PlantPAx Library
KB AID 62682
Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 2
What is the PlantPAx Library?
The PlantPAx Library is a predefined library of controller code (Add-On
Instructions), display elements (global objects), and faceplates that let you
quickly assemble large applications with proven strategies, rich
functionality, and known performance.
Step 1: Drop and
Configure AOI
Step 2: Drop global object
on display and assign
to AOI instance
Step 3: Access faceplate
from global object at runtime
for control and maintenance
The PlantPAx Library is supported through Rockwell Automation Technical Support as long
as the Add-On Instructions have not been modified from the original distribution.
Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 3
What types of PlantPAx Library objects are contained in KB AID 62682?
KB AID 62682 contains:
• PlantPAx Library of Process Objects (begin with P_) which can be used
to develop applications to automate your process devices.
• PlantPAx Library of Logix Diagnostic Objects (begin with L_) which can
be used to collect and share diagnostic information from your Logix
program.
• Built-in Instruction faceplates and display objects which can be used in
conjunction with the Process Objects and provide a consistent look and
feel to your displays
PlantPAx Library Objects include comprehensive documentation
Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 4
What do you need in order to use the PlantPAx Library?
The PlantPAx library consists of predefined application code for
RSLogix5000 and FactoryTalk View. The following table shows
compatibility with these products by PlantPAx library revision:
PlantPAx Library Revision 1.0 1.5 2.0
FactoryTalk View SE 6.1 Y Y Y
FactoryTalk View SE 6.0 Y Y Y
FactoryTalk View SE 5.1 Y Y N
FactoryTalk View ME 6.1 N Y Y
FactoryTalk View ME 6.0 N Y Y
FactoryTalk View ME 5.1 N Y N
RSLogix 5000 Professional v19.x Y Y Y
RSLogix 5000 Professional v18.x Y Y Y
RSLogix 5000 Professional v17.x Y Y N
RSLogix 5000 Professional v16.x Y Y N
Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 5
What are the differences between PlantPAx Library revisions?
• Different revisions of the library are released for:
– Additional library objects
– Revised functionality and features
– Different look-and-feel
• Changing PlantPAx Library revisions in existing applications is not
necessary; we will continue to support older revisions of the library
• You can’t mix and match revisions in a single application because there
are shared resources (i.e. AOI’s and Global Objects) for each revision as
well as look and feel differences in the faceplates and displays
• The Library is pre-built application code; not controller firmware or
system software. Updating PlantPAx Library revision on existing
applications requires careful planning; reviewing the PlantPAx Library
release notes would be the first step.
• New projects should use the latest revision of the PlantPAx Library
Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 6
What are the differences in features between PlantPAx Library Revisions?
PlantPAx Library Revision 1.0 1.5 2.0
PanelView Plus Support
(FactoryTalk ME)N Y Y
Support for FactoryTalk View 6.0
(and later) remote
acknowledgement of alarms
N N Y
Refactored displays based on
ASM GuidelinesN N Y
A summary of feature differences between revisions is shown in the table
below:
For a complete list of feature differences and revised functionality, refer to the
release notes for the specific PlantPAx Library revision
Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 7
What Process Objects are available in each PlantPAx Library Revision?
Process Object Description 1.0 1.5 2.0
Input Processing
P_AIn Analog Input Y Y Y
P_AInAdv Advanced Analog Input Y Y Y
P_AInDual Dual Sensor Analog Input Y Y Y
P_AInMulti Multiple Analog Input N N Y
P_Din Discrete Input Object Y Y Y
Motors
P_Motor Single-Speed Motor Y Y Y
P_Motor2Spd Two-Speed Motor Y Y Y
P_MotorRev Reversing Motor Y Y Y
P_MotorHO Hand Operated Motor Y Y Y
P_VSD Variable Speed Drive Y Y Y
Valves
P_ValveMO Motor Operated Valve Y Y Y
P_ValveSO Solenoid Operated Valve Y Y Y
P_ValveHO Hand Operated Valve Y Y Y
P_ValveMP Mix Proof Valve N N Y
P_ValveC Analog/pulsed control valve N N Y
Output Processing
P_AOut Analog Output Y Y Y
P_DOut Discrete Output N N Y
Process Object Description 1.0 1.5 2.0
Additional Objects
P_DoseFM Flow Meter Dosing Y Y Y
P_DoseWS Weigh Scale Dosing Y Y Y
P_StrapTbl Tank Strapping Table N N Y
P_Fanout Analog Fanout N N Y
P_PTCompPressure/Temperature
CompensationN N Y
P_D4SDDiscrete 2, 3, or 4 State
DeviceN N Y
P_nPos n Position Device N N Y
P_Logic Boolean Logic N N Y
Extension Objects
P_Intlk Interlock with First Out Y Y Y
P_Perm Permissives Y Y Y
P_ResInh Restart Inhibit Y Y Y
P_RunTime Run time and start counter Y Y Y
P_ValveStats Valve Statistics N N Y
Supporting Objects
P_Alarm Common Alarm Block Y Y Y
P_Mode Common Mode Block Y Y Y
P_Reset Central Reset Y Y Y
Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 8
What Logix Diagnostic Objects are available in each PlantPAx Library Revision?
A summary of the Logix Diagnostic Objects available in each PlantPAx
Library revision is shown in the table below:
Logix Diagnostic Object Description 1.0 1.5 2.0
L_CPU Controller Usage Monitor Y Y Y
L_TaskMonitor Controller Task Monitor Y Y Y
L_Redun Redundant Controller Monitor N N Y
L_ChangeDet Controller Change Detector N N Y
Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 9
What Built-in Instruction displays are available in each PlantPAx Library Revision?
A summary of the Built-in instruction faceplate and global objects available
in each PlantPAx Library revision is shown in the table below:
RSLogix5000 Function
Block InstructionDescription 1.0 1.5 2.0
PIDEEnhanced PID (including faceplate
for PIDE auto tune option)Y Y Y
RMPS Ramp/Soak Y Y Y
TOT Totalizer Y Y Y
See 1756-RM006 for more information on the PIDE, RMPS, and TOT instructions
Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 10
PlantPAx LibraryFrequently Asked Questions
Q: Do I need to use the PlantPAx Library if I am using PlantPAx?
A: No. The use of the PlantPAx Library of Process Objects is not a
requirement of the PlantPAx System. However, we do highly recommend
the use of the PlantPAx Library of Logix Diagnostic Objects on all PlantPAx
Systems.
Q: Where can I get the latest revision of the PlantPAx Library of
Process Objects?
A: The latest revision of the PlantPAx Library of Process Objects can
always be found on the Rockwell Automation Knowledgebase in article ID
62682. A TechConnect support contract is required for download.
Copyright © 2011 Rockwell Automation, Inc. All rights reserved. 11
PlantPAx Library Frequently Asked Questions
Q: I am currently using PlantPAx Library revision 1.5 in my plant. I
would like to use one of the new objects revision 2.0. What should I
do?
A: Using two different revisions of the PlantPAx Library in a single
application is not supported. You may use the PlantPAx library 2.0 as a
guide to develop similar functionality in your application code without
breaking your existing objects.
Q: How do I get support for the PlantPAx Library?
A: If you experience technical issues with the PlantPAx Library, you can
call Rockwell technical support. Be sure to ask for PlantPAx support.