIVERS A. Reserve capacity exceeded A. Check salt dosage requirements and resetHARD WATER program wheel to provide additional reserve.

    B. Program wheel not rotating B. Pull cable out of meter cover and rotate

    with meter output manually. Program wheel must move withoutbinding and clutch must give positive clicks

    when program wheel strikes regenerationstop. If it does not, replace timer.

    C. Meter not measuring flow C. Check flow output by observing rotation of small gear on front of timer. Each tooth totooth is approximately 30 gallons; if not,

    replace meter.

    NOTE: Program wheel must not be against

    regeneration stop for this check.

    PROBLEM CAUSE CORRECTION

    SOFTENER FAILS TO DRAW BRINE A. Drain line flow control plugged A. Clean drain l ine flow control.

    B. Injector plugged B. Clean injector.

    C. Injector screen plugged C. Clean screen.

    D.L ine pressure too low D. Increase line pressure to 20 P.S.I.

    E. Internal control leak E. Change seals, spacers, and piston assembly.

    10. CONTROL CYCLES A. Broken or shorted switch A. Determine if switch or timer is faulty andCONTINUOUSLY replace it, or replace complete power head.

    11. DRAIN FLOWS CONTINUOUSLY A. Valve not programming A. Check timer program and positioning of correctly control.

    Replace power head assembly if notpositioning properly.

    B. Foreign matter in control B. Remove power head assembly and inspect

    bore.Remove foreign material and check control in

    various regeneration positions.

    C. I nternal control leak C. Replace seals and piston assembly.

    12. BRINE TANK FILLS DURING A. Clogged drain A. Replace drain line.

    B. Internal piston seal leaks B. Replace seals in piston assembly.

    OPTIONAL WATER METER

    TENERGY WATER 2001 13

    9.

    BRINE DRAW STEP

    Troubleshooting continued

  • 7/30/2019 PN-XOS9500 Operation Manual Pure Water

    14/14

    Manufactured by: Tenergy Water, LLC, New Britain, Connecticut

    DISTRIBUTED BY:

    INSTALLATIONTYPICAL PIPING

    OPTIONAL

    DUPLEX INSTALLATIONTYPICAL PIPING

    TYPICAL INSTALLATIONBRINE TANK ASSEMBLY

    (18 Diameter)

    TYPICAL INSTALLATIONBRINE TANK ASSEMBLY(24 Diameter and Larger)

    SECTION 10