Generating power solutions from 10 - 5,000 kVA Performance Data Sheet Specification Notes Perkins Powered Range 600 - 2250 kVA BCP600P 3012TAG1A 600 480 5700 5510 4000 1457 2104 136 BCP670S 3012TAG1A 670 536 5700 5510 4000 1457 2104 149 BCP650P 3012TAG1B 650 520 5700 5510 4000 1457 2104 137 BCP700S 3012TAG1B 715 572 5700 5510 4000 1457 2104 151 BCP720P 3012TAG2A 720 576 6000 5810 4000 1457 2104 157 BCP800S 3012TAG2A 800 640 6000 5810 4000 1457 2104 173 BCP800P 3012TAG3A 800 640 6150 5960 4000 1457 2104 171 BCP880S 3013TAG3A 880 704 6150 5960 4000 1457 2104 189 BCP900P 4008TAG1A 910 728 8725 8410 5350 1927 2325 194 BCP1000S 4008TAG1A 1000 800 8725 8410 5350 1927 2325 217 BCP1000P 4008TAG2 1000 800 8900 8540 5350 1927 2325 221 BCP1100S 4008TAG2 1110 888 8900 8540 5350 1927 2325 248 BCP1250P 4012TWG2 1270 1016 12000 11840 5400 2000 2746 265 BCP1400S 4012TWG2 1403 1122 12000 11840 5400 2000 2746 294 BCP1350P 4012TAG1A 1350 1080 12880 12470 5600 2100 2592 276 BCP1500S 4012TAG1A 1500 1188 12900 12480 5600 2100 2592 309 BCP1500P 4012TAG2 1500 1200 12900 12480 5600 2100 2592 307 BCP1650S 4012TAG2 1658 1326 12900 12480 5600 2100 2592 346 BCP1750P 4016TAG 1750 1400 15800 15270 6450 2316 2956 362 BCP1900S 4016TAG 1929 1543 15800 15270 6450 2316 2956 403 BCP1800P 4016TAG1 1800 1440 17900 17370 6450 2316 2965 389 BCP2000S 4016TAG1 2000 1600 17900 17370 6450 2316 2956 428 BCP2000P 4016TAG2 2050 1640 17900 17370 6450 2316 2956 436 BCP2250S 4016TAG2 2250 1800 17900 17370 6450 2316 2956 491 Product Reference Specifications Genset Model Engine Model 50Hz Weight (kg) Dimensions(mm) Fuel Consumption(l/hr) kVA kW Wet Dry L W H 50Hz Rating Definitions Prime Power (models with suffix ‘P’) All ratings are suitable for continuous electrical power (at a variable load in lieu of main power network). There are no limitations to the annual hours of operation and all models can supply 10% overload power for 1 hour in 12 hours. Standby Power (models with suffix ‘S’) Standby ratings are for the supply of emergency power at variable load in the event of a main power network failure up to a maximum of 500 hours per year. No overloads permitted. For base load (COP) power applications, consult Broadcrown Sales Department. Standard Reference Conditions Output ratings are typical for sets operating at 380-416V (3 phase). Ratings at 0.8p.f.25 O C(77 O F) ambient, 177m (600ft) above sea level. All data in accordance with BS5514, ISO 3046, DIN6271, ISO 8528. Wet weights = with lube oil and coolant. Dry weights = with lube oil. Generating set picture and drawing may include optional accessories. Specifications and design subject to change without notice.

