PM #1 - Embedded Solutions Through Targeted Power Conditioning · Ph: 1-800-377-4384, ) 120 VA...
Transcript of PM #1 - Embedded Solutions Through Targeted Power Conditioning · Ph: 1-800-377-4384, ) 120 VA...
Embedded Solutions Through Targeted Power Conditioning
Mark Stephens, PEManagerIndustrial Studies Electric Power Research Institute 942 Corridor Park Blvd Knoxville, Tennessee 37932 Phone 865.218.8022 [email protected]
2© 2009 Electric Power Research Institute, Inc. All rights reserved.
Cost of Solutions Versus Knowledge of Sensitivity
3© 2009 Electric Power Research Institute, Inc. All rights reserved.
Example PQ Solution Levels
Machine or Subsystem Level Power Conditioning
Control LevelPower Conditioning
(1/10th to 1/20th of Machine Level Power Conditioner Cost)
Control LevelEmbedded DC Solution
(Best done by OEM in design phase)
4© 2009 Electric Power Research Institute, Inc. All rights reserved.
Embedded Solution Strategies
• Use “Selective Power Conditioners” on susceptible loads
• Embed the Solution through proper design, configuration and component selection strategies
• Utilize a Combination of both strategies
DPI and VDC DySC CoilLockCVT and
PowerRide RTD
VacuumPumps
Contactors
DCPower
Supplies
Low VoltageRide Through
Module
Relays
Batteryless Ride-Through Devices(BRTDs)
5© 2009 Electric Power Research Institute, Inc. All rights reserved.
The Premise:All equipment power users are not ultra-sensitive.
The Plan:To prop up the single-phase “weak links” only.
The Weak Links:Small, single-phase 100Vac-230Vac, typically power supplies, sensors and controls.
The Benefit: Lower Cost than Macro Solutions.
“Selective” Conditioning
6© 2009 Electric Power Research Institute, Inc. All rights reserved.
Uninterruptible Power Supply (UPS)
Battery Based Battery Based UPSUPS
Are Often Are Often ““OverkillOverkill””
For Control LoadsSmall 500Va to
3kVAUPS Systems are sometimes Used
7© 2009 Electric Power Research Institute, Inc. All rights reserved.
“Abandoned in Place” UPS Systems
• Throughout our numerous on-site power quality audits we have found many UPS systems “abandoned in place” when their batteries expire
• Without proper maintenance, UPS solutions are not effective
8© 2009 Electric Power Research Institute, Inc. All rights reserved.
• Off-line (standby) & On-Line models.
• Must consider in-rush current for On-line models.
• Some units have Square Wave Output During Voltage Sag
• Sub-Cycle to several cycle Response. Some critical control components can drop out within 1/4 cycle.
• Sizing for battery time and in-rush current of UPS is manufacturer specific.
• Protects against voltage sags and outages.
UPS Application & FeaturesUPS Application & Features
9© 2009 Electric Power Research Institute, Inc. All rights reserved.
Square Wave Compatibilitywith PLCs
PLC Model Compatible with 120Vac Input Cards?
Outcome withAPC Smart UPS 420
Outcome withAPC Back UPS Pro 650
Omron (PLC A) No Toggling input could not be resolved
Toggling input could not be resolved
TI 545 (PLC B) No All inputs dropped leading to the logical decision to drop the control relay
All inputs dropped leading to the logical decision to drop the control relay
Quantum (PLC C) No Same as TI 545 Same as TI 545
AB PLC-5 (PLC D) Yes
AB SLC 5/03 (PLC E) Yes No Effect, System OK
No Effect, System OK No Effect, System OK
No Effect, System OK
10© 2009 Electric Power Research Institute, Inc. All rights reserved.
UPS Coverage vs.Sample Historical Data
11© 2009 Electric Power Research Institute, Inc. All rights reserved.
Constant Voltage Transformer (CVT)
12© 2009 Electric Power Research Institute, Inc. All rights reserved.
CVT Application & Features
•On-line Device. In-Rush Current of load(s) MUST be considered in sizing.Output of CVT can collapse when in-rush currentgets close too high ( around 4 x rated size).
• Sub-Cycle Response.
