Performance measurements on a Photovoltaic (PV) · PDF filePerformance measurements on a...
Transcript of Performance measurements on a Photovoltaic (PV) · PDF filePerformance measurements on a...
1
Performance measurements on a
Photovoltaic (PV) system
System integration project II
Student: Zhenxue Wu 0621034
Supervisor: Prof.dr.ir.R. J. Ch. van Zolingen
Eindhoven University of Technology
Department of Mechanical Engineering
Master program of Sustainable Energy Technology
Report number WET 2007.13
Date:
02-09-2007
2
Summary
A Photovoltaic (PV) system is comprised of photovoltaic cells which convert light energy
directly into electricity. It offers consumers the ability to generate electricity in a clean,
quiet and reliable way. Both an autonomous and two grid-connected PV systems are used
for experimental purposes in this project.
In this project the focus was in the area of performance measurements on the PV system.
The goals include checking the characteristics of an autonomous PV system by testing
the battery and regulator’s performances; testing the relationship between the open circuit
voltage Voc and the cell temperature Tcell and testing the relationship between energy
output and ambient conditions, such as sunlight irradiance and cell temperature.
In order to test the battery’s performances, the internal resistance was checked and the
old battery was around 40~80 mΩ while the new one was around 20 mΩ. Besides, the
total amount of energy withdrawn from the battery during discharging was measured. For
the old battery the available energy was only 40 Ah while for the new battery was more
than 70 Ah. Therefore the old battery was considered to be aging and was replaced by the
new one.
The incorporation of a regulator in the PV system can be used as overcharge protection
and deep discharge protection for battery. For the regulator in our project the charge
status of battery will control the charging process by means of Pulse Width Modulation
(PWM) and an oscilloscope was used to observe the performance of it. By observing its
working waveforms we can know that the repetition frequency is fixed even when the
irradiance changes and the ratio between pulse duration (TD) and repetition frequency
(TR) increases with an increase of irradiance. However, with a higher State of Charge
(SOC) condition, this TD and TR ratio decreases as they are also determined by the
actual battery voltage.
As the performance of a PV module is dictated by several ambient conditions such as
ambient temperature, irradiance, wind speed, wind direction and humidity, tests were
performed to find if the open circuit voltage could be used as a measure of cell
temperature. Based on the actual open circuit voltage Voc measured, the ambient
temperature and a simple model, STCOCV , (Voc at Standard Test Conditions) can be
extrapolated. Next Voc can be used to estimate the cell temperature under operational
conditions, using STCOCV , . A conclusion was given that open circuit voltage can give an
immediate indication for the cell temperature only when the solar irradiance does not
change too fast.
In the grid-connected PV system in our project a maximum Power Point Tracking (MPPT)
is installed inside the inverters to extract the maximum power from a PV array. Through
measuring the energy output and ambient conditions we can find that with a higher
irradiance and lower cell temperature, the PV module can generate more energy.
3
Contents Summary............................................................................................................................. 2
1 Introduction...................................................................................................................... 4
1.1 Background of project............................................................................................... 4
1.2 Project goals.............................................................................................................. 4
1.3 Structure of the report ............................................................................................... 4
2 Description of PV system ................................................................................................ 5
2.1 Energy of sun ............................................................................................................ 5
2.2 Principle of photovoltaic conversion ........................................................................ 6
2.3 PV systems................................................................................................................ 7
2.3.1 Autonomous PV systems ................................................................................... 7
2.3.2 Grid-connected PV systems............................................................................... 8
2.3.3 Hybrid PV systems ............................................................................................ 8
2.4 Description of actual experimental PV system......................................................... 8
3 Battery tests.................................................................................................................... 13
3.1 Working of battery.................................................................................................. 13
3.2 Properties of battery................................................................................................ 13
3.3 Test of the old battery ............................................................................................. 14
3.4 Test of the new battery............................................................................................ 16
3.4.1 Discharging the new battery (Charged by solar energy) ................................. 16
3.4.2 Comparison with charged by a conventional battery charger.......................... 19
3.5 Re-test of the old battery......................................................................................... 20
4 Regulator tests................................................................................................................ 21
4.1 Principle of regulator .............................................................................................. 21
4.2 Observation of regulator current waveform by oscilloscope.................................. 23
5 Relationship between open circuit voltage and cell temperature................................... 26
5.1 Extrapolation of Voc to Standard Test Condition (STC)........................................ 26
5.2 Calculation of cell temperature............................................................................... 27
5.3 Analysis of outcome ............................................................................................... 28
6 Energy output and ambient conditions .......................................................................... 30
6.1 Power output of PV system..................................................................................... 30
6.2 Analysis of the relationship between energy output and ambient conditions......... 30
7 Conclusions and recommendations................................................................................ 33
References......................................................................................................................... 34
Appendix........................................................................................................................... 35
A.1: Measured data charged by solar system................................................................ 35
A.2: Measured data charged by a conventional battery charger ................................... 36
4
1 Introduction
1.1 Background of project
This project was performed by student of the Master program ‘ Sustainable Energy
Technology’ of the Eindhoven University of Technology by means of the course ‘ 0C921
Internal research traineeship’.
1.2 Project goals
A photovoltaic (PV) system is comprised of photovoltaic cells which convert light energy
directly into electricity. It offers consumers the ability to generate electricity in a clean,
quiet and reliable way. They are usually referred to the amount of energy they generate in
full sunlight, known as kilowatt peak or kWp. The greater the intensity of the light, the
more energy a solar cell generates.
For this project the focus was in the area of performance measurements on the PV system.
Accurate and consistent evaluations on it are critical for the continuing development of
the PV industry. The goals include the following: 1, checking the characteristics of
autonomous PV system by testing the battery and regulator’s performances; 2, testing the
relationship between the open circuit voltage Voc and the cell temperature Tcell ; 3, testing
the relationship between energy output and ambient conditions, such as sunlight
irradiance and cell temperature.
1.3 Structure of the report
In chapter 2 the actual system used for measurement experiments will be presented.
There descriptions about basic performance of solar cell system and the main components
of the system are given. Following in chapter 3 battery measurements which will test the
charging and discharging characteristics of both old and new batteries are carried out.
Theory of regulators (controllers) used in PV system will be introduced in chapter 4 and
its working waveform as can be observed by oscilloscope will be presented.
Extrapolation of Voc to Standard Test Condition will be given in chapter 5 and analysis
about the relationship between the open circuit voltage and cell temperature is included.
Following, experiments to test the relationship between energy output and ambient
conditions are presented in chapter 6 and conclusions and recommendations will be given
in the final chapter 7.
5
2 Description of PV system
2.1 Energy of sun
Solar energy is a source of energy that uses radiation emitted from the sun. The sun light
can be considered as a flow of quasi particles, called photons. These photons have energy
as the equation shown below:
λ/hchvE ph ==
with
phE – Photon energy;
h – Planck constant, sJ ⋅× −3410626.6 ;
v – Frequency of the light;
λ – Wavelength of the light;
c – Speed of the light, sm /100.3 8× .
