PMU-Based Forced Oscillation Source Localization FO Source Localization... · 7 Oscillation Source...

19
WECC OAWG CONFERENCE CALL. APRIL 8,2019 SLAVA MASLENNIKOV [email protected] PMU-Based Forced Oscillation Source Localization

Transcript of PMU-Based Forced Oscillation Source Localization FO Source Localization... · 7 Oscillation Source...

Page 1: PMU-Based Forced Oscillation Source Localization FO Source Localization... · 7 Oscillation Source Locating (OSL) is the key application •The OSL calculates the rate of change of

W E C C O A W G C O N F E R E N C E C A L L . A P R I L 8 , 2 0 1 9

S L A V A M A S L E N N I K O V

S M A S L E N N I K O V @ I S O - N E . C O M

PMU-Based Forced Oscillation Source Localization

Page 2: PMU-Based Forced Oscillation Source Localization FO Source Localization... · 7 Oscillation Source Locating (OSL) is the key application •The OSL calculates the rate of change of

2

PMU Infrastructure at ISO New England

• 86 PMUs at 45 locations

• Full observability of 345 kV

• Seven open PDCs at TOs and one at ISO

• Selected PMU data from NYISO, PJM and MISO

• Operational since 2012

• PhasorPoint by GE is the main PMU application

NYISO

PJM

MISO

Page 3: PMU-Based Forced Oscillation Source Localization FO Source Localization... · 7 Oscillation Source Locating (OSL) is the key application •The OSL calculates the rate of change of

3

Observed Oscillations

40 MW

Characteristics of 1000+ oscillatory events (statistics since 2012)

Property Description

Frequency 0,05 … 2 Hz

Damping 0 … 10 %

Magnitude 2 … 70 MW, RMS

Observability Local and Wide-spread

Duration From few seconds to hours

Overwhelming majority of evens are

Forced Oscillations

0.25 Hz

January 11, 2019: Forced oscillations caused by governor control failure of a Florida generator. Entire Eastern Interconnection was oscillating 17 min

MW flow in NYISO – ISO-NE

tie-line 1100+ miles away

from the source of oscillations

Page 4: PMU-Based Forced Oscillation Source Localization FO Source Localization... · 7 Oscillation Source Locating (OSL) is the key application •The OSL calculates the rate of change of

4

Why do we need to mitigate oscillations?

• Sustained oscillations (forced and natural) impose a threat

Potential uncontrolled cascading outages

Undesirable mechanical vibrations in equipment

• The key step in the mitigating of sustained oscillations is to find the Source of oscillations. The Source is typically a generator

• The capability to find the Source online means providing an actionable information for mitigation

Page 5: PMU-Based Forced Oscillation Source Localization FO Source Localization... · 7 Oscillation Source Locating (OSL) is the key application •The OSL calculates the rate of change of

5

Catastrophic consequences of rotor’s vibration2009 Sayano–Shushenskaya hydro power station accident *

• 75 people were killed• Widespread blackout• 6,400 MW power plant was out of service for 3 years• Critical damage to a generator was caused by Forced Oscillations (FO)

Before the accident After the accident

* https://en.wikipedia.org/wiki/2009_Sayano%E2%80%93Shushenskaya_power_station_accident

Page 6: PMU-Based Forced Oscillation Source Localization FO Source Localization... · 7 Oscillation Source Locating (OSL) is the key application •The OSL calculates the rate of change of

6

Online Oscillation Management

PMU

Open PDC

Phasor Point

Alarm Notification Service

Triggered by Alarm

….

Objectives:• Detect all significant oscillatory events• Estimate the Source of oscillations• Deliver results to the designated personnel

ISO personnel• Operation Engineers• Control Room

PMU

PMU

Alarms

Oscillation Source Locating (OSL)

DetectionFinding the Source Mitigation

• Email• SMS

Generator Owner

Fully automated process; operational since September 2017

Page 7: PMU-Based Forced Oscillation Source Localization FO Source Localization... · 7 Oscillation Source Locating (OSL) is the key application •The OSL calculates the rate of change of

7

Oscillation Source Locating (OSL) is the key application

• The OSL calculates the rate of change of Dissipating Energy (DEi ) for any branch ij

monitored by PMU at bus i.

• DE coefficient can be viewed as a regular MW flow in terms of Source-Sink for a flow of the transient energy: flows from Source to Sink

• The direction and the value of DE in multiple branches allow tracing the source of oscillations

MW flow in a transmission line Flow of Dissipating Energy in that line

Page 8: PMU-Based Forced Oscillation Source Localization FO Source Localization... · 7 Oscillation Source Locating (OSL) is the key application •The OSL calculates the rate of change of

8

Interpretation of DE pattern

• PMU measurement at the Point Of Interconnection allows to trance specific power plant or generator

• PMU measurements of tie-lines between control areas allow to identify which area contains the source

• Even limited system observability by PMU allows greatly localize the suspect area

Source

Area A

Area B

Area C

Source

Sub 1

Sub 2Sub 3 Suspect area

DE flow

Page 9: PMU-Based Forced Oscillation Source Localization FO Source Localization... · 7 Oscillation Source Locating (OSL) is the key application •The OSL calculates the rate of change of

9

• February 6, 2018; a large ISO-NE generator creates multi-frequency oscillations with magnitude up to RMS=3MW during 5 min