• Should be oversized to at least 2 times nominal of load to increase ride-through.
• Acts as an isolation transformer and protects against voltage sags.
13© 2009 Electric Power Research Institute, Inc. All rights reserved.
Example CVT Installation
14© 2009 Electric Power Research Institute, Inc. All rights reserved.
CVT Output
Inpu
t Vol
tage
Out
put V
olta
ge
15© 2009 Electric Power Research Institute, Inc. All rights reserved.
Sample CVT SizingRecommendations
Specs 250VA 500VA 1kVA 3kVARecommended MaxNominal Load VA/Current @ 120Vac
100 VA / 0.83 A 200 VA / 1.67 A 400 VA / 3.33 A 1200 VA / 10 A
Recommended MaxInrush Load VACurrent @ 120Vac
500 VA / 4.16A 1000 VA / 8.33A 2000 VA / 16.67 A 6000 VA / 50A
Dimensions (inch) 9.88x4.5x7.44 12.69x7.78x6.44 16.75x7.78x6.44 18.69x10.56x9.03Weight (lbs) 27 37 62 142
MIN SIZE = 2.5 X Nominal VAor
1/2 Max Inrush VA*(whichever is larger)
*most critical with contactor loads
16© 2009 Electric Power Research Institute, Inc. All rights reserved.
Example CVT Application
• The CVT is protecting only the AC control components means that the selected power conditioner will be more affordable than one that could protect the entire machine.
• The ride-though of the AC drives in this example can be enhanced by modifying their programming, thus eliminating the need for a large power conditioner.
17© 2009 Electric Power Research Institute, Inc. All rights reserved.
CVT Coverage vs.Sample Historical Data
18© 2009 Electric Power Research Institute, Inc. All rights reserved.
CVT Typical Costs ($USD)
Constant Voltage Transformer (CVT) (Sola/Hevi-Duty. Ph: 1-800-377-4384, www.sola-hevi-duty.com ) 120 VA Catalog No: 63-23-112-4, Cost $245, (8.62” X 3.31 “ X 5.18 “, 15 lbs) 250 VA Catalog No: 63-23-125-4, Cost $400, (9.88” X 4.50” X 7.44”, 27 lbs) 500 VA Catalog No: 63-23-150-8, Cost $650, (12.69” X7.78” X 6.44”, 37 lbs) 750 VA Catalog No: 63-23-175-8. Cost $700, (13.69” X 7.78” X 6.44”, 52 lbs) 1000 VA Catalog No: 63-23-210-8, Cost $850, (16.75” X 7.78” X 6.44”, 62 lbs) 1500 VA Catalog No: 63-23-215-8, Cost $1100 ( 16.44” X 10.56” X 9.03”, 95 lbs) 2000 VA Catalog No: 63-23-220-8, Cost $1200 (17” X 11” X 9”, 109 lbs) 5000 VA Catalog No: 63-23-250-8, Cost $2907 (28” X 11” X 9”, 222 lbs) 7500 VA Catalog No: 63-28-275-8, Cost $3829 (28” X 24” X 9”, 362 lbs) 15,000 VA Catalog No: 63-28-315-8, Cost $6700 (28” X 36” X 9”, 710 lbs)
19© 2009 Electric Power Research Institute, Inc. All rights reserved.
New Product: UPPI PowerRide RTDBasically a CVT on Steroids!
• Uses two phases of a three-phase supply as input and a single-phase output.
• If one phase in interrupted, constant power out of the RTD....Even if the remaining phase drops by a third.
• Typically No Need to oversize for Inrush
20© 2009 Electric Power Research Institute, Inc. All rights reserved.
UPPI PowerRide RTD:How It Works
Power Anomaly ResultLoss of Phase A Output remains constantLoss of Phase B Output remains constantLoss of Phase C Output remains constantLoss of Phase A and B -33% sag on remaining phase
Output remains constant
Loss of Phase B and C -33% sag on remaining phase
Output remains constant
Loss of Phase A and C Output goes to 0Loss of A and 33% Sag on C Output remains constantLoss of C and 33% Sag on A Output remains constant37% Sag on A and C Output remains constant
21© 2009 Electric Power Research Institute, Inc. All rights reserved.
