PID Control Manual 6540
-
Upload
lizandro-zapata -
Category
Documents
-
view
230 -
download
0
Transcript of PID Control Manual 6540
-
7/27/2019 PID Control Manual 6540
1/26
PID CONTROL MANUAL
-
7/27/2019 PID Control Manual 6540
2/26
-
7/27/2019 PID Control Manual 6540
3/26
PID Control
Manual
Document Number: 58695-000
Date: March, 2008
-
7/27/2019 PID Control Manual 6540
4/26
Introduction
Congratulations on your purchase of the Toshiba 9-Series ASD. The 9-series ASD has been designed to
provide excellent speed and torque control in an open-loop feedback configuration.
The 9-series ASD performance can be further enhanced by using either process-based or speed-based PIDcontrol. PID is a closed-loop technique that minimizes error by reacting to three feedback values:
One value that is proportional to the error.
One value that is proportional to the cumulative error.
One value that is proportional to the rate of change of the error.
Important NoticeThe instructions contained in this manual are not intended to cover all details or variations in equipment
types. Nor may it provide for every possible contingency concerning the installation, operation, or
maintenance of this equipment. Should additional information be required contact your Toshibarepresentative.
The contents of this manual shall not become a part of or modify any prior or existing agreement,
commitment, or relationship. The sales contract contains the entire obligation of Toshiba International
Corporation. The warranty contained in the contract between the parties is the sole warranty of Toshiba
International Corporation and any statements contained herein do not create new warranties or modify the
existing warranty.
Any electrical or mechanical modifications to this equipment without prior written consent of
Toshiba International Corporation will void all warranties and may void other safety certifications.
Unauthorized modifications may also result in a safety hazard or equipment damage.
Misuse of this equipment could result in injury and equipment damage. In no event will Toshiba
Corporation be responsible or liable for direct, indirect, special, or consequential damage or injury
that may result from the misuse of this equipment.
-
7/27/2019 PID Control Manual 6540
5/26
Contacting Toshibas CustomerSupport Center
Toshibas Customer Support Center can be contacted to obtain help in resolving any Adjustable Speed
Drive system problem that you may experience or to provide application information.
The center is open from 8 a.m. to 5 p.m. (CST), Monday through Friday. The Support Centers toll free
number is US (800) 231-1412/Fax (713) 937-9349 Canada (800) 527-1204.
You may also contact Toshiba by writing to:
Toshiba International Corporation
13131 West Little York Road
Houston, Texas 77041-9990
Attn: ASD Product Manager.
For further information on Toshibas products and services, please visit our website at www.toshiba.com/
ind/.
http://www.toshiba.com/ind/http://www.toshiba.com/ind/http://www.toshiba.com/ind/http://www.toshiba.com/ind/ -
7/27/2019 PID Control Manual 6540
6/26
About This Manual
This manual was written by the Toshiba Technical Publications Group. This group is tasked with
providing technical documentation for the 9-Series family of ASDs.Every effort has been made to
provide accurate and concise information to you, our customer.
At Toshiba were continuously searching for better ways to meet the constantly changing needs of our
customers. E-mail your comments, questions, or concerns about this publication to
Manuals Purpose and Scope
This manual details the PID feedback control related parameters, functions, and their default values.
Both process and speed PID feedback control can be customized by adjusting these ASD parameter
settings.
This manual is to be used in conjunction with the operations manual specified for your 9-Series ASD.
To maximize the functionality of the ASD while operating in the PID control mode a working
familiarity with this manual will be required. This manual has been prepared for the ASD installer, user,
and maintenancepersonnel. This manual may also be used as a reference manual or for training. With
this in mind, use this manual to develop a system familiarity before attempting to operate the ASD using
the PID Control Function parameters
Because of our commitment to continuous improvement, Toshiba International Corporation reserves the
right, without prior notice, to update information, make product changes, or to discontinue any product
or service identified in this publication.
Toshiba International Corporation (TIC) shall not be liable for direct, indirect, special, or
consequential damages resulting from the use of the information contained within this manual.
TOSHIBA is a registered trademark of Toshiba Corporation. All other product or trade referencesappearing in this manual are registered trademarks of their respective owners.
This manual is copyrighted. No part of this manual may be photocopied or reproduced in any form
without the prior written consent of Toshiba International Corporation.