description

Braodcrown Perkins gensets

Transcript of Perkins PDS Eng Iss1

Page 1: Perkins PDS Eng Iss1

Generating power solutions from 10 -5,000 kVA

Performance Data Sheet

Specification Notes

Perkins Powered Range600 - 2250 kVA

BCP600P 3012TAG1A 600 480 5700 5510 4000 1457 2104 136BCP670S 3012TAG1A 670 536 5700 5510 4000 1457 2104 149BCP650P 3012TAG1B 650 520 5700 5510 4000 1457 2104 137BCP700S 3012TAG1B 715 572 5700 5510 4000 1457 2104 151BCP720P 3012TAG2A 720 576 6000 5810 4000 1457 2104 157BCP800S 3012TAG2A 800 640 6000 5810 4000 1457 2104 173BCP800P 3012TAG3A 800 640 6150 5960 4000 1457 2104 171BCP880S 3013TAG3A 880 704 6150 5960 4000 1457 2104 189BCP900P 4008TAG1A 910 728 8725 8410 5350 1927 2325 194BCP1000S 4008TAG1A 1000 800 8725 8410 5350 1927 2325 217BCP1000P 4008TAG2 1000 800 8900 8540 5350 1927 2325 221BCP1100S 4008TAG2 1110 888 8900 8540 5350 1927 2325 248BCP1250P 4012TWG2 1270 1016 12000 11840 5400 2000 2746 265BCP1400S 4012TWG2 1403 1122 12000 11840 5400 2000 2746 294BCP1350P 4012TAG1A 1350 1080 12880 12470 5600 2100 2592 276BCP1500S 4012TAG1A 1500 1188 12900 12480 5600 2100 2592 309BCP1500P 4012TAG2 1500 1200 12900 12480 5600 2100 2592 307BCP1650S 4012TAG2 1658 1326 12900 12480 5600 2100 2592 346BCP1750P 4016TAG 1750 1400 15800 15270 6450 2316 2956 362BCP1900S 4016TAG 1929 1543 15800 15270 6450 2316 2956 403BCP1800P 4016TAG1 1800 1440 17900 17370 6450 2316 2965 389BCP2000S 4016TAG1 2000 1600 17900 17370 6450 2316 2956 428BCP2000P 4016TAG2 2050 1640 17900 17370 6450 2316 2956 436BCP2250S 4016TAG2 2250 1800 17900 17370 6450 2316 2956 491

Product Reference Specifications

Genset Model Engine Model 50Hz Weight (kg) Dimensions(mm) Fuel Consumption(l/hr)kVA kW Wet Dry L W H 50Hz

Rating Definitions

Prime Power (models with suffix ‘P’)All ratings are suitable for continuous electrical power (at a variable load in lieu of main power network). There are nolimitations to the annual hours of operation and all models can supply 10% overload power for 1 hour in 12 hours.

Standby Power (models with suffix ‘S’)Standby ratings are for the supply of emergency power at variable load in the event of a main power network failureup to a maximum of 500 hours per year. No overloads permitted.For base load (COP) power applications, consult Broadcrown Sales Department.

Standard Reference Conditions

Output ratings are typical for sets operating at 380-416V (3 phase). Ratings at 0.8p.f.25OC(77OF) ambient, 177m (600ft)above sea level. All data in accordance with BS5514, ISO 3046, DIN6271, ISO 8528.

Wet weights = with lube oil and coolant. Dry weights = with lube oil.

Generating set picture and drawing may include optional accessories.

Specifications and design subject to change without notice.

Page 2: Perkins PDS Eng Iss1

MOUNTING ARRANGEMENT

Baseframe

The complete generator set is mounted as a whole on a heavy duty fabricated,welded steel baseframe. The baseframe incorporates specially designed lifting eyesfor sling operation.

Coupling

The engine and alternator are directly coupled by means of an SAE flange so thatthere is no possibility of misalignment after prolonged use. The engine flywheel isflexibly coupled to the alternator and a full torsional analysis has been carried out toguarantee no harmful vibration will occur in the assembly.

Anti-Vibration Mounts

Anti-vibration mounts are supplied pre fitted between the engine/alternatorcombination and the baseframe for generators upto and including BCP880S. AVM’swill be supplied loose for site installation between the baseframe and floor on allother generator combinations.

Safety Guards

The fan, fan drive and battery charging alternator drive are fully guarded forpersonnel protection. A stone guard protects the radiator core from accidentaldamage.

GENERAL ARRANGEMENT

The generator set is designed and constructed for installation in a weatherproofbuilding. Various types of weatherproof and sound attenuated ISO containers areavailable.

