Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 1 of 88
PLANT BOWEN UNIT 3
FLUE GAS DESULFURIZATION SYSTEM
JBR VESSEL SYSTEM
ADVANCED CONTROLS OVERVIEW
NOTE: The Drawings used in this Student Guide are for Training Purposes Only. When troubleshooting these systems in the field always, use the latest drawing revision from the Document Control System.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 2 of 88
Table of Contents
ADVANCED CONTROLS OVERVIEW 4
1 Safety Considerations 4
2 Drawing References 5
3 Controls Description 13
3.1 Terms And Definitions 13
3.2 DCS Logic Description 14
3.2.1 JBR Single Element Level Controller 14
3.2.2 JBR Multi Element Level Controller 16
3.2.3 JBR Level Control Manual/Auto Station 18
3.2.4 JBR Flow Controller 20
3.2.5 JBR Narrow Range Level 22
3.2.6 JBR Wide Range Level 23
3.2.7 JBR Level Transmitter Auto Flush 24
3.2.8 JBR Transmitter Manual Flush 28
3.2.9 JBR Level Transmitter A Flush Valve (WF-XV-5020A) 30
3.2.10 JBR Level Transmitter B Flush Valve (WF-XV-5020B) 32
3.2.11 JBR Level Transmitter C Flush Valve (WF-XV-5020C) 34
3.2.12 JBR Density Measurement 36
3.2.13 Gypsum Drawoff Level Error Controller 37
3.2.14 JBR Gypsum Drawoff Density Controller 39
3.2.15 JBR Gypsum Drawoff Controller 41
3.2.16 JBR Ph Measurement 43
3.2.17 JBR Differential Pressure Measurement 44
3.2.18 Limestone Slurry Density Measurement 45
3.2.19 JBR Limestone Slurry Flow Measurement 46
3.2.20 JBR Ph Controller 47
3.2.21 JBR Slurry Flow Controller 50
3.2.22 JBR Wash Control Master 51
3.2.23 JBR Shell And Gas Riser Wash 53
3.2.24 Mist Eliminator Wash 56
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 3 of 88
Table of Contents
3.3 Instrumentation 59
3.4 Control Valves And Limit Switches 60
3.5 DCS Control Valve Commands 71
3.6 Control Valve Power Supply 74
3.7 Start Permissives 76
3.8 Setpoint And Alarm Limits 77
3.9 Alarm Response 78
4 DCS Tag-Out Process Logic 79
5 DCS Control Screens 87
5.1 Scrubber Jet Bubbling Reactor Level – D3M20008 Screen 87
5.2 Scrubber Jet Bubbling Reactor Wash – D3M20010, 11, 12 Screen 88
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 4 of 88
ADVANCED CONTROLS OVERVIEW 1 Safety Considerations
1. All Operating Companies Safety and Health Manuals shall be followed at all times.
2. The Southern Company Generation Clearance Procedure shall be followed at all times.
3. A thorough Job Safety Briefing (JSB) shall be completed before beginning work.
4. Employees should always use the proper (Personal Protection Equipment) PPE for the task they are performing.
5. Personnel must observe standard safety precautions when working around or with pressurized piping systems.
6. When using the JBR Vessel System hose stations, personnel must wear protective eyewear at all times. The aim and discharge of pressurized water toward solid surfaces may dislodge dirt or other foreign material into the surrounding environment at a high rate of velocity.
7. Personnel must be aware that many components of the JBR Vessel System are maintained in an automatic mode of operation. The equipment may start at any time without warning.
8. Personnel should remain clear of all rotating machinery, whether operating or in standby, at all times during unit operation.
9. Rotating machinery must never be placed in service without the appropriate equipment guards in place.
10. No attempt should be made to bypass or eliminate equipment safety interlocks. Doing so could result in equipment damage and possible injury to plant personnel.
11. Follow proper Confined Space Entry Procedures when entering confined spaces.
12. When employees are performing work on or associated with exposed lines or equipment energized at 50 volts or more, persons trained in First Aid including Cardiopulmonary Resuscitation (CPR), shall be available within 4 minutes per OSHA 1910.269 requirements.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 5 of 88
2 Drawing References
The JBR Vessel System is illustrated on the following drawings:
Number Sheet Rev Title
P&IDs
D3M20008 1 1 FGD Project P&ID – Jet Bubbling Reactor JBR Instrumentation
D3M20009 1 2 FGD Project P&ID – Jet Bubbling Reactor JBR Piping
D3M20010 1 1 FGD Project P&ID – Jet Bubbling Reactor Deck, JBR Shell, & Gas Riser Wash
D3M20011 1 0 FGD Project P&ID – Jet Bubbling Reactor Lower Mist Eliminator Spray System
D3M20012 1 1 FGD Project P&ID – Jet Bubbling Reactor Upper Mist Eliminator Spray System
Functionals
D3F01130 1 0 Scrubber JBR Level Functional Control Diagram
D3F01131 1 0 Scrubber Level Control Valve Functional Control Diagram
D3F01131 2 0 Scrubber Level Control Valve Functional Control Diagram
D3F01131 3 0 Scrubber Level Control Logic Functional Control Diagram
D3F01132 1 0 Scrubber JBR Level Control Logic Functional Control Diagram
D3F01133 1 0 Scrubber JBR Level Transmitter Flush Logic Functional Control Diagram
D3F01134 1 0 Scrubber JBR Level Transmitter Flush Permits Functional Control Diagram
D3F01135 1 0 Scrubber JBR Level Transmitter Flush Logic Functional Control Diagram
D3F01136 1 0 Scrubber JBR Level Transmitter A Flush Valve A Functional Control Diagram
D3F01136 2 0 Scrubber JBR Level Transmitter A Flush Valve B Functional Control Diagram
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 6 of 88
2 Drawing References
Number Sheet Rev Title
Functionals
D3F01136 3 0 Scrubber JBR Level Transmitter A Flush Valve C Functional Control Diagram
D3F01137 1 A Scrubber JBR Level Transmitter B Flush Valve A Functional Control Diagram
D3F01137 2 A Scrubber JBR Level Transmitter B Flush Valve B Functional Control Diagram
D3F01137 3 A Scrubber JBR Level Transmitter B Flush Valve C Functional Control Diagram
D3F01138 1 A Scrubber JBR Level Transmitter C Flush Valve A Functional Control Diagram
D3F01138 2 A Scrubber JBR Level Transmitter C Flush Valve B Functional Control Diagram
D3F01138 3 A Scrubber JBR Level Transmitter C Flush Valve C Functional Control Diagram
D3F01138 1 A Scrubber JBR Level Transmitter Flush Logic Functional Control Diagram
D3F01139 1 A Scrubber JBR Level Transmitter Flush Logic Functional Control Diagram
D3F01140 1 A Scrubber JBR Wash Control Master Logic Functional Control Diagram
D3F01141 1 A Scrubber JBR Shell And Wall Wash Schedule Functional Control Diagram
D3F01142 1 A Scrubber Mist Eliminator Wash Schedule Functional Control Diagram
D3F01143 1 A Scrubber JBR Shell And Gas Riser Wash Logic Functional Control Diagram
D3F01144 1 A Scrubber Mist Eliminator Wash Logic Functional Control Diagram
D3F01145 1 A Scrubber Mist Eliminator Wash Logic Functional Control Diagram
D3F01150 1 A Scrubber JBR Gas Riser Wash Valve Functional Control Diagram
D3F01151 1 A Scrubber JBR Shell Wash Valve Functional Control Diagram
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 7 of 88
2 Drawing References
Number Sheet Rev Title
Functionals
D3F01152 1 A Scrubber JBR Lower Mist Eliminator Valve 5441 Functional Control Diagram
D3F01153 1 A Scrubber JBR Lower Mist Eliminator Valve 5442 Functional Control Diagram
D3F01154 1 A Scrubber JBR Lower Mist Eliminator Valve 5443 Functional Control Diagram
D3F01155 1 A Scrubber JBR Lower Mist Eliminator Valve 5444 Functional Control Diagram
D3F01156 1 A Scrubber JBR Lower Mist Eliminator Valve 5445 Functional Control Diagram
D3F01157 1 A Scrubber JBR Lower Mist Eliminator Valve 5446 Functional Control Diagram
D3F01158 1 A Scrubber JBR Lower Mist Eliminator Valve 5447 Functional Control Diagram
D3F01159 1 A Scrubber JBR Lower Mist Eliminator Valve 5448 Functional Control Diagram
D3F01160 1 A Scrubber JBR Lower Mist Eliminator Valve 5449 Functional Control Diagram
D3F01161 1 A Scrubber JBR Lower Mist Eliminator Valve 5451 Functional Control Diagram
D3F01162 1 A Scrubber JBR Lower Mist Eliminator Valve 5452 Functional Control Diagram
D3F01163 1 A Scrubber JBR Lower Mist Eliminator Valve 5453 Functional Control Diagram
D3F01164 1 A Scrubber JBR Lower Mist Eliminator Valve 5454 Functional Control Diagram
D3F01165 1 0 Scrubber JBR Lower Mist Eliminator Valve 5455 Functional Control Diagram
D3F01166 1 0 Scrubber JBR Lower Mist Eliminator Valve 5456 Functional Control Diagram
D3F01167 1 0 Scrubber JBR Lower Mist Eliminator Valve 5457 Functional Control Diagram
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 8 of 88
2 Drawing References
Number Sheet Rev Title
Functionals
D3F01168 1 0 Scrubber JBR Lower Mist Eliminator Valve 5458 Functional Control Diagram
D3F01169 1 0 Scrubber JBR Lower Mist Eliminator Valve 5459 Functional Control Diagram
D3F01200 1 0 Scrubber JBR Density Measurement Functional Control Diagram
D3F01201 1 0 Scrubber JBR Density Control Functional Control Diagram
D3F01202 1 0 Scrubber JBR Density Control Logic Functional Control Diagram
D3F01210 1 0 Scrubber JBR Measurements Functional Control Diagram
D3F01211 1 0 Scrubber JBR Limestone Measurements Functional Control Diagram
D3F01212 1 0 Scrubber pH Control Functional Control Diagram
D3F01213 1 0 Scrubber pH Control Logic Functional Control Diagram
D3F01214 1 0 Scrubber pH Control Logic Functional Control Diagram
DCS I/O Wiring Diagrams
E3E30410 1 1 FGD Project - Wiring Diagram - JBR Elect Bldg DCS I/O Cabinet 3100 Power Supply
E3E30410 2 2 FGD Project - Wiring Diagram JBR Elect Bldg DCS I/O Cabinet 3101 Base 0
E3E30410 3 2 FGD Project - Wiring Diagram JBR Elect Bldg DCS I/O Cabine 3101 Base 0
E3E30410 4 3 FGD Project - Wiring Diagram JBR Elect Bldg DCS I/O Cabinet 3101 Base 1
E3E30410 5 3 FGD Project - Wiring Diagram JBR Elect Bldg DCS I/O Cabinet 3101 Base 1
E3E30410 6 2 FGD Project - Wiring Diagram JBR Elect Bldg DCS I/O Cabinet 3102 Base 2
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 9 of 88
2 Drawing References
Number Sheet Rev Title
DCS I/O Wiring Diagrams
E3E30410 7 2 FGD Project - Wiring Diagram JBR Elect Bldg DCS I/O Cabinet 3102 Base 2
E3E30410 8 4 FGD Project - Wiring Diagram JBR Elect Bldg DCS I/O Cabinet 3102 Base 3
E3E30410 9 1 FGD Project - Wiring Diagram JBR Elect Bldg DCS I/O Cabinet 3102 Base 3
E3E30411 1 1 FGD Project - Wiring Diagram JBR Elect Bldg DCS I/O Cabinet 3103 Power Supply
E3E30411 2 3 FGD Project - Wiring Diagram JBR Elect Bldg DCS I/O Cabinet 3104 Base 0
E3E30411 3 0 FGD Project - Wiring Diagram JBR Elect Bldg DCS I/O O Cabinet 3104 Base 0
E3E30411 4 2 FGD Project - Wiring Diagram JBR Elect Bldg DCS I/O Cabinet 3104 Base 1
E3E30411 5 1 FGD Project - Wiring Diagram JBR Elect Bldg DCS I/O Cabinet 3104 Base 1
E3E30411 6 0 FGD Project - Wiring Diagram JBR Elect Bldg DCS I/O O Cabinet 3105 Base 2
E3E30411 7 1 FGD Project - Wiring Diagram JBR Elect Bldg DCS I/O O Cabinet 3105 Base 2
E3E30411 8 0 FGD Project - Wiring Diagram JBR Elect Bldg DCS I/O Cabinet 3105 Base 3
E3E30411 9 0 FGD Project - Wiring Diagram JBR Elect Bldg DCS I/O Cabinet 3105 Base 3
E3E30445 2 2 FGD Project Wiring Diagram DCS I/O Termination Cabinet Equipment No. EE-TC-7001