UPPI PowerRide RTD:Example Output
22© 2009 Electric Power Research Institute, Inc. All rights reserved.
UPPI PowerRide RTD: Suggested List Price
Product Size Qty
Suggested List Price
1 $7792-9 $677
10 + $589
1 $1,1802-9 $1,026
10 + $892
1 $2,0112-9 $1,748
10 + $1,520
1 $2,8812-9 $2,505
10 + $2,178
1 $4,5032-9 $3,916
10 + $3,405
1 $4,8452-9 $4,404
10 + $4,004
1 $7,8932-9 $7,175
10 + $6,523
5kva
7kva
10kva
500va
1kva
2kva
3kva
http://www.uppi-ups.com
23© 2009 Electric Power Research Institute, Inc. All rights reserved.
Power Ride RTD Coverage vs.Sample Historical Data
(Red Box is coverage for Single-Phase Sags & Phaseto-Phase Sags (A-B, B-C) Blue Box for Phase-to-Phase Sags (A-C)
24© 2009 Electric Power Research Institute, Inc. All rights reserved.
The Dip Proofing Inverter
• No batteries; therefore, no replacement and maintenance costs or hazardous waste.
• Fast (<700µS) transfer, off-line system develops little heat & fails to safety.
• Able to withstand high inrush currents; no need to oversize as with UPS’s & CVT’s.
• Lightweight, small & easy to retrofit; no step-up transformers or batteries.
• Accurate application control; adjustable ride through time & variable transfer level.
• Primarily designed for inductive and low power factor loads.
25© 2009 Electric Power Research Institute, Inc. All rights reserved.
Typical Connections
26© 2009 Electric Power Research Institute, Inc. All rights reserved.
Sample DPI Specifications (120V Models)
Specs 250VA 500VA 1kVA 3hkVANominal LoadCurrent
2A 4A 8A 25A
Useable StoredEnergy
45J 90J 180J 540J
Ride-ThroughTimer Range
0.01 to 2.56 Seconds
Transfer LevelRange
50% to 80%50% to 90% Recommended (Special Order)
Dimensions (inch) 7.68x12.25x6.4 11.4x12.25x6.4 15.75x12.25x6.4 21x12.25x6.4Weight (lbs) 11 17 22 31
27© 2009 Electric Power Research Institute, Inc. All rights reserved.
DPI Output
Inpu
t Vol
tage
Out
put V
olta
ge
•1-3 second ride-through based on real power required and sizing.
Square Wave not compatible with some PLC AC Input Cards.
28© 2009 Electric Power Research Institute, Inc. All rights reserved.
DPI Used in Chiller Control Circuit
DPI
29© 2009 Electric Power Research Institute, Inc. All rights reserved.
DPI Coverage vs.Sample Historical Data
30© 2009 Electric Power Research Institute, Inc. All rights reserved.
DPI Typical Costs
31© 2009 Electric Power Research Institute, Inc. All rights reserved.
Voltage Dip Compensator (Vdc)
• No batteries; no maintenance. • Fast compensation. • Able to withstand high inrush
currents. • Small footprint, easy to retrofit. • Support exceeds SEMI F47
standard requirements. • Handles inductive and low power
factor loads.• 120Vac and 208Vac Models• Currently under evaluation by EPRI
PEAC
32© 2009 Electric Power Research Institute, Inc. All rights reserved.
VDC Output
Product by Dip Proofing Technologies
www.dipproof.comwww.measurlogic.com
AC Output is a Sine Waveinstead of a Square Wave
33© 2009 Electric Power Research Institute, Inc. All rights reserved.
VDC Coverage4T Model – Down to 50%
6T Model – Down to 37%
34© 2009 Electric Power Research Institute, Inc. All rights reserved.
VDC Coverage (4T Model) vs.Sample Historical Data
35© 2009 Electric Power Research Institute, Inc. All rights reserved.
Typical VDC Pricing
36© 2009 Electric Power Research Institute, Inc. All rights reserved.
Dynamic Sag Corrector
• Draws power from remaining sagged voltage down to 50% of nominal voltage, and injects a series voltage to regulate a sinusoidal output voltage
• Below 50%, draws power from internal storage capacitors
• Mega and Pro DySC have on board event logging.