Besides, light also can be treated as an electromagnetic wave with time varying electric
and magnetic fields, which are propagating through space in such a way that always
perpendicular to each other and to the direction of propagation.
The spectrum of the radiation emitted by the sun is close to that of a black body at a
temperature of 5900 K. About 8% of the energy is in the ultra-violet region, 44% is in the
visible region and 48% is in the infra-red region [1].
While traveling through the atmosphere layer, solar radiation is partially depleted and
attenuated due to absorption, scattering and reflection. That is to say, the intensity of
sunlight at ground level varies with latitude, geographic location, season, cloud coverage,
atmospheric pollution, elevation above sea level, solar altitude, etc. In the Netherlands,
the intensity of the sun is about 1000 W/m2 at an optimally oriented surface at noon
during the summer under blue sky conditions [2].
As the efficiency of a solar cell depends on the spectral composition of the light, air mass
(AM) is introduced which characterizes the effect of a clear atmosphere on sunlight. AM
1.5 is a typical solar spectrum on the earth’s surface on a clear sunny day, with a total
irradiance of 1000W/m2 used as standard test irradiation in Standard Test Conditions
(STC, 1000W/m2 irradiance, 25
oC cell temperature, AM 1.5 spectrum) for solar cells.
The available irradiance is usually not equal to this value because of the diverse weather
conditions and the rotation of the earth. It may sometimes be higher and in most cases
lower than this value.
The amount of radiation that reaches the ground is very variable, and it depends on
various factors, for example weather conditions, the time of the year, the time of the day
and location. From the global yearly solar radiation we know that in the Netherlands, a
large difference occurs regarding the irradiation in summer and in winter. The average
irradiation on a south oriented plane with a tilt angle of 45 degrees in June and December
6
is 5 kWh/ m2 per day and 1 kWh/m
2 per day respectively. In a poor December month the
average daily irradiation can even drop to 0.5 kWh/ m2 per day.
2.2 Principle of photovoltaic conversion
Photovoltaic (PV) conversion is the conversion of (sun) light by means of solar cells,
which use the photovoltaic effect of semiconductors to generate electricity directly from
sunlight. A simplified schematic diagram of a typical solar cell is shown in Figure 2.1.
Figure 2.1 Principle of operation of the solar cell [3]
From the schematic figure 2.1 we can see that a typical silicon PV cell is composed of a
thin wafer consisting of an ultra-thin layer of phosphorus-doped (N- type) silicon diffused
in a thicker layer of boron doped (P-type) silicon. An electric field is created at the
junction of the cell between the P-type and N-type material. When the sunlight falls on
the solar cell, photons with energy Eghv ∆≥ (the band gap of the semiconductor silicon)
are absorbed. During the absorption of such a photon an electron is transferred from the
valence band to the conduction band. A hole stays behind in the valence band. The
absorption of a photon generates an electron-hole pair, therefore. If the electron-hole pair
is generated near the p-n junction the electron and the hole will be separated by the strong
electric field which presents at the p-n junction. If the electron-hole pair is generated
deeper within the p-type semiconductor, then the electron can reach the p-n junction by
diffusion and reach the n-type area by the strong electrical field. Electrons are collected
by the contact grid and resulting in a flow of current when the solar cell is connected to
an external load.
Regardless of size, a typical multi-crystalline silicon PV cell produces about 0.6 volt DC
under open circuit, no-load conditions and about 0.5 volt DC in its maximum power point.
However, this voltage is too low for most practical applications. In autonomous PV
7
systems, therefore, photovoltaic cells are connected electrically in series and/or parallel
circuits to produce higher voltages, currents and power levels. Photovoltaic panels
include one or more PV modules assembled as a pre-wired, field-installable unit and a
PV module often contains 36 cells in series in order to obtain a maximum power point
voltage of approximately 17 to 18 volt at standard test conditions. This voltage is
sufficient to charge a lead-sulphuric acid battery with a nominal voltage of 12 volt
adequately.
Conclusively, the current and the power output of a PV system depends on its efficiency
and size, and also depends on the intensity of sunlight striking in the surface of the cell.
Besides, ambient conditions which may change its operation temperature also have
influences on the electrical power generation of the PV system.
2.3 PV systems
PV systems are usually categorized into three types: autonomous (Off-Grid), grid-
connected and hybrid. The type chosen depends on the needs, location and budget.
2.3.1 Autonomous PV systems
Autonomous PV systems are PV systems which can produce electricity independently of
other energy generation systems. They are not connected to the main utility grid and in
most cases, batteries for storage are incorporated which store energy from the PV
modules during the sunny days and supply energy at night or in periods of low solar
radiation. Such a system consists of a number of PV modules, battery storage, regulator
and loads (as shown in figure 2.2).
Figure 2.2 Circuit diagram of an autonomous PV system [4]
In figure 2.2 we can see that PV module connected in series and/or parallel give a DC
current if the module is illuminated. The PV module charges the battery via a diode
which ensures that the battery can not discharge itself via the PV module at night. The
consumer receives its current directly from the PV module or from the battery when the
8
irradiance is low. The incorporation of a regulator (also called controller) can be used as
overcharge protection and deep discharge protection for battery.
Autonomous PV systems are usually used in those areas where only small amounts of
electrical energy are required, where no public grid is available or where the cost of a
grid connection is too high such as remote homes, cottages.
2.3.2 Grid-connected PV systems
Grid-connected PV systems are systems which supply their energy to the public
electricity grid. The basic Grid-connected PV system design has the following
components:
PV modules: As in autonomous system;
Inverter: Inverts the DC power from the modules into AC power. The characteristics of
the output signal should match the voltage, frequency and power quality limits in the
supply network;
Loads: Energy consumption of the local house;
Meters: Account for the energy being drawn from or fed into the local supply network;
Local grid: Public grid which acts both as a sink for energy surplus in the PV system or
as a backup for low PV generation periods.
Figure 2.3 Circuit diagram of a Grid-connected PV system
When the PV system is connected to the grid it will produce electricity that will be used
directly in the house. If the system generates more power than needed by the home then
the excess can be sold back to the local electricity company via public grid network.
However grid connection of a PV system must have local electricity company approval
that ensure the system is properly installed and with the required degree of protection.
2.3.3 Hybrid PV systems
Hybrid systems receive a portion of their power from one or more additional sources. In
practice, PV modules are often paired with a wind generator or a fuel-fired generator.
2.4 Description of actual experimental PV system
Both an autonomous and two grid-connected PV systems in the Mechanical Engineering
laboratory are available for experimental purposes in this project. The PV panels are
mounted on the roof of the W-Laag building, TU/e, Netherlands (Latitude: 51.26’ N;
9
Longitude: 5.29’E; altitude: 19 m). They are installed on one support structure which
holds the panels at an optimal angle of about 36 degrees measured from the horizontal
and south facing for effective capturing of solar irradiation (as shown in figure 2.4).
Figure 2.4 PV panels mounted on the roof of W-Laag building
Besides these PV panels, a number of other components such as batteries, regulator and
measured meters are needed to complete the system. The wiring diagram of the whole
system is shown in figure 2.5.