Copyright 2008 Toshiba International Corporation.
All rights reserved.
Printed in the U.S.A.
mailto:[email protected]:[email protected] -
7/27/2019 PID Control Manual 6540
7/26
Table of Contents
PID Control Manual i
System Control Using PID........... .............. ............... ............... .............. ............... ............ 1
Process/Speed PID Control..... ............... .............. ............... .............. ............... ............... .. 2
Select the PID Mode .................................................................................................... 2
Specify the Process Reference Value........................................................................... 2
Specify the Feedback Response ...................................................................................4
Set the Limit Parameters ..............................................................................................6
Set the PID Gain Parameters........................................................................................6
Simple Position PID Control ............................................................................................6
Additional PID Related Commands ................................................................................7
Switch to Open Loop Operation...................................................................................7
Reset the Integral and Differential Gain for PID Control ............................................ 7Display the Process and Feedback Values ................................................................... 7
Scaling the Analog Input Signal................................................................................... 8
PID Control Parameter Summary............... .............. ............... ............ ............... .......... 10
Parameter Descriptions .............................................................................................. 12
-
7/27/2019 PID Control Manual 6540
8/26
ii PID Control Manual
-
7/27/2019 PID Control Manual 6540
9/26
PID Control Manual 1
System Control Using PIDPID is an operating mode that maintains a constant system output by comparing the monitored system
output (feedback) to a setpoint and compensating for the difference between the two. System
adjustments are increased or decreased as a function of the received feedback. This self-correcting
action eliminates the requirement for constant operator intervention.
The automatic adjustment may be either process-variable-, speed-, or position dependent.
The PID Control Switch parameter enables the PID function by allowing the user to select the PID
operating mode. Selecting PID Off disables the PID function.
1. PID Off Disables the PID feedback.
2. Process PID Monitors the control variable (e.g., temperature, pressure, etc.) as the measurement
that is to be compared to the setpoint in determining the ASD output adjustment. See Figure 1.
3. Speed PID Monitors the ASD output speed (e.g., Motor RPM, encoder, etc.) as the measurement
that is to be compared to the speed setpoint in determining the ASD output adjustment.
See Figure 2.
4. Simple Position PID Monitors the load position (e.g., crane, sprayer, etc.) as the measurementthat is to be compared to the setpoint in determining the ASD output adjustment. See Figure 3.
Figures 1 3 show the relationship of the parameters required for Process PID, Speed PID, and Easy
Position PID.
Figure 1. Diagram for F359 = Process PID.
Figure 2. Diagram for F359 = Speed PID.
ProcessReferenceValue
Process Upper LimitF367
PID ControlJump Frequency
ProcessingIncrease/
Decrease Rate
Acceleration Time 1 - F009Deceleration Time 1 - F010
F368Process Lower Limit
PID DeviationUpper Limit
F364
F365PID DeviationLower Limit
PID OutputUpper Limit
F370
F371PID OutputLower Limit
Upper LimitFrequency
F012
F013Lower Limit
Frequency
Feedback Signal
Process Upper LimitF367
PID Control Jump FrequencyProcessing
ProcessIncrease/
Decrease Rate
ProcessIncrease Rate - F372Decrease Rate - F373
F368Process Lower Limit
PID DeviationUpper Limit
F364
F365PID Deviation
Lower Limit
PID OutputUpper Limit
F370
F371PID Output
Lower Limit
Upper LimitFrequency
F012
F013Lower Limit
Frequency
Feedback Signal
DelayFilterF361
SpeedReferenceValue
-
7/27/2019 PID Control Manual 6540
10/26
2 PID Control Manual
Figure 3. Diagram for F359 = Position PID.
Process/Speed PID Control
Select the PID ModeSelect the PID mode at parameter F359 and the PID feedback source at parameter F360.
Position PID is addressed specifically in Simple Position PID Control on pg. 6.
Specify the Process Reference ValueSelect the feedback input at F004 and F207. Adjust the process reference value (set point) to deliver the
desired process variable output. The commanded frequency and actual output frequency may not
always be the same because it is only the value of the process variable that is the basis of the feedback
response.
Example: Set the Process Reference Value With an External Signal.
An example of a process reference value set with an external signal is shown on the next page. Figure 4.
The desired process output is 15 psi.