MiniDySC
Single-Phase Protection
1-50 Amps
ProDySC
Three-Phase Protection
25-200Amps
MegaDySC
Three-Phase Protection
400-3200Amps
37© 2009 Electric Power Research Institute, Inc. All rights reserved.
Example DySC Output
Input Voltage (Van)
Missing Volts
DySC Output Voltage
-500-400-300-200-100
0100200300400500
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
t ( s)
-500
-300
-100
100
300
500
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
t ( s)
-600
-400
-200
0
200
400
600
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
t ( s)
38© 2009 Electric Power Research Institute, Inc. All rights reserved.
Voltage Sag Correction & Ride-Through Times
• Ride-Through Times: (Based on 100% load, 0.7PF at 60Hz line frequency)
• Standard Runtime: 2 seconds for sags from 87% to 50% of nominal voltage every 60 seconds – Up to 5 seconds coverage on
Extended Run-Time Models
• 3 cycles for Standard Outage units from 50%-100% (zero voltage remaining)
• 12 cycles for Extended Outage units from 50%-100% (zero voltage remaining)
39© 2009 Electric Power Research Institute, Inc. All rights reserved.
Extended Run-Time Models Are Available
40© 2009 Electric Power Research Institute, Inc. All rights reserved.
Extended Run-Time Models Are Available
41© 2009 Electric Power Research Institute, Inc. All rights reserved.
MiniDySC Coverage vs.Sample Historical Data
Orange – Extended Ride-Through Full LoadRed – Standard Ride-Through Full Load
42© 2009 Electric Power Research Institute, Inc. All rights reserved.
MiniDySC Typical Cost
www.softswitch.com
1.5kVA 120Vac Single Phase MiniDySC DS10012A120V2SH1000A $2000.00
3kVA 120Vac Single Phase MiniDySC DS10025A120V2SH1000A $2820.00
6-7kVa 120Vac Single Phase MiniDySC DS10050A120V2SH1000A $4570.00
43© 2009 Electric Power Research Institute, Inc. All rights reserved.
New Product - WaveSync – Ride Through Controller
• The WaveSync was developed by Bay Controls (the parent company of Phase Solutions) R&D based on research conducted by Advanced Energy. It was developed as a solutions to the problem of motor ride through during momentary power interruptions.
• www.phasesolutions.com
44© 2009 Electric Power Research Institute, Inc. All rights reserved.
WaveSync Operation
• The WaveSync performs four primary operations to accomplish ride through.
1. Monitor supply power to detect the beginning of a momentary outage event.
2. Open the motor contactor upon event detection.3. Keep any motor control center associated with the
protected motor “alive” during the event.4. Once the event has ended, re-close the motor contactor at
the appropriate time, preventing torque and current spikes.5. Can be setup to treat voltage sag like and outage and
perform same function
45© 2009 Electric Power Research Institute, Inc. All rights reserved.
During the Momentary Interruption
• The WaveSync is working during a momentary interruption. – Monitoring the three phase supply power and,– Monitoring the three phase motor back EMF,– Supplying power and a run signal to any motor control
center– Reconnection of power when supply and motor back EMF
are in phase, or upon decay of back EMF at or below a predetermined level.
– REQUIRES POWER CONDITIONER TO KEEP WAVESYNC POWERED DURING MOMENTARY INTERRUPTION (such as DPI).
46© 2009 Electric Power Research Institute, Inc. All rights reserved.
During Voltage Sags
• The WaveSync is configured to handle voltage sags below a preset value as a momentary outage.
• The device will hold in the contactor during sags at or above the outage setting.
• During long duration sags, motors are protected utilizing existing over current protection - the WaveSync does not interfere with motor protection systems
47© 2009 Electric Power Research Institute, Inc. All rights reserved.
Reconnecting Power in Phase
1000
200
400
600
800
0
200
400
600
800
100055 60 65 70 75 80
Motor Contactor Energized
Motor Energized Safely (In-Phase)
Supply Voltage Restored
Cycles
Vol
ts
48© 2009 Electric Power Research Institute, Inc. All rights reserved.