E3E30445 3 2 FGD Project Wiring Diagram DCS I/O Termination Cabinet Equipment No. EE-TC-7001
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 10 of 88
2 Drawing References
Number Sheet Rev Title
Loop Diagrams
B3IMEP5741 1 0 Loop Sheet JBR Mist Eliminator DP ME-PDIT-5741
B3ISKL5021 1 0 Loop Sheet JBR Narrow Range Level SK-LIT-5021A/SK-LIT-5021B/SK-LIT-5021C
B3ISKL5022 1 0 Loop Sheet JBR Wide Range Level SK-LIT-5022A/SK-LIT-5022B/SK-LIT-5022C
B3ISKP5711 1 0 Loop Sheet JBR Differential Pressure SK-PDIT-5711A/SK-PDIT-5711B/SK-PDIT-5711C
B3IWFX5020 1 0 Loop Sheet JBR LVL IND XMTR A Flush Control Valve WF-XV-5020A
B3IWFX5020 2 0 Loop Sheet JBR LVL IND XMTR A Flush Control Valve WF-XV-5020B
B3IWFX5020 3 0 Loop Sheet JBR LVL IND XMTR A Flush Control Valve WF-XV-5020C
B3ISKF5030 1 0 Loop Sheet JBR Level Control Flow SK-FIT-5030
B3ISKF5030 2 0 Loop Sheet JBR Level Control Flow SK-FIT-5030
B3IMUX5421 1 0 Loop Sheet JBR Gas Riser Wash Control Valve MU-XV-5421
B3IMUX5431 1 0 Loop Sheet JBR Shell Wash Control Valve MU-XV-5431
B3IMEX5441 1 0 Loop Sheet Lower Mist Eliminator Control Valve ME-XV-5441
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 11 of 88
2 Drawing References
Number Sheet Rev Title
Loop Diagrams
B3IMEX5442 1 0 Loop Sheet Lower Mist Eliminator Control Valve ME-XV-5442
B3IMEX5443 1 0 Loop Sheet Lower Mist Eliminator Control Valve ME-XV-5443
B3IMEX5444 1 0 Loop Sheet Lower Mist Eliminator Control Valve ME-XV-5444
B3IMEX5445 1 0 Loop Sheet Lower Mist Eliminator Control Valve ME-XV-5445
B3IMEX5446 1 0 Loop Sheet Lower Mist Eliminator Control Valve ME-XV-5446
B3IMEX5447 1 0 Loop Sheet Lower Mist Eliminator Control Valve ME-XV-5447
B3IMEX5448 1 0 Loop Sheet Lower Mist Eliminator Control Valve ME-XV-5448
B3IMEX5449 1 0 Loop Sheet Lower Mist Eliminator Control Valve ME-XV-5449
B3IMEX5451 1 0 Loop Sheet Upper Mist Eliminator Control Valve ME-XV-5451
B3IMEX5452 1 0 Loop Sheet Upper Mist Eliminator Control Valve ME-XV-5452
B3IMEX5453 1 0 Loop Sheet Upper Mist Eliminator Control Valve ME-XV-5453
B3IMEX5454 1 0 Loop Sheet Upper Mist Eliminator Control Valve ME-XV-5454
B3IMEX5455 1 0 Loop Sheet Upper Mist Eliminator Control Valve ME-XV-5455
B3IMEX5456 1 0 Loop Sheet Upper Mist Eliminator Control Valve ME-XV-5456
B3IMEX5457 1 0 Loop Sheet Upper Mist Eliminator Control Valve ME-XV-5457
B3IMEX5458 1 0 Loop Sheet Upper Mist Eliminator Control Valve ME-XV-5458
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 12 of 88
2 Drawing References
Number Sheet Rev Title
Loop Diagrams
B3IMEX5459 1 0 Loop Sheet Upper Mist Eliminator Control Valve ME-XV-5459
B3IMUX5421 1 0 Loop Sheet JBR Gas Riser Wash Control Valve MU-XV-5421
B3IMUX5431 1 0 Loop Sheet JBR Shell Wash Control Valve MU-XV-5431
Vendor O&M Manuals
S52284 1 A FGD - Scrubber - 2 1/2" TSC As A-90 Deck Wash Nozzle
S52287 1 0 FGD - Scrubber - 3/8" MP 218 A-115 Wall Wash Nozzle
S81395 1 A FGD - Scrubber - 1/2" MP 218 A-110 Wall Wash Nozzle
S81397 1 C FGD - Scrubber - 2 1/2" TSC 87 A-90 Deck Wash Nozzle
S81430 1 F Scrubber - FGD - Mist Elimination System - General Arrangement
S81432 1 A Scrubber - FGD - Mist Elimination System - Operation & Maintenance Manual
S82393 1 C Scrubber - FGD - Mist Elimination System - General Arrangement - Lower Spray Wash System
S82788 1 A FGD - Scrubber - JBR Sparger Tube Alignment Grid Module Sheet 2
S82789 1 A FGD - Scrubber - JBR Sparger Tube Alignment Grid - Details Sheet 3
S85397 1 0 FGD - Scrubber - 1/2" MP 218 A-110 Wall Wash Nozzle - Final Inspection Report
S85399 1 A FGD - Scrubber - 2 1/2" TSC 87 A-90 Deck Wash Nozzle - Final Inspection Report
S90677 1 A Scrubber-FGD- JBR Inlet Duct Internal Piping- Quality Manual
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 13 of 88
3 Controls Description
The following subsections contain narrative interpretations of the DCS Logic and controls associated with the JBR Vessel System including alarms, permissives, interlocks, trips, and equipment modes of operation.
3.1 Terms and Definitions
1. Mode
A MODE is a defined set of operating conditions (recipe, sequence, automatic start/stop, interlocks) that controls a group of items of the process. A MODE is used to reduce/simplify operator interaction and/or optimize control of the process.
2. Interlock
An INTERLOCK is a condition that stops an item of the process from running regardless of the DCS mode of control (Auto/Manual status) or Operator intervention. An Interlock is used to reduce risk to personnel, avoid damage to equipment in the plant, or stop a release of material into the environment. An Interlock may also be used to stop-close an item of the process based on the action of another item of the process.
3. Permissive
A PERMISSIVE is a condition that must be met in order for an item of the process to start regardless of the DCS mode of control (Auto/Manual status) or Operator intervention. A Permissive is used to reduce risk to personnel, avoid damage to equipment in the plant, or stop a release of material into the environment. A Permissive may also be used to start-open an item of the process based on the action of another item of the process.
4. Alarm
An ALARM is a condition that notifies the operator of an unplanned event in the process (i.e., without “Mode” or Operator intervention). An Alarm is used to notify personnel of process upsets, unplanned stop/start of an item of the process, an equipment trip, or a reached limit.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 14 of 88
3.2 DCS Logic Description
The following subsections contain narrative interpretations of the DCS Logic and controls associated with the JBR Vessel System including alarms, permissives, interlocks, trips, and equipment modes of operation.
3.2.1 JBR Single Element Level Controller
The following subsections contain narrative interpretations of the DCS Logic and controls associated with JBR SINGLE ELEMENT LEVEL CONTROLLER including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawing:
Number Sheet Rev Title
Functionals
D3F01130 1 0 Scrubber JBR Level Functional Control Diagram
D3F01131 1 0 Scrubber Level Control Valve Functional Control Diagram
JBR SINGLE ELEMENT LEVEL CONTROLLER, automatically calculates a valve position setpoint for JBR LEVEL CONTROL MANUAL/AUTO STATION based on JBR Narrow Range Level Measurement and JBR Normal Liquid Level
At the DCS, JBR SINGLE ELEMENT LEVEL CONTROLLER is equipped with the following controls:
MANUAL: Allows the DCS Operator to manipulate controller output through a range of 0-100%
AUTO: DCS automatically modulates controller output through a range of 0-100%
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 15 of 88
3.2.1 JBR Single Element Level Controller
JBR Single Element Level Controller
If any JBR Level Transmitter is being flushed, controller output is held at current value
When controller is not active, output tracks JBR LEVEL CONTROL MANUAL/AUTO STATION output to allow for bumpless transfer when controller is activated
Controller is active when ONE or ALL of the following are true:
Element Condition True Not True Selected Not Selected SINGLE ELEMENT
OVERRIDE X
JBR LEVEL CONTROL FLOW (MU-FIT-5030)
Signal Flagged Bad X
JBR MAKE UP HEADER FLOW (MU-FIT-5135)
Signal Flagged Bad X
GYPSUM DRAWOFF FLOW (GD-FIT-5654)
Signal Flagged Bad X
JBR LS SLURRY FLOW A (LS-FIT-5589A)
Signal Flagged Bad X
JBR LS SLURRY FLOW B (LS-FIT-5589B)
Signal Flagged Bad X
JBR PREQUENCH SPRAY FLOW A (PQ-FIT-5132A)
Signal Flagged Bad X
JBR PREQUENCH SPRAY FLOW B (PQ-FIT-5132B)
Signal Flagged Bad X
FGD Diverter Damper Online Position X FGD Diverter Damper
Position Signal Flagged Bad X
Unit Load Signal Flagged Bad X
Controller Logic
Automatically sums an Output by calculating Setpoint and Process Variable inputs
Output: Setpoint for JBR LEVEL CONTROL MANUAL/AUTO STATION
Setpoint: JBR Normal Liquid Level setpoint
Process Variable: JBR Narrow Range Level Measurement
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 16 of 88
3.2.2 JBR Multi Element Level Controller
The following subsections contain narrative interpretations of the DCS Logic and controls associated with JBR MULTI ELEMENT LEVEL CONTROLLER including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawing:
Number Sheet Rev Title
Functionals
D3F01130 1 0 Scrubber JBR Level Functional Control Diagram
D3F01131 1 0 Scrubber Level Control Valve Functional Control Diagram
JBR MULTI ELEMENT LEVEL CONTROLLER, automatically calculates a flow setpoint for JBR FLOW CONTROLLER based on JBR Narrow Range Level Measurement and JBR Normal Liquid Level.
At the DCS, JBR MULTI ELEMENT LEVEL CONTROLLER is equipped with the following controls:
MANUAL: Allows the operator to manipulate controller output.
AUTO: DCS automatically modulates controller output.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 17 of 88
3.2.2 JBR Multi Element Level Controller
JBR Multi Element Level Controller Logic
If any JBR Level Transmitter is being flushed, controller output is held at current value
When controller is not active, output tracks the difference of the following calculations:
FLOW IN: The sum of JBR Make-Up Water Flow, Level Control Flow, Limestone Slurry Flow and Pre-Quench Flow measurements
FLOW OUT: The sum of JBR Plume Flow (calculated from plant load) and Gypsum Draw off Flow measurements
Controller is active when ONE or ALL of the following are true:
True Not True Selected Not Selected SINGLE ELEMENT
OVERRIDE X
JBR LEVEL CONTROL FLOW (MU-FIT-5030)
Signal Flagged Bad X
JBR MAKE UP HEADER FLOW (MU-FIT-5135)
Signal Flagged Bad X
GYPSUM DRAWOFF FLOW (GD-FIT-5654)
Signal Flagged Bad X
JBR LS SLURRY FLOW A (LS-FIT-5589A)
Signal Flagged Bad X
JBR LS SLURRY FLOW B (LS-FIT-5589B)
Signal Flagged Bad X
JBR PREQUENCH SPRAY FLOW A (PQ-FIT-5132A)
Signal Flagged Bad X
JBR PREQUENCH SPRAY FLOW B (PQ-FIT-5132B)
Signal Flagged Bad X
FGD Diverter Damper Online Position X FGD Diverter Damper
Position Signal Flagged Bad X
Unit Load Signal Flagged Bad X
Controller Logic
Automatically sums an Output by calculating Setpoint and Process Variable inputs.
Output: Setpoint for JBR FLOW CONTROLLER
Setpoint: JBR Normal Liquid Level setpoint
Process Variable: JBR Narrow Range Level measurement
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 18 of 88
3.2.3 JBR Level Control Manual/Auto Station
The following subsections contain narrative interpretations of the DCS Logic and controls associated with the JBR LEVEL CONTROL MANUAL / AUTO STATION including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawing:
Number Sheet Rev Title
Functional
D3F01131 1 0 Scrubber Level Control Valve Functional Control Diagram
JBR LEVEL CONTROL MANUAL/AUTO STATION, allows for manual or automatic control of JBR LEVEL CONTROL VALVE (SK-LV-5021).
At the DCS, JBR SINGLE ELEMENT LEVEL CONTROLLER is equipped with the following controls:
MANUAL: Allows the operator to manipulate controller output effectively changing valve position.
