Non red -Solid Amb
Power-Solid Green
SL. NO. LED STATUS
Non red -Off
This supply is operating properl
adapter module
1756-PA72 REDUNDANT POWER SUPPLY STATUS IND
Solid Red The Controller detected a nonre
THIS CPower-Solid Green
Both supplies are operating pro
Non red -Solid Amb
Power-OFFAll possible connections are ma
1756-L63 PROCESSOR STATUS INDICATORS
Off No power is applied
Solid Green The controller is OK
Non red- OFF
1.The supply is turned OFF
2. Line voltage is not within the
3. All connections are made, bu
4.All connections are made, incl
5. The supply is ON but defecti
Power- OFF Any of the following conditions
Off The battery supports memory
Solid Green If the controller is SERIES-A, T
If the controller is SERIES-B, D
Flashing Green The controller is storing or loadi
Flashing Red A new controller or major fault
Off Either:
- There are no devices in th
- The controller does not co
Solid Red Either the battery is not installe
Off The controller is in Program or
Solid GreenThe Controller is in Run mode
Solid Green The controller is communicatin
-
8/2/2019 Plc+Status+Check+List
2/19
12
3
4
5
1
23
4
1
2
3
1
2
3
4
5
1
2
3
1
2
3
4
5
5
COMMUNICATION WITH THE CONTROLNET BRID
Off No power or No inter 1757-SR
Red < 1 second Powerup with 1757-SRM establSolid Red Critical communication failure
forces have not been enabled
Flashing Red 1757-SRM NVS update, 1757-
Solid Red Powerup self test or 1757-SRM
1757-SRM MODULE STATUS INDICATORS
Off No power to 1757-SRMSolid Green The 1757-SRM OK
Flashing Green The 1757-SRM OK but not co
Solid Green 1757-SRM chassis state in prim
1757-ENBT- MODULE STATUS INDICATORSN
Off Not powered, No IP address
Green Flash Communication activity present
Off No power or 1757-SRM chassis
Green < 1 second Powerup with patrner 1757-SR
Flashing Red Connection time out
Off No data transmission
Solid Green Ready
Solid Green CIP connections
Flashing Green No connections
Solid Red Duplicate IP address
Flashing Red and Gr Self Test
Solid Green In operation
Flashing Green Standby
Solid Red Major fault
Flashing Green Data transmission in progress
Off No power
Flashing Red Minor fault
-
8/2/2019 Plc+Status+Check+List
3/19
1
2
3
4
1
2
3
4
4
1
2
3
4
1
2
3
4
1
2
3
4
5
3
5
3
I/O module removed
Wrong I/O module insertedFLASH program update in
Off
The module is performing a sel
Incorrect node configuration
Off
Steady Green
Off
Steady Red
Alternating Red/Gre
No power
Faulted Unit
Self Test
Alternating Red/Off In correct node configurationLED STATUS (A or B)
Channel Disabled
Normal Operation
Flashing Green/Off
Flashing Red/Off
Flashing Red/Green
Temporary errors or Node is no
Media Fault or No other nodes
Incorrect network configuration
NO POWER
1756-PA2 POWER SUPPLY 120/240VAC INPUT 2 AMP 5
THIS C
Steady green
Flashing green
Steady red Major fault
6.2 COMMUNICATION WITH THE RACK-2 CONTROLMOD
Off Module not communicating
Steady green Connections established
No connections established
4 Flashing Red
Steady red Faulted module
Alternating red/green
Alternating red/off
Media fault
COMM A ORChannel disabled
Normal Operation
Temporary network errors
Off
Incorrect network configuration
COMM A &
No power
Flashing green/off
Flashing red/off
Flashing red/green
Power-Solid Green This supply is operating properl
Power-Solid Green This supply is operating properl
Power-OFF
1606- XL- 240DR: 24VDC POWER SUPPLY UNIT 10A
THIS C
-
8/2/2019 Plc+Status+Check+List
4/19
5
1
2
1
2
3
4
1
3
5
7
Flashing Red The Chassis bad
- There are no devices in th
Either:
Off The controller is in Program or
Solid Green
Flashing Red If a new controller, the controlle
Steady red The controller is faulted. Cycle
Steady green Normal operation is occurring.