Time domain data Results of the OSL for 0.6Hz mode

This example illustrates the ability to identify an individual generator if it is monitored by PMU

FO Caused by ISO-NE generator

Combination of 0.60Hz and 0.86Hz modes

DE pattern for 0.86Hz is practically the same

Page 10: PMU-Based Forced Oscillation Source Localization FO Source Localization... · 7 Oscillation Source Locating (OSL) is the key application •The OSL calculates the rate of change of

10

FO Coming From Non-Observable Area

• December 7, 2017; 1.3 Hz oscillations with RMS=5MW magnitude coming from the ISO-NE area not observed by PMUs

Results of the OSL

Not observed by PMU suspect area

• This area contains only 3 generators

• SCADA data for these 3 generates helps to find the source - generator

SCADA data for 3 suspect generators

This example illustrates the ability to localize the suspect area non-observable by PMU

Page 11: PMU-Based Forced Oscillation Source Localization FO Source Localization... · 7 Oscillation Source Locating (OSL) is the key application •The OSL calculates the rate of change of

11

• 0.25 Hz oscillations with up to 200 MW peak-to-peak magnitude propagated through Entire Eastern Interconnection during 17 min

• The source of oscillations was a Florida generator having problem with the governor control

• Resonance conditions of 0.25 Hz inter-area mode caused the propagation of oscillations across entire EI

January 11, 2019 oscillation event

MW flow in 345 KV tie-line between NYISO and ISO-NE

Page 12: PMU-Based Forced Oscillation Source Localization FO Source Localization... · 7 Oscillation Source Locating (OSL) is the key application •The OSL calculates the rate of change of

12

Oscillation Alarm Notifications via E-mail

• Designated personnel including Operation support engineers have received multiple emails during the event

• Each email contains

Characteristics of oscillations: magnitude, frequency, damping, location

Estimated Source: DE table, DE visualization, results of Pattern Recognition

Page 13: PMU-Based Forced Oscillation Source Localization FO Source Localization... · 7 Oscillation Source Locating (OSL) is the key application •The OSL calculates the rate of change of

13

The content of E-mail

Results of DE pattern recognition• PMU only from ISO-NE footprint are used• That allows to identify that the Source:

Is located outside and In NYISO direction

Parameters of oscillations

DE in tabular form

DE visualization on oneline diagram

Page 14: PMU-Based Forced Oscillation Source Localization FO Source Localization... · 7 Oscillation Source Locating (OSL) is the key application •The OSL calculates the rate of change of

14

DE Visualization on Oneline Diagram

New BrunswickN

ew

Yo

rk IS

O

• Each black arrow is a calculated DE

• DE pattern clearly shows that oscillations are coming from NYISO direction

• All Alarms for 1/11/2019 event contain practically identical DE pattern

Page 15: PMU-Based Forced Oscillation Source Localization FO Source Localization... · 7 Oscillation Source Locating (OSL) is the key application •The OSL calculates the rate of change of

15

Consequences of the 1/11/2019 Event

• Before 1/11/2019, Oscillation Alarm Notification emails were sent to Operation support engineers only.

• After the event, Operations has requested

o To add the Control Room Shift Supervisor to the list of email recipients

o For a possibility to send also text SMS with Alarm notification

• Both requests were implemented

• Online Oscillation Management process was enhanced by adding the capability to send Oscillation Alarm Notification emails to generator personnel

o Due to confidentiality of information, specific generator can receive email related to oscillations caused by that generator only

Page 16: PMU-Based Forced Oscillation Source Localization FO Source Localization... · 7 Oscillation Source Locating (OSL) is the key application •The OSL calculates the rate of change of

16

Source Identification Results

• Results are available online and provide key actionable information for mitigation

• The first key question is the Source located inside or outside of control area? The answer defines different set of actions

o For internal source: localize, eliminate, prevent the future occurrences

o For external: facilitate the elimination of the source in a suspect control area

• For January 11 event, results of OSL mean:

o Any action within ISO-NE cannot mitigate oscillations. Tripping of tie-lines will stop oscillations within area but is unreasonable

o Control Room should not initiate any actions within ISO-NE footprint to mitigate oscillations

o The best action is to call NYISO (suspect area) to verify their observations

Page 17: PMU-Based Forced Oscillation Source Localization FO Source Localization... · 7 Oscillation Source Locating (OSL) is the key application •The OSL calculates the rate of change of

17

Statistics and Lessons Learned

• Online OSL has automatically processed 1000+ oscillatory events since September 2017. Correctly identified the source-generator/area for practically all instances of known source location

Each utility, having “OSL-like tool”, would be capable to independently estimate the Source of oscillations and greatly reducing the need in coordination with other utilities for mitigation

• Automated procedure for filtering and correcting bad PMU data is a must for robust online application

Page 18: PMU-Based Forced Oscillation Source Localization FO Source Localization... · 7 Oscillation Source Locating (OSL) is the key application •The OSL calculates the rate of change of

OSL Software

18

• Developed by ISO-NE

o Online version is integrated with ISO-NE infrastructure

o Offline version reads PMU data from file and can be used with PMU data of any utility.

Several PMU data formats are supported

The software can be used as a research or fully automated tool

• ISO-NE can share the offline OSL software free of charge on request. Details will be available soon

Page 19: PMU-Based Forced Oscillation Source Localization FO Source Localization... · 7 Oscillation Source Locating (OSL) is the key application •The OSL calculates the rate of change of

19