10
Figure 2.5 Wiring diagram of this PV system [5]
On the left side of modules array in figure 2.4 there are three PV modules that are rated at
100Wp each. One of these modules is idle which is mounted there for future research
(module 3 in figure 2.5) and the other two modules (module 1 and 2 in figure 2.5) are
connected to their own inverter that converts the DC current to AC current. The power is
then fed into the grid system by plugging a socket into the grid and the total power
transmitted will be recorded by two energy meters (energy meter 1 and 2 in figure 2.5).
These two PV panels form a grid-connected PV system without battery storage.
On the right side of these modules array there are two 36 Wp modules (module 4 and 5 in
figure 2.5) which are connected in parallel. The power output of them, which is used to
charge a 100 Ah battery, varies with variation of the radiation intensity incident on the
modules. These two PV modules form an autonomous system with battery storage. As
crystalline silicon cell produces approximately 0.5 V in its maximum power point, each
of these two modules has 36 cells connected in series, which makes sure that the 12 V
batteries can be charged completely. For this autonomous system the nominal system
voltage is 12 volt, therefore.
11
On the most right of these modules is the smallest one which is taken as a reference
module. A reference module is a specially calibrated PV module which is used to
measure irradiance. It is connected to an ampere meter which effectively short circuited it.
When solar irradiation of intensity 1000 W/m2 is incident on the panel under standard test
condition, a short circuit current of 1.5 A is measured by the meter.
As we mentioned previously, besides the PV modules, there are other components such
as battery, regulator, meters and external loads and they are placed inside the lab (figure
2.6) to protect against the environment erosion, i.e. wind, rain, sunshine and dust.
Figure 2.6 Indoor devices of the PV system
On the left of figure 2.6 is a battery for storage. The battery used for experiment is a
Varta E34s, 12 V, capacity 100 Ah lead acid batteries. In the center is the PV charge
regulator and to the right are the meters that measure the current, voltage, irradiance and
power. The charge regulator used in this project is a 12 A charge controller of Steca make.
It is used to protect the circuit from over charge and too deep discharge. The loads here
include three 35 watt incandescent lamps and one 7 watt fluorescent lamp and all of these
lamps are connected in parallel.
On the left side of top aluminum box is the voltmeter that indicates the battery voltage.
To the immediate right of the voltmeter is an ampere meter that is used to show the
charging current from the PV modules. To the right of charging current ampere meter is
another ampere meter that measures the current drawn by the loads. These meters
together with switches for the loads were encased in a small aluminum box for protection
against the external environment.
12
In the center of the bottom box is the ampere meter that measures the irradiance intensity
which is based on the short circuit current of the reference panel. On two side of this
meter there are two energy meters which are used to show the present delivering power
and to record the amount of power that have been delivered to the grid since installation.
13
3 Battery tests
3.1 Working of battery
Batteries are often used in autonomous PV systems for the purpose of storing electrical
energy produced by the PV array during the day, and supplying it to electrical loads as
needed (during the night and periods of low irradiation).
The lead sulphuric acid battery is the most common battery used in PV systems, mostly
because it has high performance compared to its cost. They are made up of a number of
cells and each cell has a nominal voltage of 2 volts. Therefore for a 12 V battery, it means
it was made up by six cells connected in series. Each cell contains a number of ‘positive’
and ‘negative’ plates immersed in a sulphuric acid solution diluted with de-ionized water
(the electrolyte).
During discharging both the lead oxide and the lead are converted into lead sulphate and
the density of the sulphuric acid decreases. During charging the lead sulphate is
converted back to lead oxide and lead and the sulphuric acid solution reaches its
maximum density when the battery cell is fully charged again. The reactions are as
shown below:
OHPbSOSOHPbPbO 24422 222 +→++ ……………….Discharging reaction
42224 222 SOHPbPbOOHPbSO ++→+ ………………Charging reaction
These batteries are charged by the PV modules in periods with high irradiation and have
different characteristics compared with being used in other fields:
1, the batteries are charged and discharged daily;
2, most of the time the batteries are not fully charged due to short charging time available;
3, exposed to low state of charge conditions for a long time, especially in the winter
period, or exposed to a high ambient temperature in summer, can shorten their life time
and accelerate their aging process.
3.2 Properties of battery
Some important properties of a battery:
Capacity:
The capacity of a battery is the quantity of charge (expressed in Ah) which can be
withdrawn from a fully charged battery. The capacity depends both on the size of the
discharge current and on the temperature of the battery. As the discharge current
increases the capacity decreases and as the temperature increases the capacity increases,
the capacity of a battery must therefore be defined at a specific discharge current and a
specific battery temperature.
State of Charge (SOC):
The State of Charge (SOC) of a battery indicates the relative quantity of charge available
in a battery. The SOC is 100% when the battery is fully charged; the SOC is 0% when the
battery is fully discharged.
14
Self-discharge:
The self-discharge of a battery indicates what part of the battery charge is lost if the
battery is not used. The self-discharge increases sharply when the temperature rises. A
typical value for the self-discharge of a lead acid battery with an antimony content of 2%
is 3% per month at 25 oC and for a lead acid battery in which the antimony is replaced by
calcium it is 1% per month.
Floating voltage:
When the batteries are used as back-up systems, the batteries are kept fully charged by
compensating for the self-discharge. This is done by keeping the battery voltage at the
float voltage under trickle charging. If the floating voltage setting is too high, the
floating current is also too high, which will accelerate corruption of the grid and shorten
the life of the battery. If the setting is lower, the battery can’t be kept in fully charged
state, which will crystallize PbSO4, decrease the capacity and also shorten the life of the
battery.
Ageing mechanisms:
Some of operating parameters are used to indicate aging effects because the actual
capacity of the battery is subjected to change during service life such as the loss of active
material, corrosion of the conducting elements, and the gradual loss of water.
Grid corrosion at the positive electrode is the most critical parameter during the float
charge of lead acid batteries. Increased grid corrosion can be induced by overcharging at
too high voltage, which may increase internal resistance of the battery and therefore
increase voltage drop and decrease the amount of energy withdrawn from battery.
Besides, if the battery is discharged too deeply or if a battery cell is exposed to a low
charging condition for too long, the amorphous lead sulphates can change to
polycrystalline lead sulphates. During charging it is virtually impossible to convert this
form of lead sulphate. This is known as sulphating and leads to a permanent decline in
the capacity of the battery. Moreover, the cyclical stress, differences in acid density and
exposure to high temperature also will speed up the aging of battery.
Because of these characteristics and high sensitivity to over-charging and deep
discharging, some forms of services such as regulators are needed to ensure the service
life of batteries by controlling its performance during charging and discharging process.
3.3 Test of the old battery
As we mentioned before, the battery used for experiment is a 12 V, capacity 100 Ah lead
acid battery. As it had been used for quite a long time, testing its performance is
necessary to see if it was still suitable for the project.