AUTO: DCS automatically modulates controller output effectively changing valve position.
TAGOUT: Designates JBR LEVEL CONTROL VALVE (SK-LV-5021) to the DCS Tagout List.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 19 of 88
3.2.3 JBR Level Control Manual/Auto Station
JBR Level Control Manual/Auto Station Controller
Modulates valve position from 0-100% either automatically or manually
Controller is forced to MANUAL and cannot be placed in AUTO if any one of three Narrow Range Level transmitters deviate greater than >1% from the median value
Controller Logic
Sums an Output range of 0-100% equal to Setpoint input.
Output: Demand to JBR LEVEL CONTROL VALVE (SK-LV-5021).
Setpoint: Output from SINGLE ELEMENT FLOW CONTROLLER or MULTI ELEMENT FLOW CONTROLLER.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 20 of 88
3.2.4 JBR Flow Controller
The following subsections contain narrative interpretations of the DCS Logic and controls associated with JBR FLOW CONTROLLER including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawing:
Number Sheet Rev Title
Functional
D3F01131 1 0 Scrubber Level Control Valve Functional Control Diagram
JBR FLOW CONTROLLER, automatically calculates a valve position setpoint for JBR LEVEL CONTROL MANUAL/AUTO STATION based on JBR MULTI ELEMENT LEVEL CONTROLLER output corrected with flow out of the JBR and calculated flow into the JBR.
At the DCS, JBR FLOW CONTROLLER is equipped with the following controls:
MANUAL: Allows the DCS Operator to manipulate controller output.
AUTO: DCS automatically modulates controller output.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 21 of 88
3.2.4 JBR Flow Controller
JBR Flow Controller
When Controller is not active, output tracks JBR LEVEL CONTROL MANAUL/AUTO STATION output to allow for bumpless transfer when controller is activated.
Controller is active when ONE or ALL of the following are true:
True Not True Selected Not Selected SINGLE ELEMENT
OVERRIDE X
JBR LEVEL CONTROL FLOW (MU-FIT-5030)
Signal Flagged Bad X
JBR MAKE UP HEADER FLOW (MU-FIT-5135)
Signal Flagged Bad X
GYPSUM DRAWOFF FLOW (GD-FIT-5654)
Signal Flagged Bad X
JBR LS SLURRY FLOW A (LS-FIT-5589A)
Signal Flagged Bad X
JBR LS SLURRY FLOW B (LS-FIT-5589B)
Signal Flagged Bad X
JBR PREQUENCH SPRAY FLOW A (PQ-FIT-5132A)
Signal Flagged Bad X
JBR PREQUENCH SPRAY FLOW B (PQ-FIT-5132B)
Signal Flagged Bad X
FGD Diverter Damper Online Position X FGD Diverter Damper
Position Signal Flagged Bad X
Unit Load Signal Flagged Bad X Controller Logic
Automatically sums an Output by calculating Setpoint and Process Variable inputs
Output: Setpoint for JBR LEVEL CONTRL MANUAL/AUTO STATION.
Setpoint: JBR MULTI ELEMENT LEVEL CONTROLLER Output summed with the sum of JBR Plume Flow (calculated from plant load) and Gypsum Draw off Flow measurements.
Process Variable: The sum of JBR Make-Up Water Flow, Level Control Flow, Limestone Slurry Flow and Pre-Quench Flow measurements.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 22 of 88
3.2.5 JBR Narrow Range Level
The following subsections contain narrative interpretations of the DCS Logic and controls associated with the JBR NARROW RANGE LEVEL including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawing:
Number Sheet Rev Title
Functional
D3F01130 1 0 Scrubber JBR Level Functional Control Diagram
Three level transmitters ranged 0-36 inwc measure JBR liquid level.
SK-LIT-5021A
SK-LIT-5021B
SK-LIT-5021C
Each level transmitter sends a 4-20ma signal to the DCS representative of JBR liquid level. The median value of all three signals make up JBR NARROW RANGE LEVEL indication and is used for dynamic JBR liquid level control
If any of the three transmitters deviate greater than 1% from the median value:
JBR LEVEL CONTROL MANUAL AUTO STATION is forced to MANUAL and cannot be placed in AUTO until the deviation is no longer present
A transmitter deviation alarm is annunciated
Transmitter Auto Flush is prevented
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 23 of 88
3.2.6 JBR Wide Range Level
The following subsections contain narrative interpretations of the DCS Logic and controls associated with the JBR WIDE RANGE LEVEL including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawing:
Number Sheet Rev Title
Functional
D3F01130 1 0 Scrubber JBR Level Functional Control Diagram
Three level transmitters ranged 0-180 inwc are used to measure JBR liquid level
SK-LIT-5022A
SK-LIT-5022B
SK-LIT-5022C
Each level transmitter sends a 4-20ma signal to the DCS representative of JBR liquid level. The median value of all three signals is corrected with JBR SLURRY DENSITY to make up JBR WIDE RANGE LEVEL indication and is used for operating alarms and equipment interlocks.
If any of the three transmitters deviate greater than 1% from the median value:
A transmitter deviation alarm is annunciated
Transmitter Auto Flush is prevented from operating
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 24 of 88
3.2.7 JBR Level Transmitter Auto Flush
The following subsections contain narrative interpretations of the DCS Logic and controls associated with the JBR LEVEL TRANSMITTER AUTO FLUSH including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawing:
Number Sheet Rev Title
Functional
D3F01133 1 0 Scrubber JBR Level Transmitter Flush Logic Functional Control Diagram
JBR LEVEL TRANSMITTER AUTO FLUSH cycles JBR Level Transmitter A, B & C Flush Valves open in sequence six times daily
At the DCS, the JBR Level Transmitter Auto Flush is equipped with the following controls:
AUTO FLSH SEQ ON: Enables sequence that automatically opens and closes transmitter flush valves
AUTO FLSH SEQ OFF: Disables sequence that automatically opens and closes transmitter flush valves
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 25 of 88
3.2.7 JBR Level Transmitter Auto Flush
The JBR LEVEL TRANSMITTER AUTO FLUSH function cycles Level Transmitter Auto Flush Valves (WF-XV-5020A, B & C) open and close in a sequence.
The sequence is scheduled to take place six times daily:
1st Flush @ 0100
2nd Flush @ 0500
3rd Flush @ 0900
4th Flush @ 1300
5th Flush @ 1700
6th Flush @ 2100
If a flush valve is in MANUAL it is skipped and the sequence continues
If feedback OPEN for any of the three flush valves is not received in a 24 hour period, an alarm is annunciated
Only one transmitter can be flushed at any given time
JBR LEVEL TRANSMITTER AUTO FLUSH sequence logic
Permissives
True Not True Selected Not Selected JBR LEVEL
TRANSMITTER AUTO FLUSH
AUTO FLSH SEQ ON X
DIVERERTER DAMPER In FGD Bypass Position X
JBR WR LEVEL Signal Deviation X
JBR NR LEVEL Signal Deviation X
JBR WR LEVEL > 8.8 Feet X
JBR WR LEVEL < 18 Feet X
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 26 of 88
3.2.7 JBR Level Transmitter Auto Flush
Meet All Permissives
Flush Initiated
300 second timer for JBR LEVEL TRANSMITTER B AUTO FLUSH
600 second timer for JBR LEVEL TRANSMITTER C AUTO FLUSH
JBR LEVEL TRANSMITTER A FLUSH VALVE (WF-XV-5020A) status AUTO
JBR LEVEL TRANSMITTER B status NOT FLUSHING
JBR LEVEL TRANSMITTER C status NOT FLUSHING
120 second timer to allow 30 second Flushing Time and 90 seconds for signal to settle after flushing has completed
JBR LEVEL TRANSMITTER A status FLUSHING
30 second timer
JBR LEVEL TRANSMITTER A FLUSH VALVE (WF-XV-5020A) command OPEN
JBR LEVEL TRANSMITTER A FLUSH VALVE (WF-XV-5020A) feedback OPEN
30 second timer TIMED OUT
JBR LEVEL TRANSMITTER A FLUSH VALVE (WF-XV-5020A) command OPEN removed
JBR LEVEL TRANSMITTER A FLUSH VALVE (WF-XV-5020A) feedback CLOSED
120 second timer to allow 30 second Flushing Time and 90 seconds for signal to settle after flushing has completed
JBR LEVEL TRANSMITTER A status NOT FLUSHING
300 second timer for JBR LEVEL TRANSMITTER B AUTO FLUSH TIMED OUT
JBR LEVEL TRANSMITTER B FLUSH VALVE (WF-XV-5020B) status AUTO
JBR LEVEL TRANSMITTER A status NOT FLUSHING
JBR LEVEL TRANSMITTER C status NOT FLUSHING
120 second timer to allow 30 second Flushing Time and 90 seconds for signal to settle after flushing has completed
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 27 of 88
3.2.7 JBR Level Transmitter Auto Flush
JBR LEVEL TRANSMITTER B status FLUSHING
30 second timer
JBR LEVEL TRANSMITTER B FLUSH VALVE (WF-XV-5020B) command OPEN
JBR LEVEL TRANSMITTER B FLUSH VALVE (WF-XV-5020B) feedback OPEN
30 second timer TIMED OUT
JBR LEVEL TRANSMITTER B FLUSH VALVE (WF-XV-5020B) command OPEN removed
JBR LEVEL TRANSMITER B FLUSH VALVE (WF-XV-5020B) feedback CLOSED
120 second timer to allow 30 second Flushing Time and 90 seconds for signal to settle after flushing has completed
JBR LEVEL TRANSMITTER B status NOT FLUSHING
600 second timer for JBR LEVEL TRANSMITTER C AUTO FLUSH TIMED OUT
JBR LEVEL TRANSMITTER C FLUSH VALVE (WF-XV-5020C) status AUTO
JBR LEVEL TRANSMITTER A status NOT FLUSHING
JBR LEVEL TRANSMITTER B status NOT FLUSHING
120 second timer to allow 30 second Flushing Time and 90 seconds for signal to settle after flushing has completed
JBR LEVEL TRANSMITTER C status FLUSHING
30 second timer
JBR LEVEL TRANSMITTER C FLUSH VALVE (WF-XV-5020C) command OPEN
JBR LEVEL TRANSMITTER C FLUSH VALVE (WF-XV-5020C) feedback OPEN
30 second timer TIMED OUT
JBR LEVEL TRANSMITTER C FLUSH VALVE (WF-XV-5020B) command OPEN removed
JBR LEVEL TRANSMITTER C FLUSH VALVE (WF-XV-5020C) feedback CLOSED
120 second timer to allow 30 second Flushing Time and 90 seconds for signal to settle after flushing has completed
JBR LEVEL TRANSMITTER C status NOT FLUSHING
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 28 of 88
3.2.8 JBR Transmitter Manual Flush
The following subsections contain narrative interpretations of the DCS Logic and controls associated with the JBR TRANSMITTER MANUAL FLUSH including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawing:
Number Sheet Rev Title
Functional
D3F01133 1 0 Scrubber JBR Level Transmitter Flush Logic Functional Control Diagram
JBR LEVEL TRANSMITTER MANUAL FLUSH automatically opens and closes the selected JBR Level Transmitter Flush Valve in a sequence
At the DCS, the JBR LEVEL TRANSMITTER MANUAL FLUSH is equipped with the following controls:
MANUAL FLUSH: Starts a sequence that automatically opens and closes the selected flush valve
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 29 of 88
3.2.8 JBR Transmitter Manual Flush
A manual flush can be performed while JBR LEVEL TRANSMITTER AUTO FLUSH is activated.