A process reference value of 5 V will produce a process output of 15 psi. This process reference value
of 5 V corresponds to a frequency command of 40 Hz.
The process feedback is input at the V/I terminals. The ASD parameters F201 F204 are set so a
feedback value of 12 mA from the pressure transducer corresponds to a frequency command of 40 Hz.
Input the frequency set points and associated process values. Set the maximum frequency to 80 Hz.
Parameter settings:
F004 = RR Input F360 = V/I Input F011 = 80.0 Hz F012 = 80.0 Hz
F201 = 20% F202 = 0 Hz F203 = 100% F204 = 80 HzF210 = 0% F211 = 0 V F212 = 100% F213 = 10 V
PID Control
Position CompletionRangeF381
F381
PositionCompletion Range
Feedback Signal
PositionReferenceValue
-
7/27/2019 PID Control Manual 6540
11/26
PID Control Manual 3
Figure 4. Process reference set with external signal.
Note: On the 9-Series ASD, set SW301 to either Current or Voltage as the feedback signal
type. SW301 is located on the Terminal Board of the 9-Series ASD. See the ASD
Operation Manual.
Figure 5. Feedback and Process reference signal frequency conversion.
Note: To simplify this example the Upper Limit Frequency (F012) was set to the Maximum
Frequency (F011). For real applications it is good practice to set the Upper Limit
Frequency lower than the Maximum Frequency.
Feedback Value (4 20 mA) Process Value (0 10 V)Operation Frequency Command
Value (0 80 Hz)
4 0 0
8 2.5 20
12 5.0 40
16 7.5 60
20 10 80
Sensor Range:
IICC
V/I
CC
RR
U
V
W
R
ST
M
sensorPressure
Pump
P
3-Phase Input
Process feedback
DC: 4 20 mA
Process reference value
DC: 5 V (0 10 V)
Desired process
value: 15 psi
10 - 20 psi
20 psi
10 psi
15 psi
10 psi
20 psi
Process feedbackProcess feedback Process reference value Process reference value
(converted into frequency) (converted into frequency)
80 Hz 80 Hz
40 Hz
0 Hz0 Hz
4 mA 20 mA 4 mA 20 mA 0 V 10 V 0 V 10 V5 V
-
7/27/2019 PID Control Manual 6540
12/26
4 PID Control Manual
Specify the Feedback ResponseFor V/I frequency control establish the response slope of the ASD by entering two parameter pairs.
Each parameter pair consists of an input point setting (F202 and F204) and a corresponding frequency
(F201 and F203) at that setting.
If using either RR or RX for frequency control, set their respective response slope parameters, F210
F213 or F216 F219, as above.
For a 4 - 20 mA current loop feedback signal, 4 mA is 20% of 20 mA. Set parameter F201 to 20% at
4 mA and F202 to 0 Hz, F203 to 100% at 20 mA and F204 to 80 Hz.
Figure 6. V/I input points for 4-20 mA feedback signal.
Reverse the Feedback Response
A negative response slope can be established by either of two methods:
Switch the values of the V/I Input Point Frequencies F202 and F204.
Switch the ASD response from normal to inverted.
Example: Reverse the Response Slope Using V/I Input Point Settings.
A system using a 4 20 mA feedback signal requires an inverted feedback response slope. Parameters
F201 F204 would have their values set as shown below.
Figure 7. Inverting the feedback response slope.
F202
F203F201
4 mA 20 mA0 Hz
80 Hz
20% 100%
F204
80 HzF202
0 Hz4 mA
F20120%
20 mA
F203100%
F204
-
7/27/2019 PID Control Manual 6540
13/26
PID Control Manual 5
Example: Invert the Response Slope Using an External Switch.
Use the S3 terminal as a PID normal/inverse slope characteristic switching signal input terminal.
This figure illustrates the PID feedback value (maximum frequency: 80 Hz) to the V/I terminal using
the S3 terminal to switch between the positive and negative response slope. When the switch to S3 is
open, the feedback slope is normal, and when the switch to S3 is closed, the slope is inverted.
Figure 8. Feedback response slope polarity switching with S3.
Figure 9. External switch on S3.
Table 1. Parameter settings for slope polarity switching output.