The test was started by disconnecting the PV module from the fully charged battery (or
SOC> 90%). This was done by removing the PV modules’ connections from the
controller. The connections of the battery to the controller were retained to prevent the
battery from too deep discharge. The loads were switched on and the voltage and current
15
were measured at a certain time intervals until the voltage regulator disconnected the load
automatically due to low energy left inside the battery. Consequently battery voltage
versus time, and battery voltage versus discharging current characteristics were obtained
and the energy (Ah) drained from the battery can be determined by multiplying the
current drawn from the battery and the number of hours this current flows ( circuit
diagram as shown in figure 3.1).
Figure 3.1 Simple circuit diagram of discharging process
During the first time of discharging test, three 35 Wp lamps in parallel were used as loads.
The battery terminal voltage was 13.1 V before connected with loads. When the lamps
were turned on, the battery terminal voltage dropped to 12.8 V. The discharging current
was kept around 7.9 A. However, only after 20 minutes, the lamps were turned off
automatically, with a terminal voltage of battery of 12.05 V. This was done by regulator,
which can control the system running and avoid deep discharging when the terminal
voltage of battery drop to the lowest allowed working voltage. Based on this the total
energy of 3.1 Ah withdrawn in this test was calculated out, which was quite far away
from the rated energy of 100 Ah. This may due to several possibilities: the dry of distilled
water immersed in the sulphuric acid solution; the battery hadn’t been used for quite a
long time and need to be charged and discharged for several times to activate the
materials; aging of battery.
In order to find out the reasons of low withdrawn energy, first the de-ionized water inside
the battery was checked. As the distilled water was still sufficient, the cause of distilled
water shortage can be eliminated. After that the battery was repeatedly charged and
discharged several times and tried to activate the reaction materials. However, when
discharging test was taken again, still only 10 Ah of energy was withdrawn. Activating
the reaction materials didn’t success, therefore.
When considering the aging of battery, we know that if a battery ages and loses capacity,
its vital internal components undergo unavoidable degradation, which can cause an
increase in the battery’s internal resistance. Therefore the internal resistance is usually
measured to determine the health of a battery. A healthy, fully charged 12 V, 24 Ah lead
acid batteries would have an internal resistance of 20 mΩ [6] and it goes up during
discharge process. This change is caused by the decrease of the specific gravity, a
depletion of the electrolyte as it becomes more watery. Therefore under different state of
charge, the internal resistance would be different.
16
One way to measure the internal resistance is to compare the difference between open
circuit voltage of the battery and voltage of battery when connected with load. The
internal resistance was then considered as the ratio between the difference of voltage and
the discharging current when connected with load. The internal resistance of the battery,
however, is a dynamic nonlinear parameter that is continuously changing along with the
temperature and discharge state. In that case using this method to measure the internal
resistance of battery under discharging is not accurate due to the status change from a still
state to a discharging state. Therefore we determined the internal resistance under
discharging state by following steps:
1, Connect a load to the battery and quickly measure the battery terminal voltage and
discharging current at the same time, U1, I1; Here as the load will heat up very quickly,
which in turn will falsify the voltage readings- so conduct the whole measurement within
max.5 s and disconnect the load immediately;
2, Wait for 4~5 minutes for the voltage to stabilize, and determine the terminal voltage
U2 and discharging current I2 with another different load;
3, Internal resistance is then calculated according to Ohm’s law, R=∆U/∆I, where ∆U is
the voltage difference and ∆I is the current difference for these two sets data (as shown in
table 3.1).
Table 3.1 Calculation of internal resistance
Loads connected Terminal voltage of
battery(V)
Discharging
current(A)
Internal resistance(mΩ)
Set 1
1*35 Wp lamp 12.86 2.85
1*7 Wp lamp 12.97 0.45 46
Set 2
1*35 Wp lamp 12.99 2.8
1*7 Wp lamp 13.18 0.45 81
From the data above we can see that the internal resistance is a little high.
3.4 Test of the new battery
As the total energy withdrawn from the old battery was too low, a new battery which is
also a Varta E34s, 12 V, and capacity 100 Ah lead acid batteries was used to continue the
experiments of this project.
3.4.1 Discharging the new battery (Charged by solar energy)
This test was discharging the new battery which had been charged by solar energy and
reached a SOC of >90%. First of all the internal resistance of this new battery was
measured and the value is around 20 mΩ, which is much less than that of the old battery.
The initial terminal voltage of battery was 11.98 V before connected to any PV panels.
As we know that the new batteries often do not give their rated capacity when received
from the manufacturer. This is due to the methods of making the plates. The plates are
usually made by applying oxides of lead, mixed with a liquid, which generally is dilute
17
sulphuric acid, to the grids. These oxides must be subjected to a charging current in order
to produce the spongy lead and lead peroxide. After the charge, they must be discharged,
and then again charged. This is necessary because not all of the oxides are changed to
active material on one charge, and repeated charges and discharges are required to
produce the maximum power available. In this case, we repeated charge and discharge
the new battery several times first. The production of discharging, however, was still
very low, with energy withdrawn of 4 Ah. It was strange for a new battery and there must
be some problems in this system.
As the system was monitored by the regulator, when checking the connection wires
between battery and controller we found that the resistance of the cable wires was higher
than 0.15 ohm, which may cause a voltage drop of 1.64 V at full load. In that case even if
the terminal voltage of battery is still very high, for example 12.2 V, the voltage
measured by regulator terminal is only 10.6 V, which was considered by the regulator
that it was near the lowest allowed voltage. Therefore the controller would disconnect the
loads automatically to protect the battery from deep discharging. In order to increase the
energy withdrawn by the loads, we displaced the original wires with some other thicker
ones, with resistance of only 0.0066 ohm and the voltage drop turns to be only 0.05 V.
During the discharging process, however, we noticed that the loads were usually turned
off for 3~5 seconds and then turned on again automatically, even though the voltage of
battery was still high then. That means the reason to disconnect the loads by the regulator
was not because of the protection of deep discharge, but the other reasons. As we found
that during that period the regulator surface was very hot, and the LED information light
turned to be red, which means the current state of regulator was under abnormal
condition. When the lamps were turned on automatically after several seconds, at the
same time the LED lights changed back to green color again, which indicated it was
under normal condition then. As we know that besides the deep discharging protection
and over charging protection functions, the regulators still have other mechanisms such
as self-protection under high temperature, current compensation, short circuit protection
and other functions. For our case as the temperature of regulator exceeded the setting
protection temperature, the regulator cut off the discharging process for several seconds
and then was recovered immediately when the temperature cooled down. Sometimes,
however, even if the temperature of regulator was low, it happened as well. It means that
the system was under instable condition. When checking the fuse of controller, we can
see that the fuse had broken and connected with thin copper wire directly. As the
resistance of copper wire is higher than fuse material, the current flowing through these
wires generated much more heat and increased the temperature of regulator consequently.
Using copper wire to replace the fuse is very dangerous as the fuse actually doesn’t have
protection function any more. The regulator could be easily damaged, especially under
high current. Besides, as the wire aged and was oxidized, the instability of wire
connection was happening. This could be the reason of automatic alternation between
turning off and turning on the loads. So here we replaced the broken fuse with a new 10
fuse and tested again.