JBR TRANSMITTER MANUAL FLUSH sequence logic
Permissives
True Not True Selected Not Selected
DIVERERTER DAMPER In FGD Bypass Position X
JBR WR LEVEL Signal Deviation X
JBR NR LEVEL Signal Deviation X
JBR WR LEVEL > 8.8 Feet X
JBR WR LEVEL < 18 Feet X CORRESPONDING JBR LEVEL TRANSMITTER
FLUSH VALVE AUTO X
REMAINING JBR LEVEL TRANSMITTERS
FLUSHING X
Meet all permissives
Select corresponding JBR LEVEL TRANSMITTER MANUAL FLUSH MANUAL FLUSH
120 second timer to allow 30 second Flushing Time and 90 seconds for signal to settle after flushing has completed
Corresponding JBR LEVEL TRANSMITTER status FLUSHING
30 second timer
Corresponding JBR LEVEL TRANSMITTER FLUSH VALVE command OPEN
Corresponding JBR LEVEL TRANSMITTER FLUSH VALVE feedback OPEN
30 second timer TIMED OUT
Corresponding JBR LEVEL TRANSMITTER FLUSH VALVE command OPEN removed
Corresponding JBR LEVEL TRANSMITTER FLUSH VALVE feedback CLOSED
120 second timer to allow 30 second Flushing Time and 90 seconds for signal to settle after flushing has completed
Corresponding JBR LEVEL TRANSMITTER status NOT FLUSHING
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 30 of 88
3.2.9 JBR Level Transmitter A Flush Valve (WF-XV-5020A)
The following subsections contain narrative interpretations of the DCS Logic and controls associated with the JBR TRANSMITTER A FLUSH VALVE (WF-XV-5020A) including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawings:
Number Sheet Rev Title
Functionals
D3F01136 1 0 Scrubber JBR Level Transmitter A Flush Valve Functional Control Diagram
D3F01137 1 0 Scrubber JBR Level Transmitter B Flush Valve Functional Control Diagram
D3F01138 1 0 Scrubber JBR Level Transmitter C Flush Valve Functional Control Diagram
JBR TRANSMITTER A FLUSH VALVE (WF-XV-5020A) controls the flow of Make-Up Water to both JBR NARROW RANGE TRANSMITTER A (SK-LIT-5021A) and JBR WIDE RANGE LEVEL TRANSMITTER A (SK-LIT-5022A) sensing lines.
At the DCS, JBR TRANSMITTER A FLUSH VALVE (WF-XV-5020A) is equipped with the following controls.
AUTO: Allows DCS TRANSMITTER AUTO FLUSH and TRANSMITTER MANAUL FLUSH logic to automatically open and close valve as needed
OPEN: Issues open command
CLOSE: Removes open command
TAGOUT: Designates valve to DCS Tagout list and inhibits operation
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 31 of 88
3.2.9 JBR Level Transmitter A Flush Valve (WF-XV-5020A)
JBR TRANSMITTER A FLUSH VALVE control logic
Automatic control allows JBR LEVEL TRANSMITTER AUTO FLUSH and JBR LEVEL TRANSMITTER MANUAL FLUSH logic to open and close valve as needed
If an OPEN or CLOSE command is issued, valve is removed from AUTO
Alarms
Alarm When
JBR LEVEL TRANSMITTER A FLUSH VALVE FAILED
Feedback OPEN is not received within 5 seconds after OPEN command is issued
Feedback CLOSED is present for greater than 5 seconds after OPEN command is issued
JBR LEVEL TRANSMITTER A 24 HR W/O FLUSH Feedback OPEN is not received within 24 hours
Permissives
True Not True Selected Not Selected JBR LEVEL
TRANSMITTER A FLUSH VALVE
DCS Tagout X
JBR LEVEL TRANSMITTER B FLUSH
VALVE CLOSED for 30 seconds X
JBR LEVEL TRANSMITTER C FLUSH
VALVE CLOSED for 30 seconds X
Valve DCS Control Open
Meet all Permissives
Select valve control OPEN
Valve command OPEN
Valve feedback OPENED
Valve DCS Control Close
Select valve control CLOSE
Valve command OPEN removed
Valve feedback CLOSED
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 32 of 88
3.2.10 JBR Level Transmitter B Flush Valve (WF-XV-5020B)
The following subsections contain narrative interpretations of the DCS Logic and controls associated with the JBR TRANSMITTER B FLUSH VALVE (WF-XV-5020B) including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawings:
Number Sheet Rev Title
Functionals
D3F01136 1 0 Scrubber JBR Level Transmitter A Flush Valve Functional Control Diagram
D3F01137 1 0 Scrubber JBR Level Transmitter B Flush Valve Functional Control Diagram
D3F01138 1 0 Scrubber JBR Level Transmitter C Flush Valve Functional Control Diagram
JBR TRANSMITTER B FLUSH VALVE (WF-XV-5020B) controls the flow of Make-Up Water to both JBR NARROW RANGE TRANSMITTER B (SK-LIT-5021B) and JBR WIDE RANGE LEVEL TRANSMITTER B (SK-LIT-5022B) sensing lines
At the DCS, JBR TRANSMITTER B FLUSH VALVE (WF-XV-5020B) is equipped with the following controls
AUTO: Allows DCS TRANSMITTER AUTO FLUSH and TRANSMITTER MANAUL FLUSH logic to automatically open and close valve as needed
OPEN: Issues open command
CLOSE: Removes open command
TAGOUT: Designates valve to DCS Tagout list and inhibits operation
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 33 of 88
3.2.10 JBR Level Transmitter B Flush Valve (WF-XV-5020B)
JBR TRANSMITTER B FLUSH VALVE control logic
Automatic control allows JBR LEVEL TRANSMITTER AUTO FLUSH and JBR LEVEL TRANSMITTER MANUAL FLUSH logic to open and close valve as needed
If an OPEN or CLOSE command is issued, valve is removed from AUTO
Alarms
Alarm When
JBR LEVEL TRANSMITTER B FLUSH VALVE FAILED
Feedback OPEN is not received within 5 seconds after OPEN command is issued
Feedback CLOSED is present for greater than 5 seconds after OPEN command is issued
JBR LEVEL TRANSMITTER B 24 HR W/O FLUSH Feedback OPEN is not received within 24 hours
Permissives
True Not True Selected Not Selected JBR LEVEL
TRANSMITTER B FLUSH VALVE
DCS Tagout X
JBR LEVEL TRANSMITTER A FLUSH
VALVE CLOSED for 30 seconds X
JBR LEVEL TRANSMITTER C FLUSH
VALVE CLOSED for 30 seconds X
Valve DCS Control Open
Meet all Permissives
Select valve control OPEN
Valve command OPEN
Valve feedback OPENED
Valve DCS Control Close
Select valve control CLOSE
Valve command OPEN removed
Valve feedback CLOSED
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 34 of 88
3.2.11 JBR Level Transmitter C Flush Valve (WF-XV-5020C)
The following subsections contain narrative interpretations of the DCS Logic and controls associated with the JBR TRANSMITTER C FLUSH VALVE (WF-XV-5020C) including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawings:
Number Sheet Rev Title
Functionals
D3F01136 1 0 Scrubber JBR Level Transmitter A Flush Valve Functional Control Diagram
D3F01137 1 0 Scrubber JBR Level Transmitter B Flush Valve Functional Control Diagram
D3F01138 1 0 Scrubber JBR Level Transmitter C Flush Valve Functional Control Diagram
JBR TRANSMITTER B FLUSH VALVE (WF-XV-5020C) controls the flow of Make-Up Water to both JBR NARROW RANGE TRANSMITTER C (SK-LIT-5021C) and JBR WIDE RANGE LEVEL TRANSMITTER C (SK-LIT-5022C) sensing lines
At the DCS, JBR TRANSMITTER C FLUSH VALVE (WF-XV-5020C) is equipped with the following controls
AUTO: Allows DCS TRANSMITTER AUTO FLUSH and TRANSMITTER MANAUL FLUSH logic to automatically open and close valve as needed
OPEN: Issues open command
CLOSE: Removes open command
TAGOUT: Designates valve to DCS Tagout list and inhibits operation
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 35 of 88
3.2.11 JBR Level Transmitter C Flush Valve (WF-XV-5020C)
JBR TRANSMITTER B FLUSH VALVE control logic
Automatic control allows JBR LEVEL TRANSMITTER AUTO FLUSH and JBR LEVEL TRANSMITTER MANUAL FLUSH logic to open and close valve as needed
If an OPEN or CLOSE command is issued, valve is removed from AUTO.
Alarms
Alarm When
JBR LEVEL TRANSMITTER C FLUSH VALVE FAILED
Feedback OPEN is not received within 5 seconds after OPEN command is issued
Feedback CLOSED is present for greater than 5 seconds after OPEN command is issued
JBR LEVEL TRANSMITTER C 24 HR W/O FLUSH Feedback OPEN is not received within 24 hours
Permissives
True Not True Selected Not Selected JBR LEVEL
TRANSMITTER BC FLUSH VALVE
DCS Tagout X
JBR LEVEL TRANSMITTER A FLUSH
VALVE CLOSED for 30 seconds X
JBR LEVEL TRANSMITTER B FLUSH
VALVE CLOSED for 30 seconds X
Valve DCS Control Open
Meet all Permissives
Select valve control OPEN
Valve command OPEN
Valve feedback OPENED
Valve DCS Control Close
Select valve control CLOSE
Valve command OPEN removed
Valve feedback CLOSED
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 36 of 88
3.2.12 JBR Density Measurement
The following subsections contain narrative interpretations of the DCS Logic and controls associated with the JBR DENSITY MEASUREMENT including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawing:
Number Sheet Rev Title
Functional
D3F01200 1 0 Scrubber JBR Density Measurement Functional Control Diagram
Two Density Transmitters ranged 0-35% measure slurry density downstream of the Gas Cooling Pumps
GD-DT-5655A
GD-DT-5655B
Each Density transmitter sends a 4-20ma signal to the DCS representative of slurry density. The average of the two signals makes up JBR DENSITY MEASURMENT
When no gas cooling pumps are running, last JBR DENSITY MEASURMENT is held
If both transmitter input signals are flagged bad or signals deviate +/- 4% from one another for more than 2 seconds:
JBR DENSITY CONTROLLER is forced to MANUAL and cannot be placed in AUTO until deviation is no longer present
Alarms
Alarm When JBR DENSITY HIGH Density measurement greater than 22%
JBR DENSITY LOW Density measurement less than 8%
JBR DENSITY TRANSMITTER DEVIATION Both transmitter signals are flagged bad High or low deviation and signal bypass is
selected
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 37 of 88
3.2.13 Gypsum Drawoff Level Error Controller
The following subsections contain narrative interpretations of the DCS Logic and controls associated with JBR GYPSUM DRAWOFF LEVEL ERROR CONTROLLER including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawing:
Number Sheet Rev Title
Functional
D3F01201 1 0 Scrubber JBR Density Control Functional Control Diagram
JBR GYPSUM DRAWOFF LEVEL ERROR CONTROLLER automatically calculates a flow setpoint for JBR GYPSUM DRAWOFF CONTROLLER based on JBR SINGLE ELEMENT CONTROLLER error and a static setpoint of -5.
At the DCS, JBR GYPSUM DRAWOFF LEVEL ERROR CONTROLLER is equipped with the following controls:
MANUAL: Allows the DCS Operator to manipulate controller output.
AUTO: DCS automatically modulates controller output.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 38 of 88
3.2.13 Gypsum Drawoff Level Error Controller
Gypsum Drawoff Level Error Controller
When Process Variable of JBR SINGLE ELEMENT LEVEL CONTROLLER deviates more than 5 from setpoint, GYPSUM DRAWOFF LEVEL ERROR CONTROLLER assists in reducing that error by increasing Gypsum Draw off Flow
Controller is not active when JBR Narrow Range Level is flagged bad
Controller Logic
Automatically sums an Output by calculating Setpoint and Process Variable inputs.
Output: Summed with JBR GYPSUM DRAWOFF DENSITY CONTROLLER Output
Setpoint: Static value of -5
Process Variable: JBR SINGLE ELEMENT LEVEL CONTROLLER control error
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 39 of 88
3.2.14 JBR Gypsum Drawoff Density Controller
The following subsections contain narrative interpretations of the DCS Logic and controls associated with JBR GYPSUM DRAWOFF DENSITY CONTROLLER including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawing:
Number Sheet Rev Title
Functional
D3F01201 1 0 Scrubber JBR Density Control Functional Control Diagram
JBR GYPSUM DRAWOFF DENSITY CONTROLLER automatically calculates a flow setpoint for JBR GYPSUM DRAWOFF CONTROLLER based on JBR Slurry Density Measurement and a static setpoint of 20% solids by weight.
At the DCS, JBR GYPSUM DRAWOFF DENSITY CONTROLLER is equipped with the following controls:
MANUAL: Allows the DCS Operator to manipulate controller output.
AUTO: DCS automatically modulates controller output.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 40 of 88
3.2.14 JBR Gypsum Drawoff Density Controller
If no Gas Cooling Pump is running, JBR Gypsum Density measurement is flagged bad or JBR GYPSUM DRAWOFF CONTROLLER is in MANUAL, output tracks to the difference of Gypsum Draw off Flow Measurement and GYPSUM DRAWOFF LEVEL ERROR CONTROLLER output
If JBR GYPSUM DRAWOFF CONTROLLER is in AUTO, JBR GYPSUM DRAWOFF DENSITY CONTROLLER is forced to AUTO
Controller Logic
Automatically sums an Output by calculating Setpoint and Process Variable inputs.
