Planet Dewy 60 BFR
-
Upload
raja-matharu -
Category
Documents
-
view
25 -
download
4
Transcript of Planet Dewy 60 BFR
Planet Dewy 60 BFTSubmittal NORTH AMERICA
We pursue a policy of continuing improvement in design and performance of our products. The right is therefore reserved to vary specifications without notice.
Project No.: Representative:
Name: Date:
Location:Specifier: Approved by:
Contractor: Date:
“PLANET DEWY 60 BFR” boilers are gasfired thermal appliances for central heating, designed and manufactured to satisfy the needs of multiple dwelling and modern boiler room requirements. They comply with ANSI Z21. 13 and CSA 4.9 GAS FIRED LOW PRESSURE STEAM AND HOT WATER BOILERS and ASME section IV of the Boiler and Pressure Vessel Code. In addition to the primary function of providing space heating, these wall hung boilers can remotely provide priority to domestic hot water heating loop. These appliances can be fired by both natural gas or Liquid Propane Gas and can be vented using separate pipe or forced draft.
Connections
M C.H. flow C 1” (25 mm) R C.H. return C 1” (25 mm) G Gas connection NPT 3/4” (19 mm) S3 Condensation outlet ø 1” (25 mm) C C.H. filling C 1/2” (13 mm) R3 Storage tank return C 1” (25 mm)
60 BFR
Dimensional details - Units mm(in)
4
ENG
FR
1.1 INTRODUCTION
“PLANET DEWY 60 BFR” boilers are gas-fired thermal appliances for central heating,designed and manufactured to satisfy theneeds of multiple dwelling and modern boi-
ler room requirements. They comply withANSI Z21. 13 and CSA 4.9 GAS FIRED LOWPRESSURE STEAM AND HOT WATER BOI-LERS. These appliances can be fired by bothnatural gas and Liquid Propane Gas. Thisbooklet provides the instructions for the
“PLANET DEWY 60 BFR” with eletronicignition, modulation, and direct sealed for-ced-draft. The instructions given in thismanual are provided to ensure properinstallation and perfect operation of theappliance.
1.2 DIMENSIONS: mm (in)
275 (10.8)55 (2)
120 (4.7)
60 (2.4)
120
(4.7
)
26
5 (1
0.5
)
170 (6.7)
75
(3)
23
0 (9
)
M
R CS3
G
409 (16)=
20
(0
,8)
87
0 (
34
)
455 (18)500 (20)
86
5 (
34
)
120 (4.7) 150 (6)
13
5 (
5.3
)
CSCA
R3=
Fig. 1
8
7
6
5
4
3
2
1
16
15
14
13
12
11
10
9
1.3 MAIN COMPONENTS
Fig. 2
KEY1 Gas valve2 Condensation drain siphon3 Fan4 Air pressure switch5 Ignition electrode6 Detection electrode7 Ignition transformer8 Exhaust thermostat9 Heating probe (SM)
10 Safety thermostat 100°C (212 °F)11 Differential pressure switch12 Single-acting valve13 Automatic air vent14 Pump15 Control panel16 Safety valve 4 BAR (60 psi)
Dimension Units Type 60 BFRR C.H. return MNPT 1” (25 mm)M C.H. supply MNPT 1” (25 mm)G Gas connection MNPT 3/4” (19 mm)C Filling system MNPT 1/2” (13 mm)R3 Tank return MNPT 1” (25 mm)S3 Condensation outlet ø 25 (1 in.)CA Inlet ø 80 (3.2 inch)CS Outlet ø 3” SCH. 40
1 DESCRIPTION OF THE BOILER
N.B.: The boiler is supplied with an aluminumadapter from diameter 80 mm to 3” SCHEDULE 40 (code 6249551). Install this adapter for direct vent installationsusing CPVC venting.Exhaust vent used is 3” or 4” PVC/
CPVC schedule 40 pipe.
Technical features
60 BFRMaximum input kW (Btu/h) 61.1 (210,000)Minimum input kW (Btu/h) 24.3 (83,000)Maximum output (60-80 °C–140-176 F) kW (Btu/h) 56.7 (192,300)Minimum output (60-80 °C–140-176 F) kW (Btu/h) 21.7 (74,400)A.F.U.E. (60 °C–140 F) % 95.2Water content l (USgal) 4.8 (1.27)Electric power consumption W 165Maximum C.H. pressure bar (psi) 3.1 (45.0)C.H. setting range °C (F) 20-80 (68-176)D.H.W. setting range °C (F) 30-60 (86-140)First-Hour rating using 180F boiler water 60 gallon indirect @ 90F rise l/h (USgph) 1,211 (320)First-Hour rating using 180F boiler water 80 gallon indirect @ 90F rise l/h (USgph) 1,276 (337)First-Hour rating using 180F boiler water 120 gallon indirect @ 90F rise l/h (USgph) 1,401 (370)Weight kg (lb) 61 (134.5)
Approved by the South Coast Air Quality Management District under rules 1146.2 and 222.Certified this product to the California Energy Commission in accordance with California law.Massachusetts Board of Plumbers and Gas Fitters Approval Code C1-0611-394.