Flashing Green
- The controller does not co
Solid Green The controller is communicatin
Flashing Temporary network errors have
The Controller is in Run mode
Off
One or more devices in the I/O
Off A channel is disabled. Program
-
8/2/2019 Plc+Status+Check+List
5/19
YES NODESCRIPTION
y but is the only supply providing power to the chassis
ICATORS
overable fault, so it cleared the project from memory
REMARKS
OMBINATION OF STATUS INDICATORS
erly
de, but the redundant power supply is turned OFF
OK INDICATOR
specified range
input power is not supplied
uding input power, but output cable (1756-CPR2) is not
e
may apply:
BATTERY INDICATOR
he controller does not show this indication
uring power-down, the controller is saving the project to its
ng a project to or from nonvolatile memory
occurred
I/O INDICATOR
I/O configuration of the controller
ntain a project (controller memory is empty)
or 95% or more dischaged
RUN INDICATOR
est mode
with all the devices in its I/O configuration
-
8/2/2019 Plc+Status+Check+List
6/19
E MODULES
NBR-1 STATUS (OK INDICATOR)
OMMUNICATION LED INDICATOR
comm activity
ishing patrner communication
RM non critical falure or 1757-SRM configured improperly
critical failure
HEALTH LED INDICATOR
municating with other modules
ary state
T (Network) LED STATUS INDICATOR
( Sampled every 250ms)
CHASSIS STATE LED INDICATOR
state is in secondary or failed state
M determining primary state
LINK LED STATUS INDICATOR
OK LED STATUS INDICATOR
-
8/2/2019 Plc+Status+Check+List
7/19
Checkthe
Module
L
EDstatus
Checkthe
ModuleLED
status
DC OUTPUT
OMBINATION OF STATUS INDICATORS
NET ADAPTER MODULE (ACNR15)LE STATUS
Ch
ecktheModule
LEDstatus
B LED INDICATOR
Checkthe
ModuleLED
status
LED INDICATOR
Checkthe
Module
LEDstatus
y but is the only supply providing power to the chassis
y but is the only supply providing power to the chassis
OMBINATION OF STATUS INDICATORS
-
8/2/2019 Plc+Status+Check+List
8/19
I/O configuration of the controller
est mode
r requires a firmware
ower. If the fault
RUN INDICATOR
ntain a project (controller memory is empty)
with all the devices in its I/O configuration
occurred. Check media
I/O INDICATOR
onfiguration of the controller are not resopnding
Network Channel Status Indicators
network for redundant
-
8/2/2019 Plc+Status+Check+List
9/19
YES NO
YES NO
1.The supply is turned OFF
2. Line voltage is not within the specified range
3. All connections are made, but input power is not supplied
1756-PA72 REDUNDANT POWER SUPPLY STATUS INDICATORS -RIGHT
SL. NO. LED STATUS DESCRIPTIONSTATUS
3Power-OFF
All possible connections are made, but the redundant power supply is turned OFF
REMARKS
THIS COMBINATION OF STATUS INDICATORS
1Power-Solid Green
Both supplies are operating properly
4.All connections are made, including input power, but output cable (1756-CPR2) is not connected
5. The supply is ON but defective
Power-Solid GreenThis supply is operating properly but is the only supply providing power to the chassis adapter module
1756-PA72 REDUNDANT POWER SUPPLY STATUS INDICATORS -LEFT
SL. NO. LED STATUS DESCRIPTIONSTATUS
REMARKS
4Power- OFF
Any of the following conditions may apply:
Non red -Solid Amber
2
Non red -Off
Non red -Solid Amber
Non red- OFF
Non red -Solid Amber
THIS COMBINATION OF STATUS INDICATORS
1