• Designed to “Prop Up” individual relays and contactors. Available at 24, 120, 230 and 480Vac.
• Holds in down to 10 to 20% of %Vnominal.• Ideal for Motor Control Center Applications.• Size Based on Voltage and Coil Resistance.• Cost: less than $100 per unit
Coil Hold-in Devices
CoilLock Low VoltageRide Through
Module
49© 2009 Electric Power Research Institute, Inc. All rights reserved.
Coil Hold-In Device Ride-Through Curve
50© 2009 Electric Power Research Institute, Inc. All rights reserved.
Coil Hold in Device Application
51© 2009 Electric Power Research Institute, Inc. All rights reserved.
Sizing Coil Hold In Devices
Name ManufacturerInformation
PhaseRef
CoilResistance(ohms)
KnowTripModel
ContactorK1
Gould Cat2250H15
φΑ 10.5 120
ContactorK2
Gould Cat2250H15
φΑ 10.5 120
K15 Gould 2210DP φΑ 326 120AK16 Cutler Hammer
D5PR3A(ice cube)
φΒ >800 120B
K17 Gould 2210DP φΒ 326 120AK18 Cutler Hammer
D5PR3A(ice cube)
φC >800 120B
K20 Cutler HammerD5PR3A(ice cube)
φΒ >800 120B
K22 Gould 2210DP φΑ 326 120AK23 Gould 2210DP φΑ 326 120A
SIZED BASED ON
1. AC Coil Voltage2. Resistance of Coil
Model 120: 8-200 ohmsModel 120A: 201-800 ohmsModel 120B: 801+ ohms
Actual Semi Tool Relays with KnowTrips Recommended.
www.scrcontrols.comwww.squared-semi.com
www.pqsi.com
52© 2009 Electric Power Research Institute, Inc. All rights reserved.
Overview of Power Quality CoverageType of Event
DPI VDC CVT RTD MiniDySC UPS Coil Hold-in Devices
Spikes and Surges
No No Solves Solves Solves Solves Yes (Coil Lock)No (Knowtrip)
Sags to 80% of Nominal Voltage
Solves Solves Solves Solves for a single phase events and most two phase events
Solves Solves Solves
Sag to50-80% of Nominal Voltage
Solves Solves Solves Depending on Sizing of Device
Solves for a single phase events and most two phase events
Solves Solves Solves
Sags to 25-50% of Nominal Voltage
Solves No Solves Depending on Sizing of Device
Solves for a single phase events and most two phase events
Solves Solves Solves
Outage Solves -time depends on load and unit size
No No Solves for a single phase events
Solves -time depends on load and unit size
Solves No
53© 2009 Electric Power Research Institute, Inc. All rights reserved.
Power Conditioner Web Sites
Batteryless Ride-Through Devices (BRTD) Standby Inverter Technology
Dip-Proofing Technologies www.dipproof.com
www.measurlogic.com
Active Ferro Technology
Uninterruptible Power Products (UPPI)
www.uppi-ups.com
DC bus hold-in Technology
Bonitron www.bonitron.com
DC bus hold-in Technology
Maxwell Technologies www.maxwell.com
Coil and Relay hold-in products
Power Quality Solutions www.pqsi.com
Coil and Relay hold-in products
SCR Controls www.scrcontrols.com
Voltage Compensation Technology
Soft Switching Technology www.softswitch.com
54© 2009 Electric Power Research Institute, Inc. All rights reserved.
Power Conditioner Web Sites (continued)
Constant Voltage Transformers (CVT) BEST Power www.bestpower.com
Sola www.sola-hevi-duty.com
Shape Electronics www.shapelectronics.com
Controlled Power www.controlledpwr.com/
Power Quality Solutions www.pqsi.com
UPPI (PowerRide-RTD) www.uppi-ups.com
Uninterruptible Power Supplies (UPS)Standby, Line-interactive
APC www.apcc.com
Standby,Line-interactive,Ferroresonant
BEST Power www.bestpower.com
Standby, On-line Exide www.exide.com
Standby, On-line Liebert www.liebert.com
On-line Clary www.clary.com
Standby Tripplite www.tripplite.com
On-line MGE UPS Systems www.mgeups.com
Rotary Piller www.piller.com/