Parameter
NumberParameter Name
Selectable Functions
RangeSetting
F117 Input Terminal 7 (S3) 0 131 54 - PID Positive/Negative Slope Switching
Parameter
NumberParameter Name Setting
F117 Input Terminal Function - S3 54
F201 V/I Input Point 1 Setting 20
F202 V/I Input Point 1 Frequency 0
F203 V/I Input Point 2 Setting 100
F204 V/I Input Point 2 Frequency 80
100%20%
4 mA 20 mA
80 Hz
0 Hz
Open between S3 and CC
Closed between S3 and CC
(Set SW 301 to Current)
DC: 0 10 VExternal analog set point
Feedback signalDC: 4 20 mA
IICC
V/I
CC
S3
External discrete input to S3
V/I Feedback
-
7/27/2019 PID Control Manual 6540
14/26
6 PID Control Manual
Set the Limit ParametersSet the high-low limit parameters. Some parameters are mode specific, as indicated in the following
table.
Table 1. Limit parameters applicability.
Set the PID Gain ParametersSet and adjust the F362 Proportional (P), F363 Integral (I), and F366 Differential (D) gain
parameters as necessary to optimize the system response. See page 14.
Simple Position PID ControlSimple Position PID control is used to keep a stopped load motionless. Simple Position PID control
would be used to keep a stopped elevator from shifting position as the elevator load changed.
Simple Position PID control mode requires the ASD be in PG Vector Feedback mode (F015 = 7 or 8)and parameters F240, F241, and F243 set to 0.0 Hz.
Simple Position PID control is performed when a position control signal is received. The discrete input
terminal assignment for Simple Position PID control is 72. The motor position at the time the command
is received is recorded and used as the position reference point.
The parameters required for Simple Position PID Control setup are listed in the following table.
Table 2. Required Simple Position PID Control parameters.
Limit Parameters Process PID Speed PID
F364, F365 PID Deviation Upper and Lower Limit YES YES
F368, F367 Process Upper and Lower Limit YES YES
F370, F371 PID Output Upper and Lower Limit YES YES
F012, F013 Upper and Lower Limit Frequency YES YES
F011 Maximum Frequency YES YES
F009, F010 Acceleration and Deceleration Time YES NO
F372, F373 Process Increasing and Decreasing Rate NO YES
F361 Delay Filter NO YES
Parameters Function Setting
F015 V/f Control Mode Selection
7: PG Vector Feedback Control
or
8: PG Vector Feedback Control
F240 Start Frequency 0.00
F241 Operating Frequency 0.00
F243 End Frequency 0.00
F359 PID Control Switching 3: Position PID Control
F360 PID Control Feedback Selection 6: PG Feedback Option
F362 Proportional Gain 0.01 100.00
F363 Integral Gain 0.01 100.00
-
7/27/2019 PID Control Manual 6540
15/26
PID Control Manual 7
Additional PID Related Commands
Switch to Open Loop Operation
Switching between PID control and open loop operation can be done with a discrete input. Use the PID
Control OFF selection, Input Terminal functions 36 or 37, to switch from PID operation (automatic
operation) to open loop operation (manual operation).
When switching between PID and open loop operation set the manual setpoint equal to the PID setpoint
during the transition in control modes.
Reset the Integral and Differential Gain forPID Control
The PID Differentiation/Integration Clear function is used to reset the PID control integral gain and
differential gain to the factory default values. Use discrete input terminal function 52.
Display the Process and Feedback Values
Parameters Display Unit Multiplication Factor (F702) and Display Unit Selection (F703) can be used to
modify the ASD display to give a direct reading of the process output.
If F703 is set to 1, the displayed value becomes
[Frequency displayed] [number specified at F702] = [Value displayed]
Example: Display motor speed for a four-pole motor.
Change the display mode from the default display setting of 60 Hz to display 1800 (rpm) for a 4-polemotor.
Set F703 to 1 PID Process Data.
Set F702 = 30.
60 x 30 = 1800
The ASD now displays the calculated motor speed of 1800 instead of the real-time output frequency of
60.
F375 Number of PG Input Pulses 12 9999
F376 Number of PG Input Poles 2
F381 Simple Positioning Completion Range 100
F111-F118 (any one) Simple Positioning 72
Parameters Function Setting
-
7/27/2019 PID Control Manual 6540
16/26
8 PID Control Manual
Scaling the Analog Input SignalAny two set points may be used to establish a response slope for the ASD. It is not necessary that the
two set points be at 0% and 100% of the feedback signal range.