Power-Solid GreenThis supply is operating properly but is the only supply providing power to the chassis adapter module
Non red -Solid Amber2
Power-Solid Green Both supplies are operating properlyNon red -Off
3
4
1.The supply is turned OFF
2. Line voltage is not within the specified range
3. All connections are made, but input power is not supplied4.All connections are made, including input power, but output cable (1756-CPR2) is not connected
5. The supply is ON but defective
Power- OFFAny of the following conditions may apply:
Non red- OFF
Power-OFFAll possible connections are made, but the redundant power supply is turned OFF
-
8/2/2019 Plc+Status+Check+List
10/19
YES NO
1
23
4
5
1
3
12
2
3
4
3 Flasing Amber
2 Solid Green
1 OFF
I/O INDICATOR
1 Off
OK INDICATOR
1756-L63 PROCESSOR STATUS INDICATORS-TOP
SL. NO. LED STATUS DESCRIPTIONSTATUS
REMARKS
A new controller or major fault occurred
BATTERY INDICATOR
Off The battery supports memory
If the controller is SERIES-A, The controller does not show this indication
If the controller is SERIES-B, During power-down, the controller is saving the project to its internal non
Flashing Red
No power is applied
Solid Green The controller is OKFlashing Green The controller is storing or loading a project to or from nonvolatile memory
Solid Red The Controller detected a nonrecoverable fault, so it cleared the project from memory
Off
Either:
- There are no devices in the I/O configuration of the controller
- The controller does not contain a project (controller memory is empty)
Solid Green The controller is communicating with all the devices in its I/O configuration
Flashing Green One or more devices in the I/O configuration of the controller are not resopnding
Either the battery is not installed or 95% or more dischaged
RUN INDICATOR
Off The controller is in Program or Test modeSolid Green The Controller is in Run mode
Solid Red
The Chassis bad
FORCE INDICATOR
- No tags contain I/O force values
- I/O forces are inactive (disabled)
- I/O forces are active (enabled)Solid Amber
- I/O force values may or may not exist2
Flashing Red
One or more input or output addresses have been forced to an ON or OFF state, but the forces have not
been enabled
-
8/2/2019 Plc+Status+Check+List
11/19
YES NO
1
2
3
4
5
1
3
12
2
3
4
2 Solid Green
1 Off
Flashing Red
2 Solid Amber
Flasing Amber
Solid Green The Controller is in Run mode
I/O INDICATOR
Either:
- There are no devices in the I/O configuration of the controller
- I/O forces are active (enabled)
- I/O force values may or may not exist
One or more input or output addresses have been forced to an ON or OFF state, but the forces have not
been enabled
Flashing Red The Chassis bad
FORCE INDICATOR
- No tags contain I/O force values- I/O forces are inactive (disabled)1 OFF
3
The Controller detected a nonrecoverable fault, so it cleared the project from memory
LED STATUS DESCRIPTION
OK INDICATOR
Off No power is applied
Solid Green The controller is OKFlashing Green The controller is storing or loading a project to or from nonvolatile memory
Solid Red
1756-L63 PROCESSOR STATUS INDICATORS-BOTTOM
SL. NO.STATUS
REMARKS
A new controller or major fault occurred
BATTERY INDICATOR
Off The battery supports memory
If the controller is SERIES-A, The controller does not show this indication