18
The new measurement data of discharging are shown in appendix A.1. Figure 3.2 and 3.3
are the terminal voltage of battery versus discharging time graph and terminal voltage of
battery versus discharging current graph. The loads used for this test was ( 3*37 Wp +1*7
Wp ) lamps.
battery terminal voltage versus time
10.4
10.6
10.8
11
11.2
11.4
11.6
11.8
12
12.2
12.4
12.6
12.8
13
0 0.05 0.484 0.884 2.217 2.717 3.767 4.717 5.717 6.717 7.55 8.05 8.21
time(h)
Vo
ltag
e (
V)
Figure 3.2: Battery terminal voltage versus discharging time
From the figure 3.2 we can see that the voltage of battery drops gradually until reached
the setting lowest voltage value.
19
discharging current versus battery terminal voltage
7.8
7.9
8
8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8
8.9
9
9.1
12.72 12.36 12.13 11.97 11.74 11.46 11.3
Voltage (V)
dis
ch
arg
ing
cu
rren
t (A
)
Figure 3.3: Discharging current versus battery terminal voltage
The figure 3.3 is the discharging current versus battery terminal voltage characteristics
curve. The discharging current decreased slightly while the voltages of battery drop.
When regulator turned off the lamps automatically, the terminal voltage of battery was
11.3 V while the terminal voltage of regulator was 11.24 V, which had a 0.06 voltage
drop on the wire connections.
As the energy (Ah) drawn from the battery can be determined by multiplying the current
drawn from the battery and the number of hours this current flows, based on the
measured data we got the energy withdrawn from the battery is 70.3 Ah in this test.
3.4.2 Comparison with charged by a conventional battery charger
This time the battery was charged by a conventional battery charger without the regulator
control.
The battery charger used is Cargador de battery, 230V; 50/60 Hz;12/24 V; 10/20 A,
which means it can convert 50/60 Hz, 230 V grid energy to charge 12 V or 24 V battery
with a charging current of 10 A or 20 A. For this test we set the charging current was 10
A and charged it almost 15 hours, which can ensure that the battery had been fully
charged. The discharging data for this test are shown in appendix A.2.
Comparing the total withdrawn energy in case of charged by solar irradiance and by
battery charger (table 3.2), we can see that the withdrawn energy charged by the battery
charger is higher than charged by solar irradiance. It is the same situation for terminal
voltage of battery before starting discharged measurement.
20
Table 3.2 Two sets data of withdrawn energy
Terminal voltage of
battery before starting
discharged
Terminal voltage of
battery when deep
discharge protection of
controller working
Withdrawn
energy
Charging by PV system 13.21 V 11.3 V 70.3 Ah
Charging by battery
charger
13.43 V 11.27 V 78.7 Ah
This can be explained by the function of regulator. Once the battery had been charged to
a reasonable amount (>90% SOC), the full charging current was not applicable any more
and the regulator is resorted to reduce the charging current to prevent from over-charging.
Therefore it is not easy to reach a fully charged state by PV system charging mechanism
due to the working of regulator. It is the same for the result of terminal voltage of battery
when finishing charging. As there is no such protection while charging with battery
charger, the terminal voltage reaches is relatively higher than charged by PV system,
which consequently obtained a higher energy withdrawn. From this we can see that more
energy can be withdrawn without the regulator mechanism. The regulator is
indispensable, however. If the battery undergoes over charged and deep discharged for
several times, it would greatly decrease the performance of battery and accelerate the
aging of battery. Therefore regulator is considered to be a very important component to
protect the PV panel systems.
3.5 Re-test of the old battery
The reason for us to change the old battery with the new one because we thought it was
aging and can not be suitable for the experiments any more. However, based on the
previous experiments done we can see that the low of energy available from the old
battery also may due to the high voltage drop on the wires connection between battery
and regulator or the instability of regulator. In order to make sure it was indeed aging, the
old battery was tested again with the new mechanism and the amount of energy obtained
from battery was around 40 Ah. Although compared with the data measured before (only
around 10 Ah) the energy increases a lot, it is still far away from the rated capacity value.
So for the old battery it is really aging and should be replaced by the new one.
21
4 Regulator tests
4.1 Principle of regulator
The controller, also known as a regulator, is used in PV power supplies with battery bank.
The charge controller monitors the charge status of the battery, controls the charging
process and the connection/disconnection of the loads. Besides, the controller can provide
other functions:
-Temperature compensation (as the gassing voltage of a battery decreases with increasing
temperature, the settings of the overcharge protection circuit have to be adjusted
according);
- External voltage sensing (in case of a rather large value of voltage drop between
controller and battery);
-Current compensation (to compensate the dependence of the battery voltage on the
discharge current);
-Short circuit protection (this can either be an electronic fuse or a conventional fuse
suitable for DC-current. If the output current becomes higher than as prescribed value
than the load is switched off automatically).
All these functions allow the battery use to be optimized and its service life to be
significantly extended. The system connections of the regulator used in the project (a 12
A charge controller of Steca make) are shown in figure 4.1.
Figure 4.1: Overview of PV system connections
22
The LED 1 is used to indicate the operating status and fault message. It flashes green
during normal operation. A red color indicates that there is a fault. The reason of fault
could be module current too high, controller overheated, battery voltage too high, battery
voltage too low, no battery connected or fuse faulty, and so on. The color of the right
LED indicates the charge status of the battery. The color changes from red (approx. 0%
charge status, 10.8 V) to yellow (approx. 50%, 12.0V), to green (approx. 100%, 13.2 V).
Besides, the flash of right LED is used to indicate deep discharging warning. To prevent
from deep discharging, the device is disconnected with loads automatically when the
charge status reaches 30 %( 11.2 V). The load is automatically reconnected when the
SOC reaches 50% (12 V). When the battery had been charged to a reasonable amount
(>90% SOC), the regulator will be resorted to restrict the charging current. When the
battery is fully charged and the PV module is still producing energy, the charge controller
will disconnect the battery automatically. This can be done by opening the circuit
between the battery and the module. If during discharge process the battery voltage
reaches a specified voltage value as low energy left, the load will be switched off
automatically by the deep discharge protection. This is done either by a relay or a solid
state switching device.
Usually, the State of Charge of the battery is being determined by means of measurement
of the battery voltage and the battery current and temperature were measured as well as
correction factors. For the regulator in our project the charge status of battery will control
the charging process by means of Pulse Width Modulation (PWM) to ensure gentle
charging of the battery.
In case of a controller with Pulse Width Modulation (PWM) (as is the case with the Steca
regulator) the charge current is modulated by means of a PWM technique. The charge
current is composed of a series of pulses of which the pulse duration can be varied. The
typical fixed repetition frequency (1/TR) is between 0.5 and 50 Hz. The pulse duration
TD depends on the battery voltage or charge status of the battery. As shown in figure 4.2
when the charge status is low the pulse duration TD is equal to the repetition time TR.