Weak feedback signals can compensated for by adjusting the set points. For instance, if the feedback
signal for the voltage input terminal below were only 3 7 V, the same slope would be created by
entering the parameter pair settings F201-F202 and F203-F204 shown in Figure 10.
Figure 10. Example of voltage scaling to compensate for feedback amplitude.
F204
F202
F203F201
7 V3 V
56 Hz
24 Hz
70%30%
0 V
0%
10 V
100%
0 Hz
80 Hz
-
7/27/2019 PID Control Manual 6540
17/26
PID Control Manual 9
Figure 11. Examples of feedback slopes.
F204
F202
Example: V/I used as a Voltage Input Terminal
F203F201
10 V0 V
80 Hz
0 Hz
100%0%
F213
F211
Example: RR Terminal Settings
F212F210
10 V0 V
80 Hz
0 Hz
100%0%
F204
F202
Example: V/I used as a Current Input Terminal
F203F201
20 mA4 mA
80 Hz
0 Hz
100%20%
F219
F217
Example: RX Terminal Settings
F218F216
10 V-10 V
80 Hz
0 Hz
100%-100%
-
7/27/2019 PID Control Manual 6540
18/26
10 PID Control Manual
PID Control Parameter SummaryThe PID-related ASD parameters are summarized in the table below.
Table 3. PID control parameters.
ParameterNumber
Parameter Name Adjustment Range Default Setting
F004 Frequency Mode 1
1: V/I
2: RR
3: RX
4: Not Used
5: EOI Keypad
6: RS485
7: Communications Option Board
8: RX2 (AI1)
9: Option V/I
10: UP/DOWN Frequency (terminal board)
11: Pulse Input (option)
12: Pulse Input (motor CPU)13: Binary/BCD Input (option)
2: RR
F009 Acceleration Time 1 0.1 6000 sec.Typeform
Specific
F010 Deceleration Time 1 0.1 6000 sec.Typeform
Specific
F011 Maximum Frequency 30.0 299.0 Hz 80.0
F012 Upper Limit Frequency 0.0 F011 Hz 60.0
F013 Lower Limit Frequency 0.00 F012 Hz 0.00
F015 V/f Pattern
0: Constant Torque
1: Voltage Decrease slope
2: Automatic Torque Boost
3: Sensorless Vector Control (Speed)
4: Sensorless Vector Control (Speed/Torque)
5: V/I 5-Point slope
6: PM Drive
7: PG Vector Feedback Control (Speed)
8: PG Vector Feedback Control (Speed/
Torque)
8: PG Vector
Feedback Control
F201 V/I Input Point 1 Setting 0 100% 0
F202 V/I Input Point 1 Frequency 0.00 F011 Hz 0.00
F203 V/I Input Point 2 Setting 0 100% 100
F204 V/I Input Point 2 Frequency 0.00 F011 Hz 60.00
F207 Frequency Mode 2 Same as F004 1
F210 RR Input Point 1 Setting 0 100% 0
F211 RR Input Point 1 Frequency 0.00 F011 Hz 0.00
F212 RR Input Point 2 Setting 0 100% 100
F213 RR Input Point 2 Frequency 0.00 F011 Hz 60.00
F216 RX Input Point 1 Setting 100% 0
F217 RX Input Point 1 Frequency 0.00 F011 Hz 0.00
F218 RX Input Point 2 Setting 100% 100
F219 RX Input Point 2 Frequency 0.00 F011 Hz 60.00
-
7/27/2019 PID Control Manual 6540
19/26
PID Control Manual 11
F240 Starting Frequency 0.00 F011 Hz 0.10
F241 Run Frequency 0.00 F011 Hz 0.00
F242 Run Frequency Hysteresis 0.00 30.00 Hz 0.00
F243 End Frequency 0.00 30.00 Hz 0.00F270 Jump Frequency 1 0.00 F011 Hz 0.00
F271 Jump Frequency 1 Bandwidth 0.00 30.00 Hz 0.00
F272 Jump Frequency 2 0.00 F011 Hz 0.00
F273 Jump Frequency 2 Bandwidth 0.00 30.00 Hz 0.00
F274 Jump Frequency 3 0.00 F011 Hz 0.00
F275 Jump Frequency 3 Bandwidth 0.00 30.00 Hz 0.00
F359 PID Control Switching
0: PID Off
1: Process PID Control (Uses parameter limits
F367, F368)
2: Speed PID Control (Uses parameter limits
F370, F371)
3: Position PID Control
0: PID Off
F360 PID Feedback Signal
0: PID Control Disabled
1: V/I
2: RR
3: RX
4: RX2 (AI1)
5: Option V/I
6: PG Feedback Option
0
F361 PID Feedback Delay Filter 0.0 25.0 0.1