If the controller is SERIES-B, During power-down, the controller is saving the project to its internal non
Solid Red Either the battery is not installed or 95% or more dischaged
RUN INDICATOR
Off The controller is in Program or Test mode
- The controller does not contain a project (controller memory is empty)
Solid Green The controller is communicating with all the devices in its I/O configuration
Flashing Green One or more devices in the I/O configuration of the controller are not resopnding
-
8/2/2019 Plc+Status+Check+List
12/19
YES NO
1
2
3
4
5
1
2
3
4
1
2
3
4
YES NO
12
3
4
5
1
2
3
4
1
2
3
4 Display Display showing as SYNC [Synchronised with Primary]
CHASSIS STATE LED INDICATOR
Off No power or 1757-SRM chassis state is in secondary or failed state
Green < 1 second
Flashing Red 1757-SRM NVS update, 1757-SRM non critical falure or 1757-SRM configured improperly
COMMUNICATION LED INDICATOR
Off No power or No inter 1757-SRM comm activity
Powerup with patrner 1757-SRM determining primary state
Solid Green 1757-SRM chassis state in primary state
Red < 1 second Powerup with 1757-SRM establishing patrner communication
Solid Red Critical communication failure
Green Flash Communication activity present ( Sampled every 250ms)
HEALTH LED INDICATOR
Off No power to 1757-SRMSolid Green The 1757-SRM OK
Flashing Green The 1757-SRM OK but not communicating with other modules
Solid Red Powerup self test or 1757-SRM critical failure
1757-SRM MODULE STATUS INDICATORS-BOTTOM
HEALTH LED INDICATOR
1757-SRM MODULE STATUS INDICATORS-TOP
STATUSREMARKS
SL. NO. LED STATUS DESCRIPTIONSTATUS
REMARKS
Display Display showing as PRIM [Primary]
SL. NO. LED STATUS DESCRIPTION
Solid Red Powerup self test or 1757-SRM critical failure
Flashing Red 1757-SRM NVS update, 1757-SRM non critical falure or 1757-SRM configured improperly
COMMUNICATION LED INDICATOR
Off No power or No inter 1757-SRM comm activity
Off No power to 1757-SRM
Solid Green The 1757-SRM OK
Flashing Green The 1757-SRM OK but not communicating with other modules
CHASSIS STATE LED INDICATOROff No power or 1757-SRM chassis state is in secondary or failed state
Green < 1 second Powerup with patrner 1757-SRM determining primary state
Solid Green 1757-SRM chassis state in primary state
Red < 1 second Powerup with 1757-SRM establishing patrner communication
Solid Red Critical communication failure
Green Flash Communication activity present ( Sampled every 250ms)
-
8/2/2019 Plc+Status+Check+List
13/19
YES NO
1
23
4
5
1
2
3
1
23
4
5
6
7
YES NO
1
2
3
4
5
1
2
3
12
3
4
5
6
7
Display Display indication 192.168.0.X1-PWQS-OK
Display Display indication 192.168.0.X2-QS-OK
Flashing Red Minor fault
Flashing Red and Green Self Test
OK LED STATUS INDICATOR
Off No powerSolid Green In operation
Flashing Green Standby
Solid Red Major fault
Flashing Red Connection time out
LINK LED STATUS INDICATOR
Off No data transmission
Solid Green Ready
Flashing Green Data transmission in progress
Solid Red Duplicate IP address
Flashing Red Connection time out
1757-ENBT- MODULE STATUS INDICATORS-TOP
NET (Network) LED STATUS INDICATOR
Off Not powered, No IP address
Solid Green CIP connections
SL. NO. LED STATUS DESCRIPTIONSTATUS
LED STATUS DESCRIPTIONSTATUS
REMARKS
Solid Red Major fault
Flashing Red Minor fault
Flashing Red and Green Self Test
1757-ENBT- MODULE STATUS INDICATORS-BOTTOM
SL. NO.