DOCUMENTATION

A full set of operation and maintenance manuals and circuit wiring diagrams aresupplied with each generating set.

FACTORY TESTS

The generator set is load tested before despatch. All protective devices, controlfunctions are simulated and the generator and its systems checked, proved andthen passed for despatch. A test certificate is provided as standard.

EQUIPMENT FINISH

Primer on all equipment. Final coat to manufacturers standard.

QUALITY STANDARDS

The equipment meets the following standards: BS.4999, BS.5000, BS.5514, IEC 34,VDE0530, NEMA MG-122

PRODUCT ENDORSEMENT

All equipment is guaranteed for a period of 12 months from date of commissioningor 18 months from shipping whichever occurs first. Where equipment is suppliedby an authorised Broadcrown Distributor or Dealer, the 12 months guarantee periodwill commence from date of ex works shipment, whichever occur first.

Please see Broadcrown Warranty Statement for a full specification of terms.Extended warranty terms are available, for details please contact BroadcrownCustomers Services Dept.

Equipment must only be used in accordance with recommended operating practicesand subject to any specified load limitations.

MISCELLANEOUS

Shrink wrapped for export.

Standard Specifications

OUTPUT RATINGS

The following 3 phase voltages are available:-50 Hz 416 400 380

240 230 220

Other voltages are available on request.

ENGINE

Perkins heavy duty industrial diesel engine.

Governor

Compliant with BS.5514 Class A1.Electronic governing standard on all 4000 series engines at 1500 rpm.

Electrical System

24V system with battery charging alternator, axial type starter motor, high capacitymaintenance free lead acid starting batteries, battery rack mounted on the generatorset baseframe and heavy duty interconnecting cables with terminations.

Engine Filtration System

Sealed paper mesh type dry air filters. Cartridge type fuel filters and full flow lubeoil filters. All filters have replaceable elements.

ALTERNATOR

Newage alternators have been carefully selected to match the overload performanceof the engine and incorporate the following: Screen protected and drip proof, selfexciting, self regulating brushless alternator with fully interconnected damperwindings, IC06 cooling system and sealed for life bearings. PMG fitted as standardon BCP 1000 models and above.

Insulation System

The insulation system is Class H.All windings are impregnated in either triple dip thermo-setting moisture, oil and acidresisting polyester or vacuum impregnated with a special polyester resin. Heavycoat of anti-tracking varnish for additional protection against moisture orcondensation.

Electrical Characteristics

Electrical design in accordance with BS.5000 Part 99, IEC34-1, VDE0530, UTE5100,NEMA MG-122, CEMA, CSA22.2 and AS1359.

Automatic Voltage Regulator

The fully sealed automatic voltage regulator maintains the voltage within the limitsof ± 0.5% (±1% on HCI5 frame) from no load to full load including cold to hotvariations at any power factor between 0.8 lagging and unity and inclusive of aspeed variation of 4.0%. Nominal adjustment is by means of a trimmer incorporatedin the AVR.

Radio Interference

Suppression is in line with the provisions of BSEN 50081 and VDE Class G.

CONTROL SYSTEM

Baseframe mounted, control panel of fabricated steel construction with a hingedlockable door. The control panel is isolated from vibration and comprises of thefollowing instrumentation and controls: Oil pressure gauge, water temperaturegauge, battery charge ammeter, voltmeter and selector switch, frequency meter andhours counter. An auto start control module and emergency stop button are fittedas standard.

Shutdown Protection Devices with Indicators for:-

High coolant temperature and low oil pressure.

FUEL SYSTEM

Fuel feed and return lines are fitted between the engine terminated at a bulkhead onthe generator baseframe.

COOLING RADIATOR

Radiator and cooling fan complete with protection guards, designed to cool theengine at specified output, in air-on temperatures up to 45ºC (113ºF)Coolant drain valve and remote filling facility and site gauge are fitted as standard.

Airfield Industrial Estate, Hixon, Stafford, Staffordshire, ST18 OPF, England. T: +44(0)1889 272200 F: +44(0)1889 272220 E: [email protected] www.broadcrown.com