Output: Setpoint for JBR GYPSUM DRAWOFF CONTROLLER
Setpoint: 20% solids by weight
Process Variable: JBR Slurry Density Measurement
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 41 of 88
3.2.15 JBR Gypsum Drawoff Controller
The following subsections contain narrative interpretations of the DCS Logic and controls associated with JBR GYPSUM DRAWOFF CONTROLLER including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawing:
Number Sheet Rev Title
Functional
D3F01201 1 0 Scrubber JBR Density Control Functional Control Diagram
JBR GYPSUM DRAWOFF CONTROLLER positions JBR Gypsum Draw off Density Control Valve based on Gypsum Draw off Flow and JBR GYPSUM DRAWOFF DENSITY CONTROLLER output
At the DCS, JBR GYPSUM DRAWOFF CONTROLLER is equipped with the following controls:
MANUAL: Allows the DCS Operator to manipulate controller output.
AUTO: DCS automatically modulates controller output.
TAGOUT: Designates JBR GYPSUM DRAWOFF DENSITY CONTROL VALVE (GD-DV-5655) to the DCS Tagout List
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 42 of 88
3.2.15 JBR Gypsum Drawoff Controller
JBR Gypsum Drawoff Controller
If the following criteria are met, controller is forced to manual:
True Not True Selected Not Selected JBR Gypsum Draw off
Controller DCS Tagout X
OR
Gypsum Draw off Flow Signal
Flagged Bad X
OR
Gypsum Draw off Pump A Running X OR
Gypsum Draw off Pump B Running X
If the following criteria are met, JBR GYPSUM DRAWOFF DENSITY CONTROL VALVE (GD-DV-5655) is forced closed:
True Not True Selected Not Selected
Gypsum Draw off Pump A Running X OR
Gypsum Draw off Pump B Running X
Controller Logic
Automatically sums an Output by calculating Setpoint and Process Variable inputs.
Output: Demand to JBR GYPSUM DRAWOFF DENSITY CONTROL VALVE (GD-DV-5655)
Setpoint: Output from JBR GYPSUM DRAWOFF DENSITY CONTROLLER
Process Variable: Gypsum Draw off Flow Measurement
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 43 of 88
3.2.16 JBR pH Measurement
The following subsections contain narrative interpretations of the DCS Logic and controls associated with JBR pH MEASURMENT including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawing:
Number Sheet Rev Title
Functional
D3F01210 1 0 Scrubber JBR Measurements Functional Control Diagram
Three level transmitters ranged 0-10 pH measure JBR Slurry pH
SK-AIT 5011A
SK-AIT-5011B
SK-AIT-5011C
Each level transmitter sends a 4-20ma signal to the DCS representative of JBR Slurry pH. The median value of all three signals make up JBR pH measurement
If any of the three transmitters deviate greater than 1% from the median value, JBR pH controller is forced to MANUAL and cannot be placed in AUTO until the deviation is no longer present.
Alarms
Alarm When JBR pH HIGH HIGH (diverter damper in online position) pH measurement greater than 5.5
JBR pH HIGH HIGH (diverter damper in bypass position) pH measurement greater than 10
JBR pH LOW LOW (diverter damper in online position) pH measurement less 4.5
JBR pH LOW LOW (diverter damper in bypass position) pH measurement less than 0
JBR pH TRANSMITTER DEVIATION If any transmitter deviates greater than 1%
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 44 of 88
3.2.17 JBR Differential Pressure Measurement
The following subsections contain narrative interpretations of the DCS Logic and controls associated with JBR DIFFERENTIAL PRESSURE MEASURMENT including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawing:
Number Sheet Rev Title
Functional
D3F01210 1 0 Scrubber JBR Measurements Functional Control Diagram
Three differential pressure transmitters ranged 0-30 inwc measure JBR Differential Pressure
SK-PDIT-5711A
SK-PDIT-5711B
SK-PDIT-5711C
Each differential pressure transmitter sends a 4-20ma signal to the DCS representative of the differential pressure between the JBR Vessel and JBR Exhaust. The median value of all three signals make up JBR DIFFERENTIAL PRESSURE measurement
JBR differential pressure greater than 28 INWC or less than 10 INWC triggers and alarm.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 45 of 88
3.2.18 Limestone Slurry Density Measurement
The following subsections contain narrative interpretations of the DCS Logic and controls associated with LIMESTONE SLURRY DENSITY MEASURMENT including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawing:
Number Sheet Rev Title
Functional
D3F01211 1 0 Scrubber JBR Limestone Measurements Functional Control Diagram
Two density transmitters, ranged 0-45% Solids, measure Limestone Slurry Density
LS-DT-5586A
LS-DT-5586B
Each density transmitter sends a 4-20ma signal to the DCS representative of Limestone Slurry Density. The average of the two signals make up LIMESTONE SLURRY DENSITY measurement.
If both transmitter input signals are flagged bad or signals deviate +/- 5% from one another for more than 2 seconds:
Output to JBR pH controller is held at last value
Alarms
Alarm When
LIMESTONE SLURRY DENSITY TRANSMITTER DEVIATION
Both transmitter signals are flagged bad High or low deviation and signal bypass is
selected
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 46 of 88
3.2.19 JBR Limestone Slurry Flow Measurement
The following subsections contain narrative interpretations of the DCS Logic and controls associated with LIMESTONE SLURRY FLOW MEASURMENT including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawing:
Number Sheet Rev Title
Functional
D3F01211 1 0 Scrubber JBR Limestone Measurements Functional Control Diagram
Two Flow Transmitters ranged 0-500 gpm measure limestone slurry flow out of the JBR.
LS-FIT-5589A
LS-FIT-5589B
Each transmitter sends a 4-20ma signal to the DCS representative of limestone slurry flow out of the JBR. The average of the two signals make up JBR LIMESTONE SLURRY FLOW measurement.
If both transmitter input signals are flagged bad or signals deviate +/- 20% from one another for more than 2 seconds:
JBR GYPSUM DRAWOFF CONTROLLER is forced to MANUAL and cannot be placed in AUTO until deviation is no longer present
JBR SINGLE ELEMENT LEVEL CONTROLLER is activated
JBR MULTI ELEMENT LEVEL CONTROLLER is de-activated
Alarms
Alarm When
JBR LIMESTONE SLURRY FLOW TRANSMITTER DEVIATION
Both transmitter signals are flagged bad High or low deviation and signal bypass is
selected
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 47 of 88
3.2.20 JBR pH Controller
The following subsections contain narrative interpretations of the DCS Logic and controls associated with JBR pH controller including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawing:
Number Sheet Rev Title
Functional
D3F01212 1 0 Scrubber pH Control Functional Control Diagram
JBR pH controller automatically calculates a flow setpoint for JBR SLURRY FLOW controller based on JBR pH measurement and a static setpoint of 5.2.
At the DCS, JBR pH controller is equipped with the following controls:
MANUAL: Allows the DCS Operator to manipulate controller output.
AUTO: DCS automatically modulates controller output.
JBR pH Controller
If the following criteria are met, controller is forced to manual:
True Not True Selected Not Selected JBR SLURRY FLOW
CONTROLLER Manual X
AND
JBR pH Flagged Bad X OR
BYPASS DIVERTER DAMPER POSITION
Flagged Bad X
OR
Plant Load Flagged Bad X
If the following criteria are met, controller is forced to auto and will track to LIMESTONE SLURRY FLOW measurement for two seconds:
True Not True Selected Not Selected JBR SLURRY FLOW
CONTROLLER Auto X
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 48 of 88
3.2.20 JBR pH Controller
Alarms
Alarm When
pH Manual JBR Slurry Flow Controller is in manual JBR pH Controller is in manual
pH Low JBR pH Controller error is <-0.2
-AND- Scrubber Diverter Damper is not in bypass
pH High JBR pH Controller error is >0.2
-AND- Scrubber Diverter Damper is not in bypass
Controller Logic
Automatically sums an Output by calculating Setpoint and Process Variable inputs.
Output: Setpoint for JBR SLURRY FLOW CONTROLLER
Setpoint: 5.2 pH
Process Variable: JBR pH measurement
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 49 of 88
3.2.20 JBR pH Controller
A feed forward control is used to compensate for unit load changes. Output of the JBR pH controller is biased either upward for increasing load, or downward for decreasing load over a several second period. This is to anticipate change in pH due to increase or decrease of absorbed SO2. Limestone Slurry Density measurement is used to bias the feed forward calculation.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 50 of 88
3.2.21 JBR Slurry Flow Controller
The following subsections contain narrative interpretations of the DCS Logic and controls associated with JBR SLURRY FLOW CONTROLLER including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawing:
Number Sheet Rev Title
Functional
D3F01212 1 0 Scrubber pH Control Functional Control Diagram
JBR SLURRY FLOW controller positions JBR Limestone Flow Control Valve based on Limestone Slurry Flow and JBR pH controller output
At the DCS, JBR SLURRY FLOW controller is equipped with the following controls:
MANUAL: Allows the DCS Operator to manipulate controller output
AUTO: DCS automatically modulates controller output.
TAGOUT: Designates JBR Limestone Flow Control Valve to the DCS tagout list and holds current valve position when selected.
JBR Slurry Flow Controller
If the following criteria are met, controller is forced to manual:
True Not True Selected Not Selected JBR Limestone Slurry
Flow Flagged Bad X
OR
JBR Limestone Flow Control Valve
Tagout X
Controller Logic
Automatically sums an Output by calculating Setpoint and Process Variable inputs
Output: Demand to JBR Limestone Flow Control Valve
Setpoint: Output from JBR pH controller
Process Variable: Limestone Slurry Flow Measurement
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 51 of 88
3.2.22 JBR Wash Control Master
The following subsections contain narrative interpretations of the DCS Logic and controls associated with JBR WASH CONTROL MASTER including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawing:
Number Sheet Rev Title
Functional
D3F01140 1 0 Scrubber JBR Wash Control Master Logic Functional Control Diagram
JBR WASH CONTROL MASTER enables or disables JBR Shell, Gas Riser, and Mist Eliminator automatic wash sequences.
When JBR WASH CONTROL MASTER is on, all washes are automatically executed at scheduled times
When JBR WASH CONTROL MASTER is off, washes are not automatically executed however can be initiated manually
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 52 of 88
3.2.22 JBR Wash Control Master
At the DCS, the JBR WASH CONTROL MASTER is equipped with the following controls:
WASH CTRL SEQ ON: Enables JBR Shell, Gas Riser, and Mist Eliminator automatic wash sequences.
WASH CTRL SEQ OFF: Disables JBR Shell, Gas Riser, and Mist Eliminator automatic wash sequences.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 53 of 88
3.2.23 JBR Shell and Gas Riser Wash
The following subsections contain narrative interpretations of the DCS logic and controls associated with JBR SHELL AND GAS RISER WASH including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawings:
Number Sheet Rev Title
Functionals
D3F01141 1 0 JBR Shell And Gas Riser Wash Schedule Functional Control Diagram
D3F01143 1 0 JBR Shell And Gas Riser Wash Logic Functional Control Diagram
3 JBR SHELL AND GAS RISER WASH opens and closes JBR Gas Riser and Shell wash valves in a sequence
At the DCS, 3 JBR Shell and Gas Riser Wash is equipped with the following controls:
SHELL/GAS RISER MANUAL WASH: Initiates Shell and Gas Riser Wash sequence
SHELL/GAS RISER WASH ABORT: Terminates current Shell and Gas Riser Wash sequence
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 54 of 88
3.2.23 JBR Shell and Gas Riser Wash
The JBR SHELL AND GAS RISER WASH cycles Gas Riser and Shell wash valves open and close in a sequence
The sequence is scheduled to start every two hours beginning at 0017
Each valve is open for two minutes beginning with the Gas Riser Wash Valve followed by the Wall Wash Valve 60 minutes later providing permissives are met
If permissives are not met, wash sequence is prevented with the exception of every fourth wash (e.g. 0617, 1417 and 2217)
Washes are carried out automatically when JBR WASH CONTROL MASTER is active
Permissives
True Not True Selected Not Selected
JBR WR Level High X AND
JBR Density Low X
JBR SHELL AND GAS RISER WASH sequence logic
Meet All Permissives
Wash Initiated and set
3600 second timer
120 second pulse
JBR GAS RISER WASH VALVE (MU-XV-5421) status AUTO
JBR GAS RISER WASH VALVE (MU-XV-5421) command OPEN
JBR GAS RISER WASH VALVE (MU-XV-5421) feedback OPEN
120 second pulse TIMED OUT
JBR GAS RISER WASH VALVE (MU-XV-5421) command OPEN removed
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 55 of 88
3.2.23 JBR Shell and Gas Riser Wash
JBR GAS RISER WASH VALVE (MU-XV-5421) feedback CLOSE
3600 second timer TIMED OUT
120 second timer
120 second pulse
JBR SHELL WASH VALVE (MU-XV-5431) status AUTO
JBR SHELL WASH VALVE (MU-XV-5431) command OPEN
JBR SHELL WASH VALVE (MU-XV-5431) feedback OPEN
120 second pulse TIMED OUT
JBR SHELL WASH VALVE (MU-XV-5431)) command OPEN removed
120 second timer TIMED OUT
JBR SHELL WASH VALVE (MU-XV-5431) feedback CLOSE
Wash complete and reset
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 56 of 88
3.2.24 Mist Eliminator Wash
The following subsections contain narrative interpretations of the DCS Logic and controls associated with MIST ELIMINATOR WASH logic including alarms, permissives, interlocks, trips, and equipment modes of operation.