F362 PID Feedback Proportional (P) Gain 0.01 100.00 0.10
F363 PID Feedback Integral (I) Gain 0.01 100.00 0.10
F364 PID Deviation Upper Limit F013 F012 Hz 60.00
F365 PID Deviation Lower Limit F013 F012 Hz 60.00F366 PID Feedback Differential (D) Gain 0.00 2.55 0.00
F367 Process Upper Limit F013 F012 Hz 60.00
F368 Process Lower Limit F013 F012 Hz 0.00
F369 PID Control Waiting Time 0 2400 sec. 0
F370 PID Output Upper Limit F013 F012 Hz 60.00
F371 PID Output Lower Limit F013 F012 Hz 4.00
F372Process Increasing Rate (Speed PID
Control)0.1 600.0 sec. 10.0
F373Process Decreasing Rate (Speed PID
Control)0.1 600.0 sec. 10.0
F375 Number of PG Input Pulses 12 9999 ASD-dependent
F376 Number of PG Input Phases1: Single Phase
2: Two PhaseASD-dependent
F381 Positioning Completion Range 1 4000 100
F466 Speed PID Switching Frequency 0.00 F011 Hz 0.00
Parameter
NumberParameter Name Adjustment Range Default Setting
-
7/27/2019 PID Control Manual 6540
20/26
12 PID Control Manual
Parameter Descriptions
F004 Frequency Mode 1 specifies the input source for the frequency command.
F009 Acceleration Time sets the time in seconds for the output of the ASD to go from 0 Hz to
Maximum Frequency.
Note: Acceleration times shorter than the load will allow may cause nuisance tripping and
mechanical stress to the loads.
F010 Deceleration Time sets the time in seconds for the output of the ASD to go from Maximum
Frequency to 0 Hz.
F011 Maximum Frequency sets the absolute maximum frequency that the ASD will output.
Acceleration/deceleration times are calculated based on this value.
F012 Upper Limit Frequency sets the highest frequency that the ASD will accept as a frequency
command. The ASD may output frequencies higher than Upper Limit Frequency (but no higher thanMaximum Frequency) when operating in PID Control, Torque Control, or Vector Control mode.
F013 Lower Limit Frequency sets the lowest frequency that the ASD will accept as a frequency
command. Under certain conditions the ASD may output frequencies lower than the Lower Limit
Frequency.
Accelerating from a stop.
Decelerating to a stop.
System is in PID Control, Torque Control, or Vector Control modes.
F660 Adding Input Selection Override
0: Disabled
1: V/I
2: RR
3: RX
4: Not Used5: EOI Keypad
6: RS485
7: Communications Option Board
8: RX2 (AI1)
9: Option V/I
10: UP/DOWN Frequency (terminal board)
11: Pulse Input (option)
12: Pulse Input (motor CPU)
13: Binary/BCD Input (option)
0: Disabled
F661 Multiplying Input Selection
0: Disabled
1: V/I
2: RR
3: RX
4: F729 Setting
5: RX2 (AI1)
0: Disabled
F702 Display Unit Multiplication Factor 0.00 (Off) 200.00 0.00
F703 Display Unit Selection0: All Frequencies
1: PID Process Data0: All Frequencies
F729 Panel Override Multiplication Gain 100.00% 0.00
Parameter
NumberParameter Name Adjustment Range Default Setting
-
7/27/2019 PID Control Manual 6540
21/26
PID Control Manual 13
F015 V/f Pattern establishes the relationship between the output frequency and the output voltage.
When using the Easy Position PID function set this parameter to 8 - PG Vector Feedback Control
(Speed/Torque).
F201, F203 V/I Input Point 1, 2 Setting set the two points that establish the V/I response slope. These
two settings are entered as a percentage of F011. See Specify the Feedback Response on pg. 4. The use
of F201 F204 is also explained in detail in the ASD Operation Manual.