When the battery voltage or the State of Charge becomes high enough the pulse duration
TD will reduce (in other words the duty cycle TD/ TR of the pulses will become smaller
than 1). This way a quasi-linear control is used to adapt the duty cycle such that the float
of battery voltage is kept in a certain narrow range.
23
Figure 4.2: Current versus time for a PWM-controller. TD is pulse duration time, TR is
repetition time
4.2 Observation of regulator current waveform by oscilloscope
Even though a quasi-linear control is performed under high charging status, it is difficult
to notice the variation of charging current by using a low sensitive analog current meter.
It is only possible to observe that the indicator needle shakes under high irradiance.
In order to observe the performance of regulator, an oscilloscope is required. An
oscilloscope is a general-purpose instrument for examining electrical waveforms. It can
be used for various sets of measurements depending on how it is has been set up.
When noticing the shake of needle in charging current meter, we considered that the
current state of charge is higher than 90% and the regulator started to control the charging
current. Between the connection of battery and controller, a wire cable with a resistance
of 17 mΩ had been added in series. When the charging current is controlled by the
regulator, the voltage drop of this wire will change consequently. In this way, we can
obtain the status of charging current by observing the status of voltage drop on this wire
cable and get the working performance of the regulator.
24
Figure 4.3: Current versus time for a PWM-controller when irradiance =613 W/m
2
When irradiance was 613 W/m2, we can read the charging current value from current
meter of 3.3 A. However this is not the actual charging current due to the interference
from controller. From the oscilloscope we can see that pulse duration TD is 98 ms and
the repetition time TR is 106 ms. From the waveform indication the magnitude of voltage
drop was 26 mV and therefore the magnitude of charging current was equal to voltage
drop/wire resistance=26mV/17 mΩ =1.53 A (as shown in figure 4.3). Based on the
waveform we also can know that the repetition frequency is equal to 1/repetition time=
1/0.106s = 9.48 Hz.
Using the same way we observed the working waveform under different irradiance and
obtained different outcome as shown in table 4.1.
Table 4.1 Working data of oscilloscope
From the data in table 4.1 we can see that the repetition time is fixed, which is 106ms and
consequently with a fixed repetition frequency of 9.4 Hz. While the irradiance increases,
the proportion of pulse duration TD increases.
As the regulator starts to control the charging current when SOC >90%, we tried to
observe how the performance of regulator changes when SOC changes. Six days after the
first time’s observing of the working waveform of regulator, we checked the waveform
again and compare these two sets data. When irradiance was 295 W/m2, the pulse
duration time TD was 64 ms and the repetition time TR was 108 ms, the ratio between
TD and TR became 0.59. From this we can conclude that with a higher SOC, the
repetition keeps the same around 106 ms. However, the ratio of TD and TR decreased
compared with previous measured data.
Irradiance
value
(W/m2)
Pulse
duration
TD (ms)
Repetition
time TR
(ms)
Repetition
frequency
(Hz)
Ratio between
TD and TR
333 94 106 9.43 0.887
613.3 98 105.5 9.48 0.93
873.3 102 106 9.43 0.96
966.7 103 106 9.43 0.96
25
As mentioned above, when irradiance was around 600W/m2
the magnitude of voltage
dropped on the shunt resistance was 26 mV and the magnitude of charging current can be
obtained as 1.53 A.
Consequently, the mean voltage drop of wire resistance is:
mVmV
VT
TDV
T
TDdtVdtV
Tdttv
TV
T
TD
TDT
15.2426*106
98
)1(*)(1
)(1
minmaxmin0
max0
==
−+=+== ∫∫∫
As the shunt resistance of wire cable is 17 mΩ, the mean charging current should be:
AmmVRVI 416.117/15.24/ =Ω==
Based on the principle we know that the working of regulator only changes the pulse
duration time, in other words, the ratio between TD and TR, which consequently changes
the mean charging current. For the magnitude of charging current, however, it mainly
depends on the irradiance and will not change due to the change of State of Charge.
Usually, the magnitude of charging current can be up to 3 A under 600 W/ m2 in our
system. Nevertheless, as we shown above, the magnitude value we obtained was only 1.5
A, which was quite low compared with the expected data. This means the oscilloscope
waveform can not right indicate the actual voltage value and consequently the current
value can not be obtained correctly. This may due to the ambient noise or the capacity of
the wire, which might cause the voltage measured to be a mixed signal. Even though the
oscilloscope used in this project can correctly show a pure AC or a pure DC signal, it can
not indicate the signal which combining DC component with low frequency AC
component successfully.
After observing the performance of regulator, another discharging test was carried out
and a total energy of 74.7 Ah was withdrawn from the battery. This value was higher than
the withdrawn energy of 70.3 Ah, which was measured following the first time’s
observation of regulator’s working performance. This energy data also proved the state of
charging this time is higher than the state of charging last time and therefore the energy
withdrawn increased.
26
5 Relationship between open circuit voltage and cell temperature
The performance of a PV module has a direct connection with cell temperature, which is
dictated by several ambient conditions such as ambient temperature, irradiance, wind
speed, wind direction and humidity. The purpose of this chapter is to determine whether
the open circuit voltage Voc can be used to estimate the cell temperature, without taking
into account ambient conditions like wind speed and ambient temperature. The work we
did in this chapter include following: (1) extrapolate STCOCV , under different ambient
conditions; (2) calculate the cell temperature based on actual open circuit voltage value
and extrapolated open circuit voltage value; (3) analyze the relationship between them.
5.1 Extrapolation of Voc to Standard Test Condition (STC)
Under different condition the measured characteristics could be different. Therefore, it is
difficult to compare the performance among different panels directly based on the
measured data obtained. It is also very hard to judge the working capability of a panel as
the measured data might be diverse under different actual on-site conditions. Actually,
they are usually extrapolated to Standard Test Conditions (STC) before compared.
Standard test condition is the condition under which a module is typically tested in a
laboratory: (1) irradiance intensity of 1000 W/m2; (2) AM 1.5 standard reference
spectrum; (3) cell temperature is 25 oC. If the panel is under good condition, the
extrapolated data should be similar to the factory given data. It is usually used to detect
the possible difference between different modules or test the possible performance
degradation of modules and arrays. [7]
In the international standard IEC 1829 [8], extrapolating the measured data of crystalline
silicon photovoltaic array characteristics to standard test condition (STC) or other
selected temperatures and irradiance values are introduced. Such a extrapolating
evaluation can provide data on power rating; verify of installed array power performance
relative to design specifications; detection of possible differences between on-site module
characteristics and laboratory or factory measurements; detection of possible
performance degradation of modules and arrays with respect to on-site initial data.
Based on this standard document, the standard corresponding extrapolated Voc,STC can be
obtained by calculated together with reading of ambient temperature TA and of irradiance
G, the equation as shown below:
)]25(**)/1000ln(*[*, ASOCSTCOC TGBGANVV −+−+= β …….………(1)
Here Voc is the open circuit voltage measured under on-site condition;
STCOCV , is the standard corresponding extrapolated value;
Ns is the number of cells in series in the array; in this project the Ns is 36.