Page 1/4
Page 2/4
Planet Dewy 60 BFR SubmittalFunctional diagram
Principal Components
SOLUZIONEPER ESTERO
SOLUZIONEPER ITALIA
87
65
4
2 1
15
14
17
13
1216
11
109
21 22
2019
18
329
87
65
4
2
1
14
17
911
10
12
16
13
15
21
19 20
22
2425
26
27
28
18
329
M
M2
GC R3
S3
M
M2
G
S3
C R3
R 23
R 23
30
KEY 1 Gasvalve 2 Condensationdrainsiphon 3 Boilerpump(notsupplied) 4 Fan 5 Heatingprobe(SM) 6 Safetythermostat95°C 7 Exhaustthermostat 8 Primaryexchanger 9 Diaphragm10 Differentialpressureswitch11 Waterpressuretransducer12 Airreliefvalve13 Circulationpump14 Drainplug15 Gascock(notsupplied)16 Nonreturnvalve17 4-BARsafetyvalve(60psi)18 Nonreturnvalve(notsupplied)19 Hydrauliccompensator(supplied in the kit code 8101528 )20 Draintap(notsupplied)21 Expansionvessel8liter(supplied in the kit code 8101528)22 Airreliefvalve(notsupplied)23 Obliquefilter(notsupplied)29 Tank
CONNECTIONSM C.H.flowR C.H.returnG GasS3 CondensationdrainC SystemfillingM2TankflowR3 Tankreturn
KEY 1 Gasvalve 2 Condensationdrainsiphon 3 Fan 4 Airpressureswitch 5 Ignitionelectrode 6 Detectionelectrode 7 Ignitiontransformer 8 Exhaustthermostat 9 Heatingprobe(SM)10 Safetythermostat100°C(212°F)11 Differentialpressureswitch12 Single-actingvalve13 Automaticairvent14 Pump15 Controlpanel16 Safetyvalve4BAR(60psi)
8
7
6
5
4
3
2
1
16
15
14
13
12
1110
9
Page 3/4
Planet Dewy 60 BFR Submittal
600
1000 4500400035003000250020001500
PORTATA (l/h)
PERDITE DI CARICO TRA
GLI ATTACCHI R3 e M2 (mbar)
500
400
100
200
300
Planet Dewy 60-100 BFR
700
800
5000 5500
60 BFR 100 BFR
FLOWRATE(l/h)
LOA
DL
OS
SES
(mba
r)
200
250
300
2
PORTATA (m3/h)
4 6 8 10 120
50
100
150
Dp (mbar)
14
60 BFR - HE 50 R
15
100 BFR - HE 110 R
LATO CALDAIALATO IMPIANTO
60 BFR - HE 50 R
100 BFR - HE 110 R
CAPACITY(m3/h)
HYDRAULIC COMPENSATOR LOAD LOSSES
CURVE LOAD LOSSES/CAPACITY BETWEEN CONNECTORS R3 and M2
017.635.2 52.8USgal/min
10
6.7
3.35
0
200
250
300
2
PORTATA (m3/h)
4 6 8 10 120
50
100
150
Dp (mbar)
14
60 BFR - HE 50 R
15
100 BFR - HE 110 R
LATO CALDAIALATO IMPIANTO
60 BFR - HE 50 R
100 BFR - HE 110 R
SIDEBOILER
SIDESYSTEM
“FOOT”
0
600
500 4000350030002500200015001000
PORTATA (l/h)
PREVALENZA RESIDUA (mbar)
500
400
100
200
300
Planet Dewy 60-100 BFR
4500
700
800
60 BFR
100 BFR
FLOWRATE(l/h)
04.4 8.813.21 17.66USgal/min
26.8
20.1
13.4
6.7
0
“FOOT”
RES
IDU
AL
HEA
D(m
bar)
SYSTEM AVAILABLE HEAD
26.8
20.1
13.4
6.7
0
“FOOT”
04.4 8.813.217.622.0USgal/min
Page 4/4
TYPICAL PIPINg “PLANET DEWY 60 BFR”
03
/2
01
2
Planet Dewy 60 BFR SubmittalWiring diagram
KEY
EV1 Gasvalvecoil
EV2 Gasvalvecoil
EA Ignitionelectrode
ER Detectionelectrode
TS Safetythermostat
V Fan
TPA Waterpressuretransducer
PI Systempump
SE Externalprobe(optional)
TA Roomthermostat
SM Heatingprobe
TR 120-24Vtransformer
PD Differentialpressureswitch
CR RemoteControlLogic(optional)
SV Fanboard
TF Exhaustthermostat
PA Airpressureswitch
SB Boilerprobe
PB Boilerpump
TRA Ignitiontransformer
NOTE: Connect the room thermostat
(TA) to terminals 5-6 after removing
the bridge. Fan control board (SV)
“MAX” and “MIN” trimmers are sealed
and must never be tampered with.
PLANET DEWY 60
BFR
INDIRECTHOT WATER
HEATER
COLDWATER
SUPPLY
HOTWATERSUPPLY
↙↙P