Refer to Drawings:
Number Sheet Rev Title
Functionals
D3F01142 1 0 Scrubber Mist Eliminator Wash Schedule Functional Control Diagram
D3F01144 1 0 Scrubber Mist Eliminator Wash Logic Functional Control Diagram
D3F01145 1 0 Scrubber Mist Eliminator Wash Logic Functional Control Diagram
MIST ELIMINATOR WASH opens and closes Upper and Lower Mist Eliminator wash valves in a sequence.
At the DCS, MIST ELIMINATOR WASH is equipped with the following controls:
MIST ELIMINATOR MANUAL WASH: Initiates Mist Eliminator Wash sequence.
MIST ELIMINATOR WASH ABORT: Terminates current Mist Eliminator Wash sequence.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 57 of 88
3.2.24 Mist Eliminator Wash
JBR MIST ELIMINATOR WASH cycles 10 Upper Mist Eliminator and 10 Lower Mist Eliminator wash valves open and close in a sequence
The sequence is scheduled to start every eight hours beginning at 0001
Each valve is opened in sequence every 20 minutes for 90 seconds. The cycle begins with Lower Mist Eliminator valves followed by Upper Mist Elimininator valves providing permissives are met
If permissives are not met, wash sequence is prevented with the exception of the last wash of the day (e.g. 1600)
Washes are carried out automatically when JBR WASH CONTROL MASTER is active
MIST ELIMINATOR WASH sequence logic
Permissives
True Not True Selected Not Selected
JBR WR Level High X AND
JBR Density Low X
Meet All Permissives
Wash Initiated and set
1200 second timer
90 second pulse
JBR LOWER MIST ELIMINATOR WASH VALVE (ME-XV-5441) status AUTO
JBR LOWER MIST ELIMINATOR WASH VALVE (ME-XV-5441) command OPEN
JBR LOWER MIST ELIMINATOR WASH VALVE (ME-XV-5441) feedback OPEN
90 second pulse TIMED OUT
JBR LOWER MIST ELIMINATOR WASH VALVE (ME-XV-5441) command OPEN removed
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 58 of 88
3.2.24 Mist Eliminator Wash
JBR LOWER MIST ELIMINATOR WASH VALVE (ME-XV-5441) feedback CLOSE
1200 second timer TIMED OUT
90 second pulse
JBR LOWER MIST ELIMINATOR WASH VALVE (ME-XV-5442) status AUTO
JBR LOWER MIST ELIMINATOR WASH VALVE (ME-XV-5442) command OPEN
JBR LOWER MIST ELIMINATOR WASH VALVE (ME-XV-5442) feedback OPEN
90 second pulse TIMED OUT
JBR LOWER MIST ELIMINATOR WASH VALVE (ME-XV-5442) command OPEN removed
JBR LOWER MIST ELIMINATOR WASH VALVE (ME-XV-5442) feedback CLOSE
This sequence is repeated for all Lower then Upper Mist Eliminator Wash Valves
Mist Eliminator Washes complete and reset
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 59 of 88
3.3 Instrumentation
Range/Scale DCS I/O Drawing Tag Description
Low High Units Signal Encl. Card Slot P&ID DCS I/O
ME-PDIT-5741 Mist Eliminator
Differential Pressure
0 2.5 IN
H20 4-20mA
CS-CC-83104
310318 3 D3M20008 B3IMEP5741 SH 1
E3E30411 SH 5
SK-LIT-5021A JBR Level A1 14.2 55 IN
H20 4-20 mA
CS-CC-83104
310313 3 D3M20008 B3ISKL5021 SH 1 E3E30411 SH 4
SK-LIT-5021B JBR Level B1 14.2 55 IN
H20 4-20 mA
CS-CC-83104
310314 3 D3M20008 B3ISKL5021 SH 1 E3E30411 SH 4
SK-LIT-5021C JBR Level C1 14.2 55 IN
H20 4-20 mA
CS-CC-83104
310315 3 D3M20008 B3ISKL5021 SH 1 E3E30411 SH 5
SK-LIT-5022A JBR Level A2 0 216 IN
H20 4-20 mA
CS-CC-83104
310313 7 D3M20008 B3ISKL5022 SH 1 E3E30411 SH 4
SK-LIT-5022B JBR Level B2 0 216 IN
H20 4-20 mA
CS-CC-83104
310314 7 D3M20008 B3ISKL5022 SH 1 E3E30411 SH 4
SK-LIT-5022C JBR Level C2 0 216 IN
H20 4-20 mA
CS-CC-83104
310315 7 D3M20008 B3ISKL5022 SH 1 E3E30411 SH 5
SK-PDIT-5711A JBR Differential
Pressure A 0 30
IN H20
4-20 mA CS-CC-83104
310313 1 D3M20008 B3ISKP5711 SH 1 E3E30411 SH 4
SK-PDIT-5711B JBR Differential
Pressure B 0 30
IN H20
4-20 mA CS-CC-83104
310314 1 D3M20008 B3ISKP5711 SH 1 E3E30411 SH 4
SK-PDIT-5711C JBR Differential
Pressure C 0 30
IN H20
4-20 mA CS-CC-83104
310315 1 D3M20008 B3ISKP5711 SH 1 E3E30411 SH 5
SK-AIT-5011A JBR pH A 2 10 pH 4-20 mA CS-CC-83104
310313 2 D3M20008 B3ISKA5011 SH 1 E3E30411 SH 4
SK-AIT-5011B JBR pH B 2 10 pH 4-20 mA CS-CC-83104
310314 2 D3M20008 B3ISKA5011 SH 1 E3E30411 SH 4
SK-AIT-5011C JBR pH C 2 10 pH 4-20 mA CS-CC-83104
310315 2 D3M20008 B3ISKA5011 SH 1 E3E30411 SH 5
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 60 of 88
3.4 Control Valves And Limit Switches
DCS I/O Drawing Tag Description Function
Signal Encl. Card Slot P&ID DCS I/O
WF-XV-5020A JBR Level A Flush
Water Regulating Valve Open/Closed D3M20008
B3IWFX5020 SH 1 E3E30411 SH 2
WF-ZSO-5020A JBR Level A Flush
Water Regulating Valve Limit Switch Open
Open Limit Switch 120VAC CS-CC-83104
310304 14 D3M20008 B3IWFX5020 SH 1
E3E30411 SH 2
WF-ZSC-5020A JBR Level A Flush
Water Regulating Valve Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83104
310304 13 D3M20008 B3IWFX5020 SH 1
E3E30411 SH 2
WF-XV-5020B JBR Level B Flush
Water Regulating Valve Open/Closed D3M20008
B3IWFX5020 SH 2 E3E30411 SH 3
WF-ZSO-5020B JBR Level B Flush
Water Regulating Valve Limit Switch Open
Open Limit Switch 120VAC CS-CC-83104
310305 14 D3M20008 B3IWFX5020 SH 2
E3E30411 SH 3
WF-ZSC-5020B JBR Level B Flush
Water Regulating Valve Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83104
310305 13 D3M20008 B3IWFX5020 SH 2
E3E30411 SH 3
WF-XV-5020C JBR Level C Flush
Water Regulating Valve Open/Closed D3M20008
B3IWFX5020 SH 3 E3E30411 SH 3
WF-ZSO-5020C JBR Level C Flush
Water Regulating Valve Limit Switch Open
Open Limit Switch 120VAC CS-CC-83104
310306 14 D3M20008 B3IWFX5020 SH 3
E3E30411 SH 3
WF-ZSC-5020C JBR Level C Flush
Water Regulating Valve Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83104
310306 13 D3M20008 B3IWFX5020 SH 3
E3E30411 SH 3
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 61 of 88
3.4 Control Valves And Limit Switches
DCS I/O Drawing Tag Description Function
Signal Encl. Block Terminal P&ID DCS I/O
SK-FV-5030 JBR Flow
Regulating Valve D3M20009
B3ISKF5030 Sh 1 E3E30410 SH 5
SK-ZT-5030 JBR Flow
Regulating Valve Position
0 100 % 4-20 mA CS-CC-83102
310038 3 D3M20009 B3ISKF5030 Sh 2 E3E30410 SH 9
SK-FE-5030 JBR Level Make-Up Flow Element
D3M20009 B3ISKF5030 Sh 1 E3E30410 SH 5
SK-FIT-5030 JBR Level Make-
Up Flow 0 3000 gpm 4-20 mA
CS-CC-83101
310018 7 D3M20009 B3ISKF5030 Sh 1 E3E30410 SH 5
ME-XV-5441
Mist Eliminator Lower System
Header 1 Wash Isolation Valve
Fail Closed D3M20011 B3IMEX5441 SH 1
E3E30411 SH 2
ME-ZSO-5441
Mist Eliminator Lower System
Header 1 Wash Isolation Valve
Limit Switch Open
Open Limit Switch 120VAC CS-CC-83104
310304 2 D3M20011 B3IMEX5441 SH 1
E3E30411 SH 2
ME-ZSC-5441
Mist Eliminator Lower System
Header 1 Wash Isolation Valve
Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83104
310304 1 D3M20011 B3IMEX5441 SH 1
E3E30411 SH 2
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 62 of 88
3.4 Control Valves And Limit Switches
DCS I/O Drawing Tag Description Function
Signal Encl. Block Terminal P&ID DCS I/O
ME-XV-5442
Mist Eliminator Lower System
Header 2 Wash Isolation Valve
Fail Closed D3M20011 B3IMEX5442 SH 1
E3E30411 SH 3
ME-ZSO-5442
Mist Eliminator Lower System
Header 2 Wash Isolation Valve
Limit Switch Open
Open Limit Switch 120VAC CS-CC-83104
310305 2 D3M20011 B3IMEX5442 SH 1
E3E30411 SH 3
ME-ZSC-5442
Mist Eliminator Lower System
Header 2 Wash Isolation Valve
Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83104
310305 1 D3M20011 B3IMEX5442 SH 1
E3E30411 SH 3
ME-XV-5443
Mist Eliminator Lower System
Header 3 Wash Isolation Valve
Fail Closed D3M20011 B3IMEX5443 SH 1
E3E30411 SH 3
ME-ZSO-5443
Mist Eliminator Lower System
Header 3 Wash Isolation Valve
Limit Switch Open
Open Limit Switch 120VAC CS-CC-83104
310306 2 D3M20011 B3IMEX5443 SH 1
E3E30411 SH 3
ME-ZSC-5443
Mist Eliminator Lower System
Header 3 Wash Isolation Valve
Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83104
310306 1 D3M20011 B3IMEX5443 SH 1
E3E30411 SH 3
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 63 of 88
3.4 Control Valves And Limit Switches
DCS I/O Drawing Tag Description Function
Signal Encl. Block Terminal P&ID DCS I/O
ME-XV-5444
Mist Eliminator Lower System
Header 4 Wash Isolation Valve
Fail Closed D3M20011 B3IMEX5444 SH 1
E3E30411 SH 2
ME-ZSO-5444
Mist Eliminator Lower System
Header 4 Wash Isolation Valve
Limit Switch Open
Open Limit Switch 120VAC CS-CC-83104
310304 4 D3M20011 B3IMEX5444 SH 1
E3E30411 SH 2
ME-ZSC-5444
Mist Eliminator Lower System
Header 4 Wash Isolation Valve
Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83104
310304 3 D3M20011 B3IMEX5444 SH 1
E3E30411 SH 2
ME-XV-5445
Mist Eliminator Lower System
Header 5 Wash Isolation Valve
Fail Closed D3M20011 B3IMEX5445 SH 1
E3E30411 SH 3
ME-ZSO-5445
Mist Eliminator Lower System
Header 5 Wash Isolation Valve
Limit Switch Open
Open Limit Switch 120VAC CS-CC-83104
310305 4 D3M20011 B3IMEX5445 SH 1
E3E30411 SH 3
ME-ZSC-5445
Mist Eliminator Lower System
Header 5 Wash Isolation Valve
Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83104
310305 3 D3M20011 B3IMEX5445 SH 1
E3E30411 SH 3
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 64 of 88
3.4 Control Valves And Limit Switches
DCS I/O Drawing Tag Description Function
Signal Encl. Block Terminal P&ID DCS I/O
ME-XV-5446
Mist Eliminator Lower System
Header 6 Wash Isolation Valve
Fail Closed D3M20011 B3IMEX5446 SH 1
E3E30411 SH 3
ME-ZSO-5446
Mist Eliminator Lower System
Header 6 Wash Isolation Valve
Limit Switch Open
Open Limit Switch 120VAC CS-CC-83104
310306 4 D3M20011 B3IMEX5446 SH 1
E3E30411 SH 3
ME-ZSC-5446
Mist Eliminator Lower System
Header 6 Wash Isolation Valve
Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83104
310306 3 D3M20011 B3IMEX5446 SH 1
E3E30411 SH 3
ME-XV-5447
Mist Eliminator Lower System
Header 7 Wash Isolation Valve