F202, F204 V/I Input Point 1, 2 Frequency set the corresponding frequencies to the V/I Input Point
1 and 2 settings. See Specify the Feedback Response on pg. 4.
F210, F212 RR Input Point 1, 2 Setting set the two points that establish the RR response slope. These
two settings are entered as a percentage of F011. See Specify the Feedback Response on pg. 4. The use
of F210 F213 is also explained in detail in the ASD Operation Manual.
F211, F213 RR Input Point 1, 2 Frequency set the corresponding frequencies for the RR Input Point
1 and 2 settings. See Specify the Feedback Response on pg. 4.
F216, F218 RX Input Point 1, 2 Setting set the two points that establish the RX response slope. These
two settings are entered as a percentage of F011. See Specify the Feedback Response on pg. 4. The use
of F216 F219 is also explained in detail in the ASD Operation Manual.
F217, F219 RX Input Point 1, 2 Frequency set the corresponding frequencies for the RX Input Point
1 and 2 settings. See Specify the Feedback Response on pg. 4.
F240 Start Frequency sets the minimum motor speed during startup at which the ASD will begin to
output the commanded frequency even if the command frequency is less than the Start Frequency.
During the startup period from stopped until the Start Frequency is reached, the ASD does not output a
command frequency.
F241 Run Frequency sets the center run frequency for the motor.
F242 Run Frequency Hysteresis sets a plus-or-minus bandwidth for the Run Frequency. See the
ASD Operation Manualfor details.
F243 End Frequency sets the lowest frequency that an ASD will recognize before the ASD output
drops to 0.0 Hz.
F270, F272, F274 Jump Frequencies 1, 2, 3 are used in conjunction with the Jump Frequency
Bandwidth. The Jump Frequency is the center frequency of a range specified by Jump Frequency
Bandwidth. See the appropriate ASD Operation Manual for details ofJump Frequency processing.
F271, F273, F275 Jump Frequency Bandwidths 1, 2, 3 sets a plus-or-minus bandwidth for the
corresponding Jump Frequency.
F359 PID Control Switching is used to set the PID control mode. It disables/enables PID feedback
control. Set this parameter to enable PID and select the feedback source.
0: PID Off
1: Process PID
2: Speed PID
3: Easy Positioning PID
-
7/27/2019 PID Control Manual 6540
22/26
14 PID Control Manual
F360 PID Feedback Signal disables/enables PID feedback control. Set this parameter to enable PID
and select the feedback source.
0: PID Control Disabled
1: V/I
2: RR
3: RX
4: RX2 (AII)
5: Option V/I
6: PG Feedback Option
F361 PID Feedback Delay Filter sets the delay in the ASD output response to the motor-control
feedback signal source selected at F360. The delay filter in the feedback signal reduces process-induced
high frequency changes in the feedback speed.
F362 PID Feedback Proportional (P) Gain sets the degree that the Proportional (P) feedback
affects the output signal. The larger the value, the quicker the ASD responds to changes in feedback.
Setting the proportional gain excessively high may result in output over-correction and oscillation.
Change in ASD Response with Change in Proportional Gain. (I and D settings held constant)
F363 PID Feedback Integral (I) Gain sets the degree that the Integral (I) feedback affects the
output signal. The smaller the value, the more pronounced the effect of the Integral feedback on the
output signal. Integral gain determines how much the cumulative deviation (difference between the
process value and the feedback value) affects the output signal. Although a larger gain setting is
effective in reducing the residual deviation, setting the gain excessively high may result in output over-
correction and oscillation.
Change in ASD Response with Changes in Integral Gain. (P and D settings held constant)
Reference Process ValueF362 = 1
F362 = 0.01
Output Frequency
Time
Reference Process Value
F363 =
0.3
Output Frequency
Time
0.5
1.0
0.01
-
7/27/2019 PID Control Manual 6540
23/26
PID Control Manual 15
F364 PID Feedback Deviation Upper Limit sets the maximum amount that the feedback signal
may increase the output signal.
F365 PID Feedback Deviation Lower Limit sets the maximum amount that the feedback signal
may decrease the output signals.