NET (Network) LED STATUS INDICATOR
Off Not powered, No IP address
Solid Green CIP connections
Flashing Green No connections
Solid Red Duplicate IP address
REMARKS
OK LED STATUS INDICATOR
Off No power
Solid Green In operationFlashing Green Standby
LINK LED STATUS INDICATOR
Off No data transmission
Solid Green Ready
Flashing Green Data transmission in progress
Flashing Green No connections
-
8/2/2019 Plc+Status+Check+List
14/19
YES NO
1
2
4
5
1
2
3
4
1
2
3
4
4
5
YES NO
1
2
4
5
12
3
4
1
2
3
4
5
6 Display Display indication QS-%CXX-KPIV-nC16-A#05-OK
Flashing Green/Off Temporary errors or Node is not configured to go online
Flashing Red/Off Media Fault or No other nodes present on network
Alternating Red/Green Self Test
Flashing Red/Green Incorrect network configuration
Alternating Red/Off In correct node configuration
LED STATUS (A or B)
Off Channel Disabled
Steady Green Normal Operation
Green Noremal operation
Flashing Green Controlnet network configuration error, Network cabling error, or no other active nodes on the network
CNBR-1 CHANNEL STATUS A and B INDICATOR
LED STATUS (A & B)
Off No powerSteady Red Faulted Unit
CNBR-1 STATUS (OK INDICATOR)
Off Module not communicating t o a power supply fault or internal fault
Red Invalid controlnet address (For a redundant system this may be a temporary condition during chassis
3 Flashing Red-Module has invalid firmware
3 Flashing Red-Module has invalid firmware
-Flash update in progress
Display Display indication PWQS-%CXX-KPAV-nC20-A#04-OK
COMMUNICATION WITH THE CONTROLNET BRIDGE MODULES-BOTTOM
SL. NO. LED STATUS DESCRIPTION
STATUS
REMARKS
STATUSREMARKS
Red
-Flash update in progress
Invalid controlnet address (For a redundant system this may be a temporary condition during chassis
COMMUNICATION WITH THE CONTROLNET BRIDGE MODULES-TOP
SL. NO. LED STATUS DESCRIPTION
Module not communicating to a power supply fault or internal fault
CNBR-1 STATUS (OK INDICATOR)
Off
Flashing Red/Off
No power
Faulted Unit
Self Test
In correct node configuration
Channel Disabled
Noremal operation
LED STATUS (A or B)
Controlnet network configuration error, Network cabling error, or no other active nodes on the network
CNBR-1 CHANNEL STATUS A and B INDICATOR
LED STATUS (A & B)
Off
Alternating Red/Green
Flashing Green
Green
Flashing Green/Off
Steady Green
Off
Flashing Red/Green
Steady Red
Alternating Red/Off
Normal Operation
Temporary errors or Node is not configured to go online
Media Fault or No other nodes present on network
Incorrect network configuration
-
8/2/2019 Plc+Status+Check+List
15/19
YES NO
1
23
4
1
2
3
4
1
2
3
4
5
YES NO
1
2
3
4
1
23
4
1
2
3
4
5
Temporary network errors
Flashing red/off Media fault
Flashing red/green Incorrect network configuration
Off Module not communicating due to a powersupply fault or internal fault.
Steady green Connections established
No connections established
Steady red Major fault
5 Flashing Red
I/O module removed
Wrong I/O module inserted
FLASH program update in progress
STATUSREMARKS
MODULE STATUS
Flashing green
COMM A & B LED INDICATOR
Off No power
Alternating red/green The module is performing a self-testAlternating red/off Incorrect node configuration
Steady red Faulted module
COMM A OR B LED INDICATOR
Off Channel disabled
Steady green Normal Operation
Flashing green/off
Alternating red/off
Steady red
5 Flashing Red
REMARKS
MODULE STATUS
Off
Steady greenFlashing green
Steady red
Module not communicating due to a powersupply fault or internal fault.
Connections establishedNo connections established
Major fault
SL. NO. LED STATUS DESCRIPTIONSTATUS
Flashing red/green
Flashing red/off
6.2 COMMUNICATION WITH THE RACK-2 CONTROLNET ADAPTER MODULE (ACNR15)-MIDDLE
Media fault
Incorrect network configuration
SL. NO. LED STATUS DESCRIPTION
Off
6.2 COMMUNICATION WITH THE RACK-2 CONTROLNET ADAPTER MODULE (ACNR15)-TOP
Flashing green/off
Steady green Normal Operation
Temporary network errors
I/O module removed
Wrong I/O module inserted
The module is performing a self-test
Incorrect node configuration
Faulted module
Channel disabled
FLASH program update in progress
No power
COMM A OR B LED INDICATOR
COMM A & B LED INDICATOR
Off
Alternating red/green
-
8/2/2019 Plc+Status+Check+List
16/19
YES NO
1
23
4
1
2
3
4
1
2
3
4
5
Steady green Normal Operation
Flashing green/off Temporary network errors
Flashing red/off Media fault
Flashing red/green Incorrect network configuration
Alternating red/green The module is performing a self-test
Alternating red/off Incorrect node configuration
Steady red Faulted module
COMM A OR B LED INDICATOR
Off Channel disabled
Steady red Major fault
5 Flashing Red
I/O module removed
Wrong I/O module inserted
FLASH program update in progress
COMM A & B LED INDICATOR
Off No power
REMARKS
MODULE STATUS
Off Module not communicating due to a powersupply fault or internal fault.