Fail Closed D3M20011 B3IMEX5447 SH 1
E3E30411 SH 2
ME-ZSO-5447
Mist Eliminator Lower System
Header 7 Wash Isolation Valve
Limit Switch Open
Open Limit Switch 120VAC CS-CC-83104
310304 6 D3M20011 B3IMEX5447 SH 1
E3E30411 SH 2
ME-ZSC-5447
Mist Eliminator Lower System
Header 7 Wash Isolation Valve
Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83104
310304 5 D3M20011 B3IMEX5447 SH 1
E3E30411 SH 2
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 65 of 88
3.4 Control Valves And Limit Switches
DCS I/O Drawing Tag Description Function
Signal Encl. Block Terminal P&ID DCS I/O
ME-XV-5448
Mist Eliminator Lower System
Header 8 Wash Isolation Valve
Fail Closed D3M20011 B3IMEX5448 SH 1 E3E30411 SH 2/3
ME-ZSO-5448
Mist Eliminator Lower System
Header 8 Wash Isolation Valve
Limit Switch Open
Open Limit Switch 120VAC CS-CC-83104
310305 6 D3M20011 B3IMEX5448 SH 1
E3E30411 SH 3
ME-ZSC-5448
Mist Eliminator Lower System
Header 8 Wash Isolation Valve
Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83104
310305 5 D3M20011 B3IMEX5448 SH 1
E3E30411 SH 3
ME-XV-5449
Mist Eliminator Lower System
Header 9 Wash Isolation Valve
Fail Closed D3M20011 B3IMEX5449 SH 1
E3E30411 SH 3
ME-ZSO-5449
Mist Eliminator Lower System
Header 9 Wash Isolation Valve
Limit Switch Open
Open Limit Switch 120VAC CS-CC-83104
310306 6 D3M20011 B3IMEX5449 SH 1
E3E30411 SH 3
ME-ZSC-5449
Mist Eliminator Lower System
Header 9 Wash Isolation Valve
Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83104
310306 5 D3M20011 B3IMEX5449 SH 1
E3E30411 SH 3
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 66 of 88
3.4 Control Valves And Limit Switches
DCS I/O Drawing Tag Description Function
Signal Encl. Block Terminal P&ID DCS I/O
ME-XV-5451
Mist Eliminator Lower System
Header 10 Wash Isolation Valve
Fail Closed D3M20012 B3IMEX5451 SH 1
E3E30411 SH 2
ME-ZSO-5451
Mist Eliminator Upper System
Header 10 Wash Isolation Valve
Limit Switch Open
Open Limit Switch 120VAC CS-CC-83104
310304 8 D3M20012 B3IMEX5451 SH 1
E3E30411 SH 2
ME-ZSC-5451
Mist Eliminator Upper System
Header 10 Wash Isolation Valve
Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83104
310304 7 D3M20012 B3IMEX5451 SH 1
E3E30411 SH 2
ME-XV-5452
Mist Eliminator Lower System
Header 11 Wash Isolation Valve
Fail Closed D3M20012 B3IMEX5452 SH 1
E3E30411 SH 2
ME-ZSO-5452
Mist Eliminator Upper System
Header 11 Wash Isolation Valve
Limit Switch Open
Open Limit Switch 120VAC CS-CC-83104
310305 8 D3M20012 B3IMEX5452 SH 1
E3E30411 SH 3
ME-ZSC-5452
Mist Eliminator Upper System
Header 11 Wash Isolation Valve
Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83104
310305 7 D3M20012 B3IMEX5452 SH 1
E3E30411 SH 3
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 67 of 88
3.4 Control Valves And Limit Switches
DCS I/O Drawing Tag Description Function
Signal Encl. Block Terminal P&ID DCS I/O
ME-XV-5453
Mist Eliminator Lower System
Header 12 Wash Isolation Valve
Fail Closed D3M20012 B3IMEX5453 SH 1
E3E30411 SH 3
ME-ZSO-5453
Mist Eliminator Upper System
Header 12 Wash Isolation Valve
Limit Switch Open
Open Limit Switch 120VAC CS-CC-83104
310306 8 D3M20012 B3IMEX5453 SH 1
E3E30411 SH 3
ME-ZSC-5453
Mist Eliminator Upper System
Header 12 Wash Isolation Valve
Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83104
310306 7 D3M20012 B3IMEX5453 SH 1
E3E30411 SH 3
ME-XV-5454
Mist Eliminator Lower System
Header 13Wash Isolation Valve
Fail Closed D3M20012 B3IMEX5454 SH 1
E3E30411 SH 2
ME-ZSO-5454
Mist Eliminator Upper System
Header 13 Wash Isolation Valve
Limit Switch Open
Open Limit Switch 120VAC CS-CC-83104
310304 10 D3M20012 B3IMEX5454 SH 1
E3E30411 SH 2
ME-ZSC-5454
Mist Eliminator Upper System
Header 13 Wash Isolation Valve
Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83104
310304 9 D3M20012 B3IMEX5454 SH 1
E3E30411 SH 2
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 68 of 88
3.4 Control Valves And Limit Switches
DCS I/O Drawing Tag Description Function
Signal Encl. Block Terminal P&ID DCS I/O
ME-XV-5455
Mist Eliminator Lower System
Header 14 Wash Isolation Valve
Fail Closed D3M20012 B3IMEX5455 SH 1
E3E30411 SH 3
ME-ZSO-5455
Mist Eliminator Upper System
Header 14 Wash Isolation Valve
Limit Switch Open
Open Limit Switch 120VAC CS-CC-83104
310305 10 D3M20012 B3IMEX5455 SH 1
E3E30411 SH 3
ME-ZSC-5455
Mist Eliminator Upper System
Header 14 Wash Isolation Valve
Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83104
310305 9 D3M20012 B3IMEX5455 SH 1
E3E30411 SH 3
ME-XV-5456
Mist Eliminator Lower System
Header 15Wash Isolation Valve
Fail Closed D3M20012 B3IMEX5456 SH 1
E3E30411 SH 3
ME-ZSO-5456
Mist Eliminator Upper System
Header 15 Wash Isolation Valve
Limit Switch Open
Open Limit Switch 120VAC CS-CC-83104
310306 10 D3M20012 B3IMEX5456 SH 1
E3E30411 SH 3
ME-ZSC-5456
Mist Eliminator Upper System
Header 15 Wash Isolation Valve
Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83104
310306 9 D3M20012 B3IMEX5456 SH 1
E3E30411 SH 3
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 69 of 88
3.4 Control Valves And Limit Switches
DCS I/O Drawing Tag Description Function
Signal Encl. Block Terminal P&ID DCS I/O
ME-XV-5457
Mist Eliminator Lower System
Header 16 Wash Isolation Valve
Fail Closed D3M20012 B3IMEX5457 SH 1
E3E30411 SH 2
ME-ZSO-5457
Mist Eliminator Upper System
Header 16 Wash Isolation Valve
Limit Switch Open
Open Limit Switch 120VAC CS-CC-83104
310304 12 D3M20012 B3IMEX5457 SH 1
E3E30411 SH 2
ME-ZSC-5457
Mist Eliminator Upper System
Header 16 Wash Isolation Valve
Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83104
310304 11 D3M20012 B3IMEX5457 SH 1
E3E30411 SH 2
ME-XV-5458
Mist Eliminator Lower System
Header 17 Wash Isolation Valve
Fail Closed D3M20012 B3IMEX5458 SH 1
E3E30411 SH 3
ME-ZSO-5458
Mist Eliminator Upper System
Header 17 Wash Isolation Valve
Limit Switch Open
Open Limit Switch 120VAC CS-CC-83104
310305 12 D3M20012 B3IMEX5458 SH 1
E3E30411 SH 3
ME-ZSC-5458
Mist Eliminator Upper System
Header 17 Wash Isolation Valve
Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83104
310305 11 D3M20012 B3IMEX5458 SH 1
E3E30411 SH 3
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 70 of 88
3.4 Control Valves And Limit Switches
DCS I/O Drawing Tag Description Function
Signal Encl. Block Terminal P&ID DCS I/O
ME-XV-5459
Mist Eliminator Lower System
Header 18 Wash Isolation Valve
Fail Closed D3M20012 B3IMEX5459
E3E30411 SH 3
ME-ZSO-5459
Mist Eliminator Upper System
Header 18 Wash Isolation Valve
Limit Switch Open
Open Limit Switch 120VAC CS-CC-83104
310306 12 D3M20012 B3IMEX5459
E3E30411 SH 3
ME-ZSC-5459
Mist Eliminator Upper System
Header 18 Wash Isolation Valve
Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83104
310306 11 D3M20012 B3IMEX5459
E3E30411 SH 3
MU-XV-5421 Gas Riser Wash
Valve Fail Closed D3M20010
B3IMUX5421 SH 1 E3E30410 SH 7
MU-ZSC-5421 Gas Riser Wash
Valve Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83102
310025 13 D3M20010 B3IMUX5421 SH 1
E3E30410 SH 7
MU-ZSO-5421 Gas Riser Wash
Valve Limit Switch Open
Open Limit Switch 120VAC CS-CC-83102
310025 14 D3M20010 B3IMUX5421 SH 1
E3E30410 SH 7
ME-XV-5431 JBR Wall Wash
Valve Fail Closed D3M20010
B3IMUX5431 SH 1 E3E30410 SH 7
MU-ZSC-5431 JBR Wall Wash
Valve Limit Switch Close
Closed Limit Switch 120VAC CS-CC-83102
310026 5 D3M20010 B3IMUX5431 SH 1
E3E30410 SH 7
MU-ZSO-5431 JBR Wall Wash
Valve Limit Switch Open
Open Limit Switch 120VAC CS-CC-83102
310026 6 D3M20010 B3IMUX5431 SH 1
E3E30410 SH 7
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 71 of 88
3.5 DCS Control Valve Commands
DCS I/O Drawing Tag Description Function
Signal Encl. Card Slot P&ID DCS I/O
WF-XVO-5020A JBR Level A Flush Water Regulating
Valve
OPEN (Command)
120VAC CS-CC-83104
310301 7 D3M20008 B3IWFX5020 SH 1
E3E30411 SH 2
WF-XVO-5020B JBR Level B Flush Water Regulating
Valve
OPEN (Command)
120VAC CS-CC-83104
310302 7 D3M20008 B3IWFX5020 SH 2
E3E30411 SH 2
WF-XVO-5020C JBR Level C Flush Water Regulating
Valve
OPEN (Command)
120VAC CS-CC-83104
310303 7 D3M20008 B3IWFX5020 SH 3
E3E30411 SH 2
MU-XVO-5421 Gas Riser Wash
Valve OPEN
(Command) 120VAC
CS-CC-83102
310021 13 D3M20010 B3IMUX5421 SH 1
E3E30411 SH 6
ME-XVO-5431 JBR Wall Wash
Valve OPEN
(Command) 120VAC
CS-CC-83102
310022 13 D3M20010 B3IMUX5431 SH 1
E3E30411 SH 6
ME-XVO-5441
Mist Eliminator Lower System
Header 1 Wash Isolation Valve
OPEN (Command)
120VAC CS-CC-83104
310301 1 D3M20011 B3IMEX5441 SH 1
E3E30411 SH 2
ME-XVO-5442
Mist Eliminator Lower System
Header 2 Wash Isolation Valve
OPEN (Command)
120VAC CS-CC-83104
310302 1 D3M20011 B3IMEX5442 SH 1
E3E30411 SH 2
ME-XVO-5443
Mist Eliminator Lower System
Header 3 Wash Isolation Valve
OPEN (Command)
120VAC CS-CC-83104
310303 1 D3M20011 B3IMEX5443 SH 1
E3E30411 SH 2
ME-XVO-5444
Mist Eliminator Lower System
Header 4 Wash Isolation Valve
OPEN (Command)
120VAC CS-CC-83104
310301 2 D3M20011 B3IMEX5444 SH 1
E3E30411 SH 2
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 72 of 88
3.5 DCS Control Valve Commands
DCS I/O Drawing Tag Description Function
Signal Encl. Card Slot P&ID DCS I/O
ME-XVO-5445
Mist Eliminator Lower System
Header 5 Wash Isolation Valve
OPEN (Command)
120VAC CS-CC-83104
310302 2 D3M20011 B3IMEX5445 SH 1
E3E30411 SH 2
ME-XVO-5446
Mist Eliminator Lower System
Header 6 Wash Isolation Valve
OPEN (Command)
120VAC CS-CC-83104
310303 2 D3M20011 B3IMEX5446 SH 1
E3E30411 SH 2
ME-XVO-5447
Mist Eliminator Lower System
Header 7 Wash Isolation Valve
OPEN (Command)
120VAC CS-CC-83104
310301 3 D3M20011 B3IMEX5447 SH 1
E3E30411 SH 2
ME-XVO-5448
Mist Eliminator Lower System
Header 8 Wash Isolation Valve