27
Voc value under ambient temperature usually depends on Voc,STC, irradiance G and cell
temperature Tcell. That is
OCV = f(Voc,STC, G, Tcell).
As )1ln(s
ph
ocI
I
q
kTV += , a coefficient value can be used to represent the relationship
between OCV and irradiance.
In equation 1, )/1000ln(* GA refers to the voltage value influenced by irradiance. Here
A is the product of the thermal voltage and the non-ideality factor. The value usually is
38 mV/cell.
As Tcell value is usually determined by Tamb and irradiance.
),( GTfTcell A=
The influenced factor caused by ambient temperature can be represented as in equation 1:
AT−25(*β ).
Here 25 is the standard cell temperature. For example if the ambient temperature is lower
than this standard cell data, the measured Voc could be higher than STCOCV , value. β is
the temperature coefficient of the open current voltage, usually - 2.2 mV/ o
C /cell for
crystalline cells.
For the irradiance part which influences the cell temperature, it can be described as in
equation 1: - GB * .
When solar irradiance increases, under illumination, the cell temperature increases too.
Therefore at high irradiance Voc will drop and a positive factor is needed to increase Voc
to get STCOCV , . Here B = dGdTJ /*β . Where dGdTJ / is usually about 0.03 oC /W.m
-2,
which means the increased cell temperature value corresponding to irradiance. The
production of β and dGdTJ / means the voltage cell temperature which refers to the
heating of the cell respecting to irradiance.
5.2 Calculation of cell temperature
As there is a good heat transfer coefficient for the PV panels, solar cell temperature is
usually considered to be the same as its junction temperature TJRO.
According to IEC 1829[8] we know that the junction temperature of PV panel can be
calculated as:
CVkVTTo
STCOCOCJROcell 25/)*('
,
'+−== β (5-1)
Here β is the voltage temperature coefficient of the referenced PV device (usually -2.2
mV/ oC);
k is a coefficient taking into account the irradiant deviation between measurement
conditions and 1000 W/m2:
28
k=1.000 for 1000 W/m2 irradiance;
k=0.996 for 900 W/m2 irradiance;
k=0.989 for 800 W/m2 irradiance;
k=0.983 for 700 W/m2 irradiance.
As '
OCV used in the equation (5-1) means the open circuit voltage of one cell and '
,STCOCV
means the extrapolated value of one cell, the equation needs to be altered as shown below:
CVkVTo
STCOCOCcell 25/)36/)*(( , +−= β (5-2)
Here OCV and STCOCV , are measured open circuit voltage and extrapolated data for total 36
cells in a panel. Therefore they need to be divided by 36 to obtain the voltage value for
one cell and then calculate the cell temperature.
5.3 Analysis of outcome
Based on this calculation, several sets of the measured data, extrapolated data and cell
temperature are shown in table 5.1.
Table 5.1 Measured Voc versus extrapolated STCOCV , versus cell temperature
Ambient
temperature (oC)
Voc (V) Irradiance
(W/m2)
STCOCV , (V) Cell
temperature
(oC)
31-05-2007
19 17.57 1133.33 19.62 50.84
19 17.33 1073.33 19.31 49.98
20 17.28 1033.33 19.29 50.43
20 17.51 833.33 19.34 48.15
28-06-2007
16 18.98 813.33 20.48 41.37
16 18.95 833.33 20.47 41.91
16 19.05 833.33 20.57 41.90
17 18.64 1066.67 20.45 48.57
From table 5.1 we can see that the extrapolated value STCOCV , obtained are around 19.4 V
with the measured data on 31st, May, 2007, under different ambient temperature and
irradiance. However, instead of keeping around 19.4V, the extrapolated value STCOCV ,
with measured data on 28th
, June, 2007 are around 20.5 V. It doesn’t conform to what we
expected. The expected extrapolated value STCOCV , should be more or less the same as all
of them should be close to the laboratory or factory data under STC tests, regardless of
ambient conditions.
This could be explained that although ambient temperature and irradiance are two major
factors that affect the deviation between actual Voc and STCOCV , , many other factors such
as wind speed, wind direction, humidity, clouds, also would more or less affect the
29
preciseness of deviation. However, the calculation in IEC 1829 doesn’t take these factors
into account. When checking the wind speed on 31st, May, it was 22 km/h while was 32
km/h on 28th
, June [10]. With a higher wind speed, the generated heat can be blown more
quickly; therefore the cell temperature reduced and open circuit value increased. Besides,
the tolerances of these measured devices also need to be taken into account.
For the cell temperature we can see that even Voc is higher, it does not mean that the cell
temperature is lower or higher as the irradiance also will cause the variation of cell
temperature, such as measured data on 31st, May. For those data which have the same
irradiance, like 833.33 W/m2 in the table, we can see that a higher Voc value can be used
to reflect a lower cell temperature existing. Based on these measured data, therefore, we
can conclude that the open circuit voltage can estimate the cell temperature only when the
solar irradiance does not change too fast and the other ambient conditions like wind speed
does not vary too much to ensure the stability of extrapolation data of STCOCV , .
30
6 Energy output and ambient conditions
6.1 Power output of PV system
The performance of a PV module has a direct connection with operating temperature. For
example, the power output of a mono or poly-crystalline silicon module decreases at
about 0.5%/oC. The operating temperature of a module could be dictated by several
factors, including module’s design characteristics, module installation type and ambient
conditions such as ambient temperature, irradiance, wind speed, wind direction and
humidity.
The characteristics of a Photovoltaic depend on fluctuations of the cell temperature and
irradiation. In our grid-connected PV system a maximum Power Point Tracking (MPPT)
is installed inside the inverters to extract the maximum power from a PV array, convert
this to alternating current and transmit the energy to the power grid.
A MPPT mechanism is a high efficiency inverter that uses maximum power point
tracking technology to harvest the maximum power from the PV array, which will change
according to the variations in parameters such as solar radiation and cell temperature. The
maximum power increases with increasing radiation at constant cell temperature the
maximum power decreases with increasing cell temperature at constant irradiance.
The working principle of it is based on the characteristics of photovoltaic cells that have
a single operating point where the values of the current and voltage of the cells result in a
maximum power output. The objective of maximum power point tracking is to move the
PV array operating voltage close to the maximum power point under changing
atmospheric conditions in order to draw the maximum power from the array. Maximum
power point trackers utilize some type of control circuit or logic algorithm to search for
this point. If a trial shows that what the best power is, it will move control point to use
new PV panels’ voltage and current output [9].
Because of this, we need to find out the relationship between cell temperature, irradiance
and energy output of PV systems, which can be considered as a reflection of MPPT
working performance.
6.2 Analysis of the relationship between energy output and ambient conditions
In order to find out the relationship between these data, firstly we need to obtain the
corresponding value. As mentioned in chapter two, two energy meters are available to
record the amount of kWh that had been delivered to the grid since installation and the
current delivering data. The power meters used in this project are 9024 power meter of
PeakTech make. This energy meter allows measuring the energy consumption of
electrical appliance, and by entering the electricity rate, to calculate the total cost of
31
appliances consumption. It also detects the overload condition and usage information. So
we can obtain energy generated currently from the power meters.