F366 PID Feedback Differential (D) Gain sets the degree that the Differential (D) feedback affects
the output signal. The larger the value, the more pronounced the effect of the Differential feedback on
the output signal. The differential gain determines how much the rate of change of the deviation
(difference between the process value and the feedback value) affects the output signal. The larger the
value entered, the more pronounced the ASD response to changes in the feedback value. Setting the
gain excessively high may result in output over-correction and oscillation.
Change in ASD Response with Change in Differential Gain. (P and I gains held constant)
F367 PID Feedback Process Upper Limit sets the Upper Limit when operating in Process PID
mode.
F368 PID Feedback Process Lower Limit sets the Lower Limit when operating in Process PID
mode.
F369 PID Control Wait Time delays the start of PID control at startup. After the wait time the ASD
switches to the PID control setup.
F370 PID Output Upper Limit sets the Upper Limit when operating in Speed PID mode.
F371 PID Output Lower Limit sets the Lower Limit when operating in Speed PID mode.
F372 Process Increasing Rate limits the rate at which the output of the ASD may increase for a
given difference in the speed reference and the PID feedback value.
F373 Process Decreasing Rate limits the rate at which the output of the ASD may decrease for a
given difference in the speed reference and the PID feedback value.
F375 Number of PG Input Pulses sets the end-of-travel range when using an encoder on a motor-driven positioning system.
F376 Number of PG Input Phases determines the type of information that is supplied by the phase
encoder.
F381 Positioning Completion Range sets the range of accuracy for a Stop command initiated from
the terminal board when the ASD is in Simple Positioning PID mode.
F466 Speed PID Switching Frequency sets the minimum threshold speed setting at which PID
control may engage or remain engaged if active.
(Previous Deviation
Output Frequency
Time
Time
Large Differential Gain
Small Differential Gain
- Current Deviation)
Deviation Change with Time
A constant deviation between the set point and the feedback will result in a
constantly increasing output frequency.
The larger the differential gain, the larger the initial output frequency jump.
-
7/27/2019 PID Control Manual 6540
24/26
16 PID Control Manual
F660 Adding Input Selection enables or disables output frequency adjustment via an external
source. If enabled, the selected input is used as a modifier of the programmed Output Frequency.
F661 Multiplying Input Selection enables or disables output frequency adjustment via an external
source. If enabled, the selected input is used as a multiplier of the programmed Output Frequency.
F702 Display Unit Multiplication Factor provides the multiplier for the displayed frequency valueon the EOI.
For example: Given a multiplication factor of 0.5, an output frequency of 100 Hz would be displayed as
50.
The multiplier allows the EOI to be used to display the rate at which a commodity is being processed by
the system in process units per time.
F703 Display Unit Selection is used in conjunction with F702 to define which frequency values
displayed on the EOI will be affected by the Multiplication Factor (F702).
All Frequencies - Only PID frequency-limiting parameters F364, F365, F367, and F368 ARE NOT
affected by F702.
PID Process Data - Only PID frequency-limiting parameters F364, F365, F367, and F368 ARE
affected by F702.
F729 Panel Override Multiplication Gain provides a value to be used if the Multiplying Input
Selection (F661) is set to 4 F729 Setting.
Discrete Input/Output Terminals ASD discrete input terminals (F111 F118) and output terminals
(F130 F132) have several PID-related parameters that can be programmed.
See Table 4 and Table 5.
Table 4. ASD Input/Output PID Terminal Functions.
The PID signal can be monitored at the AM and FM terminals.
Table 5. FM, AM, and Monitor Output Function Selection.
Parameter Setting for
Normally Open
Parameter Setting for
Normally ClosedFunction
Input terminals
36 37 PID control OFF selection
52 53 PID differentiation/integration reset
54 55 PID forward/reverse switching
72 73Simple Positioning - Initiates a STOP
command
Output terminals 38 39 PID deviation limit
Function FM / AM Output Monitor Output
Option No. Communication No. Option No. Communication No.
Operation frequency command value 1 FD02 1 FE02
PID feedback value 13 FD22 13 FE22
-
7/27/2019 PID Control Manual 6540
25/26
-
7/27/2019 PID Control Manual 6540
26/26
INDUSTRIAL DIVISION13131 West Little York Road, Houston, Texas 77041
Tel 713/466-0277 Fax 713/937-9349
US 800/231-1412 Canada 800/872-2192 Mexico 01/800/527-1204
www.toshiba.com/ind
Printed in the U.S.A.