OPEN (Command)
120VAC CS-CC-83104
310302 3 D3M20011 B3IMEX5448 SH 1
E3E30411 SH 2
ME-XVO-5449
Mist Eliminator Lower System
Header 9 Wash Isolation Valve
OPEN (Command)
120VAC CS-CC-83104
310303 3 D3M20011 B3IMEX5449 SH 1
E3E30411 SH 2
ME-XVO-5451
Mist Eliminator Lower System
Header 10 Wash Isolation Valve
OPEN (Command)
120VAC CS-CC-83104
310301 4 D3M20012 B3IMEX5451 SH 1
E3E30411 SH 2
ME-XVO-5452
Mist Eliminator Lower System
Header 11 Wash Isolation Valve
OPEN (Command)
120VAC CS-CC-83104
310302 4 D3M20012 B3IMEX5452 SH 1
E3E30411 SH 2
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 73 of 88
3.5 DCS Control Valve Commands
DCS I/O Drawing Tag Description Function
Signal Encl. Card Slot P&ID DCS I/O
ME-XVO-5453
Mist Eliminator Lower System
Header 12 Wash Isolation Valve
OPEN (Command)
120VAC CS-CC-83104
310303 4 D3M20012 B3IMEX5453 SH 1
E3E30411 SH 2
ME-XVO-5454
Mist Eliminator Lower System
Header 13Wash Isolation Valve
OPEN (Command)
120VAC CS-CC-83104
310301 5 D3M20012 B3IMEX5454 SH 1
E3E30411 SH 2
ME-XVO-5455
Mist Eliminator Lower System
Header 14 Wash Isolation Valve
OPEN (Command)
120VAC CS-CC-83104
310302 5 D3M20012 B3IMEX5455 SH 1
E3E30411 SH 2
ME-XVO-5456
Mist Eliminator Lower System
Header 15Wash Isolation Valve
OPEN (Command)
120VAC CS-CC-83104
310303 5 D3M20012 B3IMEX5456 SH 1
E3E30411 SH 2
ME-XVO-5457
Mist Eliminator Lower System
Header 16 Wash Isolation Valve
OPEN (Command)
120VAC CS-CC-83104
310301 6 D3M20012 B3IMEX5457 SH 1
E3E30411 SH 2
ME-XV-5458
Mist Eliminator Lower System
Header 17 Wash Isolation Valve
OPEN (Command)
120VAC CS-CC-83104
310302 6 D3M20012 B3IMEX5458 SH 1
E3E30411 SH 2
ME-XV-5459
Mist Eliminator Lower System
Header 18 Wash Isolation Valve
OPEN (Command)
120VAC CS-CC-83104
310303 6 D3M20012 B3IMEX5459
E3E30411 SH 2
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 74 of 88
3.6 Control Valve Power Supply
Power Panel Tag
Panel Breaker Encl. Block Terminal Loop Sheet
WF-XV-5020A EC-PBQA-7701 17 CS-CC-83104
310301 7 B3IWFX5020 SH 1
WF-XV-5020B EC-PBQA-7701 18 CS-CC-83104
310302 7 B3IWFX5020 SH 2
WF-XV-5020C EC-PBQA-7701 18 CS-CC-83104
310303 7 B3IWFX5020 SH 3
MU-XV-5421 EC-PBQA-7701 16 CS-CC-83102
310021 13 B3IMUX5421
MU-XV-5431 EC-PBQA-7701 16 CS-CC-83102
310022 13 B3IMUX5431
ME-XV-5441 EC-PBQA-7701 17 CS-CC-83104
310301 1 B3IMEX5441
ME-XV-5442 EC-PBQA-7701 17 CS-CC-83104
310302 1 B3IMEX5442
ME-XV-5443 EC-PBQA-7701 18 CS-CC-83104
310303 1 B3IMEX5443
ME-XV-5444 EC-PBQA-7701 17 CS-CC-83104
310301 2 B3IMEX5444
ME-XV-5445 EC-PBQA-7701 17 CS-CC-83104
310302 2 B3IMEX5445
ME-XV-5446 EC-PBQA-7701 18 CS-CC-83104
310303 2 B3IMEX5446
ME-XV-5447 EC-PBQA-7701 17 CS-CC-83104
310301 3 B3IMEX5447
ME-XV-5448 EC-PBQA-7701 17 CS-CC-83104
310302 3 B3IMEX5448
ME-XV-5449 EC-PBQA-7701 18 CS-CC-83104
310303 3 B3IMEX5449
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 75 of 88
3.6 Control Valve Power Supply
Power Panel Tag
Panel Breaker Encl. Block Terminal Loop Sheet
ME-XV-5451 EC-PBQA-7701 17 CS-CC-83104
310301 4 B3IMEX5451
ME-XV-5452 EC-PBQA-7701 17 CS-CC-83104
310302 4 B3IMEX5452
ME-XV-5453 EC-PBQA-7701 18 CS-CC-83104
310303 4 B3IMEX5453
ME-XV-5454 EC-PBQA-7701 17 CS-CC-83104
310301 5 B3IMEX5454
ME-XV-5455 EC-PBQA-7701 18 CS-CC-83104
310302 5 B3IMEX5455
ME-XV-5456 EC-PBQA-7701 18 CS-CC-83104
310303 5 B3IMEX5456
ME-XV-5457 EC-PBQA-7701 17 CS-CC-83104
310301 6 B3IMEX5457
ME-XV-5458 EC-PBQA-7701 18 CS-CC-83104
310302 6 B3IMEX5458
ME-XV-5459 EC-PBQA-7701 18 CS-CC-83104
310303 6 B3IMEX5459
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 76 of 88
3.7 Start Permissives
Mist Eliminators
True Not True Selected Not Selected
JBR WR Level High X AND
JBR Density Low X
JBR Shell and Gas Riser Wash
True Not True Selected Not Selected
JBR WR Level High X AND
JBR Density Low X
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 77 of 88
3.8 Setpoint and Alarm Limits
Tag Description Setpoint Low-Low Low High High-High
SK-AAHH-5011 JBR pH (diverter damper in online
position) 5.5 X
SK-AAHH-5011 JBR pH (diverter damper in bypass
position) 10.0 X
SK-AALL-5011 JBR pH (diverter damper in online
position) 4.5 pH X
SK-AALL-5011 JBR pH (diverter damper in bypass
position) 0.0 pH X
SK-LAH-5021 Narrow Range Level 18 Feet X
SK-LAHH-5021 Narrow Range Level X
SK-LAL-5021 Narrow Range Level 15 Feet X
SK-LALL-5021 Narrow Range Level X
SK-LAH-5022 Wide Range Level 19 Feet X
SK-LAHH-5022 Wide Range Level X
SK-LAL-5022 Wide Range Level 9.8 Feet X
SK-LALL-5022 Wide Range Level 8.8 Feet X
SK-PDAL-5711 JBR Differential
Pressure X
SK-PDAH-5711 JBR Differential
Pressure X
SK-PDAHH-5711 JBR Differential
Pressure X
ME-PDIT-5741 Mist Eliminator
Differential Pressure X
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 78 of 88
3.9 Alarm Response
TAG DESCRIPTION DCS
ACTION OPERATOR
ACTION
ME-PDAH-5741 Mist Eliminator
Differential Pressure High
Alarm Investagate cause of alarm
SK-AAHH-5011 JBR pH (diverter damper in online
position) High High Alarm
Lower vessel pH. Investagate cause of alarm
SK-AAHH-5011 JBR pH (diverter damper in bypass position) High High
Alarm Lower vessel pH.
Investagate cause of alarm
SK-AALL-5011 JBR pH (diverter damper in online
position) Low LOw Alarm
Increase vessel pH. Investagate cause of alarm
SK-AALL-5011 JBR pH (diverter damper in bypass position) Low Low
Alarm Increase vessel pH.
Investagate cause of alarm
SK-LAH-5021 Narrow Range Level
High Shutdown Washes and Interlocks
Limestone Slurry Feed pumps Investagate cause of alarm
SK-LAHH-5021 Narrow Range Level
High High Alarm Investagate cause of alarm
SK-LAL-5021 Narrow Range Level
Low Alarm Investagate cause of alarm
SK-LALL-5021 Narrow Range Level
Low Low Investagate cause of alarm Investagate cause of alarm
SK-LAH-5022 Wide Range Level
High Alarm Investagate cause of alarm
SK-LAHH-5022 Wide Range Level
High High Interlocks Gypsum Drawoff Pumps
Interlocks Gas Cooling Pumps Investagate cause of alarm
SK-LAL-5022 Wide Range Level
Low Alarm Investagate cause of alarm
SK-LALL-5022 Wide Range Level
Low Low
Interlocks JBR Mixers OFF Interlocks Gypsum Drawoff Pumps OFF
Interlocks Gas Cooling Pumps OFF Interlocks Gypsum Transfer Pumps OFF
Investagate cause of alarm
SK-PDAL-5711 JBR Differential
Pressure Investagate cause of alarm Investagate cause of alarm
SK-PDAH-5711 JBR Differential
Pressure Investagate cause of alarm Investagate cause of alarm
SK-PDAHH-5711 JBR Differential
Pressure Investagate cause of alarm Investagate cause of alarm
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 79 of 88
4 DCS Tag-Out Process Logic
The following subsections contain narrative interpretations of the DCS Tag-out process.
Click Tag-out on the DCS Screen and select applicable area for the task you will perform:
Red Hold Tag.
Blue Functional Tag.
White Information Tag.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 80 of 88
4 DCS Tag-Out Process Logic
To create a DCS Red Hold Tag follow the applicable directions listed below:
Enter clearance number in the clearance number box
Click ADD to add the number to the clearance list
Click YES to confirm.
Click EXIT to return to the Tag-out Menu.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 81 of 88
4 DCS Tag-Out Process Logic
To remove a DCS Red Hold Tag follow the applicable directions listed below:
Select Hold Tag number to remove.
Click REMOVE.
Click YES to confirm.
Click EXIT to return to the Tag-out Menu.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 82 of 88
4 DCS Tag-Out Process Logic
To create a Blue Functional Tag follow the applicable directions listed below:
Enter the clearance number in the clearance number box.
Click ADD.
Click YES to confirm.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 83 of 88
4 DCS Tag-Out Process Logic
Enter the name of the person requesting the controlled release for maintenance or testing.
Click ADD.
Click YES to confirm.
Click EXIT to return to the Tag-out Menu.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 84 of 88
4 DCS Tag-Out Process Logic
To remove a Blue Functional Tag follow the applicable directions listed below:
Select Blue Functional Tag number to remove.
Click REMOVE.
Click YES to confirm.
Click EXIT to return to the Tag-out Menu.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 85 of 88
4 DCS Tag-Out Process Logic
To create a White Information Tag follow the applicable directions listed below:
Enter any additional operating information.
Click ADD.
Click YES to confirm.
Click EXIT to return to the Tag-out Menu.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 86 of 88
4 DCS Tag-Out Process Logic
To remove a White Information Tag follow the applicable directions listed below:
Select the information to be removed.
Click REMOVE.
Click YES to confirm.
Click EXIT to return to the Tag-out Menu.
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 87 of 88
5 DCS Control Screens
The following subsections contain DCS control screens relative to the JBR Vessel System.
5.1 Scrubber Jet Bubbling Reactor Level – D3M20008 Screen
Southern Company Generation Bowen Unit 3 Scrubber
Technical Training JBR Vessel System
Advanced Controls Overview Student Guide
Confidential Information Page 88 of 88
5.2 Scrubber Jet Bubbling Reactor Wash – D3M20010, 11, 12 Screen
Procedure Revision Summary
Revision Document Change:
A
Initial draft of document.
B
Incorporated comments due to plant review.
C
Corrected terminal card numbers on instrumentation table.
D Updated to incorporate latest changes in JBR Level Flushing Logic 3/12/09
NOTE: See Revision Bars for specific changes within document.