Steady green Connections establishedFlashing green No connections established
6.2 COMMUNICATION WITH THE RACK-2 CONTROLNET ADAPTER MODULE (ACNR15)-BOTTOM
STATUSSL. NO. LED STATUS DESCRIPTION
-
8/2/2019 Plc+Status+Check+List
17/19
YES NO
1
2
YES NO
1
2
YES NO
1
2
YES NO
1
2
THIS COMBINATION OF STATUS INDICATORS
Power-Solid Green
Power-OFF
STATUSREMARKS
This supply is operating properly but is the only supply providing power to the chassis adapter module
NO POWER
THIS COMBINATION OF STATUS INDICATORS
THIS COMBINATION OF STATUS INDICATORS
Power-Solid Green This supply is operating properly but is the only supply providing power to the chassis adapter module
Power-OFF NO POWER
1756-PA2 POWER SUPPLY 120/240VAC INPUT 2 AMP 5VDC OUTPUT-LEFT
SL. NO. LED STATUS DESCRIPTIONSTATUS
REMARKS
1756-PA2 POWER SUPPLY 120/240VAC INPUT 2 AMP 5VDC OUTPUT-RIGHT
SL. NO. LED STATUS DESCRIPTION
THIS COMBINATION OF STATUS INDICATORS
STATUSREMARKS
STATUSREMARKS
Power-Solid Green This supply is operating properly but is the only supply providing power to the chassis adapter module
Power-OFF NO POWER
1606- XL- 240DR: 24VDC POWER SUPPLY UNIT 10A-RIGHT
1606- XL- 240DR: 24VDC POWER SUPPLY UNIT 10A-LEFT
Power-Solid Green This supply is operating properly but is the only supply providing power to the chassis adapter module
Power-OFF
SL. NO. LED STATUS DESCRIPTION
NO POWER
SL. NO. LED STATUS DESCRIPTION
-
8/2/2019 Plc+Status+Check+List
18/19
-
8/2/2019 Plc+Status+Check+List
19/19
YES NO
1
23
4
5
1
2
2
3
4
1
2
3
4
1
3
2
3 Flasing Amber
1 OFF
Solid Green2
FORCE INDICATOR
- No tags contain I/O force values
- I/O forces are inactive (disabled)
- I/O forces are active (enabled)
- I/O force values may or may not exist
One or more input or output addresses have been forced to an ON or OFF state, but the forces have not
been enabled
Solid Amber
Solid Red Either the battery is not installed or 95% or more dischaged
If the controller is SERIES-B, During power-down, the controller is saving the project to its internal non
BATTERY INDICATOR
Off The battery supports memory
If the controller is SERIES-A, The controller does not show this indication
Flashing Temporary network errors have occurred. Check media
Off
Flashing Green
Solid Green
Steady red The controller is faulted. Cycle power. If the fault
Flashing Red The Chassis bad
Network Channel Status Indicators
Off A channel is disabled. Program network for redundant
Steady green Normal operation is occurring.
Solid Green The Controller is in Run mode
I/O INDICATOR
Either:
- There are no devices in the I/O configuration of the controller1
- The controller does not contain a project (controller memory is empty)The controller is communicating with all the devices in its I/O configuration
One or more devices in the I/O configuration of the controller are not resopnding
Flashing Green The controller is storing or loading a project to or from
Solid Red Controller detected a nonrecoverable fault and cleared
Flashing Red If a new controller, the controller requires a firmware
RUN INDICATOR
Off The controller is in Program or Test mode
SL. NO. LED STATUS DESCRIPTIONSTATUS
REMARKS
OK INDICATOR
Off No power is applied
Solid Green Controller is OK.
1769-L35CR: COMPACT LOGIX CONTROL-RIGHT