By using the same approach as mentioned in previous chapter, the cell temperature is
determined by measuring Voc and comparing the Voc with STCOCV , using the equation (5-
2) from section 5.2. In table 6.1 eight sets of data which were measured with an interval
of 15 minutes are shown.
Table 6.1 Data of ambient parameters and energy output
Based on the table data we can see that when the irradiance is the same, like the data of
set 4 and set 7, the module with a lower cell temperature (47.15 oC) generated more
energy, which fits in with what we mentioned previously that the maximum power
increases with decreasing cell temperature at constant radiation. While comparing the
data of set 5 and set 6, we can find that, with a higher irradiance and lower cell
temperature, the PV module generated more energy. Therefore, a good ventilation design
of the system which can help to lower the cell temperature is very important to insure the
energy output.
Moreover, as the peak power of the grid-connected system used in our project (under
Standard Test Conditions) STCP is 108 Wp, the actual peak power of a grid-connected PV
system (under on-site condition) actP can be described by:
PRPP STCact ×=
Here PR is called performance ratio, which takes into account all the losses that occur at
systems level, apart from the losses that take place in the solar cell itself at STC. In grid-
connected PV systems important system losses are mainly including: inverter losses;
losses because the cell temperature deviates from 25 oC and losses because the irradiance
on the cell is in general lower than 1000 W/m2. For the system the invert loss is normally
taken as 9%; for a crystalline module typically the temperature loss coefficient is around
-0.45 %/oC.
When testing the quality of energy output by set 1 data, we find that the on-site peak
power actP can be estimated as:
Sets
Voc (V) Irradiance (W/m
2)
Cell temperature (oC)
Left side power meter display (W)
Right side power meter display(W)
Actual Peak power (Wp)
1 19.05 833.33 41.90 76 79 75.7
2 18.98 813.33 41.37 76 80 74.0
3 18.98 866.67 42.83 78 84 78.3
4 18.55 1006.67 47.15 90 93 89.1
5 18.61 1053.33 48.25 95 98 92.7
6 18.54 1013.33 50.71 91 94 88.1
7 18.28 1006.67 50.55 88 91 87.6
8 18.22 966.67 49.65 85 89 84.5
32
actP= STCP PR× = STCP × inverter loss factor× temperature loss factor × (
2/1000 mW
G
)
= 108 W× (1-9%)× (1+ (41.9 oC -25 oC) × (-0.45 %/ oC)) × (2
2
/1000
/33.833
mW
mW
)
= 75.7 Wp .
Comparing between this estimated peak power value and the actual energy delivered to
the grid which we obtained from energy meters, we can see that as the working of MPPT,
the power generated was kept around the on-site peak power point. The same way to test
the other sets data and we get that the MPPT in our system is under good condition and
always keeps the solar systems running near the maximum power point.
As the peak power value can be obtained by using irradiance and cell temperature
parameters and cell temperature can be estimated by open circuit voltage, we can
approximate the energy power that will be delivered to the public power grid. With good
performance of MPPT, therefore, the irradiance and open circuit voltage are considered
to be very good parameters to reflect the energy output.
33
7 Conclusions and recommendations
From the experiments we did for this project, conclusions are given as following:
* As one of the important components in PV system, testing the battery’s performance is
very necessary to check if it is suitable for the research. The total amount of energy
withdrawn from the old battery in our project was only 40 Ah while for the new one was
more than 70 Ah. Therefore we conclude that the old battery was aging and are needed to
be replaced by a new one.
* Based on the measurements of the repetition frequency and ratio between TD and TR
by an oscilloscope we know that the repetition frequency is fixed even when the
irradiance changes. Meanwhile, the ratio between TD and TR increases with an increase
of irradiance. However, with a higher SOC condition, this TD and TR ratio decreases as
they are also determined by the actual battery voltage.
* For the ideal extrapolated value STCOCV , , the calculated data should be similar to each
other. However, the deviation we obtained is a little larger which we conclude as the
effect of the other ambient factors and the tolerances of the measured devices. For the
relationship between cell temperature and open circuit voltage we can get that open
circuit voltage can give an immediate indication for the cell temperature only when the
solar irradiance does not changes too fast and the other ambient conditions like wind
speed does not vary too much to ensure the stability of extrapolation data of STCOCV , .
* Via the measurement of energy output and ambient conditions we can find out that with
a higher irradiance and lower cell temperature, the PV module can generate more energy.
Besides, the open circuit voltage and irradiance can be used to estimate the energy output
in our grid-connected system as the MPPT trackers are performed under good condition.
By performing the experiments during this project some recommendations can be drawn
as following:
Repeated discharging and charging can help to activate the reaction materials and
therefore increase the battery’s capacity, especially for those that have not been used for a
long time.
For the regulator used in the system we need to care the voltage drop on the connection
wires, especially the wires connecting between battery and regulator. Thick and low
resistance cables are recommended to make sure the voltage measured in the regulator
side is as close as possible to the actual battery voltage.
During the experiments process, it is very important to pay attention to the order to
disconnect or connect with these components. Usually remove the PV modules’
connections from the controller first, and then disconnect battery and regulator. Never
connect the PV panel with regulator directly, without the connection of battery. It will
break the regulator easily.
34
References 1, The Intensity of Solar Radiation, retrieved June, 12, 2007, from
http://www.jgsee.kmutt.ac.th/exell/Solar/Intensity.html;
2, R.van Zolingen , text book of ‘Solar cells’, technology university of Eindhoven;
3, S.O.Kasap,(2001). Optoelectronics and Photonics: Principles and Practices. Published
by prentice-Hall, Inc.
4, R.van Zolingen .Shell Solar PV course (version 3), chapter 5;
5, Arthur Okuga(2006). Design, construction and performance evaluation of a solar
energy system, Eindhoven University of Technology
6, Sato, S., Kawamura, A.; A new estimation method of state of charge using terminal
voltage and internal resistance for lead acid battery, IEEE, Volume 2, 2-5 April 2002
Page(s):565 - 570 vol.2
7, Y.Tang, G.TamizhMani, L.Ji, C.Osterwald (June 2005). Outdoor energy rating of
photovoltaic modules: module temperature prediction and spectral mismatch analysis.
20th
European photovoltaic solar energy conference, p2051-2054.
8, IEC 1829, crystalline silicon photovoltaic (PV) array- on-site measurement of I-V
characteristics
9, The basics of maximum power point tracking solar charge controller.
Retrieved June 30, 2007, from
http://www.leonics.co.th/html/en/aboutpower/mppt_basics01.php
10, Weather online, retrieved 2nd
, 08, 2007 from
http://www.weatheronline.co.uk/cgi-
bin/aktframe?TYP=windspitzen&ART=karte&RUBRIK=akt&JJ=xxxx&MM=01&TT=1
8&TIME=1800&KEY=NL&LANG=en&SORT=2&INT=06
35
Appendix
A.1: Discharging data (charged by solar system)
36
A.2:Discharging data (charged by a conventional battery charger)